UNIPOWER Advanced Power Quality Monitor UP-2210 www.unipower.se UNIPOWER offers a wide range of products for power quality measurements and demand analysis. Our product line covers a full range from traditional portable PQ analysers to fully integrated, automated Power Quality Management systems. All UNIPOWER products are developed and manufactured in Sweden.

Upload: hazime

Post on 13-Apr-2015

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PQSecure 8page Hardware 5.0AE_eng

UNIPOWER

Advanced Power Quality Monitor

UP-2210

www.unipower.seUNIPOWER offers a wide range of products for power quality measurementsand demand analysis. Our product line covers a full range from traditional portablePQ analysers to fully integrated, automated Power Quality Management systems.All UNIPOWER products are developed and manufactured in Sweden.

Page 2: PQSecure 8page Hardware 5.0AE_eng

UNIPOWER

Measure unit UP-2210

The standard unit is fitted with one RS-485, two RS-232communication ports and one USB port. Other optionsavailable include internal modem, external GSMmodem, ISDN modem and Ethernet.

The UP-2210 can also be fitted with digital inputs anddigital outputs. These may be assigned for othermonitoring purposes such as circuit breaker tripping,security alarms in substations etc, or providing localalarm or control outputs.

The UP-2210 can also be equipped with a faultrecorder module, which activates the unit's digital inputsfor supervision of the status of circuit breakers, relaysand other external equipment. Whenever there is adisturbance in the electrical grid the unit records voltageand current deviations, together with information aboutthe connected external equipment.

UP-2210Advanced 3-phasePower Quality andTransient Monitor

Norm-compliant, IEC 61000-4-30 Class A

Power Quality Monitoring

Transient Monitoring

Demand Monitoring

Fault Recorder

GPS Synchronisation

Fully Simultaneous Operation

PQ Secure Information System

The UP-2210 Power Quality Monitor is designed forpermanent installation in any 50 / 60 Hz system. Allvoltage and current channels are differential, allowingthe UP-2210 to be installed regardless of systemconfiguration.

The unit has 12 voltage and 4 current channels whichmay either be connected directly or using PTs and CTsas required. The heart of the UP-2210 is a 32-bit digitalsignal processor (DSP) enabling all 8 channels to besimultaneously monitored, thereby providing the mostadvanced features available anywhere.

The unit is designed to be fitted inside a switchboard orother equipment and to communicate to a convenientlylocated computer. Several units may be networked to asingle computer, thus providing centralised monitoringto locations both local or distributed on a global basis.

Measure unit UP-2210R

Page 3: PQSecure 8page Hardware 5.0AE_eng

UNIPOWER

The UP-2210 is based on a powerful digital signalprocessor (DSP) which makes it possible tomonitor all parameters simultaneously with highaccuracy.

The analogue sampling system is synchronised with theactual fundamental frequency, which ensures class Aaccuracy and precision as well as accurate eventcapturing.

Each and every cycle is analysed in accordance withIEC 61000-4-30 Class A. The UP-2210 can easily be setup to measure in accordance with EN 50160 or anyother national or international standard, withautomatic reporting to management or other any otherinterested receiver.

Analogue inputsThe UP-2210 has 4 differential voltage and 4 differentialvoltage transient inputs. The bandwidth of each input isadapted to the appropriate application. When measuringharmonics a lower bandwidth is needed than whencapturing transients.The UP-2210 also has 4 differential current inputchannels. In low voltage networks the fourth currentchannel can be used to measure the neutral current.

Ground fault applicationThe fourth voltage channel can be used for earth pointmonitoring in order to find ground faults in impedancegrounded networks.

Earth leakageThe UP-2210 is automatically detecting any earthleakage by summing the phase (and neutral) currents. Ifthere is a ground fault some current will flow in adifferent path and the leakage is detected.

Digital Inputs and Fault RecordingThe UP-2210 can be equipped with digital inputs thatcan interface with a variety of external equipment suchas kWh-meters, water meters, protective relays, circuitbreakers etc. By connecting signals from the protectiverelays, the UP-2210 can work like a fault recorder,recording all signals upon a trig signal at a digital input.

Digital OutputsThe UP-2210 can also be equipped with digital outputsthat can be programmed to alarm when certain pre-setconditions are met. This in turn can alert other, externalsystems. The digital outputs can be used to synchroniseother meters (or UP-2210) to record at en event.

