  • 8/16/2019 P-CIM OPC Communication

    1/37

    P-CIM OPC Communication

    User Guide

  • 8/16/2019 P-CIM OPC Communication

    2/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide I

    Contents

    About P CIM OPC Communications

    P-CIM station............................................................................................................ 1

    Requirements ............................................................................................................... 3

    Settings .........................................................................................................................3

    NetBEUI Protocol Configurations

    Defining NetBEUI settings for Windows 2000.................................................. 3

    Defining NetBEUI settings for XP ....................................................................... 4

    DCOM Configuration Properties

    DCOM Configuration Properties for Connecting to Remote OPC Servers ....... 4

    From Section 2:.................................................................................................. 6

    From Section 3:.................................................................................................. 7

    Adding a user to a group ..........................................................................................7

    OPC Browser 

    Workflow................................................................................................................ 10

    Opening the OPC Browser ................................................................................ 11

    Connecting the OPC Browser to an OPC server .............................................. 11

    Connecting the OPC Browser to a remote OPC server ...................................12

    OPC Browser Interface 

    Menu/Tool bar .................................................................................................. 14

    Disconnecting/ Reconnecting/ Refreshing connections ............................... 16

    Groups ............................................................................................................... 17

    Items .................................................................................................................. 18

    Adding an item to a group ................................................................................ 18

    Adding an item manually ..................................................................................18

    Removing an item from a group ...................................................................... 19

    Removing an advised item used in another P-CIM module ...........................19

  • 8/16/2019 P-CIM OPC Communication

    3/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide II

    Writing a new value to an advised item .......................................................... 19

    Advising multiple items 2 ....................................................................................0

    Options Menu......................................................................................................... 20

    Monitoring, displaying advised items ..............................................................21

    Displaying item syntax ...................................................................................... 22

    Configuring OPC Browser Configuration ..........................................................22

    Using the OPC Browser in a P-CIM Project................................................................ 25

    Creating an object and adding OPC Browser syntax ......................................25

    Creating datablocks.......................................................................................... 25

    Displaying a P-CIM OPC item’s syntax in the OPC Browser ............................26

    OPC Browser Alarm Summary Messages .............................................................26

    P CIM OPC Gateway

    Running the OPC Gateway ...............................................................................27

    OPC Server Properties ......................................................................................28

    The OPC Gateway Editor

    Example – Defining an OPC Item in the OPC Gateway Editor ........................30Viewing OPC Items in a Client Interface .......................................................... 30

    OPC Browser Troubleshooting ................................................................................... 32

    General ................................................................................................................... 32

    NO-SEK Stations .................................................................................................... 33

  • 8/16/2019 P-CIM OPC Communication

    4/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 1

    About P-CIM OPC Communications

    OPC (OLE for Process Control) protocol is a set of interfaces that enable standardized data exchange

    between automation/control applications, field devices and other types of applications.

    P-CIM has two OPC modules:

      • OPC Browser, an OPC client that requests information from an OPC server connected to a

    PLC. The OPC Browser enables bidirectional communications between P-CIM and an OPC

    server.

    • OPC Gateway, an OPC server, that receives data from P-CIM OPC servers. Using OPC

    protocol the data is translated and sent to the OPC client that sends it to external devices and

    programs.

    For more information about OPC technology, visit: www.OPCFoundation.org.

    P-CIM station

     A P-CIM station can act as both an OPC client and OPC server, or can be a client or server only. The

    diagram below illustrates how a P-CIM station is both an OPC server and OPC client.

     

    P-CIM Servers

    BasicSrv DBSR PfwAlarm PfwDrvr TxtSrv

    P-CIM OPC Gateway

    External OPC clients

    O P C P R O T O C O L

    C A L L B A C K P R O T O C O L

    OPC client (OPC Browser)

    O P C P R O T O C O L

    PLC OPC serverPLC

    http://www.webopedia.com/TERM/D/client_server_architecture.htmlhttp://www.webopedia.com/TERM/D/client_server_architecture.htmlhttp://www.opcfoundation.org/http://www.opcfoundation.org/http://www.webopedia.com/TERM/D/client_server_architecture.html

  • 8/16/2019 P-CIM OPC Communication

    5/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 2

    The P-CIM OPC client (Browser) receives data from the server, whereas the P-CIM OPC server

    (Gateway) sends P-CIM data to any OPC client.

     In this bidirectional process, data from the PLC arrives to the OPC server.The data is translated using

    OPC protocol, and sent to the OPC client (Browser). The data is then sent to P-CIM servers and using

    call back protocol..

    The data sent to the OPC Gateway( Gateway) where it is translated using OPC protocol and sent to

    external programs.

