preset counter with rate indicator rct2053.imimg.com/data3/jc/id/my-6251142/counter.pdf3.6 to 9999...

2
Voltage output 0~10 V / user specified Load for voltage output >10 Kohms Mutual Isolation between Input/Output/Supply 1 KV AC/1 Minute Modes Latched ON, OFF at SP Latched OFF, ON at SP Time Pulse Repeat Auto reset Relay time 0.1 to 99.9 seconds Setpoint Programmable from 0 to 999999 Setpoint 2 can be assigned to counter or batch Lower display parameter Rate, batch, totaliser or setpoint1 as selected by the user n Scale factor b.no x 10 Base no (b.no) 0.00001 to 999999 Exponent (n) -5 to 2 Reset Front panel reset or remote reset Rate unit * PPS (hz) / RPS, PPM / RPM, PPH / RPH Minimum rate * 0.001 to 2 PPS (hz) / RPS, 0.06 to 120 PPM / RPM, 3.6 to 7200 PPH / RPH * (PPS/PPM/PPH = pulses per second / minute / hour) Resolution 1/0.1/0.01/0.001 Setpoint, Program, ON/OFF Reset lock Keyboard Tactile, 3 keys Enclosure construction Plug-in (circuit removable without affecting terminal wiring) Dimensions (in mm) 48(H) x 96(W) x 100(D) Mounting Panel mount Panel cutout 44 x 92 mm Supply voltage 85~265 V AC, 50/60 Hz o Operating ambient 0~50 C temperature Relative humidity Below 90%, non condensing PROGRAMMABLE PARAMETERS OTHER PRESET COUNTER WITH RATE INDICATOR CAT#333R1/P1/2/310311/A RCT205 SPECIFICATIONS All specifications at ambient of 25 ° C, unless specified otherwise INPUTS INDICATION MEMORY OUTPUTS Input 1 Input 2 Input types +12 V DC provided) d) Voltage pulses (5~30 V DC) Maximum input frequency 5 Khz Range limits Rate * (for scale factor = 1) 0.001 to 5000 PPS/RPS 0.06 to 9999 PPM/RPM 3.6 to 9999 PPH/RPH Count/Totaliser 0.000 to 999999 Batch 0 to 999999 Accuracy Rate : ± 0.05% of reading, ± 2 counts typical Count/Totaliser/Batch : Absolute Counting modes Up (incrementing) Down (decrementing) Bi-directional Quadrature Control inputs Gate & reset Upper display 6 Lower display 6 Displayed Parameters Upper display Counter Lower display Rate, batch, totaliser or setpoint1 as selected by the user Non volatile, indefinite retention No. of relays 0, 2 Relay contact type NO-C-NC (RLY1) NO-C-NC (RLY2) Relay contact rating 5A / 230V AC, resistive No. of analog outputs 1 (current or voltage) Current output 4~20 mA / 0~20 mA / 20~4 mA / 20~0 mA isolated from input Maximum load for current 500 ohms output Count 1 input Count 2 input (Direction) a) Proximity switch, photo electric switch ( b) Limit switch, microswitch, etc. (potential free contact closure) c) Electromagnetic pickup : (Optional : 2-wire) 3-wire digit, 7 segment 0.3” red LED display digit, 7 segment 0.3” green LED display 0.000-999999 count range with absolute accuracy, 0.06 - 9999 RPM with ultra accuracy of 0.05% of reading Upto 2 user programmable relays depending on count Programmable setpoints, scale factor and relay modes Application : Event counter, Totaliser, Batch counter, RPH, RPM, RPS, Meters/Minute, Mains Frequency, Zero-speed switch, etc. Measures upto 5 Khz Isolated, programmable, 4~20 mA retransmission output Inputs : Proximity switch, voltage pulses, Limit switch, electromagnetic pickup, etc. Counting modes : Up, down, bi-directional, quadrature www.radix.co.in/rct.htm

Upload: phungkien

Post on 29-May-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PRESET COUNTER WITH RATE INDICATOR RCT2053.imimg.com/data3/JC/ID/MY-6251142/counter.pdf3.6 to 9999 PPH/RPH Count/Totaliser 0.000 to 999999 Batch ... Bi-directional Quadrature ... Y2

Voltage output 0~10 V / user specifiedLoad for voltage output >10 KohmsMutual Isolation betweenInput/Output/Supply 1 KV AC/1 Minute

Modes Latched ON, OFF at SPLatched OFF, ON at SPTime Pulse Repeat Auto reset

Relay time 0.1 to 99.9 secondsSetpoint Programmable from 0 to 999999

Setpoint 2 can be assigned to counter or batch

Lower display parameter Rate, batch, totaliser or setpoint1as selected by the user

nScale factor b.no x 10 Base no (b.no) 0.00001 to 999999 Exponent (n) -5 to 2Reset Front panel reset or remote resetRate unit * PPS (hz) / RPS,

PPM / RPM, PPH / RPH

Minimum rate * 0.001 to 2 PPS (hz) / RPS, 0.06 to 120 PPM / RPM, 3.6 to 7200 PPH / RPH* (PPS/PPM/PPH = pulses per second / minute / hour)

