portable hydrant pn10 1a; 2a; 1b; 2b; 1c; 2c · pdf file- to pehd pipe with socket and locking...

15
0 revision Rights reserved to modify dimensions or weights depending on the technical EDITION 2003 PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C TYPES HP 10 page 1A APPLICATION: In water supply systems for fire extinguishing or other necessities. DESIGN AND WORKING CHARACTERISTICS: - Design ............................................................. in conformity with STAS 698; - Nominal pressure .............................................…………. 10 bar; - Working temperature range ...……………………….....……..Tmax / Tmin : 40°C / 4°C; - Execution : - type 1 - with simple elbow; - type 2 - with double elbow; - Size of connecting piece: - A , B or C, STAS 701. MATERIALS: - Double elbow, single elbow, tube body, connecting nut with ears, sealing flange, fixed connector, bonnet ................................................ aluminium alloy; - Gasket ................................................................................................................. rubber. (dimensions in mm) HYDRANT TYPE d1 d2 d3 d4 L1 h1 Net weight ~(kg) 1A 2A 192 Rd 120 100 146 330 780 14.5 16.2 1B 2B 8.8 11 1C 2C 160 Rd 85 70 103 250 740 8 10 Product approved by Romanian Firemen’s Committee (type 1) (type 2)

Upload: truongdan

Post on 31-Jan-2018

219 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0 revision

Rig

PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C TYPES

HP 10 page 1A

(type 1 (type 2)

APPLICATION: In water supply systems for fire extinguishing or other necessities. DESIGN AND WORKING CHARACTERISTICS: - Design ............................................................. in conformity with STAS 698; - Nominal pressure .............................................…………. 10 bar; - Working temperature range ...……………………….....……..Tmax / Tmin : 40°C / 4°C; - Execution : - type 1 - with simple elbow; - type 2 - with double elbow; - Size of connecting piece: - A , B or C, STAS 701. MATERIALS: - Double elbow, single elbow, tube body, connecting nut with ears, sealing flange, fixed connector, bonnet ................................................ aluminium alloy; - Gasket ................................................................................................................. rubber. (dimensions in mm)

HYDRANT TYPE d1 d2 d3 d4 L1 h1 Net weight

~(kg) 1A 2A 192 Rd 120 100 146 330 780 14.5

16.2 1B 2B

8.8 11

1C 2C

160 Rd 85 70 103 250 740 8 10

Product approved by Romanian Firemen’s Committee

hts reserved to modify dimension

)

s or weights depending on the technical EDITION 2003

Page 2: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0 revision

UNDERGROUND HYDRANT PN 10 DN 65; 100

with locking sleeve

pipe

Connection

APPLICATION: Used as fire extinguishing equipment, may be connected to drinking water or industrial water systems PN 10 as follows: - connecting flanges DN 65÷125 PN10 ISO 7005-2; DIN 2501; BS EN 1092-2; - to PEHD pipe with socket and locking sleeve; - connecting flanges DN 65÷125 DIN 28604 PN10 for ductile iron pipes. It has been designed in order to operate in difficult working media, industrial areas, seaside or with hot climate. DESIGN AND WORKING CHARACTERISTICS: The underground hydrant HSX is manufactured in conformity with STAS 695 issued in cooperation with Firemen’s Committee. Allows the connection of portable hydrant STAS 698 or the connection of portable hydrant with valves STAS 697. The hydrant is has been designed to carry out the following functions: - shutting-off - opening – by operating hydrant stem with a special driving key (STAS 696), the operating stress being low; - at opening, the draining system shall be completely obturated, internal parts design assuring a minimum head loss, and at shutting-off the draining system shall be opened in order to allow water removal from the hydrant; - complete hydrant disassembling and spare parts replacement may be easily performed; - freezing protection – hydrant internal part, being above the main seat, shall be released of the water remained after operation. The bore located at the lower part assures an inside draining within max. 10 minutes. Waste water volume remained into the hydrant after complete draining is not exceeding 50 cm³; - disc gasket may be replaced without hydrant digging out. COMPONENTS: 1. Protection box - in conformity with STAS 3226; 2. Hydrant - in conformity with STAS 695; 3. Foot elbow: - flanged (standard execution); - with flange and locking sleeve (execution on order); - with flange and sleeve - in conformity with STAS 1875 (execution on order). MATERIALS OF MAIN PARTS: - obturator box, obturator body, bonnet, body, nut support, driving head: - cast iron EN GJL 250 SR EN 1561; GG25 DIN 1691; - body of jaw connection: - ductile iron EN GJS 500-7 SR EN 1563; GGG50 DIN 1693; - stem nut, seating ring, disc seat: - copper alloy; - stem, connecting pipe: min. 11,5% Cr stainless steel; 410 S21 BS 1506; X20Cr13 DIN 17440; - obturator, gaskets: - EPDM rubber STAS 7278; - bolting: - stainless steel A2-70. PROTECTION AGAINST CORROSION: All internal surfaces, except for: rubber, stainless steel or bronze surfaces, also external surfaces of underground part are coated with epoxy powder paint 250µm thick, GSK quality, standard colour RAL 3009. Protection box is coated with zinc primer and black resin epoxy paint. DATA TO BE SUBMITTED WITH THE ORDER: User shall specify: execution variant, nominal diameter, burying depth, type of connecting flange.

