user manual - deif
TRANSCRIPT
USER MANUAL
SGC 110Single Genset Controller
4189341228C
1. Introduction1.1 About SGC 110............................................................................................................................................................................................................................ 41.2 Key functions...............................................................................................................................................................................................................................41.3 Product overview.......................................................................................................................................................................................................................41.4 Passwords..................................................................................................................................................................................................................................... 51.5 Overview of controller buttons...........................................................................................................................................................................................51.6 Legal information.......................................................................................................................................................................................................................6
2. Safety instructions2.1 General safety instructions..................................................................................................................................................................................................72.2 Electrical safety...........................................................................................................................................................................................................................72.3 In operation safety.....................................................................................................................................................................................................................7
3. Technical_specifications3.1 Terminals........................................................................................................................................................................................................................................ 83.2 Power supply................................................................................................................................................................................................................................83.3 Genset voltage and frequency measurements..........................................................................................................................................................93.4 Digital inputs................................................................................................................................................................................................................................ 93.5 Analogue resistive sensor inputs.....................................................................................................................................................................................93.6 Analogue inputs used as digital inputs...................................................................................................................................................................... 103.7 D+ Charger alternator........................................................................................................................................................................................................... 103.8 Sensor common point...........................................................................................................................................................................................................113.9 Digital outputs...........................................................................................................................................................................................................................113.10 Communication ports.........................................................................................................................................................................................................11
4. Installation4.1 Dimensions.................................................................................................................................................................................................................................124.2 Mounting in panel....................................................................................................................................................................................................................124.3 Terminal details........................................................................................................................................................................................................................ 134.4 Typical wiring diagram......................................................................................................................................................................................................... 15
5. Monitoring mode5.1 Monitoring mode......................................................................................................................................................................................................................16
6. Configuration mode6.1 Configuration mode............................................................................................................................................................................................................... 176.2 Configurable parameters.................................................................................................................................................................................................... 17
6.2.1 Configurable parameters..............................................................................................................................................................................................176.2.2 Module..................................................................................................................................................................................................................................186.2.3 Digital inputs...................................................................................................................................................................................................................... 186.2.4 Analogue inputs................................................................................................................................................................................................................196.2.5 Outputs.................................................................................................................................................................................................................................216.2.6 Timers...................................................................................................................................................................................................................................216.2.7 Generator............................................................................................................................................................................................................................226.2.8 Engine.................................................................................................................................................................................................................................. 236.2.9 Maintenance...................................................................................................................................................................................................................... 256.2.10 Password ID....................................................................................................................................................................................................................25
6.3 Digital input source selection...........................................................................................................................................................................................266.4 Digital output source selection........................................................................................................................................................................................26
7. Running modes7.1 Remote start/stop mode...................................................................................................................................................................................................... 28
USER MANUAL 4189341228C EN Page 2 of 34
7.2 Deep sleep mode.....................................................................................................................................................................................................................297.3 Manual mode..............................................................................................................................................................................................................................29
8. Alarms8.1 Alarms........................................................................................................................................................................................................................................... 30
9. Troubleshooting9.1 Troubleshooting.......................................................................................................................................................................................................................33
USER MANUAL 4189341228C EN Page 3 of 34
1. Introduction
1.1 About SGC 110
This document presents information necessary for operating DEIF's SGC 110 genset controller.
SGC 110 is a modern genset controller with user friendly HMI and full graphics LCD. The controller comes with a highly versatilesoftware. Extensive inputs and outputs support a wide variety of industry standard features in diesel/gasoline genset applications.
The DEIF Smart Connect software offers flexibility to configure each individual input and output for a specific function or application.All parameters can also be configured on the controller.
1.2 Key functions
• Genset controller with configurable inputs:◦ Five digital inputs◦ Three analogue inputs
• Six digital outputs• Monitors and controls the genset performance effectively• Monitors genset output voltage and frequency precisely• Remote start/stop• Deep sleep mode to extend the battery lifetime• Pre-heat output for assisting engine start• PC connectivity via USB port for customised configuration• Backlit full graphics display with power saving feature• Log with the latest 30 events
1.3 Product overview
Following table gives a brief overview of SGC 110 features:
Features Specifications
Digital switch input 5
Analogue resistive inputs 3
DG alternator voltage input, D+ charging alternator I/O Yes
Digital outputs 6
Event logs Yes
USB I/O port for laptop access Yes
DC battery supply voltage (with -32 V reverse protection) 8 to 28 V
Operating temperature range -20 to 65 °C
Protection class with gasket (included) IP65
USER MANUAL 4189341228C EN Page 4 of 34
1.4 Passwords
The controller is protected from set-up changes with a four digit password.
There are two password levels:
Level Access Factory setting
1 Full access (read and write) 0123
2 Limited access (read) 1234
The passwords can be changed on the controller:1. Go to Configuration mode.2. Log on with password level 1.
3. Use the Up and Down buttons to go to Misc Settings, select with the Start button.
4. Use the Up and Down buttons to go to the password to be changed, select with the Start button.
5. Use the Up and Down buttons to choose the first digit for the new password, select with the Start button.6. Repeat for the next three digits.7. When all four digits are chosen, the display shows
PASSWORD 1
Password changed
1.5 Overview of controller buttons
1. Menu navigation up button2. Menu navigation down button3. Stop/Config button4. Display5. Alarm LED6. Start button7. Mode selection button
USER MANUAL 4189341228C EN Page 5 of 34
Button functionsIn Mode Button input Function
Manual Start Starts the engine
Manual
Stop Stops the engine
Stop (long press) Enters Configuration mode
Down + Stop (long press) Enters Programming mode
ManualAutoConfiguration
UpDown Scrolls through the views/parameters
ManualAuto Up + Down (during Alarm view) Acknowledges and clears the alarm
Configuration Start Selects/saves the parameter
Configuration Up + Down (long press) Enters the Event log page
Configuration Stop (long press) Back to Manual mode
Deep sleep Any Key (for min. 1 s) Back to Manual mode
Event log page Up + Down (long press) Back to Configuration mode
Programming Up + Down (long press) Enters Manual mode
1.6 Legal information
WarrantyWARNINGThe controller is not to be opened by unauthorised personnel. If the controller is opened anyway, the warranty will be lost.