  • 8/16/2019 P-CIM OPC Communication

    6/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 3

    Requirements

    Settings

    The following must be defined on the station using OPC communications:

    • NetBEUI protocol

    • DCOM

    • Adding Users to a group

    NetBEUI Protocol Configurations

    NetBEUI (Network Basic Input Output System) protocol is required for configuring a network of 20 to

    200 stations without requiring a router for a different subnet mask.

    NetBEUI, is an API that enhances the DOS BIOS with additional functionalities for LANS.

    Defining NetBEUI settings for Windows 2000

    1. Copy the NetBEUI files from the Windows XP CD. Instructions can be found at: http://support.microsoft.com by searching for NetBEUI and selecting How to install NetBEUI on

    Windows XP.

    2. Select the following: Start/ Settings/ Control Panel/ Network/ Dialup Connections.

    3. Right click Local Area Connection and then click the Properties button.

    4. Scroll the list, select NetBEUI protocol and then click the Install button.

    Operating System• Windows 2000 Professional/Server 

    • Windows XP Professional

    • Windows 2003 Server 

    Protocols Net BEUI, TCP/IP

    To run the OPC Browser P-CIM version 7.50 and up

    To run the OPC Gateway P-CIM version 7.50 and up

    Windows XP , 2000 & 2003 serevr are required for remote OPC server connections.

  • 8/16/2019 P-CIM OPC Communication

    7/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 4

    5. Select the relevant protocol and click OK to confirm.

    Defining NetBEUI settings for XP

    1. Open the Network dialog box, Select the following: Start/ Settings/ Control Panel/ Network.

    2. Open the Protocol tab, and click the Add button to open the Select Network Protocol dialog box.

    3. Select the NetBEUI Protocol option and click OK.

    DCOM Configuration Properties

    DCOM technology can be used to transparently send/receive information between COM components

    (for example, clients and servers) on the same network.

    • DCOM configuration is only required for accessing remote OPC servers.

    • DCOM configuration is not required when both the client and the server reside on the same

    computer DCOM configuration is not required.

    DCOM Configuration Properties for Connecting to Remote OPC Servers

    1. Select Start/ Run to open the Run dialog box.

    2. Type dcomcnfg into the Open field and click OK. The DCOM Configuration Properties dialog

    box is displayed.

    3. Select: Components Services/ Computers/ My Computer/ DCOM Config.

    4. From the Components Services list, right click PfwOPCGateway to open the PfwOPCGateway

    Properties dialog box.

  • 8/16/2019 P-CIM OPC Communication

    8/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 5

    5. Click the Identify tab and select the interactive user and system options.

    6. Click Apply.

    7. Click the Security tab.

    8. Select Customize.

    9. Click the Edit button to open the Launch Permission dialog box.

  • 8/16/2019 P-CIM OPC Communication

    9/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 6

    From Section 1:

    1. Check the Customize option and then click the Edit button. The Registry Value Permissions

    dialog box opens.

    2. Click the Add button to display the Add Users and Groups dialog box.

    3. Select the user/group that will be able to access the OPC server.

    4. From the Permissions for Administrators field, select Allow Access 

    5. Click OK and OK again, to return to the Security tab.

  • 8/16/2019 P-CIM OPC Communication

    10/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 7

    From Section 2:

    1. Check the Customize option from the Access Permissions option and then click the Edit 

    button. The Registry Value Permissions dialog box opens

    2. Select the user/group that will be able to launch the OPC server.

    3. From the Type of Access field, select Allow Access. 4. Click OK to return to the Security tab.

    From Section 3:

    1. Check the Customize option from the Configuration Permissions option and then click the

    Edit button. The Registry Value Permissions dialog box opens.

    2. Select the user/group that has permission to access the OPC server.

    3. From the Type of Access field, select Full Control. 

    4. Click OK to return to the Security tab.

    5. Click OK and OK again to save these definitions and to exit the Properties dialog box.

    Adding a user to a group

    When users are assigned to groups, they receive the group’s authorization privileges.

    1. Select the following: Start/ Settings/ Control Panel/ Administrative Tools/ Computer

    Management/ Local User and Groups.

     

    2. Double click Groups to select the group’s users.

  • 8/16/2019 P-CIM OPC Communication

    11/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 8

    3. Double click a user to open the Users Properties dialog box.

    4. Select a user and then click the Add button to open the Select Users or Groups dialog box.

  • 8/16/2019 P-CIM OPC Communication

    12/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 9

    5. Enter the name of the user and then click the Check Names button to add the user’s details 

    OR 

    Double click the name of the user and click the Add button.The user’s name is added to the list.

