preaction system with model dv-5 deluge valve...

14
General Description The Model DV-5 Double Interlock Pre- action System with Electric/Electric Actuation (Fig. 1) is designed for use in applications, such as refrigerated areas, requiring the maximum degree of protection against inadvertent flood- ing of the sprinkler system piping. The Model DV-5 Double Interlock Pre- action System with Electric/Electric Actuation utilizes a Model DV-5 Deluge Valve and a Riser Check Valve. The Riser Check Valve (that does not re- quire the use of priming water) isolates the Deluge Valve from the system air pressure. The releasing trim for the Deluge Valve utilizes a Solenoid Valve that is operated by energizing the re- leasing circuit of a Cross-Zone Deluge Valve Releasing Panel (automatic con- trol unit). Zone 1 of the Releasing Panel is oper- ated by either a fire detection device or manual pull station. Zone 2 of the Re- leasing Panel is operated by a Low Air Pressure Alarm Switch in response to a loss of system air pressure due to the opening of an automatic sprinkler. The Solenoid Valve remains closed until it is electrically energized by the Releas- ing Panel. In order for the Double Interlock Pre- action System to automatically actu- ate, two independent events must oc- cur. Zone 1 of the Releasing Panel must operate upon automatic opera- tion of the electric fire detection initiat- ing circuit or operation of the electric- manual pull initiating circuit, and Zone 2 of the Releasing Panel must operate via the Low Air Pressure Alarm Switch upon loss of air pressure from the sprinkler system piping, due to opera- tion of one or more sprinklers. The Double Interlock Preaction Sys- tem will automatically actuate only when both Zone 1 and Zone 2 of the Releasing Panel have operated, ener- gizing the Solenoid Valve. Accidental loss of system air pressure (for exam- ple: a lift truck accidentally dislodges a sprinkler), or operation of just the fire detection circuit (for example: an acci- dental operation of an electric pull sta- tion), will only cause an alarm, and will not actuate the system or flood the sprinkler system piping. The Model DV-5 Deluge Valve (de- scribed in Technical Data Sheet TFP1305) is a diaphragm style valve that depends upon water pressure in the Diaphragm Chamber to hold the Diaphragm closed against the water supply pressure. When the DV-5 Valve is set for service, the Diaphragm Chamber is pressurized through the trim connections from the inlet side of the system’s main control valve, for example an O.S.&Y. gate valve or but- terfly valve (Fig. 1). Operation the Solenoid Valve releases water from the Diaphragm Chamber faster than it can be replenished through the 1/8 inch (3,2 mm) restric- tion provided by the Model ASV-1 Automatic Shut-Off Valve in the dia- phragm supply connections (Item 5 - Fig. 2A, also described in Technical Data Sheet TFP1384). This results in a Page 1 of 14 TFP1465 SEPTEMBER, 2004 Preaction System with Model DV-5 Deluge Valve Double Interlock — Electric/Electric Actuation 1-1/2 thru 8 Inch (DN40 thru DN200) Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 (TEXT CONTINUED ON PAGE 9)

Upload: duongxuyen

Post on 05-Aug-2018

245 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

GeneralDescriptionThe Model DV-5 Double Interlock Pre-action System with Electric/ElectricActuation (Fig. 1) is designed for usein applications, such as refrigeratedareas, requiring the maximum degreeof protection against inadvertent flood-ing of the sprinkler system piping.

The Model DV-5 Double Interlock Pre-action System with Electric/ElectricActuation utilizes a Model DV-5 DelugeValve and a Riser Check Valve. TheRiser Check Valve (that does not re-quire the use of priming water) isolatesthe Deluge Valve from the system airpressure. The releasing trim for theDeluge Valve utilizes a Solenoid Valvethat is operated by energizing the re-leasing circuit of a Cross-Zone DelugeValve Releasing Panel (automatic con-trol unit).

Zone 1 of the Releasing Panel is oper-ated by either a fire detection device ormanual pull station. Zone 2 of the Re-leasing Panel is operated by a Low AirPressure Alarm Switch in response toa loss of system air pressure due to theopening of an automatic sprinkler. TheSolenoid Valve remains closed until itis electrically energized by the Releas-ing Panel.

In order for the Double Interlock Pre-action System to automatically actu-ate, two independent events must oc-cur. Zone 1 of the Releasing Panelmust operate upon automatic opera-tion of the electric fire detection initiat-ing circuit or operation of the electric-manual pull initiating circuit, and Zone2 of the Releasing Panel must operatevia the Low Air Pressure Alarm Switchupon loss of air pressure from thesprinkler system piping, due to opera-tion of one or more sprinklers.

The Double Interlock Preaction Sys-tem will automatically actuate onlywhen both Zone 1 and Zone 2 of theReleasing Panel have operated, ener-

gizing the Solenoid Valve. Accidentalloss of system air pressure (for exam-ple: a lift truck accidentally dislodges asprinkler), or operation of just the firedetection circuit (for example: an acci-dental operation of an electric pull sta-tion), will only cause an alarm, and willnot actuate the system or flood thesprinkler system piping.