DisclaimerDEIF takes no responsibility for installation or operation of the generator set. If there is any doubt about how to install or operate theengine/generator controlled by the SGC controller, the company responsible for the installation or the operation of the set must becontacted.
DEIF A/S reserves the right to change any of the contents of this document without prior notice.
The English version of this document always contains the most recent and up-to-date information about the product. DEIF does nottake responsibility for the accuracy of translations, and translations might not be updated at the same time as the English document.If there is a discrepancy, the English version prevails.
Copyright© Copyright DEIF A/S 2020. All rights reserved.
USER MANUAL 4189341228C EN Page 6 of 34
2. Safety instructions
2.1 General safety instructions
This document includes important instructions that should be followed during installation and maintenance of the controller.
Installation and maintenance must only be carried out by authorised personnel, and always in accordance with all applicable stateand local electrical codes. Efficient and safe operation of the controller can be acquired only if the equipment is correctly operated,configured and maintained.
The following notations found in this document can indicate potentially hazardous conditions to the operator, service personnel orthe equipment.
NOTE Highlights an essential element of a procedure to ensure correctness.
CAUTIONIndicates a procedure or practice, which could result in damage or destruction of equipment, if not strictly observed.
WARNINGIndicates a procedure or practice, which could result in injuring personnel or loss of life, if not followed correctly.
2.2 Electrical safety
• Electric shock can cause severe personal injury or death.• Ensure that the genset is grounded before performing any installation or service.• Generators produce high electrical voltages, and direct contact with it can cause fatal electrical shock. Prevent contact with
terminals, bare wires, connections, etc., while the generator and related equipment are running. Do not tamper with interlocks.• To handle the maximum electrical current, the wires used for electrical connections and wirings must be of appropriate size.
2.3 In operation safety
• Before installing the controller, ensure that all power voltage supplies are positively turned off at the source. Disconnect thegenerator’s battery cables and remove the panel fuse to prevent accidental start up. Disconnect the cable from the battery post,indicated by a NEGATIVE, NEG, or (–) first. Reconnect the negative cable last. Failure to do so will result in hazardous andpossibly fatal electrical shock.
• Remove the electric power supply before removing the controller or touching other electrical parts.• Use extreme caution when working on electrical components. High voltage can cause injury or death.• With floors of metal or concrete, use rubber insulation mats placed on dry wood platforms when working near the generator or
other electrical equipment.• Do not wear damp clothing (particularly wet shoes) or allow skin surface to be damp when handling electrical equipment.• Do not operate any electrical device or wires while standing in water, while barefoot, or while hands or feet are wet. It may result
in severe electrical shock.• Do not wear jewellery. Jewellery can cause a short circuit within electrical contacts and cause shock or burning.
In case of an accident caused by electric shock, immediately shut down the electrical power source. If this is not possible, try torelease the victim from the live conductor. Avoid direct contact with the victim. Use a non-conducting object (for example a rope or awooden stick) to release the victim from the live conductor. If the victim is unconscious, apply first aid and get immediate medicalhelp.
USER MANUAL 4189341228C EN Page 7 of 34
3. Technical_specifications
3.1 Terminals
The SGC 110 uses two types of terminal blocks:
Connectors of 3.5 mm pitch Connectors of 5.08 mm pitch
Table 3.1 Terminals
Connector type Pitch Male (on controller)* Female (mating part)* Quantity
4-pin 3.5 mm 5441294 5441223 2
6-pin 3.5 mm 5441317 5441249 1
8-pin 3.5 mm 5441320 5441252 1
10-pin 3.5 mm 5443962 5447560 1
2-pin 5.08 mm 5447353 5441980 1
4-pin 10.16 mm 5474274 5453499 1
*Note: Phoenix (Phoenix Contact (I) Pvt. Ltd.)
3.2 Power supply
Category Specification
Controller terminals 1 (Ground)2 (Battery or DC+)
Supply voltage range Nominal voltage: 12/24 V DCOperating range: 8 to 28 V DC
Cranking drop out period 50 ms
Maximum reverse voltage protection -32 V DC
Measurement accuracy (battery voltage) ±1 % full scale
Resolution 0.1 V
Maximum current consumption ~ 200 mA, 12/24 V DC (excluding the current load for the DCoutputs)
Standby current consumption (LCD backlight off) 124 mA, 12 V DC123 mA, 24 V DC
Deep sleep current 20 mA, 12/24 V DC
USER MANUAL 4189341228C EN Page 8 of 34
3.3 Genset voltage and frequency measurements
Category Specifications
Controller terminals
27 (Neutral)28 (L3)29 (L2)30 (L1)
Measurement type True RMS
Phase-to-neutral voltage 32 to 300 V AC RMS
Phase-to-phase voltage 32 to 520 V AC RMS
Voltage accuracy ±2 % of full scale for phase-to-phase
Voltage resolution 1 V AC RMS for phase-to-neutral2 V AC RMS for phase-to-phase
Frequency range 5 to 75 Hz
Frequency accuracy 0.25 % of full scale
Frequency resolution 0.1 Hz
NOTE For single phase applications, it is mandatory to connect the genset phase and neutral cables to the genset controller'sphase L1 and neutral terminals.
3.4 Digital inputs
Category Specifications
Controller terminals 10, 11, 12, 21, 22
Number of inputs 5
Type Negative sensing (connect to ground for activation)
Software configurable options Low Lub Oil Pressure (LLOP) Switch, High Water Temperature, and more(see Controller overview, Configurable parameters in the User manual formore details).
