parameter list deif

80
MULTI-LINE 2 PARAMETER LIST PARAMETER LIST Alarm list Parameter list Document no.: 41893400664A SW version 3.53.x or later Advanced Protection Unit, APU 200

Upload: anonymous-hj273cm

Post on 07-Nov-2015

470 views

Category:

Documents


209 download

DESCRIPTION

Parameter List DEIF

TRANSCRIPT

  • MULTI-LINE 2PARAMETER LIST

    PARAMETER LIST

    Alarm list Parameter list

    Document no.: 41893400664A SW version 3.53.x or later

    Advanced Protection Unit, APU 200

  • APU 200 Parameter List

    DEIF A/S Page 2 of 80

    Table of contents

    1. ABOUT THIS DOCUMENT .................................................................................................... 4

    GENERAL PURPOSE ...................................................................................................................... 4 INTENDED USERS.......................................................................................................................... 4 CONTENTS/OVERALL STRUCTURE .................................................................................................. 4

    2. WARNINGS AND LEGAL INFORMATION ........................................................................... 5

    LEGAL INFORMATION AND RESPONSIBILITY ..................................................................................... 5 ELECTROSTATIC DISCHARGE AWARENESS ..................................................................................... 5 SAFETY ISSUES ............................................................................................................................ 5 DEFINITIONS ................................................................................................................................ 5

    3. PARAMETER DESCRIPTIONS ............................................................................................. 6

    4. ALARM LIST .......................................................................................................................... 7

    ALARM TABLE OVERVIEW .............................................................................................................. 8 REVERSE POWER AND OVERCURRENT PROTECTION ....................................................................... 9 VOLTAGE PROTECTIONS ............................................................................................................. 12 FREQUENCY PROTECTIONS ......................................................................................................... 14 LV VOLTAGE PROTECTIONS ......................................................................................................... 16 LV FREQUENCY PROTECTIONS .................................................................................................... 19 MAINS FAILURE PROTECTIONS ..................................................................................................... 21 OVERLOAD PROTECTIONS ........................................................................................................... 23 CURRENT UNBALANCE PROTECTION ............................................................................................ 25 VOLTAGE UNBALANCE PROTECTION ............................................................................................. 25 REACTIVE POWER IMPORT PROTECTION ...................................................................................... 26 REACTIVE POWER EXPORT PROTECTION ...................................................................................... 26 NEGATIVE SEQUENCE ................................................................................................................. 27 ZERO SEQUENCE ........................................................................................................................ 28 DIRECTIONAL OVERCURRENT PROTECTION .................................................................................. 29 LV UNBALANCE VOLTAGE ............................................................................................................ 30 TIME-DEPENDENT UNDERVOLTAGE .............................................................................................. 30 NEUTRAL LINE INVERSE OVERCURRENT ....................................................................................... 33 EARTH CURRENT INVERSE .......................................................................................................... 33 POWER-DEPENDENT REACTIVE POWER IMPORT ........................................................................... 34 POWER-DEPENDENT REACTIVE POWER EXPORT ........................................................................... 34 UNDERVOLTAGE AND REACTIVE POWER LOW ............................................................................... 35 BTB EXTERNALLY TRIPPED ......................................................................................................... 36 SYNCHRONISATION AND BREAKER ALARMS .................................................................................. 36 DIGITAL INPUT 77-89 SETUP ....................................................................................................... 38 DIGITAL INPUT 46-48 SETUP (MULTI-FUNCTIONAL INPUTS) ............................................................ 38 EMERGENCY STOP ..................................................................................................................... 39 MULTI-FUNCTIONAL ANALOGUE INPUT SETUP ............................................................................... 40 AUX. SUPPLY SETUP ................................................................................................................... 51 INTERTRIP WIRE BREAK AND INTERNAL COMMUNICATION ALARMS .................................................. 51 FAN FAILURE .............................................................................................................................. 52 EXTERNAL COMMUNICATION ERROR ............................................................................................ 53 POWER MANAGEMENT COMMUNICATION ERROR ........................................................................... 54 EXTERNAL IO COMMUNICATION ERROR ........................................................................................ 54 EXTERNAL I/O ALARM SETUP ....................................................................................................... 55

    5. PARAMETER LIST .............................................................................................................. 57

    PARAMETER TABLE OVERVIEW .................................................................................................... 57 SYNCHRONISATION ..................................................................................................................... 58 RELAY OUTPUT SETUP ................................................................................................................ 58

  • APU 200 Parameter List

    DEIF A/S Page 3 of 80

    TRANSDUCER OUTPUTS .............................................................................................................. 60 SYSTEM ..................................................................................................................................... 64 GENERAL SETUP ........................................................................................................................ 64 COUNTERS AND TIMERS .............................................................................................................. 66 ALARM HORN .............................................................................................................................. 67 SUMMER/WINTER TIME ................................................................................................................ 67 FAN LOGIC ................................................................................................................................. 67 FAN LOGIC ................................................................................................................................. 68 ALARM JUMP .............................................................................................................................. 68 EXTERNAL COMMUNICATION ........................................................................................................ 68 POWER MANAGEMENT INTERNAL COMMUNICATION ....................................................................... 69 CAN A PROTOCOL ..................................................................................................................... 69 CAN B PROTOCOL ..................................................................................................................... 69 CAN C PROTOCOL ..................................................................................................................... 69 EXTERNAL I/O COMMUNICATION SETUP........................................................................................ 70 POWER MANAGEMENT SETUP ...................................................................................................... 71 ADVANCED USER MENUS ............................................................................................................. 73 TOOL MENUS .............................................................................................................................. 75 COMMAND TIMERS ...................................................................................................................... 77 PASSWORDS .............................................................................................................................. 79 MULTI-INPUT SELECTIONS ........................................................................................................... 80

  • APU 200 Parameter List

    DEIF A/S Page 4 of 80

    1. About this document This chapter includes general user information about this document concerning the general purpose, the intended users and the overall contents and structure.

    General purpose This document is the complete parameter list for DEIFs APU 200. The document includes all parameters used in the APU 200 include, and it includes all options.

    Intended users The document is mainly intended for the person responsible for the unit parameter setup or programming. In most cases, this would be a panel builder designer. Naturally, other users might also find useful information here.

    Contents/overall structure The document is divided into chapters, and in order to make the structure of the document simple and easy to use, each chapter will begin from the top of a new page. The following will outline the contents of each of the chapters.

    About this document This first chapter includes general information about this document. It deals with the general purpose and the intended users of the parameter list and Modbus addresses. Furthermore, it outlines the overall contents and structure of the document.

    Warnings and legal information The second chapter includes information about general legal issues and safety precautions relevant in the handling of DEIF products. Furthermore, this chapter will introduce note and warning symbols, which will be used throughout the document.

    Alarm list This chapter includes a complete standard alarm list for setup. Therefore, this chapter is to be used for reference, when information about specific alarms is needed.

    Parameter list This chapter includes a complete standard parameter list for setup. Therefore, this chapter is to be used for reference, when information about specific parameters is needed.

  • APU 200 Parameter List

    DEIF A/S Page 5 of 80

    2. Warnings and legal information This chapter includes important information about general legal issues relevant in the handling of DEIF products. Furthermore, some overall safety precautions will be introduced and recommended. Finally, the highlighted notes and warnings, which will be used throughout this handbook, are presented.

    Legal information and responsibility DEIF takes no responsibility for installation or operation of the device connected to the APU 200. If there is any doubt about how to install or operate the device controlled by the unit, the company responsible for the installation or the operation of the set must be contacted.

    Electrostatic discharge awareness Sufficient care must be taken to protect the terminals against static discharges during the installation. Once the unit is installed and connected, these precautions are no longer necessary.

    Safety issues Installing the unit implies work with dangerous currents and voltages. Therefore, the installation should only be carried out by authorised personnel who understand the risks involved in working with live electrical equipment.

    Definitions Throughout this document, a number of notes and warnings will be presented. To ensure that these are noticed, they will be highlighted in order to separate them from the general text.

    Notes

    Warnings

    The notes provide general information which will be helpful for the reader to bear in mind.

    The warnings indicate a potentially dangerous situation which could result in death, personal injury or damaged equipment, if certain guidelines are not followed.

    Be aware of the hazardous live currents and voltages. Do not touch any AC measurement inputs as this could lead to injury or death.

    The units are not to be opened by unauthorised personnel. If opened anyway, the warranty will be lost.

  • APU 200 Parameter List

    DEIF A/S Page 6 of 80

    3. Parameter descriptions Each parameter description is structured according to the same principles. Under the parameter title heading, the detailed parameter descriptions are illustrated and presented. First, a table indicating the parameter facts related to the individual parameter title is presented:

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1000 HV reverse power 1

    1001 HV P> 1 Setpoint -200...0 % -5,0 % Designers Reference Handbook

    The alarm and fail class are activated when the reverse power has been continuously above the programmed value during the programmed delay.

    1002 HV P> 1 Delay 0.1...100 s 10,0 s

    1003 HV P> 1 Relay output A Not used Used Not used

    1004 HV P> 1 Relay output B Not used Used Not used

    1005 HV P> 1 Enable OFF ON OFF

    1006 HV P> 1 Fail class F1F3 Trip BTB (F3)

    NO: This column indicates the menu number in the display Setting: Those two columns indicate the changeable setting in the display Min/Max: This column indicates the minimum/maximum setpoint available for this setting Factory setting: The fifth column indicates the default setpoint of the unit from the factory Notes: Here the actual setting for the unit can be added Ref. Reference of where more detailed information regarding this parameter can be

    found Description: When it is necessary, additional information will be supplied after the table in

    order to make the individual parameter descriptions as informative as possible.

    Due to the character of the parameters, small differences may exist between the individual tables.

