PCSHK1531 All rights reserved 09/15 SS c 1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced. 2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor. Cautions on product corrosion Warning Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion. Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion. Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings. If you have any enquiries, please contact your local importer, distributor and/or retailer. Specifications, designs and other content appearing in this brochure are current as of September 2015 but subject to change without notice.

Upload: others

Post on 30-Apr-2020

12 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

PCSHK1531

All rights reserved 09/15 SSc

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install

the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product by yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.Read the user's manual carefully before using this product. The user's manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

Specifications, designs and other content appearing in this brochure are current as of September 2015 but subject to change without notice.

Page 2: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

RNQ71MV1Outdoor unitIndoor unit FDMNQ71MV1

RNQ71MY1 RNQ90MV1FDMNQ90MV1

RNQ90MY1 RNQ100MV1FDMNQ100MV1

RNQ100MY1 RNQ125MY1FDMNQ125MV1

RNQ140MY1FDMNQ140MV1

RNQ60MV1 RNQ71MV1RNQ50MV1Outdoor unitIndoor unit

DUCT CONNECTION

LOW STATIC PRESSURE TYPE

MIDDLE STATIC PRESSURE TYPE

FDBNQ50MV1 FDBNQ60MV1 FDBNQ71MV1RNQ71MY1

RNQ71MY1RNQ60MV1RNQ50MV1Outdoor unitIndoor unit

CEILING SUSPENDED TYPE

FHNQ50MV1 FHNQ60MV1 FHNQ71MV1 FHNQ90MV1 FHNQ100MV1 FHNQ140MV1FHNQ125MV1

1 2

7160

RNQ60MV1 RNQ71MV1

50

RNQ50MV1

4025

Outdoor unitIndoor unit

CEILING MOUNTED CASSETTE TYPE

Round Flow

Series

Pair

FCNQ50MV1RNQ40MV1

FCNQ40MV1 FCNQ60MV1 FCNQ71MV1RNQ71MY1

90

RNQ90MV1FCNQ90MV1

RNQ90MY1

100

RNQ100MV1

RNQ71MV1 RNQ90MV1 RNQ100MV1

FCNQ100MV1RNQ100MY1

125

RNQ125MY1FCNQ125MV1

14026,00021,00018,000/17,700*113,0009,200Btu/h 30,000 36,000/35,000*2 42,600/42,000*2,3 48,000

7.66.25.3/5.2*13.82.7kW 8.8 10.6/10.4*2 12.5/12.3*2,3 14.1

RNQ140MY1

RNQ90MY1 RNQ100MY1 RNQ125MY1 RNQ140MY1

FCNQ140MV1

Outdoor unit

OUTDOOR UNIT

P r o d u c t L i n e u p

RNQ40MV1FHNQ40MV1

RNQ40MV1FDBNQ40MV1

RNQ25MV1FDBNQ25MV1

New wide lineup of SkyAir series

Note : *1Applicable to FDBNQ series. *2Applicable to FHNQ series. *3Applicable to FDMNQ series.

RNQ25MV1 RNQ40MV1 RNQ50MV1 RNQ60MV1 RNQ71MV1 RNQ71MY1 RNQ90MV1 RNQ90MY1 RNQ100MV1 RNQ100MY1 RNQ125MY1 RNQ140MY1

Page 3: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

Comfort enhanced by Round Flow!

Greater comfort

• Condition after exposure to the smoke of 600 cigarettes in 1 m3 enclosed space.

Treated surface

Untreated surface

Grimy surface

Resists soiling

External panels are treated with a coating that repels dirt

Avoids uneven temperature and discomfort caused by drafts

With uniform temperature distribution

360° airflow

To prevent dirt sticking to the external panels, they have been coated with a surface treatment

Because air flows out from corner outlets, comfort spreads more widely

Condensation does not easily form on and dirt does not cling to non-flocking flaps. It is easy to clean.

Non-flocking flapsPrevents mould and microorganisms growing out of the dust and moisture that adheres to the filters.

Filter has anti-mould and antibacterial treatment

Grime prevention and antibacterial coating: Make cleaning easier

Adapts easily to the installation space

Note: Whatever the discharge direction, the same type of panel is used. If installing for other than all-round flow, an air discharge outlet sealing material (option) must be used to close each unused outlet.

3-way flow L-shaped 2-way flow

Opposite 2-way flow

(E.g., installed in a corner)

(E.g., installed in a long room)

(E.g., installed near a wall)

(E.g., installed in middle of ceiling)

4-way flow also possible.

All-round flow

360° airflow can maintain comfort even if air discharge speed is lower.

Typical flow patterns There are a total of 23 flow patterns.

Velocity decreases by 25% when set temperature is raised 1℃ to 1.5℃.

Room remains comfortable even when set temperature is raised 1℃.

Operation sound increases when using 2-way or 3-way flow.

Enhanced Comfort

Air movement is gentle with Round Flow

Airflow distribution

creates uniform comfort throughout

the space.

Accessory required for indoor unit.Option

CEILING MOUNTED CASSETTE TYPE

FCNQ40/50/60/71/90/100/125/140MV1

Round Flow

BRC1E62

Navigation Remote Controller(Wired Remote Controller)

BRC7F633F

A signal receiver must be added to the indoor unit.

Wireless remote controller is supplied in a set with a signal receiver.

Wireless LCD remote controller

Signal receiver unit (Installed type)

Note: Remote controller cable is not included and must be procured locally.

Note: Remote controller cable is not included and must be procured locally.

Wired LCD remote controller

BRC1C61

3 4

Cassette air conditioner with 360° uniform airflow sets the standardCassette air conditioner with 360° uniform airflow sets the standard

43/32dB(A)FCNQ100M

(220V)

High Low

Sound pressure level

Page 4: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

Easier to maintain

With Ultra long-life filters (option), maintenance is not required in normal shops or offices for up to four years

The condition of the drain pan anddrain water can be checked byremoving the drain plug andsuction grille Drain plug

Just open the

suction grille!

Quick and easy to installJust 256 mm high. Installable in tight ceiling spaces (40-71M)

Fine square panels Compact body and quiet operationPanel size is same for all models.It is easy to maintain a neat appearance when multiple units are installed.

Optimal comfort and convenience assured by 2 air discharge modes

*Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room. **Wireless remote controller does not have a temperature-sensor.

Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control. This feature must be set during commissioning by the technicians.

Two selectable temperature-sensors

Note: 1Air direction is set to the standard position when the unit is shipped from the factory. The position can be changed from the remote controller.

2Closing of the corner discharge outlets is recommended.

Air direction

Auto air direction control

Settable to 5 different levels between 15° and 60°

Settable to 5 different levels between 25° and 60°

Auto-swing between15° and 60°

Auto-swing between25° and 60°

Recommended for shops with light coloured ceilings that

must be kept spotless.Standard position to

prevent draft.

Standard setting1 Setting to prevent soiling of ceiling2 (field setting)

The air direction is set automatically to the memorised position of the previous air direction.

Desired situation

Auto-swing

5-levelsair directionsetting

Even in spaces with high ceilings, a comfortable airflow is carried down to the floor level.

Suitable for high ceilings

When all round flow is selected, ceilings up to 4.2 m in height can be accommodated. (90M-140M)

Setting SettingStandard

4.2 m3.6

m3.2m

Number of air discharge outlets used

4-wayflow

3-wayflow

2-wayflow

4-wayflow

3-wayflow

2-wayflow

3.1 m3.4 m4.0 m

All round flow

2.7 m3.0 m3.5 m

3.0 m3.3 m3.5 m

3.5 m3.8 m-

3.4 m3.9 m4.5 m

All round flow

3.2 m3.6 m4.2 m

3.6 m4.0 m4.2 m

4.2 m4.2 m-

StandardCeiling height High ceiling

High ceiling

Criteria for ceiling height and number of air discharge outlets

Note: Factory settings are for standard ceiling height and all-round flow. High ceiling settings (1) and (2) are set with the remote controller by field setting.

90-140M40-71M

(Ceiling height is reference value)

Indoor unitHigh

Sound pressure levelLow

dB(A)

40/50M 31 2860/71M 35 2890/100M 43 32

125M 44 34140M 44 36

Same for all models

950 mm 950 mm

256 mm *1 266 mm *2

*1 298 mm high with 90-140M*2 308 mm high with 90-140M

All models can be installed without using lifter because of the light weight

Drain pump is equipped as standard accessory with 850 mm lift

Transparent drain socket

Since the orientation of the suction grille can be adjusted after installing,the direction of the suction grille lines can be unified when multiple units are installed.

