power harmonic filters for technological excellence

Upload: ravi-shankar

Post on 06-Jul-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    1/18

    1

    POWER HARMONIC FILTERS FOR TECHNOLOGICAL EXCELLENCEBy

    Shaikh Shamser Ali, BE, PMP, P Engr, MBA, BEE Certified Energy Auditor & Manager

    Harmonics are AC voltages and currents with frequencies that are integer multiples of thefundamental frequency. In the earlier years, harmonics were not prevalent in most of the

    industries due to the balanced linear loads using 3 phase induction motors along with

    incandescent lighting, heating etc. but the rapid advancement of the power electronics inindustrial application makes industrial loads non-linear type. These non-linear loads draw

    non-sinusoidal current from the sinusoidal voltage waveform. The distortions thus

     produced in the voltage and current waveform from the sinusoidal waveform are calledharmonic disorders.

    HOW THE HARMONICS ARE GENERATED

    Harmonics are generated due to increasing number of non-linear loads as explained

     bellow:

    When the system voltage is linear but the load is non linear, the current will be distorted

    and become non-sinusoidal. The actual current will become higher than an ammeter or

    any other measuring instrument, at the fundamental frequency, could measure that.Following figure illustrates the difference between the apparent current measured by an

    instrument and the actual current

    VIa

    Ir 

    Ih

     At fundamental frequency ‘f’

     At harmonic frequency ‘fh’

    α Φ

     Here, Ia = Active Component of Current

    Ir = Apparent current measured by an ammeter

    Ih = Actual current due to harmonic distortionsΦ = Displacement angle between the system Voltage and apparent

    current defining the PF of the loadα = Actual Phase displacement due to harmonic distortions

    When the supply system itself contains harmonics and the voltage is already distorted, the

    linear loads will also respond to such voltage harmonics and draw harmonic currents

    against each harmonic present in the system and generate the same order of currentharmonics.

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    2/18

    2

    When the system voltage and load are both non-linear, (A condition which is morecommon) the voltage harmonics will magnify and additional harmonics will be

    generated, corresponding to the non-linearity of the load and hence will further distort an

    already distorted voltage waveform

    Harmonics will thus mean:

    1.  Higher voltage and current than apparent.2.  Adding to line loading and losses.3.  Reducing the actual load PF.

    A load is “non-linear“ when the currentdrawn does not have the same waveform as

    the supply voltage. The harmonic spectrumdepends on the type of load. i.e. switch-

    mode power supplies, motors during start-

    up, transformers during switch-on,

    frequency-controled motors....

    •Non-linear loads cause voltage and currentdistortion.

    •Voltage harmonics depends on grid /source stability, current harmonics and

    network impedance.

    •Current harmonics are mainly loaddependent.

    •Shunt connected electrical equipment aresensitive to voltage harmonic and crest.

    •Series connected devices like cable /transformer are effected by current

    harmonics thus increases distribution losses

    and demagnetic interference.

    •Major harmonic related problems are due

    to current and voltage harmonics.

    V

    Fundamental Frequency Waveform

    Fifth Harmonic Waveform

    Distorted Waveform

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    3/18

    3

    SOURCES OF HARMONICS

    Transformers:

    One common source of harmonics is iron core devices like transformers. The magnetic

    characteristics of iron are almost linear over a certain range of flux density, but quickly

    saturate as the flux density increases. This non-linear magnetic characteristic is described by a hysteresis curve. Because of the non-linear hysteresis curve, the excitation current

    waveform is not sinusoidal. A fourier analysis of the excitation current waveform reveals

    a significant third harmonic component.

    Generators:

    Generators produce some 5th harmonic voltages due to magnetic flux distortions thatoccur near the stator slots and non-sinusoidal flux distribution across the air gap.

    Other producers of harmonics  include Rectifiers, Inverters, Variable Speed Drives,Welders, Arc furnaces, Voltage Controllers, Frequency Converters etc.

    Semiconductor switching devices  produce significant harmonic voltages as they

    abruptly chop voltage waveforms during their transition between conducting and cut-offstates.

    Inverter circuits are notorious for producing harmonics, and are in widespread use todayin every spectrum of the industry. A variable speed drive is one application that makesuse of inverter circuits, often using pulse width modulation (PWM) synthesis to produce

    the AC output voltage. Various synthesis methods produce different harmonic spectrum.

    Regardless of the method used to produce an AC output voltage from a DC input voltage,harmonics will be present on both sides of the inverter and must be mitigated.

