pq-direction of harmonics

Upload: consultrail

Post on 05-Apr-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 PQ-Direction of Harmonics

    1/6

    214 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 1, JANUARY 2003

    An Investigation on the Validity of Power-DirectionMethod for Harmonic Source Determination

    Wilsun Xu, Senior Member, IEEE, Xian Liu, Member, IEEE, and Yilu Liu, Member, IEEE

    AbstractThe power-direction method has been used widelyto identify the locations of harmonic sources in a power system.A number of utility-customer disputes over who is responsible forharmonic distortions have been settled with the help of the method.A closer examination of the method, however, reveals that it is un-able to fulfill the task of harmonic source detection. Case studiescan easily show that the method yields incorrect results. In thispaper, problems associated with the method are investigated usingcase studies and mathematical analysis. The results show that thepower direction method is theoretically incorrect and should notbe used to determine harmonic source locations. The main cause oftheproblemis that thedirection of activepower flow is a function ofthe phase-angle difference between the two sources. The directionof reactive power flow, on the other hand, has a better correlationwith the source magnitudes.

    Index TermsHarmonics, harmonic source detection, harmonicsources.

    I. INTRODUCTION

    WHENEVER significant harmonic voltage or current dis-

    tortions are observed in a power system, it is always

    useful to find the sources of the distortions. Correct identifica-

    tion of harmonic source locations is essential for designing ef-

    fective harmonic mitigation means and for determining the re-

    sponsibility of the parties involved. The most common situation

    that needs harmonic source detection is to resolve the disputesover who is responsible for harmonic distortions at the point of

    common coupling between a utility and a customer or between

    two customers.

    The most common method for harmonic source detection is

    the power direction method. This method checks the directionofharmonic powerflow. The side that generates harmonic power is

    considered to contain the dominant harmonic source or to have

    a larger contribution to the harmonic distortions observed at the

    measurement point. This method is apparently sound and has

    been used in industry as a tool for many years [1], [2]. A number

    of power quality monitors have included it as a key product fea-

    ture. However, we have found concrete proofs that the method is

    not suitable forharmonic sourcedetection. The method has beenfound theoretically incorrect. In this paper, problems associated

    with the method are investigated using case studies and mathe-

    Manuscript received April 25, 2001; revised March 2, 2002. This work wassupported by a Grant from the Natural Sciences and Engineering ResearchCouncil of Canada (NSERC).

    W. Xu and X. Liu are with the Department of Electrical and Computer En-gineering, University of Alberta, Edmonton, AB T6G 2V4, Canada (e-mail:[email protected]).

    Y. Liu is with the Department of Ele ctrical Engineering, Virginia PolytechnicInstitute and State University, Bla cksburg, VA 24061-0111 USA.

    Digital Object Identifier 10.1109/TPWRD.2002.803842

    Fig. 1. Problem of harmonic source detection.

    matical analysis. Causes of the problem are identified. In addi-

    tion, this paper proposes superposition-based indices to quantify

    the contributions of harmonic sources.

    II. POWER DIRECTION METHOD

    The harmonic source detection problem can be explained

    with the help of Fig. 1. In this figure, the disturbance sources

    are the customer harmonic source and the utility harmonic

    source . and are the harmonic impedances of the re-

    spective parties. The circuit is applicable to different harmonic

    frequencies (the values will be different). The task of harmonic

    source detection is to determine which side contributes moreto the harmonic distortion at the PCC, subject to the constraint

    that measurements can only be taken at the PCC.

    To determine which side causes more harmonic distortion at

    the harmonic order , the power direction method first measures

    voltage and current at the PCC and then calculates the following

    harmonic power index:

    (1)

    where and are the harmonic voltage andcurrent atthe

    PCC for a particular harmonic number. Since this paper deals

    with one harmonic at a time, the subscript that represents har-

    monic number will be omitted throughout the paper to avoid

    excessive subscripts. The direction of is defined as from

    side to the side. Conclusion of the power direction method is

    the following.

    If , the side causes more th harmonic distortion.