RigFo

(dimensions in mm)

Overall dimensions System connecting dimensions Jaw connection Net weight

~(kg) DN DE DN of system

connecting flange

H1 H d1 d2 nxd3

ξ

Head loss factor d4 d5 Hydrant Protection

box Foot

elbow

100 730 44.5 1250 980 48.5 65 1500 1230

185 145 4x18 25

65 75 90 90 115 30.7 2.8 52.5

1000 730 45.2 1220 980 49.2 80* 200 160* 26.4

8x18 1500 1230 53.2 1000 730

100 110 125

100

70.5 1250 980 77 1500 1230

128 150 83.5

46.5 32 3.2

Product approved by Romanian Firemen’s Committee

220 180

hts reserved to modify dimensions or weights depending on the technical EDITION 200r confirmation, please use the technical sheet of agreement (FTC 19)

HSX-10 page 2 A

3

Page 3: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0 revision

SURFACE HYDRANT PN 10

APPLICATION: - in water supply systems for fire extinguishing or for other needs. DESIGN AND WORKING CHARACTERISTICS: - design ....................................…….. in conformity with STAS 3479; - nominal pressure ......................…. 10 bar; - working temperature range ………. Tmax/Tmin: 40°C / 4°C; - operation ....................................…. manual; - seat …........................................… rubber / metal; - dimensions of connecting flanges... PN10 – ISO 7005-2;

BS EN 1092-2; DIN 2501. MATERIALS: - body, bonnet, obturator body, driving bonnet

- cast iron EN GJL 250 SR EN 1561; GG25 DIN 1691; - ductile iron EN GJS 500-7 SR EN 1563, GGG50 DIN 1693, on special request;

- body seat ring : copper alloy; - obturator gasket: rubber; - A, B, C type connectors : aluminium; PROTECTION AGAINST CORROSION: All internal surfaces, except for: rubber, stainless steel or bronze surfaces, also external surfaces of underground part are coated with epoxy powder paint 250µm thick, GSK quality, standard colour RAL 3009. The above-groundpart is externally coated with RAL 3020 red. DESIGNATION: - Surface hydrant DN x H1; - DN - nominal diameter [mm]; - H1 - burying depth [m]. (dimensions in mm)

Connectors Net weight ~ kg DN H H1 H2 d1 d2 nxd3

Quantity Type Dimensions (inch) Hydrant Foot

elbow 2390 1250 2120 2 C 2" 185 80 2630 1500 2360 200 160 1 A 4" 190 26.4

2450 1250 2120 2 B 2 1/2" 246 100 2690 1500 2360 220 180 8x18

1 A 4" 250 32

Product approved by Romanian Firemen’s Committee

Rights reserved to modify dimensions or weights depending on the technical EDITION 200For confirmation, please use the technical sheet of agreement. (FTC 20)