    IMPACT OF HARMONICS ON POWER FACTOR

    Power Factor (PF) is a measure of the efficiency of utilization of a power distribution

    system. The closer the PF to unity, the more will be the efficiency to do the useful work.

    With linear loads, the PF depends on the phase relationship between the current andvoltage sine waves. When these two waves are in phase, the PF is unity and no system

    capacity is wasted.

    Linear loads, such as resistance heaters and incandescent lights are 100% efficient inconverting real power to heat and therefore have a PF of unity. Induction motors require

    real power and reactive power, which is measured in KVAR. The reactive current that

    flows in the system creates a magnetic field that enables the motor to operate, but doesnot contribute to the work done by the motor. Reactive current also causes the current

    wave to lag behind the voltage wave. This process is called displacement.

    The apparent power for a motor can be calculated using the equation,

    KVA=√ (KW2+KVAR 2)

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    4/18

    4

    Since the apparent power for a motor is larger than the active power, the PF is less than

    unity. The PF for a system powering only linear loads is called the displacement power

    factor. Unless the loads are pure resistance, the PF will be less than unity.

    Today however, many electrical systems also have harmonic currents on their lines.

    Harmonics are caused by non-linear or pulsed loads and their current causes the apparent

     power to exceed the active power by a substantial amount.

    The apparent power for a non-linear load can be calculated using the equation,

    KVA =√ (P2+Q2+DVA2)

    The presence of harmonics increases the apparent power that must be delivered to do a

    certain amount of work, therefore lowering the PF. In these situations, the form of powerfactor present is called distortion power factor. In a System consisting of both linear and

    non-linear loads the true power factor (TPF) is a sum of cosine of both displacement and

    distortion angles.

    If harmonic currents are introduced into a system, the true PF will always be lower than

    the displacement PF. For example, the displacement PF for a computer is close to unity

    (usually about 0.95) whereas the true PF, which includes harmonics, is around 0.7. For both linear and non-linear loads, the result of extra current that does NO  real work

    (Whether it is reactive current or harmonic current) is a reduced capability for the system

    to support useful loads.

    For linear loads, measurements can be carried out to determine displacement power

    factor with a number of instruments. These instruments can measure Kilowatts (KW) and

    Kilo-Volt-Amperes (KVA) and some can directly read Power Factor (PF). Whenharmonics are present, meters with true RMS capability must be used to accurately

    account for the total current, which includes the current at the Fundamental 50/60 Hz and

    the harmonic currents to determine the true PF. Also, it is advisable to read the true RMSvalue of the voltage, since harmonic currents may cause voltage waveform distortion in

    some systems.

    IMPACT OF HARMONICS ON CAPACITORS

    Harmonic component affects the performance of a capacitor unit significantly due to the

    diminishing reactance at higher frequencies, which adds to its loading substantially and

    can be analysed as follows:

    Xc = 1/(2πfc) i.e Xc α 1/f  

    This means that the capacitor will offer a low reactance to the higher harmonics and will

    tend to magnify the harmonic effect due to higher harmonic currents. In fact, harmonic

    currents have a greater heating effect compared to fundamental current. The effectivecurrent caused by all the harmonics present in the system can be expressed as:

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    5/18

    5

    Ich = √ (Ic  + 9 Ich3 + 25  Ich5 + 49 I ch7 + …………..n I chn)

    Where, Ic = Rated current of the Capacitor

    Ich3, Ich5,  Ich7 .. etc. = amplitude of the harmonic current components atdifferent Harmonic orders

    To compensate for the harmonic effects, capacitor unit is designed for a minimum of 70 -100 % continuous overload capacity. Summarizing the above, the harmonic quantities

    when present in a system on which are connected a few capacitor banks affect the

    capacitors as follows:

    1.  Over current resulting in higher losses.

    2.  Over current resulting to an over voltage across the capacitor units, which wouldinflict greater dielectric stress on capacitor elements.

    3.  Since the harmonic disorders occur at higher frequencies than the fundamental,they cause higher dielectric losses

    Harmonic output of a capacitor unit:

    KVAR = √3 * V * IC  (V in Volts and Ic in Amperes)

    1000

    and IC = V

    XC

    Therefore, KVAR = √3 * V2

    1000 * XC 

    (or) KVAR = √3 * V2 *2π * f * c 

    1000

    Generalizing KVAR h is proportional to Vh .at fh

    (or) KVAR h is proportional to V1 + 3. Vh3 + 5 Vh5 + 7 Vh7 + …n.Vhn 

    The rating of the capacitor unit will thus vary in a square proportion of the effective

    harmonic voltage and in direct proportion to the harmonic frequency. This rise in the

    KVAR, however will not contribute to the improvement of system PF, but only to the

    overloading of the capacitors themselves.

