Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4way Multipoise design and throughthefurnace downflow venting. The PG8MAA/JAA furnaces are approved for use with natural or propane gas, and the PG8JAA Low NOx units are designed for California installations and meet 40 ng/J NOx emissions. Can be installed in air quality management districts with a 40 ng/J NOx emissions requirement. STANDARD FEATURES S Four-position furnace: Upflow, Horizontal Right, Horizontal Left, Downflow S Electronic control center Adjustable heating air temperature rise, LED diagnostics and self test feature. Stores fault codes during power outages. S Hot surface ignition (HSI) S Cabinet air leakage less than 2.0% at 1.0 in. W.C. and cabinet air leakage less than 1.4% at 0.5 in. W.C. when tested in accordance with ASHRAE standard 193

Upload: others

Post on 01-Mar-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

Product Data

PG8MAA/PG8JAAMULTIPOISE GAS FURNACE

A10257

The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature4−way Multipoise design and through−the−furnace downflowventing. The PG8MAA/JAA furnaces are approved for use withnatural or propane gas, and the PG8JAA − Low NOx units aredesigned for California installations and meet 40 ng/J NOxemissions. Can be installed in air quality management districts witha 40 ng/J NOx emissions requirement.

STANDARD FEATURES� Four-position furnace: Upflow, Horizontal Right, Horizontal

Left, Downflow

� Electronic control centerAdjustable heating air temperature rise, LED diagnostics and selftest feature. Stores fault codes during power outages.

� Hot surface ignition (HSI)

� Cabinet air leakage less than 2.0% at 1.0 in. W.C. andcabinet air leakage less than 1.4% at 0.5 in. W.C. whentested in accordance with ASHRAE standard 193

Page 2: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

2

MODEL NUMBER NOMENCLATURE1

BrandP

2Product

G

3Base Effy.

8

4Variation

M

5Motor

A

6Major Series

A

7 - 9Cooling Cap.

036

10 - 12Heating Cap.

070

13 - 14Minor Series

AA14

Variations| | | | | | | | | |

8 - 80 AFUEM - Multipoise

J - Low Nox

A - Std. /PSC

Brand

Product

Minor Series

Major Series

045 = 44,000 BTU070 = 66,000 BTU090 = 88,000 BTU110 = 110,000 BTU135 = 132,000 BTU

024 - 800 CFM030 - 1000 CFM036 - 1200 CFM042 - 1400 CFM048 - 1600 CFM054 - 1800 CFM060 - 2000 CFM 066 - 2200 CFM

A180214

For California Residents:For installation in SCAQMD only: This furnace does not meet the SCAQMD Rule 1111 14 ng/J NOx emission limit, and thus is subject to amitigation fee of up to $450. This furnace is not eligible for the Clean Air Furnace Rebate Program: www.CleanAirFurnaceRebate.com

DIMENSIONS

FURNACE SIZE

A CABINET

WIDTHIN (mm)

B OUTLETWIDTHIN (mm)

CTOP &

BOTTOM FLUECOLLAR IN (mm)

D BOTTOM INLET

WIDTHIN (mm)

VENTCONNECTION

SIZEIN (mm)

SHIP WTLB (KG)

024045 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 104 (47)

036045 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 107 (49)

024070 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 111 (50)

036070 14-3/16 (360) 12-9/16 (319) 9-5/16 (237) 12-11/16 (322) 4 (102) 115 (52)

048070** 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16-1/8 (410) 4 (102) 126 (57)

042090 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16-1/8 (410) 4 (102) 127 (58)

048090 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 140 (64)

060090** 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 146 (66)

036110 17-1/2 (445) 15-7/8 (403) 11-9/16 (294) 16-1/8 (410) 4 (102) 135 (61)

048110 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 146 (66)

066110 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102) 152 (69)

048135 21 (533) 19-3/8 (492) 13-5/16 (338) 19-1/2 (495) 4 (102)* 149 (68)

066135 24-1/2 (622) 22-7/8 (581) 15-1/16 (383) 23 (584) 4 (102)* 163 (74)

060155 24-1/2 (622) 22-7/8 (581) 15-1/16 (383) 23 (584) 4 (102)* 170 (77)

*135 and 155 size furnaces require a 5 or 6-in. (127 or 152 mm) vent. Use a vent adapter between furnace and vent stack. See Installation Instructions forcomplete installation requirements.

** Low NOx version not offered in this size.

Page 3: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

3

DIMENSIONS

A180207

PG

8M

AA

/ J

AA

Page 4: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

4

A10269

Always Ask For

Use of the AHRI Certified TM Mark indicates amanufacturer’s participation in the program. Forverification of certification for individual products,go to www.ahridirectory.org.