    Connecting to a remote OPC gateway in a workgroup configuration

    In order to connect to a remote OPC gateway in a workgroup network configuration, a peer-to-peer

    connection must be established between the client and server computers. The following changes

    should be made to the Local Security Policy (on Windows 2003 Server and Windows XP Service

    Pack 2 only):

    1. Open the Windows Control Panel and access the Administrative Tools group.

    2. Double-click the Local Security Policy icon.

    3. Select on the Security Options folder.

    4. On the right-hand window, double-click the “Network Access: Let Everyone Permissions Apply to

     Anonymous Users” entry.

    5. Select the Enabled option and click OK to apply the new settings.

  • 8/16/2019 P-CIM OPC Communication

    13/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 10

    6. To enable sharing folders between computers in the workgroup, locate the following entry in the

    Local Security Policy window: Network Access: Sharing and Security model for Local

     Accounts.

    7. Double-click the entry to change the current policy.

    8. From the pull-down menu select the following option: Classic - local users authenticate as them-

    selves.

  • 8/16/2019 P-CIM OPC Communication

    14/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 11

    OPC Browser

    The OPC Browser module can be used in a P-CIM project to access process data from an OPC

    server.

    During runtime, the OPC Browser receives data from the PLC after it has been processed by the OPCserver software, and then the OPC Browser sends the information to the P-CIM project.

    OPC technology enables the following actions:

      • Connection/disconnection/reconnection between the OPC Browser to more than one OPC

    server both locally and remotely (as of P-CIM version 7.02).

      • Adding groups and adding items to groups.

      • Reading/ writing item values.

      • Monitoring advised items.

      • Checking advised item’s status.

      • Checking communications.

    The following diagram displays how the OPC Browser can be used in a P-CIM project.

    Workflow

    The following workflow can be used for working with the OPC Browser:

    The protocol used by the PLC must match the protocol used by the OPC server.

    The OPC Browser can be opened without starting up P-CIM. However, P-CIM must be

    running to enable connection to the OPC Gateway server.

     PLC protocol OPC protocol P-CIM callback

    PLC P-CIM OPC Browser P-CIM projectP-CIM OPC Server

  • 8/16/2019 P-CIM OPC Communication

    15/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 12

    Opening the OPC Browser

    From the Tools menu of the P-CIM icons group,click the P-CIM OPC Browser icon

    Connecting the OPC Browser to an OPC server

    1. Open the Connect dialog box: From the OPC Browser interface, click the Connect icon

     or ,

     From the Server menu click the Connect option.

     Connect the OPC Browser to the OPC Server.

    In the OPC Browser, create a group and define group properties.

     Add items to the group.

     Activate the Option menu functions.

  • 8/16/2019 P-CIM OPC Communication

    16/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 13

    2. In the Connect dialog box double click an OPC server ,

    or  select an OPC server  and then click the Connect button.

    3. The OPC Browser is connected to the OPC server and the OPC Browser interface opens.

    Connecting the OPC Browser to a remote OPC server

    1. Open the Connect dialog box: In the OPC Browser interface click the Connect icon

    or  from the Server menu click the Connect option.

    2. Click the Network OPC Servers button and browse for the computer where the remote OPC

    server is installed.

    3. Click OK to make the connection between the servers. The OPC servers available on the remote

    computer are added to the list of OPC servers in the Connect dialog box, and the name of theremote computer is added to the Network Computer field.

     The OPC Server Key

    field is automatically filled afteran OPC server is selectedfrom the list.

  • 8/16/2019 P-CIM OPC Communication

    17/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 14

    4. Select a remote OPC server and then click the Connect button to connect between the selected

    OPC server and the OPC Browser.

    OPC Browser Interface

    When first accessed the OPC Browser has the following sections:

    The INI file name of the remote OPC server has the following format:

    OPC_NetworkComputerName_OPCServerName.ini

     The computer names ofremote OPC servers havebackslashes \\ asprefixes.

    When making remote OPC server connections, check that you have the appropriate authorization.Error! Reference source not found., page 8 for more information. Both local and remote computersmust be defined on the same domain or in the same workgroup.

  • 8/16/2019 P-CIM OPC Communication

    18/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 15

    Menu/Tool bar

    The OPC Browser menu bar is dynamic, after a connection has been made to an OPC server

    additional menus and options are available. An asterisk * next to a menu/option indicates that it is

    available both when the OPC Browser is online or offline.

    Section Description

    Menu bar See Menu bar on page 14.

    Toolbar See Toolbar on page 14.

    Address bar Displays the full name and address of the item currently selected in the OPC

    Browser.

