Copyright 1994 Carrier Corporation Form 38CKB-1PD ® Product Data 38CKB(N) (60 Hz) Air Conditioner 38CKB Sizes 018 thru 060 38CKN Sizes 024 thru 048 Model 38CKB(N) Energy-Efficient Air Conditioner incorporates innovative technology to provide reliable summer cooling performance. Built into these units are the features most desired by homeowners today, including SEER ratings of up to 12.0 when used with components designated by manufacturer. All models are listed with UL, c-UL, ARI, and CEC. FEATURES/BENEFITS Electrical Range — All units are offered in 208–230v single phase. Three-phase units are available from 030 through 060 sizes in 208/230v and from 036 through 060 sizes in 460v. Wide Range of Sizes — The 38CKB is available in 7 nominal sizes from 018 through 060 to meet the needs for residential and light commercial applications. The 38CKN is available in 5 nominal sizes from 024 through 048 to meet the needs of the manufactured housing market. Weather Armor II Cabinet — The steel is protected with a heavy coating commonly called ‘‘galvanizing,’’ and treated with a layer of zinc phosphate. A modified polyester powder coating is then applied and baked on, providing each unit with a hard, smooth finish that will last for many years. All screws on cabinet exterior are coated for a long-lasting, rust-resistant, quality appearance. Totally Enclosed Fan Motor Means greater reliability under rain conditions and dependable performance for many years. Permanent-split-capacitor-type Thi d t td ith F Mk 404

Upload: duongnhi

Post on 11-Feb-2018

218 views

Category:

Documents


5 download

TRANSCRIPT

Page 1: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

Copyright 1994 Carrier Corporation Form 38CKB-1PD

HEATING & COOLING

®

ProductData

38CKB(N) (60 Hz)Air Conditioner

38CKB Sizes 018 thru 06038CKN Sizes 024 thru 048

Model 38CKB(N) Energy-Efficient Air Conditioner incorporates innovative technology to provide reliable summer cooling performance. Built into these units are the features most desired by homeowners today, including SEER ratings of up to 12.0 when used with components designated by manufacturer. All models are listed with UL, c-UL, ARI, and CEC.

FEATURES/BENEFITS

Electrical Range

— All units are offered in 208–230v single phase. Three-phase units are available from 030 through 060 sizes in 208/230v and from 036 through 060 sizes in 460v.

Wide Range of Sizes

— The 38CKB is available in 7 nominal sizes from 018 through 060 to meet the needs for residential and light commercial applications. The 38CKN is available in 5 nominal sizes from 024 through 048 to meet the needs of the manufactured housing market.

Weather Armor II Cabinet

— The steel is protected with a heavy coating commonly called ‘‘galvanizing,’’ and treated with a layer of zinc phosphate. A modified polyester powder coating is then applied and baked on, providing each unit with a hard, smooth finish that will last for many years.

All screws on cabinet exterior are coated for a long-lasting, rust-resistant, quality appearance.

Totally Enclosed Fan Motor

— Means greater reliability under rain conditions and dependable performance for many years. Permanent-split-capacitor-type

Thi d t t d ith F M k 4 0 4

Page 2: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

2

motors provide more economical operation.

Unit Design

— Copper tube, enhanced sine wave aluminum fin coil is designed for optimum heat transfer. Vertical air discharge carries sound and hot condenser air up and away from adjacent patio areas and foliage. Heat pump style drain pan allows for easy removal of water, dirt and leaves.

Application Versatility

— The unit can be combined with a wide variety of evaporator coils and blower packages

to provide quiet, dependable comfort. Unit can be installed on a roof or at ground level.

External Service Valves

— Both service valves are brass, front seating type. The 38CKB has sweat field connections. The 38CKN has mechanical field connections. Valves are externally located so refrigerant tube connections can be made quickly and easily. Each valve has a service port for ease of checking operating refrigerant pressures.

Easy Serviceability

— One access panel provides access to electrical control box. Removal of top allows access to fan motor and coil.

Compressor Protection

— Each compressor is protected with internal temperature- and current-sensitive overloads.

Warranty

— Standard 1 year on parts, with an additional 4 years on compressor.

CERTIFICATION APPLIES ONLY WHENTHE COMPLETE SYSTEM IS LISTED WITH ARI.

The data in this publication is displayed for all series, however, every series may not be available from manufacturer.

Physical data

NOTE:

See unit Installation Instructions for proper installation.* Tube sizes are for runs up to 50 ft. For tube set over 50 ft, consult Long-Line Application Guideline.

UNIT SIZE 018-31 024-30/31 030-30, 50/

31, 51036-30, 50, 60/31/32, 52, 62

042-30, 50/31, 51, 61

048-30, 50, 60/31, 51, 61

060-30, 50, 60/31, 51, 61

OPERATING WT (LB)

COMPRESSOR Manufacturer & Type

Tec & Recip

Copeland & Recip/

Tec & Recip

Copeland & Recip/

Tec & Recip

Millennium & Scroll/Copeland & Recip/

Tec & Recip

Millennium & Scroll/Copeland &

Recip

Millennium & Scroll/Copeland &

Scroll

Millennium & Scroll/Copeland &

Scroll

REFRIGERANTControlCharge (LB) @ 15 ft

22AccuRater

(Bypass Type)3.44 3.76/3.82 4.19/4.46 4.63/5.00/4.78 5.00/5.13

6.63/6.38

9.89/8.46

COND FANAir DischargeAir Qty (CFM)

Propeller Type, Direct DriveVertical

1400 1550 2000/1700 2500 3400

COND COILFace Area (SQ FT)

Copper Tube, Aluminum Plate Fin5.6 6.3/6.9 6.9/7.4 9.0/9.0/8.2 10.7

14.8

19.8/16.1

VALVE CONNECT. (IN. ID)VaporLiquid

Sweat5/8 3/4 7/8

3/8

REFRIG TUBES* (IN. OD)VaporLiquid

5/8 3/4 7/8 1-1/8

3/8

®

AN

INDEPENDENT LABORATO

RY

TE

STINGFOR PUBLIC

SAFETY

MA

NU

FAC

TUR

ER

CERTIFIED TO ARI AS COMPLY

ING

WITH

ARI STANDARD 210

UN

ITAR

Y

AIR CONDITIO

NIN

G

EQUIPMENT

MA

NU

FA

CTU

RER

CERTIFIED TO ARI AS COMPLY

ING

WIT

H

ARI STANDARD 270

SO

UN

DR

ATING OF OUTDO

OR

UNITARY EQUIPMENT®

Model number nomenclature38CKB(N) 018

Electric Air Conditioner

Nominal Capacity018 — 18,000 Btuh 042 — 42,000 Btuh024 — 24,000 Btuh 048 — 48,000 Btuh030 — 30,000 Btuh 060 — 60,000 Btuh036 — 36,000 Btuh

3 0 1

PackagingSeries

Electrical3 — 208-230-15 — 208/230-36 — 460-3

Page 3: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

3

Accessories

* Start assist capacitor and relay required when using liquid solenoid valve or hard shut-off TXV (except 036 and 060, Series 30; and all 3-phase units). Do not use hard shut-off TXV with liquid solenoid valve.

N/A — Not Applicable

PART NO. DESCRIPTION

KSAHS0301AAA

Start Assist–Capacitor/Relay — Sizes 018–030 (31); 036 (32)

KSAHS0601AAA

Start Assist–Capacitor/Relay — Sizes 024, 030 (30); 036 (31)

KSAHS0701AAA

Start Assist–Capacitor/Relay — Size 042 (31)

N/A

Start Assist–Capacitor/Relay — Sizes 036, 042 (30); 048, 060 (30, 31); All 3 Phase

KAACS0201PTC

Start Assist–PTC — All 1 Phase except Size 036 (30)

Standard

Start Assist–PTC — Size 036 (30)

N/A

Start Assist–PTC — All 3 Phase

KAALS0101LLS*

Liquid Solenoid Valve

KSACY0101AAA

Cycle Protector — Sizes 018–030; 036 (31, 32, 52, 62); 042 (31, 51, 61)

Standard

Cycle Protector — Sizes 036 (30, 50, 60); 042 (30, 50); 048, 060; All Series

KAAWS0101AAA

Winter Start Control

KAAFT0101AAA

Evaporator Freeze Thermostat

KSAHI0101HPS

High-Pressure Switch

KAALP0101LPS

Low-Pressure Switch

KAATD0101TDR

Time-Delay Relay

KAACF0601SML

Coastal Filter — Sizes 018, 024

KAACF0401MED

Coastal Filter — Sizes 030–042

KAACF0501LRG

Coastal Filter — Sizes 048, 060

KAACH1001AAA

Crankcase Heater — Sizes 018–030; 036 (31, 32, 52); 042 (31, 51)

KAACH1101AAA

Crankcase Heater — Sizes 036 (62); 042 (61)

KAACH1201AAA

Crankcase Heater — Sizes 036, 042 (30, 50); 048, 060 (30, 31, 50, 51)

KAACH1301AAA

Crankcase Heater — Sizes 036, 042 (60); 048, 060 (60, 61)

KSASH1301TEC

Sound Hood — Size 030 (31, 51 Series)

KSASH2101COP

Sound Hood — Sizes 048, 060 (31, 51, 61)

KSASH1901CYL

Sound Hood — Sizes 036 (30, 50, 60); 042 (30, 50)

KSASH2001CYL

Sound Hood — Sizes 048, 060 (30, 50, 60)

KSASH1201COP

Sound Hood — Sizes 036 (31); 042 (31, 51)

N/A

Sound Hood — Sizes 018, 024; 030 (30, 50); 036 (32, 52, 62)

KAATX0201RPB

Thermostatic Expansion Valve (RPB) — Size 018

KAATX0301RPB

Thermostatic Expansion Valve (RPB) — Size 024

KAATX0401RPB

Thermostatic Expansion Valve (RPB) — Size 030

KAATX0501RPB

Thermostatic Expansion Valve (RPB) — Sizes 036, 042

KAATX0601RPB

Thermostatic Expansion Valve (RPB) — Size 048

KAATX0701RPB

Thermostatic Expansion Valve (RPB) — Size 060

KAATX0901HSO*

Thermostatic Expansion Valve (Hard Shut-off) — Size 018

KAATX1001HSO*

Thermostatic Expansion Valve (Hard Shut-off) — Size 024

KAATX1101HSO*

Thermostatic Expansion Valve (Hard Shut-off) — Size 030

KAATX1201HSO*

Thermostatic Expansion Valve (Hard Shut-off) — Sizes 036, 042

KAATX1301HSO*

Thermostatic Expansion Valve (Hard Shut-off) — Size 048

KAATX1401HSO*

Thermostatic Expansion Valve (Hard Shut-off) — Size 060

P251-0083 (RCD)

Low-Ambient Controller

THERMOSTAT PKG. DESCRIPTION

TSTATCCNAC01

Thermostat, Auto Changeover, Non-Programmable,

°

F/

°

C, 1-Stage Heat, 1-Stage Cool

TSTATCCPAC01

Thermostat, Auto Changeover, 7-Day Programmable,

°

F/

°

C, 1-Stage Heat, 1-Stage Cool

--HH--07AT-213

Thermostat, Manual Changeover, Non-Programmable,

°

F, 1-Stage Heat, 1-Stage Cool

TSTATCCSEN01

Outdoor Sensor

Page 4: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

4

Accessory Description and Usage

1.

Compressor Start Assist-Capacitor/Relay Type

Start capacitor and start relay gives ‘‘hard’’ boost to compressor motor at each start-up. SUGGESTED USE: Installations where interconnecting tube length exceeds 50 ft.

Installations where outdoor design temperature exceeds 105˚F (40.6˚C).Replacement installations with hard shut-off expansion valve on indoor coil.