PG

8M

AA

/ J

AA

Page 5: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

5

SPECIFICATIONS

UNIT SIZE 024045 036045 024070 036070 048070 042090 048090

RATINGS AND PERFORMANCE

Input Btuh*Non-weatherized ICS

PG8JAA Upflow; all PG8MAA 44,000 44,000 66,000 66,000 66,000 88,000 88,000

PG8JAA Downflow/Horizontal 42,000 42,000 63,000 63,000 63,000 84,000 84,000

Output Capacity(Btuh)†Non-weatherized ICS

PG8JAA Upflow; all PG8MAA 35,000 36,000 53,000 54,000 53,000 71,000 71,000

PG8JAA Downflow/Horizontal 34,000 34,000 51,000 51,000 51,000 68,000 68,000

AFUE† 80.0 80.0 80.0 80.0 80.0 80.0 80.0

Certified Temperature Rise Range °F (°C)30‐60

(17-33)20‐50

(11-28)40‐70

(22-39)30‐60

(17-33)25‐55

(14-30)40‐70

(22-39)30‐60

(17-33)

Certified External Static Pressure Heat/Cool 0.10/0.50 0.10/0.50 0.12/0.50 0.12/0.50 0.12/0.50 0.15/0.50 0.15/0.50

Airflow CFM‡Heating 865 1250 720 1195 1350 1300 1505

Cooling 835 1160 870 1200 1505 1385 1635

ELECTRICAL

Unit Volts-Hertz-Phase 115‐60‐1

Operating Voltage Range Min‐Max 104‐127

Maximum Unit Amps 5.2 7.2 5.1 7.2 9.5 8.6 10.0

Maximum Wire Length (Measure 1 Way in Ft (M)) 49 (14.9) 37 (11.2) 51 (15.5) 38 (11.5) 29 (8.8) 32 (9.7) 28 (8.5)

Minimum Wire Size 14

Maximum Fuse or Ckt Bkr Size (Amps)** 15

Transformer (24v) 40va

External Control Heating 12va

Power Available Cooling 35va

Air Conditioning Blower Relay Standard

CONTROLS

Limit Control SPST

Heating Blower Control Solid‐State Time Operation

Burners (Monoport) 2 2 3 3 3 4 4

Gas Connection Size 1/2‐in. NPT

GAS CONTROLS

Gas Valve (Redundant) White‐Rodgers

Min. inlet pressure (in. W.C.) 4.5 (Natural Gas)

Max. inlet pressure (in. W.C.) 13.6 (Natural Gas)

Ignition Device Hot Surface

BLOWER DATA

Direct‐Drive Motor HP (PSC) 1/5 1/3 1/5 1/3 1/2 1/3 1/2

Motor Full Load Amps 2.8 5.2 2.8 5.2 7.1 5.2 7.1

RPM (Nominal)‐Speeds 1075‐3 1075‐3 1075‐3 1075‐3 1075‐3 1075‐3 1075‐3

Blower Wheel Diameter x Width - In. (mm) 10 x 6(254 x152)

10 x 6(254 x152)

10 x 6(254 x152)

10 x 6(254 x152)

11 x 8(279 x203)

10 x 8(254 x203)

10 x 10(254 x254)

FILTER ARRANGEMENT External filter rack required

* Gas input ratings are certified for elevations to 2000 ft. (610 M). For elevations above 2000 ft (610 M), reduce ratings 4 percent for each 1000 ft (305 M)above sea level. In Canada, derate the unit 10 percent for elevations 2000 ft (610 M) to 4500 ft (1372 M) above sea level. Refer to National Fuel Gas CodeNFPA 54/ANSI Z223.1-2012 Table F.1 (d) or furnace installation instructions.

† Capacity in accordance with U.S. Government DOE test procedures.

‡ Airflow shown is for bottom only return‐air supply for the as‐shipped speed tap. For air delivery above 1800 CFM, see Air Delivery table for other options. Afilter is required for each return‐air supply. An airflow reduction of up to 7 percent may occur when using the factory‐specified 4‐5/16 in. (110 mm) wide, highefficiency media filter.

