® U.S. Registered Trademark Copyright © 2019 Honeywell Inc. • All Rights Reserved EN0B-0701GE51 R1219
Panel Bus I/O Modules
PRODUCT DATA
GENERAL The Honeywell Panel Bus I/O Modules communicate via the Panel Bus. The pluggable Honeywell Panel Bus I/O modules consist of a terminal socket and a removable electronic module, allowing the socket to be mounted and wired before the electronic module is installed. All such electronic modules can be swapped out without disrupting the power and bus connec-tions: Simply unplug the “old” and insert the “new” module.
WARNING
Risk of electric shock or equipment damage!
Do not touch any live parts in the cabinet. Disconnect the power supply before you start to install
the control system. More than one disconnect switch may be required to de-energize the system.
Do not reconnect the power supply until you have completed the installation.
Unused terminals must be closed (by completely screwing in the terminal screws), thus preventing the accidental touching of “live” parts.
The mixed Honeywell Panel Bus I/O modules offer a mix of 34 inputs and outputs in a compact housing. Software updates, configuration, and commissioning are all done automatically by the controller for all Panel Bus I/O Modules. The Panel Bus I/O Modules are addressed manually by adjusting their HEX switches. The Panel Bus I/O Modules may be used with any CPU supporting Panel Bus communication (e.g., the XL800, CPO-PC-6A, etc.).
FEATURES Plug-and-play functionality for easy maintenance.
Pluggable Panel Bus I/O modules can be exchanged without rewiring. Further, the separate installation of terminal sockets and electronic modules lower risk of damage and theft in the construction phase.
Fast wiring with state-of-the-art push-in terminals (screw-type terminals also available) and bridge connectors.
Wide range of sensors supported (NTC20kΩ, NTC10kΩ, PT1000-1/-2, Johnson A99 PTC, NI1000TK5000, PT3000, Balco500, 0/2…10 V, 0/4…20 mA). NOTE: The mixed Panel Bus I/O modules XF830A, XFU830A, and CPO-IO830 feature inputs suitable for signals from NTC20kΩ sensors and 0/2…10 V, 0/4…20 mA, only!
Binary input LEDs of the pluggable Honeywell Panel Bus I/O Modules can be configured for status display (off / yellow) or alarm display (green / red) per channel. NOTE: The mixed I/O modules XF830A, XFU830A, and CPO-IO830 feature only non-configurable binary input LEDs!
Configurable safety position for outputs, in case of loss of communication with the controller.
Max. wiring flexibility due to optional accessories like aux. terminals and cross-connectors.
Can be mounted in small installation housings
Flexible mix of Panel Bus I/O modules covering all your application requirements.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 2
OVERVIEW
PANELBUS MODULES
pluggableANALOG OUTPUT
pluggableANALOG INPUT
pluggableBINARY INPUT
pluggableFLOATINGOUTPUT
MIXED I/Os(with integrated socket)
XF821A
XS821-22XSU821-22CONTROLLER
XS823XSU823
XS824-25XSU824-25
XFR822A
XF822A XF823A
pluggableRELAY OUTPUT
XFR824A XFR825A
XF824A
Panel BusXF830A, XFU830A, CPO-IO830A
PANEL BUS I/O MODULES
1 2 3 4 5 6 7 8 9 10 11 12
B1 B2 B3 B4 B5 B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
DI
Binary Inputs
G1 G2
41 42
GND Analog Outputs
AI2 AI3 AI4
14 15 16
AI1
AI5 AI6 AI7 AI8
17 18 19 20
13
Analog Inputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
DO
24V Relays
NO1 NO2 NO3 NO4 NO5 NO6
IN1 IN2 IN3 IN4 IN5 IN6
35
29 30 31 32 33 34
36 37 38 39 40
1 2 3 4 5 6
HoneywellComfortPoint OpenTM
Install. Instr.MU1B-0463GE51
!
CPO-IO830A
XF830A, XFU830A
Fig. 1. Overview of Honeywell Panel Bus I/O Modules
Table 1. Overview of Honeywell Panel Bus I/O Modules order number description
Pluggable Panel Bus I/O Modules
XF821A Pluggable Panel Bus Analog Input Module (with 8 analog inputs)
XF822A Pluggable Panel Bus Analog Output Module (with 8 analog outputs)
XFR822A Pluggable Panel Bus Analog Output Module (with 8 analog outputs and manual overrides)
XF823A Pluggable Panel Bus Binary Input Module (with 12 binary inputs)
XF824A Pluggable Panel Bus Relay Output Module (with 6 relay outputs)
XFR824A Pluggable Panel Bus Relay Output Module (with 6 relay outputs and manual overrides)
XFR825A Pluggable Panel Bus Floating Output Module (with 3 floating outputs and manual overrides)
Mixed Panel Bus I/O Modules with integrated socket
XF830A Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with push-in terminals (incl. bridge connector and swivel label); housing matches XL800 design
XFU830A Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with screw terminals (incl. bridge connector and swivel label); housing matches XL800 design
CPO-IO830 Mixed Panel Bus I/O Module (with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs), with push-in terminals (incl. bridge connector); housing matches CPO-PC-6A design
Terminal Sockets (not needed for the mixed I/O modules XF830A, XFU830A, and CPO-IO830)
XS821-22 Push-in terminal socket for pluggable AI/AO modules (incl. bridge connector, swivel label)
XSU821-22 Screw-type terminal socket for pluggable AI/AO modules (incl. bridge connector, swivel label)
XS823 Push-in terminal socket for pluggable BI modules (incl. bridge connector, swivel label)
XSU823 Screw-type terminal socket for pluggable BI modules (incl. bridge connector, swivel label)
XS824-25 Push-in terminal socket for pluggable relay/floating output modules (incl. bridge connector, cross connector, swivel label)
XSU824-25 Screw-type terminal socket for pluggable relay/floating output modules (incl. bridge connector, cross connector, swivel label)
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 3
Table 2. Overview of auxiliary parts and spare parts
order number description
XS814
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block includes two groups with seven internally-connected push-in terminals. For pluggable I/O modules, only.