  • APU 200 Parameter List

    DEIF A/S Page 7 of 80

    4. Alarm list This chapter includes a complete alarm list, including all possible options. Therefore, this chapter is to be used for reference when specific information about the individual parameters is needed for the unit setup. An overview list can be seen on the next pages. The table consists of the following possible adjustments: Setpoint: The alarm setpoint is adjusted in the setpoint menu. The setting is a percentage

    of the nominal values. Delay: The timer setting is the time that must expire from the alarm level is reached

    until the alarm occurs. Relay output A: a relay can be activated by output A. Relay output B: a relay can be activated by output B. Enable: The alarm can be activated or deactivated. ON means always activated, RUN

    means that the alarm has run status. This means it is activated when the running signal is present.

    Fail class: When the alarm occurs, the unit will react depending on the selected fail class. Fail classes are:

    Fail class APU 200 F1 Block F2 Warning F3 Trip BTB

    It is also possible to configure the parameters by using the PC utility software. It will be possible to make the same configurations as described above. By using the PC utility software, extra functionality is available. For all the protections, it is possible to make an automatic acknowledgement of the alarm.

    Due to the character of the parameters, the individual tables may vary slightly.

  • APU 200 Parameter List

    DEIF A/S Page 8 of 80

    Alarm table overview Protection Protection- continuing 1000 HV -P> 1 1770 HV P depended Q Export 1-3 1010 HV -P> 2 1780 HV P depended Q Export 4-6 1030 HV I> 1 1790 HV P depended Q Export, alarm 1040 HV I> 2 1960 U and Q < 1 1050 HV Ie>> 1970 U and Q < 2 1060 HV In>> 1980 BTB external trip 1080 HV I> inverse Setup 1100 HV Iv > 1-6 setup Input/output 1110 HV Iv > Alarm - Binary input setup 1130 HV I>> 1 3000 Dig. input 77 1140 HV I>> 2 3010 Dig. input 78 1150 HV U> 1 3020 Dig. input 79 1160 HV U> 2 3030 Dig. input 80 1170 HV U< 1 3040 Dig. input 81 1180 HV U< 2 3050 Dig. input 82 1190 HV U< 3 3060 Dig. input 83 1200 HV voltage trip 3070 Dig. input 84 1210 HV f> 1 3080 Dig. input 85 1220 HV f> 2 3090 Dig. input 86 1230 HV f> 3 3100 Dig. input 87 1240 HV f< 1 3110 Dig. input 88 1250 HV f< 2 3120 Dig. input 89 1260 HV f< 3 3410 Dig. input 47 1270 LV U> 1 3420 Dig. input 48 1280 LV U> 2 3430 Dig. input 49 1290 LV U> 3 3490 Emergency stop 1300 LV U< 1 1310 LV U< 2 Control 1320 LV U< 3 - Synchronisation 1330 LV U< 4 2120 Sync window 1340 LV voltage trip 2130 BTB sync failure 1350 LV f> 1 2150 Phase seq error 1360 LV f> 2 2160 BTB open fail 1370 LV f> 3 2170 BTB close fail 1380 LV f< 1 2420 BTB pos. fail 1390 LV f< 2 1400 LV f< 3 Multi-functional input setup 1410 LV f< 4 4160 Pt100 46.1 1450 HV P> 1 4170 Pt100 46.2 1460 HV P> 2 4240 W. fail 46 1470 HV P> 3 4290 Pt100 47.1 1480 HV P> 4 4300 Pt100 47.2 1490 HV P> 5 4370 W. fail 47 1500 HV unbalance curr. 4420 Pt100 48.1 1510 HV unbalance volt. 4430 Pt100 48.2 1520 HV Q> 4500 W. fail 48 1530 HV Q> 4960 U< aux. term. 1 1620 LV unbalance U 4970 U> aux. term. 1 1630 Ut< SP 1-3 1 1640 Ut< SP 4-6 1 System 1650 Ut< Activate 1 - General setup 1660 Ut< 1 6270 Intertrip wire break 1670 Ut< SP 1-3 2 6590 Fan A failure 1680 Ut< SP 4-6 2 6600 Fan B failure 1690 Ut< Activate 2 6610 Fan C failure 1700 Ut< 2 6620 Fan D failure 1720 HV In> Inverse 1730 HV Ie>> inverse System 1740 HV P depended Q import 1-3 - Communication 1750 HV P depended Q import 4-6 7530 Int. comm. ID 1760 HV P depended Q import, alarm 7870 Any BTB missing

  • APU 200 Parameter List

    DEIF A/S Page 9 of 80

    Reverse power and overcurrent protection

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1000 HV reverse power 1

    1001 HV P> 1 Setpoint -200...0 % -5,0 % Designers Reference Handbook

    The alarm and fail class are activated when the reverse power has been continuously above the programmed value during the programmed delay.

    1002 HV P> 1 Delay 0.1...100 s 10,0 s

    1003 HV P> 1 Relay output A Not used Used Not used

    1004 HV P> 1 Relay output B Not used Used Not used

    1005 HV P> 1 Enable OFF ON OFF

    1006 HV P> 1 Fail class F1F3 Trip BTB (F3)

    1010 HV reverse power 2

    1011 HV P> 2 Setpoint -200...0 % -5,0 % Designers Reference Handbook

    The alarm and fail class are activated when the reverse power has been continuously above the programmed value during the programmed delay.

    1012 HV P> 2 Delay 0.1...100 s 10 s

    1013 HV P> 2 Relay output A Not used Used Not used

    1014 HV P> 2 Relay output B Not used Used Not used

    1015 HV P> 2 Enable OFF ON OFF

    1016 HV P> 2 Fail class F1F3 Trip BTB (F3)

    1030 HV overcurrent 1

    1031 HV I> 1 Setpoint 50...200 % 100,0 % Designers Reference Handbook

    The alarm and fail class are activated when the current has been continuously above the programmed value during the programmed delay.

    1032 HV I> 1 Delay 0,1...3200 s 0.5 s

    1033 HV I> 1 Relay output A Not used Used 23

    1034 HV I> 1 Relay output B Not used Used Not used

    1035 HV I> 1 Enable OFF ON ON

    1036 HV I> 1 Fail class F1F3 Trip BTB (F3)

    1040 HV overcurrent 2

    1041 HV I> 2 Setpoint 50...200 % 120.0 % Designers Reference Handbook

    The alarm and fail class are activated when the current has been continuously above the programmed value during the programmed delay.

    1042 HV I> 2 Delay 0.1...3200 s 5 s

    1043 HV I> 2 Relay output A Not used Used Not used

    1044 HV I> 2 Relay output B Not used Used Not used

    1045 HV I> 2 Enable OFF ON OFF

    1046 HV I> 2 Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 10 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1050 HV Fast overcurrent, Earth

    1051 HV Ie>> Setpoint 0...500 % 115,0 % Designers Reference Handbook

    The alarm and fail class are activated when the current has been continuously above the programmed value during the programmed delay.

    1052 HV Ie>> Delay 0...320 s 10,0 s

    1053 HV Ie>> Relay output A Not used Used Not used

    1054 HV Ie>> Relay output B Not used Used Not used

    1055 HV Ie>> Enable OFF ON OFF

    1056 HV Ie>> Fail class F1F3 Trip BTB (F3)

    1060 HV Fast overcurrent, Neutral

    1061 HV In>> Setpoint 0...500 % 120,0 % Designers Reference Handbook

    The alarm and fail class are activated when the current has been continuously above the programmed value during the programmed delay.

    1062 HV In>> Delay 0...320 s 5,0 s

    1063 HV In>> Relay output A Not used Used Not used

    1064 HV In>> Relay output B Not used Used Not used

    1065 HV In>> Enable OFF ON OFF

    1066 HV In>> Fail class F1F3 Trip BTB (F3)

    1080 HV inverse time overcurrent curve setting

    1081 HV I> inv. type Type IEC Inverse Custom IEC Inverse

    Option C2 Available curve types: - IEC Inverse - IEC Very inverse - IEC Extremely inv. - IEEE Moderately inv. - IEEE Very inverse - IEEE Extremely inv. - Custom

    1082 HV I> inv. limit Setpoint 50.0% 200.0% 110.0%

    1083 HV I> inv. TMS Setpoint 0.1 100.0 1.0

    1084 HV I> inv. k Setpoint 0.001 s 32.000 s 0.140 s

    1085 HV I> inv. c Setpoint 0.000 s 32.000 s 0.000 s

    1086 HV I> inv. a Setpoint 0.001 32.000 0.020

    1087 G I> inv. Relay output A

    Not used Option dependent

    Not used

    1088 G I> inv. Enable OFF ON OFF

    1089 G I> inv. Fail class F1F5 Trip GB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 11 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1100 Voltage dependent overcurrent curve setting

    1101 HV Iv > (50%) Setpoint I1 50...200 % 110,0 % @50% nom. voltage

    Designers Reference Handbook

    Settings relate to nominal current. The condition has to be true i.e. I1 (100%) Setpoint I6 50...200 % 200,0 % @100% nom. voltage

    1110 Voltage dependent overcurrent alarm

    1111 HV Iv > Timer 0.1...10 s 0,5,0 s Designers Reference Handbook

    The alarm and fail class are activated when the overcurrent has been continuously above the programmed value during the programmed delay. Values are set in parameters 1101-1106.

    1112 HV Iv > Relay output A Not used Used Not used

    1113 HV Iv > Relay output B Not used Used Not used

    1114 HV Iv > Activate OFF ON OFF

    1115 HV Iv > Fail class F1F3 Trip BTB (F3)

    1130 HV fast overcurrent 1

    1131 HV I>> 1 Setpoint 150...500 % 150.0 % Designers Reference Handbook

    The alarm settings relate to the nominal current setting. The alarm and fail class are activated when the current has been continuously above the programmed value during the programmed delay.