** Time‐delay type is recommended.

ICS Isolated Combustion System

N/A Not applicable

PG

8M

AA

/ J

AA

Page 6: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

6

SPECIFICATIONS continued

UNIT SIZE 060090 036110 048110 066110 048135 066135 060155

RATINGS AND PERFORMANCE

Input Btuh*Non-weatherized ICS

PG8JAA Upflow; all PG8MAA 88,000 110,000 110,000 110,000 132,000 132,000 154,000

PG8JAA Downflow/Horizontal 84,000 105,000 105,000 105,000 126,000 126,000 147,000

Output Capacity(Btuh)†Non-weatherized ICS

PG8JAA Upflow; all PG8MAA 71,000 89,000 89,000 89,000 107,000 107,000 125,000

PG8JAA Downflow/Horizontal 68,000 85,000 85,000 85,000 102,000 102,000 119,000

AFUE† 80.0 80.0 80.0 80.0 80.0 80.0 80.0

Certified Temperature Rise Range °F (°C)25‐55

(14-30)50‐80

(28-44)40‐70

(22-39)30‐60

(17-33)50‐80

(28-44)40‐70

(22-39)45‐75

(25-41)

Certified External Static Pressure Heat/Cool 0.15/0.50 0.20/0.50 0.20/0.50 0.20/0.50 0.20/0.50 0.20/0.50 0.20/0.50

Airflow CFM‡Heating 1900 1295 1515 1840 1480 1830 1790

Cooling 2025 1355 1655 2160 1710 2085 2215

ELECTRICAL

Unit Volts-Hertz-Phase 115‐60‐1

Operating Voltage Range Min‐Max 104‐127

Maximum Unit Amps 14.1 8.6 10.2 15.1 10.5 14.5 15.4

Maximum Wire Length (Measure 1 Way in Ft (M)) 31 (9.4) 32 (9.7) 27 (8.2) 29 (8.8) 27 (8.2) 30 (9.1) 29 (8.8)

Minimum Wire Size 12 14 12 14 12

Maximum Fuse or Ckt Bkr Size (Amps)** 20 15 20 15 20

Transformer (24v) 40va

External Control Heating 12va

Power Available Cooling 35va

Air Conditioning Blower Relay Standard

CONTROLS

Limit Control SPST

Heating Blower Control Solid‐State Time Operation

Burners (Monoport) 4 5 5 5 6 6 7

Gas Connection Size 1/2‐in. NPT

GAS CONTROLS

Gas Valve (Redundant) White‐Rodgers

Min. inlet pressure (in. W.C.) 4.5 (Natural Gas)

Max. inlet pressure (in. W.C.) 13.6 (Natural Gas)

Ignition Device Hot Surface

BLOWER DATA

Direct‐Drive Motor HP (PSC) 3/4 1/3 1/2 3/4 1/2 3/4 3/4

Motor Full Load Amps 11.8 5.2 7.1 11.8 7.1 11.8 11.8

RPM (Nominal)‐Speeds 1075‐3 1075‐3 1075‐3 1075‐3 1075‐3 1075‐3 1075‐3

Blower Wheel Diameter x Width - In. (mm) 11 x 11(279 x279)

10 x 8(254 x203)

10 x 10(254 x254)

11 x 11(279 x279)

10 x 10(254 x254)

11 x 11(279 x279)

11 x 11(279 x279)

FILTER ARRANGEMENT External filter rack required

* Gas input ratings are certified for elevations to 2000 ft. (610 M). For elevations above 2000 ft (610 M), reduce ratings 4 percent for each 1000 ft (305 M)above sea level. In Canada, derate the unit 10 percent for elevations 2000 ft (610 M) to 4500 ft (1372 M) above sea level. Refer to National Fuel Gas CodeNFPA 54/ANSI Z223.1-2012 Table F.1 (d) or furnace installation instructions.

† Capacity in accordance with U.S. Government DOE test procedures.

‡ Airflow shown is for bottom only return‐air supply for the as‐shipped speed tap. For air delivery above 1800 CFM, see Air Delivery table for other options. Afilter is required for each return‐air supply. An airflow reduction of up to 7 percent may occur when using the factory‐specified 4‐5/16 in. (110 mm) wide, highefficiency media filter.