    Server window Displays the OPC server group tree structure. When expanded the tree has

    the following structure:

    Server name, Group name, Sub-group name

    Group window Displays the properties of a selected OPC Browser group:

      • Group name, which is the name identifying the group.

      • Update rate, which specifies the frequency (in milliseconds) that the

    OPC server sends updated data.  • Percent deadband, specifiying the percent change of the scale

    required before notifying the OPC Browser of the data changes. The

    percent deadband is defined for the item in the OPC server

    Deadband default = 0.

    See Groups on page 17.

    Items window Displays the items of the selected group or sub-group in the Server window

    from which items can be added into the list of advised items.

    Advised items window Displays selected items from the Items list. When monitoring is defined,

    these items are scanned according to predefined conditions.

    Table 1: OPC Browser Menu/Tool b ar

    Menu Icon Option Description

    File Save Saves the OPC Browser groups and items.

    *Exit  Exits the OPC Browser module.

  • 8/16/2019 P-CIM OPC Communication

    19/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 16

    Server *Connect  Opens the OPC servers Connect dialog box where the

    connection between the OPC Browser and a selected OPC

    server are made.

    Disconnect  Ends communications between the OPC Browser and theselected OPC server.

    Refresh When clicked, the OPC Browser reads the items from the tree of

    the selected OPC server again and updates the OPC Browser

    window.

    Reconnect Reconnects the OPC Browser  to the OPC server after

    communication failure. This option is only available when

    automatic reconnection is disabled in the Keep Alive dialog

    box See page 23.

    Disconnect allservers

    Disconnects all open servers and displays the OPC Browser  window with the basic menu bar options and toolbar  Connect

    icon.

    Show Items When connected to an OPC server, select this option to expend

    the items tree.

    Server

    Properties

    Shows the OPC Server  properties. Server specific settings are

    modified from this location.

    *Item  Add group Opens the Group Parameters dialog box. OPC Browser groupsand their properties are displayed in the Group Window of the

    OPC Browser interface. See Groups on page 17.

    Remove group Removes a selected group from the Group Window.

     Add item Opens the Add Item dialog box where items that require

    constant monitioring are defined.

    Remove item Removes a selected item from the Advised Items list.

    Write item Opens the Writing dialog box whereyou can modify the selected

    advised item’s value.

     Add multiple

    items

    Opens the Multiple Advise dialog box where you can define

    batches of items that require constant monitoring.

     An advised item is an item that is constantly monitored by the

    P-CIM client modules. For example, Operator Worksation.

    View *Status bar Toggles the Status bar where the total number of advised items

    and the total number of items in a selected group are displayed.

     Address bar  Toggles the address bar. The information in the address bar can

    be copied and added to objects during project development.

    Table 1: OPC Browser Menu/Tool b (Continued)ar

    http://-/?-http://-/?-

  • 8/16/2019 P-CIM OPC Communication

    20/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 17

    Disconnecting/ Reconnecting/ Refreshing connections

      • Disconnecting:

      • Disconnecting a single OPC server :select the OPC server from the Server window and

    from the toolbar click the Disconnect icon 

    or  from the Server menu select the Disconnect option.

      • Disconnect all OPC servers connected to the OPC Browser : select the Disconnect

    All option from the Server menu.

      • Reconnecting:To reconnect to the OPC server that was last disconnected, click the

    Reconnect icon from the toolbar 

     or  from the Server menu select the Reconnect option.

      • Refreshing: The OPC Browser with items and their values that were added/ removed

    to/ from the selected OPC server, click the Refresh icon

    or  from the Server menu select the Refresh option.

    Options Monitoring When activated, displays updated values of advised items.

    P-CIM itemsyntax 

    When activated, displays the Server| Topic| defined for the itemin the OPC server Item syntax of a selected item (or advised

    item) in the interface’s Address bar.

    *OPC Browser

    configuration

    Opens the Browser Configuration dialog box where connection

    settings can be defined.

    When the Monitoring option is selected, data is transferred between the OPC Browser and the

    OPC server. Advised items and their details are displayed in the Advised Items window. This

     process requires extensive CPU memory resources. We recommend using this option only when

    absolutely required.From Version P-CIM 7.50 the OPC browser is capable of supporting EGU conversion functions:

    bcd, byte, nib and alarm. To use these functions add the character d  before each function. For

    example: dbcd, dbyte.

     An OPC server that has items that are advised (by the Operator Workstation, DBSR or other

    modules), cannot be disconnected until their items become unadvised 

    If the OPC server has advised items and you wish to disconnect; shutdown P-CIM and then

    restart the application.

