user manual - deif

34
USER MANUAL SGC 110 Single Genset Controller 4189341228C

Upload: others

Post on 25-Dec-2021

24 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: USER MANUAL - DEIF

USER MANUAL

SGC 110Single Genset Controller

4189341228C

Page 2: USER MANUAL - DEIF

1. Introduction1.1 About SGC 110............................................................................................................................................................................................................................ 41.2 Key functions...............................................................................................................................................................................................................................41.3 Product overview.......................................................................................................................................................................................................................41.4 Passwords..................................................................................................................................................................................................................................... 51.5 Overview of controller buttons...........................................................................................................................................................................................51.6 Legal information.......................................................................................................................................................................................................................6

2. Safety instructions2.1 General safety instructions..................................................................................................................................................................................................72.2 Electrical safety...........................................................................................................................................................................................................................72.3 In operation safety.....................................................................................................................................................................................................................7

3. Technical_specifications3.1 Terminals........................................................................................................................................................................................................................................ 83.2 Power supply................................................................................................................................................................................................................................83.3 Genset voltage and frequency measurements..........................................................................................................................................................93.4 Digital inputs................................................................................................................................................................................................................................ 93.5 Analogue resistive sensor inputs.....................................................................................................................................................................................93.6 Analogue inputs used as digital inputs...................................................................................................................................................................... 103.7 D+ Charger alternator........................................................................................................................................................................................................... 103.8 Sensor common point...........................................................................................................................................................................................................113.9 Digital outputs...........................................................................................................................................................................................................................113.10 Communication ports.........................................................................................................................................................................................................11

4. Installation4.1 Dimensions.................................................................................................................................................................................................................................124.2 Mounting in panel....................................................................................................................................................................................................................124.3 Terminal details........................................................................................................................................................................................................................ 134.4 Typical wiring diagram......................................................................................................................................................................................................... 15

5. Monitoring mode5.1 Monitoring mode......................................................................................................................................................................................................................16

6. Configuration mode6.1 Configuration mode............................................................................................................................................................................................................... 176.2 Configurable parameters.................................................................................................................................................................................................... 17

6.2.1 Configurable parameters..............................................................................................................................................................................................176.2.2 Module..................................................................................................................................................................................................................................186.2.3 Digital inputs...................................................................................................................................................................................................................... 186.2.4 Analogue inputs................................................................................................................................................................................................................196.2.5 Outputs.................................................................................................................................................................................................................................216.2.6 Timers...................................................................................................................................................................................................................................216.2.7 Generator............................................................................................................................................................................................................................226.2.8 Engine.................................................................................................................................................................................................................................. 236.2.9 Maintenance...................................................................................................................................................................................................................... 256.2.10 Password ID....................................................................................................................................................................................................................25

6.3 Digital input source selection...........................................................................................................................................................................................266.4 Digital output source selection........................................................................................................................................................................................26

7. Running modes7.1 Remote start/stop mode...................................................................................................................................................................................................... 28

USER MANUAL 4189341228C EN Page 2 of 34

Page 3: USER MANUAL - DEIF

7.2 Deep sleep mode.....................................................................................................................................................................................................................297.3 Manual mode..............................................................................................................................................................................................................................29

8. Alarms8.1 Alarms........................................................................................................................................................................................................................................... 30

9. Troubleshooting9.1 Troubleshooting.......................................................................................................................................................................................................................33

USER MANUAL 4189341228C EN Page 3 of 34

Page 4: USER MANUAL - DEIF

1. Introduction

1.1 About SGC 110

This document presents information necessary for operating DEIF's SGC 110 genset controller.

SGC 110 is a modern genset controller with user friendly HMI and full graphics LCD. The controller comes with a highly versatilesoftware. Extensive inputs and outputs support a wide variety of industry standard features in diesel/gasoline genset applications.

The DEIF Smart Connect software offers flexibility to configure each individual input and output for a specific function or application.All parameters can also be configured on the controller.

1.2 Key functions

• Genset controller with configurable inputs:◦ Five digital inputs◦ Three analogue inputs

• Six digital outputs• Monitors and controls the genset performance effectively• Monitors genset output voltage and frequency precisely• Remote start/stop• Deep sleep mode to extend the battery lifetime• Pre-heat output for assisting engine start• PC connectivity via USB port for customised configuration• Backlit full graphics display with power saving feature• Log with the latest 30 events

1.3 Product overview

Following table gives a brief overview of SGC 110 features:

Features Specifications

Digital switch input 5

Analogue resistive inputs 3

DG alternator voltage input, D+ charging alternator I/O Yes

Digital outputs 6

Event logs Yes

USB I/O port for laptop access Yes

DC battery supply voltage (with -32 V reverse protection) 8 to 28 V

Operating temperature range -20 to 65 °C

Protection class with gasket (included) IP65

USER MANUAL 4189341228C EN Page 4 of 34

Page 5: USER MANUAL - DEIF

1.4 Passwords

The controller is protected from set-up changes with a four digit password.

There are two password levels:

Level Access Factory setting

1 Full access (read and write) 0123

2 Limited access (read) 1234

The passwords can be changed on the controller:1. Go to Configuration mode.2. Log on with password level 1.

3. Use the Up and Down buttons to go to Misc Settings, select with the Start button.

4. Use the Up and Down buttons to go to the password to be changed, select with the Start button.

5. Use the Up and Down buttons to choose the first digit for the new password, select with the Start button.6. Repeat for the next three digits.7. When all four digits are chosen, the display shows

PASSWORD 1

Password changed

1.5 Overview of controller buttons

1. Menu navigation up button2. Menu navigation down button3. Stop/Config button4. Display5. Alarm LED6. Start button7. Mode selection button

USER MANUAL 4189341228C EN Page 5 of 34

Page 6: USER MANUAL - DEIF

Button functionsIn Mode Button input Function

Manual Start Starts the engine

Manual

Stop Stops the engine

Stop (long press) Enters Configuration mode

Down + Stop (long press) Enters Programming mode

ManualAutoConfiguration

UpDown Scrolls through the views/parameters

ManualAuto Up + Down (during Alarm view) Acknowledges and clears the alarm

Configuration Start Selects/saves the parameter

Configuration Up + Down (long press) Enters the Event log page

Configuration Stop (long press) Back to Manual mode

Deep sleep Any Key (for min. 1 s) Back to Manual mode

Event log page Up + Down (long press) Back to Configuration mode

Programming Up + Down (long press) Enters Manual mode

1.6 Legal information

WarrantyWARNINGThe controller is not to be opened by unauthorised personnel. If the controller is opened anyway, the warranty will be lost.

DisclaimerDEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate theengine/generator controlled by the SGC controller, the company responsible for the installation or the operation of the set must becontacted.

DEIF A/S reserves the right to change any of the contents of this document without prior notice.

The English version of this document always contains the most recent and up-to-date information about the product. DEIF does nottake responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document.If there is a discrepancy, the English version prevails.

Copyright© Copyright DEIF A/S 2020. All rights reserved.

USER MANUAL 4189341228C EN Page 6 of 34

Page 7: USER MANUAL - DEIF

2. Safety instructions

2.1 General safety instructions

This document includes important instructions that should be followed during installation and maintenance of the controller.

Installation and maintenance must only be carried out by authorised personnel, and always in accordance with all applicable stateand local electrical codes. Efficient and safe operation of the controller can be acquired only if the equipment is correctly operated,configured and maintained.

The following notations found in this document can indicate potentially hazardous conditions to the operator, service personnel orthe equipment.

NOTE Highlights an essential element of a procedure to ensure correctness.

CAUTIONIndicates a procedure or practice, which could result in damage or destruction of equipment, if not strictly observed.

WARNINGIndicates a procedure or practice, which could result in injuring personnel or loss of life, if not followed correctly.

2.2 Electrical safety

• Electric shock can cause severe personal injury or death.• Ensure that the genset is grounded before performing any installation or service.• Generators produce high electrical voltages, and direct contact with it can cause fatal electrical shock. Prevent contact with

terminals, bare wires, connections, etc., while the generator and related equipment are running. Do not tamper with interlocks.• To handle the maximum electrical current, the wires used for electrical connections and wirings must be of appropriate size.

2.3 In operation safety

• Before installing the controller, ensure that all power voltage supplies are positively turned off at the source. Disconnect thegenerator’s battery cables and remove the panel fuse to prevent accidental start up. Disconnect the cable from the battery post,indicated by a NEGATIVE, NEG, or (–) first. Reconnect the negative cable last. Failure to do so will result in hazardous andpossibly fatal electrical shock.

• Remove the electric power supply before removing the controller or touching other electrical parts.• Use extreme caution when working on electrical components. High voltage can cause injury or death.• With floors of metal or concrete, use rubber insulation mats placed on dry wood platforms when working near the generator or

other electrical equipment.• Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment.• Do not operate any electrical device or wires while standing in water, while barefoot, or while hands or feet are wet. It may result

in severe electrical shock.• Do not wear jewellery. Jewellery can cause a short circuit within electrical contacts and cause shock or burning.

In case of an accident caused by electric shock, immediately shut down the electrical power source. If this is not possible, try torelease the victim from the live conductor. Avoid direct contact with the victim. Use a non-conducting object (for example a rope or awooden stick) to release the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medicalhelp.

USER MANUAL 4189341228C EN Page 7 of 34

Page 8: USER MANUAL - DEIF

3. Technical_specifications

3.1 Terminals

The SGC 110 uses two types of terminal blocks:

Connectors of 3.5 mm pitch Connectors of 5.08 mm pitch

Table 3.1 Terminals

Connector type Pitch Male (on controller)* Female (mating part)* Quantity

4-pin 3.5 mm 5441294 5441223 2

6-pin 3.5 mm 5441317 5441249 1

8-pin 3.5 mm 5441320 5441252 1

10-pin 3.5 mm 5443962 5447560 1

2-pin 5.08 mm 5447353 5441980 1

4-pin 10.16 mm 5474274 5453499 1

*Note: Phoenix (Phoenix Contact (I) Pvt. Ltd.)

3.2 Power supply

Category Specification

Controller terminals 1 (Ground)2 (Battery or DC+)

Supply voltage range Nominal voltage: 12/24 V DCOperating range: 8 to 28 V DC

Cranking drop out period 50 ms

Maximum reverse voltage protection -32 V DC

Measurement accuracy (battery voltage) ±1 % full scale

Resolution 0.1 V

Maximum current consumption ~ 200 mA, 12/24 V DC (excluding the current load for the DCoutputs)

Standby current consumption (LCD backlight off) 124 mA, 12 V DC123 mA, 24 V DC

Deep sleep current 20 mA, 12/24 V DC

USER MANUAL 4189341228C EN Page 8 of 34

Page 9: USER MANUAL - DEIF

3.3 Genset voltage and frequency measurements

Category Specifications

Controller terminals

27 (Neutral)28 (L3)29 (L2)30 (L1)

Measurement type True RMS

Phase-to-neutral voltage 32 to 300 V AC RMS

Phase-to-phase voltage 32 to 520 V AC RMS

Voltage accuracy ±2 % of full scale for phase-to-phase

Voltage resolution 1 V AC RMS for phase-to-neutral2 V AC RMS for phase-to-phase

Frequency range 5 to 75 Hz

Frequency accuracy 0.25 % of full scale

Frequency resolution 0.1 Hz

NOTE For single phase applications, it is mandatory to connect the genset phase and neutral cables to the genset controller'sphase L1 and neutral terminals.

3.4 Digital inputs

Category Specifications

Controller terminals 10, 11, 12, 21, 22

Number of inputs 5

Type Negative sensing (connect to ground for activation)

Software configurable options Low Lub Oil Pressure (LLOP) Switch, High Water Temperature, and more(see Controller overview, Configurable parameters in the User manual formore details).