    1132 HV I>> 1 Delay 0...100 s 2.0 s

    1133 HV I>> 1 Relay output A Not used Used 23

    1134 HV I>> 1 Relay B Not used Not used

    1135 HV I>> 1 Enable OFF ON ON

    1136 HV I>> 1 Fail class F1F3 Trip BTB (F3)

    1140 HV fast overcurrent 2

    1141 HV I>> 2 Setpoint 50...500 % 200.0 % Designers Reference Handbook

    The alarm and fail class are activated when the current has been continuously above the programmed value during the programmed delay.

    1142 HV I>> 2 Delay 0...100 s 0.5 s

    1143 HV I>> 2 Relay A Not used Not used

    1144 HV I>> 2 Relay B Not used Not used

    1145 HV I>> 2 Enable OFF ON OFF

    1146 HV I>> 2 Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 12 of 80

    Voltage protections

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1150 HV overvoltage 1

    1151 HV U> 1 Setpoint 100... 120 % 103,0 % Designers Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously above the programmed value during the programmed delay.

    1152 HV U> 1 Timer 0.1... 100 s 10,0 s

    1153 HV U> 1 Relay output A Not used Used Not used

    1154 HV U> 1 Relay output B Not used Used Not used

    1155 HV U> 1 Enable OFF ON OFF

    1156 HV U> 1 Fail class F1F3 Warning (F2)

    1160 HV overvoltage 2

    1161 HV U> 2 Setpoint 100... 120 % 105,0 % Designers Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously above the programmed value during the programmed delay.

    1162 HV U> 2 Timer 0.1... 100s 5,0 s

    1163 HV U> 2 Relay output A Not used Used Not used

    1164 HV U> 2 Relay output B Not used Used Not used

    1165 HV U> 2 Enable OFF ON OFF

    1166 HV U> 2 Fail class F1F3 Warning (F2)

    1170 HV undervoltage 1

    1171 HV U< 1 Setpoint 40... 100% 97,0 % Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously under the programmed value during the programmed delay.

    1172 HV U< 1 Timer 0.1... 100 s 10,0 s

    1173 HV U< 1 Relay output A Not used Used Not used

    1174 HV U< 1 Relay output B Not used Used Not used

    1175 HV U< 1 Enable OFF ON OFF

    1176 HV U< 1 Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 13 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1180 HV undervoltage 2

    1181 HV U< 2 Setpoint 40... 100 % 95,0 % Designers Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously under the programmed value during the programmed delay.

    1182 HV U< 2 Timer 0.1... 100 s 5,0 s

    1183 HV U< 2 Relay output A Not used Used Not used

    1184 HV U< 2 Relay output B Not used Used Not used

    1185 HV U< 2 Enable OFF ON OFF

    1186 HV U< 2 Fail class F1F3 Warning (F2)

    1190 HV undervoltage 3

    1191 HV U< 3 Setpoint 40... 100 % 95,0 % Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously under the programmed value during the programmed delay.

    1192 HV U< 3 Timer 0.1... 100 s 5,0 s

    1193 HV U< 3 Relay output A Not used Used Not used

    1194 HV U< 3 Relay output B Not used Used Not used

    1195 HV U< 3 Enable OFF ON OFF

    1196 HV U< 3 Fail class F1F3 Warning (F2)

    1200 HV voltage trip

    1201 HV voltage trip Setpoint Ph-Ph Ph-N Ph-Ph

    Designers Reference Handbook

    Selection between phase-phase or phase-neutral voltage detection. When phase-phase tripping is selected, the voltage alarms relate to the nominal voltage. When phase-neutral tripping is selected, the voltage alarms relate to the nominal voltage divided by 3.

  • APU 200 Parameter List

    DEIF A/S Page 14 of 80

    Frequency protections

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1210 HV overfrequency 1

    1211 HV f> 1 Setpoint 100... 120 % 103,0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously above the programmed value during the programmed delay. Frequency settings relate to nominal frequency setting.

    1212 HV f> 1 Timer 0.2... 100 s 10,0 s

    1213 HV f> 1 Relay output A

    Not-used Used

    Not used

    1214 HV f> 1 Relay output B

    Not used Used

    Not used

    1215 HV f> 1 Enable OFF ON OFF

    1216 HV f> 1 Fail class F1F3 Warning (F2)

    1220 HV overfrequency 2

    1221 HV f> 2 Setpoint 100... 120 % 105,0 % Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously above the programmed value during the programmed delay.

    1222 HV f> 2 Timer 0.2... 100 s 5,0 s

    1223 HV f> 2 Relay output A

    Not- used Used

    Not used

    1224 HV f> 2 Relay output B

    Not- used Used

    Not used

    1225 HV f> 2 Enable OFF ON OFF

    1226 HV f> 2 Fail class F1F3 Warning (F2)

    1230 HV f> overfrequency 3

    1231 HV f> 3 Setpoint 100.0% 120.0% 110,0 % Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously above the programmed value during the programmed delay.

    1232 HV f> 3 Timer 0.2 s 100.0 s 5.0 s

    1233 HV f> 3 Relay output A

    Not-used Used

    Not used

    1234 HV f> 3 Relay output B

    Not- used Used

    Not used

    1235 HV f> 3 Enable Not-used Used

    Not used

    1236 HV f> 3 Fail class F1F3 Warning (F2)

    Frequency settings relate to the nominal frequency setting.

  • APU 200 Parameter List

    DEIF A/S Page 15 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1240 HV underfrequency 1

    1241 HV f < 1 Setpoint 80.0% 100.0% 97,0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously under the programmed value during the programmed delay.

    1242 HV f< 1 Timer 0.2 s 100.0 s 5.0 s

    1243 HV f < 1 Relay output A

    Not- used Used

    Not used

    1244 HV f < 1 Relay output B

    Not- used Used

    Not used

    1245 HV f < 1 Enable OFF ON OFF

    1246 HV f < 1 Fail class F1F3 Warning (F2)

    1250 HV underfrequency 2

    1251 HV f< 2 Setpoint 80.0% 100.0% 95.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously under the programmed value during the programmed delay.

    1252 HV f< 2 Timer 0.2 s 100.0 s 5.0 s

    1253 HV f< 2 Relay output A

    Not- used Used

    Not used

    1254 HV f< 2 Relay output B

    Not-used Used

    Not used

    1255 HV f< 2 Enable OFF ON OFF

    1256 HV f< 2 Fail class F1F3 Warning (F2)

    1260 HV underfrequency 3

    1261 HV f< 3 Setpoint 80.0% 100.0% 95.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously under the programmed value during the programmed delay.

    1262 HV f< 3 Timer 0.2 s 100.0 s 5.0 s

    1263 HV f< 3 Relay output A

    Not- used Used

    Not used

    1264 HV f< 3 Relay output B

    Not-used Used

    Not used

    1265 HV f< 3 Enable OFF ON OFF

    1266 HV f< 3 Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 16 of 80

    LV voltage protections

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1270 LV overvoltage 1

    1271 LV U> 1 Setpoint 100.0% 120.0% 103.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously above the programmed value during the programmed delay.

    1272 LV U> 1 Timer 0.0 s 99.9 s 10.0 s

    1273 LV U> 1 Relay output A Not used Used Not used

    1274 LV U> 1 Relay output B Not used Used Not used

    1275 LV U> 1 Enable OFF ON ON

    1276 LV U> 1 Fail class F1F3 Warning (F2)

    1280 LV overvoltage 2

    1281 LV U> 2 Setpoint 100.0% 120.0% 105.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously above the programmed value during the programmed delay.

    1282 LV U> 2 Timer 0.0 s 99.9 s 5.0 s

    1283 LV U> 2 Relay output A Not used Used Not used

    1284 LV U> 2 Relay output B Not used Used Not used

    1285 LV U> 2 Enable OFF ON ON

    1286 LV U> 2 Fail class F1F3 Warning (F2)

    1290 LV overvoltage 3

    1291 LV U> 3 Setpoint 100.0% 120.0% 105.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously above the programmed value during the programmed delay.

    1292 LV U> 3 Timer 0.0 s 99.9 s 5.0 s

    1293 LV U> 3 Relay output A Not used Used Not used

    1294 LV U> 3 Relay output B Not used Used Not used

    1295 LV U> 3 Enable OFF ON OFF

    1296 LV U> 3 Fail class F1F3 Warning (F2)

    Voltage settings relate to the nominal voltage setting.

  • APU 200 Parameter List

    DEIF A/S Page 17 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1300 LV undervoltage 1

    1301 LV U< 1 Setpoint 40.0% 100.0% 97.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously under the programmed value during the programmed delay.

    1302 LV U< 1 Timer 0.00 s 99.99 s 10.00 s

    1303 LV U< 1 Relay output A Not used Used Not used

    1304 LV U< 1 Relay output B Not used Used Not used

    1305 LV U< 1 Enable OFF ON OFF

    1306 LV U< 1 Fail class F1F3 Warning (F2)

    1310 LV undervoltage 2

    1311 LV U< 2 Setpoint 40.0% 100.0% 95.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously under the programmed value during the programmed delay.

    1312 LV U< 2 Timer 0.00 s 99.99 s 5.00 s

    1313 LV U< 2 Relay output A Not used Used Not used

    1314 LV U< 2 Relay output B Not used Used Not used

    1315 LV U< 2 Enable OFF ON OFF

    1316 LV U< 2 Fail class F1F3 Warning (F2)

    1320 LV undervoltage 3

    1321 LV U< 3 Setpoint 40.0% 100.0% 97.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously under the programmed value during the programmed delay.