HSf-10 page 3 A

3

Page 4: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0 revision

Rights rese

Used a follows- conne- to PE- conne

of the h

climatebolting - saf

affe- Sh- Pro

affe- At

hea- Fre

remmin

- Eaaga

- Bu- Po- Co All interundergThe ab

SURFACE HYDRANT “FOCUS” TYPE

PN 16

APPLICATION:

s fire extinguishing equipment, may be connected to drinking water or industrial water systems PN 16 as: cting flanges DN 80÷100 PN16 ISO 7005-2; DIN 2501; BS EN 1092-2;

HD pipe with socket and locking sleeve; cting flanges DN 80÷100 DIN 28605 PN16 for ductile iron pipes.

DESIGN AND WORKING CHARACTERISTICS:

Designed in 3 modules, FOCUS hydrant ensures besides a modern design a performance at the level ighest European exigencies in matters of fire extinguishing equipment and valves. FOCUS was designed for operation in difficult medium conditions, industrial areas, and seaside or cold

. Internal and external coating system with epoxy powder meeting GSK norm requirements, also all manufactured in stainless steel A2-70, assure a long lifetime. FOCUS meets the requirements of DIN 3222 and STAS 3479, carrying out the following functions:

e tightness at two levels: disc and spherical obturator. EPDM parts, also the design system are not cted by possible deposits or sediments.

utting-off – opening, by operating hydrant stem with a special driving key, the operating stress being low.tection against eruption – the above-ground part is able to support accidental lateral impacts without cting tightness. Hydrant repaire shall consist only in bolts and half-flanges replacement

opening, the draining system shall be completely obturated, internal parts design assuring a minimum d loss. ezing protection – hydrant internal part, being above the main seat, shall be released of the water ained after operation. The bore located at the lower part assures an inside draining within max. 15 utes. Waste water volume remained within the hydrant after complete draining is not exceeding 80cm³.

sy connection through the two, respectively, the three specific connectors, protected with covers safe inst theft.

rying depth: 1.25 m or 1.5 m, depending on requests. ssibilities of angular orientation of the upper body. nnection to different pipe types: steel, PEHD and ductile iron.

MANUFACTURER TESTS:

- shell and compactity: 24 bar; - seat 17.6 bar. Tests are 100% performed on each product in a lot.

PROTECTION AGAINST CORROSION:

nal surfaces, except for: rubber, stainless steel or bronze surfaces, also external surfaces of round part are coated with epoxy powder paint 250µm thick, GSK quality, standard colour RAL 3009. ove-ground part is externally coated with RAL 3020 red.

rved to modify dimensions or weights depending on the technical EDITION 200

FOCUS page 4 A

3

Page 5: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0 revision

Ri

SURFACE HYDRANT “FOCUS” TYPE PN 16

FOCUS page 5 A

th locking

H1

– bu

ryin

g de

pth

pipe

DESIGN AND WORKING CHARACTERISTICS: - nominal pressure ….......................…..16 bari; - working temperature range ………..... Tmax/Tmin : 40°C / 4°C; - seat ......................................……..…. rubber / metal; - burying depth: ………......................…1.25 m and 1.5 m; - operation........................................…. manual, with special key; - Possibility of angular orientation of the upper body; - Protection against eruption; FOCUS was designed to meet DIN 3222 and STAS 3479 standard requirements. MATERIALS OF MAIN PARTS: - obturator body, lower body, protection half-flange, bonnet: - cast iron EN GJL 250 SR EN 1561; GG25 DIN 1691; - upper body: - ductile iron EN GJS 500-7 SR EN 1563; GGG50 DIN 1693 on special request; - disc: - ductile iron EN GJS 500-7 SR EN 1563-99 / EPDM rubber; - nut 1: - cast iron / EPDM rubber; - obturator: - ATCu8 / EPDM rubber; - driving bonnet: - ductile iron EN GJS 500-7 SR EN 1563, GGG50 DIN 1693; - stem: - min. 11,5% Cr stainless steel; 410 S21 BS 1506; X20Cr13 DIN 17440 / copper alloy; - connectors A, B type : - aluminium; - bolting: - stainless steel A2-70. DATA TO BE SUBMITTED WITH THE ORDER: User shall specify: execution variant, nominal diameter, burying depth, type of connecting flange. (dimensions in mm)