Power Quality Monitor (UP-2210)The UP-2210 is a full-featured, norm-compliant (IEC61000-4-30 Class A) power quality monitor capable ofdetecting any disturbances encountered in a network.It interfaces with the PQ Secure software package.

Measure unit (UP-2210)

Graphical displayAn optional graphical display is also available. The unitis equipped with Unipower’s unique and user-friendlyTurn&Click® interface, and can be connected to a PC(RS-232) on-site via a front panel connector.

Graphical Display Unit

Page 4: PQSecure 8page Hardware 5.0AE_eng

UNIPOWER

Measured parametersThe UP-2210 has been developed as a full-featuredpower quality and transient monitor to simultaneouslymeasure all events on all channels. Individual triggerlevels can be set to enable an infinitely variable range ofuser-defined trigger conditions, either from the remoteworkstation or via a laptop directly connected to themonitor. If a disturbance occurs that exceeds thedefined trigger levels the monitor will record thedisturbance.

The internal memory has been chosen so that there areno moving parts. Problems with hard disks are a thingof the past. Instead, the analyser stores the events onits solid-state internal memory using a sophisticated datacompression technique so that 4 MB representstypically 20 days storage. Remember that the key is theautomatic download to the central database.

Waveforms and power quality parameters can be viewedin real-time with PQ Online or as historical data with the

PQ Secure software (SQL database).

Basic parameters and demandsAll basic power quality parameters are measuredcontinuously and can be viewed in real-time withPQ Online, or as historical data with PQ Secure.

Voltage (phase-phase, phase-neutral) Current (phase-phase, phase-neutral) Active, Reactive and Apparent Power Active, Reactive and Apparent Energy Power Factor and cos phi Frequency

Fault Recorder ModuleThe UP-2210 can also be equipped with a fault recordermodule, which activates the unit's digital inputs forsupervision of the status of circuit breakers, relays andother external equipment. Whenever there is a distur-bance in the electrical grid the unit records voltage andcurrent deviations, together with information about theconnected external equipment.

CommunicationA central feature of UP-2210 is the flexibility and easeof communication between the workstation and thepermanently installed monitor. Communication can bevia a wire, phone connection, radio (and GSM), fibre/wire, etc. The monitor has built-in RS-232, RS-485,USB, Ethernet and also a modem.

Fault Recorder window, displaying voltages, currents anddigital input channels during a fault.

GPS ModuleThe UP-2210 can also be equipped with a GPS module,for time-synchronisation of the UP-2210 unit.

Page 5: PQSecure 8page Hardware 5.0AE_eng

UNIPOWER

HarmonicsHarmonic distortion is caused by non-linear generatorsor loads and can cause severe problems. For example,capacitor banks can easily be damaged and neutralconnectors can overheat. To identify harmonic-relatedproblems it is necessary to measure continuously. TheUP-2210 unit measures harmonics, both amplitude andphase, up to the 50th harmonic. Both THD-F, THD-Rtogether with K-factor and harmonic power arecalculated. All harmonics calculations are in accordancewith IEC 61000-4-30 Class A (IEC 61000-4-7 Class I).The UP-2210 also has a module for studyinginterharmonics and signalling.

Transients, Sags and SwellsDisturbances in a power system are defined as voltagetransients, sags or swells. Transients are fastdisturbances originating from lightning, load switchingetc. Voltage sags are short-duration low RMS-valuesgenerally caused by faults such as short circuits in theutility system. The reliability of a power system iscritical to most businesses and is greatly affected by sagsand swells.

The UP-2210 detects and categorises the type ofdisturbance, and helps to identify the source bydetermining the direction. It measures and calculates theRMS value for each half cycle and uses precision peakdetectors to detect transients down to 1 microsecondduration. When a transient or a sag/swell occurs theUP-2210 records it and stores all necessary data in thebuilt-in memory. It is then automatically transferred tothe workstation with a seamless timebase for evaluation.Transients and sags & swell measurements are based onIEC 61000-4-30 Class A.

PQ Online: real-time evaluation of harmonics.