XS830A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9
Ten Auxiliary Terminal Blocks (for distribution of signals/power). Each terminal block consists of two groups of nine internally-connected push-in terminals. For XF830A and XFU830A, only.
XS831A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8
Ten Auxiliary Terminal Blocks (for connection of 0…20 mA signals). Each terminal block consists of two groups of four pairs of push-in terminals (each with a 499Ω resistor to GND) for supporting up to eight current inputs. For XF830A and XFU830A, only.
XS815
20 Cross-Connectors for connection of six relay commons. One Cross-Connector is included in the Terminal Socket package. For pluggable I/O modules, only.
XS816
10 Bridge Connectors. One Bridge Connector is included in the Terminal Socket package.
XAL10
10 Swivel Labels Holders (for attaching the application-specific label printed with CARE). One Swivel Label Holder is included in each Terminal Socket package. For pluggable I/O modules, only.
XAL11
10 Swivel Label Holders for XF830A and XFU830A mixed Panel Bus I/O modules. One Swivel Label Holder is included in each package of XF830A and XFU830A mixed Panel Bus I/O modules.
NOTE: All Honeywell Panel Bus I/O analog and binary I/O Modules are protected against short circuit, 24 VAC +20% and
40 VDC. The relay outputs of relay output modules, floating output modules, and mixed I/O modules should be equipped with appropriate fusing to protect against short-circuiting of the load.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 4
Table 3. Pluggable Panel Bus I/O Module specifications
Module Analog Inputs Analog Outputs Binary Inputs Relay Outputs Floating Outputs
XF821A XF822A, XFR822A XF823A XF824A, XFR824A XFR825A no. of I/Os
8 analog inputs 8 analog outputs 12 binary inputs requiring a gold contact or open collector
6 relay outputs 3 floating outputs
charac-teristics
Linear Graph, 0..10 VDC with pull-up, 0(2)…10 VDC without pull-up NTC20kΩ (-50…+150 °C, default) NTC10kΩ (-30…+100 °C) PT1000-1 (-50…150 °C) PT1000-2 (0…400 °C) Johnson A99 (-40…+120 °C) NI1000TK5000 (-30…+130 °C) PT3000 (-50…150 °C) BALCO500 (-30…120 °C) Also configurable as: binary inputs Linear graph (0…10 V with
pull-up) Features: 16-bit resolution configurable offset per input auxiliary voltage: 10 VDC, Imax
= 5 mA
0…11 VDC / 1 mA Also configurable as: floating outputs or binary outputs (0 V / 10 V) Features: 8-bit resolution
(default) Safety position
(remain, 0%, 50%, 100%) red LED per output light intensity follows
output level in auto Version with manual override (R): 1 potentiometer per
output auto feedback signal
(mode + value) blinking in manual
override position
static binary input, (default: dry contact) Also configurable as: totalizers (20 Hz) Features: 1 LED per input Color mode can be
set per input to OFF/yellow or green/red using CARE ON: < 1.6 kΩ to
GND or < 2.5 V to GND, OFF: > 90 kΩ to GND or > 4 V to GND
relay outputs (default) Features: Changeover relays Voltage:
19…250 VAC, 1…29 VDC, P>50 mW max. total current:
12 A current per relay:
N.O.: 4(4) A (AC) or 4(1) A (DC), N.C.: 2(1) A (AC) or 4(1) A (DC) Safety position
(remain, 0%, 100%) yellow LED per output With man. override (R): 1 switch per output auto feedback signal
(mode + value) blinking in manual
override position
floating outputs Features: 2 relays per
floating output Voltage:
19…250 VAC, 1…29 VDC, P>50 mW max. total current:
12 A current per relay:
N.O.: 4(4) A (AC) or 4(1) A (DC), N.C.: 2(1) A (AC) or 4(1) A (DC) 1 potentiometer per
floating output 2 LEDs per output:
green: relay 1 closed, red: relay 2 closed blinking in manual
override position auto feedback sig-
nal (mode + value) Manual Overrides as per EN ISO 16484-2:2004 The manual override switches and potentiometers of the output modules (…R822A, …R824A, and XFR825A) support direct operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units." Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the corresponding output LED will blink continuously, and the output module will send a feedback signal with the status "manual override" and the given override position to the controller (which will then also store this information in its alarm memory). NOTE: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their
manual override switches and/or potentiometers.
Table 4. Mixed Panel Bus I/O module specifications (XF830A, XFU830A, and CPO-IO830)
Analog Inputs Analog Outputs Binary Inputs Relay Outputs Number: 8 Configurable types: NTC20kΩ (-30…+110 °C)
(default) Linear Graph 0..10 VDC with pull-up 0(2)…10 VDC without pull-up Also configurable as: binary inputs (static, dry con-
tact, only) Features: 10-bit resolution configurable offset per input
Number: 8 Configurable types: 0…11 VDC / 1 mA (default) Also configurable as: binary outputs (0 V / 10 V) Features: 10-bit resolution (default) Safety position (remain, 0%,
50%, 100%)
Number: 12 (requiring a gold contact or open collector) Configurable types: Static binary inputs (default:
static, dry contact); ON: < 1.6 kΩ to GND or < 2.5 V to GND, OFF: > 90 kΩ to GND or > 4 V to GND
Also configurable as: totalizers (15 Hz) Features: 1 yellow LED per input
Number: 6 Configurable types: Relay outputs (default) Features: Voltage: 24 VAC/DC,
P>50 mW max. total current: 3 A
(AC/DC) current per relay: 500 mA normally-open contacts: P >
50 mW, voltage: 24 V (AC/DC) 1 yellow LED per output
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 5
GENERAL FEATURES
PRESS PR
ESS PR
ESS PRES
S
1 2 3 Honeywell
AUTO
0
!