    2

    2 222 2

    2 2 2 2 2

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    6/18

    6

    IMPACT OF HARMONICS ON VARYING LOADS

    Wherever variation in loading pattern is observed, Automatic Power Factor Correction

    systems are installed for maintenance of healthy power factor. However, one cannotindiscriminately add power factor correction capacitors to a system without

    understanding how their presence will affect the system, especially in the presence of

    harmonics.

    RESONANCE:

    The operation of non-linear loads in a power distribution system

    creates harmonic currents that flow throughout the power system.

    The inductive reactance of the power system increases and thecapacitive reactance decreases as the frequency increases, as

    shown in this fig.

    PARALLEL RESONANCE:

    At a given harmonic frequency in any system where a capacitor exists, there will be acrossover point where the network impedance and capacitive reactances are equal. This

    crossover point, called the parallel resonant point, is where the power system has

    coincidental similarity of system impedances. Every system with a capacitor has a parallel resonant point. Parallel resonance causes problems only if a source of harmonicsexists at the frequency where the impedances match. This is typically called harmonic

    resonance. Harmonic resonance results in very high harmonic currents and voltages at the

    resonant frequency.

    Capacitance of 

    Capacitor Bank

    Network

    Inductance

    Harmonic

    source

    Capacitor Bank

    Harmonic generating load

     

    PARALLEL RESONANT CIRCUIT AND ITS EQUIVALENT

    HV Bus

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    7/18

    7

    At resonant frequency the resultant impedance of a parallel resonant circuit increases to a

    very high value. This leads to excitation of parallel resonance circuit between the power

    factor correction capacitor and the network inductance resulting in a high voltage across

    the inductors and very high circulating current inside the loop.

    SERIES RESONANCE:

    The increased use of non-linear loads distorts the current waveform thereby affecting the

    voltage profile. In case of voltage distortion the series resonant circuit formed by the

    capacitance of the capacitor and the short circuit inductance of the transformer drawshigh harmonic current through the capacitor. Series resonance can create high voltage

    distortion in the LV side of the transformer.

    400 V

    Capacitance of the

    Capacitor BankHarmonic source

    Transformer's

    Inductance's

    Capacitor BankHarmonic generating load

     

    SERIES RESONANT CIRCUIT AND ITS EQUIVALENT

    For example, consider a 1500 KVA transformer and a capacitor bank rating of 250

    KVAR. Substitute, these values in the equation given below will yield the harmonic orderat which this combination will form a parallel resonant circuit

    A 1500 KVA transformer with 5% impedance yields about 30 MVAsc  (1.5 MVA ÷

    0.05). So the 250KVAR capacitor bank will be resonant with that source impedance atthe 11th harmonic. If any amplitude of 11th harmonic current flows on the power system

    at that bus, the effect could be catastrophic.

    Due to the combination of inductance and capacitance in series the net impedance of thecircuit reduces to a bare minimum level at the resonant frequency and this impedance is

     basically resistive in nature at resonant frequency, since at resonant frequency, the

    capacitive reactance and the inductive reactance are equal. This low impedance to theinput power at resonant frequency will result in multiple increases in current.

    HV Bus HV Bus

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    8/18

    8

    EFFECT OF HARMONICS ON POWER SYSTEM

    DISTRIBUTION SIDE:

    Tripping of circuit breakers and fuses

    Due to resonance effects, the current levels may rise to multifold levels, which results intripping of the breakers and melting fuses. This situation results into serious problems in

    industries, which rely on the quality of power for the continuous operation of their

    sensitive processes.

    Impact of Harmonics on Transformers

    Transformers are designed to deliver power at network frequency (50/60Hz). The ironlosses are composed of the eddy current loss (which increase with the square of the

    frequency) and hysterics losses (which increase linearly with the frequency). Eddy

    current concentrations are higher at the ends of the transformer windings due to thecrowding effect of the leakage magnetic fields at the coil extremities. Very often, the

    damage to the coils in a transformer is not known until a failure occurs. With increasing

    frequencies the losses also increase, causing an additional heating of the transformer.