The Model DV-5 Deluge Valve (de-scribed in Technical Data SheetTFP1305) is a diaphragm style valvethat depends upon water pressure inthe Diaphragm Chamber to hold theDiaphragm closed against the watersupply pressure. When the DV-5 Valve

is set for service, the DiaphragmChamber is pressurized through thetrim connections from the inlet side ofthe system’s main control valve, forexample an O.S.&Y. gate valve or but-terfly valve (Fig. 1).

Operation the Solenoid Valve releaseswater from the Diaphragm Chamberfaster than it can be replenishedthrough the 1/8 inch (3,2 mm) restric-tion provided by the Model ASV-1Automatic Shut-Off Valve in the dia-phragm supply connections (Item 5 -Fig. 2A, also described in TechnicalData Sheet TFP1384). This results in a

Page 1 of 14 TFP1465SEPTEMBER, 2004

Preaction System with Model DV-5 Deluge ValveDouble Interlock — Electric/Electric Actuation1-1/2 thru 8 Inch (DN40 thru DN200)

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500

(TEXT CONTINUED ON PAGE 9)

Page 2: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Page 2 of 14 TFP1465

Page 3: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Page 3 of 14TFP1465

Page 4: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Page 4 of 14 TFP1465

Page 5: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Page 5 of 14TFP1465

Page 6: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Page 6 of 14 TFP1465

Page 7: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Page 7 of 14TFP1465

Page 8: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Page 8 of 14 TFP1465

FIGURE 31-1/2 thru 8 INCH (D40 and DN200) MODEL DV-5 DELUGE VALVES

DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/ELECTRIC ACTUATION TRIM— NOMINAL INSTALLATION DIMENSIONS —

CHAMBER SUPPLYCONNECTING TRIM

(FIELD FABRICATED)

MAINCONTROL

VALVE

DA

E

2" NPSDRAIN

DIAPHRAGM

L

1/2" NPS

G

H KJ

LEFT VIEW FRONT VIEW

* *

*

1-1/4" NPSDRAIN

B

F

M

C*

(231,8)9.13

(266,7)10.50

(535,0)21.06

(152,4)6.00

(152,4)6.00

(390,5)15.38

(DN50)2"

(79,4)3.13

(177,8)7.00

(225,4)8.88

(330,2)13.00

(266,7)10.50

(520,7)20.50

(147,6)5.81

(147,6)5.81

(76,2)3.00

(101,6)4.00

(376,2)14.81

(DN40)1-1/2"

(101,6)4.00

(177,8)7.00

(181,0)7.13

(330,2)13.00

(76,2)3.00

(177,8)7.00

(79,4)3.13

(254,0)10.00

(289,0)11.38

(298,5)11.75

(363,5)14.31

(454,0)17.88

(476,3)18.75

(266,7)10.50

(739,8)29.13

(811,2)31.94

(165,1)6.50

(200,0)7.88

(217,5)8.56

(252,4)9.94

(158,8)6.25

(181,0)7.13

(9,5)0.38

(39,7)1.56

(644,5)25.38

(752,5)29.63

(44,5)1.75

(88,9)3.50

(266,7)10.50

(181,0)7.13

(198,4)7.81

(265,1)10.44

(266,7)10.50

(635,0)25.00

(170,0)6.69

(108,0)4.25

(536,6)21.13

(DN80)3"

(368,3)14.50

(42,9)1.69

(177,8)7.00

A B C D E G H J K L MFNominal Installation Dimensions in Inches and (mm)

SizeValve

(170,0)6.69

(6,4)0.25

(DN100)4"

(DN150)6"

(158,8)6.25

(304,8)12.00

(406,4)16.00

(539,8)21.25

(933,5)36.75

(273,1)10.75

(269,9)10.63

(927,1)36.50

(DN200)8"

(44,5)1.75

(266,7)10.50

(158,8)6.25

(181,0)7.13

(181,0)7.13

MINIMUM CLEARANCE.*

Page 9: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

rapid pressure drop in the DiaphragmChamber below the valve trip point.The water supply pressure then forcesthe Diaphragm open permitting waterto flow into the system piping, as wellas through the Alarm Port to actuatethe system alarms.

As water flows into the system, thepilot chamber of the Model ASV-1Automatic Shut-Off Valve (Item 5 - Fig.2A) becomes pressurized and theASV-1 automatically shuts off the dia-phragm chamber supply flow to theDV-5 Diaphragm Chamber. Shuttingoff the diaphragm chamber supply flowprevents the DV-5 Diaphragm Cham-ber from becoming re-pressurized,thereby preventing inadvertent closingof the DV-5 during a fire (as may be thecase should the Solenoid Valve be-come de-energized after its initial op-eration).

WARNINGThe Model DV-5 Double Interlock Pre-action System with Electric/ElectricActuation described herein must beinstalled and maintained in compli-ance with this document, as well aswith the applicable standards of theNational Fire Protection Association,in addition to the standards of anyother authorities having jurisdiction.Failure to do so may impair the per-formance of the related devices.