3.5 Analogue resistive sensor inputs
Category Specifications
Controller terminals 24 (Engine temperature)25 (Fuel level sensor)26 (Oil pressure)
Number of inputs 3
Type Ratio-metric sensing
Range 10 to 5000 Ω (terminal 24)10 to 1000 Ω (terminal 25 and 26)
Open circuit detection Above 5.5 kΩ (terminal 24)Above 1.5 kΩ (terminal 25 and 26)
Measurement accuracy ±2% of full scale (up to 1000 Ω)
Connection method Connect the sensor output terminals between the gensetcontroller terminal and the battery ground terminal
USER MANUAL 4189341228C EN Page 9 of 34
SCP connectionSCP connections for Analogue inputs 1 to 3*:
BatteryEngine body
Sensorinput
Sensorcommon
Terminal 41
Terminal 2
Terminal 1Supply
SGC 1xx series
Analogueresistive
sensor
*SCP connections for Analogue input 2 used as Fuel level sensor with the reference configured as Battery Negative
Battery
Sensorinput
Sensorcommon
Terminal 2
Terminal 1SupplyAnalogue
resistivesensor
SGC 1xx series
3.6 Analogue inputs used as digital inputs
Analogue inputs can be used as digital inputs when wired as shown.
F1
8-28V DC
+
-
3.7 D+ Charger alternator
Category Specifications
Controller terminal 7
Voltage range 0 to VBATTVBATT = 8 to 28 V DC
Excitation PWM (power limited to 3 W, 12 V/250 mA)
Accuracy ±1 % of full scale
USER MANUAL 4189341228C EN Page 10 of 34
The charge fail is a combined input and output terminal. When the genset starts, the terminal provides controlled power output toexcite the charging alternator. After the excitation is successfully done, the controller reads the charging alternator's output voltagefor monitoring its health. The action for charge fail is configurable.
3.8 Sensor common point
Category Specifications
Controller terminal 41
Range ±2 V
Accuracy ±2 % of full scale
NOTE The sensor common point (SCP) terminal 41 of the controller should be directly connected to an electrically sound point onthe engine body. This point on the engine body should serve as a common reference point for all analogue sensors such asthose for measuring lube oil pressure, engine temperature and fuel level. The electrical cable used for the connectionshould not be shared with any other electrical connection. Such a wiring practice is strongly recommended to ensure thatthere is negligible potential difference, if any, between the engine body and the controller's SCP terminal, and, predictableand accurate analogue sensor measurements are always available in a wide variety of field conditions.
3.9 Digital outputs
Category Specifications
Controller terminals 3, 4, 5, 6, 8, 9
Number of outputs 6
Type DC outputs
Maximum current rating Max. per output: 500 mATotal max.: 1 A
Software configurable options Start relay, Fuel relay and many more (see Controller overview,Configurable parameters for more details).
NOTE • Do not connect the starter motor relay and the stop solenoid directly to the controller's output terminals.• Genset and mains contactor latching relays should be compiled against 4 kVA surge as per IEC-61000-4-5 standard.
3.10 Communication ports
Category Specifications
USB USB 2.0 type B for connection to PC with DEIF Smart Connect software.
USER MANUAL 4189341228C EN Page 11 of 34
4. Installation
4.1 Dimensions
139.0 (5.47)
114.
0 (4
.49)
38.3(1.51)
38.3
(1.5
1)
Length Height Depth
Controller 139.0 mm (5.47 in) 114.0 mm (4.49 in) 38.3 mm (1.51 in)
Panel cut-out 118.0 mm (4.65 in) 93.0 mm (3.66 in) Tolerance: ± 0.3 mm (0.01 in)
4.2 Mounting in panel
To mount the controller into the panel, use the fixing clips provided along with the controller.
1. Panel surface.2. Mounting clips.
a. Insert the mounting clips into the slots on the controller.b. Press the mounting clips backwards until they "click" in place.c. Turn the screws to tighten the mounting clips (max. torque: 0.19 Nm).
CAUTIONOver-tightening the screw may damage the controller casing.
USER MANUAL 4189341228C EN Page 12 of 34
4.3 Terminal details
Rear view of the controller with terminal details.
USB
Terminal Text Description Phoenix connector
1 GND Power ground 5441980
2 BATT + Power supply positive
3 DIG OUT A DC output - A
5441223 4 DIG OUT B DC output - B
5 DIG OUT C DC output - C
6 DIG OUT D DC output - D
7 D+ CHG ALT Input for charging alternator control
5441223 8 DIG OUT E DC output - E
9 DIG OUT F DC output - F
10 DIG IN A Input from switch - A
11 DIG IN B Input from switch - B
5441249
12 DIG IN C Input from switch - C
13 Reserved -
14 Reserved -
15 Reserved -
16 Reserved -
17 Reserved -
5447560
18 Reserved -
19 Reserved -
20 Reserved -
21 DIG_IN D Input from switch - D
22 DIG_IN E Input from switch - E
23 Reserved -
24 ANLG_IN ENG_TEMP Analogue input from Engine temperature sensor
25 ANLG_IN FUEL_LEVEL Analogue input from Fuel level sensor
26 ANLG_IN LOP Analogue input from Lube oil pressure sensor
USER MANUAL 4189341228C EN Page 13 of 34
Terminal Text Description Phoenix connector
27 GEN_V–IN NTRL Voltage input from Generator Neutral
5453499 28 GEN_V–IN L3 Voltage input from Generator phase L3
29 GEN_V–IN L2 Voltage input from Generator phase L2
30 GEN_V–IN L1 Voltage input from Generator phase L1
31 Reserved -
32 Reserved -
33 Reserved -
34 Reserved -
35 Reserved -
5441456
36 Reserved -
37 Reserved -
38 Reserved -
39 Reserved -
40 Reserved -
41 SCP Sensor common point
42 Reserved -
USER MANUAL 4189341228C EN Page 14 of 34
4.4 Typical wiring diagram
Figure 4.1 SGC 110 typical wiring
G
24 4125 26
10 11 12 21 2227 28 29 30
+ ‐
‐
+
+
‐
3 4 5 6 8 9 71 2
Enginebody
F1
Supply Analogue inputs
DC
(+)
DC
(-)
D+
Inpu
t
Inpu
t
Inpu
tU
SBDigital inputs(configurable)
InInInInIn
AC voltagegenset
N L3 L2 L1
F4
GB
L1
L2
L3
N
L1
L2
L3
N
Outputs
Out
put
Out
put
Out
put
Out
put
Out
put
Out
put
G D+
B+
Sens
orco
mm
on
Enginebody
NOTE • Fuses:◦ F1: 5 A◦ F4: 2 A
• Wiring diagrams are examples. Use the application's wiring diagram during installation.• Genset and mains contactor latching relays should be compiled against 4 kV surge as per IEC-61000-4-5 standard.• Relay cards used with the controller should be protected against reverse battery voltages.• Analogue input 2 used for Fuel level sensor can be wired with the reference to Battery Negative, see Specifications,
Analogue resistive sensor inputs.• If a digital output is connected to a relay, the relay must include freewheeling diodes.