3.5 Analogue resistive sensor inputs

Category Specifications

Controller terminals 24 (Engine temperature)25 (Fuel level sensor)26 (Oil pressure)

Number of inputs 3

Type Ratio-metric sensing

Range 10 to 5000 Ω (terminal 24)10 to 1000 Ω (terminal 25 and 26)

Open circuit detection Above 5.5 kΩ (terminal 24)Above 1.5 kΩ (terminal 25 and 26)

Measurement accuracy ±2% of full scale (up to 1000 Ω)

Connection method Connect the sensor output terminals between the gensetcontroller terminal and the battery ground terminal

USER MANUAL 4189341228C EN Page 9 of 34

Page 10: USER MANUAL - DEIF

SCP connectionSCP connections for Analogue inputs 1 to 3*:

BatteryEngine body

Sensorinput

Sensorcommon

Terminal 41

Terminal 2

Terminal 1Supply

SGC 1xx series

Analogueresistive

sensor

*SCP connections for Analogue input 2 used as Fuel level sensor with the reference configured as Battery Negative

Battery

Sensorinput

Sensorcommon

Terminal 2

Terminal 1SupplyAnalogue

resistivesensor

SGC 1xx series

3.6 Analogue inputs used as digital inputs

Analogue inputs can be used as digital inputs when wired as shown.

F1

8-28V DC

+

-

3.7 D+ Charger alternator

Category Specifications

Controller terminal 7

Voltage range 0 to VBATTVBATT = 8 to 28 V DC

Excitation PWM (power limited to 3 W, 12 V/250 mA)

Accuracy ±1 % of full scale

USER MANUAL 4189341228C EN Page 10 of 34

Page 11: USER MANUAL - DEIF

The charge fail is a combined input and output terminal. When the genset starts, the terminal provides controlled power output toexcite the charging alternator. After the excitation is successfully done, the controller reads the charging alternator's output voltagefor monitoring its health. The action for charge fail is configurable.

3.8 Sensor common point

Category Specifications

Controller terminal 41

Range ±2 V

Accuracy ±2 % of full scale

NOTE The sensor common point (SCP) terminal 41 of the controller should be directly connected to an electrically sound point onthe engine body. This point on the engine body should serve as a common reference point for all analogue sensors such asthose for measuring lube oil pressure, engine temperature and fuel level. The electrical cable used for the connectionshould not be shared with any other electrical connection. Such a wiring practice is strongly recommended to ensure thatthere is negligible potential difference, if any, between the engine body and the controller's SCP terminal, and, predictableand accurate analogue sensor measurements are always available in a wide variety of field conditions.

3.9 Digital outputs

Category Specifications

Controller terminals 3, 4, 5, 6, 8, 9

Number of outputs 6

Type DC outputs

Maximum current rating Max. per output: 500 mATotal max.: 1 A

Software configurable options Start relay, Fuel relay and many more (see Controller overview,Configurable parameters for more details).

NOTE • Do not connect the starter motor relay and the stop solenoid directly to the controller's output terminals.• Genset and mains contactor latching relays should be compiled against 4 kVA surge as per IEC-61000-4-5 standard.

3.10 Communication ports

Category Specifications

USB USB 2.0 type B for connection to PC with DEIF Smart Connect software.

USER MANUAL 4189341228C EN Page 11 of 34

Page 12: USER MANUAL - DEIF

4. Installation

4.1 Dimensions

139.0 (5.47)

114.

0 (4

.49)

38.3(1.51)

38.3

(1.5

1)

Length Height Depth

Controller 139.0 mm (5.47 in) 114.0 mm (4.49 in) 38.3 mm (1.51 in)

Panel cut-out 118.0 mm (4.65 in) 93.0 mm (3.66 in) Tolerance: ± 0.3 mm (0.01 in)

4.2 Mounting in panel

To mount the controller into the panel, use the fixing clips provided along with the controller.

1. Panel surface.2. Mounting clips.

a. Insert the mounting clips into the slots on the controller.b. Press the mounting clips backwards until they "click" in place.c. Turn the screws to tighten the mounting clips (max. torque: 0.19 Nm).

CAUTIONOver-tightening the screw may damage the controller casing.

USER MANUAL 4189341228C EN Page 12 of 34

Page 13: USER MANUAL - DEIF

4.3 Terminal details

Rear view of the controller with terminal details.

USB

Terminal Text Description Phoenix connector

1 GND Power ground 5441980

2 BATT + Power supply positive

3 DIG OUT A DC output - A

5441223 4 DIG OUT B DC output - B

5 DIG OUT C DC output - C

6 DIG OUT D DC output - D

7 D+ CHG ALT Input for charging alternator control

5441223 8 DIG OUT E DC output - E

9 DIG OUT F DC output - F

10 DIG IN A Input from switch - A

11 DIG IN B Input from switch - B

5441249

12 DIG IN C Input from switch - C

13 Reserved -

14 Reserved -

15 Reserved -

16 Reserved -

17 Reserved -

5447560

18 Reserved -

19 Reserved -

20 Reserved -

21 DIG_IN D Input from switch - D

22 DIG_IN E Input from switch - E

23 Reserved -

24 ANLG_IN ENG_TEMP Analogue input from Engine temperature sensor

25 ANLG_IN FUEL_LEVEL Analogue input from Fuel level sensor

26 ANLG_IN LOP Analogue input from Lube oil pressure sensor

USER MANUAL 4189341228C EN Page 13 of 34

Page 14: USER MANUAL - DEIF

Terminal Text Description Phoenix connector

27 GEN_V–IN NTRL Voltage input from Generator Neutral

5453499 28 GEN_V–IN L3 Voltage input from Generator phase L3

29 GEN_V–IN L2 Voltage input from Generator phase L2

30 GEN_V–IN L1 Voltage input from Generator phase L1

31 Reserved -

32 Reserved -

33 Reserved -

34 Reserved -

35 Reserved -

5441456

36 Reserved -

37 Reserved -

38 Reserved -

39 Reserved -

40 Reserved -

41 SCP Sensor common point

42 Reserved -

USER MANUAL 4189341228C EN Page 14 of 34

Page 15: USER MANUAL - DEIF

4.4 Typical wiring diagram

Figure 4.1 SGC 110 typical wiring

G

24 4125 26

10 11 12 21 2227 28 29 30

+ ‐

+

+

3 4 5 6 8 9 71 2

Enginebody

F1

Supply Analogue inputs

DC

(+)