The owner is responsible for maintain-ing their fire protection system and de-vices in proper operating condition.The installing contractor or manufac-turer should be contacted with anyquestions.

TechnicalDataApprovalsUL and C-UL Listed. FM Approved.

Deluge ValveModel DV-5.

Riser Check ValveModel CV-1FR.

NOTE1-1/2 inch (DN40) risers utilize a 2 inch(DN50) Riser Check Valve in combina-tion with the 1-1/2 (DN40) Model DV-5Deluge Valve.

Valve TrimThe Double Interlock Preaction Sys-tem with Electric/Electric ActuationTrim (Fig. 2A/2B) forms a part of thelaboratory listings and approvals. Thetrim is necessary for proper operationof the DV-5 Valve.

Each package of trim includes the fol-lowing items:

• Water Supply Pressure Gauge• Diaphragm Chamber

Pressure Gauge• Diaphragm Chamber Connections• Manual Control Station• Main Drain Valve• System Drain Valve• Alarm Test Valve• Automatic Drain Valve• System Air Pressure Gauge• Air Supply Connections• Low Air Pressure Alarm Switch• Waterflow Pressure Alarm Switch

To ease field assembly of the trim ar-rangement, the trim components areprovided par tially assembled asshown in Figure 2B.

The trim arrangement is provided withgalvanized or black nipples and fit-tings. The galvanized trim is intendedfor non-corrosive or corrosive condi-tions, whereas the black trim is princi-pally intended for use with AFFF sys-tems.

NOTEWhen the system pressure is greaterthan 175 psi (12,1 bar), provision is tobe made to replace the standard order300 psi (20,7 bar) Water PressureGauges, shown in Figure 2A/2B withseparately ordered 600 psi (41,4 bar)Water Pressure Gauges.

System Design ConsiderationsBecause a double interlock preactionsystem requires time for a drop in sys-tem air pressure to occur (concurrentlywith the response time for the separatefire detection system), before it willallow water to enter the system piping,this system has characteristics similarto a dry pipe sprinkler system. There-fore, the system design considerationsfor a dry pipe system are normallyapplied to a double interlock preactionsystem — including a 30% increase indesign area; a maximum 1 minutewater delivery time for system capaci-ties of 750 gallons (2800 litres) ormore; and, prohibition of gridded sys-tem piping.

In order to readily perform the SystemInspection Procedure described in theCare and Maintenance section, it isrecommended that a System Shut-OffValve be installed above the RiserCheck Valve, as shown in Figure 1. TheSystem Shut-Off Valve should be alisted or approved (as appropriate) in-dicating valve with a supervisoryswitch to monitor the normally openposition.

Detection SystemThe Double Interlock Preaction Sys-tem With Electric/Electric ActuationTrim provides for electric operation ofthe DV-5 Valve by a detection systemconsisting of electrical devices such asheat sensitive thermostats, smoke de-tectors, and/or electric manual pull sta-tions. Information on the various typesof separately ordered Solenoid Valvesthat may be used with this trim pack-age is given in Technical Data SheetTFP2180. Nominal installation dimen-sions for the Double Interlock Preac-tion System With Electric/Electric Ac-tuation Trim are shown in Figure 3.

The cross-zone deluge valve releasingpanel (automatic control unit) with bat-tery back-up, fire detection devices,manual pull stations, and signaling de-vices, that are utilized with the DoubleInterlock Preaction System with Elec-tric/Electric Actuation must be ULListed, ULC Listed, C-UL Listed, or FMApproved, as applicable.

NOTESApproval by Factory Mutual is contin-gent on the use of an FM Approved24VDC Solenoid Valve (P/N 52-287-1-024 or P/N 52-287-1-124). FM onlyapproves solenoid valves for use innon-hazardous locations.

Consult with the Authority Having Ju-risdiction regarding installation criteriapertaining to electric actuation cir-cuitry.

The Double Interlock Preaction Sys-tem With Electric/Electric ActuationTrim is provided with a Model ASV-1Automatic Shut-Off Valve (Item 5 - Fig.2A); consequently, the release circuitof the releasing panel need only pro-vide the standard ten minutes of alarmcondition intended to energize the So-lenoid Valve to open. After the tenminute duration, at which point shouldthe Solenoid Valve become de-ener-gized and close (especially while oper-ating under battery back-up), the Auto-matic Shut-Off Valve will have alreadyautomatically closed, thereby prevent-ing the DV-5 Diaphragm Chamber frombecoming re-pressurized and prevent-ing an inadvertent closing of the DV-5during a fire event.

System Air Pressure RequirementsThe recommended system air pres-sure for the Double Interlock PreactionSystem with Electric/Electric Actuationis nominally 15 psi (1,0 bar), irrespec-tive of the water supply pressure. Theuse of a higher system air pressuremay increase water delivery time, andthe use of a lower system air pressuremay prevent clearing the alarm of theLow Air Pressure Alarm Switch (ItemP3 - Fig. 2A) on increasing pressure.