USER MANUAL 4189341228C EN Page 15 of 34
5. Monitoring mode
5.1 Monitoring mode
In Monitoring mode, the display views shift automatically after a pre-defined time. This delay time can be configured in theconfiguration menu.
The views can also be changed manually with the Up and Down buttons.
Engine status and operating mode
Manual mode Auto mode Generator voltage
Engine battery voltage Engine temperature Engine lube oil pressure
Engine remaining fuel Engine speed Engine run time
Alarms (example) Product info
USER MANUAL 4189341228C EN Page 16 of 34
6. Configuration mode
6.1 Configuration mode
To configure the controller, follow these steps:
1. Press and hold the Stop/Config button for at least three seconds.2. The display shows
3. To see the configuration, press the Stop/Config button. To change the configuration, press the Start button.4. The display shows
PASSWORD
5. To enter the the four digit password:
• Scroll through the digits with the Up and Down buttons.
• Select a digit with the Start button.
6. To leave the Configuration mode, press and hold the Stop/Config button.7. Until the configuration is saved, the display shows
6.2 Configurable parameters
6.2.1 Configurable parameters
The tables give an overview of configurable parameters.
Level 1 (table titles) and Level 2 texts are shown twice:• DEIF Smart Connect software: Normal sentence case, for example Power on Mode.• Controller display: Capital case in brackets, for example (POWER ON MODE)
USER MANUAL 4189341228C EN Page 17 of 34
6.2.2 Module
Table 6.1 General (GENERAL)
Level 2 Range
Profile name Profile 1
Power on Mode(POWER ON MODE)
ManualAuto
Power on Lamp Test(POWER ON LAMP TEST)
EnableDisable
Deep Sleep Mode(DEEP SLEEP MODE)
EnableDisable
Auto-Clear Warning Alarm(AUTO CLEAR WARNINGS)
EnableDisable
Language(LANGUAGE SUPPORT)
EnglishChinese
Table 6.2 Display (DISPLAY)
Level 2 Range
Contrast(CONTRAST) 0 to 100 %
Power Save Mode(POWER SAVE MODE)
EnableDisable
6.2.3 Digital inputs
Table 6.3 Digital Input # (DIG IN #)
Level 2 Range
Source(SOURCE) See Digital input source selection in this document
Name(NAME) Auxiliary Input #
Polarity(POLARITY)
Close to ActivateOpen to Activate
Action(ACTION)
NoneNotificationWarningElectrical TripShutdown
Activation(ACTIVATION)
NeverFrom Engine StartFrom Monitoring OnAlways
Activation Delay(ACTIVATION DELAY) 0 to 60 s
USER MANUAL 4189341228C EN Page 18 of 34
6.2.4 Analogue inputs
Table 6.4 Analogue Input 1 (ENG TEMP / DIG G)
Level 2 Range
Use Input As(SENSOR SELECTION)
Not usedDigital Input GEngine Coolant Temperature Sensor
(Digital) Source((DIG) SOURCE) See Digital input source selection in this document
Name(NAME) Auxiliary Input G
(Digital) Polarity((DIG) POLARITY)
Close to ActivateOpen to Activate
(Digital) Action((DIG) ACTION)
NoneNotificationWarningElectrical TripShutdown
(Digital) Activation((DIG) ACTIVATION)
NeverFrom Engine StartFrom Monitoring OnAlways
(Digital) Activation Delay((DIG) ACTIVATION DELAY) 1 to 60 s
(ETS) Circuit Fault Action(OPEN CKT ALARM)
NoneNotificationWarningElectrical TripShutdown
(ETS) Engine Temperature Sensor Calibration Table Resistance: 0 to 1000 ΩTemperature: 25 to 300 °C
Table 6.5 Analogue Input 2 (FUEL LVL / DIG H)
Level 2 Range
Use Input As(SENSOR SELECTION)
Not usedDigital Input HFuel Level Sensor
(Digital) Source((DIG) SOURCE) See Digital input source selection in this document
Name(NAME) Auxiliary Input H
(Digital) Polarity((DIG) POLARITY)
Close to ActivateOpen to Activate
(Digital) Action((DIG) ACTION)
NoneNotificationWarningElectrical TripShutdown
(Digital) Activation((DIG) ACTIVATION)
NeverFrom Engine Start
USER MANUAL 4189341228C EN Page 19 of 34
Level 2 Range
From Monitoring OnAlways
(Digital) Activation Delay((DIG) ACTIVATION DELAY) 1 to 60 s
(FLS) Low Fuel Level Shutdown(SHUTDOWN)
EnableDisable
(FLS) Shutdown Threshold(SHUTDOWN THRESHOLD) 0 to 78 %
(FLS) Low Fuel Level Notification(NOTIFICATION)
EnableDisable
(FLS) Notification Threshold(NOTIFICATION THRESHOLD) 2 to 80 %
(FLS) Fuel Tank Capacity(FUEL TANK SIZE) 2 to 1000 litre
(FLS) Fuel Theft Warning(FUEL THEFT ALARM)
EnableDisable
(FLS) Fuel Theft Alarm Threshold(FUEL LVL THRESH) 1 to 100 % per hour
(FLS) Circuit Fault Action(OPEN CKT ALARM)
NoneNotificationWarningElectrical TripShutdown
