pages from ba_26410

Upload: safald

Post on 09-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/8/2019 Pages From BA_26410

    1/8

  • 8/8/2019 Pages From BA_26410

    2/8

    Planning the installation Page 2 of 8 Chapter 3

    VF03de05a.doc Subject to technical alterations Sterling SIHI 2003

    3.1.1 Circulating liquid operation

    This method of operation is recommended for:

    Service liquids that due to their properties must

    neither leave the process circuit nor come into

    contact with the cooling liquid (e.g. when using

    oil, alkali or acid as service liquid). Waste water systems that must not be

    contaminated by the service liquid or by the gas

    dissolved in it etc.

    The service liquid B consists of circulating liquid

    U (B = U) that is cooled in the heat exchanger to therequired operating temperature. The heat exchanger

    must be selected so that it is able to extract

    completely the heat generated in the service liquid

    both by the effects of the motor and by the latent

    heat arising from any gas condensation.

    ATTENTION

    In case of this operating method the inner liquidreturn is not possible. Therefore the adjusting screw

    must not be turned out according to the paragraph

    3.2.8.

    The liquid pump shown in the circulating liquid line is

    necessary if the vacuum pump runs without a

    significant pressure difference between suction and

    discharge branch or, if the flow resistance of the heat

    exchanger exceeds approx. 0.2 bar.The heat exchanger can be omitted if the vacuum

    pump runs for only few minutes and the liquid can

    cool down to around ambient temperature before the

    next start-up.

    3.1.2 Combined liquid operation

    The service liquid B consists of make-up liquid F and

    circulating liquid U (B = F + U). The circulating liquidU flows either through the circulating liquid line or it

    is taken directly from the surge chamber during the

    inner liquid return (assembly according to 3.2.8). A

    liquid flow equal in quantity to the make up liquid F

    supplied, leaves the separator as drain liquid A

    through the liquid drain uA. The make up liquid shall

    have only slight overpressure (max. 0.1 bar or max.

    0.1 bar exceeding the compression pressure).

    3.1.2.1 Lay-outThis method of operation has a simple lay-out,

    requires little space and has a reduced make-up

    water consumption.

    The circulating liquid line is not necessary if the

    adjusting screw for the inner liquid return has been

    removed according to the section 3.2.8. If theseparate discharge of gas and liquid is not required

    the top mounted separator can be omitted. A pipe

    discharging into an outlet (gully) is sufficient. The line

    for cavitation protection, is led from the connection

    uc and must be connected to this pipework.

  • 8/8/2019 Pages From BA_26410

    3/8

    Planning the installation Page 3 of 8 Chapter 3

    VF03de05a.doc Subject to technical alterations Sterling SIHI 2003

    3.1.2.2 Temperature regulation

    In combined liquid operation the make-up liquid flow

    is regulated by means of a thermostat. In this way

    the required temperature of the service liquid can be

    maintained.

    3.1.3 Make-up liquid operation

    In uses corresponding to Category 1, it is not

    permitted to operate the pump using only make up

    water in the pump

    This method of operation is applicable where

    adequate liquid is available and where there is no

    need to reuse it as service liquid.

    The make-up liquid method of operation is

    recommended also in those cases where the

    temperature increase in the vacuum pump is low,

    e.g. when handling liquids with a low specific heat. In

    this case the inner liquid return is not reasonable so

    that the adjusting screw should not be turned out

    according to the section 3.2.8.

    If the separate discharge of gas and liquid is not

    required the top mounted separator can be omitted.

    A pipe discharging into an outlet (gully) is sufficient.

    The line for cavitation protection, is led from the

    connection uc and must be connected to this

    pipework. The service liquid B consists of make-up

    liquid F (B = F). Its pressure should not exceed 0 bar

    (atmospheric pressure) at the manometer vacuum

    gauge.