A A A100
S1 S221
0F E DCB
98
76543
A
71 COM a
72 COM b
73 24V~
74 24V 0~
21
22
23
14 4424 5434 64 25
13
12
11 31
32
33
41
42
43
51
52
53
61
62
61
62
6363
1 2 3 4 5 6 7 8 Honeywell
AUTO
0
!
A A A A A A A A100
S1 S221
0F EDCB
98
76543
A
21
9
GND GND
AI/AOVAUX
10 11 12 13 14 15 16 17 18 25 26
22 1 2 3 4 5 6 7 8
1 2 3 4 5 6 Honeywell
--1--0--AUTO
!
S1 S221
0F E DCB
98
76543
A
21
22
23
14 4424 5434 64 25
13
12
11 31
32
33
41
42
43
51
52
53
61
62
61
62
6363
1 2 3 4 5 6 7 8 Honeywell
!
21
9
GND GND
AI/AOVAUX
10 11 12 13 14 15 16 17 18 25 26
22 1 2 3 4 5 6 7 8
GND
BI
13 14 15 16 17 18 19 20 21 22 23 24 25 26
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12 Honeywell
!
S1 S221
0F EDCB
98
76543
A
71 COM a
72 COM b
73 24V~
74 24V 0~
PRESS PR
ESS
1:ABCDFERTAQWESDERT1
2:ABCDFERTAQWESDERT2
3:ABCDFERTAQWESDERT3
4:ABCDFERTAQWESDERT4
5:ABCDFERTAQWESDERT5
6:ABCDFERTAQWESDERT6
7:ABCDFERTAQWESDERT7
8:ABCDFERTAQWESDERT8
3 42
6 7
571 COM a
72 COM b
73 24V~
74 24V 0~
1
Fig. 2. Panel Bus I/O Modules on DIN rails
Legend 1 Controller (e.g., XL800, XL Web II, CPO-PC-6A, etc.) 2 Cable (power and LONWORKS) connection from controller
to Panel Bus I/O Modules 3 Swivel label holder 4 Cable connection between Panel Bus I/O Modules on
separate DIN rails 5 Bridge connectors between Panel Bus I/O Modules on
same DIN rail 6 Stopper (from 3rd-party supplier) 7 Auxiliary terminal packages
LEDs Each Honeywell Panel Bus I/O Module is equipped with: one green power LED one yellow service LED
Overvoltage Protection All Honeywell Panel Bus I/O analog and binary I/O Modules are protected against short circuit, 24 VAC +20% and 40 VDC. The relay outputs of relay output modules, floating output modules, and mixed I/O modules should be equipped with appropriate fusing to protect against short-circuiting of the load.
Service LED Each Panel Bus I/O Module is equipped with a yellow service LED (status: yellow/OFF) for easy diagnosis of failures.
Microprocessor Each Panel Bus I/O Module is equipped with its own microprocessor.
System Constraints Depending upon the given controller, up to 64 I/O modules in any combination of models may be connected.
Addressing Addressing is performed using the HEX switch.
System Constraints
Table 5. System constraints
Max. no. of I/O modules (any combination) per controller
depends upon controller type
Max. no. of I/O modules per row 10
Max. current (F1) 4 A
Max. current (F2) 12 A
Max. current (F3) 12 A
Max. row length 3 m
Max. distance between rows 40 m
Min. cross-section of GND (terminal 9) (protected by F2)
1.5 mm2
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 6
Analog Input Module
1
2 3
Fig. 3. XF821A Panel Bus AI Module (shown with terminal
socket) Legend 1 Hex switch S2 2 Service LED 3 Power LED The pluggable Honeywell Panel Bus Analog Input Module, with 8 analog inputs, is installed with the XS821-22 or XSU821-22 Terminal Socket.
24.9 kOHM
RTD
10 VDC
AI
GND
Fig. 4. Analog input low impedance (input circuit for
PT1000, Johnson A99 PTC, Balco500, PT3000, NI1000TK5000, slow binary input)
199.9 kOHMVi
AI
GND
Fig. 5. Analog input high impedance (input circuit for
voltage input for active sensors)
199.9 kOHM(8.9 VDC IFCONNECTIONINTERRUPTED)
Vi
AI
GND
24.9 kOHM
10 VDC
Fig. 6. Analog input impedance setpoint (input circuit for
NTC10kΩ, NTC20kΩ, wall module setpoint)
71 75
72 76
73 77
74
21
9
VAUX
GND GND GND GND GND GND GND GND GND GND
VAUX
22
10
1
11
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
2
12
3
13
4
14
5
15
6
16
7
17
8
18 25 26
78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
Fig. 7. Terminal assignment and internal connections
Features 0…10 VDC, 2…10 VDC without pull-up 0…10 VDC with pull-up (linear graph, e.g. used for wall
module connection) 0/4…20 mA, needs 499 Ω resistor in parallel NTC20kΩ (-50…+150 °C, default) NTC10kΩ (-30…+100 °C) PT1000-1 (-50…+150 °C) PT1000-2 (0…+400 °C) NI1000TK5000 (-30…+130 °C) PT3000 (-50…+150 °C) BALCO500 (-30…+120 °C) Binary input 16-bit resolution Configurable offset per input Auxiliary voltage: 10 VDC, IMAX = 5 mA Sensor failure detection
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 7
OPT. AUX. TERMINAL MODULE XS814
A1 A2 A3 A4 A5 A6 A7 B1 B
XF821A ANALOG INPUT MODULE
74
21
9 925
GND GNDGND GNDGNDGNDGNDGND GNDGND GND GND
22
10 1026
1
11
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
2
12
3
13
4
14
5
15
6
16
7
17
8
18
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
VAUX VAUX
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
ACTIVE SENSOR1: 24V POWER2: 0...10 VDC SIGNAL3: GND (24V 0)
~
~
AUX. VOLTAGE + POT.1: SIGNAL2: GND3: 10 VDC AUX.