(FLS) Fuel Sensor Reference(FUEL LVL REF)
Battery NegativeEngine Body
(FLS) Fuel Level Sensor Calibration Table Resistance: 0 to 1000 ΩFuel level: 0 to 100 %
Table 6.6 Analogue Input 3 (LOP / DIG F)
Level 2 Range
Use Input As(SENSOR SELECTION)
Not usedDigital Input FLube Oil Pressure
(Digital) Source((DIG) SOURCE) See Digital input source selection in this document
Name(NAME) Auxiliary Input F
(Digital) Polarity((DIG) POLARITY)
Close to ActivateOpen to Activate
(Digital) Action((DIG) ACTION)
NoneNotificationWarningElectrical TripShutdown
(Digital) Activation((DIG) ACTIVATION)
NeverFrom Engine StartFrom Monitoring OnAlways
USER MANUAL 4189341228C EN Page 20 of 34
Level 2 Range
(Digital) Activation Delay((DIG) ACTIVATION DELAY) 1 to 60 s
(LOP) Circuit Fault Action(OPEN CKT ALARM)
NoneNotificationWarningElectrical TripShutdown
(LOP) Lube Oil Pressure Sensor Calibration Resistance: 10 to 100 ΩPressure: 1.0 to 10.0 bar
6.2.5 Outputs
Table 6.7 Outputs # (OUT #)
Level 2 Range
Source(SOURCE) See Digital output source selection in this document
On Activation(ON ACTIVATION)
EnergiseDe-energise
6.2.6 Timers
Table 6.8 Cranking (CRANKING TIMERS)
Level 2 Range
Crank Hold Time(CRANK HOLD TIME) 1 to 15 s
Crank Rest Time(CRANK REST TIME) 2 to 60 s
Manual Start Delay(MANUAL START DELAY) 0 to 300 s
Auto Start Delay(AUTO START DELAY) 0 to 43200 s
Table 6.9 General (GENERAL TIMER)
Level 2 Range
Safety Monitoring Delay(SAFETY MONITOR DELAY) 10 to 60 s
Mains Detect Delay(MAINS DETECT DELAY) N/A
Alternator Detect Delay(ALT DETECT DELAY) 1 to 30 s
Warm-Up Delay(WARM-UP DELAY) 0 to 60 s
Return To Mains Delay(RETN-TO-MAINS DELAY) N/A
Engine Cooling Time(ENG COOL TIME) 0 to 300 s
USER MANUAL 4189341228C EN Page 21 of 34
Level 2 Range
Stop Action Time(STOP ACTION TIME) 10 to 120 s
Additional Stopping Time(ADDN STOPPING TIME) 0 to 120 s
Load Transfer Delay(LOAD TRANSFER DELAY) 0 to 60 s
Power Save Mode Delay(PWR SAVE MODE DELAY) 5 to 1800 s
Screen Changeover Time(SCRN CHNGOVER TIME) 1 to 1800 s
Deep Sleep Mode Delay(DEEP SLP MODE DELAY) 5 to 1800 s
Sounder Alarm Time(SOUNDER ALARM TIMER) 1 to 300 s
Auto Exit Config Mode(AUTO EXIT CNFG MODE) 10 to 1800 s
6.2.7 Generator
Table 6.10 Alternator configuration (ALT CONFIG)
Level 2 Range
Alternator Present(ALT PRESENT)
YesNo
Number of Poles(NUMBER OF POLES) 2/4/6/8
AC system(ALT AC SYSTEM)
1 phase3 phase
Min Healthy Voltage(MIN HEALTHY VOLT) 50 to 350 V phase-neutral
Min Healthy Frequency(MIN HEALTHY FREQ) 10 to 75 Hz
Phase Reversal Detection(PHASE REVERSAL DETECT)
EnableDisable
Phase Reversal Action(PHASE REVERSAL ACTION)
NoneNotificationWarningElectrical TripShutdown
Auto Load Transfer(AUTO LOAD TRANSFER)
EnableDisable
Table 6.11 Voltage Monitoring (VOLT MONITOR)
Level 2 Range
Under-voltage Shutdown(UNDER VOLT SHUTDOWN)
EnableDisable
Under-voltage Shutdown Threshold(UV SHUTDOWN THRESH) 50 to 295 V phase-neutral
USER MANUAL 4189341228C EN Page 22 of 34
Level 2 Range
Under-voltage Warning(UNDER VOLT WARNING)
EnableDisable
Under-voltage Warning Threshold(UV WARNING THRESHOLD) 55 to 300 V phase-neutral
Over-voltage Shutdown(OVER VOLT SHUTDOWN)
EnableDisable
Over-voltage Shutdown Threshold(OV SHUTDOWN THRESH) 105 to 350 V phase-neutral
Over-voltage Warning(OVER VOLT WARNING)
EnableDisable
Over-voltage Warning Threshold(OV WARNING THRESHOLD) 100 to 345 V phase-neutral
Table 6.12 Frequency Monitoring (FREQ MONITOR)
Level 2 Range
Under-frequency Shutdown(UNDER FREQ SHUTDOWN)
EnableDisable
Under-frequency Shutdown Threshold(UF SHUTDOWN THRESH) 10.0 to 59.0 Hz
Under-frequency Warning Enable(UNDER FREQ WARNING)
EnableDisable
Under-frequency Warning Threshold(UF WARNING THRESHOLD) 11.0 to 60.0 Hz
Over-frequency Shutdown Enable(OVER FREQ SHUTDOWN)
EnableDisable
Over-frequency Shutdown Threshold(OF SHUTDOWN THRESH) 26.0 to 75.0 Hz
Over-frequency Warning Enable(OVER FREQ WARNING)
EnableDisable
Over-frequency Warning Threshold(OF WARNING THRESHOLD) 25.0 to 74.0 Hz
6.2.8 Engine
Table 6.13 Crank Disconnect (CRANK DISCONN)
Level 2 Range
Start Attempts(START ATTEMPTS) 1 to 9
Disconnect on Oil Pressure Sensor(DISCONN ON LOP SENS)
EnableDisable
Monitor Pressure Sensor Before Crank(MON LLOP BEF CRANK)
EnableDisable
Pressure Sensor Monitoring Threshold(DISCONN LOP SENS) 0.5 to 10.0 bar