    If the pressure in the make-up liquid line varies

    considerably so that a temporary overpressure of

    about 0.1 bar at the manometer vacuum gauge is

    likely to be exceeded, a pressure reducing valve

    must be installed or the make-up liquid must be

    diverted into a tank with float valve (see fig. below).

    The liquid level in the tank from which the vacuum

    pump is supplied with service liquid must be at shaft

    level.

    For compressor operation the make-up liquid must

    be supplied at discharge pressure.

  • 8/8/2019 Pages From BA_26410

    4/8

    Planning the installation Page 4 of 8 Chapter 3

    VF03de05a.doc Subject to technical alterations Sterling SIHI 2003

    3.2 Pump, pipework connections

    ATTENTION

    Take note of the arrows indicating flow direction.

    The nominal diameters of the pipework must not

    be smaller than the nominal diameters of the

    corresponding pump branches.

    All pipework must be cleaned prior to installation

    of the pump.

    The pipework must be supported in order to

    avoid damage to pump components (danger ofbreaking the pump components).

    The suction, discharge and service liquid lines

    must be as short as possible and their cross

    section must be at least as large as the

    corresponding pump connections. For long

    lengths of pipework larger cross sections are

    required.

    LEH. 350 / 450, LEH. 600 / 800 / 900:

    The service liquid line can be connected to the

    second connection uB as well. This can be made

    alternatively but also additionally. If both connections

    are used, it must be ensured that the pressures and

    liquid flows are the same size.

    As from construction size LEH.1200 / 1500 / 1800:

    The connections uB must be used on both sides.

    3.2.1 Position of the pump

    The pump must be installed horizontally; the suctionbranch then points vertically upwards.

    3.2.2 Protection against cavitation

    Long operating periods under cavitation result in

    damage to the material of the pump and failure of

    the liquid ring vacuum pump.

    To ensure cavitation-free operation the pump must

    continuously be supplied with a minimum quantity of

    non condensable (inert) gas.

    Cavitation occurs if the pumping medium consistsmainly of vapour that condenses during

    compression. In order to prevent this, the

    connections uc at the pump and at the separator

    must be connected by pipework or by a hose. This

    enables the vacuum pump to draw non-condensable

    (inert) gas from the separator, if the suction pressure

    is 40 mbar or lower. This type of connection serves

    mainly to protect the pump during start-up if the

    suction side is closed (i.e. not effective protectionduring continuous operation with suction side

    closed).

    If the liquid ring vacuum pump is run at a suction

    pressure close to the vapour pressure of the service

    liquid, cavitation can also occur. In order to prevent

    cavitation at this operating point, the pump must be

    vented with non-condensable (inert) gas at the

    connection um.

    Cavitation does not occur, if the vacuum pump

    operates in combination with a gas ejector.

    Independent of the service liquid used, the

    suction pressure p1,min must not be allowed to

    fall below the preset limit. An inert (non

    condensable) gas must then be fed on the

    suction side.

    The smallest permitted suction pressure p1,min

    is 20 mbar higher than the vapour pressure of the

    service liquid.

    If pure vapour is pumped with the liquid ring

    vacuum pump, then on the suction side an inert

    gas must always be supplied.

    3.2.3 Suction line

    A non-return valve should be installed in the suctionline. For that purpose the SIHI non-return valves,

    type XCk, have proved to be good because of their

    low pressure loss.

    The venting of the pump, for example during

    starting-up and stopping, is possible by means of a

    vent cock, which must be installed at the

    connection ul um1 resp.

    If the pump is started or stopped with a closed shut-

    off component, e.g. valve in the suction line,

    cavitation will occur. This can be avoided by

    adopting cavitation protection measures (see 3.2.2).

  • 8/8/2019 Pages From BA_26410

    5/8

    Planning the installation Page 5 of 8 Chapter 3

    VF03de05a.doc Subject to technical alterations Sterling SIHI 2003

    3.2.4 Discharge line

    The valve (1) must not be closed during pump start-

    up.