    1322 LV U< 3 Timer 0.00 s 99.99 s 10.00 s

    1323 LV U< 3 Relay output A Not used Used Not used

    1324 LV U< 3 Relay output B Not used Used Not used

    1325 LV U< 3 Enable OFF ON OFF

    1326 LV U< 3 Fail class F1F3 warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 18 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1330 LV undervoltage 4

    1331 LV U< 4 Setpoint 40.0% 100.0% 60.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the voltage has been continuously under the programmed value during the programmed delay.

    1332 LV U< 4 Timer 0.00 s 99.99 s 0.10 s

    1333 LV U< 4 Relay output A Not used Used Not used

    1334 LV U< 4 Relay output B Not used Used Not used

    1335 LV U< 4 Enable OFF ON OFF

    1336 LV U< 4 Fail class F1F3 Warning (F2)

    1340 LV voltage trip

    1341 LV voltage trip Setpoint Ph-Ph Ph-N Ph-Ph Designers

    Reference Handbook

    Selection between phase-phase or phase-neutral voltage detection.

  • APU 200 Parameter List

    DEIF A/S Page 19 of 80

    LV frequency protections

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1350 LV overfrequency 1

    1351 LV f> 1 Setpoint 100.0% 120.0% 120.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously above the programmed value during the programmed delay.

    1352 LV f> 1 Timer 0.00 s 99.99 s 10.00 s

    1353 LV f> 1 Relay output A Not used Used Not used

    1354 LV f> 1 Relay output B Not used Used Not used

    1355 LV f> 1 Enable OFF ON OFF

    1356 LV f> 1 Fail class F1F3 Warning (F2)

    1360 LV overfrequency 2

    1361 LV f> 2 Setpoint 100.0% 120.0% 110.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously above the programmed value during the programmed delay.

    1362 LV f> 2 Timer 0.00 s 99.99 s 3.00 s

    1363 LV f> 2 Relay output A Not used Used Not used

    1364 LV f> 2 Relay output B Not used Used Not used

    1365 LV f> 2 Enable OFF ON ON

    1366 LV f> 2 Fail class F1F3 Warning (F2)

    1370 LV overfrequency 3

    1371 LV f> 3 Setpoint 100.0% 120.0% 105.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously above the programmed value during the programmed delay.

    1372 LV f> 3 Timer 0.00 s 99.99 s 5.00 s

    1373 LV f> 3 Relay output A Not used Used Not used

    1374 LV f> 3 Relay output B Not used Used Not used

    1375 LV f> 3 Enable OFF ON OFF

    1376 LV f> 3 Fail class F1F3 Warning (F2)

    Frequency settings relate to the nominal frequency setting.

  • APU 200 Parameter List

    DEIF A/S Page 20 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1380 LV underfrequency 1

    1381 LV f< 1 Setpoint 80.0% 100.0% 97.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously under the programmed value during the programmed delay.

    1382 LV f< 1 Timer 0.00 s 99.99 s 10.00 s

    1383 LV f< 1 Relay output A Not used Used Not used

    1384 LV f< 1 Relay output B Not used Used Not used

    1385 LV f< 1 Enable OFF ON OFF

    1386 LV f< 1 Fail class F1F3 Warning (F2)

    1390 LV underfrequency 2

    1391 LV f< 2 Setpoint 80.0% 100.0% 95.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously under the programmed value during the programmed delay.

    1392 LV f< 2 Timer 0.00 s 99.99 s 5.00 s

    1393 LV f< 2 Relay output A Not used Used Not used

    1394 LV f< 2 Relay output B Not used Used Not used

    1395 LV f< 2 Enable OFF ON OFF

    1396 LV f< 2 Fail class F1F3 Warning (F2)

    1400 LV underfrequency 3

    1401 LV f< 3 Setpoint 80.0% 100.0% 97.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously under the programmed value during the programmed delay.

    1402 LV f< 3 Timer 0.00 s 99.99 s 10.00 s

    1403 LV f< 3 Relay output A Not used Used Not used

    1404 LV f< 3 Relay output B Not used Used Not used

    1405 LV f< 3 Enable OFF ON OFF

    1406 LV f< 3 Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 21 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1410 LV underfrequency 4

    1411 LV f< 4 Setpoint 80.0% 100.0% 95.0% Designers Reference Handbook

    The alarm and fail class are activated when the frequency has been continuously under the programmed value during the programmed delay.

    1412 LV f< 4 Timer 0. 00 s 99.99 s 5.00 s

    1413 LV f< 4 Relay output A Not used Used Not used

    1414 LV f< 4 Relay output B Not used Used Not used

    1415 LV f< 4 Enable OFF ON OFF

    1416 LV f< 4 Fail class F1F3 Warning (F2)

    Mains failure protections

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1420 df/dt (ROCOF)

    1421 df/dt (ROCOF) Setpoint 1.5Hz/s 10.0Hz/s 5.0Hz/s Option A1 The alarm and fail class

    are activated when the df/dt rate has been continuously above the programmed value during the programmed number of periods (delay).

    1422 df/dt (ROCOF) Period(s) 1 per 20 per 6 per

    1423 df/dt (ROCOF) Relay output A Not used Used Not used

    1424 df/dt (ROCOF) Relay output B Not used Used Not used

    1425 df/dt (ROCOF) Enable OFF ON OFF

    1426 df/dt (ROCOF) Fail class F1F3 Trip BTB (F3)

    1430 Vector jump

    1431 Vector jump Setpoint 1.0 deg. 90.0 deg. 10.0 deg. Option A1 The alarm and fail class

    are activated when a vector jump is detected.

    1432 Vector jump Relay output A Not used Used Not used

    1433 Vector jump Relay output B Not used Used Not used

    1434 Vector jump Enable OFF ON OFF

    1435 Vector jump Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 22 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1440 LV positive sequence voltage low

    1441 LV pos seq volt Setpoint 10.0% 110.0% 70.0% Option A4 The alarm and fail class

    are activated when the symmetrical (positive sequence) voltage has been continuously below the programmed value during the programmed delay. The timer factory setting is set to 2 periods. This means that the error has to be active for 2 whole periods before the alarm will be tripped. E.g. in a 50 Hz system, the alarm will be activated if the positive sequence is below 70% of U nominal voltage for 40 ms. The alarm will trip the fail class as soon as possible after this delay.

    1442 LV pos seq volt Period(s) 1 per 9 per 2 per

    1443 LV pos seq volt Relay output A Not used Used Not used

    1444 LV pos seq volt Relay output B Not used Used Not used

    1445 LV pos seq volt Enable OFF ON OFF

    1446 LV pos seq volt Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 23 of 80

    Overload protections

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1450 HV VA overload 1

    1451 HV S> 1 Setpoint -200.0% 200.0% 100.0% Designers

    Reference Handbook

    Settings relate to nominal power. The alarm and fail class are activated when the power has been continuously above the programmed value during the programmed delay.

    1452 HV S> 1 Timer 0.1 s 3200.0 s 10.0 s

    1453 HV S> 1 Relay output A Not used Used Not used

    1454 HV S> 1 Relay output B Not used Used Not used

    1455 HV S> 1 Enable OFF ON OFF

    1456 HV S> 1 Fail class F1F3 Warning (F2)

    1460 HV VA overload 2

    1461 HV S> 2 Setpoint -200.0% 200.0% 110.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the power has been continuously above the programmed value during the programmed delay.

    1462 HV S> 2 Timer 0.1 s 3200.0 s 5.0 s

    1463 HV S> 2 Relay output A Not used Used Not used

    1464 HV S> 2 Relay output B Not used Used Not used

    1465 HV S> 2 Enable OFF ON ON

    1466 HV S> 2 Fail class F1F3 Trip BTB (F3)

    1470 HV VA overload 3

    1471 HV S> 3 Setpoint -200.0% 200.0% 100.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the power has been continuously above the programmed value during the programmed delay.

    1472 HV S> 3 Timer 0.1 s 3200 s 10.0 s

    1473 HV S> 3 Relay output A Not used Used Not used

    1474 HV S> 3 Relay output B Not used Used Not used

    1475 HV S> 3 Enable OFF ON OFF

    1476 HV S> 3 Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 24 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1480 HV VA overload 4

    1481 HV S> 4 Setpoint -200.0% 200.0% 110.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the power has been continuously above the programmed value during the programmed delay.

    1482 HV S> 4 Timer 0.1 s 3200 s 5.0 s

    1483 HV S> 4 Relay output A Not used Used Not used

    1484 HV S> 4 Relay output B Not used Used Not used

    1485 HV S> 4 Enable OFF ON OFF

    1486 HV S> 4 Fail class F1F3 Trip BTB (F3)

    1490 HV VA overload 5

    1491 HV S> 5 Setpoint -200.0% 200.0% 100.0% Designers

    Reference Handbook

    The alarm and fail class are activated when the power has been continuously above the programmed value during the programmed delay.

    1492 HV S> 5 Timer 0.1 s 3200 s 10.0 s

    1493 HV S> 5 Relay output A Not used Used Not used

    1494 HV S> 5 Relay output B Not used Used Not used

    1495 HV S> 5 Enable OFF ON OFF

    1496 HV S> 5 Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 25 of 80

    Current unbalance protection

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1500 HV unbalanced current

    1501 HV unbalance curr. Setpoint 0.0% 100.0% 30.0%

    Designers Reference Handbook

    Settings relate to nominal current. The alarm and fail class are activated when the difference between the max. reading and the min. reading of the 3 measured currents has been continuously above the programmed value during the programmed delay.