Page 9 of 14TFP1465

Page 10: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Page 10 of 14 TFP1465

200 400 1000 3000200060010050

FLOW RATE IN GALLONS PER MINUTE (GPM)

3.0

NO

MIN

AL

PR

ES

SU

RE

DR

OP

IN P

OU

ND

S P

ER

SQ

UA

RE

INC

H(P

SI)

0.8

0.4

0.5

0.6

0.7

1.00.9

2.0

6.0

4.0

5.0

9.0

7.0

8.0

10.0

15.0

FLOW RATE IN LITRES PER MINUTE (LPM)

200 1000600400

(1 GPM = 3,785 LPM)

2000 70003000 5000 10000

(1P

SI=

0,06

895

BA

R)

NO

MIN

AL

PR

ES

SU

RE

DR

OP

IN B

AR

0,040

0,030

0,050

0,080

0,060

0,070

0,0900,100

0,200

0,800

0,400

0,300

0,600

0,500

0,700

1,0000,900

2 IN

CH

(DN

50)

1-1/

2IN

CH

(DN

40)

6 IN

CH

(DN

150)

4 IN

CH

(DN

100)

3 IN

CH

(DN

80)

8 IN

CH

(DN

200)

GRAPH BDELUGE AND CHECK VALVE COMBINATION*

— NOMINAL PRESSURE LOSS VERSUS FLOW —

* Model DV-5 Deluge Valve combined with Model CV-1FR Riser Check Valve

**1-1/2 inch Model DV-5 Deluge Valve combined with 2 inch Model CV-1FR Riser Check Valve

The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe with C=120, is asfollows:

15 feet of 1-1/2 Sch. 40 pipe for the 1-1/2 inch Valve Combination** calculated on a typical flow rate of 100 GPM.28 feet of 2 inch Sch. 40 pipe for the 2 inch Valve Combination* calculated on a typical flow rate of 175 GPM.37 feet of 3 inch Sch. 40 pipe for the 3 inch Valve Combination* calculated on a typical flow rate of 350 GPM.48 feet of 4 inch Sch. 40 pipe for the 4 inch Valve Combination* calculated on a typical flow rate of 600 GPM.73 feet of 6 inch Sch. 40 pipe for the 6 inch Valve Combination* calculated on a typical flow rate of 1500 GPM.103 feet of 8 inch Sch. 30 pipe for the 8 inch Valve Combination* calculated on a typical flow rate of 1500 GPM.

Page 11: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

The Low Pressure Alarm Switch isfield set to alarm at nominally 12 psi(0,8 bar) on decreasing pressure. It isrecommended that the system airpressure be maintained by either ofthe following methods.

• A maximum 200 psi (13,8 bar) plantair supply in combination with theModel AMD-1 Air Maintenance De-vice described in Technical DataSheet TFP1221.

• A maximum 3000 psi (206,9 bar)nitrogen cylinder in combination withthe Model AMD-3 Nitrogen Mainte-nance Device described in Techni-cal Data Sheet TFP1241.

NOTESIt is recommended that the pressuremaintenance device be of a type thatmaintains a constant system pressure,i.e., a pressure maintenance devicethat utilizes a pressure regulator ver-sus a pressure switch (e.g., the AMD-1or AMD-3). Use of a pressure switchoperated pressure maintenance de-vice with a cut-in/cut-out differentialmay result in a delay in the operationof the system due to a fire, because ofthe cut-out pressure being higher thanthe recommended nominal system airpressure.

The dew point of the air or nitrogensupply, for a system exposed to freez-ing conditions, must be maintained be-low the lowest ambient temperature towhich the system piping will be ex-posed. Introduction of moisture intothe system piping can create ice buildup which could prevent proper opera-tion of the system.

The Pressure Relief Valve (Item P4-Fig. 2A) is typically field set to crackopen at a pressure of about 20 psi (1,4bar).

Friction LossThe nominal pressure loss versus flowdata for the Model DV-5 Deluge Valveplus Riser Check Valve is provided inGraph A.

InstallationNOTES

1-1/2 inch (DN40) risers utilize a 2 inch(DN50) Riser Check Valve in combina-tion with the 1-1/2 (DN40) Model DV-5Deluge Valve.

Proper operation of the Model DV-5Deluge Valves depends upon their trimbeing installed in accordance with theinstructions given in this TechnicalData Sheet. Failure to follow the ap-propriate trim diagram may preventthe DV-5 Valve from functioning prop-erly, as well as void listings, approvals,and the manufacturer’s warranties.

Field adjustments of the Air Mainte-nance Device, Low Pressure AlarmSwitch, and Pressure Relief Valve arerequired. The Air Maintenance Deviceand the Low Pressure Alarm Switchshould be set as close as possible tothe specified settings in order to mini-mize water delivery time.

When using compressed air as op-posed to compressed nitrogen for re-frigerated area service, alternate airsupply connections with an air dryermay be required by the Authority Hav-ing Jurisdiction. The “1/2 Inch NPTConnection For System Air Supply”shown in Figure 2B is to be pluggedwhen using an alternate air supplyconnection; the location of the AirPressure Maintenance is to be asspecified by the Authority Having Ju-risdiction; and, Step 10 regarding theadjustment of the Pressure ReliefValve can be omitted, since the Pres-sure Relief Valve in this case will beineffective.