2.

Compressor Start Assist-PTC Type

Solid-state electrical device which gives a ‘‘soft’’ boost to the compressor at each start-up. SUGGESTED USE: Installations with marginal power supply.

Replacement installations with rapid pressure balance (RPB) expansion valve on indoor coil.

3.

Liquid Solenoid Valve (LSV)

An electrically operated shut-off valve to be installed at the outdoor or indoor unit (depending on tubing configuration) which stops and starts refrigerant liquid flow in response to compressor operation. Maintains a column of refrigerant liquid ready for action at next compressor operation cycle. Note: Compressor start assist–capacitor/relay type (Item 1) must also be used.

SUGGESTED USE: For improved system performance in air conditioners for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.) In certain long-line applications. (Refer to Long-Line Application Guideline).

4.

Cycle Protector

Solid-state timing device which prevents compressor rapid recycling. Control provides an approximate 5-minute delay after power to the compressor has been interrupted for any reason, including normal room thermostat cycling.

SUGGESTED USE: Installations in areas where power interruptions are frequent.Where user is likely to ‘‘play’’ with the room thermostat.All commercial installations.Installations where interconnecting tube length exceeds 50 ft.High-rise applications.

5.

Winter Start Control

A SPST delay relay which bypasses the low-pressure switch for approximately 3 minutes to permit start-up for cooling operation under low-load conditions.

SUGGESTED USE: All air conditioners where low-ambient controller has been added.

6.

Evaporator Freeze Thermostat

A SPST temperature actuated switch which stops unit operation when evaporator reaches freeze-up conditions. SUGGESTED USE: All units where winter start control (Item 5) has been added.

7.

High-Pressure Switch

Auto reset SPST switch activated by refrigerant pressure on high side of refrigerant circuit. Cycles compressor off if refrigerant pressure rises to about 425 psig. Provides protection against compressor damage due to loss of outdoor airflow. To prevent rapid compressor recycling, cycle protector (Item 4) can be used with this switch.

SUGGESTED USE: Installations exposed to very ‘‘dirty’’ outdoor air.Installations where condenser inlet air temperature exceeds 125˚F (51.7˚C).

8.

Low-Pressure Switch

Auto reset SPST switch activated by refrigerant pressure on low side of refrigerant circuit. Cycles compressor off if refrigerant pressure drops to about 27 psig. Prevents indoor coil freeze-up due to loss of indoor airflow. Provides additional protection against compressor damage due to loss of refrigerant charge. To prevent rapid compressor recycling, cycle protector (Item 4) can be used with this switch.

SUGGESTED USE: Where indoor coil is exposed to ‘‘dirty’’ air.All commercial installations.

9.

Time-Delay Relay

A SPST delay relay which briefly continues operation of the indoor blower motor to provide additional cooling after the compressor cycles off.

SUGGESTED USE: For improved efficiency ratings for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.)

10.

Coastal Filter

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow. SUGGESTED USE: In geographic areas where salt damage could occur.

11.

Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart and minimizes chance of refrigerant slugging. May or may not include a thermostat control.

SUGGESTED USE: When interconnecting tube length exceeds 50 ft.When unit will be operated below 55˚F (12.8˚C) outdoor air temperature. (Use with low-ambient controller.)All commercial installations.

12.

Sound Blanket/Shield/Hood

Wraparound sound attenuation cover for the compressor. Reduces unit sound level by about 0.2 bels. SUGGESTED USE: Unit installed closer than 15 ft to quiet areas — bedrooms, etc.

Unit installed between 2 houses less than 10 ft apart.

13.

Thermostatic Expansion Valve (TXV)

A modulating flow-control valve which meters refrigerant liquid flow rate into the evaporator in response to the superheat of the refrigerant gas leaving the evaporator. Kit includes valve, adapter tubes, and external equalizer tube. Both hard shut-off and RPB valves are available.

SUGGESTED USE: For improved system performance in cooling mode for certain combinations of indoor and outdoor units. (Refer to ARI Unitary Directory.)

Page 5: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

5

Electrical data

* Permissible limits of the voltage range at which unit will operate satisfactorily. Operation outside these limits may result in unit failure.† Time-delay fuse.‡ Length shown is as measured 1 way along wire path between the unit and service panel for a voltage drop not to exceed 2%.** If wire is applied at ambient greater than 30˚C (86˚F), consult Table 310-16 of the NEC (ANSI/NFPA 70).

The ampacity of nonmetallic-sheathed cable (NM), trade name ROMEX, shall be that of 60˚C (140˚F) conductors, per the NEC (ANSI/NFPA 70) Article 336-26. If other than uncoated (non-plated), 60 or 75˚C (140 or 167˚F) insulation, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (ANSI/NFPA 70).

FLA — Full Load AmpsHACR — Heating, Air Conditioning, RefrigerationLRA — Locked Rotor AmpsMCA — Minimum Circuit AmpsRLA — Rated Load AmpsNOTES: 1. Control circuit is 24v on all units and requires external power source.

2. Copper wire must be used from service disconnect to unit.3. All motors/compressors contain internal overload protection.

UNITSIZE V/PH

OPER VOLTS* COMPRESSOR FANFLA MCA

MINWIRESIZE

60˚C/75˚C**

MAX LENGTH

(Ft)60˚C/75˚C‡

MAX FUSE† OR

HACR TYPE CKT BKR

AMPS

Max Min LRA RLA

018-31

208–230-1 253 197

49.0 8.0 0.8 10.8 14/14 70/65 15

024-30

56.0 10.7 0.9 14.3 14/14 50/50 20

024-31

61.0 10.9 0.9 14.5 14/14 55/50 20

030-30

75.0 14.2 0.8 18.6 14/14 40/40 25

030-31

71.0 12.9 0.8 16.9 14/14 45/40 25

036-30

95.0 16.7 1.4 22.3 12/12 55/50 30

036-31

86.0 14.8 1.4 19.9 12/12 55/55 30

036-32

86.0 15.7 1.4 21.0 12/12 55/55 30

042-30

115.0 20.5 1.4 27.0 10/10 70/70 40

042-31

102.0 19.7 1.4 26.0 10/10 75/70 40

048-30

140.0 24.4 1.4 31.9 8/10 95/55 50

048-31

129.0 23.7 1.4 31.0 8/10 100/60 50

060-30

165.0 28.9 1.4 37.5 8/8 80/75 60

060-31 169.0 28.8 1.4 37.4 8/8 80/75 60

030-50

208/230-3 253 187

68.0 9.4 0.8 12.6 14/14 70/65 15

030-51 64.5 8.3 0.8 11.2 14/14 80/75 15

036-50 75.0 10.6 1.4 14.7 14/14 60/55 20

036-52 64.5 10.1 1.4 14.0 14/14 60/60 20

042-50 90.0 12.4 1.4 16.9 14/14 50/50 25

042-51 91.0 13.6 1.4 18.4 14/14 45/45 25

048-50 105.0 14.1 1.4 19.0 14/14 54/51 25

048-51 99.0 13.5 1.4 18.3 14/14 45/45 25

060-50 125.0 16.0 1.4 21.4 12/12 48/46 30

060-51 123.0 17.3 1.4 23.0 12/12 65/60 35

036-60

460-3 506 414

37.5 5.3 0.8 7.4 14/14 240/230 15

036-62 35.0 4.8 0.8 6.8 14/14 265/250 15

042-61 42.0 6.2 0.8 8.6 14/14 210/200 15

048-60 52.5 7.1 0.8 9.7 14/14 227/216 15

048-61 49.5 7.4 0.8 10.1 14/14 185/175 15

060-60 66.5 8.0 0.8 10.8 14/14 165/157 15

060-61 62.0 9.0 0.8 12.1 14/14 165/157 15

Page 6: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

6

METERING DEVICE

* Piston listed is for any approved non-capillary tube coil combination. Piston is shipped with outdoor unit and must be installed in an approved indoor coil.

UNIT SIZEPISTON

IDENTIFICATION NO.

018-31 52

024-30, 31 57

030-30, 50 67

030-31, 51 65

036-30, 50, 60 73

036-31 70

036-32, 52, 62 70

042-30, 50 76

042-31, 51, 61 82

048-30, 50, 60 82

048-31, 51, 61 84

060-30, 50, 60 93

060-31, 51, 61 90

Page 7: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

7

Performance data

UNIT SIZE-SERIES

INDOORMODEL

TOT. CAP.BTUH

FACTORY-SUPPLIED ENHANCE-

MENT STANDARD

RATING

FIELD-SUPPLIEDACCESSORY† SOUND

RATING(BELS) TDR TXV

018-31

*CC5A/CD5A/CD5BA018CC5A/CD5A/CD5BA024CC5A/CD5A/CD5BW024

CD3(A,B)018CD3(A,B)A024

CE3AA024CF5AA024CG5AA024

F(A,B)4ANF018F(A,B)4ANF024

FC4BNF024FC4BNF033FD3ANA018FD3ANA024

FF1(A,B)NA018FF1(A,B)NA024

FG3AAA024FK4BNF001FK4BNF002FK4BNF004

17,20017,60017,60017,00017,60017,80017,80017,80316,80017,60017,60017,60017,10017,60017,20017,60017,50017,50017,50017,500

NONENONENONENONENONENONENONENONETDRTDR

TDR & TXVTDR & TXV

NONENONETDRTDR

NONETDR & TXVTDR & TXVTDR & TXV

—10.0010.00

—10.0010.0010.0010.0010.0010.5010.5010.50

——

10.5010.5010.0012.0012.0012.00

10.0010.5010.5010.2010.5010.5010.5010.50

————

10.0010.50

——

10.20———

10.0010.5010.5010.2010.5010.5010.5010.5010.0010.50

——

10.0010.5010.5010.5010.20

———

8.0

COILS + 58MVP040-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA018CC5A/CD5A/CD5BA024

CD3(A,B)A018CD3(A,B)A024

17,20017,60017,20017,600

NONENONENONENONE

11.0011.0011.0011.00

————

11.0011.0011.0011.00

8.0

COILS + 58MVP060-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA018CC5A/CD5A/CD5BA024

CD3(A,B)A018CD3(A,B)A024

17,20017,60017,20017,600

NONENONENONENONE

11.0011.0011.0011.00

————

11.0011.0011.0011.00

8.0

COILS + 58MVP080-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA018CC5A/CD5A/CD5BA024

CD3(A,B)A018CD3(A,B)A024

17,20017,60017,20017,600

NONENONENONENONE

11.0011.0011.0011.00

————

11.0011.0011.0011.00

8.0

024-30, 31

*CC5A/CD5A/CD5BA024CB5AA030

CC5A/CD5A/CD5BA030CC5A/CD5A/CD5BW024CC5A/CD5A/CD5BW030

CD3(A,B)A024CD3(A,B)A030

CD3CA024CE3AA024CE3AA030CF5AA024CG5AA024

F(A,B)4ANF024F(A,B)4ANF030

FC4BNF024FC4BNF033FC4BNF030FD3ANA024FD3ANA030

FF1(A,B)NA024FF1(A,B)NA030

FG3AAA024FK4BNB005FK4BNF001FK4BNF002FK4BNF003FK4BNF004

22,40022,00022,60022,40022,60022,40022,60022,60022,60023,00022,60022,60022,60023,00022,40023,40022,80022,20023,00022,60023,20022,00024,80023,60023,80023,60024,000

NONENONENONENONENONENONENONENONENONENONENONENONETDRTDR

TDR & TXVTDR & TXVTDR & TXV

NONENONETDRTDR

NONETDR & TXVTDR & TXVTDR & TXVTDR & TXVTDR & TXV

——————————

10.00—

10.0010.2010.2010.5010.50

——

10.0010.00

—12.0011.5011.5011.5011.50

10.0010.0010.0010.0010.0010.0010.0010.0010.0010.0010.2010.00

—————

10.2010.20

——

10.00—————

10.00—

10.0010.0010.0010.0010.0010.0010.0010.0010.2010.0010.0010.20

———

10.2010.2010.0010.0010.00

—————

8.0

COILS + 58MVP040-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA024CC5A/CD5A/CD5BA030CC5A/CD5A/CD5BW030

CD3(A,B)A024CD3(A,B)A030

22,40022,60022,60022,40022,600

NONENONENONENONENONE

10.5011.0011.0010.5011.00

—————

10.5011.0011.0010.5011.00

8.0

COILS + 58MVP060-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA024CC5A/CD5A/CD5BA030CC5A/CD5A/CD5BW030

CD3(A,B)A024CD3(A,B)A030

22,40022,60022,60022,40022,600

NONENONENONENONENONE

10.5011.0011.0010.5011.00

—————

10.5011.0011.0010.5011.00

8.0

See notes on pg. 11.

