product manual mms digital switchgear motor control unit ... · providing with redundant ethernet...
TRANSCRIPT
—PRODUCT MANUAL
MMS digital switchgear
Motor control unit MC510 user guide
A reliable, available, simple,
safe and powerful MNS solution
— MN
S d
igit
al
sw
itc
hg
ea
r
Mo
tor
co
ntr
ol u
nit
MC
510
us
er
gu
ide
GENERAL
The information in this document is subject to change without
notice and should not be construed as a commitment by ABB.
ABB assumes no responsibility for any errors that may appear
in this document.
In no event shall ABB be liable for direct, indirect, special, inci-
dental, or consequential damages of any nature or kind arising
from the use of this document, nor shall ABB be liable for inci-
dental or consequential damages arising from use of any soft-
ware or hardware described in this document.
This document and parts thereof must not be reproduced or
copied without ABB's written permission, and the contents
thereof must not be imparted to a third party nor be used for
any unauthorized purpose. The software described in this doc-
ument is furnished under a license and may be used, copied, or
disclosed only in accordance with the terms of such license.
All rights reserved.
Copyright © 2016 Xiamen ABB Low Voltage Equipment Co., Ltd.
GENERAL
—
Table of content
4-6 General
4 Target Group
4 Use of Warning, Caution, Information and Tip icon
5 Terminology
5 Related Documentation
6 Related System Version
6 Document Revision History
7 Product Overview
7 Introduction
7 Structure
10 Mounting
10 Mounting of MC510
11-17 Interfaces
12 Terminal Designations
16 Typical Diagram
18-88 Functionality
18 Starter Types
35 Protection Functions
72 Logic Block
79 Maintenance Function
80 Metering and Monitoring
82 Using extension modules
83 Communication interface
89 Parameterization
90-105 Accessories
90 MP51/MP52 Operator Panel
104 Parameterization Software: MConfig
106-109 Appendix A Technical Data
106 A.1 Common Technical Data
106 A.2 Technical Data of the Basic Unit MC510
109 A.3 Technical Data of the Operation panel MP51/52
109 A.4 Technical Data of the Loop Switch MS571
GENERAL
4/110
—
General
Target Group
The manual is primarily intended for those requiring information on the applications of MC510 for the
purpose of understanding, engineering, wiring & operation.
The objective of this manual is to provide the technical functions description of MC510.This manual
should be studied carefully before installing, parameterizing or operating the motor control unit. It is
assumed that the user has a basic knowledge of physical and electrical fundamentals, electrical wiring
practices and electrical components.
This document should be used along with MC510 Parameter Description, which provides detailed
information about parameters and their applications.
Use of Warning, Caution, Information and Tip icon
The electrical warning icon indicates the presence of a hazard that could
result in electrical shock.
The warning icon indicates the presence of a hazard that could result in per-
sonal injury.
The caution icon indicates important information or warnings related to the
concept discussed in the text. It might indicate the presence of hazard that
could result on corruption of software or damage to equipment/property.
The information icon alerts the reader to pertinent facts and conditions.
The tip icon indicates advice on, for example, how to design your project or
how to use a certain function
GENERAL
5/110
Terminology
List of the terms, acronyms, abbreviations and definitions that being used in this document.
Abbreviation Term Description
Alarm Alarm is defined as status transition from any state to ab-
normal state. Status transition to abnormal state can be
data crossing over the pre-defined alarm limit.
DCS Distributed Control
System
High level distributed control system
Local Hardwiring A Control Access term describing that MC510 accepts its
commands from the hardwired inputs, when the Local
control authority is enabled.
PCS Process Control System High level process control system
MODBUS TCP Ethernet communication protocol
PTC Positive Temperature
Coefficient
PTC thermistors are semiconductor elements with a very
high positive temperature coefficient.
RCU Remote Control Unit Local control unit with pushbutton and indicator to operate a
device (e.g. motor) from field level.
Remote Fieldbus A Control Access term describing that MC510 accepts its
commands from the fieldbus inputs, when the remote
control authority is enabled.