    Impact of Harmonics on Motors

    Hysteresis and eddy current losses are part of iron losses that are produced in the core dueto the alternating magnetic field. Hysteresis losses are proportional to frequency, andeddy current losses vary as the square of the frequency. Therefore, higher frequency

    voltage components produce additional losses in the core of AC motors, which in turn,

    increase the operating temperature of the core and the windings surrounding the core.Application of non-sinusoidal voltages to motors results in harmonic current circulation

    in the windings of motors.

    Stray motor losses, which include winding eddy current losses, high frequency rotor and

    stator surface losses, and tooth pulsation losses, also increase due to harmonic voltages

    and currents

    The interaction between the positive and negative sequence magnetic fields and currents

     produces torsional oscillations of the motor shaft. These oscillations result in shaft

    vibrations. If the frequency of oscillations coincides with the natural mechanical

    frequency of the shaft, the vibrations are amplified and severe damage to the motor

    shaft may occur.

    Overloading of the capacitors

    The rated current through capacitor is calculated as follows:

    Ic = V = V.2.CXc 

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    9/18

    9

    However due to harmonics, the capacitors are overloaded according to the following

    equation producing excessive heat.

    Ich = √ ( Ic + 9 Ich3 + 25  Ich5 + 49 I ch7 + …………..n I chn)

    As the capacitive reactance decreases with the frequencies, even smaller amplitudes of

    the harmonic voltages result into higher currents, which are detrimental to the capacitors.

    Losses in distribution equipment

    Harmonics in addition to the fundamental current cause additional losses in the cables,

    fuses and also the bus bars.

    Excessive currents in the neutral conductor

    Under balanced load conditions without harmonics, the phase currents cancel each otherin neutral, and resultant neutral current is zero. However, in a 4-wire system with single-

     phase non-linear loads, odd numbered multiples of the third harmonics (3rd

    , 9th

    , 15th

    ) do

    not cancel, rather add together in the neutral conductor.

    In systems with substantial amount of the non-linear single-phase loads, the neutral

    currents may rise to a dangerously high level. There is a possibility of excessive heating

    of the neutral conductor since there are no circuit breakers in the neutral conductors likein the phase conductors.

    Malfunctioning of the Electronic Controls and Computers

    Electronic controls and computers relay on power quality for their reliable operation.

    Harmonics result into distorted waveforms, neutral currents and over voltages, whichaffect the performance of these gadgets.

    Measurement errors in the metering systems

    The accuracy of metering systems is affected by the presence of harmonics. Watt-hour

    meters accurately register the direction of power flow at harmonic frequencies, but they

    have amplitude errors, which increase with frequency.

    GENERATION SIDE:

    Generally power electronic devices cause line current to be non-sinusoidal. Thisharmonics increases the losses in the stator conductors and it affects the field and damper

    currents, thus distorting the voltage profile. The voltage profile distortion depends on the

    current harmonics and the alternator characteristics. The following points needs to be

    accounted:

    2 2 2 2 2

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    10/18

    10

    Increased summated net current flows through the alternator winding.

    Reverse harmonic current flow in the windings: Harmonic current flows back into the

    alternator, thereby distorting the voltage waveform (voltage harmonics). Basicallyvoltage harmonics affects all the loads either linear or non-linear and the voltage

    harmonics also induces current harmonics even for linear loads.

    Increased winding resistance for harmonic frequencies: Harmonic current produces

    large heating than the fundamental current due to the increase in resistance at different

    frequencies. 5th

      Harmonic current produces approximately 5 times more heat andsimilarly higher order of harmonics produces higher heating. This leads to higher

    temperature in the winding.

    Rotor Jerking: Due to the reverse flow of harmonics, there is blocking movement in thealternator speed i.e., jerking of the rotor takes place due to harmonic current flow.

    Rotor Retardation: Due to inherent distortion in the voltage waveform, induced EMF

    rotates at different frequencies. Depending on the phase angle of the 5th

     Harmonics, this

    may have retardation or acceleration effect on the rotor.

    REMIDIES TO OVERCOME POWER HARMONICS

    Elimination of voltage and current harmonics by using harmonic filters is an easy option

    to any harmonics problem.

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    11/18

    11

    CLASSIFICATION OF HARMONIC FILTERS

    HARMONIC FILTERS

    PASSIVE

    FILTERS

     ACTIVE FILTERS

    DE-TUNEDFILTERS

    TUNEDFILTERS

    Suppression Filters Absorption Filters

    Blocking Filters

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    12/18

    12

    TYPES OF PASSIVE FILTER SYSTEMS

    Passive harmonic filters are reactor-based systems basically used for the suppression of

    harmonics and maintenance of healthy power factor. These filters are broadly classifiedas:

    1.  Detuned Filters2.  Tuned Filters

    The classification of de-tuned filters and tuned filters basically depends on the tuningfrequency of the filter reactor & capacitor circuit and the selection of harmonic filter type

    depends on the level & order of harmonics present in the distribution network.