Page 8: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

8

Performance data continued

UNIT SIZE-SERIES

INDOORMODEL

TOT. CAP.BTUH

FACTORY-SUPPLIED ENHANCE-

MENT STANDARD

RATING

FIELD-SUPPLIEDACCESSORY† SOUND

RATING(BELS) TDR TXV

024-30, 31

COILS + 58MVP080-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA024CC5A/CD5A/CD5BA030CC5A/CD5A/CD5BW030

CD3(A,B)A024CD3(A,B)A030

22,40022,60022,60022,40022,600

NONENONENONENONENONE

10.5011.0011.0010.5011.00

—————

10.5011.0011.0010.5011.00

8.0

030-30, 31,50, 51

*CC5A/CD5A/CD5BA030CB5AA030CB5AW036

CC5A/CD5A/CD5BW030CC5A/CD5A/CD5BA036

CD5A/CD5BW036CD3(A,B)A030CD3(A,B)A036

CD3A030CE3AA030CE3AA036CF5AA036CG5AA036

F(A,B)4ANF030F(A,B)4ANF036

FC4BNF030FC4BNF036FC4BNF033FD3ANA030

FF1(A,B)NA030FG3AAA036FK4BNF001FK4BNF002FK4BNF003FK4BNF004

28,00027,60028,80028,00029,00029,00028,00029,00027,80027,80028,60028,80028,80027,60028,20027,60028,20029,00027,80028,00028,00029,00029,00029,00029,000

NONENONENONENONENONENONENONENONENONENONENONENONENONETDRTDR

TDR & TXVTDR & TXVTDR & TXV

NONETDR

NONETDR & TXVTDR & TXVTDR & TXVTDR & TXV

10.00—

10.0010.0010.0010.0010.0010.00

—10.0010.0010.0010.0010.0010.0010.0010.0010.10

—10.0010.0010.5010.5011.0011.00

10.1010.1010.1010.1010.1010.1010.1010.1010.0010.1010.1010.1010.10

—————

10.00—

10.10————

10.10——

10.1010.1010.1010.1010.1010.0010.1010.1010.1010.1010.0010.00

———

10.0010.0010.10

———

8.0

COILS + 58MVP040-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA030CC5A/CD5A/CD5BA036CC5A/CD5A/CD5BW030CC5A/CD5A/CD5BW036

CD3(A,B)A030CD3(A,B)A036

28,00029,00028,00029,00028,00029,000

NONENONENONENONENONENONE

10.5011.0010.5011.0010.5011.00

——————

10.5011.0010.5011.0010.5011.00

8.0

COILS + 58MVP060-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA030CC5A/CD5A/CD5BA036CC5A/CD5A/CD5BW030CC5A/CD5A/CD5BW036

CD3(A,B)A030CD3(A,B)A036

28,00029,00028,00029,00028,00029,000

NONENONENONENONENONENONE

10.5011.0010.5011.0010.5011.00

——————

10.5011.0010.5011.0010.5011.00

8.0

COILS + 58MVP080-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA030CC5A/CD5A/CD5BA036CC5A/CD5A/CD5BW030CC5A/CD5A/CD5BW036

CD3(A,B)A030CD3(A,B)A036

28,00029,00028,00029,00028,00029,000

NONENONENONENONENONENONE

10.5011.0010.5011.0010.5011.00

——————

10.5011.0010.5011.0010.5011.00

8.0

036-30, 31, 32,50, 52, 60, 62

*CC5A/CD5A/CD5BA036CB5AW036

CC5A/CD5A/CD5BA042CC5A/CD5A/CD5BW042

CD5A/CD5BW036CD3(A,B)A036CD3(A,B)A042

CD3CA036CE3AA036CE3AA042CF5AA036CG5AA036

F(A,B)4ANF036F(A,B)4AN(F,B)042FB4AN(A,M,F)042

FC4BNB054FC4BNF033FC4BNF036FC4BNF038

FC4BN(F,B)042FG3AAA036FK4BNB005FK4BNB006

34,00033,80034,00033,60034,00034,00034,00032,40033,60034,20033,80033,60033,20034,00034,00035,00034,20033,60035,00034,20033,20035,00033,500

NONENONENONENONENONENONENONENONENONENONENONENONETDRTDRTDR

TDR & TXVTDR & TXVTDR & TXVTDR & TXVTDR & TXV

NONETDR & TXVTDR & TXV

10.0010.0010.0010.0010.0010.0010.00

——

10.0010.0010.0010.0010.0010.0010.5010.0010.0010.0010.00

—11.0011.50

10.2010.2010.2010.2010.2010.2010.2010.0010.2010.2010.2010.20

————————

10.00——

10.20—

10.2010.2010.2010.2010.2010.0010.2010.2010.2010.2010.0010.0010.00

—————

10.00——

8.2

See notes on pg. 11.

Page 9: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

9

See notes on pg. 11.

Performance data continued

UNIT SIZE-SERIES

INDOORMODEL

TOT. CAP.BTUH

FACTORY-SUPPLIED ENHANCE-

MENT STANDARD

RATING

FIELD-SUPPLIEDACCESSORY† SOUND

RATING(BELS) TDR TXV

036-30, 31, 32,50, 52, 60, 62

FK4BNF001FK4BNF002FK4BNF003FK4BNF004

34,00034,00034,40034,600

TDR & TXVTDR & TXVTDR & TXVTDR & TXV

10.5010.5011.0010.50

————

————

8.2

COILS + 58MVP040-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA036CC5A/CD5A/CD5BA042CC5A/CD5A/CD5BW036CC5A/CD5A/CD5BW042

CD3(A,B)A036CD3(A,B)A042

33,40033,40033,40033,40033,40033,400

NONENONENONENONENONENONE

10.5011.0010.5011.0010.5011.00

——————

10.5011.0010.5011.0010.5011.00

8.2

COILS + 58MVP060-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA036CC5A/CD5A/CD5BA042CC5A/CD5A/CD5BW036CC5A/CD5A/CD5BW042

CD3(A,B)A036CD3(A,B)A042

33,40033,40033,40033,40033,40033,400

NONENONENONENONENONENONE

10.5011.0010.5011.0010.5011.00

——————

10.5011.0010.5011.0010.5011.00

8.2

COILS + 58MVP080-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA036CC5A/CD5A/CD5BA042CC5A/CD5A/CD5BW036CC5A/CD5A/CD5BW042

CD3(A,B)A036CD3(A,B)A042

33,40033,40033,40033,40033,40033,400

NONENONENONENONENONENONE

10.5011.0010.5011.0010.5011.00

——————

10.5011.0010.5011.0010.5011.00

8.2

COILS + 58MVP100-20 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA036CC5A/CD5A/CD5BA042CC5A/CD5A/CD5BW036CC5A/CD5A/CD5BW042

CD3(A,B)A036CD3(A,B)A042

33,40033,40033,40033,40033,40033,400

NONENONENONENONENONENONE

10.5011.0010.5011.0010.5011.00

——————

10.5011.0010.5011.0010.5011.00

8.2

042-30, 31, 50,51, 61

*CC5A/CD5A/CD5BA042CB5AA048

CC5A/CD5A/CD5BC048CC5A/CD5A/CD5BW042CC5A/CD5A/CD5BW048

CD3(A,B)A042CD3(A,B)A048

CD3CA042CD5A/CD5BA048

CE3AA042CE3AA048CF5AA048CG5AA036

F(A,B)4AN(F,B)042F(A,B)4AN(F,B)048

FC4BNB054FC4BNF038

FC4BN(F,B)042FC4BN(F,B)048

FG3AAA048FK4BNB005FK4BNB006FK4BNF003

40,00039,50039,50040,00040,00040,00040,00038,00040,00039,50040,50040,50040,50040,00041,00041,50041,50040,00041,00040,00041,00041,50040,000

NONENONENONENONENONENONENONENONENONENONENONENONENONETDRTDR

TDR & TXVTDR & TXVTDR & TXVTDR & TXV

NONETDR & TXVTDR & TXVTDR & TXV

10.0010.0010.0010.0010.0010.0010.00

—10.0010.0010.0010.0010.0010.0010.1010.5010.1010.0010.1010.0010.5011.0010.50

10.1010.1010.1010.1010.1010.1010.1010.0010.1010.1010.1010.1010.10

——————

10.10———

—10.1010.1010.1010.1010.1010.0010.1010.1010.1010.1010.1010.0010.10

————

10.10———

8.2

COILS + 58MVP040-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA042CC5A/CD5A/CD5BC048CC5A/CD5A/CD5BW042CC5A/CD5A/CD5BW048

CD3(A,B)A042CD3(A,B)A048

40,00040,00040,00040,00040,00040,000

NONENONENONENONENONENONE

10.5010.5010.5010.5010.5010.50

——————

10.5010.5010.5010.5010.5010.50

8.2

COILS + 58MVP060-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA042CC5A/CD5A/CD5BC048CC5A/CD5A/CD5BW042CC5A/CD5A/CD5BW048

CD3(A,B)A042CD3(A,B)A048

40,00040,00040,00040,00040,00040,000

NONENONENONENONENONENONE

10.5010.5010.5010.5010.5010.50

——————

10.5010.5010.5010.5010.5010.50

8.2

Page 10: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

10

Performance data continued

UNIT SIZE-SERIES

INDOORMODEL

TOT. CAP.BTUH

FACTORY-SUPPLIED ENHANCE-

MENT STANDARD

RATING

FIELD-SUPPLIEDACCESSORY† SOUND

RATING(BELS) TDR TXV

042-30, 31, 50,51, 61

COILS + 58MVP080-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA042CC5A/CD5A/CD5BC048CC5A/CD5A/CD5BW042CC5A/CD5A/CD5BW048

CD3(A,B)A042CD3(A,B)A048

40,00040,00040,00040,00040,00040,000

NONENONENONENONENONENONE

10.5010.7010.5010.7010.5010.70

——————

10.5010.7010.5010.7010.5010.70

8.2

COILS + 58MVP100-20 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BA042CC5A/CD5A/CD5BC048CC5A/CD5A/CD5BW042CC5A/CD5A/CD5BW048

CD3(A,B)A042CD3(A,B)A048

40,00040,00040,00040,00040,00040,000

NONENONENONENONENONENONE

10.5010.7010.5010.7010.5010.70

——————

10.5010.7010.5010.7010.5010.70

8.2

048-30, 31, 50, 51, 60, 61

*CD5A/CD5BA048CB5AA048

CC5A/CD5A/CD5BA060CC5A/CD5A/CD5BC048CC5A/CD5A/CD5BW048CC5A/CD5A/CD5BW060

CD3(A,B)A048CD3(A,B)A060

CD3CA048CE3AA048CE3AA060CF5AA048CG5AA048

F(A,B)4AN(F,B)048F(A,B)4AN(F,B)060

FB4ANB070FC4BNB070FC4BNB054

FC4BN(F,B)048FC4BN(F,B)060

FG3AA048FG3AA060

FK4BNB006

46,00046,00046,00045,00046,00047,50046,00046,00045,50046,50048,00046,00046,00047,00048,00049,00048,50048,50047,00047,50046,00047,00049,000