    1502 HV unbalance curr. Timer 0.1 s 100.0 s 10.0 s

    1503 HV unbalance curr. Relay output A

    Not used Used Not used

    1504 HV unbalance curr. Relay output B

    Not used Used Not used

    1505 HV unbalance curr. Enable OFF ON OFF

    1506 HV unbalance curr. Fail class F1F3 Trip BTB (F3)

    Voltage unbalance protection

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1510 HV unbalanced voltage

    1511 HV unbalance volt. Setpoint 0.0% 50.0% 10.0%

    Designers Reference Handbook

    Settings relate to nominal voltage. The alarm and fail class are activated when the difference between the max. reading and the min. reading of the 3 measured voltages has been continuously above the programmed value during the programmed delay.

    1512 HV unbalance volt. Timer 0.1 s 100.0 s 10.0 s

    1513 HV unbalance volt. Relay output A

    Not used Used Not used

    1514 HV unbalance volt. Relay output B

    Not used Used Not used

    1515 HV unbalance volt. Enable OFF ON OFF

    1516 HV unbalance volt. Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 26 of 80

    Reactive power import protection

    No. Setting

    Min.

    Max.

    Factory setting

    Notes Ref. Description

    1520 HV reactive power import

    1521 HV Q> Setpoint 0.0% 150.0% 50.0% Designers

    Reference Handbook

    Settings relate to nominal power setting value. The alarm and fail class are activated when imported VAr has been continuously above the programmed value during the programmed delay.

    1522 HV Q> Timer 0.1 s 100.0 s 10.0 s

    1523 HV Q> Relay output A Not used Used Not used

    1524 HV Q> Relay output B Not used Used Not used

    1525 HV Q> Enable OFF ON ON

    1526 HV Q> Fail class F1F3 Warning (F2)

    Reactive power export protection

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1530 HV reactive power export

    1531 HV Q> Setpoint 0.0% 100.0% 60.0% Designers

    Reference Handbook

    Settings relate to nominal power setting value. The alarm and fail class are activated when exported VAr has been continuously above the programmed value during the programmed delay.

    1532 HV Q> Timer 0.1 s 100.0 s 10.0 s

    1533 HV Q> Relay output A Not used Used Not used

    1534 HV Q> Relay output B Not used Used Not used

    1535 HV Q> Enable OFF ON ON

    1536 HV Q> Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 27 of 80

    Negative sequence

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1540 HV negative sequence current

    1541 HV neg seq I Setpoint 1.0% 100.0% 20.0% Option C2 Settings relate to

    nominal current. The alarm and fail class are activated when the negative sequence has been continuously above the programmed value during the programmed delay.

    1542 HV neg seq I Timer 0.2 s 100.0 s 0.5 s

    1543 HV neg seq I Relay output A Not used Used Not used

    1544 HV neg seq I Relay output B Not used Used Not used

    1545 HV neg seq I Enable OFF ON OFF

    1546 HV neg seq I Fail class F1F3 Trip BTB (F3)

    1550 HV negative sequence voltage

    1551 HV neg seq U Setpoint 1.0% 100.0% 5.0% Option C2 Settings relate to

    nominal voltage. The alarm and fail class are activated when the negative sequence has been continuously above the programmed value during the programmed delay.

    1552 HV neg seq U Timer 0.2 s 100.0 s 0.5 s

    1553 HV neg seq U Relay output A Not used Used Not used

    1554 HV neg seq U Relay output B Not used Used Not used

    1555 HV neg seq U Enable OFF ON OFF

    1556 HV neg seq U Fail class F1F3 Trip BTB (F3)

    1560 HV negative sequence selection

    1561 HV neg seq select Setpoint Conn 61 27 Conn 68 74

    Con 61 67 measurement

    Option C2 Selection between LV or HV measurement of negative sequence voltage.

  • APU 200 Parameter List

    DEIF A/S Page 28 of 80

    Zero sequence

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1570 HV zero sequence current

    1571 HV zero seq I Setpoint 0.0% 100.0% 20.0% Option C2 Settings relate to

    nominal current. The alarm and fail class are activated when the zero sequence has been continuously above the programmed value during the programmed delay.

    1572 HV zero seq I Timer 0.2 s 100.0 s 0.5 s

    1573 HV zero seq I Relay output A Not used Used Not used

    1574 HV zero seq I Relay output B Not used Used Not used

    1575 HV zero seq I Enable OFF ON OFF

    1576 HV zero seq I Fail class F1F3 Trip BTB (F3)

    1580 HV zero sequence voltage

    1581 HV zero seq U Setpoint 0.0% 100.0% 5.0% Option C2 Settings relate to

    nominal voltage. The alarm and fail class are activated when the zero sequence has been continuously above the programmed value during the programmed delay.

    1582 HV zero seq U Timer 0.2 s 100.0 s 0.5 s

    1583 HV zero seq U Relay output A Not used Used Not used

    1584 HV zero seq U Relay output B Not used Used Not used

    1585 HV zero seq U Enable OFF ON OFF

    1586 HV zero seq U Fail class F1F3 Trip BTB (F3)

    1590 HV zero sequence selection

    1591 HV zero seq select Setpoint Conn 61 27 Conn 68 74

    Con 61 67 measurement

    Option C2 Selection between HV or LV measurement of zero sequence voltage.

  • APU 200 Parameter List

    DEIF A/S Page 29 of 80

    Directional overcurrent protection

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1600 HV directional overcurrent 1

    1601 HV I> direct 1 Setpoint -200.0% 200.0% 120.0% Option A5 Settings relate to

    nominal current. The alarm and fail class are activated when the directional current has been continuously above the programmed value during the programmed delay. The current measure-ment is positive when current is supplied from the mains to the plant. The current measure-ment is negative when current is being supplied to the mains.

    1602 HV I> direct 1 Timer 0.0 s 100.0 s 0.1 s

    1603 HV I> direct 1 Relay output A Not used Used Not used

    1604 HV I> direct 1 Relay output B Not used Used Not used

    1605 HV I> direct 1 Enable OFF ON OFF

    1606 HV I> direct 1 Fail class F1F3 Trip BTB (F3)

    1610 HV directional overcurrent 2

    1611 HV I> direct 2 Setpoint -200.0% 200.0% 130.0% Option A5 Settings relate to

    nominal current. The alarm and fail class are activated when the directional current has been continuously above the programmed value during the programmed delay. The current measure-ment is positive when current is supplied from the mains to the plant. The current measure-ment is negative when current is being supplied to the mains.

    1612 HV I> direct 2 Timer 0.0 s 100.0 s 0.1 s

    1613 HV I> direct 2 Relay output A Not used Used Not used

    1614 HV I> direct 2 Relay output B Not used Used Not used

    1615 HV I> direct 2 Enable OFF ON OFF

    1616 HV I> direct 2 Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 30 of 80

    LV unbalance voltage

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1620 LV unbalance U

    1621 LV unbalance U Setpoint 0.0% 50.0% 6.0% Designers

    Reference Handbook

    Settings relate to average actual voltage. The alarm and fail class are activated when the difference between the max. reading and the min. reading of the 3 measured busHVr voltages has been continuously above the programmed value during the programmed delay.

    1622 LV unbalance U Timer 0.1 s 100.0 s 10.0 s

    1623 LV unbalance U Relay output A Not used Used Not used

    1624 LV unbalance U Relay output B Not used Used Not used

    1625 LV unbalance U Enable OFF ON OFF

    1626 LV unbalance U Fail class F1F3 Warning (F2)

    Time-dependent undervoltage

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1630 Time-dependent undervoltage 1 1-3

    1631 Ut < 1 Setting 1 30.0% 120.0% 30.0% Option A1 Curve setting for time-

    dependent under-voltage. Settings relate to nominal voltage. The condition has to be true i.e. Ut(1)1Ut(2)Ut(3) Ut(4)Ut(5)Ut(6). If this is not fulfilled, the worst-case setpoint Ut(6) will be used.

    1632 Ut < 1 Delay 1 0.00 s 20.00 s 0.15 s

    1633 Ut < 1 Setting 2 30.0% 120.0% 70.0%

    1634 Ut < 1 Delay 2 0.00 s 20.00 s 0.15 s

    1635 Ut < 1 Setting 3 30.0% 120.0% 70.0%

    1636 Ut < 1 Delay 3 0.00 s 20.00 s 0.70 s

    1640 Time-dependent undervoltage 1 4-6

    1641 Ut < 1 Setting 4 30.0% 120.0% 90.0% Option A1 Curve setting for time-

    dependent under-voltage. Settings relate to nominal voltage. The condition has to be true i.e. Ut(1)1Ut(2)Ut(3) Ut(4)Ut(5)Ut(6). If this is not fulfilled, the worst-case setpoint Ut(6) will be used.

    1642 Ut < 1 Delay 4 0.00 s 20.00 s 1.50 s

    1643 Ut < 1 Setting 5 30.0% 120.0% 90.0%

    1644 Ut < 1 Delay 5 0.00 s 20.00 s 2.00 s

    1645 Ut < 1 Setting 6 30.0% 120.0% 90.0%

    1646 Ut < 1 Delay 6 0.00 s 20.00 s 3.00 s

  • APU 200 Parameter List

    DEIF A/S Page 31 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1650 Time-dependent undervoltage 1 activation

    1651 Ut < act 1 Activate 0.0% 120.0% 90% Option A1 Activate is the voltage

    value where the function timer starts. Reset is the value where the function timer is reset to 0 ms. Delay is the delay timer for the reset. The relay outputs will activate immediately when the function timer starts.

    1652 Ut < act 1 Reset 0.0% 120.0% 95%

    1653 Ut < act 1 Delay 0.0 s 320.0 s 1.00 s

    1654 Ut < act 1 Relay

    output A

    Not used Option- dep.

    Not used

    1655 Ut < act 1 Relay

    output B

    Not used Option- dep.

    Not used

    1656 Ut < act 1 Enable OFF ON OFF

    1660 Time-dependent undervoltage 1

    1661 Ut < 1 Relay output A

    Not used Option- dep.