The DV-5 Valve must be installed in areadily visible and accessible location.

The DV-5 Valve and associated trimmust be maintained at a minimum tem-perature of 40°F/4°C.

Heat tracing of the DV-5 Valve or itsassociated trim is not permitted. Heattracing can result in the formation ofhardened mineral deposits that canprevent proper operation.

The Model DV-5 Deluge Valve is to beinstalled in accordance with the follow-ing criteria:

Step 1. All nipples, fittings, and de-vices must be clean and free of scaleand burrs before installation. Use pipethread sealant sparingly on male pipethreads only.

Step 2. The DV-5 Valve must betrimmed in accordance with Figure2A/2B.

Step 3. Care must be taken to ensure

that check valves, strainers, globevalves, etc. are installed with the flowarrows in the proper direction.

Step 4. Drain tubing to the drip funnelmust be installed with smooth bendsthat will not restrict flow.

Step 5. The main drain and drip funneldrain may be interconnected provideda check valve is located at least 12inches (300 mm) below the drip funnel.

Step 6. Suitable provision must bemade for disposal of drain water.Drainage water must be directed sothat it will not cause accidental dam-age to property or danger to persons.

Step 7. Connect the DiaphragmChamber Supply Control Valve to theinlet side of the system’s main controlvalve in order to facilitate setting of theDV-5 Valve (Fig. 3).

Step 8. Unused pressure alarmswitch connections must be plugged.

Step 9. A suitable automatic supervi-sory air (nitrogen) supply, as describedin the Technical Data Section, is to beinstalled in accordance with the appli-cable Technical Data Sheet and set tomaintain nominally 15 psi (1,0 bar).

Step 10. Adjust the Pressure ReliefValve (P4-Fig. 2A), as applicable, tocrack open at approximately 20 psi(1,4 bar). As shipped, it is set to openat approximately 45 psi (3,1 bar).

To reset the Pressure Relief Valve, firstloosen the jam nut and then adjust thecap accordingly — clockwise for ahigher pressure setting or counter-clockwise for a lower pressure setting.After verifying the desired pressuresetting, tighten the jam nut.

Step 11. Adjust the Low PressureAlarm Switch (P3-Fig. 2A) to transferthe electrical contacts at nominally 12psi (0,8 bar) on decreasing pressure.As shipped, the switch is set to transferthe electrical contacts at approxi-mately 5 psi (0,3 bar) on decreasingpressure.

Use the instructions provided with theswitch to adjust the pressure setting.

Step 12. Conduit and electrical con-nections are to be made in accordancewith the requirements of the authorityhaving jurisdiction and/or the NationalElectric Code.

NOTEThe heat detection devices are to beconnected to the Zone 1 initiating cir-cuit contacts of the Cross-Zone Del-uge Valve Releasing Panel.

The Low Air Pressure Alarm Switchcontacts are to be connected to theZone 2 initiating circuit contacts of the

Page 11 of 14TFP1465

Page 12: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Cross-Zone Deluge Valve ReleasingPanel.

Step 13. Before a system hydrostatictest is performed in accordance withNFPA 13 system acceptance test re-quirements, the DV-5 DiaphragmChamber is to be depressurized; theAutomatic Drain Valve (4, Fig. 2A) is tobe temporarily replaced with a 1/2 inchNPT plug, the 3/32 inch Vent Fitting (16- Fig. 2A) is to be temporarily replacedwith a 1/4 inch NPT plug, and the Dia-phragm Cover Bolts must be uni-formly and securely tightened usinga cross-draw sequence. After tight-ening, double-check to make certainthat all of the Diaphragm Cover Boltsare securely tightened.

Valve SettingProcedureSteps 1 through 15 are to be per-formed when initially setting the ModelDV-5 Deluge Valve; after an opera-tional test of the fire protection system;or, after system operation due to a fire.

Step 1. Close the Main Control Valve.

Step 2. Close the Diaphragm Cham-ber Supply Control Valve and the Sys-tem Air Supply Control Valve.

Step 3. Open the Main Drain Valve,System Drain Valve, and all auxiliarydrains in the system. After waterceases to discharge, close the SystemDrain Valve and auxiliary drain valves.Leave the Main Drain Valve open.

NOTEDo not open the Inspector’s Test Con-nection and auxiliary drains if resettingafter a system test; otherwise, systemair pressure will be relieved unneces-sarily.

Step 4. Depress the plunger of theAutomatic Drain Valve to verify that itis open and that the DV-5 Valve iscompletely drained.

Step 5. Clean the Strainer in the Dia-phragm Chamber Supply connectionby removing the clean-out plug andstrainer basket. The Strainer may beflushed out by momentarily openingthe Diaphragm Chamber Supply Con-trol Valve.

Step 6. Inspect for and clear all iceplugs where system piping has beenexposed to freezing conditions andwhen there has been a flow of waterinto the system.