NONENONENONENONENONENONENONENONENONENONENONENONENONETDRTDRTDR

TDR & TXVTDR & TXVTDR & TXVTDR & TXV

NONENONE

TDR & TXV

10.0010.0010.0010.0010.0010.2010.0010.20

—10.2010.2010.2010.2010.5010.5011.0011.0011.0010.5010.5010.0010.2011.50

10.5010.2010.5010.5010.5010.5010.5010.5010.0010.5010.5010.5010.50

———————

10.5010.50

10.50—

10.5010.5010.5010.5010.5010.5010.0010.5010.5010.5010.5010.5010.5011.00

————

10.5010.50

8.2

COILS + 58MVP040-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BC048CC5A/CD5A/CD5BA060CC5A/CD5A/CD5BW048CC5A/CD5A/CD5BW060

CD3(A,B)A048CD3(A,B)A060

45,50045,50045,50046,00045,50045,500

NONENONENONENONENONENONE

10.5010.4010.5010.5010.5010.40

——————

10.5010.4010.5010.5010.5010.40

8.2

COILS + 58MVP060-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BC048CC5A/CD5A/CD5BA060CC5A/CD5A/CD5BW048CC5A/CD5A/CD5BW060

CD3(A,B)A048CD3(A,B)A060

45,50045,50045,50046,00045,50045,500

NONENONENONENONENONENONE

10.5010.4010.5010.5010.5010.40

——————

10.5010.4010.5010.5010.5010.40

8.2

COILS + 58MVP080-14 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BC048CC5A/CD5A/CD5BA060CC5A/CD5A/CD5BW048CC5A/CD5A/CD5BW060

CD3(A,B)A048CD3(A,B)A060

45,50046,00045,50046,50045,50046,000

NONENONENONENONENONENONE

10.8010.5010.8011.0010.8010.50

——————

10.8010.5010.8011.0010.8010.50

8.2

COILS + 58MVP100-20 VARIABLE-SPEED FURNACECC5A/CD5A/CD5BC048CC5A/CD5A/CD5BA060CC5A/CD5A/CD5BW048CC5A/CD5A/CD5BW060

CD3(A,B)A048CD3(A,B)A060

45,50046,00045,50046,50045,50046,000

NONENONENONENONENONENONE

10.8010.5010.8011.0010.8010.50

——————

10.8010.5010.8011.0010.8010.50

8.2

060-30, 31, 50, 51, 60, 61

*CC5A/CD5A/CD5BW060CC5A/CD5A/CD5BA060

CD3(A,B)A060CD3CA060CE3AA060

F(A,B)4AN(F,B)060FB4ANB070FC4BNB054

57,00054,50054,50056,00057,50057,50058,00057,500

NONENONENONENONENONETDRTDR

TDR & TXV

10.0010.0010.00

—10.0010.0010.5010.00

10.5010.5010.5010.0010.50

———

10.5010.5010.0010.5010.0010.50

——

8.2

See notes on pg. 11.

Page 11: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

11

* Tested combination.† Refer to TDR table prior to utilizing accessory TDR. TXV must be hard shut-off type.NOTES: 1. Ratings are net values reflecting the effects of circulating fan motor heat. Supplemental electric heat is not included.

2. Tested outdoor/indoor combinations have been tested in accordance with DOE test procedures for central air conditioners. Ratings for other combinations are determined under DOE computer simulation procedures.

3. Determine actual CFM values obtainable for your system by referring to fan performance data in fan coil or furnace coil literature.4. Minimum outdoor operating ambient in cooling mode is 55˚F (12.8˚C), maximum 125˚F (51.7˚C).

TDR.90 TABLE

NOTE: In most cases, only 1 of the above should be used to achieve TDR function. More than 1 of the methods listed above in a system may cause degradation in performance.

Performance data continued

UNIT SIZE-SERIES

INDOORMODEL

TOT. CAP.BTUH

FACTORY-SUPPLIED ENHANCE-

MENT STANDARD

RATING

FIELD-SUPPLIEDACCESSORY† SOUND

RATING(BELS) TDR TXV

060-30, 31, 50, 51, 60, 61

FC4BNB070FC4BN(F,B)060

FG3AAA060FK4BNB006

58,00057,00056,50058,000

TDR & TXVTDR & TXV

NONETDR & TXV

10.5010.0010.0011.00

——

10.20—

——

10.20—

8.2

METHOD PART/MODEL NO.

Time-Delay Relay

KAATD0101TDR

FurnacesWith TDR

58DHC, 58DX, 58DXA, 58DXC, 58EJA, 58EJB, 58MCA, 58MVP, 58MXA, 58PAP, 58PAV, 58RAP, 58RAV, 58SSC, 58SX, 58SXA, 58SXB, 58TMA, 58TUA, 58VCA, 58VUA, 58WAV, 58ZAV

Page 12: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

12

Detailed cooling capacities*

See notes on pg. 15.

EVAPORATORAIR

CONDENSER ENTERING AIR TEMPERATURES ˚F

75 85 95 105 115 125

CFM EWB

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡

38CKB018-31 Outdoor Section With CC5A/CD5A/CD5BA018 Indoor Section

52572 21.0 10.0 1.77 19.9 9.58 1.88 18.7 9.11 1.98 17.4 8.65 2.09 16.2 8.18 2.18 14.9 7.73 2.2767 19.1 12.3 1.71 18.0 11.9 1.81 16.8 11.4 1.91 15.7 10.9 2.01 14.5 10.4 2.09 13.4 9.96 2.1762 17.2 14.6 1.65 16.2 14.1 1.75 15.1 13.6 1.84 14.1 13.0 1.93 13.0 12.5 2.01 12.0 11.9 2.0857 15.9 15.9 1.61 15.1 15.1 1.71 14.3 14.3 1.81 13.5 13.5 1.90 12.7 12.7 1.99 11.9 11.9 2.07

60072 21.5 10.4 1.82 20.3 9.97 1.92 19.0 9.50 2.03 17.8 9.02 2.13 16.4 8.55 2.23 15.2 8.09 2.3267 19.5 13.0 1.75 18.4 12.5 1.86 17.2 12.0 1.96 16.0 11.5 2.05 14.8 11.1 2.14 13.6 10.6 2.2262 17.7 15.5 1.70 16.6 15.0 1.79 15.5 14.4 1.89 14.4 13.8 1.98 13.3 13.2 2.06 12.3 12.3 2.1457 16.6 16.6 1.67 15.8 15.8 1.77 14.9 14.9 1.87 14.1 14.1 1.96 13.2 13.2 2.05 12.3 12.3 2.14

67572 21.9 10.8 1.86 20.7 10.4 1.97 19.4 9.86 2.07 18.0 9.39 2.18 16.7 8.90 2.27 15.3 8.44 2.3667 19.9 13.7 1.80 18.7 13.2 1.90 17.5 12.7 2.00 16.3 12.2 2.09 15.0 11.7 2.18 13.8 11.2 2.2662 18.0 16.4 1.74 16.9 15.8 1.84 15.8 15.2 1.93 14.6 14.5 2.02 13.6 13.6 2.11 12.7 12.7 2.2057 17.2 17.2 1.71 16.3 16.3 1.82 15.4 15.4 1.92 14.5 14.5 2.01 13.6 13.6 2.11 12.7 12.7 2.20

Multipliers for Determining the Performance With Other Indoor Sections

IndoorSection Size

CoolingIndoorSection Size

Cooling

Capacity Power Capacity Power

CC5A/CD5A/CD5BA 018 1.00 1.00 FC4BNF 024 1.02 1.02

024 1.02 1.01 033 1.02 1.04

CC5A/CD5A/CD5BW 024 1.02 1.01 FD3ANA 018 0.99 1.02

CD3(A,B) 018 0.99 1.00 024 1.02 1.00

024 1.02 1.01 FF1(A,B)NA 018 1.00 0.97

CE3AA 024 1.03 1.02 024 1.02 1.02

CF5AA 024 1.03 1.02 FG3AAA 024 1.02 1.01

CG5AA 024 1.03 1.02 FK4BNF 001 1.02 0.94

F(A,B)4ANF 018 0.98 0.99 002 1.02 0.95

024 1.02 1.02 004 1.02 0.93

38CKB(N)024-30, 31 Outdoor Section With CC5A/CD5A/CD5BA024 Indoor Section

70072 27.2 13.2 2.34 25.8 12.6 2.46 24.3 12.0 2.57 22.7 11.5 2.68 21.1 10.9 2.78 19.5 10.3 2.8867 24.8 16.4 2.25 23.4 15.8 2.36 22.0 15.2 2.47 20.5 14.6 2.57 19.1 14.0 2.67 17.6 13.4 2.7662 22.4 19.5 2.17 21.1 18.9 2.27 19.8 18.2 2.37 18.5 17.6 2.47 17.2 16.8 2.56 15.9 15.9 2.6557 21.0 21.0 2.12 20.0 20.0 2.23 19.0 19.0 2.34 18.0 18.0 2.45 17.0 17.0 2.55 15.9 15.9 2.65

80072 27.8 13.8 2.40 26.3 13.2 2.52 24.7 12.6 2.63 23.1 12.0 2.75 21.5 11.4 2.85 19.8 10.9 2.9567 25.3 17.4 2.31 23.9 16.8 2.42 22.4 16.2 2.53 20.9 15.6 2.64 19.4 15.0 2.73 17.8 14.4 2.8262 23.0 20.9 2.23 21.6 20.2 2.33 20.2 19.4 2.44 18.9 18.6 2.53 17.6 17.6 2.63 16.5 16.5 2.7357 21.9 21.9 2.19 20.9 20.9 2.30 19.8 19.8 2.42 18.7 18.7 2.52 17.6 17.6 2.63 16.5 16.5 2.73

90072 28.3 14.3 2.46 26.7 13.7 2.58 25.1 13.1 2.69 23.4 12.5 2.80 21.7 11.9 2.91 20.0 11.4 3.0067 25.8 18.3 2.37 24.3 17.7 2.48 22.7 17.1 2.59 21.2 16.5 2.69 19.6 15.8 2.79 18.0 15.2 2.8762 23.4 22.0 2.28 22.0 21.3 2.39 20.6 20.4 2.50 19.3 19.3 2.60 18.1 18.1 2.70 16.9 16.9 2.8057 22.7 22.7 2.26 21.6 21.6 2.37 20.5 20.5 2.49 19.3 19.3 2.60 18.1 18.1 2.70 16.9 16.9 2.81

Multipliers for Determining the Performance With Other Indoor Sections

IndoorSection Size

CoolingIndoorSection Size

Cooling

Capacity Power Capacity Power

CC5A/CD5A/ 024 1.00 1.00 FC4BNF 024 1.00 1.00

CD5BA 030 1.01 1.00 030 1.02 0.99

CB5AA 030 0.98 0.99 033 1.04 1.01

CC5A/CD5A/ 024 1.00 1.00 FD3ANA 024 0.99 0.97

CD5BW 030 1.01 1.00 030 1.03 1.01

CD3(A,B)A 024 1.00 1.00 FF1(A,B)NA 024 1.01 1.01

030 1.01 1.00 030 1.04 1.02

CD3CA 024 1.01 1.00 FG3AAA 024 0.98 0.99

CE3AA 024 1.01 1.00 FK4BNF 001 1.05 0.94

030 1.03 1.01 002 1.06 0.95

CF5AA 024 1.01 1.00 003 1.05 0.93

CG5AA 024 1.01 1.00 004 1.07 0.93

F(A,B)4ANF 024 1.01 1.00 FK4BNB 005 1.11 0.94

030 1.03 1.00 — — —

Page 13: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

13

Detailed cooling capacities* continued

See notes on pg. 15.