DC

(-)

D+

Inpu

t

Inpu

t

Inpu

tU

SBDigital inputs(configurable)

InInInInIn

AC voltagegenset

N L3 L2 L1

F4

GB

L1

L2

L3

N

L1

L2

L3

N

Outputs

Out

put

Out

put

Out

put

Out

put

Out

put

Out

put

G D+

B+

Sens

orco

mm

on

Enginebody

NOTE • Fuses:◦ F1: 5 A◦ F4: 2 A

• Wiring diagrams are examples. Use the application's wiring diagram during installation.• Genset and mains contactor latching relays should be compiled against 4 kV surge as per IEC-61000-4-5 standard.• Relay cards used with the controller should be protected against reverse battery voltages.• Analogue input 2 used for Fuel level sensor can be wired with the reference to Battery Negative, see Specifications,

Analogue resistive sensor inputs.• If a digital output is connected to a relay, the relay must include freewheeling diodes.

USER MANUAL 4189341228C EN Page 15 of 34

Page 16: USER MANUAL - DEIF

5. Monitoring mode

5.1 Monitoring mode

In Monitoring mode, the display views shift automatically after a pre-defined time. This delay time can be configured in theconfiguration menu.

The views can also be changed manually with the Up and Down buttons.

Engine status and operating mode

Manual mode Auto mode Generator voltage

Engine battery voltage Engine temperature Engine lube oil pressure

Engine remaining fuel Engine speed Engine run time

Alarms (example) Product info

USER MANUAL 4189341228C EN Page 16 of 34

Page 17: USER MANUAL - DEIF

6. Configuration mode

6.1 Configuration mode

To configure the controller, follow these steps:

1. Press and hold the Stop/Config button for at least three seconds.2. The display shows

3. To see the configuration, press the Stop/Config button. To change the configuration, press the Start button.4. The display shows

PASSWORD

5. To enter the the four digit password:

• Scroll through the digits with the Up and Down buttons.

• Select a digit with the Start button.

6. To leave the Configuration mode, press and hold the Stop/Config button.7. Until the configuration is saved, the display shows

6.2 Configurable parameters

6.2.1 Configurable parameters

The tables give an overview of configurable parameters.

Level 1 (table titles) and Level 2 texts are shown twice:• DEIF Smart Connect software: Normal sentence case, for example Power on Mode.• Controller display: Capital case in brackets, for example (POWER ON MODE)

USER MANUAL 4189341228C EN Page 17 of 34

Page 18: USER MANUAL - DEIF

6.2.2 Module

Table 6.1 General (GENERAL)

Level 2 Range

Profile name Profile 1

Power on Mode(POWER ON MODE)

ManualAuto

Power on Lamp Test(POWER ON LAMP TEST)

EnableDisable

Deep Sleep Mode(DEEP SLEEP MODE)

EnableDisable

Auto-Clear Warning Alarm(AUTO CLEAR WARNINGS)

EnableDisable

Language(LANGUAGE SUPPORT)

EnglishChinese

Table 6.2 Display (DISPLAY)

Level 2 Range

Contrast(CONTRAST) 0 to 100 %

Power Save Mode(POWER SAVE MODE)

EnableDisable

6.2.3 Digital inputs

Table 6.3 Digital Input # (DIG IN #)

Level 2 Range

Source(SOURCE) See Digital input source selection in this document

Name(NAME) Auxiliary Input #

Polarity(POLARITY)

Close to ActivateOpen to Activate

Action(ACTION)

NoneNotificationWarningElectrical TripShutdown

Activation(ACTIVATION)

NeverFrom Engine StartFrom Monitoring OnAlways

Activation Delay(ACTIVATION DELAY) 0 to 60 s

USER MANUAL 4189341228C EN Page 18 of 34

Page 19: USER MANUAL - DEIF

6.2.4 Analogue inputs

Table 6.4 Analogue Input 1 (ENG TEMP / DIG G)

Level 2 Range

Use Input As(SENSOR SELECTION)

Not usedDigital Input GEngine Coolant Temperature Sensor

(Digital) Source((DIG) SOURCE) See Digital input source selection in this document

Name(NAME) Auxiliary Input G

(Digital) Polarity((DIG) POLARITY)

Close to ActivateOpen to Activate

(Digital) Action((DIG) ACTION)

NoneNotificationWarningElectrical TripShutdown

(Digital) Activation((DIG) ACTIVATION)

NeverFrom Engine StartFrom Monitoring OnAlways

(Digital) Activation Delay((DIG) ACTIVATION DELAY) 1 to 60 s

(ETS) Circuit Fault Action(OPEN CKT ALARM)

NoneNotificationWarningElectrical TripShutdown

(ETS) Engine Temperature Sensor Calibration Table Resistance: 0 to 1000 ΩTemperature: 25 to 300 °C

Table 6.5 Analogue Input 2 (FUEL LVL / DIG H)

Level 2 Range

Use Input As(SENSOR SELECTION)

Not usedDigital Input HFuel Level Sensor

(Digital) Source((DIG) SOURCE) See Digital input source selection in this document

Name(NAME) Auxiliary Input H

(Digital) Polarity((DIG) POLARITY)

Close to ActivateOpen to Activate

(Digital) Action((DIG) ACTION)

NoneNotificationWarningElectrical TripShutdown

(Digital) Activation((DIG) ACTIVATION)

NeverFrom Engine Start

USER MANUAL 4189341228C EN Page 19 of 34

Page 20: USER MANUAL - DEIF

Level 2 Range

From Monitoring OnAlways

(Digital) Activation Delay((DIG) ACTIVATION DELAY) 1 to 60 s

(FLS) Low Fuel Level Shutdown(SHUTDOWN)