Step 7. Replace all damaged or oper-ated sprinklers. Replacement sprin-klers must be of the same type andtemperature rating as those that oper-ated.

NOTEIn order to prevent the possibility of asubsequent operation of an over-heated solder type sprinkler, any sol-der type sprinklers that were possiblyexposed to a temperature greater thantheir maximum rated ambient mustalso be replaced.

Step 8. Service the air dryer, if appli-cable, in accordance with the manu-facturer’s instructions.

Step 9. Open the System Air SupplyControl Valve and allow the system toautomatically re-establish its nominalair pressure of 15 psi (1,0 bar). Ob-serve the Automatic Drain Valve forleaks. If there are leaks, deter-mine/correct the cause of the leakageproblem within the Riser Check Valve.

Step 10. Reset the actuation system.

Manual Actuation — Push the operat-ing lever up; however, do not close thehinged cover at this time.

Electric Actuation — Reset the electricdetection system in accordance withthe manufacturer’s instructions to de-energize the Solenoid Valve.

Step 11. Open the Diaphragm Cham-ber Supply Control Valve and allow fullpressure to build up in the DiaphragmChamber.

Step 12. Operate (open) the ManualControl Station to vent trapped air fromthe Diaphragm Chamber. If necessary,first open the hinged cover, and thenfully pull down on the operating lever.SLOWLY close the operating lever, bypushing it up, after aerated waterceases to discharge from the ManualControl Station drain tubing. Close thehinged cover and insert a new breakrod in the small hole through the top ofthe enclosing box.

Step 13. Inspect the drain connectionsfrom the Manual Control Station andthe Solenoid Valve. Any leaks must becorrected before proceeding to thenext step.

Step 14. Verify the ability for the DV-5Diaphragm to hold pressure as fol-lows:

With the diaphragm chamber pressur-ized per Step 12, temporarily close theDiaphragm Chamber Supply ControlValve, and monitor the DiaphragmChamber Pressure Gauge for a drop inpressure.

If a drop in pressure is noted, the DV-5Diaphragm is to be replaced and/orany leaks must be corrected beforeproceeding to the next step.

If the Diaphragm Chamber PressureGauge does not indicate a drop inpressure, re-open the Diaphragm

Chamber Supply Control Valve andproceed to the next step.

Step 15. Slowly open the Main ControlValve. Close the Main Drain Valve assoon as water discharges from thedrain connection. Observe the Auto-matic Drain Valve for leaks. If there areleaks, determine/correct the cause ofthe leakage problem. If there are noleaks, the DV-5 Valve is ready to beplaced in service and the Main ControlValve must then be fully opened.

NOTESWhen the Main Control Valve isopened, the pressure on the Dia-phragm Chamber may increase. Thisincrease in pressure is normal, and ifthe pressure is greater than 250 psi(17,2 bar), the pressure is to be re-lieved by partially and temporarilyopening the Manual Control Station;however, do not allow the pressure asindicated on the Diaphragm ChamberPressure Gauge to drop below thesupply pressure shown on the WaterSupply Pressure Gauge, since this ac-tion may result in tripping of the DV-5Valve.

After setting a fire protection system,notify the proper authorities and ad-vise those responsible for monitoringproprietary and/or central stationalarms.

Care andMaintenanceThe following procedures, inspections,and maintenance must be performedas indicated, in addition to any specificrequirements of the NFPA, and anyimpairment must be immediately cor-rected.

The owner is responsible for the in-spection, testing, and maintenance oftheir fire protection system and de-vices in compliance with this docu-ment, as well as with the applicablestandards of the National Fire Protec-tion Association (e.g., NFPA 25), inaddition to the standards of anyauthority having jurisdiction. The in-stalling contractor or product manufac-turer should be contacted relative toany questions.

It is recommended that automaticspr inkler systems be inspected,tested, and maintained by a qualifiedInspection Service in accordance withlocal requirements and/or nationalcodes.

It is recommended that the SystemInspection Procedure be performed atleast semi-annually by a qualified In-spection Service. The Double Interlock

Page 12 of 14 TFP1465

Page 13: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

Preaction System Inspection Proce-dure may be followed in lieu of per-forming any of the operational testsrecommended in the Technical DataSheets for the Model DV-5 DelugeValve, Riser Check Valve, 24 VDC So-lenoid Valve, and Model MC-1 ManualControl Station.

NOTESIt is recommended that the individualsresponsible for the care and mainte-nance of the Double Interlock Preac-tion System develop a working under-standing of the system, in general,prior to performing inspection and/ormaintenance procedures. These in-structions, as well as individual in-structions for the deluge valve, risercheck valve, solenoid valve, manualcontrol station, switches, and pressuremaintenance device should be re-viewed.

The following procedures pertain tothe automatic control valve portion ofthe Double Interlock Preaction Sys-tem. Refer to the manufacturer’s in-structions and NFPA 25 for care andmaintenance procedures for all otherdevices (e.g., electric detection, maincontrol and system shut-off valves, su-pervisory devices, sprinklers, etc.).

Before performing the System Inspec-tion Procedure, which will result in op-eration of alarms, notify the properauthorities and all personnel who maybe affected.

Before closing a fire protection systemmain control valve for maintenancework on the fire protection system thatit controls, permission to shut down theaffected fire protection system must beobtained from the proper authoritiesand all personnel who may be affectedby this action must be notified.

System Inspection Procedure

Step 1. Close the Main Control Valve(Fig. 1) and then open the DV-5 MainDrain Valve (Fig. 2B).

Step 2. Manually operate Zone 1 of theReleasing Panel, and verify the follow-ing:

• Verify the operation of the ReleasingPanel and its associated alarms.

• Verify that there is no leakage fromthe Solenoid Valve (Fig. 2B).

NOTESDuring this procedure, the SolenoidValve should remain closed and theDV-5 Deluge Valve Diaphragm Cham-ber should remain pressurized.

This procedure is used to verify thatthe DV-5 Deluge Valve will remain setif the electric detection system(Zone 1)operates but the sprinkler system

(Zone 2) remains in its normally pres-surized condition.

Step 4. Restore the electric fire detec-tion system to a normal condition inaccordance with the manufacturer’s in-structions.

Step 5. Open the Inspector’s Test Con-nection to relieve system air pressure,and verify the following:

• Verify that the Low Air PressureAlarm Switch (Fig. 2B) and Zone 2of the Releasing Panel, as well as itsassociated alarms, operate prop-erly. The Low Pressure AlarmSwitch should operate at approxi-mately 12 psi (0,8 bar).

• Verify that there is no leakage fromthe Solenoid Valve (Fig. 2B).

Close the Inspector’s Test Connection.

NOTESDuring this procedure, the SolenoidValve should remain closed and theDV-5 Deluge Valve Diaphragm Cham-ber should remain pressurized.

This procedure is used to verify thatthe DV-5 Deluge Valve will remain setif the Low Pressure Alarm Switch(Zone 2) operates due to loss of sys-tem air pressure and the electric de-tection system (Zone 1) remains in anormal condition.

Step 6. Restore the electric fire detec-tion system to a normal condition inaccordance with the manufacturer’s in-structions after the system air pres-sure has automatically been restoredto normal.

Step 7. Close the System Shut-offValve (Fig. 1).

Step 8. Open the Main Control Valve(Fig. 1) one turn beyond the position atwhich water just begins to flow fromthe Main Drain Valve (Fig. 2B).

Step 9. Close the Main Drain Valve.

Step 10. Close the Air Supply ControlValve.

Step 11. Manually operate Zone 1 ofthe Releasing Panel, and then operateZone 2 of the Releasing Panel by par-tially opening the System Main DrainValve (Fig. 2B) to relieve air pressureat the Low Pressure Alarm Switch, andverify the following:

• Verify that the DV-5 Deluge Valveoperates, as is indicated by a dis-charge of water from the SystemMain Drain Valve.

• Verify that the Waterflow PressureAlarm Switch (Fig. 2B) and its asso-ciated alarms properly operate.

• Verify that the Water Motor Alarm, ifapplicable, properly operates.

NOTEThis procedure simulates automaticsystem operation upon both electricdetection and loss of system air pres-sure.

Step 12. Reset the Double InterlockDry System in accordance with theSystem Setting Procedure section.

Quarterly Waterflow Alarm TestProcedureTesting of the system waterflow alarmsmust be performed quarterly. To testthe waterflow alarm, open the AlarmTest Valve, which will allow a flow ofwater to the Waterflow Pressure AlarmSwitch and/or Water Motor Alarm.Upon satisfactory completion of thetest, close the Alarm Test Valve.

LimitedWarrantyProducts manufactured by Tyco FireProducts are warranted solely to theoriginal Buyer for ten (10) yearsagainst defects in material and work-manship when paid for and properlyinstalled and maintained under normaluse and service. This warranty will ex-pire ten (10) years from date of ship-ment by Tyco Fire Products. No war-ranty is given for products orcomponents manufactured by compa-nies not affiliated by ownership withTyco Fire Products or for products andcomponents which have been subjectto misuse, improper installation, corro-sion, or which have not been installed,maintained, modified or repaired in ac-cordance with applicable Standards ofthe National Fire Protection Associa-tion, and/or the standards of any otherAuthorities Having Jurisdiction. Mate-rials found by Tyco Fire Products to bedefective shall be either repaired orreplaced, at Tyco Fire Products’ soleoption. Tyco Fire Products neither as-sumes, nor authorizes any person toassume for it, any other obligation inconnection with the sale of products orparts of products. Tyco Fire Productsshall not be responsible for sprinklersystem design errors or inaccurate orincomplete information supplied byBuyer or Buyer’s representatives.