EVAPORATORAIR

CONDENSER ENTERING AIR TEMPERATURES ˚F

75 85 95 105 115 125

CFM EWB

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡

38CKB(N)030-30, 31, 50, 51 Outdoor Section With CC5A/CD5A/CD5BA030 Indoor Section

87572 34.0 16.4 2.85 32.2 15.7 3.01 30.3 15.0 3.17 28.4 14.3 3.33 26.5 13.6 3.49 24.6 12.9 3.6467 30.9 20.4 2.74 29.2 19.7 2.89 27.5 19.0 3.04 25.7 18.2 3.20 23.9 17.5 3.34 22.2 16.8 3.4962 28.0 24.3 2.63 26.4 23.5 2.78 24.8 22.7 2.92 23.2 21.9 3.07 21.6 21.0 3.21 20.0 20.0 3.3557 26.2 26.2 2.57 25.0 25.0 2.73 23.8 23.8 2.88 22.5 22.5 3.04 21.3 21.3 3.19 20.0 20.0 3.35

100072 34.8 17.1 2.93 32.8 16.4 3.09 30.9 15.7 3.25 28.9 15.0 3.41 26.9 14.3 3.57 24.9 13.6 3.7267 31.6 21.6 2.82 29.8 20.9 2.97 28.0 20.1 3.12 26.2 19.4 3.27 24.3 18.7 3.42 22.5 17.9 3.5762 28.6 25.9 2.71 27.0 25.1 2.86 25.3 24.2 3.00 23.7 23.2 3.15 22.1 22.1 3.30 20.7 20.7 3.4557 27.3 27.3 2.66 26.0 26.0 2.82 24.7 24.7 2.98 23.4 23.4 3.13 22.1 22.1 3.29 20.7 20.7 3.45

112572 35.3 17.8 3.01 33.3 17.1 3.17 31.3 16.3 3.32 29.3 15.6 3.48 27.3 14.9 3.64 25.2 14.2 3.8067 32.2 22.7 2.89 30.3 22.0 3.04 28.4 21.2 3.19 26.5 20.5 3.35 24.6 19.7 3.50 22.7 19.0 3.6462 29.1 27.4 2.78 27.5 26.4 2.93 25.8 25.4 3.08 24.2 24.2 3.23 22.7 22.7 3.39 21.3 21.3 3.5457 28.3 28.3 2.75 26.9 26.9 2.91 25.5 25.5 3.06 24.1 24.1 3.23 22.7 22.7 3.39 21.3 21.3 3.55

Multipliers for Determining the Performance With Other Indoor Sections

IndoorSection Size

CoolingIndoorSection Size

Cooling

Capacity Power Capacity Power

CC5A/CD5A/ 030 1.00 1.00 F(A,B)4ANF 030 0.99 1.00

CD5BA 036 1.04 1.02 036 1.01 1.03

CB5AA 030 0.99 0.99 FC4BNF 030 0.99 1.00

CB5AW 036 1.03 1.00 033 1.04 1.02

CC5A/CD5A/CD5BW 030 1.00 1.00 036 1.01 1.02

CD5A/CD5BW 036 1.04 1.02 FD3ANA 030 0.99 1.01

CD3(A,B)A 030 1.00 1.00 FF1(A,B)NA 030 1.00 1.01

036 1.04 1.02 FG3AAA 036 1.00 1.01

CD3CA 030 0.99 0.99 FK4BNF 001 1.04 0.97

CE3AA 030 0.99 1.00 002 1.04 0.98

036 1.02 1.01 003 1.04 0.94

CF5AA 036 1.03 1.01 004 1.04 0.95

CG5AA 036 1.03 1.01 — — —

38CKB(N)036-30, 31, 32, 50, 52, 60, 62 Outdoor Section With CC5A/CD5A/CD5BA036 Indoor Section

105072 41.3 20.5 3.41 39.1 19.6 3.61 36.8 18.8 3.81 34.5 18.0 4.00 32.2 17.1 4.19 29.9 16.3 4.3867 37.6 25.8 3.28 35.5 25.0 3.47 33.4 24.1 3.65 31.3 23.3 3.84 29.1 22.4 4.02 27.0 21.6 4.2062 34.1 31.0 3.16 32.2 30.0 3.33 30.3 29.0 3.51 28.4 28.0 3.69 26.6 26.6 3.87 25.0 25.0 4.0657 32.8 32.8 3.10 31.2 31.2 3.30 29.7 29.7 3.49 28.2 28.2 3.68 26.6 26.6 3.87 25.0 25.0 4.06

120072 42.1 21.4 3.51 39.8 20.6 3.70 37.4 19.7 3.90 35.1 18.9 4.09 32.6 18.0 4.29 30.2 17.2 4.4767 38.4 27.5 3.37 36.2 26.6 3.56 34.0 25.7 3.74 31.8 24.8 3.93 29.6 23.9 4.11 27.3 23.1 4.2962 34.9 33.1 3.24 33.0 32.0 3.42 31.0 30.8 3.61 29.2 29.2 3.80 27.5 27.5 3.99 25.8 25.8 4.1957 34.1 34.1 3.22 32.5 32.5 3.41 30.9 30.9 3.60 29.2 29.2 3.80 27.5 27.5 3.99 25.8 25.8 4.19

135072 42.7 22.3 3.59 40.3 21.4 3.79 37.9 20.6 3.98 35.4 19.7 4.18 33.0 18.9 4.37 30.5 18.1 4.5667 38.9 29.0 3.45 36.7 28.1 3.64 34.4 27.2 3.83 32.1 26.3 4.01 29.8 25.4 4.19 27.6 24.5 4.3762 35.6 34.9 3.33 33.6 33.5 3.52 31.8 31.8 3.71 30.1 30.1 3.91 28.3 28.3 4.10 26.5 26.5 4.3057 35.2 35.2 3.32 33.5 33.5 3.51 31.8 31.8 3.71 30.1 30.1 3.91 28.3 28.3 4.11 26.5 26.5 4.30

Multipliers for Determining the Performance With Other Indoor Sections

IndoorSection Size

CoolingIndoorSection Size

Cooling

Capacity Power Capacity Power

CB5AW 036 0.99 0.99 FB4AN(A,M,F) 042 1.00 1.01

CC5A/CD5A/ 036 1.00 1.00 FC4BNB 054 1.03 1.02

CD5BA 042 1.00 1.00 FC4BNF 033 1.01 1.01

CC5A/CD5A/CD5BW 042 0.99 1.00 036 0.99 1.01

CD3(A,B)A 036 1.00 1.00 038 1.03 1.03

042 1.00 1.00 FC4BN(F,B) 042 1.01 1.01

CD3CA 036 0.99 1.00 FG3AAA 036 0.98 0.99

CD5A/CD5BW 036 1.00 1.00 FK4BNB 005 1.03 0.95

CE3AA 036 0.99 0.99 006 0.99 0.94

042 1.01 1.00 FK4BNF 001 1.00 0.97

CF5AA 036 0.99 1.00 002 1.00 0.98

CG5AA 036 0.99 1.00 003 1.01 0.93

F(A,B)4ANF 036 0.98 1.00 004 1.02 0.95

F(A,B)4AN(F,B) 042 1.00 1.01 — — —

Page 14: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

14

Detailed cooling capacities* continued

See notes on pg. 15.

EVAPORATORAIR

CONDENSER ENTERING AIR TEMPERATURES ˚F

75 85 95 105 115 125

CFM EWB

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡

38CKB(N)042-30, 31, 50, 51, 61 Outdoor Section With CC5A/CD5A/CD5BA042 Indoor Section

122572 48.6 23.6 4.08 45.9 22.6 4.35 43.2 21.6 4.60 40.5 20.6 4.85 37.7 19.6 5.08 34.8 18.5 5.3167 44.2 29.5 3.92 41.8 28.4 4.17 39.3 27.4 4.41 36.7 26.3 4.64 34.1 25.3 4.86 31.2 24.2 5.0662 40.2 35.2 3.77 37.9 34.0 4.01 35.5 32.9 4.23 33.2 31.7 4.45 30.8 30.3 4.65 28.2 28.2 4.8657 37.8 37.8 3.69 36.1 36.1 3.93 34.3 34.3 4.17 32.5 32.5 4.40 30.5 30.5 4.63 28.2 28.2 4.86

140072 49.6 24.7 4.19 46.8 23.6 4.45 44.0 22.6 4.71 41.1 21.6 4.96 38.2 20.5 5.20 35.3 19.5 5.4267 45.2 31.2 4.03 42.6 30.2 4.28 40.0 29.1 4.52 37.4 28.0 4.75 34.7 27.0 4.97 31.8 25.8 5.1762 41.1 37.5 3.88 38.7 36.3 4.11 36.3 35.0 4.35 34.0 33.6 4.57 31.7 31.7 4.78 29.3 29.3 5.0157 39.4 39.4 3.82 37.6 37.6 4.07 35.7 35.7 4.31 33.7 33.7 4.55 31.7 31.7 4.78 29.3 29.3 5.01

157572 50.4 25.6 4.29 47.5 24.6 4.55 44.6 23.5 4.81 41.6 22.5 5.06 38.6 21.5 5.30 35.6 20.4 5.5267 46.0 32.9 4.13 43.3 31.8 4.38 40.6 30.8 4.62 37.8 29.7 4.85 35.0 28.6 5.07 32.1 27.4 5.2762 41.8 39.7 3.98 39.4 38.3 4.22 37.0 36.7 4.45 34.8 34.8 4.68 32.6 32.6 4.92 30.3 30.3 5.1557 40.8 40.8 3.94 38.8 38.8 4.19 36.8 36.8 4.44 34.8 34.8 4.69 32.6 32.6 4.92 30.3 30.3 5.15

Multipliers for Determining the Performance With Other Indoor Sections

IndoorSection Size

CoolingIndoorSection Size

Cooling

Capacity Power Capacity Power

CC5A/CD5A/CD5BA 042 1.00 1.00 CG5AA 048 1.01 1.00

CB5AA 048 0.99 1.00 F(A,B)4AN(F,B) 042 1.00 1.01

CC5A/CD5A/CD5BC 048 0.99 1.00 048 1.02 1.02

CC5A/CD5A/ 042 1.00 1.00 FC4BNB 054 1.04 1.02

CD5BW 048 1.00 1.00 FC4BNF 038 1.04 1.04

CD3(A,B)A 042 1.00 1.00 FC4BN(F,B) 042 1.00 1.02

048 1.00 1.00 048 1.02 1.02

CD5A/CD5BA 048 1.00 1.00 FG3AAA 048 1.00 1.00

CD3CA 042 0.95 0.96 FK4BNB 005 1.02 1.00

CE3AA 042 0.99 1.00 006 1.04 0.97

048 1.01 1.01 FK4BNF 003 1.00 0.95

CF5AA 048 1.01 1.00 — — —

38CKB(N)048-30, 31, 50, 51, 60, 61 Outdoor Section With CD5A/CD5BA048 Indoor Section

140072 54.3 26.2 4.17 51.9 25.3 4.65 49.5 24.4 5.18 47.0 23.5 5.75 44.4 22.6 6.35 41.8 21.6 6.9967 49.6 32.8 4.07 47.4 31.8 4.55 45.2 30.9 5.06 42.9 30.0 5.61 40.5 29.0 6.21 38.1 28.0 6.8362 45.2 39.2 3.99 43.2 38.2 4.45 41.1 37.2 4.95 39.0 36.1 5.49 36.8 35.0 6.07 34.4 33.6 6.6657 42.4 42.4 3.94 40.9 40.9 4.41 39.3 39.3 4.91 37.7 37.7 5.45 36.0 36.0 6.03 33.9 33.9 6.64