DN DE H H1 h1 h2 d1 d2 nxd3 ConnectorNet

weight~(kg)

2445 1250 135 80 90 2695 1500 200 160 2xB 139 2470 1250 160 100 110 2720 1500

1035 795 220 180

8x182xB + 1xA 164

Connectors

DN Pieces Type Dimensions 80 2 B 2 1/2"

2 B 2 1/2" 100 1 A 4"

Product approved by Romanian Firemen’s Committee

Connection wisleeve

ghts reserved to modify dimensions or weights depending on the technical EDITION 2003

Page 6: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0

Rights reserved to modify dimensions or weights depending on the technical EDITION 200For confirmation, please use the technical sheet of agreement. (FTC 20)

SURFACE HYDRANT PN 16

2 B 2 1/2" 2 A 4" 150 525 - 546 2860 1535 2415 1165 700 380 285 240 8x22 2 B 2 1/2"

Product approved by Romanian Firemen’s Committee

APPLICATION: - in water supply systems for fire extinguishing or for other needs. DESIGN AND WORKING CHARACTERISTICS: - nominal pressure ….......................….16 bar; - working temperature range ………..... Tmax/Tmin : 40°C / 4°C; - operation ......................................….. manual; - seat .......................................…….… rubber / metal; - dimensions of connecting flanges .…. PN16 – ISO 7005-2;

BS EN 1092-2; DIN 2501. MATERIALS: - body, bonnet, disc body , driving bonnet - cast iron EN GJL 250 SR EN 1561; GG25 DIN 1691; - ductile iron EN GJS 500-7 SR EN 1563; GGG50 DIN 1693, on special request; - body seat ring .............…. copper alloy; - disc gasket ….................. rubber; - stem ..........................…... min. 11,5% Cr stainless steel;

410 S21 BS 1506; X20Cr13 DIN 17440; - connectors A, B, C type ... aluminium; PROTECTION AGAINST CORROSION: All internal surfaces, except for: rubber, stainless steel or bronze surfaces, also external surfaces ofpart are coated with epoxy powder paint 250µm thick, GSK quality, standard colour RAL 3009. The part is externally coated with RAL 3020 red. DESIGNATION: - Surface hydrant DN x H1; - DN - nominal diameter [mm]; - H1 - burying depth [m]. (dime

DN L L1 L2 H H1 H2 H3 H4Connectors

H5 d1 d2 nxd3Quantity Type Dimensions

(inch) h

1 A 4" 100 512 265 - 2640 1305 2310 1210 823 505 220 180 8x18

HSR-16 page 6 A

revision

3

375 37.5

underground above-ground

nsions in mm) Net weight

~(kg) ydrant foot

elbow

244 32

Page 7: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0 revision

R

A T b W ---

------

PPLICATION:

he automatic plants for fire extinguishing water-water system are so designed that, without man intervention, canoth detect fire beginning and extinguish it with damages at the smallest level.

ORKING AND DESIGN CHARACTERISTICS:

nominal pressure .............…............................. ..10 bar; working pressure range ...................………........ 3 ÷ 10 bar; working fluid ................................…...........….... drinking or industrial water with max. slurry

10 000 mg/dm3 and pH 6.5 ÷ 8.5; working temperature range ……….................... Tmax/Tmin : 40°C / 4°C; electric switch box supply voltage .................... 220 V ; 50 Hz; mounting position ........................................….. vertical; electric switch box protection degree ................ IP 32; connecting flanges ......................................….. PN 10 – ISO 7005-2; BS EN 1092-2; DIN 2501; net weight ................................................…..…. ~ 394 kg.