2 23 31 1
F1
F2
XF...
(24 VAC)EXTERNALGROUND
REQUIRED TOPOWER
EXTERNALDEVICES
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 8. XF821A Panel Bus AI Module, wiring example 1: Active sensor and potentiometer
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 8
DRY CONTACT1: SIGNAL2: GND
XF821A ANALOG INPUT MODULE
XF... XF...
74
21
9 925
GND GNDGND GNDGNDGNDGNDGND GND GND GND GND
22
10 1026
1
11
AI1 AI2 AI3 AI4 AI5 AI6 AI7 AI8
2
12
3
13
4
14
5
15
6
16
7
17
8
18
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
VAUX VAUX
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
2 22 1 11
DRYCONTACT TEMP. SENSOR
(NTC20k or Pt1000)
0(4)...20 mA1: IN2: OUT
7824V~0
77
76
75
24V~
COMB
COMA
EXTERNAL 499 OHMRESISTOR WITHTWIN WIRE-END
FERRULESREQUIRED.
EXTERNALDC POWER
SUPPLY
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 9. XF821A Panel Bus AI Module, wiring example 2: Passive sensor and 0 (4) … 20 mA signal
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 9
Analog Output Modules
4 53
2
1
Fig. 10. XFR822A Panel Bus AO Module (shown with
terminal socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable Honeywell Panel Bus Analog Output Modules, with 8 analog outputs, are available in the following models: XF822A Panel Bus Analog Output Module (without
manual overrides) XFR822A Panel Bus Analog Output Module (with manual
overrides)
They are installed with the XS821-22 or XSU821-22 Terminal Socket.
71 75
72 76
73 77
74
21
9
GND GND GND GND GND GND GND GND GND GND
22
10
1
11
AO1NC NC AO2 AO3 AO4 AO5 AO6 AO7 AO8
2
12
3
13
4
14
5
15
6
16
7
17
8
18 25 26
78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
Fig. 11. Terminal assignment and internal connections
Features 0…11 VDC, +/-1 mA Floating actuator (requires MCD3) Binary output (0 V / 10 V) red LED per output (brightness according to signal level) Optional versions with manual override potentiometers
(Auto, 0…100%; LED flashes in override mode) Feedback on manual override signal 8-bit resolution Configurable safety position for outputs in case of
communication problems (remain, 0%, 50%, 100%)
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 10
XF822A ANALOG OUTPUT MODULE
XF...
OPT. AUX. TERMINAL MODULE XS814
74
925
GND GND
1026
A1 A2 A3 A4 A5 A6 A7 B1
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
2 31
F1
F2
21
NC NC22 1
AO1AO2AO3AO4AO5AO6AO7AO8
2 3 4 5 6 7 8
M
9
GND GND GNDGNDGNDGND GND GND GND GND
10 11 12 13 14 15 16 17 18
24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL
~
~~
B
XS814
A1 A
(24 VAC)EXT. GROUND
REQUIREDTO POWER
EXT. DEVICES
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 12. XF822A Panel Bus AO Module, wiring example 1: Actuator
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 11
XF822A ANALOG OUTPUT MODULE
XF...
OPT. AUX. TERMINAL MODULE XS814
74
925
GND GND
1026
A1 A2 A3 A4 A5 A6 A7 B1
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
2
2
3
3L N
1
1
F1
F2
21
NC NC22 1
AO1AO2AO3AO4AO5AO6AO7AO8
2 3 4 5 6 7 8
M
M
2 1
M
9
GND GND GNDGNDGNDGND GNDGND GND GND
10 11 12 13 14 15 16 17 18
11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8
MCD 3
K1 K2 K3
24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL
~
~~
B
XS814
A1 A
(24 VAC)
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
EXT. GROUNDREQUIREDTO POWER
EXT. DEVICES
Fig. 13. XF822A Panel Bus AO Module, wiring example 2: Relay Module MCD 3
The relay module facilitates the control of peripheral devices with high load via the analog outputs. Input terminal 17 of MCD3 controls changeover contact K3. Relay terminal 18 of MCD3 controls the N.O. contacts (floating outputs) K1, K2.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 12
XF822A ANALOG OUTPUT MODULE
XF...
OPT. AUX. TERMINAL MODULE XS814
74
925
GND GND
1026
A1 A2 A3 A4 A5 A6 A7 B1
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
2 31
F1
F2
21
NC NC22 1
AO1AO2AO3AO4AO5AO6AO7AO8
2 3 4 5 6 7 8
M
9
GND GND GNDGNDGNDGND GND GND GND GND
10 11 12 13 14 15 16 17 18
24V DRIVE WITH0...10 VDC SIGNAL1: 24V POWER2: GND (24V 0)3: 0...10 VDC SIGNAL
~
~~
B
XS814
A1
(24 VAC)
11 12 13 14 15 16 17 18
1 2 3 4 5 6 7 8
MCE 3
K1 K2 K3
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F2
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
EXT. GROUNDREQUIREDTO POWER
EXT. DEVICES
Fig. 14. XF822A Panel Bus AO Module, wiring example 3: Relay Module MCE 3
The relay module facilitates the control of peripheral devices with high load via the analog outputs.
Input terminal 16 of MCE3 controls the N.O. contact K3.
Input terminal 17 of MCE3 controls the changeover contact K2.
Input terminal 18 of MCE3 controls the changeover contact K1.
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 13
Binary Input Module
3 42
1
Fig. 15. XF823A Panel Bus BI Module (shown with XS823
terminal socket) Legend 1 Hex switch S2 2 Status LEDs 3 Service LED 4 Power LED The pluggable Honeywell Panel Bus Binary Input Module, with 12 binary inputs, is installed with the XS823 or XSU823 Terminal Socket.