    De-Tuned Harmonic Filters:

    The de-tuned filters are effective in circuits where variation of Q and different order of

    harmonics level are anticipated. Such filters are shunt connected with matching tuningfrequencies below the predominant harmonic frequency, thus having most reliable life,

     but also achieving the required harmonic reduction. The selection of the tuning

    frequency depends on the system impedance behavior under varying loads or constant

    loads.

    The system impedance needs a detailed harmonic behavioral study to arrive at the correct

    tuning frequency. However, depending on the predominant level of harmonics present,following tuning frequencies are generally selected:

    Blocking Filter  – Wherever the level of 3rd harmonics is predominant in the distributionnetwork, it is necessary to select Blocking Filter systems of tuning frequency at 154.8 Hz.These filters are designed to block the effect of 3

    rd harmonics affecting the life of shunt

    connected capacitors and reduces the risk of harmonic resonance and amplification.

    Suppression Filter  –  Wherever the level of 5th harmonics is predominant, it is necessaryto select Suppression Filter systems of tuning frequency at 279 Hz. These filters are also

    designed to block the effect of 5th

      harmonics affecting the life of the shunt connected

    capacitors & suppress the line current harmonics. In general following are the benefits ofBlocking & Suppression Filters:

    1.  Avoids premature failure of capacitors due to the basic blocking nature of thefilters

    2.  Harmonic amplification due to impedance matching is avoided3.  Possibility of harmonic resonance is avoided

    Tuned Harmonic Filters:

    The tuned filters are basically designed to match to the predominant harmonic frequency, but slightly tuned away from the harmonic frequency, since the supply frequency

    variations needs to be accounted. Even the tuned filters act like de-tuned filters when the

    frequency is at the normal level, but they operate as tuned filters only at the minimum

    defined supply frequency. 

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    13/18

    13

    These types of filters are tuned above the detuned filter frequencies, thus having the

    impact of blocking filter and harmonic absorption capability. In other words, these filters

    not only improve the power factor, but also absorb the harmonics. Here, the capacitors

    are fully protected due to the blocking nature of the filters, thus ensuring a long life forthe filter circuit. Such filters are normally used for both harmonic suppression and power

    factor improvement.

    ACTIVE FILTER TECHNOLOGY

    Active filters are IGBT based power electronic devicesinstalled in parallel to the harmonic generators. It

    analyses the harmonic current produced by the non-

    linear loads and supplies a 180  out-of-phasecompensating current, either over the entire spectrum

    from the 2nd

     to the 25th

     harmonic or a specially selectedharmonic. This technique is called as active injection

    mode (AIM). This is not done by absorbing currents, but

     by injecting additional currents whenever required.

    A current transformer first measures the current being drawn momentarily by the load.

    The control unit in the harmonic filters then analyses this current for amplitude andharmonics. It consequently feeds a current into the supply system whose amplitude and

    individual harmonic numbers is exactly equal to the current drawn by the load but which

    is, however, 180 out of phase with it. The harmonic currents cancel each other out and

    the supply network only has to supply the fundamental frequency and is not contaminatedwith harmonics at the point of connection, provided that the system has been

    appropriately dimensioned.

    The combination of harmonic filter and harmonic load appears to the network as an

    overall linear load drawing a sinusoidal current. Installation is quite simple. A three-

     phase feeder with or without a neutral conductor needs to be available. The currenttransformer is then installed in the line to the non-linear load. One great advantage of the

    active filter compared to conventional techniques is its flexibility in adapting thecorrective power. Depending on the requirements, the filter can supply more or less

    corrective current.

    Even on overload, the filter does not switch off, but assumes a current-limiting mode i.e.,

    the filter supplies its maximum current and in doing so compensates for a large

     proportion of the harmonics. Interaction with other system components, such as UPSunits is therefore reduced to a minimum that is not critical. There is no problem to extend

    the system or install a combination of several filters. If operating or network conditionschange, the filter automatically adapts to the new conditions within the scope of itsnominal rating.