Product approved by Romanian Firemen’s Committee

ights reserved to m

SIGNALING AND CONTROL DEVICE FOR AUTOMATIC FIRE EXTINGUISHING PLANTS OF SPRINKLERS TYPE,

WATER-WATER SYSTEM PN 10 DN 150

odify dimensions or weights depending on the technical EDITION 200

ISIA-10 page 7 A

3

Page 8: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0 revision

Rights reserved to modify dimensions or weights depending on the technical

wat

er

inle

t

APPLICATION: The automatic plants for fire extinguishing water-air system are so designed that, without man intervention, can both detect fire beginning and extinguish it with damages at the smallest level. WORKING AND DESIGN CHARACTERISTICS: - nominal pressure .............….......................…...10 bar; - working pressure range ...................……….......3 ÷ 10 bar; - working pressure range in the sprinklers system ..................…………………….1.5÷2.5 bari - working fluid ................................…...........…....drinking or industrial water with max. slurry 10 000 mg/dm3; - working temperature range ……….................... Tmax/Tmin : 40°C / 4°C; - electric switch box supply voltage .................... 220 V ; 50 Hz; - mounting position ........................................…..vertical; - electric switch box protection degree ................IP 32; - connecting flanges ......................................…..PN 10 – ISO 7005-2; BS EN 1092-2; DIN 2501; - net weight .................................................….... ~ 450 kg.

Product approved by Romanian Firemen’s Committee

ISIAE-10 page 8 A

SIGNALING AND CONTROL DEVICE FOR AUTOMATIC FIRE EXTINGUISHING PLANTS OF SPRINKLERS TYPE,

WATER-AIR SYSTEM PN 10 DN 150

EDITION 2003

Page 9: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0 revision

SOLENOID VALVE PN 10 DN 150

VE-10 page 9 A

Rig

APPLICATION: The PN 10 solenoid valve is used in fire extinguishing plants on the main water supplying pipe. WORKING AND DESIGN CHARACTERISTICS: - working pressure .......................... 10 bar; - nominal diameter .......................... 150 mm; - working temperature range ……… Tmax/Tmin: 40°C / 4°C; - working fluid …............................. water; - flow direction ........................….... unique; - seat ……....................................... rubber / metal; - connecting flange ......................... PN10 ISO 7005-2; BS EN 1092-2; DIN 2501; - operation ....................................... electric, electromagnet 220 V c.a. ; 24 V c.c. ; P = 1,55 kW;

protection degree IP 44; - opening time ………....................... max. 4 sec. - maintaining in open position .......... max. 30 min. - pause time .................................... 3 hours; - mounting position ........................... on horizontal pipes with electromagnet up; - net weight ...................................... ~122 kg. MATERIALS: - body, disc, closing flange - cast iron EN GJL 250 SR EN 1561; GG25 DIN 1691; - disc seat - copper alloy; - adjusting stem, driving stem, seat - min. 13% Cr stainless steel; 410 S21 BS 1506; X20Cr13 DIN 17440;- disc gasket - rubber.

Product approved by Romanian Firemen’s Committee

hts reserved to modify dimensions or

weights depending on the technical EDITION 2003
Page 10: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0

Rights reserved to modify dimensions or weights depending on the technical EDITION 2003

AEROMECHANICAL FOAM GENERATOR FOR TANKS WITH FIXED BONNET

p

220 180 295 12x22 1253 1160 450 55 400 2

Product approved by Romanian Firemen’s Committee

APPLICATION: - in fix fire extinguishing plants at the tanks for petroleum products and inflammable liquids, plants usinextinguishing agent a mixture of air, water and foamy liquid (aeromechanical foam). DESIGN AND WORKING CHARACTERISTICS: - working presure range .....................................………..… 3.5 ÷ 7 bar; - solution flow ............................................……….........…... 400; 800; 1600 l/min; - foam ratio in water ..................................…………............ 6 %. MATERIALS: - body, bonnet, suction chamber, flanges ...................…... OL – carbon steel – St 37-3 DIN 17100. (dimen

Size Solution

flow at 5 bar [l/min]

d1 d2 nxd3 d4 d5 d6 nxd7 A B C D E F

GSA400CF 400 50 100 4x18 165 125 180 8x18 1010 950 300 60 130 270 2GSA800CF 800 80 150 200 160 240 8x22 1150 1020 350 85 350 2

GSA1600CF 8x18 170 1600 100 200

GSCF age 10 A

revision

90 82

g as

sions in mm)