     All connected OPC servers are automatically disconnected when P-CIM is shutdown.

    Table 1: OPC Browser Menu/Tool b (Continued)ar

  • 8/16/2019 P-CIM OPC Communication

    21/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 18

    Groups

    Groups with any number of items can be created where each group has global parameters specific to

    the group. This option increases efficiency in a P-CIM project.

     An advised item is processed in the OPC Browser, after it has been added, and results are displayed

    in the Advised Items window. A list of all OPC Browser groups is displayed in the Groups window.

      • Adding a new group

    Groups are created/ modified in the Group dialog box. To open this dialog box either right click in the

    Servers window or  from the Items menu select the Add Group option.

    The Group Properties dialog box has the following fields:

    Field Description

    Name Group name.

    Update rate Indicating the frequency that the group of advised items is scanned. For example, if

    1000 msec is defined the group is scanned every 1000 msec.

    Deadband Specifying the required percentage of change in the scale defined for the item in the

    OPC server before notifying the OPC Browser of the data changes.

    Deadband default = 0.

    Time Bias Indicates the time zone where the data was collected. Time Bias indicates the time

    difference between the server and the client. By default= -120

  • 8/16/2019 P-CIM OPC Communication

    22/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 19

      • Removing groups from the Groups window

    Select the group and then either right click and select Remove Group or, from the Items menu select

    the Remove Group option.

      • Modifying group properties

    Group properties are defined in the Group Properties dialog box.

    To open this dialog box either, select a group and then right click and select Group Properties or,

    from the Items menu select Group Properties.

    Items

    Items can be advised and added to groups. All items that are defined in the application are displayed in

    the OPC Items window. When an item is added to a group it becomes an advised item and is displayed

    in the Advised Items window.

    Adding an item to a group

    On first connection to the OPc server, the items tree is not visible.

    2. To display the items list, right-click the OPC Server name and choose Show Items from the

    menu.

    3. In the Server window tree, select a branch and then select a group.

    4. Select an item from the OPC Items window and then right click on the item and select the Add

    Item option or  

    From the Items menu double click on the item, select the Add Item option.

    Adding an item manuallyThis option is used to add an item that does not appear in the OPC Items window, but is supported by

    the OPC server.

    1. In the Server window tree, select a branch and then select a group.

    2. From the OPC Items List window, right click and select Add Item.The Add Item dialog box is

    displayed.

    The OPC Browser has a default group named Root that cannot be deleted.

    Since the OPC Browser is used for test purposes, not all OPC items need to be added to

    the Advised window.

  • 8/16/2019 P-CIM OPC Communication

    23/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 20

    3. Complete the Item field:

      • If you know the item Name and Path select the Name button and then type in this

    information.

      • If you do not know the full path, type in the name of the item and then check the Full Path

    option to complete the location.

    4. Click the Add Item button to add the selected item to the Advised Items window.

    5. The Copy button can be used to copy the item and its path into another location.

    Removing an item from a group

    1. From the Group window, select a group.

    2. From the Advised Items window select the advised item.

    • On your keyboard, press the Delete button.

      • Right click and select the Remove Item option.

      • From the Items menu, select the Remove option.

    Removing an advised item used in another P-CIM module

    If you wish to remove an advised item used in Operator Workstation or another P-CIM module.

    1. In the other module,change the status of the selected item to not advised. (for example, by

    closing the display).

    2. Remove the advised item from the OPC Browser.

    Writing a new value to an advised item

    This option is used to manually update values during runtime.

    1. From the Groups window select a group and from the Server window select an advised item.

    2. Open the Writing dialog box, right click and select the Write Value option

    or  in the Items menu select the Write option.

    Data blocks must first be deleted from the Database Editor before they are removed from the

    OPC Browser 

  • 8/16/2019 P-CIM OPC Communication

    24/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 21

    3. Modify the value in the New Value field.

    4. Click OK to confirm the new definitions and to exit this dialog box.

    Advising multiple items

    This option enables advising items in bulk quantity of up to 3000 items per batch.

    Multiple items can be added to the monitored list in one of the following ways:

      • To add items from a specific location in a set quantity  

    1. From the Items window select the relevant items.

    2. On your keyboard, press the Shift button.

    3. Double click to add the items to the monitored list

    or  right click and select the Add Items option.

    4. The items are added to the monitored list.

      • To add a Sequential List 

    • From the Groups window select a group and then in the OPC Items window select the first itemfrom which to create multiple advised items.

    5. From the Items menu select the Multiple Advised option. The Add Multiple Items dialog

    box opens, and the From field displays the name of the selected item.