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    14/18

    14

    SELECTION OF HARMONIC FILTERS:

    Harmonics filter systems should be best based on harmonic study. Harmonic filter system

    design depends on the filter reactive power output, tuning frequency and impedance ofthe network at the point of connection. The followings should be considered while

    selecting the appropriate harmonic filter:

    Considering the amplitude of harmonic current measured, sizing of the filter circuit is

    arrived based on the distributed network harmonics consisting of different orders.

    Appropriate tuning frequency is selected based on the measurement and network

    analysis.

    Based on the tuning frequency of passive filter, the current harmonics of that particulartuning frequency will be absorbed by the filter. Such filters can be tuned for a particular

    order (Frequency) of harmonics.

    HARMONIC FILTER SELECTION CHART –  (Examples)

    Harmonic levelless than

    IEEE519

    Harmonic level above IEEE 519 / IEC 1000-2-4.

    / IEC 1000-2-4.THD >10% &

    20% &major odd

    Harmonics

    THD >20%& major 3

    rd 

    Harmonics

    Steady

    Load

    Power

    Capacitors upto 85% of the

     No-Load

    MagentisingKVAR

    Fixed De-TunedHarmonic

    Suppression Filter

    & P.F Correction

    Fixed TunedHarmonic Filter& P.F Correction

    Fixed

    TriplenHarmonicFilter & P.F

    Correction

    VaryingLoads

    APFC System

    up to 100% ofthe Reactive

    Power.

    Variable De-Tuned

    HarmonicSuppression Filter

    & APFC

    Variable Tuned

    Harmonic Filter

    & APFC

    VariableTriplen

    Harmonic

    Filters &

    APFC

    Dynamical

    ly VaryingLoads

    ----- Active HarmonicFilter Active HarmonicFilter

    Active

    HarmonicFilter

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    15/18

    15

    BENEFITS OF HARMONIC FILTERS

    Harmonic filters offers superior harmonic filtration along with following incomparable

     benefits:

    Avoidance of frequent capacitor failures Elimination of Resonance

    Safeguards Neutral Conductor Improves Voltage StabilityReduces System losses Shunts Harmonic Currents

    Reduces Neutral Current Increases System Capacity

    Reduces local Neutral to Ground Voltage Reduces Transformer Overloading

    PERFORMANCE OF PASSIVE HARMONIC FILTERS

    Improvement in Voltage Profile  - With the installation of harmonic filters, the RMSvalue of voltage waveform is improved, thereby avoiding motor winding burn-outs,

    repetitive fuse failures etc due to low voltage and improves voltage regulation.

    -400

    -300

    -200

    -100

    0

    100

    200

    300

    400

    0 0.005 0.01 0.015 0.02 0.025 0.03

    Time in secs

       C  u  r  r  e  n  t   i  n  a  m  p  s ,

       V  o   l  t  a  g  e   i  n  v  o   l  t  s

    VoltageCurrent

     

    -400

    -300

    -200

    -100

    0

    100

    200

    300

    400

    0 0.005 0.01 0.015 0.02 0.025 0.03

    Time in secs

       C

      u  r  r  e  n  t   i  n  a  m  p  s ,

       V  o   l  t  a  g  e   i  n  v  o   l  t  s

    VoltageCurrent

     

    VOLTAGE & CURRENT WAVEFORM

    BEFORE FILTERATION

    VOLTAGE & CURRENT WAVEFORM

    AFTER FILTERATION

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    16/18

    16

    Improvement in current profile- With the installation of harmonic filter the net currentis brought down due to the elimination of harmonic current thereby reducing losses in the

    electrical distribution system and leads to enhance life of transformers, cables, switchgear

    etc.

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    17/18

    17

    PERFORMANCE OF ACTIVE HARMONICS FILTER

  • 8/18/2019 Power Harmonic Filters for Technological Excellence

    18/18

    18

    CONCLUSION

    Power harmonics is an electrical phenomenon. The negative effects due to power

    harmonics is not necessarily be only electrical but can also be mechanical as explained on“Impact of harmonics” earlier in this article. Awareness and acceptance of having better power quality is increasing and the industries are gradually realizing the positive impact

    of having electrical power without harmonics.

    Primary aim of the end user to install a harmonics filter could be the elimination of

    harmonics but an economic analysis will prove that the expenditure to install theharmonic filter can generate an ROI of more than 30%, should it be looked at as an

    investment. Implementation of harmonic filters as Demand Side Management (DSM)

     project operating on “Performance Contracting” basis will not only benefit the end userand the harmonic filters supplier but will also benefit the utility and funding organization.