71 75
72 76
73 77
74
GND GND GND GND GND GND GND GND GND GND GND GND
1
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12
2 3
13
4
14
5
15
6
16
7
17
8 9 10 11 12
18 19 20 21 22 23 24 25 26
78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
Fig. 16. Terminal assignment and internal connections
Features Static binary input (dry contact) Totalizer for up to 20 Hz LEDs per binary input supporting alarm display mode
(red/green) or status mode (off/yellow). Color mode of each LED can be set to OFF/yellow or
green/red in CARE.
Configuration as Fast Totalizer Using CARE, the binary inputs can be configured as fast totalizers for operation in conjunction with devices equipped with an open collector output.
Table 6. Binary inputs used as fast totalizers
Frequency max. 20 Hz
Pulse ON min. 25 ms
Pulse OFF min. 25 ms
Bounce max. 5 ms
FASTTOTALIZER
DRY CONTACT4 ... 40 VDC = OPEN0 ... 2 VDC = CLOSED
150 kOHM
10 kOHM
18 VDC (NOT STABILIZED)
+V
BI
GND
Fig. 17. Configuration of binary input as fast totalizer
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 14
DRY CONTACT1: SIGNAL2: GND
TOTALIZER1: SIGNAL2: GND
XF823A BINARY INPUT MODULE
XF...
74
25
GNDGND GND GND GND GND GND GND GND GND GND GND
26
1
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10BI11BI12
2 3
13
4
14
5
15
6
16
7
17
8 9 10 11 12
18 19 20 21 22 23 24
747824V~0
24V~0
24V~0
73 7377
72 7276
71 7175
24V~
24V~
24V~
COMB
COMB
COMB
COMA
COMA
COMA
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
21
DRYCONTACT
F1
21
TOTALIZERMIN. 25 ms
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm 2
DASHED LINES
THIN LINES
F1
LEGEND:
THICK LINES
MAX. 4 A
Fig. 18. XF823A Panel Bus BI Module, wiring example: Dry contact and totalizer
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 15
Relay Output Modules
1
4 53
2
Fig. 19. XFR824A Panel Bus Relay Output Module (shown
with terminal socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable Honeywell Panel Bus Relay Output Modules, with 6 relay outputs, are available in the following versions: XF824A Panel Bus Relay Output Module (without manual
overrides) XFR824A Panel Bus Relay Output Module (with manual
overrides) They are installed with the XS824-25 or XSU824-25 Terminal Socket.
REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
25
71 75
72 76
73 77
74 78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
RELAY BLOCK 1 RELAY BLOCK 2
Fig. 20. Terminal assignment and internal connections
Features - Cross-Connecter - 1 yellow LED per output - Optional versions with manual override switches (Auto, 0,
1; LED flashes in override mode) - Feedback on manual override signal - Configurable safety position for outputs in case of
communications problems (remain, OFF, ON) - Permissible load per Relay Output Module (total)
Max. load: 19…250 VAC: 12 A 1…29 VDC: 12 A resistive, 3 A inductive
- Permissible load per normally-open contact: Max. load:
19…250 VAC: 4 A resistive or inductive 1…29 VDC: 4 A resistive, 1 A inductive
Min. load: P > 50 mW - Permissible load per normally-closed contact:
Max. load: 19…250 VAC: 2 A resistive, 1 A inductive 1…29 VDC: 2 A resistive, 1 A inductive
Min. load: P > 50 mW
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 16
OPTIONAL AUX. TERMINAL PACKAGE XS814
POWER SUPPLY230 VAC
NL
B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7
XF...
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
74 24V~0
73
72
71
24V~
COMB
COMA
XF824A RELAY OUTPUT MODULE
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
25
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
FIELD DEVICE1: 230 V (N)2: 230 V (L)
FIELD DEVICE1: 230 V (N)2: 230 V (L)
1 2
M230 V
1 2
M230 V
F1
F3
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F32
DASHED LINES
THIN LINES
F3
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
CROSS CONNECTOR XS815 (FACTORY-MOUNTED)
Fig. 21. XF824A Panel Bus RO Module, wiring example 1: Both relay blocks with line voltage
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 17
POWER SUPPLY230 VAC
CROSS CONNECTOR XS815 (FACTORY-MOUNTED)
NL
XF...
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
74 24V~0
73
72
71
24V~
COMB
COMA
XF824A RELAY OUTPUT MODULE
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
25
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
FIELD DEVICE1: 230 V (N)2: 230 V (L)
FIELD DEVICE1: 230 V (N)2: 230 V (L)
1 2
M230 V
1 2
M230 V
F1
FIELD DEVICE1: 230 V (N)2: 230 V (L)
1 2
M230 V
OPTIONAL AUX. TERMINAL PACKAGE XS814
B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7
F3
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F32
DASHED LINES
THIN LINES
F3
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 22. XF824A Panel Bus RO Module, wiring example 2: Relay blocks with low and line voltage
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 18
Floating Output Module
4 53
2
1
Fig. 23. XFR825A Panel Bus Floating Output Module
(shown with socket) Legend 1 Hex switch S2 2 Manual overrides 3 Status LEDs 4 Service LED 5 Power LED The pluggable XFR825A Panel Bus Floating Output Module, with manual overrides and 3 floating outputs, is installed with the XS824-25 or XSU824-25 Terminal Socket.
