BUSHINGS: GENERAL INFORMATION 1.0 Electrical characteristics (Ir = rated current; Ur = rated voltage) 1.1Standard insulation levels
Rated voltage Ur
kV (r.m.s.)
One minute power frequency withstand voltage wet and dry
kV (r.m.s.)
Dry lighting impulse withstand voltage dry
(1,2/50 ms) kV
1 3,6 12 24 36 52
10 10 28 50 70 95
20 40 75
125 170 250
1.2 Standard values of rated thermal short time current (Ith) 25 times the rated current (Ir) for 2 s ; for Ir equal or greater than 4000A, Ith is always 100kA 1.3 Overload conditions (IEC 354): Bushing selected with Ir not less than 120% of the rated current of the transformers are considered to be able to withstand the overload conditions according to IEC 354. 2.0 Mechanical characteristic 2.1 Cantilever operating load (bushing installed less than 30° from vertical)
Ur Ir
kV 800 A 1600 A 2500 A 3150 A
36 52
500 N 500 N
625 N 625 N
1000 N 1000 N
1575 N 1575 N
2.2 Cantilever operating load ( bushing installed more than 30° from vertical)
Ur Ir
kV 800 A 1600 A 2500 A 3150 A
36 52
300 N 300 N
375 N 375 N
600 N 600 N
945 N 945 N
2.3 Cantilever test load
Ur Ir
kV 800 A 1600 A 2500 A 3150 A
36 52
1000 N 1000 N
1250 N 1250 N
2000 N 2000 N
3150 N 3150 N
File : ISOLATORI DISTRIBUZIONE UNCONTROLLED COPY Rev. 4 dtd 22/03/11
3.0 Tightening torque (suggested values, +/- 10% depending on the quality of the tank cover surface) 3.1 On the central conductor LV/HV in brass or copper
3.2 On the steel fixing stud of HV bushings
Size Torque
M10 M12 M16
15 Nm 25 Nm 40 Nm
3.3 On the locking bolts of the flags
Size Torque
M10 M12 M16
25 Nm 40 Nm 90 Nm
File : ISOLATORI DISTRIBUZIONE UNCONTROLLED COPY Rev. 4 dtd 22/03/11
4.0 Surface treatment of active metallic parts Unless by special request, all active metallic parts in brass and copper have self colour surfaces. Upon request, particularly for use in highly polluted enviroment conditions or in tropical climate, above parts can be supplied with electrolytic tinplated surfaces with 6-8 micron average coating thickness. 5.0 N.B.R. gaskets The material of our gaskets is suitable to be used in mineral oil at the max temperature of 100°C (minimum temperature -20°C) for continous service; for different limit temperatures, please contact our engineering department. During the impregnation of the transformer it is possible to reach the max temperature of 110°C in oil and 120°C in air for 24 hours, without damaging the gaskets. Upon request available cork rubber impregnated gaskets, or in Viton, or in silicon rubber.
Sect. 1 : L.V. BUSHINGS Page 1.8/1.9 : L.V. bushings according to DIN 42539 (3,6 kV) Page 1.10 : Bushings type 3/4500-6300
Sect. 2 : BUSHINGS HV-250 Page 2.1 : Bushings type 10-20-30Nf/250 acc. to DIN42531 standard Page 2.1EN : Bushings type 12-24-36/250 P1-2-3-4 acc. to the new european standard EN50180 Page 2.2EN : Kit H-ED-025 acc. to the new european standard EN50180 Page 2.3 : Special 36kV bushings with long creepage distance Page 2.4 : Arching horn assembly for HV250 single gap Page 2.5 : Arching horn assembly for HV250 double gap
Sect. EPOXY :
Sect. 3-MT : BUSHINGS HV-630 Page 3.1 : Bushings type 10-20-30Nf/630 acc. to DIN42532 standard Page 2.1EN : Bushings type 12-24-36/630 P1-2-3-4 acc. to the new european standard EN50180
Sect. 4-BT : CONNECTING FLAGS
HV Plug-in type bushings LV Busbar Bushing Monoblock bushing plates acc. to BS2562 Cable boxes acc to BS2562