    Not used Option A1 The alarm and fail class

    is activated instantaneously when the voltage value is under the programmed value curve.

    1662 Ut < 1 Relay

    output B

    Not used Option- dep.

    Not used

    1663 Ut < 1 Enable OFF ON OFF

    1664 Ut < 1 Fail class F1F5 Trip BTB (F3)

    1670 Time-dependent undervoltage 2 1-3

    1671 Ut < 2 Setting 1 30.0% 120.0% 30.0% Option A1 Curve setting for time-

    dependent undervoltage. Settings relate to nominal voltage. The condition has to be true i.e. Ut(1)1Ut(2)Ut(3) Ut(4)Ut(5)Ut(6). If this is not fulfilled, the worst-case setpoint Ut(6) will be used.

    1672 Ut < 2 Delay 1 0.00 s 20.00 s 0.15 s

    1673 Ut < 2 Setting 2 30.0% 120.0% 70.0%

    1674 Ut < 2 Delay 2 0.00 s 20.00 s 0.15 s

    1675 Ut < 2 Setting 3 30.0% 120.0% 70.0%

    1676 Ut < 2 Delay 3 0.00 s 20.00 s 0.70 s

  • APU 200 Parameter List

    DEIF A/S Page 32 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1680 Time-dependent undervoltage 2 4-6

    1681 Ut < 2 Setting 4 30.0% 120.0% 90.0% Option A1 Curve setting for time-

    dependent undervoltage. Settings relate to nominal voltage. The condition has to be true i.e. Ut(1)1Ut(2)Ut(3) Ut(4)Ut(5)Ut(6). If this is not fulfilled, the worst-case setpoint Ut(6) will be used.

    1682 Ut < 2 Delay 4 0.00 s 20.00 s 1.50 s

    1683 Ut < 2 Setting 5 30.0% 120.0% 90.0%

    1684 Ut < 2 Delay 5 0.00 s 20.00 s 2.00 s

    1685 Ut < 2 Setting 6 30.0% 120.0% 90.0%

    1686 Ut < 2 Delay 6 0.00 s 20.00 s 3.00 s

    1690 Time-dependent undervoltage 2 activation

    1691 Ut < act 2 Activate 0.0% 120.0% 90% Option A1 Activate is the voltage

    value where the function timer starts. Reset is the value where the function timer is reset to 0 ms. Delay is the delay timer for the reset. The relay output will activate immediately when the function timer starts.

    1692 Ut < act 2 Reset 0.0% 120.0% 95%

    1693 Ut < act 2 Delay 0.0 s 320.0 s 1.00 s

    1694 Ut < act 2 Relay

    output A

    Not used Option- dep.

    Not used

    1695 Ut < act 2 Relay

    output B

    Not used Option- dep.

    Not used

    1696 Ut < act 2 Enable OFF ON OFF

    1700 Time-dependent undervoltage 2

    1701 Ut < 2 Relay output A

    Not used Option- dep.

    Not used Option A1 The alarm and fail class

    is activated instantaneously when the voltage value is under the programmed value curve.

    1702 Ut < 2 Relay

    output B

    Not used Option- dep.

    Not used

    1703 Ut < 2 Enable OFF ON OFF

    1704 Ut < 2 Fail class F1F5 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 33 of 80

    Neutral line inverse overcurrent

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1720 HV In> inverse

    1721 In> Inverse Type IEC inverse Custom

    IEC Inverse

    Designers Reference Handbook

    1722 In> Inverse Limit 2.0% 120.0% 30.0%

    1723 In> Inverse TMS 0.1 100.0 1.0

    1724 In> Inverse k 0.001s 32.000s 0.140s

    1725 In> Inverse c 0.000s 32.000s 0.000s

    1726 In> Inverse a 0.001 32.000 0.020

    1727 In> Inverse Output A Not used Used Not used

    1728 In> Inverse Enable OFF ON OFF

    1729 In> Inverse Fail class F1F3 Trip BTB (F3)

    Earth current inverse

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1730 HV Ie>> inverse

    1731 Ie> Inverse Type IEC inverse Custom

    IEC Inverse

    Designers Reference Handbook

    1732 Ie> Inverse Limit 2.0% 120.0% 30.0%

    1733 Ie> Inverse TMS 0.1 100.0 1.0

    1734 Ie> Inverse k 0.001s 32.000s 0.140s

    1735 Ie> Inverse c 0.000s 32.000s 0.000s

    1736 Ie> Inverse a 0.001 32.000 0.020

    1737 Ie> Inverse Output A Not used Used Not used

    1738 Ie> Inverse Enable OFF ON OFF

    1739 Ie> Inverse Fail class F1F3 Trip BTB (F3)

  • APU 200 Parameter List

    DEIF A/S Page 34 of 80

    Power-dependent reactive power import No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1740 HV P-dependent Q import 1-3

    1741 HV P dep Q1< Setpoint 0...100% 20% Option C2

    1742 HV P dep P1< Setpoint 0...100% 0% 1743 HV P dep Q2< Setpoint 0...100% 22% 1744 HV P dep P2< Setpoint 0...100% 7% 1745 HV P dep Q3< Setpoint 0...100% 27% 1746 HV P dep P3< Setpoint 0...100% 12% 1750 HV P-dependent Q import 4-6

    1751 HV P dep Q4< Setpoint 0...100% 18% Option C2

    1752 HV P dep P4< Setpoint 0...100% 55% 1753 HV P dep Q5< Setpoint 0...100% 21% 1754 HV P dep P5< Setpoint 0...100% 97% 1755 HV P dep Q6< Setpoint 0...100% 1% 1756 HV P dep P6< Setpoint 0...100% 100% 1760 HV P-dependent Q import, alarm

    1761 HV P dep Q< Timer 0,1 s 200 s 1.0 s Option C2

    1762 HV P dep Q< Relay output A Not used Used Not used

    1763 HV P dep Q< Relay output B Not used Used Not used

    1764 HV P dep Q< Enable OFF ON OFF

    1765 HV P dep Q< Fail class F1F3 Trip BTB (F3)

    Power-dependent reactive power export No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1770 HV P-dependent Q export 1-3

    1771 HV P dep Q1> Setpoint 0...100% 88% Option C2

    1772 HV P dep P1> Setpoint 0...100% 0% 1773 HV P dep Q2> Setpoint 0...100% 86% 1774 HV P dep P2> Setpoint 0...100% 24% 1775 HV P dep Q3> Setpoint 0...100% 77% 1776 HV P dep P3> Setpoint 0...100% 53%

  • APU 200 Parameter List

    DEIF A/S Page 35 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1750 HV P-dependent Q export 4-6

    1781 HV P dep Q4> Setpoint 0...100% 60% Option C2

    1782 HV P dep P4> Setpoint 0...100% 80% 1783 HV P dep Q5> Setpoint 0...100% 33% 1784 HV P dep P5> Setpoint 0...100% 95% 1785 HV P dep Q6> Setpoint 0...100% 1% 1786 HV P dep P6> Setpoint 0...100% 100% 1790 HV P-dependent Q export, alarm

    1791 HV P dep Q> Timer 0,1 s 200 s 1.0 s Option C2

    1792 HV P dep Q> Relay output A Not used Used Not used

    1793 HV P dep Q> Relay output B Not used Used Not used

    1794 HV P dep Q> Enable OFF ON OFF

    1795 HV P dep Q> Fail class F1F3 Trip BTB (F3)

    Undervoltage and reactive power low

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1960 U and Q < 1

    1961 U and Q < 1 Setpoint 70.0% 100.0% 85.0% Option A1 The setting relates to the

    nominal voltage. The condition for trip is that the actual voltage drops below the setting value and that the reactive power is 0 kVAr.

    1962 U and Q < 1 Delay 0.0 s 10.0 s 5.0 s

    1963 U and Q < 1 Relay output A Option dep. Not used

    1964 U and Q < 1 Relay output B Option dep. Not used

    1965 U and Q < 1 Enable OFF ON OFF

    1966 U and Q < 1 Fail class F1F5 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 36 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1970 U and Q < 2

    1971 U and Q < 2 Setpoint 70.0% 100.0% 85.0% Option A1 The setting relates to the

    nominal voltage. The condition for trip is that the actual voltage drops below the setting value and that the reactive power is 0 kVAr.

    1972 U and Q < 2 Delay 1.0 s 10.0 s 5.0 s

    1973 U and Q < 2 Relay output A Option dep. Not used

    1974 U and Q < 2 Relay output B Option dep. Not used

    1975 U and Q < 2 Enable OFF ON OFF

    1976 U and Q < 2 Fail class F1F5 Trip BTB (F3)

    BTB externally tripped

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    1980 BTB Ext tripped

    1965 BTB Ext. Trip Enable OFF ON ON

    1966 BTB Ext. Trip Fail class F1F5 Warning (F2)

    Synchronisation and breaker alarms

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    2150 Phase sequence error

    2151 Phase seq error Relay output A Not used Used Not used

    Designers Reference Handbook

    During synchronisation the controller has detected that the rotation direction of the phases is opposite direction as the busbar.

    2152 Phase seq error Relay output B Not used Used Not used

    2153 Phase seq error Fail class F1F3 Block (F1)

    2160 BTB open failure

    2161 BTB open fail Delay 1.0 s 5.0 s 2.0 s Designers

    Reference Handbook

    The breaker open failure will occur, if the unit has transmitted a breaker open signal and the breaker feedback has not changed position from ON to OFF within 2 s.

    2162 BTB open fail Relay output A Not used Used Not used

    2163 BTB open fail Relay output B Not used Used Not used

    2164 BTB open fail Enable OFF ON ON

    2165 BTB open fail Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 37 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    2170 BTB close failure

    2171 BTB close fail Delay 1.0 s 5.0 s 2.0 s Designers

    Reference Handbook

    The breaker close failure will occur, if the unit has transmitted a breaker close signal and the breaker feedback has not changed position from OFF to ON within 2 s.