** Time‐delay type is recommended.

ICS Isolated Combustion System

N/A Not applicable

PG

8M

AA

/ J

AA

Page 7: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

7

A02058

SEE NOTES: 1,2,4,7,8,9UPFLOW

SEE NOTES: 1,2,3,4,7,8,9UPFLOW

SEE NOTES: 1,2,4,5,7,8,9DOWNFLOW

A02059 A02061

SEE NOTES:1,2,3,4,5,7,8,9DOWNFLOW

SEE NOTES: 1,2,3,4,5,7,8,9DOWNFLOW

SEE NOTES: 1,2,4,5,6,7,8,9DOWNFLOW

A02060 A02063 A02062

Venting Notes1. For common vent, vent connector sizing and vent material: United States, latest edition of the National Fuel Gas

Code (NFGC), ANSI Z223.1/NFPA 54.2. Immediately increase to 5‐in. (127 mm) vent connector outside furnace casing when 5‐in. (127 mm) vent connector

required, refer to Note 1.3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace,

except when accessory Downflow Vent Guard is used in downflow position.4. Type B vent where required, refer to Note 1.5. 4-in. (102 mm) single wall vent must be used inside furnace casing and the Downflow Vent Guard Kit.6. Accessory Downflow Vent Guard Kit required in downflow installations with bottom vent configuration.7. Chimney Adapter Kit required for exterior masonry chimney applications. Refer to Chimney Adapter Kits for sizing

and complete application details.8. Secure vent connector to furnace elbow with (2) corrosion‐resistant sheet metal screws, space approximately 180°

apart.9. Secure all other single wall vent connector joints with (3) corrosion‐resistant screws spaced approximately 120°

apart. Secure Type B vent connectors per vent connector manufacturer's recommendations.

PG

8M

AA

/ J

AA

Page 8: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

8

SEE NOTES: 1,2,4,5,7,8,9HORIZONTAL RIGHT

A02068

SEE NOTES: 1,2,4,5,7,8,9HORIZONTAL RIGHT

A02070

SEE NOTES: 1,2,4,7,8,9HORIZONTAL RIGHT

A02069

SEE NOTES: 1,2,4,7,8,9HORIZONTAL LEFT

A02064

SEE NOTES: 1,2,4,5,7,8,9HORIZONTAL LEFT

A02065

SEE NOTES: 1,2,4,5,7,8,9HORIZONTAL LEFT

A02066

SEE NOTES: 1,2,4,5,7,8,9HORIZONTAL LEFT

A02067

PG

8M

AA

/ J

AA

Page 9: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

9

ACCESSORIES

DESCRIPTION PART NO. 024045 036045 024070 036070 048070 042090 048090 060090 036110 048110 066110 048135 066135 060155

External Bottom Return Filter Rack

KGBFR0401B14 X X X X

KGBFR0501B17 X X X

KGBFR0601B21 X X X X X

KGBFR0701B24 X X

Unframed Filter, 3/4‐in. (19 mm)

KGAWF1306UFR X X X X X X X

KGAWF1406UFR X X X X X

KGAWF1506UFR X X

Flue Extension KGAFE0112UPH X X X X X X X X X X X X X X

Twinning Kit KGATW0601HSI X X X X X X X X X X X X X X

Combustible Floor Base KGASB0201ALL X X X X X X X X X X X X X X

Downflow Vent Guard KGBVG0101DFG X X X X X X X X X X X X X X

Vent Extension Kit KGAVE0101DNH X X X X X X X X X X X X X X

Chimney Adapter KitKGACA02014FC X X X X X X X X X X X

KGACA02015FC X X X

Natural‐to‐Propane Conversion Kit * KGBNP50011SP X X X X X X X X X X X X X X

Propane‐to‐Natural Conversion Kit KGBPN42011SP X X X X X X X X X X X X X X

Label Kit KGALB0301KIT X X X X X X X X X X X X X X

Gas Orifice

LH32DB207

See Installation Instructions for model, altitude, and heat value usages.

LH32DB202

LH32DB200

LH32DB205

LH32DB208

LH32DB078

LH32DB076

LH32DB203

LH32DB201

LH32DB206

LH32DB209

LH32DB210

* Factory authorized, field installed. Fuel conversion kits are CSA (formerly AGA/CGA) recognized.

X Accessory

PG

8M

AA

/ J

AA

Page 10: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

10

AIR DELIVERY—CFM (With Filter)*

FURNACESIZE

RETURN-AIRINLET

SPEEDEXTERNAL STATIC PRESSURE (In. W.C.)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

024045Bottom or

Side(s)

HighMed-HighMed-Low

1035865760

995830720

945790680

895745635

835690580

770625520

675545445

565440345

390250220

195195195

036045Bottom or

Side(s)

HighMed-HighMed-Low

144013601250

137513001210

130512401160

124011751100

116011151040

10701040965

975950885

870850790

730725670

560575520

024070Bottom or

Side(s)

HighMed-HighMed-Low

1030835725

1005815700

965790675

925755635

870710595

810660545

740590460

645480350

465325250

280205--

036070Bottom or

Side(s)