    3.2.5 Operation with minimal pressure

    difference

    If a pump is run for a long period without a significant

    pressure difference (less than 0.2 bar), e.g. toevacuate a large tank, an orifice plate must be

    installed in the suction line.

    3.2.6 Shaft seal

    Mechanical seals or gland packing are used to seal

    the shaft. In the as delivered pump, seal flushing is

    by liquid from the interior of the pump.

    To change the pump to flushing / sealing with an

    external liquid, please contact the manufacturer.

    3.2.7 Dirt drain

    If any fine-grained dirt went along with the pumped

    gas or the service liquid might reach the pump, it can

    be washed out by liquid through the connection use

    during the operation in order to avoid any corrosion.

    In case of strong dirt sediment the dirt drain can be

    operated continuously.

    In order to safely wash out the dirt particles the

    suction pressure should not be lower than approx.

    300 mbar. However it must be observed that the

    pump is nearly completely drained through this

    connection during standstill. Therefore the drain line

    must be closed before putting out of operation or the

    pump must be refilled up to the shaft height before

    putting into operation.

    3.2.8 Inner liquid return

    In the casing the pump has a mounted line for the

    liquid return from the surge chamber up to the

    service liquid chamber. During delivery this line is

    closed by an adjusting screw (grub screw). Itbecomes accessible after turning out the locking

    screw on the connection uiF. The inner liquid return

    enables a combined liquid operation with a low

    expenditure of technical devices. The make-up liquid

    must be fed with slight overpressure. The make-up

    liquid flow can be regulated by the pressure.

    LEH. 600-900

    LEH. 1200-1800

    LEH. 2200 / 3000

    LEH. 3600 / 4400

    LEH. 350 / 450

  • 8/8/2019 Pages From BA_26410

    6/8

    Planning the installation Page 6 of 8 Chapter 3

    VF03de05a.doc Subject to technical alterations Sterling SIHI 2003

    3.3 Electrical connections

    For the drive motor a mains connection is required

    that complies with the regulations valid at site.

    The rules and instructions prescribed by the local

    public utilities regarding precautions against

    explosion must be observed. The motor protectionswitch or the excess current trip must be adjusted to

    the rated current of the motor.

    3.4. Accessories

    The following accessories are available for liquid ring

    vacuum pumps:

    Motor protection switch to control the power

    absorption of the motor

    Soft starter

    Liquid separator Gas ejector

    Heat exchanger

    Required connection pipework

    Fittings for the thermostatic control of the service

    liquid temperature

    Ball type non-return valve

    Drain valve

    Safety valve

    Liquid discharge trap

    3.4.1 Motor protection switch

    The motor protection switch controls the power

    absorption of the drive motor. If the rated current is

    exceeded the motor is switched off automatically.

    3.4.2 Soft starter

    A soft starter can be used to start-up the pump. Slow

    acceleration of the pump is preferable both for the

    pump/package and for the power system.

    3.4.3 Liquid separator

    A part of the service liquid leaves the pump together

    with the compressed gas. In the liquid separator the

    gas and liquid are separated.

    The following types of liquid separators are available:

    top mounted liquid separator

    upright liquid separator

    3.4.4 Gas ejector

    Sterling SIHI gas ejectors complement Sterling SIHI

    liquid ring vacuum pumps.

    Detailed information is available from the operating

    instructions for gas ejectors.

    3.5. Compressor operation

    If the operational limits (see chapter 9) are observed,

    this pumps can also be used as compressors.

    For compressor operation a pressure liquid

    separator XBd should be used and be placed in such

    a way alongside the liquid ring compressor that the

    liquid drain uA is at shaft level. A safety valve, set in

    accordance with the operating conditions, must be

    connected to the connection ub of the separator. A

    liquid discharge trap XUk must be provided for thedrain liquid.

    For this application there are three different methods

    of operation:

    - Circulating liquid operation

    - Combined liquid operation

    - Make-up liquid operation

    If the evacuated gases or vapours are inflammable

    or injurious to health, a gas tight take-off must be

    installed. In addition leakage tests must be carriedout at regular intervals. This is also required after

    repair work.