    2172 BTB close fail Relay output A Not used Used Not used

    2173 BTB close fail Relay output B Not used Used Not used

    2174 BTB close fail Enable OFF ON ON

    2175 BTB close fail Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 38 of 80

    Digital input 77-89 setup

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    3000 Digital input 77

    3001 Dig. input 77 Delay 0.0 s 100.0 s 10.0 s Designers

    Reference Handbook

    The input is configurable and can have different functions in different units. Inputs 24-27 are by default used for breaker feedback. These inputs are only available if no MB or TB is present in the application.

    3002 Dig. input 77 Relay output A Not used Used Not used

    3003 Dig. input 77 Relay output B Not used Used Not used

    3004 Dig. input 77 Enable OFF ON OFF

    3005 Dig. input 77 Fail class F1F3 Warning (F2)

    3006 Dig. input 77 N/X N/O N/C N/O

    Digital input 46-48 setup (multi-functional inputs)

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    3400 Digital input 46

    3401 Wire fail 46 Enable OFF ON OFF Designers

    Reference Handbook

    The input is configurable and can have different functions in different units. (Only available if multi-input 46 are configured to digital).

    3402 Dig. input 46 Delay 0.0 s 100.0 s 10.0 s

    3403 Dig. input 46 Relay output A Not used Used Not used

    3404 Dig. input 46 Relay output B Not used Used Not used

    3405 Dig. input 46 Enable OFF ON OFF

    3406 Dig. input 46 Fail class F1F3 Warning (F2)

    The same settings apply to inputs 78-89, settings 3010 to 3120.

    These parameters are used when a digital input is used as protection input or to activate a limit relay.

  • APU 200 Parameter List

    DEIF A/S Page 39 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    3410 Digital input 47

    3411 Wire fail 47 Enable OFF ON OFF Designers

    Reference Handbook

    The input is configurable and can have different functions in different units. (Only available if multi-input 47 are configured to digital).

    3412 Dig. input 47 Delay 0.0 s 100.0 s 10.0 s

    3413 Dig. input 47 Relay output A Not used Used Not used

    3414 Dig. input 47 Relay output B Not used Used Not used

    3415 Dig. input 47 Enable OFF ON OFF

    3416 Dig. input 47 Fail class F1F3 Warning (F2)

    3420 Digital input 48

    3421 Wire fail 48 Enable OFF ON OFF Designers

    Reference Handbook

    The input is configurable and can have different functions in different units. (Only available if multi-input 48 are configured to digital).

    3422 Dig. input 48 Delay 0.0 s 100.0 s 10.0 s

    3423 Dig. input 48 Relay output A Not used Used Not used

    3424 Dig. input 48 Relay output B Not used Used Not used

    3425 Dig. input 48 Enable OFF ON OFF

    3426 Dig. input 48 Fail class F1F3 Warning (F2)

    Emergency stop

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    3490 Emergency stop

    3491 Emer. stop Delay 0.0 s 60.0 s 0.0 s Designers

    Reference Handbook

    Emergency stop input is intended for a normally closed contact. 3492 Emer. stop

    Relay output A

    Not used Used Not used

    3493 Emer. stop Relay output B Not used Used Not used

    3494 Emer. stop Enable OFF ON OFF

    3495 Emer. stop Fail class F1F3 Trip BTB(F3)

  • APU 200 Parameter List

    DEIF A/S Page 40 of 80

    Multi-functional analogue input setup

    Multi-input no. 46

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4120 4-20 mA 46.1

    4121 4-20 mA 46.1 Setpoint 4 mA 2 0mA 10 mA Designers

    Reference Handbook

    The multi-input 46 has been configured as 4-20 mA.

    4122 4-20 mA 46.1 Delay 0.0 s 999.0 s 120.0 s

    4123 4-20 mA 46.1 Relay output A Not used Used Not used

    4124 4-20 mA 46.1 Relay output B Not used Used Not used

    4125 4-20 mA 46.1 Enable OFF ON OFF

    4126 4-20 mA 46.1 Fail class F1F3 Warning (F2)

    4130 4-20 mA 46.2

    4131 4-20 mA 46.2 Setpoint 4 mA 20 mA 10 mA Designers

    Reference Handbook

    The multi-input 46 has been configured as 4-20 mA.

    4132 4-20 mA 46.2 Delay 0.0 s 999.0 s 120.0 s

    4133 4-20 mA 46.2 Relay output A Not used Used Not used

    4134 4-20 mA 46.2 Relay output B Not used Used Not used

    4135 4-20 mA 46.2 Enable OFF ON OFF

    4136 4-20 mA 46.2 Fail class F1F3 Warning (F2)

    4160 Pt100 46.1

    4161 Pt100 46.1 Setpoint -49 482 80 Designers

    Reference Handbook

    The multi-input 46 has been configured as Pt100. Pt100 setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4162 Pt100 46.1 Delay 0.0 s 999.0 s 5.0 s

    4163 Pt100 46.1 Relay output A Not used Used Not used

    4164 Pt100 46.1 Relay output B Not used Used Not used

    4165 Pt100 46.1 Enable OFF ON OFF

    4166 Pt100 46.1 Fail class F1F3 Warning (F2)

    The available menus for multi-input no. 46 depend on the input type configured in the PC utility software (menu 10980).

  • APU 200 Parameter List

    DEIF A/S Page 41 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4170 Pt100 46.2

    4171 Pt100 46.2 Setpoint -49 482 80 Designers

    Reference Handbook

    The multi-input 46 has been configured as Pt100. Pt100 setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4172 Pt100 46.2 Delay 0.0 s 999.0 s 10.0 s

    4173 Pt100 46.2 Relay output A Not used Used Not used

    4174 Pt100 46.2 Relay output B Not used Used Not used

    4175 Pt100 46.2 Enable OFF ON OFF

    4176 Pt100 46.2 Fail class F1F3 Warning (F2)

    4180 VDO Pressure 46.1

    4181 VDO Pressure 46.1 Setpoint 0.0 145.0 4.0

    Designers Reference Handbook

    The multi-input 46 has been configured as VDO oil pressure. Oil pressure setpoint can be in VAr or PSI, dependent on the unit selection (setting 10970).

    4182 VDO Pressure 46.1 Delay 0.0 s 999.0 s 5.0 s

    4183 VDO Pressure 46.1 Relay output A

    Not used Used Not used

    4184 VDO Pressure 46.1 Relay output B

    Not used Used Not used

    4185 VDO Pressure 46.1 Enable OFF ON OFF

    4186 VDO Pressure 46.1 Fail class F1F3 Warning (F2)

    4190 VDO Pressure 46.2

    4191 VDO Pressure 46.2 Setpoint 0.0 145.0 5.0

    Designers Reference Handbook

    The multi-input 46 has been configured as VDO oil pressure. Oil pressure setpoint can be in VAr or PSI, dependent on the unit selection (setting 10970).

    4192 VDO Pressure 46.2 Delay 0.0 s 999.0 s 5.0 s

    4193 VDO Pressure 46.2 Relay output A

    Not used Used Not used

    4194 VDO Pressure 46.2 Relay output B

    Not used Used Not used

    4195 VDO Pressure 46.2 Enable OFF ON OFF

    4196 VDO Pressure 46.2 Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 42 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4200 VDO Temperature 46.1

    4201 VDO Temp. 46.1 Setpoint -49 482 100 Designers

    Reference Handbook

    The multi-input 46 has been configured as VDO water temperature. Water temperature setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4202 VDO Temp. 46.1 Delay 0.0 s 999.0 s 5.0 s

    4203 VDO Temp. 46.1 Relay output A Not used Used Not used

    4204 VDO Temp. 46.1 Relay output B Not used Used Not used

    4205 VDO Temp. 46.1 Enable OFF ON OFF

    4206 VDO Temp. 46.1 Fail class F1F3 Warning (F2)

    4210 VDO Temperature 46.2

    4211 VDO Temp. 46.2 Setpoint -49 482 110 Designers

    Reference Handbook

    The multi-input 46 has been configured as VDO water temperature. Water temperature setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4212 VDO Temp. 46.2 Delay 0.0 s 999.0 s 5.0 s

    4213 VDO Temp. 46.2 Relay output A Not used Used Not used

    4214 VDO Temp. 46.2 Relay output B Not used Used Not used

    4215 VDO Temp. 46.2 Enable OFF ON OFF

    4216 VDO Temp. 46.2 Fail class F1F3 Warning (F2)

    4220 VDO level 46.1

    4221 VDO Level 46.1 Setpoint 0% 100% 10% Designers

    Reference Handbook

    The multi-input 46 has been configured as VDO fuel level.

    4222 VDO Level 46.1 Delay 0.0 s 999.0 s 10.0 s

    4223 VDO Level 46.1 Relay output A Not used Used Not used

    4224 VDO Level 46.1 Relay output B Not used Used Not used

    4225 VDO Level 46.1 Enable OFF ON OFF

    4226 VDO Level 46.1 Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 43 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4230 VDO Level 46.2

    4231 VDO Level 46.2 Setpoint 0% 100% 5% Designers

    Reference Handbook

    The multi-input 46 has been configured as VDO fuel level.

    4232 VDO Level 46.2 Delay 0.0 s 999.0 s 10.0 s

    4233 VDO Level 46.2 Relay output A Not used Used Not used

    4234 VDO Level 46.2 Relay output B Not used Used Not used

    4235 VDO Level 46.2 Enable OFF ON OFF

    4236 VDO Level 46.2 Fail class F1F3 Warning (F2)

    4240 Wire fail 46

    4241 W. fail 46 Relay output A Not used Used Not used

    Designers Reference Handbook

    The wire break fault detection is activated.