IN NO EVENT SHALL TYCO FIREPRODUCTS BE LIABLE, IN CON-TRACT, TORT, STRICT LIABILITY ORUNDER ANY OTHER LEGAL THE-ORY, FOR INCIDENTAL, INDIRECT,SPECIAL OR CONSEQUENTIALDAMAGES, INCLUDING BUT NOTLIMITED TO LABOR CHARGES, RE-GARDLESS OF WHETHER TYCO

Page 13 of 14TFP1465

Page 14: Preaction System with Model DV-5 Deluge Valve …firehose.com.ar/.../DV_5_Double_Interlock_Electric_Electric.pdf · Preaction System with Model DV-5 Deluge Valve Double Interlock

FIRE PRODUCTS WAS INFORMEDABOUT THE POSSIBILITY OF SUCHDAMAGES, AND IN NO EVENTSHALL TYCO FIRE PRODUCTS’ LI-ABILITY EXCEED AN AMOUNTEQUAL TO THE SALES PRICE.

THE FOREGOING WARRANTY ISMADE IN LIEU OF ANY AND ALLOTHER WARRANTIES EXPRESS ORIMPLIED, INCLUDING WARRANTIESOF MERCHANTABILITY AND FIT-NESS FOR A PARTICULAR PUR-POSE.

OrderingProcedureWith reference to Table A on Page 14,the following items must be orderedseparately:

• Deluge Valve• Riser Check Valve• Coupling (Deluge Valve to Riser

Check Valve)• Double Interlock Preaction Trim• Automatic System Air Supply• Solenoid Valve• Accessories

NOTE1-1/2 inch (DN40) risers utilize a 2 inch(DN50) Riser Check Valve in combina-tion with the 1-1/2 (DN40) Model DV-5Deluge Valve.

Part Numbers for factory pre-trimmedModel DV-5 Valves are provided in thePrice Book.

Replacement Trim Parts:Specify: (description) for use withModel DV-5 Deluge Valve, P/N (seeFigure 2A).

Page 14 of 14 TFP1465

TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446

DELUGE VALVE (SELECT ONE)P/N’s are for American Standard Groove x Groove Connections, and Threaded Ports, Forother configurations refer to Technical Data Sheet TFP1305. Specify: (size) Model DV-5groove x groove Deluge Valve, P/N (specify).

1-1/2 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-9192 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-9103 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-9124 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-9136 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-9158 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-916

RISER CHECK VALVE (SELECT ONE)P/N’s are for American Standard Grooved Connections. For other configurations refer toTechnical Data Sheet TFP950 for the groove x groove Model CV-1FR Riser Check Valve.Specify: (size), Model CV-1FR groove x groove Riser Check Valve, P/N (specify). For 1-1/2inch risers, use the 2 Inch Riser Check Valve.

2 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-0203 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-0304 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-0406 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-0608 Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-080

COUPLING (SELECT ONE)P/N’s are for American Standard Grooved Connections. For other configurations andfinishes refer to Technical Data Sheet TFP1830 or TFP1880. A coupling to attach theRiser Check Valve to the outlet of the Deluge Valve must be separately ordered. Specify:(Size), (Figure #), painted, (description), P/N (specify). For 1-1/2 inch risers, order anadditional Reducing Coupling for the outlet of the 2 inch Riser Check Valve.

2 x 1-1/2 Inch Figure 716 Painted Reducing Coupling . . . . . . . . . . . . . . . . . . . . . . . P/N 7162015ES2 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77220ASC3 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77230ASC4 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77240ASC6 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77260ASC8 Inch Figure 772 Painted Rigid Coupling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 77280ASC

DOUBLE INTERLOCK PREACTION TRIM (SELECT ONE)Specify: (specify size and finish — galvanized is standard) Semi-Preassembled DoubleInterlock Preaction System With Electric/Electric Actuation Trim for Model DV-5 DelugeValves, P/N (specify).

1-1/2 & 2 Inch Galvanized. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-2-1281-1/2 & 2 Inch Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-1-1283 Inch Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-2-1253 Inch Black . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-1-1254 & 6 Inch Galvanized . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-2-1224 & 6 Inch Black. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-478-1-122

AUTOMATIC SYSTEM AIR SUPPLY (SELECT ONE)A device capable of maintaining a nominal system air or nitrogen pressure of nominal 15psi (1,0 bar) must be separately ordered. Specify: (Specify model and description), P/N(specify).

Model AMD-1 Air Maintenance Device (TFP1221) . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-324-2-002Model AMD-3 Nitrogen Maintenance Device (TFP1241) . . . . . . . . . . . . . . . . . . . . . P/N 52-328-2-001

SOLENOID VALVE (SELECT ONE)A Solenoid Valve compatible with the anticipated maximum water supply pressure mustbe ordered separately. Refer to Technical Data Sheet TFP2180 for other voltage ratingsand NEMA classifications. Specify: 24 VDC, NEMA 2, 4 and 4X, (specify 175 or 250 psi)Solenoid Valve, P/N (specify).

175 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-287-1-024250 psi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-287-1-124

ACCESSORIES (AS NEEDED)Specify: (description), PN (specify).

600 PSI Water Pressure Gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 92-343-1-004Model WMA-1 Water Motor Alarm (TFP921) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . P/N 52-630-1-001

TABLE A — ORDERING LIST