    If , the side causes more th harmonic distortion.

    III. QUANTITATIVE HARMONIC CONTRIBUTION INDICES

    While the power direction method could be intuitively sound,

    the term causing more harmonic distortions is vaguely de-

    0885-8977/03$17.00 2003 IEEE

  • 7/31/2019 PQ-Direction of Harmonics

    2/6

    XU et al.: VALIDITY OF POWER DIRECTION METHOD FOR HARMONIC SOURCE DETERMINATION 215

    Fig. 2. Determination of harmonic source contributions for th harmonic.

    Fig. 3. Decomposition of of the th harmonic into two components.

    fined. There is a need to be more precise on this term so that the

    effectiveness of any harmonic source detection methods can beassessed. To this end, the principle of superposition is applied to

    the th system shown in Fig. 1 [3]. According to the principle,

    the contribution of each source to the th harmonic current

    can be determined according to Fig. 2 and the following equa-

    tions:

    (2a)

    (2b)

    (2c)

    where and are the contributions of respective

    sources to the PCC current. Again, all quantities in Fig. 2 and (2)

    refer to a particular harmonic, the th harmonic. The equations

    shown before are phasor equations. There are still some ambi-

    guities to define harmonic contributions since (2c) is a phasor

    summation. A more precise method is to decompose into

    two scalar components as shown in Fig. 3 and (3) [4]

    (3)

    where is the projection of onto , and is the

    projection of onto . Thus, is the algebraic sum-mation of twoscalar components, one dueto customer harmonic

    source and the other due to utility source. For example, if

    is equal to 3 A and is equal to 7 A, the current is 10 A.

    One can say that the customers contribution is 70%.

    Both and are scalars and can have opposite signs. If

    they have the same sign, the customer and utility harmonics add

    up toform . Ifthey haveopposite signs, the negativeone has

    the effect of reducing the harmonic flow at PCC. We believe that

    the and indices accurately characterize the contributions

    of respective harmonic sources to the PCC current. They are

    used in this paper to refute the validity of the power direction

    method.

    A similar index can be defined from the voltage distortion

    perspective. The contribution to voltage distortions at PCC by

    each harmonic source can be determined as follows

    (4a)

    (4b)

    (4c)

    Again, the phasors and need to be projected

    onto the axis to provide scalar harmonic contribution in-

    dices. The process is similar to what has been applied to the

    current indices.

    IV. SAMPLE TEST RESULTS

    The validity of the power direction method can be tested with

    the following simple experiment:

    1) Select a set of practical , , and data that cor-

    respond to any particular harmonic number. In this paper, wechose the following case:

    p.u. p.u.

    angle p.u. p.u.

    Let the phase angle of vary from 0 to 360 . Phase angle of

    is set to 0 as a reference.

    2) Check the correlation between the power direction index

    and the superposition indices. If the power direction method was

    correct, the following condition should always hold:

    If then (5)

    Fig. 4 shows the results. The figure depicts the variation of

    normalized harmonic power , current , and its components

    and withrespectto the phase angle of . The normaliza-

    tion divides thecurrentsand powerby their respective maximum

    values sothat theyreside between the range of 1 to 1 and can

    be easily plotted in one chart for comparison. It can be clearly

    seen from the figure that the condition shown before (5) does

    not always hold true. For example, is always greater than

    and the side should be considered as the main harmonic

    current contributor. The harmonic power, on the other hand, can

    flow in either direction. When the angle is greater than 190 ,

    the power direction contradicts to the principle of superposition.

    There is an approximate 50% chance that the contradiction canoccur. Fig. 5 is a practical case that can create a situation where

    the phase angle between and is far apart. Since there is

    no guarantee that the phase angle between and resides in a

    certain range, one can conclude that the power direction method

    is unsuitable for harmonic source detection.

    Test results are also obtained for the voltage distortion index

    defined in (4). The results are shown in Fig. 6. It is noted that,

    according to the voltage superposition index, the side con-

    tributes more to the PCC voltage distortion. This conclusion ap-

    plies to all customer current angles. The power direction index,

    however, changes sign when the current angle is between 190

    and 340 . The contradiction between the two indices is obvious.