PQ Secure, Sag&Swell RMS evaluation window

PQ Secure, Sag&Swell duration

PQ Secure, Transient evaluation window

Page 6: PQSecure 8page Hardware 5.0AE_eng

UNIPOWER

MountingThe UP-2210 is a compact and rugged unit and isintended to be mounted permanently on site. The size isonly 205 x 300 x 65 mm (width x height x depth) andideal for mounting in any switchboard. An optionalgraphical display is also available for front panelmonitoring on site and measures only 184 x 91 x 96mm. The display unit can be mounted remotely fromthe UP-2210 and is equipped with an extra front panelRS-232 communication port to which a portablecomputer easily can be connected to view real-timeparameters on site.

UP-2210 installed in a substation cabinet

FlickerFluctuating loads cause voltage variations that are oftenreferred to as flicker. Lamps connected to such a voltageproduce a flickering light, very annoying to the humaneye. The UP-2210 measures voltage flicker inaccordance with IEC 61000-4-30 Class A (IEC 61000-4-15) and calculates flicker parameters such as IFL, PSTand PLT.

UnbalanceUnbalance is a condition where the three phases differin amplitude. This unbalance is frequently expressed asthe ratio of the negative phase sequence divided by thepositive phase sequence, as a percentage. Even smallamounts of voltage unbalance decrease the efficiency ofa three-phase motor. Monitoring the unbalance can helpto improve efficiency and increase the longevity of amotor.

The UP-2210 measures and stores the positive-, nega-tive- and zero-phase sequence and the unbalance forboth voltage and current in accordance with IEC61000-4-30 Class A.

PQ Secure, historical evaluation of PST,short-term flicker severity.

Real-time and troubleshootingWithout interrupting the logging of all parameters, theUP-2210 can show values in different real-time graphs.This makes a great tool that can be used whentroubleshooting different problems on site as well asremote.

Voltage, current, instantaneous flicker level andfrequency in real-time.

Page 7: PQSecure 8page Hardware 5.0AE_eng

UNIPOWER

Example of wiring diagram, 3-phase, 3-wire deltawith 3 PT´s and 3 CT´s

Example of wiring diagram, 3-phase, 3-wire deltawith 2 PT’s and 2 CT’s

ConnectionsThe UP-2210 supports all power configurations as listedbelow.

3-wire system 4-wire system Phase-to-phase, wye and delta configurations

All calculations are based on the correct electricalconfiguration which is set from a drop-down menu.

Typical Substation Application

Installation Fourth voltage input available for measurements in

open delta configurations etc. Fourth current input available for neutral or ground

current measurements 8 (32) digital inputs available for indication

purposes such as circuit breaker tripping etc. 2 (4) digital outputs available for alarm purposes

etc.

L1 L2 L3LINE

LOAD

CT

CT

PT´s

UL1

UL2

UL3

CT

LOAD

CT

CT

PT´s

UL3-L2

UL1-L2

L1 L2 L3

LINE

Power supply(85-264 V AC / 110-375 V DC)

4 current inputs (0-6 A TRMS)

4 voltage inputs (0-275 V TRMS)

Communication(RS-485 in this case)

Connection box(connected to PT’sand CT’s)

PT primary: 11 kVPT secondary: 110 V

CT primary: 3000 ACT secondary: 5 A

Digital In-/Outputs

Power supply(85-264 V AC / 110-375 V DC)

4 current inputs (0-6 A TRMS)

4 voltage inputs (0-275 V TRMS)

Communication(RS-485 in this case)

Connection box(connected to PT’sand CT’s)

PT primary: 11 kVPT secondary: 110 V

CT primary: 3000 ACT secondary: 5 A

Digital In-/Outputs

Page 8: PQSecure 8page Hardware 5.0AE_eng

UNIPOWER

Voltage inputsVoltage channels 4 differential inputsChannel input level 0 - 275 V RMSResolution 14 bit (84 dB)Basic sampling rate 256 samples/cycleInput impedance 2 MohmBandwidth 3.2 kHz analogue anti-aliasing filtersAccuracy IEC 61000-4-30 class A (0.1%)

For maximum accuracy, automatic synchronisation to the power frequency is performedby a phase-locked loop (PLL).