    6. Type in the number of items into the Amount field.

    If,for example, 70 is entered, the selected item and 70 items after it are added to the

     Advised Items window.

    7. Click OK to save this definition and to exit this dialog box.

    Options Menu

    This menu has the following options:

      • Monitoring

      • P-CIM item syntax

      • OPC Browser Configuration

    Values can also be updated manually in the Operator Workstation module.

  • 8/16/2019 P-CIM OPC Communication

    25/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 22

    Monitoring, displaying advised items

    1. From the Options menu select the Monitoring option

    or  in the toolbar click the Monitoring button.

    The Advised Items list is displayed with the following columns:

    Table 2: OPC Browser Options Menu

    Column Description

    Item name Displays the full name and location of the item.

    Value Displays the value of the item in the OPC server.

    Data type Displays the item’s data type as defined in the OPC server. For example, word,

    double word.

    Time Stamp Displays the time of the last update of the item by the OPC Browser.

    Column Description

    Quality Each OPC item’s value has an indication of its quality. This is known as the OPC

    Item Quality. The quality of an item is based on whether or not the physical device

    has provided a value for the Item ID.

     Quality status can be:

      • Good, indicating that a value has been sent by the physical device for the

    OPC item.

      • Bad, indicating that a value has not yet been received for the OPC item and

    the value is unknown.

    Access Defines if this item is read only or read and write.

  • 8/16/2019 P-CIM OPC Communication

    26/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 23

    Displaying item syntax

    In the Options menu select the P-CIM Item Syntax option. The full Server|Topic!Item syntax of the

    item is displayed in the Address bar.

    Configuring OPC Browser Configuration

    This option is used to define the OPC Browser settings.

    From the Options menu:

    1. Select the OPC Browser Configuration option. The General tab is displayed.

    The OPC Browser Configuration dialog box has the following fields:

    When the Monitoring option is selected, data is transferred between the OPC Browser and the

    OPC server. Advised items and their details are displayed in the Advised Items window. This

     process uses extensive CPU memory resources. Afcom recommends using this option only

    when necessary.

  • 8/16/2019 P-CIM OPC Communication

    27/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 24

    2. Click the Keep Alive tab.

    This dialog box is used to define the continual communication of OPC servers connected to the OPC

    Browser. It has the following fields:

    Table 3: OPC Browser Configuration

    Field Description

    Connectionsettings Timeout  Defines the maximum/minimum amount of time waited toconnect to the OPC server and to receive a list of items from

    it.

    Data change rate Defines the interval for scanning updated OPC server

    advised items.

    Logging

    options

    Log … Alarm

    Handler 

    When checked, indicates that advised items from the

    callback server are written to and displayed in the Alarm

    Handler.

    Log…(0-2) Indicates whether (or not) the advised item is logged:

    0 = not logged

    1 = logged

    2 = internal use only

    Field Description

    Communication

    … (10-36000)

    Indicates the time interval between each communication test.

    Communication

    test attempts

    Indicates the number of communication test attempts.

  • 8/16/2019 P-CIM OPC Communication

    28/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 25

    Time … attempts Indicates the number of seconds between each reconnect communication

    attempt.

    When 0 is defined this indicates that reconnection to an OPC server can be made

    manually by clicking the Reconnect button.

  • 8/16/2019 P-CIM OPC Communication

    29/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 26

    Using the OPC Browser in a P-CIM Project

    When developing a project, an object whose data is processed through the OPC Browser and OPC

    servers must have syntax assigned. As in all P-CIM modules, the syntax used in the OPC Browser is

    built from Server|Topic!Item elements, where:

      • Server = OPCSrv

      • Topic = OPC server name

      • Item = Itemname

    Creating an object and adding OPC Browser syntax

    The Animation Editor is used to develop the graphical display of a P-CIM project. During runtime, the

    display is shown in the Operator Workstation on the operator’s station, and acts as an interface

    between the operator and the factory floor.

    1. From the P-CIM Group, click the Animation Editor icon to access the Animation Editor.

    2. Create or select an object in a display

    3. Double click the object

    or  right click the object and select the Properties option.

    4. The Properties dialog box is displayed.

    The example below displays the Server|Topic!Item of an object that has input properties.

    Creating datablocks

    Data blocks are generally defined for generating alarms and history collection.

    From the P-CIM Group, double click the Database Editor  icon to access the Database Editor. The

    example below displays the AV1 data block.

    The following syntax can be used to advise items per group: groupname(itemname)

    For example, Group 1 will have the following syntax: Group1(DBSR.P-CIM.$WDAY)

  • 8/16/2019 P-CIM OPC Communication

    30/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 27

    Displaying a P-CIM OPC item’s syntax in the OPC Browser

    From the View menu, select the Address bar  option to display the address bar.