G Net

weight ~(kg)

30 40 35 58

Page 11: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0

on the technical

AEROMECHANICAL FOAM GENERATOR FOR TANKS WITH FLOATING BONNET

APPLICATION: - in fix fire extinguishing plants at the tanks for petroleum products and inflammable liquids, plants uextinguishing agent a mixture of air, water and foamy liquid (aeromechanical foam). DESIGN AND WORKING CHARACTERISTICS: - working pressure range ..................................….... 3.5 ÷ 7 bar; - solution flow ....................................................….... 200, 400 l/min; - expansion degree ................................................... 7 ÷ 8; - foam ratio in water …….....................................….. 6 %. MATERIALS: - body, flanges .......................................................... OL – carbon steel – St 37-3 DIN 17100. (dimensions in mm)

Size Solution flow at 5 bar [l/min] A B

Net weight ~(kg)

GSA 200 CP 200 575 250 9.8 GSA 400 CP 400 755 350 11

Product approved by Romanian Firemen’s Committee

Rights reserved to modify dimensions or weights depending EDITION 200

GSCP page 11 A

revision

sing as

3

Page 12: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0

Rights reserved to modify dimensions or weights depending on the technical EDITION 200

AUTOMATIC WATER DOSIMETER WITH VARIABLE FLOW

ATif D------ M----

water inlet

DAS-16 page 12 A

revision

PPLICATION: he automatic water dosimeter with variable flow is used in fire extinguishing systems at petroleum and

nflammable product plants using as extinguishing agent a mixture of water and foamy liquid (aeromechanical oam). ESIGN AND WORKING CHARACTERISTICS:

min. water flow ...............................................…..... 1000, 1200, 1600 l/min; max. water flow ...............................................….... 10 000, 12 000, 16 000 l/min; foam ratio in water ……...................................…..... 6 %; water max. working pressure ...........................…... 12 bar; foam working pressure ........................…………..... water pressure + 1 bar; flanges nominal pressure ...............................…….. 16 bar.

ATERIALS: sections : - carbon steel; case : - cast steel; gasket : - rubber, klingerite; sleeve : - NBR rubber.

(dimensions in mm)

Size D d1 d2 nxd3 D2 D4 nxd5 Net

weight ~(kg)

DSA 1000÷10000 250 65 145 335 405 305 DSA 1200÷12000 80 160 325 DSA 1600÷16000 300 100 180

4x18 410 460 12x26 350

Product approved by Romanian Firemen’s Committee

3

Page 13: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

0

Rights reserved to modify dimensions or weights depending on the technical EDITION 2003

pDISCHARGE VALVE FOR TANK WAGONS

For confirmation, please use the technical sheet of agreement. (FTC 30 )

RVC age 13 A

revision

DESIGN CHARACTERISTICS: - nominal diameter: DN 100 - maximum working pressure: 4 bar - maximum flow speed through the valve: 2.5 m/s - connecting flanges: PN10 SR-ISO 7005/2-97 - raised and notched sealing surfaces: PN10 STAS 1732-80 - working fluid: -white or black petroleum products, fuel, aircraft fuel, fuel for reaction aircrafts,

kerosen, white-spirit, etc . - branch flange shall be delivered on customer request, fitted with 8 nuts M16 gr.8 STAS 4071-89 and 8

Grower washers SR 7666/2-N16. MATERIALS: - body, disc: - ductile iron 400-18-L SR ISO 1083 – GGG - disc gasket: - rubber - VITON type - bonnet gasket: - rubber - VITON type - NBR type. - shaft: - min. 11,5% Cr stainless steel. SEATS: - body/disc: - gasket - VITON type; - body/bonnet: - gasket - VITON type (STANDARD execution) - NBR type - shaft/body: - virgin PTFE bushing WORKING TEMPERATURE: Tmax/Tmin : 60°C / -20°C; WORKING AND TEST PARAMETERS: - shell: - at 6 bar - seat: - at hydraulic pressure 4.5 bar - at pneumatic pressure 4.5 bar Allowed leakage in conformity with ISO 5208 grade A. MOUNTING: - flow direction: - unique, marked with arrow - mounting position: - horizontal.