EnableDisable

(FLS) Shutdown Threshold(SHUTDOWN THRESHOLD) 0 to 78 %

(FLS) Low Fuel Level Notification(NOTIFICATION)

EnableDisable

(FLS) Notification Threshold(NOTIFICATION THRESHOLD) 2 to 80 %

(FLS) Fuel Tank Capacity(FUEL TANK SIZE) 2 to 1000 litre

(FLS) Fuel Theft Warning(FUEL THEFT ALARM)

EnableDisable

(FLS) Fuel Theft Alarm Threshold(FUEL LVL THRESH) 1 to 100 % per hour

(FLS) Circuit Fault Action(OPEN CKT ALARM)

NoneNotificationWarningElectrical TripShutdown

(FLS) Fuel Sensor Reference(FUEL LVL REF)

Battery NegativeEngine Body

(FLS) Fuel Level Sensor Calibration Table Resistance: 0 to 1000 ΩFuel level: 0 to 100 %

Table 6.6 Analogue Input 3 (LOP / DIG F)

Level 2 Range

Use Input As(SENSOR SELECTION)

Not usedDigital Input FLube Oil Pressure

(Digital) Source((DIG) SOURCE) See Digital input source selection in this document

Name(NAME) Auxiliary Input F

(Digital) Polarity((DIG) POLARITY)

Close to ActivateOpen to Activate

(Digital) Action((DIG) ACTION)

NoneNotificationWarningElectrical TripShutdown

(Digital) Activation((DIG) ACTIVATION)

NeverFrom Engine StartFrom Monitoring OnAlways

USER MANUAL 4189341228C EN Page 20 of 34

Page 21: USER MANUAL - DEIF

Level 2 Range

(Digital) Activation Delay((DIG) ACTIVATION DELAY) 1 to 60 s

(LOP) Circuit Fault Action(OPEN CKT ALARM)

NoneNotificationWarningElectrical TripShutdown

(LOP) Lube Oil Pressure Sensor Calibration Resistance: 10 to 100 ΩPressure: 1.0 to 10.0 bar

6.2.5 Outputs

Table 6.7 Outputs # (OUT #)

Level 2 Range

Source(SOURCE) See Digital output source selection in this document

On Activation(ON ACTIVATION)

EnergiseDe-energise

6.2.6 Timers

Table 6.8 Cranking (CRANKING TIMERS)

Level 2 Range

Crank Hold Time(CRANK HOLD TIME) 1 to 15 s

Crank Rest Time(CRANK REST TIME) 2 to 60 s

Manual Start Delay(MANUAL START DELAY) 0 to 300 s

Auto Start Delay(AUTO START DELAY) 0 to 43200 s

Table 6.9 General (GENERAL TIMER)

Level 2 Range

Safety Monitoring Delay(SAFETY MONITOR DELAY) 10 to 60 s

Mains Detect Delay(MAINS DETECT DELAY) N/A

Alternator Detect Delay(ALT DETECT DELAY) 1 to 30 s

Warm-Up Delay(WARM-UP DELAY) 0 to 60 s

Return To Mains Delay(RETN-TO-MAINS DELAY) N/A

Engine Cooling Time(ENG COOL TIME) 0 to 300 s

USER MANUAL 4189341228C EN Page 21 of 34

Page 22: USER MANUAL - DEIF

Level 2 Range

Stop Action Time(STOP ACTION TIME) 10 to 120 s

Additional Stopping Time(ADDN STOPPING TIME) 0 to 120 s

Load Transfer Delay(LOAD TRANSFER DELAY) 0 to 60 s

Power Save Mode Delay(PWR SAVE MODE DELAY) 5 to 1800 s

Screen Changeover Time(SCRN CHNGOVER TIME) 1 to 1800 s

Deep Sleep Mode Delay(DEEP SLP MODE DELAY) 5 to 1800 s

Sounder Alarm Time(SOUNDER ALARM TIMER) 1 to 300 s

Auto Exit Config Mode(AUTO EXIT CNFG MODE) 10 to 1800 s

6.2.7 Generator

Table 6.10 Alternator configuration (ALT CONFIG)

Level 2 Range

Alternator Present(ALT PRESENT)

YesNo

Number of Poles(NUMBER OF POLES) 2/4/6/8

AC system(ALT AC SYSTEM)

1 phase3 phase

Min Healthy Voltage(MIN HEALTHY VOLT) 50 to 350 V phase-neutral

Min Healthy Frequency(MIN HEALTHY FREQ) 10 to 75 Hz

Phase Reversal Detection(PHASE REVERSAL DETECT)

EnableDisable

Phase Reversal Action(PHASE REVERSAL ACTION)

NoneNotificationWarningElectrical TripShutdown

Auto Load Transfer(AUTO LOAD TRANSFER)

EnableDisable

Table 6.11 Voltage Monitoring (VOLT MONITOR)

Level 2 Range

Under-voltage Shutdown(UNDER VOLT SHUTDOWN)

EnableDisable

Under-voltage Shutdown Threshold(UV SHUTDOWN THRESH) 50 to 295 V phase-neutral

USER MANUAL 4189341228C EN Page 22 of 34

Page 23: USER MANUAL - DEIF

Level 2 Range

Under-voltage Warning(UNDER VOLT WARNING)

EnableDisable

Under-voltage Warning Threshold(UV WARNING THRESHOLD) 55 to 300 V phase-neutral

Over-voltage Shutdown(OVER VOLT SHUTDOWN)

EnableDisable

Over-voltage Shutdown Threshold(OV SHUTDOWN THRESH) 105 to 350 V phase-neutral

Over-voltage Warning(OVER VOLT WARNING)

EnableDisable

Over-voltage Warning Threshold(OV WARNING THRESHOLD) 100 to 345 V phase-neutral

Table 6.12 Frequency Monitoring (FREQ MONITOR)

Level 2 Range

Under-frequency Shutdown(UNDER FREQ SHUTDOWN)

EnableDisable

Under-frequency Shutdown Threshold(UF SHUTDOWN THRESH) 10.0 to 59.0 Hz

Under-frequency Warning Enable(UNDER FREQ WARNING)