  • 7/31/2019 PQ-Direction of Harmonics

    3/6

    216 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 1, JANUARY 2003

    Fig. 4. Correlation between the power direction and current superpositionindices.

    Fig. 5. A practical case that can cause large phase-angle difference betweenand .

    Fig. 6. Correlation between the power direction and voltage superpositionindices.

    V. MATHEMATICAL ANALYSIS

    Figs. 4 and 6 can be produced easily for many test cases. The

    evidence against the power direction method is overwhelming.

    This finding is also supported by the results shown in [5] and[6]. In this section, we try to demonstrate mathematically that

    the contradiction does exist. The sources of the contradiction are

    also identified and explained.

    A. DC Circuit Case

    The first case is a general dc circuit shown in Figs. 7 and 8. Al-

    though the actual harmonic source detection problem involves

    ac circuits, the dc circuit case can reveal key characteristics of

    the power direction method. A dc circuit is much simpler to an-

    alyze since there is no phasor involved. The dc case can also be

    considered a special ac case where the system has resistances

    only and the harmonic sources have the same phase angle.

    Fig. 7. DC circuit to demonstrate the power direction method ( andoppose each other).

    Fig. 8. DC circuit to demonstrate the power direction method ( and addup).

    The PCC voltage and current of the circuit can be determined

    as follows:

    (6a)

    (6b)

    Since the voltage is always positive, the condition for the

    power ( ) to flow from side to side is or

    (7)

    On the other hand, the superposition current index shows that

    if

    (8)

    or

    (9)

    holds, the sidecontributes more current than the side. Equa-

    tions (7) and (9) are therefore consistent, which implies that the

    power direction method works well in this case.

    If the customer current changes polarity as shown in Fig. 8,

    however, the current becomes positive all of the time. The

    condition for the power to flow from side to side is ,

    or

    (10)

    [based on Equation (6b)]. The condition for is still

    the same as that shown in (9). This equation does not alwaysagree with (10), depending on the relative size of and .

    Therefore, a mathematical proof has been found to show thatthere is a contradiction between the power direction method and

    the superposition method. Another conclusion drawn from the

    analysis is that the polarity (or phase) difference between the

    two sources has more influence on the direction of power flow

    than that caused by their magnitude difference.

    B. AC Circuit With Reactance Only

    The second case is an ac circuit shown in Fig. 1. To sim-

    plify the analysis, the impedances are assumed to contain imagi-

    nary parts only. The circuit corresponds to a particular harmonic

  • 7/31/2019 PQ-Direction of Harmonics

    4/6

    XU et al.: VALIDITY OF POWER DIRECTION METHOD FOR HARMONIC SOURCE DETERMINATION 217

    frequency. Following the classic power-angle equation for two

    source ac circuits, the power flowing from side to side canbe determined as:

    (11)

    where and are the open circuit th

    harmonic voltages of the and sides, respectively. is thephase-angle difference between utility and customer side th

    harmonic current sources. The significance of this equation is

    the following: the direction of power is controlled by , the

    phase-angle difference between two harmonic sources.

    For the superposition-based current index, we want to show

    at first that condition implies .

    According to Fig. 3 and the well known triangular formula, the

    superposition currents and can be determined as

    follows

    (12a)

    (12b)

    Therefore

    (13a)

    (13b)

    Subtracting the above two equations yields

    (14)

    This equation shows that if is satisfied,will be true. Note that this is a general conclusion. It

    does not rely on the assumption of the impedances having imag-

    inary parts only. In the following step, the relationship between

    the superposition currents and the source currents is determined.

    The principle of superposition shows

    (15a)

    (15b)

    The condition for or to hold

    becomes

    (16)

    The condition just mentioned is not related to phase-angle ,

    while (11) is. The powerdirection index is therefore inconsistent

    with the current superposition index. Hence, the invalidity of the

    power direction index has been demonstrated analytically. The

    same process can be used to show the inconsistency between the

    power index and voltage-based superposition index.