REMOVABLE CROSS CONNECTOR (FACTORY-MOUNTED)
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
25
71 75
72 76
73 77
74 78
COMA
COMA
COMB
COMB
24V~
24V~
24V~0
24V~0
ACTUATOR 1 ACTUATOR 2 ACTUATOR 3
Fig. 24. Terminal assignment and internal connections
Features - Cross-Connecter - 1 red LED (opening) and 1 green LED (closing) per
floating output - Manual override potentiometers (Auto, 0%...100%; LED
flashes in override mode) - Feedback on manual override signal - Configurable safety position for outputs in case of
communication problems (remain, 0%, 50%, 100%) - Permissible Load per Floating Output Module (total)
Max. load: 19…250 VAC: 12 A 1…29 VDC: 12 A resistive, 3 A inductive
- Permissible load per normally-open contact: Max. load:
19…250 VAC: 4 A resistive or inductive 1…29 VDC: 4 A resistive, 1 A inductive
Min. load: P > 50 mW - Permissible load per normally-closed contact:
Max. load: 19…250 VAC: 2 A resistive, 1 A inductive 1…29 VDC: 2 A resistive, 1 A inductive
Min. load: P > 50 mW
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 19
FLOATING ACTUAOR WITH 230VAC(REQUIRES TWO RELAYS)1: 2: 3: N
NO
NC
COM
11
12
13
NO
NC
COM
21
22
23
31
32
33
NO
NC
COM
41
42
43
NO
NC
COM
51
52
53
NO
NC
COM
61
62
63
NO
NC
COM
CON CON CON CON CON CON14 24 34 44 54 64
XF...
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
74 24V~0
73
72
71
24V~
COMB
COMA
XFR825A FLOATING OUTPUT MODULEF1
25
SHIELDINTERNALLYCONNECTEDTO DIN RAIL
POWER SUPPLY230 VAC
NL 23 1
M
F3
OPTIONAL AUX. TERMINAL PACKAGE XS814
B1 B2 B3 B4 B5 B6 B7A1 A2 A3 A4 A5 A6 A7
CROSS CONNECTOR XS815 (FACTORY-MOUNTED)
SELECTED INTERNAL CONNECTIONS
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F32
DASHED LINES
THIN LINES
F3
F1
LEGEND:
THICK LINES
MAX. 12 A
MAX. 4 A
Fig. 25. XFR825A Panel Bus FO Module, wiring example: Floating actuator
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 20
Mixed I/O Modules XF830A XFU830A CPO-IO830
Fig. 26. XF830A, XFU830A, and CPO-IO830 Mixed Panel
Bus Modules The mixed Honeywell Panel Bus I/O modules, with 8 analog inputs, 8 analog outputs, 12 binary inputs, and 6 relay outputs, are available in the following versions: XF830A mixed Honeywell Panel Bus I/O module, with
push-in terminals; XFU830A mixed Honeywell Panel Bus I/O module, with
screw terminals; CPO-IO830 mixed Honeywell Panel Bus I/O module, with
push-in terminals. Each features an integrated terminal socket and electronic module. The XF830A can be equipped with up to two rows of (XS830 and/or XS831) auxiliary terminal blocks on the top and/or bottom. The XFU830A and CPO-IO830 can be equipped with up to two rows of (XS830 and/or XS831) auxiliary terminal blocks on the top, only.
AI5
AI1 AI2 AI3 AI4 41
G1 G2
42
17
13 14 15 16
18 19 20
AI6 AI7 AI8 AO525
21 22 23 24
26 27 28 35
29 30 31 32 33 34
36 37 38 39 40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
1 2 3 4 5 6
25 26 27 28 35 36 37 38 39 40
1 21 22 23 24 29 30 31 32 33 342 3 4 5 6 13 14 15 16 41 42
7 8 9 10 11 12 17 18 19 20
Analog Inputs Analog OutputsGND
DO
Honeywell
!
XF830A12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T500706AX0001-XFU830A
Made in Germany0532
8
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B91
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B92
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B93
24V Relays
2
1 0
F
E
D C B
9 8
7
6 5 4 3
A
40External
24V for relay 1...5
24V
J1 J2 J3 J4 J5
71 75
76
77
78
COM a
COM b
24V~
24V~0
COM a
COM b
24V~
24V~0
72
73
74 S2
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B84
B7
B1 B2 B3 B4 B5 B6
B8 B9 B10 B11 B12
DI
Binary Inputs
Install. Instr.EN1B-0375GE51
7
1 2 3 4 5 6
8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Fig. 27. XF830A mixed Panel Bus I/O module, shown with
4 optional aux. terminal blocks (top view)
7 25 26 27 28 35 36 37 38 39 40
1 21 22 23 24 29 30 31 32 33 34
8
2
9
3
10
4
11
5
12
6
17
13
18
14
19
15
20
16 41 42
XFU830A12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T500706AX0001-XFU830A
Made in Germany0532
8
2
1 0
F E
D C B
9 8
7
6 5 4 3
A
40External
24V for relay 1...5
24V
J1 J2 J3 J4 J5
71 75
76
77
78
COM a
COM b
24V~
24V~0
COM a
COM b
24V~
24V~0
72
73
74 S2
AI5
AI1 AI2 AI3 AI4 41
G1 G2
42
17
13 14 15 16
18 19 20
AI6 AI7 AI8 AO525
21 22 23 24
26 27 28 35
29 30 31 32 33 34
36 37 38 39 40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
1 2 3 4 5 6
Analog Inputs Analog OutputsGND
DO
Honeywell
!
24V Relays
B7
B1 B2 B3 B4 B5 B6
B8 B9 B10 B11 B12
DI
Binary Inputs
Install. Instr.EN1B-0375GE51
7
1 2 3 4 5 6
8 9 10 11 12
1 2 3 4 5 6 7 8 9 10 11 12
Fig. 28. XFU830A mixed Panel Bus I/O module, shown
without optional aux. terminal blocks (top view)
1 2 3 4 5 6 7 8 9 10 11 12
B1 B2 B3 B4 B5 B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
DI
Binary Inputs
G1 G2
41 42
GND Analog Outputs
AI2 AI3 AI4
14 15 16
AI1
AI5 AI6 AI7 AI8
17 18 19 20
13
Analog Inputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
DO
24V Relays
NO1 NO2 NO3 NO4 NO5 NO6
IN1 IN2 IN3 IN4 IN5 IN6
35
29 30 31 32 33 34
36 37 38 39 40
1 2 3 4 5 6
HoneywellComfortPoint OpenTM
Install. Instr.MU1B-0463GE51
!