EnableDisable

Under-frequency Warning Threshold(UF WARNING THRESHOLD) 11.0 to 60.0 Hz

Over-frequency Shutdown Enable(OVER FREQ SHUTDOWN)

EnableDisable

Over-frequency Shutdown Threshold(OF SHUTDOWN THRESH) 26.0 to 75.0 Hz

Over-frequency Warning Enable(OVER FREQ WARNING)

EnableDisable

Over-frequency Warning Threshold(OF WARNING THRESHOLD) 25.0 to 74.0 Hz

6.2.8 Engine

Table 6.13 Crank Disconnect (CRANK DISCONN)

Level 2 Range

Start Attempts(START ATTEMPTS) 1 to 9

Disconnect on Oil Pressure Sensor(DISCONN ON LOP SENS)

EnableDisable

Monitor Pressure Sensor Before Crank(MON LLOP BEF CRANK)

EnableDisable

Pressure Sensor Monitoring Threshold(DISCONN LOP SENS) 0.5 to 10.0 bar

Monitor Pressure Switch Before Crank(MON LOP BEF CRANK)

EnableDisable

USER MANUAL 4189341228C EN Page 23 of 34

Page 24: USER MANUAL - DEIF

Level 2 Range

Disconnect on Oil Pressure Switch(DISCONN ON LLOP SW)

EnableDisable

Pressure Switch Transient Time(LLOP SW TRANS TIME) 0.0 to 3.0 s

Crank Disconnect At Alt Frequency(ALT FREQUENCY) 10 to 70 Hz

Crank Disconnect At Engine Speed(ENGINE SPEED) 150 to 4000 RPM

Disconnect On Charging Alt Voltage(DISC ON CHG ALT VOLT)

EnableDisable

Charging Alt Disconnect Volt Threshold(CHG ALT THRESHOLD) 5.0 to 30.0 V

Table 6.14 Speed Monitoring (SPEED MONITOR)

Level 2 Range

Engine Speed Sense Source(SPEED SENSE SOURCE) Alternator frequency

Flywheel Teeth (Magnetic Pickup) N/A

W-Point Frequency@ 1500 N/A

Under-speed Shutdown(UNDER SPEED SHUTDOWN)

EnableDisable

Under-speed Threshold(UNDER SPEED THRESH) 0 to 3600 RPM

Under-speed Delay(UNDER SPEED DELAY) 1 to 60 s

Over-speed Threshold(OVER SPEED THRESH) 700 to 4000 RPM

Over-speed Delay(OVER SPEED DELAY) 1 to 20 s

Gross Over-speed Threshold(GROSS OS THRESHOLD) 100 to 200 %

Table 6.15 Battery Monitoring (BATTERY MONITOR)

Level 2 Range

Low Battery Voltage Action(LOW VOLT ACTION)

NoneNotificationWarningElectrical TripShutdown

Low Battery Voltage Threshold(LOW VOLT THRESHOLD) 8.0 to 31.0 V

Low Battery Voltage Delay(LOW VOLT DELAY) 5 to 1800 s

High Battery Voltage Action(HIGH VOLT ACTION)

NoneNotificationWarningElectrical Trip

USER MANUAL 4189341228C EN Page 24 of 34

Page 25: USER MANUAL - DEIF

Level 2 Range

Shutdown

High Battery Voltage Threshold(HIGH VOLT THRESHOLD) 9.0 to 32.0 V

High Battery Voltage Delay(HIGH VOLT DELAY) 5 to 1800 s

Table 6.16 Charging Alternator Monitoring (CHARGE ALT MON)

Level 2 Range

Charging Alternator Fail Action(FAIL ACTION)

NoneNotificationWarningElectrical TripShutdown

Charging Alternator Fail Threshold(FAIL THRESHOLD) 0.0 to 35.0 V

Charging Alternator Fail Delay(FAIL DELAY) 5 to 60 s

Table 6.17 Preheating (PREHEAT)

Level 2 Range

Pre-heat Timer(PREHEAT TIMER) 1 to 900 s

Engine Temperature(ENG TEMP EN)

EnableDisable

Engine Temperature Threshold(ENG TEMP LIMIT) 10 to 300 °C

6.2.9 Maintenance

Table 6.18 Maintenance (MAINT ALARM)

Level 2 Range

Alarm Action(ACTION)