Monitor Pressure Switch Before Crank(MON LOP BEF CRANK)
EnableDisable
USER MANUAL 4189341228C EN Page 23 of 34
Level 2 Range
Disconnect on Oil Pressure Switch(DISCONN ON LLOP SW)
EnableDisable
Pressure Switch Transient Time(LLOP SW TRANS TIME) 0.0 to 3.0 s
Crank Disconnect At Alt Frequency(ALT FREQUENCY) 10 to 70 Hz
Crank Disconnect At Engine Speed(ENGINE SPEED) 150 to 4000 RPM
Disconnect On Charging Alt Voltage(DISC ON CHG ALT VOLT)
EnableDisable
Charging Alt Disconnect Volt Threshold(CHG ALT THRESHOLD) 5.0 to 30.0 V
Table 6.14 Speed Monitoring (SPEED MONITOR)
Level 2 Range
Engine Speed Sense Source(SPEED SENSE SOURCE) Alternator frequency
Flywheel Teeth (Magnetic Pickup) N/A
W-Point Frequency@ 1500 N/A
Under-speed Shutdown(UNDER SPEED SHUTDOWN)
EnableDisable
Under-speed Threshold(UNDER SPEED THRESH) 0 to 3600 RPM
Under-speed Delay(UNDER SPEED DELAY) 1 to 60 s
Over-speed Threshold(OVER SPEED THRESH) 700 to 4000 RPM
Over-speed Delay(OVER SPEED DELAY) 1 to 20 s
Gross Over-speed Threshold(GROSS OS THRESHOLD) 100 to 200 %
Table 6.15 Battery Monitoring (BATTERY MONITOR)
Level 2 Range
Low Battery Voltage Action(LOW VOLT ACTION)
NoneNotificationWarningElectrical TripShutdown
Low Battery Voltage Threshold(LOW VOLT THRESHOLD) 8.0 to 31.0 V
Low Battery Voltage Delay(LOW VOLT DELAY) 5 to 1800 s
High Battery Voltage Action(HIGH VOLT ACTION)
NoneNotificationWarningElectrical Trip
USER MANUAL 4189341228C EN Page 24 of 34
Level 2 Range
Shutdown
High Battery Voltage Threshold(HIGH VOLT THRESHOLD) 9.0 to 32.0 V
High Battery Voltage Delay(HIGH VOLT DELAY) 5 to 1800 s
Table 6.16 Charging Alternator Monitoring (CHARGE ALT MON)
Level 2 Range
Charging Alternator Fail Action(FAIL ACTION)
NoneNotificationWarningElectrical TripShutdown
Charging Alternator Fail Threshold(FAIL THRESHOLD) 0.0 to 35.0 V
Charging Alternator Fail Delay(FAIL DELAY) 5 to 60 s
Table 6.17 Preheating (PREHEAT)
Level 2 Range
Pre-heat Timer(PREHEAT TIMER) 1 to 900 s
Engine Temperature(ENG TEMP EN)
EnableDisable
Engine Temperature Threshold(ENG TEMP LIMIT) 10 to 300 °C
6.2.9 Maintenance
Table 6.18 Maintenance (MAINT ALARM)
Level 2 Range
Alarm Action(ACTION)
NoneNotificationWarning
Due At Engine Hours(DUE AT ENGINE HOURS) 10 to 65000 hours
Alarm Due Date(ALARM DUE DATE) dd/mm/yyyy
6.2.10 Password ID
Table 6.19 ID
Level 1 Level 2 Range
(PASSWORD 1) #### Numbers: 0 to 9
(PASSWORD 2) #### Numbers: 0 to 9
USER MANUAL 4189341228C EN Page 25 of 34
6.3 Digital input source selection
No. Input source
1 Not Used
2 User Configured
3 Low Fuel LVL Switch
4 Low Lube Oil Press Switch
5 High Engine Coolant Temp Switch
6 Low Water LVL Switch
7 Emergency Stop
8 Remote Start/Stop
9 Simulate Start
10 Simulate Stop
11 Simulate Auto
12 Close Gen/Open Mains Switch
13 Close Mains/Open Gen Switch
14 Reserved1
15 V-Belt Broken Switch
6.4 Digital output source selection
No. Output source
1 Disable
2 Sounder Alarm
3 Battery Over Volt
4 Battery Under Volt
5 Charge Alt Shutdown
6 Charge Alt Warning
7 Configurable
8 Configurable
9 Reserved1
10 Common Alarm
11 Common Electrical Trip
12 Common Shutdown
13 Common Warning
14 Cooling Down
15 Dig In A
16 Dig In B
17 Dig In C
18 Dig In D
19 Dig In E
USER MANUAL 4189341228C EN Page 26 of 34
No. Output source
20 Dig In F (Anlg In LOP 1)
21 Dig In G (Analog Eng Temp)
22 Dig In H (Anlg In Fuel LVL)
23 Reserved2
24 Emergency Stop
25 Stop Solenoid
26 Fail To Start
27 Fail To Stop
28 Fuel Relay
29 Gen Available
30 L1 Phase OV Shutdown
31 L1 Phase UV Shutdown
32 L2 Phase OV Shutdown
33 L2 Phase UV Shutdown
34 L3 Phase OV Shutdown
35 L3 Phase UV Shutdown
36 Reserved3
37 High Engine Coolant Temp
38 Low Fuel LVL
39 Low LOP
40 Reserved4
41 Reserved5
42 Oil Pressure Open Circuit
43 Open Gen Contactor
44 Configurable
45 Over Freq Shutdown
46 Over Speed Shutdown
47 Gross Over Speed Shutdown
48 Start Relay
49 Temp Sensor Open Circuit
50 Under Freq Shutdown
51 Under Speed Shutdown
52 Maintenance Due
53 Stop Mode
54 Auto Mode
55 Manual Mode
56 Preheat Output
USER MANUAL 4189341228C EN Page 27 of 34
7. Running modes
7.1 Remote start/stop mode
To use the Remote start/stop mode, configure one of the digital input as Remote start/stop (Latched type input) and set thecontrollerto Auto mode.