TOL Thermal Overload
Protection
Protection against overheated caused by overload
Trip A consequence of an alarm activated or an external trip
command from another device to stop the motor or trip the
circuit breaker.
MCC Motor Control Centre Common term for a switchgear used for motor control
and protection.
SOE Sequence of events A record of events with time stamp.
FDR Failure Device
Replacement
Maintenance method for failure device
Related Documentation
1TNC 928206M MC510 Parameter Description
1TNC 928207M MC510 Modbus/TCP Protocol Implementation
1TNC 928208M MConfig User Guide
1TNC 928238M Extension module User Guide
Related System Version
The content of this document is related to MC510 products with the following hardware and firmware
version release,
HW FW
MC510-MT-DC 1.0 1.2
GENERAL
6/110
MC510-MT-AC 1.0 1.2
MP51 1.0 1.2
MP52 1.0 1.2
Until further notice, this document is also applicable for future firmware versions other than those
listed above.
The described functions are designed but may not be fully implemented in all details. Please refer to
the release notes regarding possible restrictions.
Document Revision History
Revision Page(s) Description of change Date
M0201 Initial Edition 12/08/2016
M0202 Update extension module description 24/08/2018
PRODUCT OVERVIEW
7/110
—
Product Overview
Introduction
MC510 is an intelligent motor control and protection device based on current and voltage measure-
ment. It is part of low voltage system family to provide customers the intelligent system solution and
supplied as part of ABB Low Voltage switchgear MNS®.
MC510 is microprocessor-based product providing comprehensive features. Every motor starter could
be equipped with one MC510 device. By predefined parameters, MC510 will provide specific control,
monitoring and protection functions in various motor applications.
Providing with redundant Ethernet interface, MC510 could be integrated into industry control system
and plant management system efficiently and smoothly. Every MC510 device can be accessed to get
actual operating data. Fast response time for alarm and trip makes real time control of production
process possible. Statistical recording of maintenance data, like running hours and number of opera-
tions, assists with predictive maintenance scheduling.
For AC motor and the operated installation this means:
•Reliable protection
•Maximum utilization
•Continuous supervision
•Flexibility
Structure
MC510 Main unit
Main unit is constructed with two parts, the electronics of the motor control unit and the integrated
CT. Main unit is a one type device with the integrated CT range starting from 0.24 to 63A. For motor
rating larger than 63A, interposing CTs should be selected.
Main unit is designed with a mounting rail fixed to the bottom of the device for easy vertical DIN rail
mounting.
Screws and other mounting accessories are also provided for vertical and horizontal screw mounting.
Operator panel
The Operator panel is the user interface mounted on the front door or instrument plate of a drawer.
PRODUCT OVERVIEW
8/110
With control buttons, LED, LCD module (MP51 only), MP51/MP52 provides the functions as motor con-
trol, supervision and parameterizing. One operator panel is provided for each main unit at request.
Extension modules (optional module)
All extension modules are powered by the basic unit. The type of extension modules will be automatic
detected by the basic unit after configured in parameter setting.
DIDO module (MB550/MB551)
The DIDO module MB550 provides four 24VDC digital inputs and two relay outputs.
The DIDO module MB551 provides four 110/240VAC digital inputs and two relay outputs.
AIAO module (MA552)
The AIAO module MA552 provides two RTD inputs, one 0-10V voltage input and one 0-20mA/4-20mA
current output.
Hotspots monitor module (MT561)
The hotspots monitor module MT561 supervises the temperature of power contacts in the drawer by
infrared temperature sensor.
Wireless temperature monitor module (MT564)
The wireless temperature monitor module MT564 supervises the temperature of switchgear bus-bar
by wireless temperature sensor WT01.
Note: Max. 4 extension modules can be connected with MC510 basic unit.
Material
The enclosure of MC510 is made of PA6. Flammability rating of the material is UL 94 V-2 and material is
halogen free.
Colour of the enclosure is RAL 7012.
For detail description of MP51/MP52, please refer to Chapter ‘Accessories’.
PRODUCT OVERVIEW
9/110
Fig 1 MC510 and MP51
MOUNTING
10/110
—
Mounting
Mounting of MC510
Basic dimension of MC510
W X H X D = 123mm X 121mm X 72mm
Typical Installation of MC510
DIN rail mounting, or screw mounting on plate
Fig 1 MC510 in 8E/2 module
Basic dimension of MP51
W X H X D = 91mm X 75mm X 29.3mm
Mounting dimension of MP51
W X H = 84mm X 68mm
Basic dimension of MP52
W X H X D = 91mm X 52mm X 29.3mm
Mounting dimension of MP52
W X H = 84mm X 45mm
The installation details of MC510 and MP5x, please see the related documentation installa-
tion manual.
INTERFACES
11/110
—
Interfaces
Terminal blocks of MC510 are located on the top of the main unit for easy access. There are 3 sets of
I/O terminal blocks and 1 set of RJ12 connector as shown.
Fig 3 Top View Terminal Layout
Fig 4 Side View Terminal Layout
INTERFACES
12/110
Terminal Designations
Terminal name Designation…
Plug/Contacts
Remark
DI0...DI7, COM Digital inputs Cross section 2.5mm2
VL1,VL2,VL3 Voltage input
I0a,I0b RCT input
CCA,CCB,CCI Control relay output
R0a,R0b,R0c,R1a,R1b Relay output
L+,M Power supply 24V DC type
L,N 110-240V AC type
ETH1 Ethernet interface 1 RJ45
ETH2 Ethernet interface 1
MP Interface of MP5x RJ12
L1-T1;L2-T2;L3-T3 Current Measurement Φ 12mm Window
IO-BUS Interface of extension modules
Table 1 Device terminals
Power Supply
Depending on different product type, three types of power supply are available, i.e. 24VDC, 110VAC &
240VAC. Power supply of the device should be always derived from uninterrupted and reliable supply
source.
Power supply Terminal Description
DC L+ 24 VDC +
M 0 VDC
AC L Line
N Neutral
Table 1 Power supply input terminals
Digital Input
MC510 has 8 DIs. Digital inputs are cyclically read. Functions of all digital inputs can be configured by
logic block.
Terminal Description
DI0 Digital Input 0
DI1 Digital Input 1
DI2 Digital Input 2
DI3 Digital Input 3
INTERFACES
13/110
DI4 Digital Input 4
DI5 Digital Input 5
DI6 Digital Input 6
DI7 Digital Input 7
COM Common input of digital inputs
Table 3 Digital inputs with 24VDC supply
i ) For 24VDC, it is recommended to use separate supply source for power supply and digital
inputs especially in the case that DI signals are taken from the field which is located long
distance from MCCs
Fig 5 Illustration of DIs wiring to MC510
Residual Current Transformer
MC510 supports earth fault protection through external Residual Current Transformer (RCT).
Terminal Description
I0a Residual current transformer input A
I0b Residual current transformer input B
Table 2 Residual current transformer terminals
INTERFACES
14/110
i) Different size or types of RCT are available. Refer to MNS Digital Ordering Guide for de-
tails.
ii) It is recommended to short terminals I0a and I0b to avoid potential external disturbance in
case that RCT is not in use.
iii) It is recommended to use STP cable for RCT circuit connections.
Voltage Measurement
Voltage measurement and protections are supported in MC510.
Terminal Description
VL3 Phase L3 voltage input
VL2 Phase L2 voltage input
VL1 Phase L1 voltage input
Table 5 Voltage input terminals
i)When single phase system is selected, voltage measurement is based on phase L1 - phase
L3. Connect L to VL1 and neutral to VL3.
ii)If PT is selected, according to phase sequence, connect the secondary side of PT to VL1 VL2
VL3.
iii)PT type should be single-phase voltage transformer or Yy0 connection for three-phase
voltage transformer.
Current Measurement Terminal
MC510 measures continuously three motor phase currents. The phase current data will be used by the
protection functions and reported to the fieldbus. Phase currents are reported as a value relative to
the motor nominal current In.
Current wires are lead through current sensors from either side of the terminal.
Direction can be either L->T or T->L considering that all currents must have the same direction.
Motor nominal currents above 63A are not measured directly, but instead intermediate current
transformer’s secondary side is connected through MC510 current measurement terminal.
i)When single phase system is selected, current measurement is based on phase L1.
ii)The measurement range of internal CT is from 0.08A to 63A.
Contactor Control Output
MC510 supports various motor starter types. The control of the contactor by MC510 is via internal
output relays (CCA, CCB, CCC(R1) relays) by the microprocessor. There is a interlock between CCA and
CCB to avoid closing together.
INTERFACES
15/110
1) Relay output R0/R1 is to be set as the function of CCC in the control circuits.
2) For external connecting contactors, spark suppression is necessary for all types of
contactors except the AF types to maintain a reasonable service life of relays.
Terminal Description
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
Table 6 Contactor control terminals
Relay Output
MC510 is also equipped with two relay outputs which functions according to project specific settings.
Terminal Description
R0a NC terminal of SPDT
R0b NO terminal of SPDT
R0c Common terminal of SPDT
R1a NO terminal of R1
R1b NO terminal of R1
Table 7 Relay output terminals
The output status of relays may change in responding to different functions assigned.
For external connecting contactors, spark suppression is necessary for all types of contac-
tors except the AF types to maintain a reasonable service life of relays.
Interface for MP51/MP52
MC510 connects with operator panel MP51/MP52 via RJ12 interface, which marked “MP”.
Ethernet communication Interface
Redundant Ethernet communication is provided, in which RJ45 interface is applied, with mark “ETH1”
and “ETH2”.
INTERFACES
16/110
Extension module interface
IO-BUS interface is used for the extension function of basic unit for more complex application. Exten-
sion functions, such as temperature measurement, analog output etc. are implemented separately in
extension modules. IO-Bus interface provides the power supply of extension modules and the data
exchange between MC510 and extension modules.
Typical Diagram
Typical wiring diagrams of different types of MC510 are shown in this section.
MC510 110-240V AC type
Fig 6 Typical wiring diagram for MC510 110-240V AC type
INTERFACES
17/110
MC510 24V DC type
Fig 7 Typical wiring diagram for MC510 24V DC type
Roc is the common terminal of NO and NC contact of R0 relay, output status of NO and NC
contact would change synchronously in responding to different functions assigned
FUNCTIONALIT Y
18/110
—
Functionality
Starter Types
MC510 offers various kinds of motor starting control modes via the control of relay output. It super-
vises the operating state of the contactor according to the feedback of auxiliary contact, predefined
feedback timeout and current.
The following starting control modes are offered:
Starter type
NR-DOL
REV-DOL
NR-DOL/RCU
REV-DOL/RCU
Actuator
NR-S/D
NR-2N
NR-2N Dahlander
Autotransformer
NR_softstater
REV_softstater
Contactor Feeder
Contactor Feeder/RCU
Table 8 Starter types supported by MC510
Starter type is selected with a dedicated parameter to match the wiring for contactor and motor
control circuits.
i) Pin numbers assigned for DIs in below starters are shown as per default settings and
subject to be changed to meet different project engineering.
ii) Spark suppression is necessary for all types of connecting contactors except AF
types through MC510 output relays to maintain a reasonable service life of the output
relays. Interface relays should also be considered in engineering to increase the
FUNCTIONALIT Y
19/110
reasonable service life. Interface relay is recommended to be used for contactor type
A210 and above.
Fig 8 Surge Suppressors on Contactor Coils
Precautious measures shall be taken in system designs to avoid potential high electromag-
netic disturbance which may result in unstable network and malfunction of MC510 relays.
For example, in applications that Variable Speed Drives are used in a large scale, harmonic
filter devices shall be required in system design to reduce the impact to the network.
NR-DOL STARTER
NR_DOL starter is a basic starter type for driving motor to one direction. When start command has
been received from field or local I/O, the contactor control output will be energized and remains this
condition until stop command has been received or any protection function activated.
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
DI5 Contactor control A feedback (F_Ca)
Table 9 NR-DOL starter contactor control interface
The definition of the terminal in the above list is only an example.
FUNCTIONALIT Y
20/110
Fig 9 Control circuit for NR-DOL starter (for MC510)
Operating Sequence for NR-DOL:
Motor is Stopped - > Start1 - > Close CCA
Motor is Running - > Stop - > Open CCA
NR-DOL/RCU STARTER
RCU (Remote Control Unit) is a starter type where contactors are directly controlled by a special
RCU-switch located near the motor. This allows control of the motor even without MC510
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
R1a NO contact of R1
(CCC)
R1b
DI5 Contactor control A feedback (F_Ca)
Table 10 NR-DOL/RCU starter contactor control interface
The definition of the terminal in the above list is only an example.
FUNCTIONALIT Y
21/110
Fig 10 Control circuit for NR-DOL/RCU starter
Operating Sequence for NR-DOL/RCU:
Motor is Stopped - > Start1 - > Close CCA for 1s and open
Motor is Running - > Stop - > Close CCC (R1) for 1s and open
REV-DOL STARTER
REV-DOL uses contactor control output A for controlling the contactor which drives motor to
direction CW and correspondingly contactor control output B is used for direction CCW. When
starting motor to either direction contactor will be energized and is stopped (not energized) by
command (fieldbus or local I/O) or active protection function.
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
DI5 Contactor control A feedback (F_Ca)
DI6 Contactor control A feedback (F_Cb)
Table 11 REV-DOL starter contactor control interface
FUNCTIONALIT Y
22/110
The definition of the terminal in the above list is only an example.
Fig 11 Control circuit for REV-DOL starter
Operating Sequence for REV-DOL:
Motor is Stopped - > Start1 - > Close CCA
Motor is Stopped - > Start2 - > Close CCB
Motor is Running - > Stop - > Open CCA&CCB
REV-DOL/RCU STARTER
The functionality of this starter type is according to NR-DOL/RCU starter with support for revers-
ing use of motor.
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
R1a NO contact of R1 (CCC)
R1b
FUNCTIONALIT Y
23/110
DI5 Contactor control A feedback (F_Ca)
DI6 Contactor control A feedback (F_Cb)
Table 12 REV-DOL starter contactor control interface (for MC510)
The definition of the terminal in the above list is only an example.
Fig 12 Control circuit for REV-DOL/RCU starter
Operating Sequence for REV-DOL/RCU:
Motor is Stopped - > Start1 - > Close CCA for 1s and open
Motor is Stopped - > Start2 - > Close CCB for 1s and open
Motor is Running - > Stop - > Close CCC (R1) for 1s and open
Actuator STARTER
This starter type is for controlling valves and actuators by using limit switches. Limit switches
cause the motor to be stopped when activated and additionally start command is allowed only to
reverse direction. Torque switch is selectable by parameterization.
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
FUNCTIONALIT Y
24/110
R1a NO contact of R1
(CCC)
R1b
DI0 Limit position switch 1 input (Limit1)
DI1 Limit position switch 2 input (Limit2)
DI7 Torque switch input (Tor)
DI5 Contactor control A feedback (F_Ca)
DI6 Contactor control A feedback (F_Cb)
Table 13 Actuator starter contactor control interface
The definition of the terminal in the above list is only an example.
Fig 13 Control circuit for Actuator starter
Operating Sequence for Actuator:
Motor is Stopped with Limit1 and Torque inactivated - > Start1 - > Close CCA for 1s and open
Motor is Stopped with Limit2 and Torque inactivated - > Start2 - > Close CCB for 1s and open
Motor is Running CW - > Limit1 activated or Stop - > Close CCC (R1) for 1s and open CCC (R1)
Motor is Running CCW - > Limit2 activated or Stop - > Close CCC (R1) for 1s and open CCC (R1)
Motor is Running - > Torque activated - > Close CCC (R1)
FUNCTIONALIT Y
25/110
NR-S/D STARTER
Motor start current is reduced in star connection to 1/3 rd of the current in delta connection, with
lower torque during the same time.
Start to delta starting sequence is based on the presented control logic Figure. The changeover
condition is time.
The following guideline applied for selecting parameter values:
Changeover time < Motor startup time
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
R1a NO contact of R1 (CCC)
R1b
DI5 Contactor control A feedback (F_Ca)
DI6 Contactor control B feedback (F_Cb)
DI7 Contactor control C feedback (F_Cc)
Table 14 NR_S/D starter contactor control interface
The definition of the terminal in the above list is only an example.
Fig 14 Control circuit for NR-S/D starter
FUNCTIONALIT Y
26/110
Operating Sequence for NR-S/D:
Motor is Stopped - > Start1 - > Close CCB & CCC (R1) - > Changeover Time - > Open CCB & Close
CCA
Motor is Running - > Stop - > Open CCA & CCB & CCC (R1)
NR-2N STARTER
NR-2N uses two contactors control motor rotation speed, the motor contains separate windings.
Rotation speed can be changed “on the fly” without stop command in between. Low speed (start1)
could be changed to high speed (start2) immediately, and high speed could be changed to low
speed after a changeover time.
Current measurement for NR-2N utilizes two external current transformers measuring current
from motor main supply. External current transformers can be selected separately for both
speeds.
The following guideline applied for selecting parameter values:
Changeover time < Motor startup time
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
DI5 Contactor control A feedback (F_Ca)
DI6 Contactor control A feedback (F_Cb)
Table 15 NR-2N starter contactor control interface
The definition of the terminal in the above list is only an example.
FUNCTIONALIT Y
27/110
Fig 15 Control circuit for NR_2N starter, separate windings
Operating Sequence in NR-2N
Sending command ‘Start1’ (Low Speed N1) to close contactor CCA.
Sending command ‘Start2’ (High Speed N2) to close contactor CCB.
Contactors are latched
Stop command opens CCA or CCB.
Motor can be controlled with sequences.e.g.
Stop -> Start1-> Stop
Stop -> Start2 -> Stop
Stop -> Start1 -> Start2 ->Stop
NR-2N Dahlander STARTER
NR-2N Dahlander uses three contactors control motor rotation speed where motor is equipped
with a three phase winding. Rotation speed can be changed “on the fly” without stop command in
between. Low speed (start 1) could be changed to high speed (start 2) immediately, and high
speed could be changed to low speed after a changeover time.
Current measurement for NR-2N Dahlander utilizes two external current transformers measuring
current from motor main supply. External current transformers can be selected separately for
both speeds.
FUNCTIONALIT Y
28/110
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
R1a NO contact of R1
(CCC)
R1b
DI5 Contactor control A feedback (F_Ca)
DI6 Contactor control A feedback (F_Cb)
DI7 Contactor control A feedback (F_Cc)
Table 16 NR-2N Dahlander starter contactor control interface
The definition of the terminal in the above list is only an example.
Fig 16 Control circuit for NR_2N Dahlander starter
Operating Sequence in NR-2N Dahlander
Sending command ‘Speed1’ to close contactor CCA.
Sending command ‘Speed2’ to close contactor CCB and CCC(R1).
Contactors are latched
Sending stop command to open CCA or CCB + CCC(R1).
FUNCTIONALIT Y
29/110
Motor can be controlled with sequences.e.g.
Stop -> Start1-> Stop
Stop -> Start2 -> Stop
Stop -> Start1 -> Start2 ->Stop
Stop -> Start2 -> Chang over delay-> Start1 -> Stop
.
AUTOTRANSFORMER STARTER
This starter type is used to control autotransformer unit in order to minimize the voltage drop
during motor startup. Autotransformer starter with three contactors supports motor starting
with reduced voltage thus providing reduced motor startup current. The starting torque will be
reduced accordingly.
The following guideline applied for selecting parameter values:
Changeover time < Motor startup time
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
R1a NO contact of R1
(CCC)
R1b
DI5 Contactor control A feedback (F_Ca)
DI6 Contactor control B feedback (F_Cb)
DI7 Contactor control C feedback (F_Cc)
Table 17 Autotransformer starter contactor control interface
The definition of the terminal in the above list is only an example.
FUNCTIONALIT Y
30/110
Fig 17 Control circuit for Autotransformer starter
Operating Sequence for Autotransformer:
Motor is Stopped - > Start1 - > Close CCB & CCC (R1) - > Changeover Time - > Open CCB & Close
CCA
Motor is Running - > Stop - > Open CCA & CCB & CCC (R1)
NR-SOFTSTARTER
Softstarter applications are for controlling motor accessory softstarter device. MC510 gives start
and stop commands to the softstarter unit. The softstarter is set for adjusting motor voltage
with its own parameters. More information about softstarter can be found from softstarter’s
manual.
This starter type supports all protection functions during normal “Running” situation. For motor
start and stop period some of the protection functions are disabled by these parameters.
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
R1a NO contact of R1
(CCC)
R1b
DI5 Contactor control A feedback (F_Ca)
Table 18 NR_Softstarter starter contactor control interface
FUNCTIONALIT Y
31/110
The definition of the DI terminal in the above list is only an example.
Fig 18 Control circuit for NR-softstarter
Operating Sequence for NR-Softstarter:
Motor is Stopped - > Start1 - > Close CCA - > Close CCC (R1)
Motor is Running - > Stop - > Open CCC (R1) -> Ramp down time -> Open CCA
REV-softstarter
This starter is of similar functionality as NR-softstarter starter with additional function on sup-
porting reversing motor.
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
CCB Contactor control B
R1a NO contact of R1
(CCC)
R1b
FUNCTIONALIT Y
32/110
DI5 Contactor control A feedback (F_Ca)
DI6 Contactor control B feedback (F_Cb)
Table 19 REV-softstarter starter contactor control interface
The definition of the DI terminal in the above list is only an example.
Fig 19 Control circuit for REV-Softstarter
Operating Sequence for REV-Softstarter:
Motor is Stopped - > Start1 - > Close CCA - > Close CCC (R1)
Motor is Stopped - > Start2 - > Close CCB - > Close CCC (R1)
Motor is Running - > Stop - > Open CCC (R1) -> Ramp down time -> Open CCA & CCB
Contactor Feeder
Contactor feeder is regarded in MC510 as a specific starter type to provide measurement, control
and protection functionality to a contactor feeder circuit. When start command has been received
from field or local I/O, the contactor control output will be energized and remains this condition
until stop command has been received or any protection function activated.
Terminal Description Remark
CCI Contactor control voltage input
FUNCTIONALIT Y
33/110
CCA Contactor control A
DI5 Contactor control A feedback (F_Ca)
Table 20 Contactor Feeder contactor control interface
i) The definition of the terminal in the above list is only an example.
ii) Power, energy and other parameters related to Power factor are NOT correct and
should not be refer to!
Fig 20 Control circuit for Contactor Feeder
Operating Sequence for Contactor Feeder:
Motor is Stopped - > Start1 - > Close CCA
Motor is Running - > Stop - > Open CCA
Contactor Feeder/RCU
The functionality of this starter type is according to NR-DOL/RCU starter with support for con-
tactor feeder.
FUNCTIONALIT Y
34/110
Terminal Description Remark
CCI Contactor control voltage input
CCA Contactor control A
R1a NO contact of R1
(CCC)
R1b
DI5 Contactor control A feedback (F_Ca)
Table 21 Contactor Feeder/RCU contactor control interface (for MC510)
i) The definition of the DI terminal in the above list is only an example.
ii) Power, energy and other parameters related to Power factor are NOT correct and should
not be refer to!
Fig 21 Control circuit for Contactor Feeder/RCU
Operating Sequence for Contactor Feeder/RCU:
Motor is Stopped - > Start1 - > Close CCA for 1s and Open CCA
Motor is Running - > Stop - > Close CCC (R1) for 1s and Open CCC (R1)
FUNCTIONALIT Y
35/110
Protection Functions
The module provides full protection for motor by supervising three phases voltage, three phases
current, earth fault current, startup time, the state of contactors and the state of main switch.