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B91
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B93
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B92
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B84
Fig. 29. CPO-IO830 mixed Panel Bus I/O module, shown
with 4 optional aux. terminal blocks (top view)
Features - 1 yellow LED per output - Configurable safety position for outputs in case of
communications problems (remain in last position, OFF, ON)
WARNING
Risk of electric shock or equipment damage! It is not permitted to wire the relays of the mixed Panel Bus I/O modules for anything other than low voltage.
Permissible Loads Table 7. Permissible loads of mixed Panel Bus I/O
modules
max. load min. load
per module (total for all relay contacts)
19…29 VAC, 1…29 VDC 3 A resistive or inductive, cos φ ≥ 0.6, no capacitive load, protected by fuse F4
–
per nor-mally open contact
19…29 VAC, 1…29 VDC 0.5 A resistive or inductive, cos φ ≥ 0.6, no capacitive load
>50 mW, 0.05 A res./ind.,cos φ ≥ 0.6
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 21
199.9 kOHMVi
AI
GND
Fig. 30. Analog input high impedance (input circuit for
voltage input for active sensors)
199.9 kOHM(8.9 VDC IFCONNECTIONINTERRUPTED)
Vi
AI
GND
24.9 kOHM
10 VDC
Fig. 31. Analog input impedance setpoint (input circuit
for NTC10kΩ, NTC20kΩ, wall module setpoint)
FASTTOTALIZER
DRY CONTACT16 ... 22 VDC = OPEN 0 ... 2 VDC = CLOSED
150 kOHM
10 kOHM
18 VDC (NOT STABILIZED)
+V
BI
GND
Fig. 32. Configuration of a binary input as a fast totalizer
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 22
XF830A Mixed I/O Module
2 21
DRYCONTACT1: GND2: SIGNAL
DRYCONTACT1: GND2: SIGNAL
21 1
ACTIVESENSOR1: GND (24V 0)2: 24V POWER3: 0...10 VDC
~~
23 31
0...10 VDC 0...10 VDCM
1 2
M
1 2
XS830 OPT. AUX. TERM. MODULE XS830
F1
F4
1 2
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
41 42
B10 B11 B12 AI5
AI1
AI6
AI2
AI7
AI3
AI8
AI4
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
IN1
NO1
IN2
NO2
IN3
NO3
IN4
NO4
IN5
NO5
IN6
NO6
B7 B8 B9
7 8 9 10 11 12 17
13
18
14
19
15
20
16
25
21
26
22
27
23
28
24
35
29
36
30
37
31
38
32
39
33
40
34
B1 B2 B3 B4 B5 B6
1 2 3 4 5 6
G1 G2
A7 A7B7 B7A8 A8B8 B8A9 A9B9 B9A1 A1B1 B1A2 A2B2 B2A3 A3B3 B3A4 A4B4 B4A5 A5B5 B5A6 A6B6 B6
TOTALIZER1: GND2: SIGNAL
NTC20kOHMSENSOR1: GND2: SIGNAL
24V
1: GND (24V 0)2: 24V POWER3: 0...10 VDC
~ DRIVE with0...10V SIGNAL
~~
DCA1: 24V 02: 24V
~~
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F2, F42
THIN LINES
F4
F1 F2LEGEND:
THICK LINES
MAX. 3 A
MAX. 4 A MAX. 12 A
F2
(GND 24 VAC)
BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS
(24 VAC)(GND)
Fig. 33. XF830A mixed Panel Bus I/O Module, wiring example: Actuators
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 23
ACTIVESENSOR1: GND (24V 0)2: 24V POWER3: 4...20 mA
~~
CPO-IO830 Mixed I/O Module
74 24V~0
73
72
71
24V~
COMB
COMA
7824V~0
77
76
75
24V~
COMB
COMA
A7 A7B7 B7A8 A8B8 B8A9 A9B9 B9A1 A1B1 B1A2 A2B2 B2A3 A3B3 B3A4 A4B4 B4A5 A5B5 B5A6 A6B6 B6
A4 A8B4 B8G1 G2A1 A5B1 B5A2 A6B2 B6A3 A7B3 B7
OPT. AUX. TERM. MODULE XS830 OPT. AUX. TERM. MODULE XS830
OPT. AUX. TERM. MODULE XS831
F2
F1
4...20 mA
1 2 3
MIN. 0.75 mm 2
MIN. 1.5 mm - or less, as per F22
THIN LINES
F1 F2LEGEND:
THICK LINES
MAX. 4 A MAX. 12 A
BINARY INPUTS ANALOG INPUTS ANALOG OUTPUTS 24V RELAYS
41 42
B10 B11 B12 AI5
AI1
AI6
AI2
AI7
AI3
AI8
AI4
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
IN1
NO1
IN2
NO2
IN3
NO3
IN4
NO4
IN5
NO5
IN6
NO6
B7 B8 B9
7 8 9 10 11 12 17
13
18
14
19
15
20
16
25
21
26
22
27
23
28
24
35
29
36
30
37
31
38
32
39
33
40
34
B1 B2 B3 B4 B5 B6
1 2 3 4 5 6
G1 G2
Fig. 34. CPO-IO830 Connection example (for current inputs)
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 24
Approvals, Certifications, and Standards Approvals and Certifications
CE-approved Conforms to EN 60730-1 and EN 60730-2-9 Investigated according to United States Standard
UL916 (USL-listed) as well as according to Canadian National Standard(s) C22.2 (CNL-listed)
Classification according to EN60730-1 Environmental conditions: For use in home (residential,
commercial, and light-industrial) environments
Pollution degree: Class 2 Protection against shock: Class II Software class: Class A Overvoltage category: II
Classification according to EN60529 (Degree of Protection Provided by Enclosures) Classification: IP20
Ambient Environmental Limits Operating temperature: 0 … +50 °C at 5…93% r.H. Storage temperature: -20 … +70 °C at 5…93% r.H. Humidity: 5 … 93% r.h. non-condensing
Current Requirements and Heat Dissipation The Panel Bus I/O Modules are equipped with highly-efficient switching power supplies which provide for relatively uniform power consumption over a wide range of supply voltages (see Table 8). The specific heat dissipation inside the modules amounts to less than 2 W for all models. Table 8. Current requirements of Panel Bus I/O modules
devices powered supply voltage
24 VAC 24 VDC
XF821A 130 mA 80 mA
XF822A, XFR822A 150 mA 90 mA
XF823A 180 mA 130 mA
XF824A, XFR824A, XFR825A 140 mA 80 mA
XF830A, XFU830A, CPO-IO830 200 mA 95 mA
Mechanical Housing Dimensions (H x W x D) The pluggable Panel Bus I/O Modules (mounted on Terminal Sockets) all have the dimensions: 110 X 90 X 93 mm (see also Fig. 35 on page 25). The XF830A and XFU830A mixed Panel Bus I/O Modules have the dimensions: 216 X 110 X 93 mm (see also Fig. 36 on page 25). The CPO-IO830 mixed Panel Bus I/O Module has the dimensions: 216 X 110 X 61 mm (see also Fig. 37 on page 26).
