presentation of a case study egress and smoke … sfpe... · presentation of a case study egress...
TRANSCRIPT
Presentation of a Case StudyEGRESS AND SMOKE MOVEMENT
MODELING AT5 BEEKMAN STREET
for theNew Jersey Chapter
Society of Fire Protection Engineers
September 9, 2013
Introduction1. Building Description2. Project Overview3. Atrium Details4. Atrium Challenges5. Atrium Solutions
6. Smoke & Egress Models7. Applicable Codes & Standards8. Tenability Criteria9. Design Fire Scenarios10. Analysis of Models
Building Description
• 150,000 square feet
• Originally constructed in 1882
• First “fireproof” office building
• Located in historic district
Project OverviewConversion to hotel occupancy with new hotel/residential tower addition.
Original BuildingAnnex
New Tower
Atrium Details• 9 stories and 144 feet in height
• Floor openings 28 ft by 21 ft
• Skylight completely overhangs 9th Floor
• Decorative stair and elevators open to atrium
• SHPO request to maintain “original historic fabric”
Atrium DetailsFire rating separating the egress balcony from guest rooms
Means of EgressAtrium and guest room egress through 2-hour atrium separation to new exit stairs.
Elevators and Open Stair
Exit Stair
Balcony Walkway
Exit Stair
Atrium
Paths of Egress
2-hr Atrium Separation
Atrium Challenges
• Using prescriptive design = large smoke exhaust capacity
• Limited physical means to provide smoke exhaust• Open stairs and elevators connect at all levels of
atrium without separation• Skylight overhanging upper balcony• Maintain original historic appearance
Atrium Solutions
• Maximize smoke exhaust capacity from top of atrium• Use smoke curtains and glass corner barriers to:
– Minimize atrium volume– Minimize smoke movement/leakage onto egress balconies
• Limit potential fire size at the 1st Floor• Provide early detection
– Beam smoke detectors for upper atrium– Flame (UV/IR) detectors for the 1st Floor
Smoke Curtains• Automatic, electrically operated
• Forms a continuous barrier against smoke movement
• Gravity “fail safe” operation
• Two stage deployment option
• UL Listed• UL 10D Fire & Smoke
Curtains• UL 864 Control Accessories
for Fire Alarm Systems
Smoke Curtain and Glass Corner LocationsTypical floors 2 - 9
Atrium
GlassCorner
Barriers
SmokeCurtains
Smoke Curtain at Floors 2 - 8Sectional view along balcony
SmokeCurtain Housing
Deployed SmokeCurtain
Smoke Curtain with Canopy at Floor 9Sectional view along balcony
SmokeCurtain Housing
Deployed SmokeCurtain
Glass Canopy
Interferences at CornersGlass corner barriers provided at Floors 2 – 8 to limit gaps
Glass Corner Barrier
Deployed SmokeCurtain
Smoke Exhaust SystemTwelve smoke exhaust fans with total capacity of 48,000 CFM.
Smoke Exhaust SystemFour exhaust points on three sides (North, East and West)
Beam Smoke DetectionEarly detection of smoke.
Flame DetectionRapid detection of fire with flame detectors at the 1st Floor.
Smoke Exhaust System Make-Up Air• Make-up air enters at the 1st
Floor through louvers on the West side and via the main entrance doors.
• All make-up air components to be automatically activated by the fire alarm system.
• A minimum of 180 square feet of free area is provided.
Main Entrance Doors
Louvers
Smoke and Egress Models
• Demonstrate that the design meets the intent of Section 909 of the 2008 New York City Building Code.
• Demonstrate that a tenable environment is provided for evacuation of occupants from the atrium.
• Fire Dynamic Simulator (FDS) version 5.3.2, Smokeview and Pathfinder 2011TM
Applicable Codes & Standards
• Applicable Code– 2008 New York City Building Code
• Other Referenced Standards– NFPA 92B, Standard for Smoke Management Systems in
Malls, Atriums, and Large Spaces, 2009 Edition– International Building Code, 2009 Edition
Applicable Codes & Standards
• All portions of an atrium smoke exhaust system are required to be capable of continued operation for a minimum of 20 minutes. (2008 NYCBC 909.4.6)
• A time of tenability to be maintained for 1.5 times a calculated egress time or 20 minutes, whichever is less. (IBC 909.4.6)
• When the design is based on occupants exiting a building, a timed egress analysis should be conducted. (NFPA 92B 4.5.3.3)
Tenability Criteria
• Visibility– The measured distance an occupant can see through smoke
• Temperature– The higher temperatures that may be present due to a fire
• Carbon Monoxide Concentration– The concentration of carbon monoxide that may be present
due to a fire
Tenability Criteria
Tenability Parameter Performance Criteria
Visibility2 33 ft (10 m)
Occupant Exposure Temperature1 140oF (60oC)
Carbon Monoxide Concentration1 1000 ppm
1. David A. Purser, “Assessment of Hazards to Occupants from Smoke, Toxic Gases, and Heat” SFPE Handbook, 4th
Edition2. G.V. Hadjisophocleous, N. Benichou, and A.S. Tamin, “Literature Review of Performance-Based Fire Codes and
Design Environment,” Journal of Fire Protection Engineering, 9(1), 1998, pp12-40.
Measured at 6 feet above the walking surface of the means of egress.
Design Fire Scenarios
• Two Severe Case Scenarios– 1st Floor below the atrium opening (not sprinkler protected)– 1st Floor restaurant bar (sprinkler protected with 15.57 feet
ceiling height)
• Anticipated Fuel Load– Seating complying with CAL-TB 133– Dining tables– Restaurant furnishings (e.g., pillows)– Wood bar
Design Fire Scenarios
• No large fuel loads anticipated on Floors 2 – 9 of atrium since balconies are part of the means of egress.– Assumes balconies kept clear as means of egress– Housekeeping cart may be present at times, but balconies
are sprinkler protected (less severe case)
CAL-TB 133
• California Technical Bulletin 133 (CAL-TB 133)– Full scale test of the entire seating piece.– Each piece of furniture is listed as an entire assembly.