NoneNotificationWarning

Due At Engine Hours(DUE AT ENGINE HOURS) 10 to 65000 hours

Alarm Due Date(ALARM DUE DATE) dd/mm/yyyy

6.2.10 Password ID

Table 6.19 ID

Level 1 Level 2 Range

(PASSWORD 1) #### Numbers: 0 to 9

(PASSWORD 2) #### Numbers: 0 to 9

USER MANUAL 4189341228C EN Page 25 of 34

Page 26: USER MANUAL - DEIF

6.3 Digital input source selection

No. Input source

1 Not Used

2 User Configured

3 Low Fuel LVL Switch

4 Low Lube Oil Press Switch

5 High Engine Coolant Temp Switch

6 Low Water LVL Switch

7 Emergency Stop

8 Remote Start/Stop

9 Simulate Start

10 Simulate Stop

11 Simulate Auto

12 Close Gen/Open Mains Switch

13 Close Mains/Open Gen Switch

14 Reserved1

15 V-Belt Broken Switch

6.4 Digital output source selection

No. Output source

1 Disable

2 Sounder Alarm

3 Battery Over Volt

4 Battery Under Volt

5 Charge Alt Shutdown

6 Charge Alt Warning

7 Configurable

8 Configurable

9 Reserved1

10 Common Alarm

11 Common Electrical Trip

12 Common Shutdown

13 Common Warning

14 Cooling Down

15 Dig In A

16 Dig In B

17 Dig In C

18 Dig In D

19 Dig In E

USER MANUAL 4189341228C EN Page 26 of 34

Page 27: USER MANUAL - DEIF

No. Output source

20 Dig In F (Anlg In LOP 1)

21 Dig In G (Analog Eng Temp)

22 Dig In H (Anlg In Fuel LVL)

23 Reserved2

24 Emergency Stop

25 Stop Solenoid

26 Fail To Start

27 Fail To Stop

28 Fuel Relay

29 Gen Available

30 L1 Phase OV Shutdown

31 L1 Phase UV Shutdown

32 L2 Phase OV Shutdown

33 L2 Phase UV Shutdown

34 L3 Phase OV Shutdown

35 L3 Phase UV Shutdown

36 Reserved3

37 High Engine Coolant Temp

38 Low Fuel LVL

39 Low LOP

40 Reserved4

41 Reserved5

42 Oil Pressure Open Circuit

43 Open Gen Contactor

44 Configurable

45 Over Freq Shutdown

46 Over Speed Shutdown

47 Gross Over Speed Shutdown

48 Start Relay

49 Temp Sensor Open Circuit

50 Under Freq Shutdown

51 Under Speed Shutdown

52 Maintenance Due

53 Stop Mode

54 Auto Mode

55 Manual Mode

56 Preheat Output

USER MANUAL 4189341228C EN Page 27 of 34

Page 28: USER MANUAL - DEIF

7. Running modes

7.1 Remote start/stop mode

To use the Remote start/stop mode, configure one of the digital input as Remote start/stop (Latched type input) and set thecontrollerto Auto mode.

To start or stop the genset while in Remote start/stop mode, activate/deactivate (continuous signal) the pre-configured Remote start/stop input. The controller latches the genset contactor when the controller confirms that all the engine and genset parameters arewithin the configured thresholds. When the pre-configured input is deactivated the controller opens the genset contactor.

USER MANUAL 4189341228C EN Page 28 of 34

Page 29: USER MANUAL - DEIF

7.2 Deep sleep mode

Deep sleep mode is a useful feature to prolong the battery life. In this mode, normal functions of the controller are suspended andthe controller is placed in its lowest power consumption state. The controller maintains the status and alarms it had before Deepsleep mode. When the controller wakes up, normal operations are resumed automatically.

The controller goes in Deep sleep mode when there is no user interaction for the preset Deep sleep mode delay. In Auto mode, ifRemote start/stop is configured to a digital input, the controller wakes up after receiving a Remote start command.

Press and hold any key for at least one second to come out of Deep sleep mode.

7.3 Manual mode

• Inputs: Stop pressed, Start pressed, Simulate start, Simulate stop, Estop, Electric trip, Shutdown, Warning, LLOP, Auto loadtransfer.

• Outputs: flag_start, flag_stop.

USER MANUAL 4189341228C EN Page 29 of 34

Page 30: USER MANUAL - DEIF

8. Alarms

8.1 Alarms

With SGC 110 it is possible to configure several Shutdown/Electrical trip, Warning and Notification alarms, for example Low oilpressure shutdown, Overload warning, and more.

An alarm occurs when a pre-configured parameter is out of the preset level. The Alarm LED flashes and the Sounder alarmactivates (if configured). The controller shows the alarm names on the Alarms display and the nature of alarm on Engine statusdisplay.

To acknowledge the alarms, press the Up and Down buttons simultaneously.

All the alarms are activated at the end of Safety monitoring timer. The controller will not send the start command if Warning,Electrical trip or Shutdown alarms are left unacknowledged.

Alarm typesNo. Alarm actions Description

1 Shutdown Load is taken off from the genset and the genset is immediately stopped by skipping theEngine cooling time.

2 Electrical trip Load is taken off from the genset, the Engine cooling timer begins, after which the gensetis stopped.

3 Warning Warning alarms draw the operator's attention to an undesirable condition without affectingthe genset's operation.The genset cannot be started without acknowledging the Warning alarms

4 Notification The controller shows the message on the display. The genset start/stop operation is notaffected.

Alarms and their causesNo. Alarms Causes/Indication Actions

1

Low Oil Pressure (Sensor) Indicates that the oil pressure measured is below thepreset threshold.

ShutdownWarning

Low Oil Pressure (Switch) Indicates that the oil pressure measured is low throughswitch.

ShutdownWarningElectrical TripNotification

2

Low Fuel level sensor Indicates that the amount of fuel level is below the presetthreshold.

ShutdownWarning

Low Fuel level switch Indicates that the amount of fuel level is below the presetthreshold.

ShutdownWarningElectrical TripNotification

3

High Eng Temp sensor Indicates that the engine temperature is above the presetthreshold. This condition is detected only when engine ison.

ShutdownWarning

High Eng Temp switch Indicates that the engine temperature measured is highthrough switch.

ShutdownWarningElectrical TripNotification

4 Low Water Level switch Indicates that radiator water level is below the presetthreshold.

ShutdownWarning

USER MANUAL 4189341228C EN Page 30 of 34

Page 31: USER MANUAL - DEIF

No. Alarms Causes/Indication Actions

Electrical TripNotification

5 Over Speed Indicates that genset speed has exceeded the presetoverspeed threshold. The genset will shut down afterOverspeed delay.

Shutdown

6 Gross Over Speed Indicates that genset speed has exceeded the presetGross overspeed threshold. The genset will shut downimmediately without any delay.