160072 55.4 27.4 4.28 52.9 26.5 4.76 50.4 25.5 5.29 47.8 24.6 5.85 45.1 23.6 6.46 42.4 22.6 7.1167 50.6 34.6 4.17 48.4 33.7 4.65 46.0 32.7 5.17 43.6 31.8 5.72 41.2 30.8 6.31 38.6 29.8 6.9462 46.2 41.7 4.08 44.0 40.7 4.55 41.9 39.6 5.05 39.8 38.4 5.60 37.5 37.0 6.18 35.2 35.2 6.7957 44.1 44.1 4.04 42.5 42.5 4.52 40.8 40.8 5.03 39.1 39.1 5.57 37.2 37.2 6.17 35.2 35.2 6.79

180072 56.2 28.4 4.37 53.7 27.5 4.85 51.1 26.5 5.38 48.4 25.6 5.96 45.6 24.6 6.56 42.8 23.6 7.2167 51.5 36.4 4.27 49.1 35.5 4.74 46.7 34.5 5.26 44.2 33.5 5.82 41.6 32.5 6.41 39.0 31.5 7.0462 46.9 44.0 4.17 44.8 42.8 4.64 42.6 41.6 5.15 40.4 40.2 5.70 38.3 38.3 6.29 36.2 36.2 6.9257 45.5 45.5 4.15 43.8 43.8 4.62 42.0 42.0 5.14 40.2 40.2 5.69 38.3 38.3 6.29 36.2 36.2 6.92

Multipliers for Determining the Performance With Other Indoor Sections

IndoorSection Size

CoolingIndoorSection Size

Cooling

Capacity Power Capacity Power

CB5AA 048 1.00 1.01 CG5AA 048 1.00 0.99

CC5A/CD5A/CD5BA 060 1.00 1.00 F(A,B)4AN(F,B) 048 1.02 1.02

CC5A/CD5A/CD5BC 048 0.98 0.99 060 1.04 1.04

CC5A/CD5A/ 048 1.00 1.00 FB4ANB 070 1.07 1.03

CD5BW 060 1.03 1.01 FC4BNB 054 1.05 1.02

CD3(A,B)A 048 1.00 1.00 070 1.05 1.02

060 1.00 1.00 FC4BN(F,B) 048 1.02 1.02

CD3CA 048 0.99 1.06 060 1.03 1.04

CD5A/CD5BA 048 1.00 1.00 FG3AA 048 1.00 1.00

CE3AA 048 1.01 1.00 060 1.02 1.01

060 1.04 1.01 FK4BNB 006 1.07 0.97

CF5AA 048 1.00 0.99 — — —

Page 15: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

15

Detailed cooling capacities* continued

* Detailed cooling capacities are based on indoor and outdoor unit at the same elevation per ARI standard 210/240-89. If additional tubing length and/or indoor unit is located above outdoor unit, a slight variation in capacity may occur.

† Total and sensible capacities are net capacities. Blower motor heat has been subtracted.‡ Sensible capacities shown are based on 80˚F (27˚C) entering air at the indoor coil. For sensible capacities at other than 80˚F (27˚C), deduct 835

Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air for each degree below 80˚F (27˚C), or add 835 Btuh (245 kw) per 1000 CFM (480 L/S) of indoor coil air per degree above 80˚F (27˚C).When the required data falls between the published data, interpolation may be performed.

** Unit kw is total of indoor and outdoor unit kilowatts.EWB — Entering Wet Bulb

System Design1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01-in. wc.2. Minimum outdoor operating air temperature without low-ambient operation accessory is 55˚F (12.8˚C).3. Maximum outdoor operating air temperature is 125˚F (51.7˚C).4. For reliable operation, unit should be level in all horizontal planes.5. Maximum elevation of indoor coil above or below base of outdoor unit is: indoor coil above = 50 ft, indoor coil below = 150 ft. (See items 6

and 7 following.)6. For interconnecting refrigerant tube lengths greater than 50 ft, consult Long-Line Application Guideline available from equipment distributor.7. Crankcase heater required when interconnecting refrigerant tube length exceeds 50 ft.8. Not more than 36 in. of refrigerant tube should be buried in the ground. If necessary to bury tubes under a sidewalk, provide a minimum 6-in.

vertical rise to the valve connections at the unit.9. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector provided.

EVAPORATORAIR

CONDENSER ENTERING AIR TEMPERATURES ˚F

75 85 95 105 115 125

CFM EWB

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**

CapacityMBtuh† Tot

SysKw**Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡ Total Sens‡

38CKB060-30, 31, 50, 51, 60, 61 Outdoor Section With CC5A/CD5A/CD5BW060 Indoor Section

175072 66.3 32.0 5.14 63.7 31.0 5.64 61.0 30.0 6.20 58.1 28.9 6.82 55.0 27.8 7.50 51.7 26.6 8.2467 60.6 40.0 4.96 58.1 38.9 5.46 55.6 37.9 6.01 52.9 36.7 6.63 50.0 35.6 7.30 47.1 34.4 8.0262 55.2 47.8 4.81 52.9 46.7 5.30 50.6 45.5 5.85 48.1 44.3 6.46 45.4 42.9 7.12 42.8 41.5 7.8057 51.8 51.8 4.72 50.0 50.0 5.22 48.2 48.2 5.78 46.3 46.3 6.40 44.2 44.2 7.07 42.1 42.1 7.77

180072 66.6 32.3 5.17 64.0 31.3 5.67 61.2 30.3 6.23 58.3 29.2 6.85 55.2 28.1 7.53 51.9 26.9 8.2767 60.8 40.4 4.99 58.4 39.4 5.48 55.8 38.3 6.04 53.1 37.2 6.65 50.2 36.0 7.33 47.2 34.8 8.0562 55.5 48.4 4.83 53.2 47.3 5.33 50.8 46.1 5.88 48.2 44.8 6.49 45.6 43.5 7.14 42.9 42.0 7.8357 52.2 52.2 4.75 50.4 50.4 5.25 48.6 48.6 5.81 46.6 46.6 6.43 44.5 44.5 7.11 42.4 42.4 7.81

210072 68.1 33.9 5.34 65.3 32.9 5.83 62.4 31.8 6.39 59.4 30.7 7.01 56.1 29.6 7.69 52.8 28.4 8.4367 62.2 43.1 5.14 59.7 42.1 5.64 57.0 41.0 6.20 54.2 39.8 6.81 51.2 38.6 7.48 48.0 37.4 8.2162 56.7 52.0 4.98 54.4 50.8 5.48 51.9 49.5 6.03 49.3 48.0 6.64 46.6 46.3 7.30 44.1 44.1 8.0157 54.6 54.6 4.93 52.7 52.7 5.43 50.7 50.7 5.99 48.6 48.6 6.62 46.4 46.4 7.29 44.1 44.1 8.01

225072 68.7 34.6 5.41 65.9 33.6 5.91 62.9 32.6 6.47 59.8 31.4 7.09 56.5 30.3 7.77 53.1 29.1 8.5167 62.8 44.4 5.22 60.2 43.4 5.71 57.5 42.3 6.27 54.6 41.1 6.89 51.5 39.9 7.56 48.3 38.6 8.2862 57.3 53.7 5.05 54.9 52.4 5.55 52.4 51.0 6.10 49.8 49.3 6.71 47.2 47.2 7.38 44.8 44.8 8.1157 55.6 55.6 5.01 53.7 53.7 5.51 51.6 51.6 6.08 49.5 49.5 6.70 47.2 47.2 7.38 44.8 44.8 8.11

Multipliers for Determining the Performance With Other Indoor Sections

IndoorSection Size

CoolingIndoorSection Size

Cooling

Capacity Power Capacity Power

CC5A/CD5A/CD5BA 060 0.96 0.97 FB4ANB 070 1.02 1.04

CC5A/CD5A/ 060 1.00 1.00 FC4BNB 054 1.01 0.99

CD5BW 070 1.02 1.01

CD3(A,B)A 060 0.96 0.97 FC4BN(F,B) 060 1.00 1.03

CD3CA 060 0.98 1.04 FG3AAA 060 0.99 1.00

CE3AA 060 1.01 1.00 FK4BNB 006 1.02 0.95

F(A,B)4AN(F,B) 060 1.01 1.05 — — —

Page 16: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

16

Condenser only ratings*

See notes on pg. 18.

SST˚F

CONDENSER ENTERING AIR TEMPERATURES ˚F

55 65 75 85 95 105 115 125

38CKB018-31

30TCG 17.6 16.2 14.7 13.4 12.0 10.7 9.52 8.35KW 1.37 1.49 1.58 1.66 1.73 1.77 1.80 1.82SDT 75.6 86.1 96.4 106.0 116.0 126.0 136.0 146.0

35TCG 19.6 18.1 16.6 15.1 13.6 12.3 10.9 9.68KW 1.40 1.52 1.63 1.73 1.81 1.87 1.91 1.93SDT 76.5 87.2 97.4 107.0 117.0 127.0 137.0 146.0

40TCG 21.8 20.1 18.5 16.9 15.4 13.9 12.5 11.1KW 1.42 1.56 1.68 1.79 1.88 1.96 2.01 2.05SDT 77.6 88.4 98.6 109.0 119.0 128.0 138.0 147.0

45TCG 24.1 22.3 20.6 18.9 17.2 15.6 14.1 12.6KW 1.44 1.59 1.73 1.85 1.96 2.05 2.12 2.17SDT 78.7 89.7 100.0 110.0 120.0 130.0 139.0 149.0

50TCG 26.5 24.6 22.7 20.9 19.1 17.4 15.8 14.2KW 1.46 1.62 1.77 1.91 2.03 2.14 2.22 2.29SDT 79.8 91.0 102.0 112.0 122.0 131.0 141.0 150.0

55TCG 29.0 27.0 25.0 23.1 21.2 19.4 17.6 15.9KW 1.47 1.65 1.82 1.97 2.10 2.22 2.32 2.40SDT 81.1 92.3 103.0 113.0 123.0 133.0 142.0 152.0

38CKB(N)024-30, 31

30TCG 22.5 20.9 19.2 17.5 15.9 14.2 12.6 11.0KW 1.83 1.95 2.05 2.14 2.21 2.26 2.29 2.29SDT 70.0 82.2 93.6 104.0 115.0 125.0 135.0 145.0

35TCG 24.9 23.2 21.5 19.7 17.9 16.2 14.5 12.8KW 1.89 2.01 2.13 2.23 2.32 2.38 2.43 2.45SDT 69.8 82.6 94.2 105.0 116.0 126.0 136.0 145.0

40TCG 27.5 25.7 23.8 22.0 20.1 18.3 16.5 14.6KW 1.94 2.08 2.21 2.32 2.42 2.50 2.57 2.60SDT 69.5 82.9 95.0 106.0 117.0 127.0 137.0 146.0

45TCG 30.1 28.3 26.3 24.4 22.4 20.5 18.5 16.6KW 2.00 2.15 2.29 2.42 2.53 2.63 2.70 2.76SDT 69.7 83.2 95.6 107.0 118.0 128.0 138.0 148.0

50TCG 32.9 31.0 29.0 26.9 24.8 22.7 20.7 18.7KW 2.07 2.22 2.37 2.51 2.64 2.75 2.84 2.91SDT 70.3 83.4 96.3 108.0 119.0 129.0 139.0 149.0