Housing Material Plastic, flame-retardant
Mounting Methods DIN-rail mounting (e.g., in control cabinet).
Calculated Lifetime of Weakest Components MTBF 13.7 years (under typical operating conditions)
PANEL BUS I/O MODULES – PRODUCT DATA
EN0B-0701GE51 R1219 25
Dimensions
LOCK
89.5 94.1
51.5
45
83 67.5
14
110
XS814 Aux. Terminal Package (optional)
2830.6
SWIVEL LABEL HOLDER
38
SCREW-TYPETERMINALS
REMOVABLEELECTRONIC
MODULE
TERMINALSOCKET
Fig. 35. Pluggable Honeywell I/O Modules (example with manual overrides), incl. terminal socket, dimensions (in mm)
92.5
51.5
45
69
100
CLE
AR
AN
CE
15
110
28
SWIVEL LABEL HOLDER
B7
B1 B2 B3 B4 B5 B6
7
1 2 3 4 5 6
8 9 10 11 12
B8 B9 B10 B11 B12 AI5
AI1 AI2 AI3 AI4 41
G1 G2
42
17
13 14 15 16
18 19 20
AI6 AI7 AI8 AO525
21 22 23 24
26 27 28 35
29 30 31 32 33 34
36 37 38 39 40
AO1 AO2 AO3 AO4 NO1 NO2 NO3 NO4 NO5 NO6
AO6 AO7 AO8 IN1 IN2 IN3 IN4 IN5 IN6
1 12 23 34 45 56 67
25 26 27 28 35 36 37 38 39 40
1 21 22 23 24 29 30 31 32 33 342
8 9
3
10
4
11
5
12
6 13 14 15 16 41 42
7 8 9 10 11 12 17 18 19 20
DI
Binary Inputs Analog Inputs Analog Outputs 24V RelaysGND
S2
DO
Honeywell
!
Install. Instr.EN1B-0375GE51
XF830A12 BI / 8 AI / 8 AO / 6 RO
24V, 15VA, T500706AX0001-XFU830A
Made in Germany0532
8
2
1 0
F
E
D C B
9 8
7
6 5 4 3
A
40External
24V for relay 1...5
24V
J1 J2 J3 J4 J5
71 75
76
77
78
COM a
COM b
24V~
24V~0
COM a
COM b
24V~
24V~0
72
73
74
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9A
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9B
A1 A2 A3 A4 A5 A6 A7 A8 A9 B1 B2 B3 B4 B5 B6 B7 B8 B9C
216
38
SCREW-TYPE TERMINALS(XFU830A)
A1 B1 A2 B2 A3 B3 A4 B4 G1 G2A5 B5 A6 B6 A7 B7 A8 B8D
D = XS831 Aux. Terminal Package (optional)A, B, and C = XS830 Aux. Terminal Packages (optional)
Fig. 36. XF830A (shown) and XFU830A mixed Honeywell I/O Module (example with 4 auxiliary terminal packages),
dimensions (in mm)
PANEL BUS I/O MODULES – PRODUCT DATA
Manufactured for and on behalf of the Connected Building Division of Honeywell Products and Solutions SARL, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative: Home and Building Technologies Honeywell GmbH Böblinger Strasse 17 71101 Schönaich, Germany Phone +49 (0) 7031 637 01 Fax +49 (0) 7031 637 740 http://ecc.emea.honeywell.com EN0B-0701GE51 R1219 Subject to change without notice
1 2 3 4 5 6 7 8 9 10 11 12
B1 B2 B3 B4 B5 B6
B12
12
6
B11
11
5
B10
10
4
B9
9
3
B8
8
2
B7
7
1
DI
Binary Inputs
G1 G2
41 42
GND Analog Outputs
AI2 AI3 AI4
14 15 16
AI1
AI5 AI6 AI7 AI8
17 18 19 20
13
Analog Inputs
AO5
AO1
AO6
AO2
AO7
AO3
AO8
AO4
21
25 26 27 28
22 23 24
DO
24V Relays
NO1 NO2 NO3 NO4 NO5 NO6
IN1 IN2 IN3 IN4 IN5 IN6
35
29 30 31 32 33 34
36 37 38 39 40
1 2 3 4 5 6
HoneywellComfortPoint OpenTM
Install. Instr.MU1B-0463GE51
!
216 54.444
61.1
110
Fig. 37. CPO-IO830 Mixed Honeywell I/O Modules, dimensions (in mm)