• During the test, the furnishing cannot:– Exceed 80 kW maximum heat release rate at any point– Exceed 25 MJ total heat release rate in first 10 minutes– Exceed 75% opacity at any point within 4 feet– Exceed 1,000 ppm carbon monoxide concentration
Design Fire Scenario 1• Fire located under atrium
opening• Not sprinkler protected• CAL TB 133 furniture, table and
pillows
3 Tables = 750 kW8 Chairs = 640 kWMiscellaneous Furnishings = 200 kWConservative Addition of 400 kW
Total = 2,000 kW
Fuel Package Peak Heat Release Rate
Cal TB133 seating furniture
80 kW
Wood table w/ metal legs (area 10sqft)
250 kW
Design Fire Scenario 2• Fire located at restaurant bar
area• Sprinkler protected• CAL TB 133 furniture, wood bar
and miscellaneous items
Bar (2 x Desks) = 1,300 kW8 Bar Chairs = 640 kWMiscellaneous Items = 250 kWConservative Addition of 410 kW
Total = 2,600 kW
Fuel Package Peak Heat Release Rate
Cal TB133 seating furniture
80 kW
Wooden desk (2 ft by 4 ft by 2.6 ft)
650 kW
Analysis of Models
• Timed egress analysis using Pathfinder (Thunderhead Engineering)
• Two Severe Case Design Fire Scenarios using Fire Dynamics Simulator (FDS) (National Institute of Standards and Technology)
• Compare results to ensure tenable environment is maintained for required egress time.
Egress Model Results• Fire Detection
• Fire Scenario 1 = 20 seconds• Fire Scenario 2 = 50 seconds
• Occupant Notification• 10 seconds (NFPA 72)
• Occupant Pre-Movement Delay• Perception, Interpretation and
Action• 240 seconds• SFPE Handbook, 3rd Edition,
Table 3-13.1
• Occupant Movement• Pathfinder results
SFPE Handbook, 3rd Edition
Occupant Load• 2 guests per single guest room
• 4 guests per double guest room
• 4 guests per suite
• 2 guests per accessible guest room
• 15 sqft per person for 2nd Floor conference room
Minimum Required Safe Egress Times• Scenario 1 detection time
established based on flame detector response.
• Scenario 2 detection time based on quick response sprinkler activation (smoke detectors will activate more quickly).
• Total evacuation time includes time to reach exit stairs. Occupants will be out of the atrium sooner.
Time Element (sec)
Design Fire Scenario 1
Design Fire Scenario 2
Ignition 0 0Detection 20 50Fire Alarm Processing 10 10
Occupant Delay 240 240
Occupant Movement 140 140
MinimumEvacuation 410 440
Safety Factor 1.5 1.5Total Evacuation 615 660
Design Fire Scenario 1Temperature Elevation
at 615 secondsTemperature Floor 9
at 615 secondsElevator Lobby
Access Stair
Egress Balconies
Design Fire Scenario 1Carbon Monoxide
Elevation at 615 seconds
Design Fire Scenario 1Visibility Floor 9at 615 seconds
Visibility Floor 8at 615 seconds
Elevator Lobby
Access Stair
Egress Balconies
Design Fire Scenario 1Visibility Floor 2 – 7
at 615 secondsElevator Lobby
Access Stair
Egress Balconies
Design Fire Scenario 1Results
• None of the tenability thresholds was exceeded in the means of egress during the required safe egress time of 615 seconds (10.25 minutes).
• A sensitivity analysis, including winter and summer scenarios, indicating no significant differences in performance.
Design Fire Scenario 2Temperature Elevation
at 660 secondsTemperature Floor 9
at 660 secondsElevator Lobby
Access Stair
Egress Balconies
Design Fire Scenario 2Carbon Monoxide
Elevation at 660 seconds
Design Fire Scenario 2Visibility Floor 9at 660 seconds
Elevator Lobby
Access Stair
Egress Balconies
23 feet to atrium exit
Design Fire Scenario 2Visibility Floor 8at 660 seconds
Elevator Lobby
Access Stair
Egress Balconies
Design Fire Scenario 2Visibility Floors 2 – 7
at 660 seconds
Elevator Lobby
Access Stair
Egress Balconies
Design Fire Scenario 2Results
• The tenability thresholds for temperature and carbon monoxide concentration were not exceeded in the means of egress during the required safe egress time of 660 seconds (11 minutes).
• The visibility threshold was exceeded on the 9th and 8th Floors, where additional exit signage will be provided along the egress balcony.
Design Fire Scenario 2Results
• The visibility threshold at the access stair / elevator lobby is exceeded as they are within the atrium.– Automatic smoke curtains will be provided with signage;– Automatic smoke curtains are within the visibility distance
available at the end of 660 seconds (11 min);– Time to egress from this area will be less than 30 seconds.
• A sensitivity analysis, including winter and summer scenarios, indicating no significant differences in performance.
SummaryTenability Parameter
Performance Criteria
Design Fire Scenario 1
Design Fire Scenario 2
Visibility 33 ft (10 m) PassPass
w/additional signage
Occupant Exposure
Temperature140oF (60oC) Pass Pass
Carbon Monoxide
Concentration1000 ppm Pass Pass
Thank You!Presentation of a Case Study
EGRESS AND SMOKE MOVEMENT MODELING AT
5 BEEKMAN STREET
for theNew Jersey Chapter
Society of Fire Protection Engineers
September 9, 2013