Installable in any direction

Because the drain socket is transparent, after the drain piping has been installed, it is easy to check if the drain come out through the socket.

175 mm

850 mm

5 6

CEILING MOUNTED CASSETTE TYPE Round Flow

DIII-NET communication standardConnection to a centralised control system is available without option.

Each corner of the unit has an Adjuster Pocket that lets you easily adjust the unit's suspended height. Note: If the wireless remote controller is installed, a signal receiver unit is housed in one of the adjuster pockets.

Easy height adjustment

Options required for specific operating environments

Filter chamber (Can be used with ultra long-life filter)

High-efficiency filter

Filter chamber (Can be used with high-efficiency filter)

Ultra long-life filter

High-efficiency filter unitAvailable in two types: 65% and 90% colorimetry.

Please use if you think the temperature and humidity inside the ceiling exceeds 30°C and RH 80%, respectively.

Insulation kit for high humidity

Using this kit, a duct can be fitted to increase the intake of outdoor air.There are two chamber types that have intake in two places: with T-duct joint and without T-duct joint.

Fresh air intake kit

Even in dusty environments where the air conditioning is on most of the time, the ultra long-life filter only has to be cleaned once a year.

Ultra long-life filter unit

Panel spacerUse when only minimal space is available between drop ceilings and ceiling slabs.

Sealing material of air discharge outletSealing material block air discharge openings not used in 2-way or 3-way blow.

Outside

Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing your unit.

40mm

Panel spacer

Branch duct (direct-connection round duct)A round duct can be attached without the need for a chamber.A flanged port for direct connection of a round duct is provided. An existing branch duct chamber can also be fitted (square slit hole).

Dusty area: annual filter change

Ordinary store or office: filter change every 4 years

*For dust concentration of 0.3 mg/m3 (Requires separately sold Air purifier.) 1 year (Approx. 5,000 hr) 15 hr/day x 28 day/month x 12 month/year

*For dust concentration of 0.15 mg/m3

4 years (Approx. 10,000 hr) 8 hr/day x 25 day/month x 12 month/years x 4 years

1 Use of options will increase operating sound.2 Connecting ducts, fan, insect nets, fire dampers, air filters, and other parts

should, as required, be procured locally. 3 When a local-procured fan is used, an interlock with air conditioner is

necessary.Optional PCB(KRP1C63)is required for interlocking.4 It is recommended that the volume of outdoor air introduced through the kit is

limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating sound and may also influence temperature sending.

Note:

The units can be installed in the following different ways.

Intake duct(procured locally)

Direct installation type

Chamber type (with T-duct joint)

KDDP55X160

KDDP55B160K

Chamber type (without T-duct joint) Note 3.4

Note 3.4

KDDP55B160

Intake duct(procured locally)(duct length: 4 m max.)Connection

chamber

Suction chamber

Connection chamber

Suction chamberTop panel insulation(1)

Top panel insulation(2)Top panel insulation(3)Insulation for decoration panelSide panel insulation Suspension bracket insulation

Flexible duct(procured locally)

T-duct joint(procured locally)

Intake duct(procured locally)(duct length: 4 m max.)

Flexible duct

T-duct joint

Duct flange (with insulation material)

Note 1.2

Switchable fan speed: High/Low

Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

On/Off timer

Page 5: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

(mm)

Uses quiet stream fan and other quiet technologies.

Turbulent flow is reduced

Straightening plate

Quiet stream fan

50°

50/60M 44 4071/90M 45 40

100/125M 48 42140M 49 43

Indoor unitHigh

Sound pressure levelLow

40M 43 39

195960 1,160

680

Height

Indoor unit

WidthDepth

40M 50/60M

1,400 1,590

71/90M 100/125/140M

Quiet operation

Easy maintenanceLong-life filter (standard) requires no maintenance for about 1 year*

* For dust concentration of 0.15 mg/m3

Two time settings (2500 hrs and 1250 hrs) are available to match the installation environment. Maintenance time warning is displayed on the wired remote controller (filter sign).

The filter is washable and reused after 1 year.

Oil resistant grille

Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification is not suitable for kitchens or other harsh environments.

Oil-resistant plastic is used for the air suction grille. This satisfies durability in restaurants and other similar environments

For all maintenance tasks, access is from bottom surface

It is easy to wipe dirt off the flat side and lower surfaces of the unit.

Easy-clean, flat surfaces

Diffuses comfortable air throughout the room

Installation flexibility for freedom of design

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

Programme "Dry"

Auto-swing (up&down) brings comfort to the room

Wide air discharge openings produce a spreading 100° airflow

Air is blown up to 50° in the downward direction

Switchable fan speed: High/Low

Installable on ceilings 3.5 m high

100°

*Water used in the test-run can be drained from the air discharge opening rather than from the side as was formerly the case.

The unit fits more snugly into tight spaces.

Flexible installation

Uniform height and depth. Compact design for small-capacity models to meet tighter dimensional constraints

30 mm or more

30 mm or more

(220V) dB(A)

Pipes more easily riggedPlastic panels are used to conceal piping holes.Holes can be easily punched out without requiring special tools.

All wiring and internal servicing can be done from under the unit

Non-flocking flap

Condensation does not easily form on and dirt does not cling to non-flocking flap. It is easy to clean.

Non-flocking flap

CEILING SUSPENDED TYPE

7 8

Comfortable airflow travels throughout the roomComfortable airflow travels throughout the room

Accessory required for indoor unit.Option

FHNQ40/50/60/71/90/100/125/140MV1

45/40dB(A)FHNQ90M

(220V)

High Low

Sound pressure level

BRC7NU66

A signal receiver must be added to the indoor unit.

Note: Remote controller cable is not included and must be procured locally.

Wireless remote controller is supplied in a set with a signal receiver.

Wired LCD remote controller

Wireless LCD remote controller

BRC1NU61

Signal receiver unit (Installed type)

Page 6: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

Quiet operation Quiet operation

Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)

Ventilation grille

Door-installedventilation grille

Ventilation grille

Wall-installedventilation grille

Under-door cutout

Under-door cutoutWhen air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms.

Ventilates air through the partitioning wall. (See right)

Partitioning wall

Note: The under-door cutout method should be used only when there is a small volume of airflow.

9 10

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

Freedom of layout

Wired LCD remote controller

BRC1C61

Accessory required for indoor unitOption

Switchable fan speed: High/Low

Drain pipe connection can be done inside the unit. Refrigerant and drain pipe outlets are at the same opening.

The duct system allows the efficient location of discharge outlets in accordance with the room layout

Duct connection is simpler with standard rear suction chambers

Indoor unitHigh Low

60/71M 43 4025/40/50M 41 38

(220V) dB(A)

Indoor unitHigh

Sound pressure level Sound pressure levelLow

90M 44 3671M 42 38

125/140M 46 37100M 45 37

(220V) dB(A)

Wired LCD remote controller

BRC1C61

Accessory required for indoor unitOption

BRC4C64

A signal receiver must be added to the indoor unit.

Wireless remote controller is supplied in a set with a signal receiver.

Wireless LCD remote controller

Signal receiver unit (Separate type)

BRC4C64

A signal receiver must be added to the indoor unit.

Wireless remote controller is supplied in a set with a signal receiver.

Wireless LCD remote controller

Signal receiver unit (Separate type)

FDBNQ25/40/50/60/71MV1 FDMNQ71/90/100/125/140MV1

DUCT CONNECTION LOW STATIC PRESSURE TYPE

45/37dB(A)FDMNQ100M

(220V)

High Low

Sound pressure level

43/40dB(A)FDBNQ71M

(220V)

High Low

Sound pressure level

Ideal for quiet, beautiful living spacesIdeal for quiet, beautiful living spaces Unit can be mounted in the ceiling and air can be delivered freely by ductUnit can be mounted in the ceiling and air can be delivered freely by duct

CompactSmall, lightweight, and easy-to-install indoor unit.

Suction chamberAir filter

(Note)

[Duct connection]

or moreor more To prevent increased operation sound, avoid installing the air suction grille directly below the suction chamber.

Note : 270 mm is the minimum size. Extra height is necessary for drain piping slope and insulation.

Note : 325 mm is the minimum size. Extra height is necessary for drain piping slope and insulation.

Air conditioner305 mm

Ordinary duct (procured locally)

Air discharge Air intake

(Note)or moreor more325 mm325 mm

Ordinary duct (procured locally)

Note: Remote controller cable is not included and must be procured locally.

BRC1E62

Navigation Remote Controller(Wired Remote Controller)

Note: Remote controller cable is not included and must be procured locally.

Note: Remote controller cable is not included and must be procured locally.

BRC1E62

Navigation Remote Controller(Wired Remote Controller)

Note: Remote controller cable is not included and must be procured locally.

Suitable for condominiums and apartments, houses and hotels

Page 7: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

OUTDOOR UNIT

Quiet Operation

To suppress turbulence and achieve quiet operation, the curved ribs of the grille are optimised to meet the outflow of air.

Fitted with Super Aero Grille

Equipped with scroll compressor for quiet operation

Smooth running, minimal vibration, low operating sound.

Allowed refrigerant piping length and level difference

Max. length

Max. leveldifference

Pre charged1

RNQ25/40M RNQ50/60M RNQ71M RNQ90-140M

10 m

30 m

10 m 15 m 20 m 30 m

30 m(Equivalent length

50m)

50 m(Equivalent length

70m)

15 m

(Applies to RNQ90-140M)

Installation and maintenance

Pre charged for up to 15 mIf refrigerant piping length does not exceed 10m (RNQ25-71M), 15m (RNQ90-140M), there is no need for on-site gas charging.

DurabilityAs the bottom frame is subject to corrosion, corrosion-proof galvarium steel plate is adopted to enhance the durability

Heat exchange fins are provided with anti-corrosion treatment

11 12

RNQ25MV1RNQ40MV1

RNQ50MV1RNQ60MV1

RNQ71MV1RNQ71MY1

RNQ90MV1RNQ90MY1

RNQ100MV1RNQ100MY1RNQ125MY1RNQ140MY1

Operation sound

dB(A)

(Applies to RNQ125-140M)

(Applies to RNQ90-140M)

(Applies to RNQ25-71, 100-140M)

4-direction piping offers greater layout freedomThe outer panel for the piping connection part of the front, right side and backside can be removed and is easier for post-installation piping work.

(Applies to RNQ90-140M)

Removable part of bottom frame makes the piping work easier (Applies to RNQ90-140M)

Note: 1Additional refrigerant charging is required if the refrigerant pipe is longer than the length.

Outdoor unit Sound pressure levelRNQ25MV1 48RNQ40MV1 49RNQ50MV1 51RNQ60MV1 52

RNQ71MV1/RNQ71MY1 54RNQ90MV1/RNQ90MY1 55

RNQ100MV1/RNQ100MY1 54RNQ125MY1 56RNQ140MY1 58

ConstructionNon-treated fin

Anti corrosion treated fin

Aluminium

AluminiumCorrosion resistant resin

Hydrophilic treatment

(In case of RNQ25-60M:220-240 V, RNQ71-100M:220 V/380 V, 240 V/415 V, RNQ125-140M:380 V, 415 V)

Separation available

To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, Anti corrosion treated fin for heat exchangers (with special coating) are used for the heat exchanger of the outdoor unit.

Whatever your space, give it the comfort it deserves

Page 8: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

REMOTE CONTROLLER Optional accessory

Enables temperature sensing closer to target area for improved comfort. (When using remote control from another room, temperature-sensor in indoor unit's air inlet must be selected.)

Facilitates maintenance and repairAll initial settings can be set from the remote controller. After interior construction is complete, ceiling mounted cassette type can be remotely set without having to use stepladder access for manual setting.Setting contents: High ceiling use, air direction, filter type, address for centralised control (group control address is set automatically).

Remote controller is equipped with model name and failure display functions. This facilitates service in the unlikely event of a malfunction.

SkyAir shares common control with Heat Reclaim Ventilator and the other Daikin air-conditioning units, thus simplifying interlocking operations.

Easily adaptable to large-scale, high-function, centralised remote control systems.Installing and connecting control wiring between SkyAir and other Daikin air-conditioning equipment is easy.

LCD panel shows operating status in letters, numbers, and motion.Airflow / swing display Displays auto-swing operating status and setting position of air discharge angle.

Preset temperature / operation mode display Displays preset room temperature and operating status (fan, dry, cool).

Programming time display Operation start and stop time can be set for individual timers up to 72 hours. The LCD also shows when it is time to clean the filter, when changeover is under centralised control, and ventilation/cleaning.

Self-diagnosis function Monitors operating status within the system covering 40 items, and displays a message to indicate as soon as a malfunction occurs.

CEILING MOUNTED CASSETTE TYPECEILING SUSPENDED TYPEDUCT CONNECTION LOW STATIC PRESSURE TYPE

BRC7NU66BRC7F633F

BRC4C64DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE BRC4C64

Wired remote controller has built-in temperature-sensor (Applies to wired remote controllers (BRC1C61/1E62))

(Model name display function applies to BRC1E62 only.)

13 14

Navigation Remote Controller(Wired LCD Remote Controller)

Easy-to-read LCD remote controller allows various system control configurations and can control multiple indoor units. Remote controller options are shown on the page introducing each indoor unit model.

NEW

- 5 actions per day can be scheduled for each day of the week.- The holiday function will disable schedule timer for the days that have been set as holiday.- 3 independent schedules can be set. (e.g. summer, winter, mid-season)

Display is available in 11 languages.

ConvenienceWeekly schedule Multilingual display

(English, German, French, Spanish, Italian, Portuguese, Greek, Dutch, Russian, Turkish, and Polish).NEW

Clear DisplayDot matrix display Backlight

displayA combination of fine dots enables various icons.Large text display is easy to see.

This simple, modern designed remote controller with fresh white colour matches your interior design. Operation is much easier and smoother, just follow the indications on the navigation remote controller.

Energy savingNEW

- Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts.- Period can be preset from 30 to 180 minutes in10-minute increments.

Off timer (programmed)

Setpoint range setNEW Setpoint auto reset

Restaurant sampleRestaurant opened

Temperature is set to 27ºC

27°C

- Saves energy by limiting the min. and max. set temperature.

- Avoids excessive heating or cooling.

- This function is convenient when the remote controller is installed at a place where any number of people may operate it.

- Even if the set temperature is changed, it returns to the preset temperature after a preset period of time.

- Period selectable from 30min/60min/90min/120min.

Full tables at lunchtimeThen is lowered to 24ºC for crowded room

24°C

After 30 minutes*Automatically returns to preset temperature (27ºC)

*Setting possible for after 30, 60, 90, and 120 minutes.

Returns to

27°Cautomatically

Signal receiver unit (For ceiling mounted cassette type)

Wireless remote controller for each indoor unit type

Wireless LCD remote controller

Note: The signal receiver unit shown in the photograph is for mounting inside the decoration panel of the ceiling mounted cassette type.

Wireless remote controller

BRC7F633F

The wireless remote controller is supplied in a set with a signal receiver.Signal receiver unit is contained inside decoration panel or indoor unit.Shape of signal receiver unit differs according to the indoor unit.

The rubber switch and the oil-resistant plastic casing are adopted for durability.Only 17 mm thick. Can be installed either recessed or exposed.

Easy to read because of large LCD screen.Wired LCD remote controller

BRC1C61BRC1E62

Page 9: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

FunctionsoverviewFunctionsoverview

FUNCTIONSREMOTE CONTROLLER Optional accessory

Cooling only

15 16

*1 : Applicable when wired remote controller is used*2 : Applicable when BRC1E62 is used*3 : Applicable to RNQ90-140M

*4 : Applicable to RNQ25-71M*5 : For outdoor units*6 : Installable on max. 3.5 m high ceiling

*7 : Applicable when BRC1C61 is used*8 : Option

FCNQ40-140MV1

RNQ40-100MV1RNQ71-140MY1

FHNQ40-140MV1

RNQ40-100MV1RNQ71-140MY1

FDBNQ25-71MV1

RNQ25-71MV1RNQ71MY1

FDMNQ71-140MV1

RNQ71-100MV1RNQ71-140MY1

Indoor unit

Outdoor unit

Comfort

Cleanliness

Remote Controller

Work & servicing

Control features

Options

Others

CEILING SUSPENDED TYPE

DUCT CONNECTIONLOW STATIC PRESSURE TYPE

DUCT CONNECTIONMIDDLE STATIC PRESSURE TYPE

CEILING MOUNTED CASSETTE TYPERound Flow

Note:

Auto swing

Swing pattern selection

DC fan mortor (Indoor unit)

Switchable fan speed

Programme “Dry”

High ceiling application

Two selectable temperature-sensors *1

Setpoint auto reset *2

Setpoint range set *2

Weekly schedule timer *2

Off timer (programmed) *2

On/Off timer

Anti-bacterial air filter

Drain pump mechanism

Pre-charged for up to 15 m *3

Pre-charged for up to 10 m *4

Long-life filter

Filter sign

Ceiling soiling prevention

Auto-restart

Control by 2 remote controllers

Group control by 1 remote controller

External command control

Central remote control

Interlock control with Heat Reclaim Ventilator

DIII-NET communication standard

High-efficiency filter

Ultra long-life filter

Fresh air intake kit

Anti corrosion treated heat exchangers *5

*8

*7 *7*7

*6

Central remote controller

Easily adaptable to large-scale, high-function, centralised remote control system.

Centralised control, with setting as simple as it is with a standardremote controller, of up to 64 groups (1,024 indoor units) is possible.

DCS302CA61 (Option)

With its high functionality, the full colour “all-in-one” graphic controller facilitates management of SkyAir System in a variety of ways.

DCS601C51 (Option)

Unified on/off controller

Centralised control of on/off by group or all at once for up to 256 indoor units.

DCS301BA61 (Option)

Schedule timer

Unified control of weekly schedule for up to 1,024 indoor units.

DST301BA61 (Option)

Schedule timer sets on/off time in 1 minute units to be executed twice a day for a week at a time.

System variation to control multiple indoor units

Control by 1remote

controller

Control pattern

Applicable model

FCNQ

FDBNQ

FDMNQ

Wired remote controller Wireless remote controller

Control by 2remote

controllers

Group control

Control by external

command

Centralised remotecontrol

Interlock control

with Heat Reclaim

Ventilator

(Basic system)

Control by 1 wireless remote controller and 1 wired remotecontroller (See note 2, 3)Signal receiver unit installed on indoor unit

Signal receiver unit installed on indoor unit

Can be operated simultaneously or independently by remote controller (set by ventilation mode)

Heat ReclaimVentilator

Non-polar, double-core (max. wiring length 500 m)

Connects 2 wired remote controllers (See note 1)

Automatic address setting function Automatic address setting functionSignal receiver unit installed on 1 indoor unit

Optional wiring adaptor for electrical appendices is necessary

Can be operated simultaneously by remote controller (set by ventilation mode)

Heat ReclaimVentilator

For control from 2 locations such as in room and control room, exits, etc.

For simultaneous control of up to 16 indoor units.

Operation and monitoring is carried out using the contact signal from the operation control box in the monitoring room.

Centralised control of up to 64 indoor groups from remote location up to 1 km away.

Link by remote controller group control.

Zone link control by centralised control.

Optional wiring adaptor for electrical appendices is necessary

Note: 1BRC1E62 can connect to BRC1E62 only. 2It is not possible to use two wireless remote controllers. 3BRC1E62 cannot connect to wireless remote controller.

(Command from outside) (Command from outside)

Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking Can also be operated independently by remote controller.

Central remote controller (option)

Heat ReclaimVentilator

Heat Reclaim Ventilator for indoor units within a zone are operated by interlocking

Central remote controller (option)

Heat ReclaimVentilator

Central remote controller (option) Central remote controller (option)

FCNQ only

FCNQ series only

2step 2step2step2step

Page 10: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

Work and Servicing

Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping.

Maintenance is not required for one year.The filter is washable and can be reused.

If refrigerant piping length does not exceed 15 m, there is no need for on-site gas charging.

The filter sign warns you when it is time to clean the filter. *When using a wired remote controller the sign is displayed in the LCD. When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit.

Drain pump mechanism

Long-life filter

Pre charged for up to 15 m

Filter sign

Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required.

Ceiling soiling prevention function

RNQ25-71M : 10 m*Applicable to RNQ90-140M.

Others

To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, Anti corrosion treated fin for heat exchangers (with special coating) are used for the heat exchanger of the outdoor unit.In high corrosive areas, regular maintenance needs to be carried out.

Anti corrosion treated heat exchangers

You can turn up to 16 indoor units on/off with a single remote controller. (When using connected indoor units, the settings must all be the same and on/off will be simultaneous.)

Group control by 1 remote controller

Control features

If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored.

Auto-restart

Optional central remote controller enables centralised control of up to 1024 indoor units (64 groups) from up to 1 km away.

Central remote control

Enables interlocking control with external equipment such as Heat Reclaim Ventilator.

Interlock control with Heat Reclaim Ventilator

Standardly equipped interface enables connection to centralised control system without need of an adaptor.

DIII-NET communication standard

Using 2 remote controllers you can operate the equipment locally or from a remote location.Note: When a wireless remote controller is used, remote control by two remote controllers is not possible.

Control by 2 remote controllers

Operation and monitoring is carried out using the contact signal from the operation control box in the building monitoring room.

External command control

*An option is required.

Two types are available: 65% and 90% colorimetry. High-efficiency filter

You can provide air-conditioning with fresh air from outside. Convenient for places where a ventilation fan cannot be installed.

Fresh-air intake kit

Options

Ultra long-life filterRequires no maintenance for about 4 years* (10,000h) in stores and offices.*For dust concentration of 0.15 mg/m3

*For dust concentration of 0.15 mg/m3

FUNCTIONS

17 18

Abundance of functions that provide comfortable air-conditioning in stores and offices.

Cleanliness

The air filter has an anti-bacterial treatment to help prevent the growth of bacteria and mould on it.Anti-bacterial air filter

Note: Some functions only available on selected models. See overview page for full list of features applicable to each unit.

Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply.

Delivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings.

High-ceiling application

High setting provides maximum reach while low setting minimises drafts.

Switchable fan speed

DC fan motor improves efficiency.DC fan motor (indoor unit)

Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. Useful for reducing uncomfortable humidity without uncomfortable cooling of the room.

Programme "Dry"

Comfort

Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner.

Auto-swingThe air flow direction can be fixed at your desired angle by the remote controller.

Note: Wireless remote controllers have no temperature-sensor.

Use the temperature-sensor in the indoor unit when controlling air conditioning from another room.

Two selectable temperature-sensorsTemperature-sensors are included in the indoor unit and optional wired remote controller. Temperature sensing closer to target area is possible to further increase the comfort level.

Remote Controller

Sets and saves setting for an increment of time that automatically turns off air conditioner after a preset period of time for each time operation starts.

Off timer (programmed)

Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

On/Off timer

Up to five operation ON/OFF settings can be programmed per day for each day of the week. Not only can the time be set for the operation ON setting, but also the temperature.

Weekly schedule timer

Even if the set temperature is changed, it returns to the preset temperature after a preset period of time.

Saves energy by limiting the minimum and maximum set temperatures. Avoids excessive heating and cooling.

Setpoint auto reset

Setpoint range set

(1) Standard setting

(2) Ceiling soiling prevention setting

(standard, ceiling soiling prevention)You can freely set 2 air discharge setting by remote controller.

Swing pattern selection

Page 11: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

CEILING MOUNTED CASSETTE TYPE

CEILING SUSPENDED TYPE

DUCT CONNECTION LOW STATIC PRESSURE TYPE

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

SPECIFICATIONS

43/39

24

White

VP20 (I.Do/ 20XO.Do/ 26)

19.4 to 46o/ 6.4

49

36 40 49--------- --------- ---------

1.2 (Charged for 10 m)

0.9

51

1.4 (Charged for 10 m)

1.4

52

1.5 (Charged for 10 m)

1.82.0

(Charged for 10 m)

2.21.9

(Charged for 15 m)3.2

(Charged for 15 m)

2.72.7

(Charged for 15 m)

3.753.2

(Charged for 15 m)

4.5

Ivory white

30

10 15

Hermetically sealed rotary type

o/ 12.7 o/ 15.9

o/ 18.0 (Hole)

°CWB

°CDBCertified operation range

Certified operation range

Motor outputCompressor

Dimensions (HXWXD)

Colour

mmdB(A)

kWRefrigerant charge (R-410A) kg

dB(A)Sound pressure level3Dimensions (HXWXD) mmMachine weight kg

kgV1Y1

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Machine weight kg

Airflow rate (H/L) m3/min 16/-565/-

Outdoorunit

Colour

mm

Heat insulation

Max. interunit piping length m

mMax. installation level difference

Type

Sound pressure level (H/L) (220 V)3

Indoorunit

Both liquid and gas piping

cfm

14 to 23 14 to 25

19 20

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). 2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

°CDBCertified Operation range

Sound pressure level3

°CWBCertified Operation range

Motor outputCompressor

Dimensions(HXWXD)

Colour

mmmm

dB(A)

kWRefrigerant charge (R-410A) kg

dB(A)Dimensions (HXWXD) mmMachine weight kgV1

Y1

Unit

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Outdoor unit

Decoration panel

UnitDecoration panel

Machine weight kg

kgUnitDecoration panel

Airflow rate (H/L) m3/mincfm

Outdoorunit

Colour

mm

Heat insulation

Max. interunit piping length m

mMax. installation level difference

Type

Sound pressure level (H/L)3

Indoorunit

Hermetically sealed rotary type Hermetically sealed scroll type

o/ 6.4o/ 15.9o/ 12.7

50X950X950

5.5

----------

10 15 20 30

Ivory white

Fresh white

Both liquid and gas piping

30 30 (Equivalent length 50)

30 (Equivalent length 50)

50 (Equivalent length 70)

o/ 26.0 (Hole)o/ 18.0 (Hole)VP25 (I.Do/ 25XO.Do/ 32)

19.4 to 46o/ 9.5

21 to 46

14 to 23 14 to 25

0.9 1.4 1.8 2.2 2.7 3.75 4.5

31/28 35/28 43/32 44/34 44/36

49 51 52 54 55 54 56 58

36 40 49 56 77 99 --------- ------------------ --------- --------- 56 74 99 107 111

19.5 21 24

256X840X840 298X840X840

1.2(Charged for 10 m)

1.4(Charged for 10 m)

1.5(Charged for 10 m)

2.0(Charged for 10 m)

1.9(Charged for 15 m)

3.2(Charged for 15 m)

2.7(Charged for 15 m)

3.2(Charged for 15 m)

13/10 21/13.5 32/20 33/22.5459/353 741/477 1,130/706 1,165/794

Cooling capacity1,2 kWY1V1Y1V1

kWPower consumption

ModelName

Indoor unit

Power supply

Cooling1 Btu/h

W/WCOP

40FCNQ40MV1RNQ40MV1

3.813,000

550X765X285

1.243.07

50FCNQ50MV1RNQ50MV1

5.318,000

595X845X300

1.892.80 2.80

60FCNQ60MV1RNQ60MV1

--------- --------- ---------

6.221,0002.21

71FCNQ71MV1RNQ71MV1

7.626,000

735X825X300

735X825X300

2.533.00

90FCNQ90MV1RNQ90MV1

8.830,000

990X940X320

2.733.22

100FCNQ100MV1RNQ100MV1

RNQ71MY1

71FHNQ71MV1RNQ71MV1RNQ71MY1

RNQ90MY1 RNQ100MY1

10.636,000

1,345X900X320

3.313.20

125FCNQ125MV1

---------

12.542,6004.153.01

140FCNQ140MV1

---------RNQ125MY1 RNQ140MY1

14.148,0005.042.80

1 Phase, 220–240 V, 50 Hz---------

---------3 Phase, 380–415 V, 50 Hz

Hermetically sealed scroll type

o/ 9.5

o/ 26.0 (Hole)50

(Equivalent length 70)30

21 to 46

45/40 48/42 49/43

5554 54 56 58

7756 99 --------- ---------7456

20

99 107 111

195X1,590X680

26-27/22-23 38-40/23-25918-953/777-812 1,341-1,412/812-883

90FHNQ90MV1RNQ90MV1

8.830,000

990X940X320

3.072.87

7.626,0002.65

100FHNQ100MV1RNQ100MV1

RNQ90MY1 RNQ100MY1

10.435,000

1,345X900X320

3.642.86

125FHNQ125MV1

---------

12.342,0004.512.73

140FHNQ140MV1

---------RNQ125MY1 RNQ140MY1

14.148,0005.512.56

42-44/24-261,483-1,553/847-918

---------3 Phase, 380–415 V, 50 Hz

Outdoor unit

Outdoor unit

Cooling capacity1,2 kWY1V1Y1V1

kWPower consumption

ModelName

Indoor unit

Power supply

Cooling1 Btu/h

W/WCOP

40FHNQ40MV1RNQ40MV1

195X960X680

3.813,000

550X765X285

1.582.40

50FHNQ50MV1RNQ50MV1

195X1,160X680 195X1,400X68026 32 35

44/40777-812/671-706

22-23/19-20

5.318,000

595X845X300

2.042.60 2.60

60FHNQ60MV1RNQ60MV1

--------- --------- ---------

6.221,0002.38

1 Phase, 220–240 V, 50 Hz---------

Outdoor unit

Outdoor unit

°CDB

°CWBCertified Operation range

Certified Operation range

Motor outputCompressor

Indoorunit

Dimensions (HXWXD)

Colour

mmdB(A)

kWRefrigerant charge (R-410A)Sound pressure level4

Sound pressure level (H/L) (220 V)4

dB(A)Dimensions (HXWXD) mmMachine weight kgV1

Y1

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Machine weight kg

kg

Airflow rate (H/L)3Fan

Outdoorunit

Colour

Heat insulation

Max. interunit piping length m

mMax. installation level difference

Type

----------

Both liquid and gas piping

mmOutdoor unit

Ivory white

mmH2Ocfm

Rated external static pressure3

10 15 20

19.4 to 46 21 to 46

14 to 23 14 to 25

m3/min

30 30 (Equivalent length 50 m)

3/4B (I.Do/ 21.6XO.Do/ 27.2)

o/ 6.4 o/ 9.5o/ 12.7o/ 9.5 o/ 15.9

o/ 18.0 (Hole)

0.65 0.9 1.4 1.8 2.2

25 32

35 36 40 49 56---------- ---------- ---------- ---------- 56

Hermetically sealed rotary type

0.9 (Charged for 10 m)

1.2 (Charged for 10 m)

1.4 (Charged for 10 m)

1.5 (Charged for 10 m)

2.0 (Charged for 10 m)

459/38813/11

635/53018/15

41/38 43/40

48 49 51 52 54

2.0

Y1V1Y1V1

Cooling capacity1,2 kW

kWPower consumption

ModelName

Indoor unit

Power supply

Cooling1 Btu/h

W/WCOP

25FDBNQ25MV1

RNQ25MV1

260X900X580

2.79,200

550X765X285

0.863.14

40FDBNQ40MV1

RNQ40MV1

3.813,0001.282.97

50FDBNQ50MV1

RNQ50MV1

5.217,700

595X845X300

2.062.52

60FDBNQ60MV1

RNQ60MV1

260X1,300X580

6.221,000

2.382.60

71FDBNQ71MV1

RNQ71MV1--------- --------- --------- --------- RNQ71MY1

7.626,000

735X825X300

2.622.90

1 Phase, 220–240 V, 50 Hz--------- 3 Phase, 380–415 V, 50 Hz

Outdoor unit

Outdoor unit

Note : 1Rated cooling capacities are based on the following conditions: Indoor temp., 27°CDB, 19.0°CWB; outdoor temp. 35°CDB, 24°CWB. Equiv. refrigeration piping, 7.5 m (horizontal). 2Capacities are net, including a deduction for cooling for indoor fan motor heat.3Please see fan characteristic document in detail.4Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

°CDB

°CWBCertified Operation range

Certified Operation range

Motor outputCompressor

Indoorunit

Dimensions (HXWXD)

Colour

mmdB(A)

kWRefrigerant charge (R-410A)Sound pressure level4

Sound pressure level (H/L) (220 V)4

dB(A)Dimensions (HXWXD) mmMachine weight kgV1

Y1

Piping connections

mmLiquid (Flare)mmGas (Flare)mmDrain Indoor unit

Machine weight kg

kg

Airflow rate (H)3Fan

Outdoorunit

Colour

Heat insulation

Max. interunit piping length m

mMax. installation level difference

Type

----------

Both liquid and gas piping

mmOutdoor unit

Ivory white

mmH2Ocfm

Rated external static pressure3

20 30

21 to 46

14 to 25

m3/min

30 (Equivalent length 50 m)

50 (Equivalent length 70 m)

3/4B (I.Do/ 21.6XO.Do/ 27.2)

o/ 9.5o/ 15.9

o/ 26.0 (Hole)o/ 18.0 (Hole)

2.2 2.7 3.75 4.5

43 52

56 77 99 ---------- ----------56 74 99 107 111

Hermetically sealed rotary type Hermetically sealed scroll type

2.0 (Charged for 10 m)

1.9 (Charged for 15 m)

3.2 (Charged for 15 m)

2.7 (Charged for 15 m)

3.2 (Charged for 15 m)

81223

1,30637

1,48342

42/38 44/36 45/37 46/37

54 55 54 56 58

8.5 9.8 8.0

Y1V1Y1V1

Cooling capacity1,2 kW

kWPower consumption

ModelName

Indoor unit

Power supply

Cooling1 Btu/h

W/WCOP

71FDMNQ71MV1

RNQ71MV1

305X1,350X680

7.626,000

735X825X300

2.622.90 2.90

90FDMNQ90MV1

RNQ90MV1

305X1,550X680

8.830,000

990X940X320

3.03

100FDMNQ100MV1

RNQ100MV1

10.636,0003.533.00

1,345X900X320

125FDMNQ125MV1

---------

12.342,000

4.492.74

140FDMNQ140MV1

---------RNQ71MY1 RNQ90MY1 RNQ100MY1 RNQ125MY1 RNQ140MY1

14.148,000

5.562.54

1 Phase, 220–240 V, 50 Hz ---------3 Phase, 380–415 V, 50 Hz

Outdoor unit

Outdoor unit

Page 12: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

For each flow pattern – all round, 4-way, 3-way, 2-way, branch duct connection – the compatibility of each independently installed option (shown in the column on the left) to accessory options (listed across the top of each table) is shown in the cells where the relevant row and column intersect.A circle (o) indicates compatibility, and a cross (x) indicates incompatibility. Any options not shown below are not suitable for independent or accessory installation.

Round flow type: List of optional parts required to achieve different flow patterns

1In some cases, depending on how the unit is embedded in the ceiling, use of branch ducts and fresh air intake kits may not be possible. Before starting installation work make sure to check whether or not joint installation is possible. In particular, ensure that the lower fixing position caused by the addition of panel spacers is acceptable.

2Use a chamber connection kit if two different types of optional chamber are used together. In this case, the fresh air intake kit must be installed in the upper position.3It is not possible to use panel spacers in a 2-way flow installation. 4It is not possible to install a branch duct on the same side to which a fresh air intake kit (direct mount) is installed.

Panel/grille relatedIndependently installable optional parts

Operation control relatedAuxillary function related

Filter related

Optional accessory parts

Independently installable optional partsOptional accessory parts

Independently installable optional partsOptional accessory parts

Panel spacer1

Panel spacer1 o o ox oWireless remote controller o o oo o

Fresh air intake kit (direct mount) o o oo ox o o

xx

High-efficiency filter2

Filter related Ultra-long-life filter2

o o ox

xUltra-long-life filter2 o o o xx

High-humidity operation kit

Panel/grille relatedOperation control relatedAuxillary function related

Panel spacer1

Wireless remote controller

Fresh air intake kit (direct mount)High-humidity operation kit

All round flow 4-way flow

o3 o3 xx o3

o3 o

x

xxo o

o3 o xx

o ox o o x

o3 o o xx

3-way flow 2-way flow

1-way branch / unit 3-way flowBranch duct1(Chamber type)(Round duct type)

o o o4 xx o2-way branch / unit 2-way flow1-way branch / unit 2-way flow

x o o4 xx ox o o4 xx o

Branch duct connection

Wireless remote controller

Fresh air intake kit (direct mount)

High-efficiency filter2

High-humidity operation kit

Ultra-long-life filter2

Panel spacer1 Wireless remote controller

Fresh air intake kit (direct mount)

High-efficiency filter2

High-humidity operation kit

Ultra-long-life filter2

Panel spacer1 Wireless remote controller

Fresh air intake kit (direct mount)

Fresh air intake kit (Chamber type)1,2 o o ox o

Fresh air intake kit (Chamber type)1,2 o3 o xx o

oo

xoo

o3

o

x

x

x

o

o o o

Fresh air intake kit (Chamber type)1,2

Fresh air intake kit (Chamber type)1,2

Fresh air intake kit (Chamber type)1,2

High-efficiency filter2

High-humidity operation kit

Ultra-long-life filter2

21 22

Indoor unit Indoor unit

Outdoor unitKit name

RNQ50MV1 RNQ60MV1RNQ25MV1 RNQ40MV1 RNQ71MV1 RNQ90MV1 RNQ100MV1 ------- -------------- -------------- ------- RNQ71MY1 RNQ90MY1 RNQ100MY1 RNQ125MY1 RNQ140MY1

Central drain plug

Name of option

KKPJ5F180-------------- KKP014A4

intelligent Touch Controller4

Note: 1Refer to page 6 for the details.2Required for installing high-efficiency filter and ultra long-life filter unit. 3Wiring for wired remote controller to be procured locally.4The indoor unit is equipped standardly with the interface adaptor for SkyAir series. An option is unnecessary. 5Installation box for adaptor PCB (KRP1H98) is necessary.

Note: 1Wiring for wired remote controller to be procured locally.

Kit nameFCNQ60MV1 FCNQ71MV1 FCNQ90MV1FCNQ40MV1 FCNQ50MV1 FCNQ100MV1 FCNQ125MV1 FCNQ140MV1Name of option Remark

Chamber type

Decoration panel

Fresh air intake kit1

Central remote controller4

Unified ON/OFF controller4

Schedule timer4

Adaptor for wiring5

Without T-duct jointWith T-duct joint

Direct installation type

Sealing material of air discharge outletPanel spacer

Chamber connection kit2Insulation kit for high humidity

Wiring adaptor for electrical appendices(2)5

Installation box for adaptor PCB

High-efficiency filter unit(including filter chamber)

Filter chamber Replacement long-life filterUltra long-life filter unit (including filter chamber)Replacement ultra long-life filter

(Colorimetric method 65%)(Colorimetric method 90%)

Replacement high-efficiency filter

(Colorimetric method 65%)(Colorimetric method 90%)

Remote controller Wireless type Cooling onlyWired type3

Branch duct chamber

Remote sensor (for indoor temperature)

CEILING MOUNTED CASSETTE TYPEKit name

KHFJ5F50

BRC1NU61BRC7NU66

KAF501DA56KHFJ5F60 KHFP5MA160

KAF501DA80 KAF501DA112 KAF501DA160FHNQ60MV1 FHNQ71MV1 FHNQ90MV1 FHNQ100MV1 FHNQ125MV1 FHNQ140MV1FHNQ40MV1 FHNQ50MV1Name of option Remark

Replacement long-life filterL-type piping kit (for upward direction)Remote controller

Wired type1Wireless type

CEILING SUSPENDED TYPE

Note: 1Wiring for wired remote controller to be procured locally.

Kit name

BRC1C61BRC4C64

FDBNQ50MV1FDBNQ25MV1 FDBNQ40MV1 FDBNQ60MV1 FDBNQ71MV1Name of option Remark

Remote controllerWired type1Wireless type

DUCT CONNECTION LOW STATIC PRESSURE TYPE

Note: 1Wiring for wired remote controller to be procured locally.

Kit name

BRC1C61BRC4C64

FDMNQ100MV1FDMNQ71MV1 FDMNQ90MV1 FDMNQ125MV1 FDMNQ140MV1Name of option Remark

Remote controllerWired type1Wireless type

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

Navigation Remote Controller Wired type3

BRC1E62Navigation Remote Controller Wired type1

BRC1E62Navigation Remote Controller Wired type1

DCS601C51

DCS302CA61DCS301BA61DST301BA61

KRP1C63

KDDFP55B160

KDBH55K160FKDBP55H160FA

KKSJ55KA160

KDDP55B160KDDP55B160KKDDP55X160

KRP4AA53

KAFP551K160

KAFP556B80KAFP557B80KAFP552B80

KDTP55K80

KDJP55B160KDJP55B80

BRC7F633FBRC1C61

KAFP553B80

KDTP55K160

KAFP556B160KAFP557B160KAFP552B160KAFP553B160

BYCP125K-W1

KRP1H98

KAFP55B160KAFP55H160H

KRCS01-4B

BRC1E62

OPTIONS

Page 13: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

4

155

11

o/ 45

4090

5 80

1455

195

30 or more 30 or more

4-M8~M10Hanging bolt

(Service space)(Service space)

1

B

127

8

10

1718

(Han

ging

p

ositi

on)

(Hanging position)A

16

210

36

170

58

19285 160

105

102

14290

185

260

4170

7

225

Drain pipe connection VP206

275

Brand name plateThe Front

(Note.2)

80

275

105

(For left piping)

300

3 2 5

80

6

(Requi

red sp

ace)

Obstacle

680

Floor side

515

5

55

(Req

uire

d sp

ace)

300 o

r more13

For h

eight

instal

lation

From t

he floo

r side

2500 o

r more

10515 (R

equi

red

spac

e)13

55

Position : Hole of wall for taking out in piping back(View from the front)

6550

135

1459 60

65

12

40 60

6011

5

Position slit hole for taking out in piping back(View from the front)

23 24

CEILING SUSPENDED TYPE

236

3×P.150=45016

260

16

151 704

10

688

150

900

127

(All Around)

219

1012-M4 Holes

52

674

5

7

4

6

664

170110

684

260

(All Around)1

228

3×P150=450

50010-M4 Holes16

4

2

29

50

134

107

10 o

r mor

e

300 or more

317

3

704

500

167

580

151

1268

271

(Suspension bolt pinch)

3

55(S

uspe

nsio

n bo

lt pi

nch)

755

137

900

Service space

DUCT CONNECTION LOW STATIC PRESSURE TYPE

A B

[FHNQ40/50/60/71/90/100/125/140MV1]

[FDBNQ25/40/50MV1]

123456789101112131415161718

Air discharge grilleAir suction grilleAir filterGas pipe connectionLiquid pipe connectionDrain pipe connectionEarth terminal (Inside the electric components box)Suspension bracketBackward pipe and wiring connection opening lidUpward pipe and wiring connection opening lidRight side pipe connectionLeft back drain pipe connectionLeft side drain pipe connectionRight side drain pipe connectionHole of wall for taking out in pipe backUpward drain pipe connectionUpward gas pipe connectionUpward liquid pipe connection

Notes:1Location of unit's Name plate : Bottom of fan housing inside the suction grille.2In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.3The remote control code is the standard <about 3m outside the machine> attached.(0.5mm2x2 wicks O.D. 5.4)(It is not attached to VRV.)

Note: 1Location of unit's Name Plate: Chamber cap

Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

1234

Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

5678

920 9601120 11601120 1160

FHNQ40MV1FHNQ50MV1FHNQ60MV1

1360 1400FHNQ71MV11360 1400FHNQ90MV11550 1590FHNQ100MV11550 1590FHNQ125MV11550 1590FHNQ140MV1

CEILING MOUNTED CASSETTE TYPE

Notes:1Sticking location for manufacture's label manufacture's label for indoor unit: Suction grille inner side's electric components box's lid surface manufacture's label for decoration panel : Decoration panel's corner decoration cover inner surface2In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

3When the temperature and humidity in the ceiling exceed 30˚C and RH 80% or the fresh air is inducted into the ceiling or the unit continues 24 hour operation, an additional insulation (thickness 10mm or more of glasswool or polyethylene form) is required.

4Though the installation is acceptable up to maximum of 910mm square ceiling opening, keep the clearance of 35mm or less between the indoor unit and the ceiling opening so that

the panel overlap allowance can be ensured.5Please do not place the thing been damp and troubled under an indoor unit. When the case where humidity is 80% or more, and the drain outlet are choked up and the air filter are dirty, dew may fall.

[FCNQ40-140MV1] [FCNQ40-140MV1]

[FCNQ40-71MV1] [FCNQ40-71MV1]

[FCNQ40-71MV1]

[FCNQ40-71MV1] [FCNQ90-140MV1]

[FCNQ90-140MV1]

[FCNQ90-140MV1] [FCNQ90-140MV1]

7

6

950

8950

Pipe ConnectionSide

Drain ConnectionSide

Note 2

A arrow view

9

C

B

420

710(Hanging bolt pitch)420

860~910(Ceiling opening space) (Note 4)

860~

910(C

eiling

open

ing sp

ace) (N

ote 4)

780(

Han

ging

bol

t pitc

h)95

330

165

Connection positionof branch duct

160

20

16-M4 Prepared hole

50

350

12480

175

125

2

(square-shaped type)

4 1157

246

55

4-M8~M10

2x100=200 80

124

10

Hanging bolt

Connection positionof branch duct

C/L

110

(round shape type)

84055

280

256

40

Adjus

table(

0~67

5)

340

850

Connection positionof branch duct

1500

or m

ore

Connection positionof branch duct

20-M4 Prepared hole

60

From th

e floor s

ide 250

0 or mo

re

130

124

2x100=200

35 or less (Note 4)

55

A

150

84055

160

157256

105

(square-shaped type)

For h

eight

instal

lation

42

(requ

ired s

pace

)

(Note 4)95

3 85124

35 or less

5

(round shape type)

64

350

81

11050

124

81 2x100=200

350

Connection positionof branch duct

160

16-M4 Hole

B arrow view

(round shape type)

110

C/L124

85

157

(square-shaped type)

95

Connection positionof branch duct

80

157

213

95

160

Connection positionof fresh air intake kit

(square-shaped type)

C arrow view

(knock hole)90(round shape type)

124

183

109

25

C/L

124

802x1

00=200

(direct installation type)

ø100

20-M4Prepared hole

Connection positionof branch duct

Connection positionof branch duct

90

350

157

93

2x100=200 85

67

Connection positionof branch duct

C/L(round shape type)160

Connection positionof branch duct

16-M4 Hole

167

(square-shaped type)B arrow view

160

95

81

350

29

213

29

350

80

160

ø100

Connection positionof fresh air intake kit

C/L 157

90

(direct installation type)

67

(knock hole)

Connection positionof branch duct

C arrow view

Connection positionof branch duct

2x100=

200

(round shape type)

(square-shaped type)

196

93

90

8025

95

160

20-M4Prepared hole

167

280

5028

8

80

167

95

157

340840

16510

4Hanging bolt

1

175

55

4-M8~M10Connection positionof branch duct(round shape type)

Connection positionof branch duct

2

40

80

160

2x100=200

125

(square-shaped type)

C/L

298

20

350

850

Adjus

table(

0~67

5) 55

29

330

160

16-M4 Prepared hole

160

1500

or m

ore

81

93

157

130

Connection positionof branch duct

160

2x100=200

A

55

(square-shaped type)

From th

e floor s

ide 250

0 or mo

re

(Note 4)

67

105

For h

eight

instal

lation

85

150

(requ

ired s

pace

)

350

42

29

64

(round shape type)

27-M4 Prepared hole

60

35 or less (Note 4)

35 or less

3

Connection positionof branch duct

256

160 5

95

50

84055

167

The necessary space is 500mm or more when the air-outlet is blocked with the accessory.Moreover when the corner areas are blocked (both right and left of the blocked air outlet), the necessary space is 200mm or more.

1500mm or more200mm or more

1500mm or more

1500mm or more1500mm

or more200mmor more

Required space

300 or less

Liquid pipe connectionGas pipe connectionDrain pipe connectionPower-source wiring and a unit wiring connectionConnection wiring/remote control wiring connectionAir-outletSuction grilleCorner decoration coverDrain hose (accessory)

1234

5

6789

DIMENSIONS (Unit: mm)

Page 14: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

OUTDOOR UNIT // RNQ25/40MV1

25 26

22

50

100

50

150 50

50 300

150

100

285 8

Handle

Wall height on air outlet side =less than 1200Minimum space for air passage

105.5

13

311

490574

29.5

Drain outlet(I.D. 15.9 hose for connection)

4-Hole for anchor bolts (M8 or M10)

550

12 63765Brand name label

Manufacture’s label

196

165

105

Wiring inlet

Gas stop valve( 15.9CuT for RNQ13)( 9.5CuT for RNQ09)

Service port

In case of removing stop valve cover

Liquid stop valve( 6.4CuT)

300 or more

13531337

151

74 1626

3

7×P150=1050

1550

(All Around)

51

20-M4 Holes

8

10

16

305

150

280

1321

5012

3

1314

175

305

18-M4 Holes

212

206

(All Around)

152

827

274

1334

7×P150=1050 2

129 76

5

4

1353

146

3

151

600

116

(Sus

pens

ion

bolt

pinc

h)

381

3

1403

1550

(Suspension bolt pinch)126

55

427

8

680

Service space

[FDMNQ90/100/125/140MV1]

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

Note: 1Location of unit's Name Plate: Chamber cap

Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

1234

Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

5678

300 or more

7×P150=1050

263

151

20-M4 Holes

51

1350

1137

16

1121

8

10

305

(All Around)

16

150

74

280

1153

7

5

6

4

11141134

129

5012

3

18-M4 Holes

152

206

274

175

2

305

(All Around)727

212

7×P150=1050

126

600

1350

8

116

1153

680

3

381

3

(Suspension bolt pinch)

146

1203

151

427

(Sus

pens

ion

bolt

pinc

h)55

Service space

Service space

300 or more

260

10

236

16

151

102

1300

219

1104

1074

1088

18-M4 Holes

16

(All Around)

52 10

150

6×P.150=900

700

50

16-M4 Holes 29

26×P150=900

164

134

1064

(All Around)

170

260

228

107

1084

1

110 5

6

4

7

10 o

r mor

e

271

317

500

167

580

137

(Sus

pens

ion

bolt

pinc

h)(Suspension bolt pinch)

3

1300

151

551155 1268

31104

[FDBNQ60/71MV1]

[FDMNQ71MV1]

DUCT CONNECTION LOW STATIC PRESSURE TYPE

Note: 1Location of unit's Name Plate: Chamber cap

Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

1234

Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

5678

DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

Note: 1Location of unit's Name Plate: Chamber cap

Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

1234

Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

5678

DIMENSIONS (Unit: mm)

Page 15: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

OUTDOOR UNIT // RNQ90MV1, RNQ90MY1

OUTDOOR UNIT // RNQ100MV1, RNQ100/125/140MY1

OUTDOOR UNIT // RNQ50/60MV1

OUTDOOR UNIT // RNQ71MV1, RNQ71MY1

27 28

30

620

91

160

3030

Hole for anchor bolt 4-M12

55

(345~

355)

37

320

160

350

38

145

5

84

53

7

95

6

80

55

19

416

68

161

595

61

16

260

262

36

279

285

8 90

16

5

95

13

53

5

5522

3

6

7

67

52

339

89

95

19

2

5

3

6

4

990

142

34060

89

1

940

7

53

30

8019

84

6

5

55

95

145

54

7

24

1

95

2

19

142

54

7

89

900

6

60

1345

435

410

5

4

3

89

71 1670

45

58

5

102

191

16

376

811

7

48

30

140

3061

96

320

140

350

(345

~355

)

Hole for anchor bolt 4-M12

620

41

53

13

95

52

5522

3

5

67

12345678

Gas pipe connectionLiquid pipe connectionService port (in the unit)Grounding terminalRefrigerant piping intakePower supply wiring intakeControl wiring intakeDrain pipe connection

Gas pipe connectionLiquid pipe connectionService portGrounding terminalRefrigerant piping intakePower supply wiring intakeControl wiring intakeDrain pipe connection

12345678

50

50

300 30

0

50 300

150

50

100

20

845

573.5

20

131

734

2

300

78

326

300

Drain outletI.D. 18 hose for connection

4-Hole for anchor bolts (M8 or M10)

595

Brand name labelWiring inlet

Name plate

105

144

60

Earth terminal in switch box

Gas stop valve( 15.9CuT for RNQ21MV1)( 12.7CuT for RNQ18MV1)

Liquid stop valve( 6.4CuT)

Service port

Wall height on air outlet side =less than 1000Minimum space for air passage

325

36

350

78

580

330

825

2510

300

2124

Drain outletI.D. 15.9 hose for connection

4-Hole for anchor bolts (M8 or M10)

735

Brand name label Wiring inletName plate

3018

64

155160

89

Earth terminal in switch box

Gas stop valve( 15.9CuT)

Liquid stop valve( 9.5CuT)

Service port

350

100

50

100

100

50

350

50

350

Wall height on air outlet side =less than 1200Minimum space for air passage

DIMENSIONS (Unit: mm)

Page 16: PCSHK1531aprv 00 31 - Daikinweb.daikin.com.hk/en/products/download/PCSHK1531.pdf · Note: Some ceiling constructions may hinder installation. Contact your Daikin Dealer before installing

29 30

1000 or more

100 or more 100 or more

1000

or more

300

or more

L H

L H

100 or more 100 or more

300 or more

1000 or more

200 or more

100 or more 100 or more

500 or less

1000 or more

1000

or m

ore

An obstruction in the overhead space

100 or more

100 or more

300 or more

1000 or more

200 or more

500 or less

1000

or m

ore

An obstruction in the overhead space

100 or more

100 or more

When there is an obstruction on the inlet side

When there are obstructions on the inlet side and both sides

2. For multiple units installation (more than two units)

When there are obstructions on both sides

1) When the overhead space is open

1. For single unit installation

When there is an obstruction only on the inlet side

2) When there is an obstruction in the overhead space

1) When the overhead space is open

When there are obstructions on both sides

2) When there is an obstruction in the overhead space

When there is an obstruction on the inlet side

When there are obstructions on the inlet side and both sides

2. For multiple units installation (more than two units)

1. For single unit installation

1. For single unit installation

2. For multiple units installation (more than two units)

1. For single unit installation

2. For multiple units installation (more than two units)

1. For single unit installation

2. For multiple units installation (more than two units)

Note : As for other patterns of installation, please refer to Installation manual or Engineering Data Book.

1 When there is an obstruction on the outlet side2

1) When the overhead space is open (There is no limit to the height of the obstruction on the outlet side.)

When there are obstructions on both the inlet and outlet sides(When the obstruction on the outlet side is higher than the unit itself)

3

H

L

500

or more

100

or more

L H

100 or more

100 or more100 or more

100 or more

500 or more

100 or more

500 or less

1000

or m

ore

An obstruction in the overhead space

500 or less

500 or more

1000

or m

ore

An obstruction in the overhead space

150 or more

150 or more150 or more

500 or less

1000

or m

ore

An obstruction in the overhead space

For RNQ90-140MV1/Y1 REMOTE CONTROLLER

Wired type

Staple17

17

0~5

117

17(fl12~fl16)

A EXposed body, exposed cord C Exposed body, embedded code

( Distance between remote controller and control box )

B Exposed body, embedded cordConduit

CONTROL BOX

Through hole

Size

Specifications of cord

0.75~1.25 mm2

Total length 500 m

Type Vinyl cord with sheath or cable (Insulated thickness: 1 mm or more)

Note) 1. Remote controller cord and staple are not attached. they are field supplied parts.

Note) The dimension of hole.

* Countries requiring EMC: Shield wire (insulated thickness: 1 mm or more)

120

120

17 18

42

84

38

Cord outlet hole

282346

Wireless type

BRC1C61

BRC1NU61

BRC7NU66

Transmitting part

157

62 17.5

Liquid crystalremote controller(Wireless)

Remote controllerholder

CEILING SUSPENDED TYPE

A

22

38

6

A

41

13

A25R2

7

B

44.5

10

20

B

A

25

25 17

41.5

7

A

B

111

119

246

Hole type

a

10

20

4

B

a (mm)

ReceiverThe Front

Remote controller holderinstallation procedure<Installation to wall surface>

Remote controller holderinstallation procedure<Installation to wall surface>

Transmitting part

115.

5

54 18.1

Remote controller(Wireless)

Remote controllerholder

Receiver installation procedure

Service space for ceiling installation

Receiver detail

Note :

Mor

e th

an 9

0(S

revi

ce s

pace

)

120

72 83.5

106

(Ceil

ing o

penin

g)

70 180.5

35 49(Ceiling opening)

2-5x9 Slot

Switch box(field Supplied parts)

Do not install more than 3 receivers in the vicinity of one another.With 4 or more units, there is always the possibility of malfunction

Remote controller dimensions

Remote controller installation procedure

Receiver detail

Remote controller dimensions

BRC7F633F BRC4C64 CEILING MOUNTED CASSETTE TYPE <Round Flow>

• Receiver installation procedure • Receiver detailReceiver

Drain pipingside

Refrigerantpiping side

Decoration panel

19

Upper case Lower case

40

2346

2848.5

4284

5X7 oblong hole

Code outlet hole5X15 oblong hole

Lower case portion

Lower case portion

Staple

19

A Exposed cord C Embedded cord(use switch box)

B Embedded cord

84

46Switch box for two switchex.) KJB211A(optional accessory)

Condit

19

0~5

Switch box [field supplied part]

(Between remotecontroller and control box)

48.5

19

Note)2Through hole

40

( 8- 10)

84

28

Switch box for one switchex.) KJB111A(optional accessory)

• Installation method

2.If the hole size is too large or the location is not proper, the hole may come out from the remote controller.

Note) 1. Remote controller cord and staple are not attached. They are field

supplied parts.

Size

Specifications of cord

0.75~1.25 mm2

Total length 500 m

Type Vinyl cord with sheath or cable (insulated thickness: 1mm or more)

BRC1E62

(Green)120

120

   Operationlamp

Top left outlet

Left outlet

Top centeroutlet

DIMENSIONS (Unit: mm) Installation service space for outdoor unit (Unit: mm)