55TCG 35.8 33.8 31.8 29.6 27.3 25.1 23.0 20.9KW 2.13 2.29 2.45 2.60 2.74 2.87 2.98 3.07SDT 70.9 83.8 97.0 109.0 120.0 131.0 141.0 151.0

38CKB(N)030, 30, 31, 50, 51

30TCG 28.0 26.0 24.0 22.0 20.1 18.2 16.4 14.7KW 2.21 2.35 2.48 2.61 2.72 2.82 2.91 2.98SDT 77.5 87.5 97.4 107.0 117.0 127.0 136.0 146.0

35TCG 31.1 28.9 26.7 24.6 22.6 20.6 18.6 16.8KW 2.29 2.44 2.59 2.72 2.85 2.97 3.07 3.15SDT 78.9 88.9 98.8 109.0 118.0 128.0 137.0 147.0

40TCG 34.3 32.0 29.7 27.4 25.2 23.1 21.0 18.9KW 2.38 2.54 2.70 2.85 2.99 3.11 3.23 3.33SDT 80.5 90.6 100.0 110.0 120.0 129.0 139.0 148.0

45TCG 37.7 35.2 32.8 30.4 28.0 25.7 23.4 21.2KW 2.47 2.64 2.81 2.97 3.12 3.27 3.40 3.51SDT 82.1 92.3 102.0 112.0 121.0 131.0 140.0 150.0

50TCG 41.3 38.7 36.1 33.5 31.0 28.5 26.1 23.7KW 2.56 2.75 2.92 3.10 3.27 3.42 3.57 3.70SDT 83.9 94.0 104.0 114.0 123.0 133.0 142.0 151.0

55TCG 45.1 42.3 39.5 36.8 34.1 31.4 28.8 26.3KW 2.66 2.86 3.05 3.23 3.41 3.58 3.74 3.89SDT 85.8 96.0 106.0 116.0 125.0 135.0 144.0 153.0

Page 17: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

17

Condenser only ratings* continued

See notes on pg. 18.

SST˚F

CONDENSER ENTERING AIR TEMPERATURES ˚F

55 65 75 85 95 105 115 125

38CKB(N)036-30, 31, 32, 50, 52, 60, 62

30TCG 32.1 30.5 28.9 27.2 25.5 23.7 21.8 19.9KW 2.33 2.57 2.84 3.11 3.40 3.68 3.95 4.21SDT 78.6 89.0 99.3 109.0 120.0 129.0 139.0 149.0

35TCG 35.2 33.5 31.8 30.0 28.2 26.3 24.3 22.3KW 2.40 2.65 2.92 3.21 3.51 3.81 4.10 4.39SDT 79.9 90.4 101.0 111.0 121.0 131.0 141.0 150.0

40TCG 38.4 36.7 34.9 33.0 31.0 29.0 26.9 24.8KW 2.47 2.72 3.00 3.30 3.61 3.93 4.25 4.56SDT 81.3 91.9 102.0 112.0 123.0 132.0 142.0 152.0

45TCG 41.8 40.0 38.1 36.1 34.0 31.8 29.7 27.4KW 2.55 2.81 3.10 3.40 3.73 4.06 4.40 4.74SDT 82.9 93.5 104.0 114.0 124.0 134.0 144.0 154.0

50TCG 45.4 43.5 41.5 39.3 37.1 34.9 32.5 30.2KW 2.63 2.90 3.19 3.51 3.84 4.20 4.55 4.91SDT 84.6 95.3 106.0 116.0 126.0 136.0 146.0 155.0

55TCG 49.2 47.2 45.0 42.8 40.4 38.0 35.5 33.0KW 2.72 2.99 3.29 3.62 3.97 4.33 4.70 5.08SDT 86.4 97.0 107.0 118.0 128.0 138.0 148.0 157.0

38CKB(N)042-30, 31, 50, 51, 61

30TCG 37.9 36.1 34.2 32.1 30.0 27.8 25.6 23.3KW 2.73 3.03 3.34 3.67 4.01 4.35 4.68 4.98SDT 80.8 91.0 101.0 111.0 121.0 131.0 141.0 150.0

35TCG 41.5 39.6 37.5 35.4 33.2 30.9 28.5 26.0KW 2.82 3.12 3.45 3.79 4.15 4.51 4.87 5.21SDT 82.5 92.7 103.0 113.0 123.0 133.0 142.0 152.0

40TCG 45.3 43.3 41.1 38.9 36.5 34.1 31.5 28.9KW 2.91 3.22 3.56 3.92 4.29 4.67 5.06 5.43SDT 84.3 94.5 105.0 115.0 125.0 134.0 144.0 154.0

45TCG 49.4 47.2 44.9 42.5 40.0 37.4 34.8 32.0KW 3.01 3.33 3.68 4.05 4.44 4.84 5.25 5.65SDT 86.3 96.5 107.0 117.0 127.0 136.0 146.0 156.0

50TCG 53.6 51.2 48.8 46.3 43.6 40.9 38.1 35.2KW 3.11 3.44 3.80 4.18 4.59 5.01 5.44 5.87SDT 88.3 98.5 109.0 119.0 129.0 138.0 148.0 158.0

55TCG 58.0 55.5 52.9 50.2 47.5 44.6 41.6 38.5KW 3.22 3.56 3.93 4.32 4.74 5.18 5.63 6.09SDT 90.4 101.0 111.0 121.0 131.0 140.0 150.0 160.0

38CKB(N)048-30, 31, 50, 51, 60, 61

30TCG 42.6 40.8 38.9 36.9 34.8 32.7 30.5 28.3KW 3.22 3.56 3.93 4.34 4.80 5.28 5.79 6.31SDT 76.5 87.0 97.4 108.0 118.0 128.0 138.0 148.0

35TCG 46.6 44.7 42.7 40.6 38.4 36.1 33.8 31.4KW 3.28 3.61 3.99 4.41 4.87 5.37 5.89 6.44SDT 77.7 88.2 98.6 109.0 119.0 129.0 139.0 149.0

40TCG 50.9 48.8 46.7 44.4 42.1 39.7 37.2 34.7KW 3.34 3.68 4.06 4.49 4.95 5.46 6.00 6.57SDT 79.0 89.6 99.9 110.0 120.0 131.0 141.0 150.0

45TCG 55.4 53.2 50.9 48.5 46.0 43.4 40.8 38.1KW 3.42 3.75 4.14 4.57 5.04 5.56 6.11 6.70SDT 80.4 91.0 101.0 112.0 122.0 132.0 142.0 152.0

50TCG 60.1 57.8 55.3 52.8 50.1 47.4 44.5 41.7KW 3.49 3.84 4.22 4.66 5.13 5.66 6.23 6.83SDT 81.8 92.5 103.0 113.0 124.0 134.0 144.0 154.0

55TCG 65.1 62.6 60.0 57.3 54.5 51.5 48.5 45.4KW 3.58 3.93 4.32 4.75 5.24 5.77 6.34 6.96SDT 83.4 94.1 105.0 115.0 125.0 135.0 145.0 155.0

Page 18: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

18

Condenser only ratings* continued

* ARI listing applies only to systems shown in Performance Data table.SST — Saturated Temperature Entering Compressor (˚F)TCG — Gross Cooling Capacity (1000 Btuh)KW — Total Power (Kw)SDT — Saturated Temperature Leaving Compressor (˚F)

SST˚F

CONDENSER ENTERING AIR TEMPERATURES ˚F

55 65 75 85 95 105 115 125

38CKB060-30, 31, 50, 51, 60, 61

30TCG 52.8 50.6 48.2 45.8 43.3 40.6 37.9 35.2KW 3.87 4.27 4.73 5.23 5.78 6.37 6.99 7.63SDT 75.7 86.2 96.6 107.0 117.0 127.0 137.0 147.0

35TCG 57.8 55.4 52.9 50.3 47.6 44.8 41.9 39.0KW 3.94 4.35 4.81 5.32 5.87 6.48 7.12 7.79SDT 76.9 87.5 97.9 108.0 118.0 129.0 139.0 148.0

40TCG 63.0 60.5 57.8 55.1 52.2 49.2 46.1 43.0KW 4.02 4.44 4.90 5.41 5.98 6.60 7.27 7.95SDT 78.2 88.9 99.3 110.0 120.0 130.0 140.0 150.0

45TCG 68.6 65.8 63.0 60.0 57.0 53.8 50.5 47.2KW 4.12 4.53 5.00 5.52 6.09 6.72 7.41 8.12SDT 79.6 90.3 101.0 111.0 121.0 132.0 142.0 152.0

50TCG 74.4 71.5 68.5 65.3 62.1 58.7 55.2 51.5KW 4.22 4.64 5.11 5.63 6.22 6.86 7.55 8.29SDT 81.1 91.9 102.0 113.0 123.0 133.0 143.0 153.0

55TCG 80.5 77.4 74.2 70.9 67.4 63.8 60.1 56.2KW 4.33 4.75 5.23 5.76 6.35 7.00 7.70 8.46SDT 82.7 93.6 104.0 115.0 125.0 135.0 145.0 155.0

Page 19: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

19

Certified drawing — 38CKB

A94396

AIR DISCHARGE

AIR IN

A SQ

B

P

C

3/8 IN. (9.5mm) DIA

TIEDOWN KNOCKOUTS

(2) PLACES

2 7/8″ (73.0mm)

1 1/4″ (31.8mm)

HG

F

E

FIELD CONTROL SUPPLY CONN 7/8 IN. (22.2mm) DIA HOLE

FIELD POWER SUPPLY CONN 7/8 IN. (22.2mm) DIA HOLE WITH 1 1/8 IN. (28.6mm) DIA KNOCKOUT AND 1 3/8 IN. (34.9mm) DIA KNOCKOUT

3/8 IN. (9.5mm) DIA LIQUID LINE CONN

D DIA VAPOR LINE CONN

LK

J

AIR INM

N

AIR DISCHARGE

AIR IN

AIR IN

1. Allow 30 In. (762.0mm) clearance to service side of unit, 48 In. (1219.2mm) above unit, 6 In. (152.4mm) on one side, 12 In.(308.8mm) on remaining side, and 24 In. (609.6mm) between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55°F(13°C), max 125°F(52°C). 3. Series designation is the 13th position of the unit model number. 4. Center of gravity

NOTES:

18, 24

30, 36, 42

48, 60

18 x 18

22 1⁄2 x 22 1⁄2

30 x 30

UNIT SIZEMINIMUM

MOUNTING PAD DIMENSIONS (In.)