    4242 W. fail 46 Relay output B Not used Used Not used

    4243 W. fail 46 Enable OFF ON OFF

    4244 W. fail 46 Fail class F1F3 Warning (F2)

    Multi-input no. 47

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4250 4-20 mA 47.1

    4251 4-20 mA 47.1 Setpoint 4 mA 20 mA 10 mA Designers

    Reference Handbook

    The multi-input 47 has been configured as 4-20 mA.

    4252 4-20 mA 47.1 Delay 0.0 s 999.0 s 120.0 s

    4253 4-20 mA 47.1 Relay output A Not used Used Not used

    4254 4-20 mA 47.1 Relay output B Not used Used Not used

    4255 4-20 mA 47.1 Enable OFF ON OFF

    4256 4-20 mA 47.1 Fail class F1F3 Warning (F2)

    The available menus for multi-input no. 47 depend on the input type configured in the PC utility software (menu 10990).

  • APU 200 Parameter List

    DEIF A/S Page 44 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4260 4-20 mA 47.2

    4261 4-20 mA 47.2 Setpoint 4 mA 20 mA 10 mA Designers

    Reference Handbook

    The multi-input 47 has been configured as 4-20 mA.

    4262 4-20 mA 47.2 Delay 0.0 s 999.0 s 120.0 s

    4263 4-20 mA 47.2 Relay output A Not used Used Not used

    4264 4-20 mA 47.2 Relay output B Not used Used Not used

    4265 4-20 mA 47.2 Enable OFF ON OFF

    4266 4-20 mA 47.2 Fail class F1F3 Warning (F2)

    4290 Pt100 47.1

    4291 Pt100 47.1 Setpoint -49 482 80 Designers

    Reference Handbook

    The multi-input 47 has been configured as Pt100. Pt100 setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4292 Pt100 47.1 Delay 0.0 s 999.0 s 5.0 s

    4293 Pt100 47.1 Relay output A Not used Used Not used

    4294 Pt100 47.1 Relay output B Not used Used Not used

    4295 Pt100 47.1 Enable OFF ON OFF

    4296 Pt100 47.1 Fail class F1F3 Warning (F2)

    4300 Pt100 47.2

    4301 Pt100 47.2 Setpoint -49 482 80 Designers

    Reference Handbook

    The multi-input 47 has been configured as Pt100. Pt100 setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4302 Pt100 47.2 Delay 0.0 s 999.0 s 10.0 s

    4303 Pt100 47.2 Relay output A Not used Used Not used

    4304 Pt100 47.2 Relay output B Not used Used Not used

    4305 Pt100 47.2 Enable OFF ON OFF

    4306 Pt100 47.2 Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 45 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4310 VDO Pressure 47.1

    4311 VDO Pressure 47.1 Setpoint 0.0 145.0 4.0

    Designers Reference Handbook

    The multi-input 47 has been configured as VDO oil pressure. Oil pressure setpoint can be in VAr or PSI, dependent on the unit selection (setting 10970).

    4312 VDO Pressure 47.1 Delay 0.0 s 999.0 s 5.0 s

    4313 VDO Pressure 47.1 Relay output A

    Not used Used Not used

    4314 VDO Pressure 47.1 Relay output B

    Not used Used Not used

    4315 VDO Pressure 47.1 Enable OFF ON OFF

    4316 VDO Pressure 47.1 Fail class F1F3 Warning (F2)

    4320 VDO Pressure 47.2

    4321 VDO Pressure 47.2 Setpoint 0.0 145.0 5.0

    Designers Reference Handbook

    The multi-input 47 has been configured as VDO oil pressure. Oil pressure setpoint can be in VAr or PSI, dependent on the unit selection (setting 10970).

    4322 VDO Pressure 47.2 Delay 0.0 s 999.0 s 5.0 s

    4323 VDO Pressure 47.2 Relay output A

    Not used Used Not used

    4324 VDO Pressure 47.2 Relay output B

    Not used Used Not used

    4325 VDO Pressure 47.2 Enable OFF ON OFF

    4326 VDO Pressure 47.2 Fail class F1F3 Warning (F2)

    4330 VDO Temperature 47.1

    4331 VDO Temp 47.1 Setpoint -49 482 100 Designers

    Reference Handbook

    The multi-input 47 has been configured as VDO water temperature. Water temperature setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4332 VDO Temp 47.1 Delay 0.0 s 999.0 s 5.0 s

    4333 VDO Temp 47.1 Relay output A Not used Used Not used

    4334 VDO Temp 47.1 Relay output B Not used Used Not used

    4335 VDO Temp 47.1 Enable OFF ON OFF

    4336 VDO Temp 47.1 Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 46 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4340 VDO Temperature 47.2

    4341 VDO Temp 47.2 Setpoint -49 482 110 Designers

    Reference Handbook

    The multi-input 47 has been configured as VDO water temperature. Water temperature setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4342 VDO Temp 47.2 Delay 0.0 s 999.0 s 5.0 s

    4343 VDO Temp 47.2 Relay output A Not used Used Not used

    4344 VDO Temp 47.2 Relay output B Not used Used Not used

    4345 VDO Temp 47.2 Enable OFF ON OFF

    4346 VDO Temp 47.2 Fail class F1F3 Warning (F2)

    4350 VDO Level 47.1

    4351 VDO Level 47.1 Setpoint 0% 100% 10% Designers

    Reference Handbook

    The multi-input 47 has been configured as VDO fuel level.

    4352 VDO Level 47.1 Delay 0.0 s 999.0 s 10.0 s

    4353 VDO Level 47.1 Relay output A Not used Used Not used

    4354 VDO Level 47.1 Relay output B Not used Used Not used

    4355 VDO Level 47.1 Enable OFF ON OFF

    4356 VDO Level 47.1 Fail class F1F3 Warning (F2)

    4360 VDO Level 47.2

    4361 VDO Level 47.2 Setpoint 0% 100% 5% Designers

    Reference Handbook

    The multi-input 47 has been configured as VDO fuel level.

    4362 VDO Level 47.2 Delay 0.0 s 999.0 s 10.0 s

    4363 VDO Level 47.2 Relay output A Not used Used Not used

    4364 VDO Level 47.2 Relay output B Not used Used Not used

    4365 VDO Level 47.2 Enable OFF ON OFF

    4366 VDO Level 47.2 Fail class F1F3 Warning (F2)

    4370 Wire fail 47

    4371 W. fail 47 Relay output A Not used Used Not used

    Designers Reference Handbook

    The wire break fault detection is activated.

    4372 W. fail 47 Relay output B Not used Used Not used

    4373 W. fail 47 Enable OFF ON OFF

    4374 W. fail 47 Fail class F1F3 Warning (F2)

  • APU 200 Parameter List

    DEIF A/S Page 47 of 80

    Multi-input no. 48

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4380 4-20 mA 48.1

    4381 4-20 mA 48.1 Setpoint 4 mA 20 mA 10 mA Designers

    Reference Handbook

    The multi-input 48 has been configured as 4-20 mA.

    4382 4-20 mA 48.1 Delay 0.0 s 999.0 s 120.0 s

    4383 4-20 mA 48.1 Relay output A Not used Used Not used

    4384 4-20 mA 48.1 Relay output B Not used Used Not used

    4385 4-20 mA 48.1 Enable OFF ON OFF

    4386 4-20 mA 48.1 Fail class F1F3 Warning (F2)

    4390 4-20 mA 48.2

    4391 4-20 mA 48.2 Setpoint 4 mA 20 mA 10 mA Designers

    Reference Handbook

    The multi-input 48 has been configured as 4-20 mA.

    4392 4-20 mA 48.2 Delay 0.0 s 999.0 s 120.0 s

    4393 4-20 mA 48.2 Relay output A Not used Used Not used

    4394 4-20 mA 48.2 Relay output B Not used Used Not used

    4395 4-20 mA 48.2 Enable OFF ON OFF

    4396 4-20 mA 48.2 Fail class F1F3 Warning (F2)

    4420 Pt100 48.1

    4421 Pt100 48.1 Setpoint -49 482 80 Designers

    Reference Handbook

    The multi-input 48 has been configured as Pt100. Pt100 setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4422 Pt100 48.1 Delay 0.0 s 999.0 s 5.0 s

    4423 Pt100 48.1 Relay output A Not used Used Not used

    4424 Pt100 48.1 Relay output B Not used Used Not used

    4425 Pt100 48.1 Enable OFF ON OFF

    4426 Pt100 48.1 Fail class F1F3 Warning (F2)

    The available menus for multi-input no. 48 depend on the input type configured in the PC utility software (menu 11000).

  • APU 200 Parameter List

    DEIF A/S Page 48 of 80

    No. Setting Min.

    Max.

    Factory setting

    Notes Ref. Description

    4430 Pt100 48.2

    4431 Pt100 48.2 Setpoint -49 482 80 Designers

    Reference Handbook

    The multi-input 48 has been configured as Pt100. Pt100 setpoint can be in deg. C or Fahrenheit, dependent on the unit selection (setting 10970).

    4432 Pt100 48.2 Delay 0.0 s 999.0 s 10.0 s

    4433 Pt100 48.2 Relay output A Not used Used Not used

    4434 Pt100 48.2 Relay output B Not used Used Not used

    4435 Pt100 48.2 Enable OFF ON OFF

    4436 Pt100 48.2 Fail class F1F3 Warning (F2)

    4440 VDO Pressure 48.1

    4441 VDO Pressure 48.1 Setpoint 0.0 145.0 4.0

    Designers Reference Handbook

    The multi-input 48 has been configured as VDO oil pressure. Oil pressure set