Voltage transient inputsVoltage transient channels 8 differential inputsChannel input level +/- 1500 V peak levelResolution 14 bit (84 dB)Transient detection Fast transients (>1us / 1 MHz), sag/swells, interruptionsInput impedance 2 MohmBandwidth 3 MHz

Current inputsCurrent channels 4 differential inputs (fully isolated inputs optional)Channel input level 0 - 6 A RMS (voltage input optional)Resolution 14 bitBasic sampling rate 256 samples/cycleInput impedance max 10 mohmBandwidth 3.2 kHz analogue anti-aliasing filtersAccuracy 0.1%

Digital inputs8 opto-isolated digital inputs (0-250 VDC). 32 channels optional.

Digital outputs2 solid state relays (0-110 VDC, 0-110 mA). 4 channels optional.

Time synchronisationOptional GPS unit for time synchronisation.

Selected calculated parametersPower Quantities All 3-phase configurations. Active power [kW], Reactive

power [kVAr], Apparent power [kVA], Power Factor andcosϕ (displacement factor), Active Energy [kWh], Reactiveenergy [kVArh], Apparent energy [kVAh]Energy accuracy class 0.2S (IEC 62053-22)

Frequency 45 - 65 Hz according to IEC 61000-4-30 Class A.Harmonics 0 - 50th individual harmonics of voltage and current in

accordance with standard IEC 61000-4-30 Class A. THDfactors (THD-R, THD-F, TDD, THD-I etc), K-factor

Power Harmonics (PFFT) Harmonic power with directionInterharmonics In accordance with IEC 61000-4-30 Class A.Flicker: IFL, Pst, Plt calculated in accordance with standard

IEC 61000-4-30 Class A (IEC 61000-4-15)Voltage / Current Unbalance Positive-, negative- and zero phase sequence plus

unbalance value (%) according to standard IEC 61000-4-30 Class A

Signalling Voltage In accordance with EN 50160 and IEC 61000-4-30Class A

RVC Rapid voltage changes in accordance with IEC 61000-3-7and 61000-4-30 Class A

Current leakage and Isum and Usum parametersVoltage sum

Memory capacity4 MB (8 MB is optional) built-in flash memory for measure data. A unit with standardmemory will be able to measure for at least 20 days with normal configuration.

CommunicationBuilt-in RS-232, RS-485 and USB. Optional Ethernet and internal modem. Support forexternal modems, radio devices, ISDN- and GSM/GPRS-modems.

StandardsVoltage Quality EN 50160, IEC 61000-2-2, IEC 61000-2-12 and other

normsHarmonics Measurements IEC 61000-4-30 Class A (IEC 61000-4-7)Flicker Measurements IEC 61000-4-30 Class A (IEC 61000-4-15)Power Quality IEC 61000-4-30 Class A (Testing and measurement

techniques)Mechanical dataSize W x H x D 205 x 300 x 65 mmOperational temperature -10 ºC to +55 ºCHumidity 10% - 98% non-condensingWeight 1.3 kgSafety IEC 61 010-1EMC IEC 61000-6-4 and IEC 61000-6-2 (EN 50 081-1,2;

EN 50 082-1,2)Calibration and self-testThe calibration of UP-2210 is software-based and is therefore easy to make directly onsite without having to dismount the units. To assure maximum reliability the UP-2210always performs an automatic self-test (AST) before measuring.

Power supplyStandard: 110/230 V AC or 100-375 V DCOptional: 18-36 V DC or 36-72 V DC

Technical SpecificationUP-2210 main features:

Sampling frequencyHigh-speed sampling frequency (256 samples/cycle)gives a high accuracy of all measured parameters.

Transient high speed captureHigh-speed transients down to 1 us are captured andthe waveforms for all 8 channels are recorded and caneasily be evaluated with pre- and post trig.

Sag & Swell long time recording8-channel recording of sags/swells up to 10 seconds(every single cycle is recorded). Selectable pre- and post-trig.

Realtime graphsRealtime values can be studied together with waveform,harmonics graph, vector diagram and unique realtimetime graph of instantaneous flicker level and otherparameters.

Historical Trend graphUnique automatic historical trend graph that shows allimportant values 24 hours back in time in real-timemode. This can also be shown in the optional displayunit that can be mounted in substations etc.

PLL Sampling SynchronisationHigh accuracy of all measured parameters achieved by asynchronisation between the sampling of the inputsignals and the power frequency. The synchronisation ismade possible by a built-in PLL (phase-locked loop).

Flash memoryEasy to upgrade with new software thanks to thebuilt-in flash memory. No moving parts ensures totalreliability.