Shutdown

7 Under Speed The engine speed has fallen below the preset RPM. Shutdown

8 L1 Phase Over Voltage Indicates that genset (L1) phase voltage has exceeded thepreset over-voltage threshold.

ShutdownWarning

9 L1 Phase Under Voltage Indicates that genset (L1) phase voltage has fallen belowpreset under-voltage threshold.

ShutdownWarning

10 L2 Phase Over Voltage Indicates that genset (L2) phase voltage has exceeded thepreset over-voltage threshold.

ShutdownWarning

11 L2 Phase Under Voltage Indicates that genset (L2) phase voltage has fallen belowpreset under-voltage threshold.

ShutdownWarning

12 L3 Phase Over Voltage Indicates that genset (L3) phase voltage has exceeded thepreset over-voltage threshold.

ShutdownWarning

13 L3 Phase Under Voltage Indicates that genset (L3) phase voltage has fallen belowpreset under-voltage threshold.

ShutdownWarning

14 Over Frequency Indicates that genset output frequency has exceeded thepreset threshold.

ShutdownWarning

15 Under Frequency Indicates that genset output frequency has fallen below thepreset threshold.

ShutdownWarning

16 Emergency stop Configured as digital input has triggered longer than presetduration or when the immediate shutdown is required. Shutdown

17 Charge Fail The charge alternator voltage has dropped below thepreset threshold.

ShutdownWarningNotification

18 Battery Over Voltage The battery voltage has exceeded the preset threshold.

ShutdownWarningElectrical TripNotification

19 Battery Under Voltage The battery voltage has fallen below the preset threshold.

ShutdownWarningElectrical TripNotification

20 Maintenance due Indicates that engine running hours exceed the presethours limit or maintenance due date has occurred and filterservicing is required.

WarningNotification

21 Auxiliary input/User definedname

Configured auxiliary input has triggered longer than presetduration.

ShutdownWarningElectrical TripNotification

22 Fail to Stop It is detected that genset is still running after sending stopcommand. Shutdown

23 Fail to Start Indicates that genset has not started after the presetnumber of Start attempts. Shutdown

USER MANUAL 4189341228C EN Page 31 of 34

Page 32: USER MANUAL - DEIF

No. Alarms Causes/Indication Actions

24 Fuel theft The fuel consumption exceeds the preset threshold. Warning

25 Eng Temp/terminal 24 - CktOpn The temperature sensor is not detected (circuit open). Warning

26 Fuel Level Ckt Open The fuel level sensor is not detected (circuit open). Shutdown

27 LOP/terminal 26 - Ckt Opn The oil pressure sensor is not detected (circuit open). Warning

28 DG Phase Reversed Alternator phase sequence (L1-L2-L3) is not correct. ShutdownWarningElectrical Trip

29

High Oil Pressure sensor Indicates that the measured oil pressure is above thepreset threshold.

ShutdownWarning

High Oil Pressure switch Indicates that the measured oil pressure is above thepreset threshold.

ShutdownWarningElectrical TripNotification

USER MANUAL 4189341228C EN Page 32 of 34

Page 33: USER MANUAL - DEIF

9. Troubleshooting

9.1 Troubleshooting

This section explains the common faults, their possible causes and remedial actions.

General troubleshootingFault Action

The controller does not power ON.

• Check the battery voltage.• Check the fuse on the battery supply.• Check continuity between battery positive and controller terminal 2.• Check continuity between battery ground and controller terminal 1.

The controller display freezes or hangsup. • Reset the controller power.

The controller fails to crank-start theengine.

• Check the battery voltage.• Enter the Configuration mode in the controller and verify the configuration for the

Start output. Check that the Start output is working correctly by measuring itsoutput voltage.

• Enter the Configuration mode in the controller and verify the configuration of theCrank disconnect method.

• Verify the configuration of the LLOP Switch polarity. Ensure that the lube oilpressure switch and sensor are working OK. Check their wiring.

The Emergency Stop alarm is shownwithout the Emergency Stop is activated.

• Check if the Emergency stop switch is working OK, including the wiring.• Enter the Configuration mode in the controller and verify the configuration of the

Emergency stop polarity.

The controller generates unnecessaryShutdown alarms or Warning alarms.

• Check the respective switch, sensor and wiring.• Enter Configuration mode in the controller and verify the respective threshold

configuration.

The controller shows Charge fail alarm.

• To check if the controller's charging alternator terminal is working:◦ Disconnect the charging alternator wiring to the controller's terminal 7.◦ Short terminal 7 to the ground through a DC ammeter.◦ Crank-start the engine.◦ The DC ammeter should indicate the current in the range of 200 to 400 mA for

~30 seconds.◦ If yes, the controller's charging alternator terminal is working OK.

• Disconnect and re-connect the charging alternator connection to the controller'sterminal 7.

• Check if the charging alternator is working OK.

The controller shows Error C03.

Error C03 can occur if the controller is disconnected from the PC during aconfiguration.

1. Press and hold the Stop/Config button during a power cycle to reset thecontroller.

2. Re-send the configuration file.

The controller shows genset ON whilegenset is at rest.Fail to stop alarm when genset is at rest.

• Enter Configuration mode in the controller and verify the configuration for the LLOPand LOP, including the wiring.

• Ensure that Mains voltage wiring is not connected by mistake to the controller'sgenset voltage terminals.

The controller sends a Crank-startcommand immediately after power on.

• Ensure that the controller's output terminal is not directly connected to the starterrelay. The controller's output should be given to an intermediate relay which should

USER MANUAL 4189341228C EN Page 33 of 34

Page 34: USER MANUAL - DEIF

Fault Action

in-turn power the starter relay. The controller can get permanently damaged andwill need to be replaced if this precaution is not taken.

• Check the start-relay connection with the suitable controller terminal.• Enter the Configuration mode in the controller and verify the configuration for Start

mode and the Start relay output polarity.

The engine runs, but the controller showsgenset to be OFF.

• Check if the alternator voltage signal (L1 phase) is received by the controllerterminals.

• Check if the LOP and LLOP are working OK, including the wiring to the controller.

The controller shows incorrect reading forany of LOP, fuel level or temperaturesensors.

• Check the respective sensor and its wiring.• Enter the Configuration mode in the controller and verify the calibration for the

respective sensor in the configuration.

The controller shows incorrect engineRPM. Check the wiring from the main alternator’s L1 phase and neutral to the controller.

The controller shows incorrect enginetemperature/Lube oil pressure. Check the wiring between the controller's terminal 41 (SCP) and the engine body

The controller shows incorrect fuel level.

Enter Configuration mode, check if the Fuel analogue input configuration for the Fuelsensor reference is like the physical connection. For example, if the configuration isset as Battery negative the connection of the fuel sensor negative must be on batterynegative.

USER MANUAL 4189341228C EN Page 34 of 34