    From the Items window click an item.

    For example, when A1 is selected in the Items window, the following syntax is displayed in the Address

    bar.

    Where:

    • Server = OPCSrv

      • Topic = PFWOPCGateway.Server 

      • Item = DBSR.PCIM.A1

    OPC Browser Alarm Summary Messages

     Activity in the OPC Browser is viewed in the Alarm Summary window. Messages can be generated for:

      • Successful/ failed OPC server connection.

      • OPC server disconnection/ reconnection from the OPC Browser.

      • Success/failure to advise items.

      • OPC Browser loader successfully.

      • OPC Browser receives a request to close.

      • OPC Browser successfully closed.

    The Database Editor can only be fully accessed when P-CIM is running.

    OPCsrv|PFWOPCGateway.Server!DBSR.PCIM.A1

  • 8/16/2019 P-CIM OPC Communication

    31/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 28

    P-CIM OPC Gateway

    The P-CIM OPC Gateway is a P-CIM OPC server program that runs in P-CIM. It can be connected to

    any OPC client.

    The function of the OPC Gateway is to send data from P-CIM servers to external OPC client programsvia OPC protocol. Once an OPC client is connected to the OPC Gateway, the Gateway runs

    automatically, bringing data from the following P-CIM servers:

      • BasicSrv

      • DBSR

      • PfwAlarm

      • PFWDrvr  

      • TxtSrv

    The diagram below illustrates how data is received from P-CIM servers, translated by callback protocol

    and sent to the OPC Gateway.

    The data is then translated by OPC protocol and sent to external OPC clients. This is a bidirectional

    process.

    Running the OPC Gateway

    During runtime, when an OPC client is connected, the OPC Gateway runs automatically and

    the OPC Gateway icon is displayed in the traybar as an indicator.

    OPC item settings can be updated during runtime, If you wish to define new items or settings before

    the OPC client runs, open the Gateway manually.

    To open the Gateway manually: From the P-CIM Runtime icons group double click the OPCGateway Editor icon.

  • 8/16/2019 P-CIM OPC Communication

    32/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 29

    OPC Server Properties

    Open the OPC Browser and from the Server menu select the PfwOPCGateway Server Properties

    option.

    When P-CIM is not running, it is automatically started up if the OPC Gateway icon is double clicked in

    the P-CIM Group. Right clicking the OPC Gateway traybar icon displays three options:

      • About: when clicked displays details about P-CIM and the OPC Gateway.

      • Edit: when clicked displays the P-CIM OPC Gateway Editor.

      • Shutdown: when clicked shutsdown the OPC Gateway server.

    The OPC Gateway Editor

    The P-CIM OPC Gateway Editor enables definition of:

    Field Description

    Synchronous

    Read

    When enabled the OPC Browser polls the OPC Gateway for advised items every

    60 seconds using synchronous read..

    Synchronous

    Write

    When checked enables the OPC Browser to write advised items values in

    synchronous connection.

    Case Sensitive To enable usage of the case sensitive function,Case Sensitive check box.

    Communication

    test interval

    Defines the time interval between each communication test. Default = 30 seconds.

    Range: 10-36000 seconds.

    Communciation

    test attempts

    Defines the number of communication attempts that will be made by the OPC

    Browser until failed. Default = 3 attempts. Range: 1-100

    Time between

    reconnect

    attempts

    Time interval between reconnection attempts. Default = 60 seconds.

  • 8/16/2019 P-CIM OPC Communication

    33/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 30

      • Address names and settings.

    • An item’s Read/Write/Read and Write access permission.

      • An item’s data type.

    To access OPC Gateway Editor dialog box: From the traybar right click the OPC Gateway icon and

    select the Edit option.

    This dialog box has the following fields:

    Table 4: OPC Gateway Properties

    Field Description

    Name Where the name of a new item is defined.

    Server Indicating the type of P-CIM server used, which can be: BasicSrv, DBSR,

    PfwAlarm, PfwDrvr or TxtSrv.

    Note: The BasicSrv, PfwDrvr, and TxtSrv.servers items can only be assigned to

    OPC items in the P-CIM OPC Gateway Editor dialog box.

    Topic Indicating the name of the DDE format topic, which is always Pcim.

    Item Indicating the item’s address in DDE format.

    Data type Indicating the type of data block. The following block types are available:Boolean, byte, double, float, long, short and string.

    Access Indicating whether the item is Read, Write or Read and Write in the OPC client.

    Table Listing all item addresses and their settings.

    Add When clicked adds a new item to the Items table.