AIR DISCHARGE

38CKB018

38CKB024

38CKB024

38CKB030

38CKB030

38CKB036

38CKB036

38CKB036

38CKB042

38CKB042

38CKB048

38CKB048

38CKB060

38CKB060

1

0

1

0

1

0

1

2

0

1

0�

1

0

1

X

X

X

X

X

X

X

X

X

X

X�

X

X

X

O

O

O

O

O

O

O

O

O

O

O�

O

O

O

O

O

O

X

X

X

O

X

X

X

X�

X

X

X

O

O

O

O

O

X

O

X

X

X

X�

X

X

X

15

15

15

18 1⁄8 18 1⁄8

18 1⁄8 18 1⁄8

18 1⁄8 18 1⁄8 18 1⁄8 23 1⁄2 23 1⁄2 23 1⁄2 23 1⁄2

18

18

18

22 1⁄2 22 1⁄2

22 1⁄2 22 1⁄2

22 1⁄2

22 1⁄2 22 1⁄2

30�

30 30 30

21 15⁄16 23 15⁄16 25 15⁄16 21 15⁄16 21 15⁄16 25 15⁄16

25 15⁄16�

23 15⁄16 29 15⁄16 29 15⁄16

27 15⁄16�

27 15⁄16 35 15⁄16

29 15⁄16

5⁄8 5⁄8 5⁄8

3⁄4 3⁄4

3⁄4

3⁄4

3⁄4 7⁄8 7⁄8

7⁄8�

7⁄8 7⁄8

7⁄8

3 3⁄16

3 3⁄16

3 3⁄16

3 3⁄16 3 3⁄16 3 3⁄16 3 3⁄16

3 3⁄16 3 1⁄4 3 1⁄4 3 1⁄4�

3 1⁄4 3 1⁄4 3 1⁄4

16 5⁄16 16 5⁄16

16 5⁄16

19 3⁄4�

19 3⁄4

19 3⁄4�

19 3⁄4 19 3⁄4�

19 3⁄4 19 3⁄4 27 1⁄4�

27 1⁄4 27 1⁄4 27 1⁄4

17 3⁄4 17 3⁄4

17 3⁄4

22 1⁄4 22 1⁄4 22 1⁄4 22 1⁄4

22 1⁄4 22 1⁄4 22 1⁄4 29 3⁄4�

29 3⁄4 29 3⁄4 29 3⁄4

10 3⁄16

10 3⁄16

10 3⁄16

14 3⁄8 14 3⁄8

14 3⁄8

14 3⁄8

14 3⁄8 14 3⁄8

14 3⁄8 20�

20

20 20

16 1⁄8 16 1⁄8

16 1⁄8

19 9⁄16

19 9⁄16

19 9⁄16

19 9⁄16�

19 9⁄16

19 9⁄16

19 9⁄16

27 1⁄16�

27 1⁄16

27 1⁄16

27 1⁄16

17 9⁄16

17 9⁄16

17 9⁄16

22 1⁄16

22 1⁄16

22 1⁄16

22 1⁄16�

22 1⁄16

22 1⁄16

22 1⁄16

29 9⁄16�

29 9⁄16

29 9⁄16

29 9⁄16

7 7⁄8

7 7⁄8

7 7⁄8

10 3⁄8

10 3⁄8

10 1⁄4

10 1⁄4�

10 3⁄8

10 1⁄4

10 3⁄8

15�

15

15 1⁄2

15 1⁄2

8 3⁄8

8 3⁄8

8 3⁄8

10 1⁄4

10 3⁄4

9 1⁄2

9 1⁄2

10 3⁄4

9 1⁄2

10 3⁄4

13�

13

14

14

118�

120�

122�

129�

127�

134�

143�

138�

143�

147�

197�

203�

238�

223

UNIT

SE

RIE

S

ELECTRICAL CHARACTERISTICS

A B C D

3

3

3

3 11⁄16 3 11⁄16

3 11⁄16 3 11⁄16

3 11⁄16 3 11⁄16 3 11⁄16 6 1⁄2�

6 1⁄2 6 1⁄2 6 1⁄2

E F G H J K L M N P SHIPPING WEIGHT

In. In. In. In. In. In. In. In. In. In. In. In. In. In. Lb.

9 3⁄8

9 1⁄2

10 1⁄8

10 3⁄4

10 3⁄4

11 1⁄4

11 1⁄4

10 7⁄8 �

11 5⁄8

11 1⁄8

14 1⁄2�

14 1⁄2

15 1⁄2

15

X = YES O = NO

208-

230-

1-60

208/

230-

3-60

230-

1-60

460-

3-60

Page 20: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

20

Certified drawing — 38CKN

A94397

AIR DISCHARGE

AIR IN

A SQ

B

P

C

3/8 IN. (9.5mm) DIA

TIEDOWN KNOCKOUTS

(2) PLACES

2 7/8″ (73.0mm)

1 1/4″ (31.8mm)

HG

F

E

FIELD CONTROL SUPPLY CONN 7/8 IN. (22.2mm) DIA HOLE

FIELD POWER SUPPLY CONN 7/8 IN. (22.2mm) DIA HOLE WITH 1 1/8 IN. (28.6mm) DIA KNOCKOUT AND 1 3/8 IN. (34.9mm) DIA KNOCKOUT

3/8 IN. (9.5mm) DIA LIQUID LINE CONN

D DIA VAPOR LINE CONN

LK

J

AIR INM

N

AIR DISCHARGE

AIR IN

AIR IN

1. Allow 30 In. (762.0mm) clearance to service side of unit, 48 In. (1219.2mm) above unit, 6 In. (152.4mm) on one side, 12 In.(308.8mm) on remaining side, and 24 In. (609.6mm) between units for proper airflow. 2. Minimum outdoor operating ambient in cooling mode is 55°F(13°C), max 125°F(52°C). 3. Series designation is the 13th position of the unit model number. 4. Center of gravity

NOTES:

24

30, 36, 42

48

18 x 18

22 1⁄2 x 22 1⁄2

30 x 30

UNIT SIZEMINIMUM

MOUNTING PAD DIMENSIONS (In.)

AIR DISCHARGE

38CKN024

38CKN024

38CKN030

38CKN030

38CKN036

38CKN036

38CKN036

38CKN042

38CKN042

38CKN048

38CKN048

0

1

0

1

0

1

2

0

1

0

1

X

X

X

X

X

X

X

X

X

X

X

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

O

15

15

18 1⁄8

18 1⁄8 18 1⁄8

18 1⁄8 18 1⁄8

18 1⁄8 18 1⁄8 23 1⁄2 23 1⁄2

18

18

22 1⁄2

22 1⁄2 22 1⁄2

22 1⁄2 22 1⁄2

22 1⁄2

22 1⁄2 30 30

25 15⁄16 23 15⁄16 21 15⁄16 21 15⁄16 25 15⁄16 25 15⁄16

23 15⁄16�

29 15⁄16 29 15⁄16 27 15⁄16

27 15⁄16

5⁄8 5⁄8 3⁄4

3⁄4 3⁄4

3⁄4

3⁄4

7⁄8 7⁄8 7⁄8

7⁄8

3 3⁄16

3 3⁄16

3 3⁄16

3 3⁄16 3 3⁄16 3 3⁄16 3 3⁄16

3 1⁄4 3 1⁄4 3 1⁄4 3 1⁄4

16 5⁄16 16 5⁄16

19 1⁄2

19 1⁄2 19 1⁄2

19 1⁄2�

19 1⁄2 19 3⁄4�

19 3⁄4 27 1⁄4 27 1⁄4

17 3⁄4 17 3⁄4

2111⁄16

2111⁄16 2111⁄16 2111⁄16 2111⁄16

22 1⁄4 22 1⁄4 29 3⁄4 29 3⁄4

10 3⁄16

10 3⁄16

14 3⁄8

14 3⁄8 14 3⁄8

14 3⁄8

14 3⁄8

14 3⁄8 14 3⁄8

20 20

16 1⁄8 16 1⁄8

19

19

19

19

19�

19 9⁄16

19 9⁄16

27 1⁄16

27 1⁄16

17 9⁄16

17 9⁄16

21 3⁄4

21 3⁄4

21 3⁄4

21 3⁄4

21 3⁄4�

22 1⁄16

22 1⁄16

29 9⁄16

29 9⁄16

7 7⁄8

7 7⁄8

10 3⁄8

10 3⁄8

10 1⁄4

10 1⁄4

10 3⁄8�

10 1⁄4

10 3⁄8

15

15

8 3⁄4

8 3⁄8

10 1⁄4

10 3⁄4

9 1⁄2

9 1⁄2

10 3⁄4

9 1⁄2

10 3⁄4

13

13

120�

122�

129�

127�

134�

143�

138�

143�

147�

197�

203

UNIT

SE

RIE

S

ELECTRICAL CHARACTERISTICS

A B C D

3

3

3 11⁄16

3 11⁄16 3 11⁄16

3 11⁄16 3 11⁄16

3 11⁄16 3 11⁄16 6 1⁄2 6 1⁄2

E F G H J K L M N P SHIPPING WEIGHT

In. In. In. In. In. In. In. In. In. In. In. In. In. In. Lb.

X = YES O = NO

208-

230-

1-60

208/

230-

3-60

230-

1-60

460-

3-60

9 1⁄2

10 1⁄8

10 3⁄4

10 3⁄4

11 1⁄4

11 1⁄4

10 7⁄8 �

11 5⁄8

11 1⁄8

14 1⁄2

14 1⁄2

Page 21: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

21

Guide specifications

GENERALSystem Description

Outdoor-mounted, air-cooled, split-system air conditioner unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, propeller-type condenser fan, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a packaged fan coil or coil unit.Quality Assurance

Unit will be rated in accordance with the latest edition of ARI Standard 210 and 270.

Unit will be certified for capacity, efficiency, and sound and listed in the latest ARI directory.

Unit construction will comply with latest edition of ANSI/ASHRAE and with NEC.

Unit will be constructed in accordance with UL standards and will carry the UL label of approval. Unit will have c-UL approval.

Unit cabinet will be capable of withstanding Federal Test Method Standard No. 141 (Method 6061) 500-hr salt spray test.

Air-cooled condenser coils will be leak tested at 150 psig and pressure tested at 300 psig.

Unit constructed in ISO9002 approved facility.Delivery, Storage, and Handling

Unit will be shipped as single package only and is stored and handled per unit manufacturer’s recommendations.Warranty (for inclusion by specifying engineer)

U.S. and Canada only.

PRODUCTSEquipment

Factory-assembled, single piece, air-cooled air conditioner unit. Contained within the unit enclosure is all factory wiring, piping, controls, compressor, refrigerant charge (R-22), and special features required prior to field start-up.Unit Cabinet

Unit cabinet will be constructed of galvanized steel, bonderized, and coated with a powder coat paint.Fans

Condenser fan will be direct-drive propeller type, discharging air upward.

Air-Cooled, Split-SystemAir Conditioner

38CKB1-1/2 to 5 Tons Nominal

Condenser fan motors will be totally enclosed, 1-phase type with class B insulation and permanently lubricated bearings.

Shafts will be corrosion resistant.Fan blades will be statically and dynamically balanced.Condenser fan openings will be equipped with PVC-coated

steel wire safety guards.Compressor

Compressor will be hermetically sealed.Compressor will be mounted on rubber vibration isolators.

Condenser CoilCondenser coil will be air cooled.Coil will be constructed of aluminum fins mechanically

bonded to copper tubes which are then cleaned, dehydrated, and sealed.Refrigeration Components

Refrigeration circuit components will include liquid line shut-off valve with sweat connections, suction shut-off valves with sweat connections, system charge of refrigerant R-22, and compressor oil.Operating Characteristics

The capacity of the unit will meet or exceed _____ Btuh at a suction temperature of _____ F. The power consumption at full load will not exceed _____ kw.

Combination of the unit and the evaporator or fan coil unit will have a total net cooling capacity of _____ Btuh or greater at conditions of _____ CFM entering air temperature at the evaporator at _____ F wet bulb and _____ F dry bulb, and air entering the unit at _____ F.

The system will have an SEER of _____ Btuh/watt or greater at DOE conditions.Electrical Requirements

Nominal unit electrical characteristics will be _____ v, 1 phase, 60 hertz. The unit will be capable of satisfactory operation within voltage limits of _____ v to _____ v.

Unit electrical power will be single point connection.Control circuit will be 24v.

Special FeaturesRefer to section of this literature identifying accessories

and descriptions for specific features and available enhancements.

Page 22: Product Data Air Conditioner - dms.hvacpartners.comdms.hvacpartners.com/docs/1009/Public/01/38CKB-1PD.pdf · 2 motors provide more economical operation. Unit Design — Copper tube,

Carrier Corporation • Syracuse, New York 13221 2-95

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1 2 4 Page 22 Catalog No. 523-830 Printed in U.S.A. PC 101 Form 38CKB-1PD

Tab 3a 1a 2a Replaces: New

SERVICE TRAINING

Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: • Unit Familiarization • Maintenance • Installation Overview • Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog.