presented by thant zin win department of mechanical engineering technological university (kyaukse)...
TRANSCRIPT
Presented by
THANT ZIN WIN
Department of Mechanical EngineeringTechnological University (Kyaukse)
Mandalay Division, Myanmar
2
Presentation Outlines
1. Introduction2. Operating Principle of Coreless Induction Furnace3. Important Role of Water Cooling4. Types of Water Cooling System5. Layout Description6. Design Parameters of Cooling Pond7. Pond Design Model Consideration8. Equilibrium Temperature and Surface Heat Flux9. Pond Design Calculation10. Case Study11. Cooling Pond Performance12. Conclusion13. Further Suggestions
3
Introduction
Core Type Coreless Type
Fig 1 – Core and Coreless Type of Induction Furnace
Electric Induction Furnace
4
Operating Principle of Coreless Induction Furnace
Electromagnetic induction Connect to a source of AC Create thermal energy Melt the charge Stirring action caused by molten metal
Fig 2 - Simplified Cross Section of Coreless Induction Furnace
5
Important Role of Water Cooling
Fig 3 - A Sample Induction Coil with Cooling Water
Water is vital to be success. Need high water quality. Flow velocity of all water
circuit should be monitored.
Cooling water supply temperature should not be below 25°C.
Upper limit of leaving the coil should be no more than 70°C.
If too cold water is allowed, condensation may be formed.
Fig 4 - Sample of the Damaging Induction Coil
6
Types of Water Cooling System
The types of water cooling system are as follow: Cooling Pond System Spray Pond System Evaporative Cooling Tower – Open-circuit System Fan-radiator Closed-circuit System Water/water Heat Exchanger Dual System Dual System with Closed-circuit Cooling Tower
7
Cooling Pond System
Fig 5 – Sketch of Typical Cooling Pond System
Large ground area Small investment
Hot water inlet Cool water outlet
Water surface
Pond
Process Description
24.33 ft3/min Cool water inlet
Pumps
Hot water outlet
Control panel
Capacitor bank
Furnace 2
Furnace 1
Cooling pond(8,000 ft3)
Fig 6 – Schematic Diagram of Cooling Pond Model
8
Layout Description of 0.16 ton Coreless Induction Furnace
Fig 7 - Functional Layout of 0.16 ton Coreless Induction Furnace
Pump
Discharge Pipeline
Suction Pipeline
Capacitor Bank
Furnace No. 1
Cooling Pond
Control Panel
Furnace No. 2
9
Design Parameters of Cooling Pond
The hot water or inlet temperature into the pond The cool water or outlet temperature from the pond The operating time occupied in melting The solar heat flux or solar energy identified as the
main heating mechanisms The pond volume and size corresponding to the
equilibrium temperature
10
Pond Design Model Consideration
HcQTRTcTVcdt
di ˆˆ)ˆ(
Fig 8 - Illustrative Diagram of Cooling Pond Model
V = volumeT = temperatureA = area
Induction Furnaces
Cooling Pond
V, T
Q, T Ti, R
H
Interchange with Atmosphere
Q =
Out
flow
rat
e
R =
inflo
w r
ate
TE
Tb
Ta
Td
Ts
W
11
Equilibrium Temperature and Surface Heat Flux
Windspeed
sc
s
a
ar
br e c
Ground
Subsurfaceconduction
Hot waterinlet
Cool wateroutlet
srR, ToQ, Ti Tsw
W2
Ta
Td
TE
sn anTb
T
Sun
)255.0)((23
1600]255.0)[(
Wf
TTWfT adscE
Fig 9 – Heat Transfer Mechanisms in Cooling Pond
12
Pond Design CalculationKnown Data◙ Relative humidity, RH = 62%◙ Ambient air, Ta = 88ºF◙ Dew point, Td = 72ºF◙ Hot water, Ti = 91.4ºF◙ Cold water, To = 82.4ºF◙ Latitude of Yangon, = 16.45 N◙ Wind speed, W = 4 mph◙ Flow rate, Q = 24.37 ft3/min
Assumptions◙ Steady-state (Completely mixed Pond)◙ Inflow rate is equal to outflow rate◙ Ts = T (Completely well-mixed pond)◙ No seepage into or from groundwater◙ Neglect heat conduction between the surrounding soil◙ Heat exchange occurs near the pond surface only◙ Volume, V = constant◙ Density, ρ = constant◙ At time t = 0, T = 28ºC
)Tk(kk.k.dt
dTTrTr 5962491 where,
kr = water retention ratekT = thermal rate
ftftftftV 62050 6000 3 210002050 ftftftA
Pond volume
Pond surface area
13
Case StudyData for the Example
Parameter Specified Value
Capacity 0.16 ton
Current frequency 1,000 Hz
Metal overheating temperature 2.912°F
Consumed power 16 kW
Dry bulb temperature 88°F
Relative humidity 62%
Wind speed 4 mph
Entering water temperature 82.4°F
Leaving water temperature 91.4°F
Latitude of Yangon 16.45 N
14
Cooling Pond Performance
0
1
2
3
4
5
6
7
8
7000 8000 9000 10000 11000
Pond Area (ft2)
(Fixed on 8 ft depth)
All
owab
le O
pera
ting
Tim
e (h
r)
The results corroborate the fact that the most important variable oncooling pond performance is pond surface area itself, but not is volume.
15
Conclusion Cooling system is the important part of coreless
induction furnace.
Cooling ponds are one of the economically competitive alternatives for removing of heat from induction furnaces.
The most important influence factor on the cooling pond configurations is pond surface area.
16
Further Suggestions
◙ Extending the baffles in the pond.
◙ Using the heat exchangers.
Highly baffled pond, longitudinal baffles, rectangular dischargeHighly baffled pond, lateral baffles, rectangular discharge
18
Spray Pond System
Fig - Sample Spray Pond System Use a number of nozzles Depend on relative humidity
19
Fan-radiator Closed-circuit System
Fig - Fan-radiator (closed-circuit) System
Completely enclosed Loss of water is slight
20
Water/water Heat Exchanger Dual System
Fig - Dual System with Water/water Heat Exchanger More compact Easier to clean and maintain
21
Dual System with Closed-circuit Cooling Tower
Fig - Dual System with Closed-circuit Cooling Tower
Slightly more expensive Lower Piping and pumping costs
23
By using the following equations, 25.04.824.91
4.8265.84
o
v
T
T
)3.0( IPThe type of pond is shallow
51.10)74264(365
360sin45.23
rads 5159.185.86)51.10tan45.16tan(cos 1
hrSo 58.1185.8615
2
)/( 62.34233 ))85.86sin()51.10cos()45.16cos()51.10sin()45.16sin(52.1(
75365
360cos033.015141
24
2daymkJ
osc
Declination angle,
The hour angle,
Maximum possible sunshine duration,
The extraterrestrial solar radiation ,
Ref: Magal, B. S. (1999), Solar Power Engineering, Fourth reprint, TATA McGraw Hill Publishing Company Limited, Bombay.
Cooling Pond Area and Volume Calculation
24
) /( 62.2034)/( 25.23106 9.11
5.962.018.0
62.3423322 ftdayBtudaymkJsc
sc
FTE59.625917.62
) /( 1060 2ftdayBtue
) /( 73 2ftdayBtuc
) /( 18215100
1217 2ftdayBtusn
) /( 50815100
3386 2ftdayBtuan
) /( 3519 2ftdayBtubr
) /( 38167310603519508182 2ftdayBtun
Clear sky solar radiation,
Equilibrium temperature by using the iterative method,
The net heat flux,
25
) /( 173)59.6265.84(
3816 2 FftdayBtuK
6876.059.624.91
59.624.82
iT
rTi
1
1
4543.0 1
16876.0
rr
Qc
KAr
ˆ
2 5768 )37.24003.14.62(
)1440/173(4543.0
ftA
A
The net heat exchange coefficient,
Normalized intake temperature,
Pond cooling capacity,
Required cooling pond area,
26
ftftftftV 62049 5768 3
By implementing to unit depth, the volume of cooling pond is
ftftftft 62050 6000 3 Approximately, the volume is used in the construction.
210002050 ftftftA
)Tk(k62.59k91.4kdt
dTTrTr
From the above volume and area, the relationship between the temperature and operating time is obtained as follows:
Where, kr = water retention rate kT = thermal rate
27
Solar Heat Flux
cebransnn
sc
s
a ar
e c
sn an
br
srCloud
Sun
Water surface
Fig – Components of Surface Heat Transfer
where, n = the net heat flux into the water surfacesn = the net solar (short-wave) radiation into the water surface an = the net atmospheric (long-wave) radiation from the water surface br = the back (long-wave) radiation from the water surface e = the evaporative heat flux from the water surface c = the conductive heat flux from the water surface s = the solar radiation at water surfacesr = the reflected solar radiationa = the atmospheric (long-wave) radiation ar = the reflected atmospheric radiation