    Delete When clicked deletes a selected item from the Items table.

    Change When clicked updates a modified item in the Items table.

    Save When clicked saves the settings in the OPC Gateway.

    Close When clicked shuts down the OPC Gateway Editor.

  • 8/16/2019 P-CIM OPC Communication

    34/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 31

    Example – Defining an OPC Item in the OPC Gateway Editor

    1. Open the OPC Gateway Editor dialog box.

    2. Complete the dialog box fields using the information in the table above

    t

    3. Click the Save button to confirm these settings.

    4. To view/ read/ write the OPC item, connect the OPC client to the OPC Gateway. 

    Viewing OPC Items in a Client Interface

    In the OPC client Connect field, select and enter  the PfwOPCGateway.Server  key to the connect

    between the client and the OPC server.

    OPC items are displayed in an Items tree such as the one below:

    Field Settings

    Name Item 1

    Server DBSR

    Topic Pcim

    Item D:1

    Data type Boolean

    Access Read

    If the OPC client is already connected it may need refreshing manually when new items are

    added.Other OPC clients are automatically updated.

  • 8/16/2019 P-CIM OPC Communication

    35/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 32

    Branch Containing

    PfwOPCGateway.Server Indicates which OPC key is used to reference the OPC server. This

    name is automatically displayed in the Servers List in the client.

    DBSR  This branch holds P-CIM Database Server items.

    PfwAlarm This branch holds P-CIM Alarm Server items

    The PfwAlarm branch is only displayed when the Advanced Alarm

    Handler module is open and if items have been defined in it.

    User This branch is a container for the OPC items defined in the OPCGateway Editor.

  • 8/16/2019 P-CIM OPC Communication

    36/37

    Afcon Software and Electroncis Ltd

    P-CIM 7.70 OPC Communication User Guide 33

    OPC Browser Troubleshooting

    General

    The OPC Browser fails to advise items.

    Possible Cause: Upper Case Sensitivity in OPC Servers

    This situation could occur because the OPC server is case sensitive. The following definitions must be

    set when working with an OPC server that is case sensitive:

    File: OPC server name Section: General Token: Uppercase = 0

    The OPC Browser fails to connect to the OPC server,or connects but does not

    display the OPC tree..

    Possible Cause: Single Thread Connections to OPC Servers

    The OPC server is connected via a single-thread connections (and not via multi-thread connections).

    The following definitions must be set when connecting to an OPC server in a single-thread connection:

    File: OPCSRV.INI Section:[MainThreadConnection]NameSrvN= Token: OPCserver name

    Connection Failure Error Message

     A connection failure error message may be displayed when the OPC Browser connects to an OPC

    server, even though the connection is successful.

    To avoid this message the following definitions must be set:

    File: OPCSRV.INI Section:[IgnoreConnectError]NameSrvN= Token: OPCserver name

    Problems with Remote Connections

    If you have problems with remote connection, check the OPC server’s DCOM settings. During server

    startup the DCOM settings may be overwritten.

    IAfcom recommends that you contact the manufacturer of the server.

    The file name is the name of the OPC server.

    To date, this is a problem only for an Rslinx OPC on a local PC.

    To date, this is a problem only for an Rslinx OPC on a local PC.

  • 8/16/2019 P-CIM OPC Communication

    37/37

    Afcon Software and Electroncis Ltd

    NO-SEK Stations

    P-CIM No-SEK station is able to connect to a remote OPC server only if the P-CIM Master node is

    equipped with a site License and Unlimited IO SEK support.

    From a NO-SEK node, the OPC Browser will only be able to connect to a remote OPC server which

    resides on the P-CIM-Master station.

    Message Description

    P-CIM OPC Browser cannot

    connect to local OPC server

    when no SEK is attached

    The OPC Browser cannot connect to the local OPC

    server(s) while running on a Non-SEK station

    P-CIM OPC Browser cannot

    connect to remote OPC server -

    Master SEK is IO limited.

    OPC Browser cannot connect to remote OPC servers when

    the remote Master is a limited IO SEK.

    P-CIM OPC Browser cannot

    connect to remote OPC server -

    Master sites limitation.

    OPC Browser is unable connect to remote OPC servers

    when the Master nodes threshold has been reached. The

    "Connect" dialog box the "Network OPC Servers" button

    isdisabled.

    P-CIM OPC Browser cannot

    connect to remote OPC server –

    remote IP address is not equal to

    P-CIM Master IP

    The network OPC gateway is not reachable or the IP

    address is incorrect

    P-CIM OPC Browser cannot

    connect to remote OPC server –

    invalid IP address syntax

     An incorrect P-CIM Master IP or it does not exists.