    It is common knowledge for power engineers that the phase

    angles of bus voltages mainly affect the flow of active power

    while the magnitudes of bus voltages mainly affect the flow of

    reactive power. One would, therefore, wonder if the direction of

    reactive power could indicate the relative size (i.e., magnitudes)

    of two harmonic sources. This question can be analyzed by ex-

    amining the reactive power flowing out of source

    (17)

    where is the phase-angle difference between the two sources.

    Since is always less than 1 and if , condition

    automatically implies that the direction of reactive

    power is from side to the side. In other words, the direction

    of reactive power can be used as an (necessary but not sufficient)

    indicator to determine which side has a larger voltage source.

    The reason that the indicator is not a sufficient one is because

    the reactive power can still flow from side to the side if

    is greater than but is less than . The phase-angle

    , therefore, plays an important role in this case as well. Despite

    this restriction, the direction of reactive power is still a more

    reliable indicator than the direction of active power in this case.Another important prerequisite for using the direction of reac-

    tive power as a harmonic source locator is . While

    this condition is generally true at the fundamental frequency, it

    may not be true at the harmonic frequencies. This is the main

    problem associated with the reactive power direction method.

    C. AC Circuit With Resistances Only

    It is interesting and important to examine the hypothetical

    case where the system and customer impedances are entirely re-

    sistive, namely, and . In this case, the branch

    resistance consumes power. The amount and direction of the ac-

    tive power flowing on the branch are dependent on the location

    of measurement. To simplify the problem, we first consider thepower generated or absorbed by harmonic source , as shown

    in Fig. 9. For this case, the power flowing out of source is

    (18)

    where is the phase-angle difference between the two sources.

    It can be seen that (18) is very similar to (17). It means that the

    direction of active power can be used as an (necessary but not

    sufficient) indicator to determine which side has a larger voltage

    source for the resistive circuit. The reactive power flow for this

    case takes the following form:

    (19)

    This equation is very similar to (11). Comparing (11) to (19),

    and (17) to (18), one can conclude that the characteristics of the

    circuit impedance determine which power, or , has

    more bearing on the source magnitudes instead of source phase

    angles. If the circuit impedance is dominated by reactance, the

    direction of reactive power is a better indicator on the relative

    magnitude of the two sources. If the impedance is dominated

    by resistance, however, the direction of active power is a better

    indicator.

  • 7/31/2019 PQ-Direction of Harmonics

    5/6

    218 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 18, NO. 1, JANUARY 2003

    Fig. 9. AC circuit with resistive elements.

    The second analysis deals with a general case where the me-

    tering point is the PCC. As shown in Fig. 9, the PCC voltage

    and current can be determined as follows

    (20a)

    (20b)

    The active power flowing from side to side can be de-

    termined as

    (21)

    The equation just shown reveals that the resistances and

    could havea large impacton the signof , orthedirection

    of active power. We can quantify the impact by considering the

    special case of . For this case, Equation (21) can be

    simplified as

    (22)

    The equation just shown demonstrates clearly that the direc-

    tion of active power is affected by the relative size of and

    or the location of the meter. If , the power flows

    from side to side, even if the two sources have the same

    magnitude. This analysis has revealed another impact factor, the

    point of measurement, which can influence the reliability of the

    power direction method.

    VI. CONCLUSION

    The concern for power system harmonics is mainly on thedistortion of sinusoidal voltage and current waveforms. Even

    with little harmonic power, a distorted waveform can trigger the

    malfunction of electronic circuits. It is, therefore, important to

    define the contribution of each harmonic source based on the

    current and/or voltage parameters. This paper proposes superpo-

    sition-based current and voltage indices to quantify the contri-

    butions of harmonic sources. Using these indices, the validity of

    the power direction method for harmonic source determination

    is investigated. Both case studies and mathematicaly analyses

    have shown that the power direction method is not suitable for

    harmonic source detection. Main findings of this work are sum-

    marized as follows.