Page 14: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

r0

Rights reserved to modify dimensions or weights depending on the technical EDITION 2003

PROTECTION BOXES FOR UNDERGROUND HYDRANTS

pa

APPLICATION: The protection boxes shall be mounted along with the underground hydrant on PN 10 distribution nwater supplying for fire extinguishing or other needs. DESIGN CHARACTERISTICS: - design and dimensions in conformity with DIN 4055. MATERIALS: - frame, bonnet : - cast iron EN GJL 250 SR EN 1561; GG 25 DIN 1691;

- ductile iron EN GJS 500-7 SR EN 1563; GGG50 DIN1693 -on special request. COATING:

- epoxy primer with zinc coated with tar-epoxy paint or black epoxy enamel; - without coating, on special request.

(dimensions in

DN A B C D E F G H K L N N

Wei≈(k

65 367 336 340 420 262 231 235 315 30100 457 427 430 510 332 302 304 310 10 130 384 46

H

A B

C

D

E

G

B

N

F

LK

CP ge 14 A

evision

etworks for

mm) et ght g) .7 .5

Product approved by Romanian Firemen’s Commitee

Page 15: PORTABLE HYDRANT PN10 1A; 2A; 1B; 2B; 1C; 2C · PDF file- to PEHD pipe with socket and locking sleeve; ... in conformity with STAS 3226; 2. ... Internal and external coating system

AIR RELEASE VALVE WITH SHUT-OFF VALVE PN16

Valves DN 50-200 shequipped with detach

Rights reserved to modify dimensions or weights depending on the technical EDITION 20For confirmation, please use the tec

A-aD--

-M--- -S--- M-- -N--

hnical sheet of agreement. (FTC 18)

RAD-VI-16 page 15 A

0 revision

all be able flange

PPLICATION: automatically performs air release during plants filling in with drinking and industrial water without impurities, pipe iring during plants emptying and releasing of air accumulation into pipes during service. ESIGN AND WORKING CHARACTERISTICS:

connecting flanges PN 16 ISO 7005-2; BS EN 1092-2; DIN 2501; the valve meets EN 1074 requirements; DN 50 65 80 100 125 150 200 Min. airing flow (m3/h) 9.1 14.3 31.8 74.8 159.6 Min. disairing flow (m3/h) 1.1 1.25 1.4 2.7 3.2 the valve has been freeze tested up to -30°C. ATERIALS:

body, bonnet: - ductile iron EN GJS 500-7 SR EN 1563, GGG50 DIN 1693; stem: - min. 11,5% Cr stainless steel - 410 S21 BS 1506 - X20Cr13 DIN 17440; disc: - cast iron EN GJL 250 SR ISO 1561; GG 25 DIN 1691+ rubber;

- carbon steel + rubber; floating balls: - aluminium + rubber. EATS: WORKING TEMPERATURE: Tmax/Tmin: 80°C / -10°C

body - disc: - ductile iron / rubber; body - bonnets: - rubber O-rings; bonnets – balls: - rubber / copper alloy;

- all rubber. ANUAFCTURER TESTS; TEST PRESSURE; LEAKAGE:

hydraulic tests in conformity ISO 5208. test pressure: - shell 1.5xPN

- seat 1.1xPN - seat low pressure 0.3 bar

without leakage in conformity with ISO 5208, grade A. OTE:

The valve shall be mounted with the disc stem in vertical position and handwheel (driving head) in position up. For other liquids, please do not hesitate to ask the manufacturer for confirmation.

(dimensions in mm) Connecting flanges

DN D H H1 Lxl R d1 c d2 nxd3 b Net weight

~(kg) 50 165 100 125 15,2 65 50 260 315 328 x 108 185 121 145 4x19 22 16,6 80 65 273 398 416 x 132

160200 133 160 19 33

100 220 156 180 50 125 78 400 460 526 x 180 250 186 210

8x19 22 54 150 125 506 535 690 x 240

200285 212 240 8 x 23 23 101

200 172 610 665 845 x 310 250 340 267 295 12 x 23* 26 196

03