To start or stop the genset while in Remote start/stop mode, activate/deactivate (continuous signal) the pre-configured Remote start/stop input. The controller latches the genset contactor when the controller confirms that all the engine and genset parameters arewithin the configured thresholds. When the pre-configured input is deactivated the controller opens the genset contactor.
USER MANUAL 4189341228C EN Page 28 of 34
7.2 Deep sleep mode
Deep sleep mode is a useful feature to prolong the battery life. In this mode, normal functions of the controller are suspended andthe controller is placed in its lowest power consumption state. The controller maintains the status and alarms it had before Deepsleep mode. When the controller wakes up, normal operations are resumed automatically.
The controller goes in Deep sleep mode when there is no user interaction for the preset Deep sleep mode delay. In Auto mode, ifRemote start/stop is configured to a digital input, the controller wakes up after receiving a Remote start command.
Press and hold any key for at least one second to come out of Deep sleep mode.
7.3 Manual mode
• Inputs: Stop pressed, Start pressed, Simulate start, Simulate stop, Estop, Electric trip, Shutdown, Warning, LLOP, Auto loadtransfer.
• Outputs: flag_start, flag_stop.
USER MANUAL 4189341228C EN Page 29 of 34
8. Alarms
8.1 Alarms
With SGC 110 it is possible to configure several Shutdown/Electrical trip, Warning and Notification alarms, for example Low oilpressure shutdown, Overload warning, and more.
An alarm occurs when a pre-configured parameter is out of the preset level. The Alarm LED flashes and the Sounder alarmactivates (if configured). The controller shows the alarm names on the Alarms display and the nature of alarm on Engine statusdisplay.
To acknowledge the alarms, press the Up and Down buttons simultaneously.
All the alarms are activated at the end of Safety monitoring timer. The controller will not send the start command if Warning,Electrical trip or Shutdown alarms are left unacknowledged.
Alarm typesNo. Alarm actions Description
1 Shutdown Load is taken off from the genset and the genset is immediately stopped by skipping theEngine cooling time.
2 Electrical trip Load is taken off from the genset, the Engine cooling timer begins, after which the gensetis stopped.
3 Warning Warning alarms draw the operator's attention to an undesirable condition without affectingthe genset's operation.The genset cannot be started without acknowledging the Warning alarms
4 Notification The controller shows the message on the display. The genset start/stop operation is notaffected.
Alarms and their causesNo. Alarms Causes/Indication Actions
1
Low Oil Pressure (Sensor) Indicates that the oil pressure measured is below thepreset threshold.
ShutdownWarning
Low Oil Pressure (Switch) Indicates that the oil pressure measured is low throughswitch.
ShutdownWarningElectrical TripNotification
2
Low Fuel level sensor Indicates that the amount of fuel level is below the presetthreshold.
ShutdownWarning
Low Fuel level switch Indicates that the amount of fuel level is below the presetthreshold.
ShutdownWarningElectrical TripNotification
3
High Eng Temp sensor Indicates that the engine temperature is above the presetthreshold. This condition is detected only when engine ison.
ShutdownWarning
High Eng Temp switch Indicates that the engine temperature measured is highthrough switch.
ShutdownWarningElectrical TripNotification
4 Low Water Level switch Indicates that radiator water level is below the presetthreshold.
ShutdownWarning
USER MANUAL 4189341228C EN Page 30 of 34
No. Alarms Causes/Indication Actions
Electrical TripNotification
5 Over Speed Indicates that genset speed has exceeded the presetoverspeed threshold. The genset will shut down afterOverspeed delay.
Shutdown
6 Gross Over Speed Indicates that genset speed has exceeded the presetGross overspeed threshold. The genset will shut downimmediately without any delay.