Resolution 1/0.1/0.01/0.001Setpoint, Program, ON/OFF

Reset lock

Keyboard Tactile, 3 keysEnclosure construction Plug-in (circuit removable without

affecting terminal wiring)Dimensions (in mm) 48(H) x 96(W) x 100(D)Mounting Panel mountPanel cutout 44 x 92 mmSupply voltage 85~265 V AC, 50/60 Hz

oOperating ambient 0~50 C temperature

Relative humidity Below 90%, non condensing

PROGRAMMABLE PARAMETERS

OTHER

PRESET COUNTER WITH RATE INDICATOR

CA

T#

33

3R

1/P

1/2

/31

03

11/A

RCT205

SPECIFICATIONS All specifications at ambient of 25 °C, unless specified otherwise

INPUTS

INDICATION

MEMORY

OUTPUTS

Input 1 Input 2 Input types

+12 V DC provided)

d) Voltage pulses (5~30 V DC)Maximum input frequency 5 KhzRange limits Rate * (for scale factor = 1) 0.001 to 5000 PPS/RPS

0.06 to 9999 PPM/RPM3.6 to 9999 PPH/RPHCount/Totaliser 0.000 to 999999Batch 0 to 999999

Accuracy Rate : ± 0.05% of reading, ± 2 counts typical

Count/Totaliser/Batch : AbsoluteCounting modes Up (incrementing)

Down (decrementing)Bi-directionalQuadrature

Control inputs Gate & reset

Upper display 6

Lower display 6

Displayed ParametersUpper display CounterLower display Rate, batch, totaliser or

setpoint1 as selected by the user

Non volatile, indefinite retention

No. of relays 0, 2Relay contact type NO-C-NC (RLY1)

NO-C-NC (RLY2) Relay contact rating 5A / 230V AC, resistiveNo. of analog outputs 1 (current or voltage)Current output 4~20 mA / 0~20 mA / 20~4 mA /

20~0 mA isolated from input Maximum load for current 500 ohms output

Count 1 inputCount 2 input (Direction)a) Proximity switch, photo electric switch (b) Limit switch, microswitch, etc. (potential free contact closure)c) Electromagnetic pickup : (Optional : 2-wire)

3-wire

digit, 7 segment 0.3” red LED display

digit, 7 segment 0.3” green LED display

·

·

·

·

·

·

·

·

0.000-999999 count range with absolute accuracy, 0.06 - 9999 RPM with ultra accuracy of 0.05% ofreading

Upto 2 user programmable relays depending on count

Programmable setpoints, scale factor and relay modes

Application : Event counter, Totaliser, Batch counter, RPH, RPM, RPS, Meters/Minute, Mains Frequency, Zero-speed switch, etc.

Measures upto 5 Khz

Isolated, programmable, 4~20 mA retransmission output

Inputs : Proximity switch, voltage pulses, Limit switch, electromagnetic pickup, etc.

Counting modes :

Up, down, bi-directional, quadrature

www.radix.co.in/rct.htm

Page 2: PRESET COUNTER WITH RATE INDICATOR RCT2053.imimg.com/data3/JC/ID/MY-6251142/counter.pdf3.6 to 9999 PPH/RPH Count/Totaliser 0.000 to 999999 Batch ... Bi-directional Quadrature ... Y2

CA

T#

33

3R

1/P

2/2

/31

03

11/A

ORDERING INFORMATIONCONNECTION DIAGRAM

PRESET COUNTER WITH RATE INDICATOR RCT205

STK-254

1 2 3 4 5 6 7 8 9 10

11 12 13 14 15 16 17 18 19 20

85~265V AC/DC VS

V+ CNT1 GND

f <5hz

CNT2/ DIR RESET GATE

+

V/Iout*

RLY1* RLY2*

NCCNO NCCNO

11 12 13

PROX SW

BRN BLU

BLK12 13

+

5-30 V DC

11 16 13 16 13

LIMIT SW

11 12

11 16

17

18

13

13

CNT 1

CNT 2 / DIR

RESET

GATE

SHORT

- OPTIONAL*

Product url : www.radix.co.in/rct.htm

OTHER PRODUCTS

PRESET COUNTER · RCT403

72x72x100

PROGRAMMABLE RPM/RATE INDICATOR

48x96x100 RCT202

PRESET COUNTER · RCT401

72x72x100

PRESET COUNTER · RCT404

72x72x100

RPM/RATE INDICATOR WITH ALARMS · RCT206

48x96x100 · 2 RELAY & ANALOG OUTPUT

RPM/RATE INDICATOR, TOTALISER · RCT203

48x96x100

1800-22-72341800-22-radix

SALES INQUIRIES

www.radix.co.inRadix Electrosystems Pvt Ltd, B-14, 2nd Floor, Ghanshyam Indl Estate, Veera Desai Road, Andheri (West), Mumbai - 400 053, IndiaTel : + 91 22 26730101 · Fax : + 91 22 26731891 · Email : [email protected] · www.radix.co.in

AN ISO 9001:2008 COMPANY

INSTRUMENTS T : + 91 22 26730101 x 701 F : + 91 22 26731891 E : [email protected]

SENSORS T : + 91 22 26731826 x 732 F : + 91 22 66910029 E : [email protected]

GAUGES T : + 91 22 26731826 x 733 F : + 91 22 66910029 E : [email protected]

AUTOMATION C : 0-9322405471 C : E : [email protected]

Configuration

01

00

Relay 4~20 mA output

2 1

2 0

A

A2231

Option

Analog output

Electromagnetic pickup1.

2.

Details

0~10 V DC