    1) The direction of active power is mainly affected by the

    relative phase angle between the two harmonic sources. It has

    little bearing on the relative magnitude of the sources. Note that

    it is the source magnitudes instead of phase angles that are of

    main interest for the harmonic source detection problem.

    2) The direction of reactive power, on the other hand, has

    a closer relationship to the source magnitudes. If the circuit

    impedance is purely reactive, the direction of reactive power isactually a necessary (but not sufficient) condition indicating one

    source has a larger magnitude than the other.

    3) The conclusions shown above are applicable to circuits

    dominated by reactances. If a circuit consists of mainly resistive

    components, the conclusions mentioned before are reversed.

    Namely, the direction of active power is mainly affected by

    the source magnitudes and that of the reactive power by the

    phase angles. The implication of this conclusion is that the

    characteristics of the circuit impedance ( ratio) will affect

    the reliability of the active or reactive power-direction-based

    harmonic source detection methods.

    4) The metering point or the relative size of the source and

    the customer impedances will also affect the direction of eitheractive or reactive powers. This is another important factor that

    makes the powe-direction-based methods unreliable.

    The (active)power direction method has been used frequently

    as a practical method for locating harmonic sources. This work

    has shown that the method does not work and there is an urgent

    need to develop new harmonic source detection methods.

    ACKNOWLEDGMENT

    The authors wish to express sincere thanks to M. B. Hughes

    of BC Hydro for valuable comments during the course of this

    work.

    REFERENCES

    [1] P. H. Swart, M. J. Case, and J. D. Van Wyk, On techniques for local-ization of sources producing distortion in three-phase networks, Eur.Trans. Elect . Power Eng., vol. 6, no. 6, Nov./Dec. 1996.

    [2] L. Cristaldi and A. Ferrero, Harmonic power flow analysis for the mea-surement of the electric power quality,IEEE Trans. Instrum. Meas., vol.44, pp. 683685, June 1995.

    [3] H. Yang, P. Porotte, and A. Robert, Assessing the harmonic emissionlevel from one particular customer, in Proc., 1994.

    [4] W. Xu and Y. Liu, A method for determining customer and utility har-monic contributions at the point of common coupling, IEEE Trans.Power Delivery, vol. 15, pp. 804811, Apr. 2000.

    [5] A. E. Emanuel, Onthe assessment of harmonic pollution,IEEE Trans.Power Delivery, vol. 10, pp. 16931698, July 1995.

    [6] M. B. Marz, J. F. Witte, D. L. Williams, and P. M. Thompson, Findingand determining the influence of multiple harmonic sources on a utilitysystem using harmonic measurements, in Power Quality 2000 Conf.,Boston, MA, Oct. 2000.

    Wilsun Xu (M90SM95) received the Ph.D. degree from the University ofBritish Columbia, Vancouver, BC, Canada, in 1989.

    He is presently a Professor at the University of Alberta, Edmonton, AB,Canada. He was with BC Hydro from 1990 to 1996 as an Engineer. His mainresearch interests are power quality and voltage stability.

    Dr. Xu chairs the Harmonics Modeling and Simulation Task Force of theIEEE PES.

  • 7/31/2019 PQ-Direction of Harmonics

    6/6

    XU et al.: VALIDITY OF POWER DIRECTION METHOD FOR HARMONIC SOURCE DETERMINATION 219

    Xian Liu (M95) received the Ph.D. degree from the University of British Co-lumbia, Vancouver, BC, Canada, in 1994.

    He is presentlyan Assistant Professorat theUniversityof Alberta, Edmonton,AB, Canada. He was with Nortel Networks from 1995 to 1999 as an ElectricalEngineer. His main research interests are electric machines, optimization, andreal-time software.

    Yilu Liu (M91) is an Associate Professor of electrical engineering at VirginiaPolytechnic Institute and State University, Blacksburg.

    Her current research interests are power system transients, power quality, andpower system equipment modeling and diagnoses.

    Dr. Liu is the recipient of the 1993 National Science Foundation Young In-vestigator Award and the 1994 Presidential Faculty Fellow Award.