Shutdown
7 Under Speed The engine speed has fallen below the preset RPM. Shutdown
8 L1 Phase Over Voltage Indicates that genset (L1) phase voltage has exceeded thepreset over-voltage threshold.
ShutdownWarning
9 L1 Phase Under Voltage Indicates that genset (L1) phase voltage has fallen belowpreset under-voltage threshold.
ShutdownWarning
10 L2 Phase Over Voltage Indicates that genset (L2) phase voltage has exceeded thepreset over-voltage threshold.
ShutdownWarning
11 L2 Phase Under Voltage Indicates that genset (L2) phase voltage has fallen belowpreset under-voltage threshold.
ShutdownWarning
12 L3 Phase Over Voltage Indicates that genset (L3) phase voltage has exceeded thepreset over-voltage threshold.
ShutdownWarning
13 L3 Phase Under Voltage Indicates that genset (L3) phase voltage has fallen belowpreset under-voltage threshold.
ShutdownWarning
14 Over Frequency Indicates that genset output frequency has exceeded thepreset threshold.
ShutdownWarning
15 Under Frequency Indicates that genset output frequency has fallen below thepreset threshold.
ShutdownWarning
16 Emergency stop Configured as digital input has triggered longer than presetduration or when the immediate shutdown is required. Shutdown
17 Charge Fail The charge alternator voltage has dropped below thepreset threshold.
ShutdownWarningNotification
18 Battery Over Voltage The battery voltage has exceeded the preset threshold.
ShutdownWarningElectrical TripNotification
19 Battery Under Voltage The battery voltage has fallen below the preset threshold.
ShutdownWarningElectrical TripNotification
20 Maintenance due Indicates that engine running hours exceed the presethours limit or maintenance due date has occurred and filterservicing is required.
WarningNotification
21 Auxiliary input/User definedname
Configured auxiliary input has triggered longer than presetduration.
ShutdownWarningElectrical TripNotification
22 Fail to Stop It is detected that genset is still running after sending stopcommand. Shutdown
23 Fail to Start Indicates that genset has not started after the presetnumber of Start attempts. Shutdown
USER MANUAL 4189341228C EN Page 31 of 34
No. Alarms Causes/Indication Actions
24 Fuel theft The fuel consumption exceeds the preset threshold. Warning
25 Eng Temp/terminal 24 - CktOpn The temperature sensor is not detected (circuit open). Warning
26 Fuel Level Ckt Open The fuel level sensor is not detected (circuit open). Shutdown
27 LOP/terminal 26 - Ckt Opn The oil pressure sensor is not detected (circuit open). Warning
28 DG Phase Reversed Alternator phase sequence (L1-L2-L3) is not correct. ShutdownWarningElectrical Trip
29
High Oil Pressure sensor Indicates that the measured oil pressure is above thepreset threshold.
ShutdownWarning
High Oil Pressure switch Indicates that the measured oil pressure is above thepreset threshold.
ShutdownWarningElectrical TripNotification
USER MANUAL 4189341228C EN Page 32 of 34
9. Troubleshooting
9.1 Troubleshooting
This section explains the common faults, their possible causes and remedial actions.
General troubleshootingFault Action
The controller does not power ON.
• Check the battery voltage.• Check the fuse on the battery supply.• Check continuity between battery positive and controller terminal 2.• Check continuity between battery ground and controller terminal 1.
The controller display freezes or hangsup. • Reset the controller power.
The controller fails to crank-start theengine.
• Check the battery voltage.• Enter the Configuration mode in the controller and verify the configuration for the
Start output. Check that the Start output is working correctly by measuring itsoutput voltage.
• Enter the Configuration mode in the controller and verify the configuration of theCrank disconnect method.
• Verify the configuration of the LLOP Switch polarity. Ensure that the lube oilpressure switch and sensor are working OK. Check their wiring.
The Emergency Stop alarm is shownwithout the Emergency Stop is activated.
• Check if the Emergency stop switch is working OK, including the wiring.• Enter the Configuration mode in the controller and verify the configuration of the
Emergency stop polarity.
The controller generates unnecessaryShutdown alarms or Warning alarms.
• Check the respective switch, sensor and wiring.• Enter Configuration mode in the controller and verify the respective threshold
configuration.
The controller shows Charge fail alarm.
• To check if the controller's charging alternator terminal is working:◦ Disconnect the charging alternator wiring to the controller's terminal 7.◦ Short terminal 7 to the ground through a DC ammeter.◦ Crank-start the engine.◦ The DC ammeter should indicate the current in the range of 200 to 400 mA for
~30 seconds.◦ If yes, the controller's charging alternator terminal is working OK.
• Disconnect and re-connect the charging alternator connection to the controller'sterminal 7.
• Check if the charging alternator is working OK.
The controller shows Error C03.
Error C03 can occur if the controller is disconnected from the PC during aconfiguration.
1. Press and hold the Stop/Config button during a power cycle to reset thecontroller.
2. Re-send the configuration file.
The controller shows genset ON whilegenset is at rest.Fail to stop alarm when genset is at rest.
• Enter Configuration mode in the controller and verify the configuration for the LLOPand LOP, including the wiring.
• Ensure that Mains voltage wiring is not connected by mistake to the controller'sgenset voltage terminals.
The controller sends a Crank-startcommand immediately after power on.
• Ensure that the controller's output terminal is not directly connected to the starterrelay. The controller's output should be given to an intermediate relay which should
USER MANUAL 4189341228C EN Page 33 of 34
Fault Action
in-turn power the starter relay. The controller can get permanently damaged andwill need to be replaced if this precaution is not taken.
• Check the start-relay connection with the suitable controller terminal.• Enter the Configuration mode in the controller and verify the configuration for Start
mode and the Start relay output polarity.
The engine runs, but the controller showsgenset to be OFF.
• Check if the alternator voltage signal (L1 phase) is received by the controllerterminals.
• Check if the LOP and LLOP are working OK, including the wiring to the controller.
The controller shows incorrect reading forany of LOP, fuel level or temperaturesensors.
• Check the respective sensor and its wiring.• Enter the Configuration mode in the controller and verify the calibration for the
respective sensor in the configuration.
The controller shows incorrect engineRPM. Check the wiring from the main alternator’s L1 phase and neutral to the controller.
The controller shows incorrect enginetemperature/Lube oil pressure. Check the wiring between the controller's terminal 41 (SCP) and the engine body
The controller shows incorrect fuel level.
Enter Configuration mode, check if the Fuel analogue input configuration for the Fuelsensor reference is like the physical connection. For example, if the configuration isset as Battery negative the connection of the fuel sensor negative must be on batterynegative.
USER MANUAL 4189341228C EN Page 34 of 34