    ATTENTION

    In case of compressor operation > 0.5 bar the EU

    Pressure Equipment Directive must also be

    observed.

  • 8/8/2019 Pages From BA_26410

    7/8

    Planning the installation Page 7 of 8 Chapter 3

    VF03de05a.doc Subject to technical alterations Sterling SIHI 2003

    3.6 V Belt Operation

    The preferred method of drive for the load on both

    the pump shaft and on its bearings is direct drive. In

    case of large vacuum pumps it is recommendable to

    use a gearing between motor and pump. If a V-belt

    drive is to be used, the motor should be arranged asfollows:

    Pump with clockwise rotating shaft (fig. 3.6):

    Motor adjacent to and on the right side of the

    pump

    Pump with anticlockwise rotating shaft:

    Motor adjacent to and on the left side of the pump

    fig. 3.6 Pump with clockwise rotating shaft

    ATTENTION

    The minimum permitted diameter of the pulley is set

    out in chapter 9.3.

    In Ex- areas, electrically conducting pulleys must be

    used (< 106). The halves of the sheave must be

    electrically connected to ensure that they are at the

    same potential.

    3.7 Explosion protection

    In accordance with the Directive 94/9/EG, all

    components of a package for use in explosive areas

    must comply with the required equipment category.

    In this connection it is important to distinguish

    between the location of the pump and the internal

    environment of the pump.

    3.7.1 Location

    Pump location corresponds to Category 2.

    3.7.2 Internal environment of the pump

    Requirements:

    If it is required that the internal parts of the pump

    conform to Category 2, then the following additional

    requirements must be considered at the planning

    stage of the installation.

    Category 1 for the pump internals:

    For applications requiring Category 1, the operating

    instructions Ex 1G/2G must, in addition, be adhered

    to.

    Category 2 for the pump internals:

    Explosion protection in the working chamber of the

    liquid ring vacuum pump is assured by prevention of

    any effective ignition source. This is made possible

    by ensuring that in all operating conditions (at start

    up, shut down as well as when operating) a sufficient

    quantity of liquid is in the pump. For conformity with Category 2 for the pump

    internals, the level of the liquid in the pump on

    start up and the liquid inlet during operation, must

    be monitored.

    When a safety control is activated, the vacuum

    pump must automatically switch off.

  • 8/8/2019 Pages From BA_26410

    8/8

    Planning the installation Page 8 of 8 Chapter 3

    VF03de05a.doc Subject to technical alterations Sterling SIHI 2003

    Technical Execution:

    To guarantee Category 2 for the internals of the liquid ring vacuum pump, Sterling SIHI suggests the following

    layout:

    N1 = Process gas

    N2 = Gas out

    A = Overflow

    F = Make-up liquid

    K = Cooling liquid

    c = Cavitation protection

    e = Draining

    Flow chart: Vacuum pump system with alternative safety devices

    Package with liquid separator unit with coupled cavitation protection pipework and with a backflow

    prevention ball valve in the suction line.

    Measuring equipment:

    LS1 Liquid level in the vacuum pump

    or

    LS2 Liquid level in the adjacent liquid separator.

    FS1 Liquid flow in the service liquid line

    or

    TS1 Temperature in the pressure chamber of the pump casing or in the pressure line directly behind

    the discharge orifice of the pump.

    The measurement positions LS1 and LS2 should be adjusted so as to be on the same level as the shaft of the

    liquid ring vacuum pump. For LS1 the connection um1 resp. um (see dimensions table) can be used.If a check valve is installed in the service liquid line from the liquid separator to the pump, it must be ensured that

    during start up as well as during operation, that the valve remains open.

    Monitoring of the pressure in the pressure line PS2 is recommended if, because of the system design, the

    permitted compression pressure (see Chapter 9) is likely to be exceeded.