HighMed-HighMed-Low

142513201200

137512801175

132012401145

126512051105

120011401050

11251075990

1035995920

940905840

830790725

655620555

048070Bottom or

Side(s)

HighMed-HighMed-Low

175515501355

170015201340

163514751310

157014301280

150513751240

143513101190

135012401125

126011551060

11601070975

1055970890

042090Bottom or

Side(s)

HighMed-HighMed-Low

160514701310

157014451295

153514101265

146513801230

138513001195

128512201120

117511151025

1055990915

895830710

645600565

048090Bottom or

Side(s)

HighMed-HighMed-Low

194017401505

188017001505

180516501480

172015901440

163515251375

154014401300

142513351190

129011951045

10901010890

830820740

060090

Bottom Only

HighMed-HighMed-Low

240521701920

231021101875

222020401835

213019701780

202518951715

192017851630

179016751535

166015651420

153014201275

135012601135

Both Sides or 1Side & Bottom

HighMed-HighMed-Low

253022301895

245021701890

236521101845

227020501815

216519851755

206518901685

194017801600

180516601480

167015251350

150513601180

1Side Only

HighMed-HighMed-Low

247521051850

239521451860

230020701810

220020101770

209019401715

198518451650

186517351555

173016201445

158514751310

142513251150

036110Bottom or

Side(s)

HighMed-HighMed-Low

160014751315

155014351295

149013951265

142513351220

135512851155

126011851080

11351070985

990890810

785725675

530450440

048110Bottom or

Side(s)

HighMed-HighMed-Low

198017451530

191517101515

183516501470

175015601400

165514501310

149513401215

136512051095

11851090990

965865830

700605670

066110

Bottom Only

HighMed-HighMed-Low

248521351855

241521001840

234020601815

225520001775

216019301725

208018601675

195017651600

184016701510

172015551405

156514251290

Bottom Sidesor 1 Side & Bot­

tom

HighMed-HighMed-Low

--21401855

--21001840

235520501815

228519901775

219019351725

209018651675

196517601600

185016701510

170515451405

153514101290

1Side Only

HighMed-HighMed-Low

24952030--

244020251735

237020001725

229019501695

220519051650

212018501595

201517501535

191016601455

177515551335

162514251230

* A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in factory-authorized ac­cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure.

-- Indicates unstable operating conditions.

PG

8M

AA

/ J

AA

Page 11: Product Data - DCNE Data... · 2021. 2. 25. · Product Data PG8MAA/PG8JAA MULTIPOISE GAS FURNACE A10257 The Payne PG8MAA/JAA 80% AFUE Gas Furnaces feature 4−way Multipoise design

11

AIR DELIVERY—CFM (With Filter)* continued

FURNACESIZE

RETURN-AIRINLET

SPEEDEXTERNAL STATIC PRESSURE (In. W.C.)

0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0

048135Bottom or

Side(s)

HighMed-HighMed-Low

206517901480

200017551480

193017051480

183516401450

171015501380

159014651295

142012951160

123511451005

1025945855

835775670

066135

Bottom Only

HighMed-HighMed-Low

244521301860

236520801830

228020251800

219019601755

208518801705

198017951630

185016901530

170515501415

152014051280

135512551140

Bottom, Sidesor 1 Side & Bot­

tom

HighMed-HighMed-Low

--21201860

--20751830

235519951800

228019701755

216019051725

206518351630

193017351530

180516451415

165515151280

146513251140

1 Side Only

HighMed-HighMed-Low

--20701860

--20151830

221519701800

213019351755

203018551725

192017651630

179516551530

167515501415

154014451280

138512651140

060155

Bottom Only

HighMed-HighMed-Low

246521151800

243020951790

237520551770

230520051735

221519401695

211018451640

200018201570

186516751465

171515251345

153013901225

Both Sides Or 1Side & Bottom

HighMed-HighMed-Low

--21551800

--21251790

237520751770

228520151735

218519351695

210518301640

199517801570

187016351465

172014851345

155513651225

1Side Only

HighMed-HighMed-Low

--21401800

--20851790

226020201770

218019501735

207018501695

197517451640

186516951570

174015451465

159514151345

144012901225

* A filter is required for each return-air inlet. Airflow performance included 3/4-in. (19 mm) washable filter media such as contained in factory-authorized ac­cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 In. W.C. available external static pressure.

-- Indicates unstable operating conditions.

�2018 Payne Heating & Cooling Systems � 7310 W. Morris St. � Indianapolis, IN 46231 . Edition Date: 09/18

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.