phase shifting transformers -...
TRANSCRIPT
Page 1 Siemens Energy, Inc.Phase Shifter Application Workshop
Phase Shifter Application Workshop
James McIver
SIEMENS Energy, Inc.SIEMENS Transformers Austria, Weiz
Phase Shifting Transformers –Principles, Design Aspects
and Operation
Page 2 Siemens Energy, Inc.Phase Shifter Application Workshop
Purpose and function of PSTs
Basic function of a PST§ In principle, a phase shifting transformer creates a phase
shift between primary (source) & secondary (load) side
§Usually, this phase shift can be varied under load
§Sometimes, it can be made advance and retard
A Phase Angle Regulator >Controls power flow through specific linesCreates a driving force onto power transmission networks
Page 3 Siemens Energy, Inc.Phase Shifter Application Workshop
Purpose and function of PSTs
How does phase shift influence power flow?
The „natural“ current distribution is dependent on theimpedance of the lines
i1
i2
X1
X2
itotal
VS VL
DV
Page 4 Siemens Energy, Inc.Phase Shifter Application Workshop
Purpose and function of PSTs
i1
i2VS VL
DV
DV
The „natural“ distribution may be rather inefficient, if X1 andX2 are extremely different.For example if X1 = 2*X2:
Page 5 Siemens Energy, Inc.Phase Shifter Application Workshop
Purpose and function of PSTs
Equalization of currents:
An additional voltage source must be introduced
i1 +Di
i2- Di
X1
X2
itotal
VS VL
~
VS´
VPST DV1
DV2
Page 6 Siemens Energy, Inc.Phase Shifter Application Workshop
Purpose and function of PSTs
This additional voltage source, perpendicular to the phasevoltage, generates a „circulating“ current, increasing i1 anddecreasing i2:
DV1
i1+Di i2- Di
VPST
DV2
DV2
DV1
VLVS´VS
VPST
Page 7 Siemens Energy, Inc.Phase Shifter Application Workshop
Purpose and function of PSTs
Another control need –
Power transfer between nodeswith fixed voltage
Node 1Voltage V1
Node 2Voltage V2
desired power flow
Power System
Page 8 Siemens Energy, Inc.Phase Shifter Application Workshop
Categories and types
Phase shifting transformers can be classifiedfor different parameters:
§ symmetrical – non symmetrical§ quadrature - non quadrature§ single core - two core§ single tank - two tank
Page 9 Siemens Energy, Inc.Phase Shifter Application Workshop
Categories and types
Non-symmetrical singlecore solution:
Advantageous for small phase angleand rating
Reversing switch operation is critical
§ Delta-connected excitingwinding,
§ One tap winding§ One LTC§ One reversing change-over
switch
Phasor Diagram:
j
L1 S1
L2
S3
S2L3
Winding Connection with Reversing Switch:S3 L2 S1 L3 S2L1
Page 10 Siemens Energy, Inc.Phase Shifter Application Workshop
Categories and types
Symmetrical single coresolution:
Load tap changers exposed to systemdisturbances
Rating strongly limited by LTC
§ Delta-connectedexciting winding
§ Two tap windings§ Two tap changers§ Two advance retard
switches j
L1 S1
L2S3
S2L3
Phasor Diagram:
L1 S1 L2 S2 L3 S3
Winding Connection with two ARS Switches:
Page 11 Siemens Energy, Inc.Phase Shifter Application Workshop
Categories and types
Alternative symmetricaloption:
Often used for lower voltage level
Delta- hexagonal design
§ Hexagonal connection ofexciting winding and tapwinding
§ One LTC§ Two ARS
Winding Scheme with Advance-Retard Switch:S1 L2 S2 L3 S3L1
RW
EW
AdditionalImpedance
j
L1 S1
L2S3
S2L3
Phasor Diagram:
Page 12 Siemens Energy, Inc.Phase Shifter Application Workshop
Categories and types
Classic solution:
Widely used in USA
Phase Shifting Transformer (PAR)
Winding Arrangement and Connections:
S1 L1 S2 L2 S3 L3
a b c
Phasor Diagram:
a
bc
Secondary (regulating) circuit
j
S1
L2S3
S2L3
L1
Primary circuit
§ Symmetrical two coredesign
§ Series unit and excitingunit
§ One LTC
Page 13 Siemens Energy, Inc.Phase Shifter Application Workshop
Operational considerations
Phase shifting transformers in Operation:
Variation of load voltage due to load current,ohmic components neglected
iLXPST
VS VL
~
VPST
VL0
jXPST*iL
a
iL
VL
VSVL0
Da
jXPST*iL VPST
j
Page 14 Siemens Energy, Inc.Phase Shifter Application Workshop
Operational considerations
Effect of load on effective phase angle
Page 15 Siemens Energy, Inc.Phase Shifter Application Workshop
Operational considerations
§ Impedance as low as possible, minimum value determinedby short circuit requirements
§ With lower impedance, no load phase angle can be reduced
§ Lower no load phase angle means lower design rating, lowerweight, lower cost.
For a given phase shift under load, designoptimization is necessary:
Page 16 Siemens Energy, Inc.Phase Shifter Application Workshop
Page 17 Siemens Energy, Inc.Phase Shifter Application Workshop
Tap changer limitations @Max MVA andregulating angle
§ PST’s can be designed with fixed or variable phase angle.For a variable phase angle design, a load tap changer(LTC) and a regulating winding is required.
§ In general, the regulating winding and therefore the LTCmust be designed for the maximum design rating of thePST
§ The maximum regulating capacity (switching capacity perstep times the number of steps) is limited by the capacityof available tap changers.
Tap changer application
Page 18 Siemens Energy, Inc.Phase Shifter Application Workshop
Tap changer application
Maximum throughput rating Pmaxversus maximum regulating capacity R
0
2
4
6
8
10
0 10 20 30 40 50 60Maximum phase angle (deg)
Pmax/R
Single core, with two tap changers
Single core, with hexagonal winding connection
Dual core, with series and exciting unit
Page 19 Siemens Energy, Inc.Phase Shifter Application Workshop
Page 20 Siemens Energy, Inc.Phase Shifter Application Workshop
F1
FS
F2
F1FS
2 1
F2
Power transformerFlux distribution at rated load, cos j ~ 1
Operational considerations
Page 21 Siemens Energy, Inc.Phase Shifter Application Workshop
Testing
Testing phase shifting transformers :
Heat run§ PST fully assembled§ minimized deviation of loss distribution during short circuit
condition§ access to all windings for resistance measurement
Specific requirements:
Induced voltage test§ PST fully assembled§ tests at zero and maximum phase shift
Page 22 Siemens Energy, Inc.Phase Shifter Application Workshop
Testing
Heat run test:
For resistance measurement, all these connections can be opened
Temporary bushings inserted at all connections between series and exciting unit
~
Series Transformer
Exciting Transformer
AuxiliaryBushings
Short circuit connection
Page 23 Siemens Energy, Inc.Phase Shifter Application Workshop
No Load Losses (kW) a = 0 a =maximum
Series UnitExciting Unit
0100
10070
Load Losses (kW) a = 0 a =maximum
Series UnitExciting Unit
4000
400400
Total Losses (kW) a = 0 a =maximum
Series UnitExciting Unit
400100
500470
Note difference in loss distribution for nominaloperation vs. condition for heat run test
Design consideration - Heat run test settings
Page 24 Siemens Energy, Inc.Phase Shifter Application Workshop
Testing
Induced voltage test:
Application of an additional step-up transformer is avoided by proper tap selection
Temporary bushings are connected to the regulating winding
S2 L2 S3 L3S1 L1
Series Transformer
Exciting Transformer
~ Auxiliary bushings
Page 25 Siemens Energy, Inc.Phase Shifter Application Workshop
Operational considerations
Bypass breaker considerations
§ Due to the PST’s impedance, inserting the PST withphase angle zero normally reduces the load flow
§ A minimum advance phase angle is necessary to restorethe original load flow condition
§ Therefore, by-passing the PST might be advantageous incertain conditions
§ On the other hand, lightning strikes can also appear withthe PST by-passed
§ Internal stresses have to be investigated carefully for thiscondition
Page 26 Siemens Energy, Inc.Phase Shifter Application Workshop
Testing
Lightning impulse test:
Recommended test if by-pass breaker is provided - at least for tap position zero (0°)
Only the primary windings of one phase are shown
L2S2 S2 L2
Standard LI test:
Source- andload- terminalconnected
Special LI test:
Page 27 Siemens Energy, Inc.Phase Shifter Application Workshop
Testing
-50
0
50
100
150
0 40 80 120T(ms)
V(%)
Applied voltage and typical wave shape of voltage at crossover during lightningimpulse test with source and load side terminals connected
Lightning impulse stresses in the series winding
Page 28 Siemens Energy, Inc.Phase Shifter Application Workshop
Phase shifting transformer protection
In PST, difference between source & load current @ normaloperating condition becomes too large for conventionaldifferential protection.
Therefore, specific differential schemes for PST’s are required,different for single core and dual core designs.
CTs required for protection often located inside tank of the PST.
NOTE > protection scheme must be finalized @ design stage.
In general, PST protection is similar to power transformers.There is one exception > differential relaying
Page 29 Siemens Energy, Inc.Phase Shifter Application Workshop
Differential protection scheme for dual core design (example)
87-1
87-2
S1
L1
S2
L2
S3
L3
primary
secondary
Page 30 Siemens Energy, Inc.Phase Shifter Application Workshop
Recent PST units
Phase Shifting Transformer
Two-tank designTwo-core design
Classical design PST
n 700MVA, 230kV, 60Hzn ±32° no load (± 24Taps); 22.2°..-41.8° loadn uk: 11.1% Tap 0; 17.4% Tap 24n Noise Level < 74 dB(A) with fans
Page 31 Siemens Energy, Inc.Phase Shifter Application Workshop
Recent PST units
Phase Shifting Transformer
Two-tank designTwo-core design
Classical design PST
n 800MVA, 230kV, 60Hzn ±35° no load (± 32Taps); load 25.3°..-44.9°n uk: 11.4% Tap 0 ; 17.6% Tap 32n Noise Level < 77dB(A)
Page 32 Siemens Energy, Inc.Phase Shifter Application Workshop
650 MVA, 525 kV, ±24°, Largest PSTs in world,(2) for SRP, Arizona and (2) for NPC, Nevada
Page 33 Siemens Energy, Inc.Phase Shifter Application Workshop
Lake ElsionrePumpPowerHouse
To SCE ValleySub 30
miles
To SCE SerranoSub32
miles
500 kV230 kV115 kV
13.8 to 20 kVExisting
New AdditionsFurtherAdditions
16.5miles
12.7miles
To SDG&E TalegaSub10
miles
To SG&E EscondidoSub37
miles
Lee LakeSubstation
Camp PendletonSubstation
LEAPSTransmission One-
Line
Page 34 Siemens Energy, Inc.Phase Shifter Application Workshop
Recent PST units
Phase Shifting Transformer
Classical design PST
n 300 MVA, 138 kV, 60 Hz
n ±25.0° at no load (± 16 taps);n 14.4° at rated load - extreme advancen -5.4° at rated load - mid tapn -35.6° at rated load - extreme retardn uk: 9.5% Tap 0; 18.6% Tap 16n Noise level < 70 dB(A)
Single-tank designTwo-core design
Page 35 Siemens Energy, Inc.Phase Shifter Application Workshop
Recent PST units
Phase Shifting Transformer
Classical design PST
Two-tank designTwo-core design
n 1200MVA, 400kV, 50Hzn ± 24° no load (±16 taps);n 16.6° at rated load - extreme advancen -5.3° at rated load - mid tap (0)n -31.4° at rated load - extreme retardn uk: 9.25% Tap 0; 13.0% Tap 32n Noise power level < 80 dB(A) - sound house
Page 36 Siemens Energy, Inc.Phase Shifter Application Workshop
Phase shifting transformers >
•Look like normal power transformers
•Manufactured using the same technology
However, several special aspects only in PST’s
PST issues appear in both design and testing.
Therefore special expertise required.
Conclusion
Page 37 Siemens Energy, Inc.Phase Shifter Application Workshop
Conclusion
§The classical two-tank two-core solution:Offers greatest operational security @higher voltageThis because LTC not directly exposed to systemdisturbances.
§The single-core solution offers economic advantagesat lower system voltage levels (and lower MVA).
Page 38 Siemens Energy, Inc.Phase Shifter Application Workshop
Thank you!
Questions?