Responding of protection functions is based on the parameters given by user. The operation of
separate functions is independent thus protection functions can be active at the same time but
the one which indicates the situation first will give a trip for motor.
According to the application, all kinds of protection can be enabled, disabled by the upper level
system or MCU parameter setting tool, also the protection characteristics can be adjusted.
MC510 offers the following protection and supervisory function.
Thermal overload protection
Stall protection
Long start protection
Phase failure protection
Unbalance protection
Unbalance protection
Noload protection
Under power protection
Over power protection
Under power factor protection
Earth fault protection
Undervoltage protection
Overvoltage protection
Phase sequence protection
Start limitation protection
Environment temperature protection*
Hotspots temperature protection*
Busbar temperature protection*
Motor temeprature protection (PTC/PT100/PT1000) *
Table 22 Protection Functions in MC510
* Extension module is required.
FUNCTIONALIT Y
36/110
Thermal Overload protection
Thermal overload protection (TOL) protects the motor against overheating.
The motor thermal condition is simulated by a calculation. The result of the calculation is stored in a
thermal register and can be reported via operator panel or fieldbus interface.
Calculation is accomplished in a different motor operation conditions, principle presented below,
thermal increase and decrease are simulated by TOL protection function for running and stopped
motor.
Fig 22 Principle picture of motor thermal simulation
MC510 simulates thermal conditions in the motor for all operating modes (Running or Stopped).
This permits maximum utilization of an installation and assures safe protection of the motor.
Thermal overload protection simulation accounts for the temperature rise of both the stator
winding and the iron mass of the motor, it gives thorough consideration on the effect of motor
overheating due to three phase unbalance during the simulation calculation of motor thermal
overload.
There are two thermal models supported by MC510: Standard or EEx e. The standard model
makes use of parameters Trip class, t6 in thermal overload calculation. The protection of explo-
sion proof three-phase motors with type of protection ‘increased safety’ EEx e is done with two
special parameters, the Ia/In ratio (stall/nominal current ratio) and Te time.
The following diagram offers the characteristic curve of overload protection, in which the charac-
.
If EEx e thermal overload protection is required, please contact ABB for detailed clarifi-
cation.
FUNCTIONALIT Y
37/110
Fig 23 Trip curve from cold condition
The Maximum thermal capacity level is 100%. Maximum level is reached when motor has been
running with a current 6xIn at the time t6 starting from the cold state in ambient temp. 40°C.
Trip class T6
10A 3-7
10 7-12
20 10-25
30 15-38
Table 23 IEC 60947-4-1 trip class when ambient temp. 40°C, balanced motor current
If motor is in overload condition, i.e. ILmax > 1.14 x TFLC (Thermal full load current multiplier re-
duced by motor ambient temperature), the Overload alarm is active to indicate overload.
In some applications it is beneficial to be able to bypass the TOL protection momentarily because
of the process reasons. The lifetime of the motor will be shortened but it might be more costly to
stop the process.
MC510 provides the function of TOL bypass protection. If the TOL bypass is triggered:
That is, when the motor is running, the thermal capacity value is allowed to reach 200% before a
FUNCTIONALIT Y
38/110
trip occur.
Or when the motor has been tripped due to thermal overload protection, the motor is required to
start urgently when the heat capacity is below 200%.
TOL bypass protection may cause overheating and even fire. This function can be used
only if the customer is clear about the load, even if the motor is required to operate
under overload conditions. Otherwise, it may cause equipment damage, serious injuries
or even death.
Function
Setting range 0=Disabled 1=Enabled 4=Protection bypass1
5=Enabled, and disable during motor startup
Default value 1
Step value 1
Thermal model
Setting range 0=Standard model 1=EEX e
Default value 0
Step value 1
T62
Setting range 3-40s
Default value 6s
Step value 1
Ia/In3
Setting range 1.2-8.0
Default value 5.0
Step value 0.1
Te3
Setting range 5-40s
Default value 5s
Step value 1s
Cool coe.
Setting range 1-10
Default value 4
Step value 1
TOL Alarm Level
Setting range 60-100%
Default value 90%
FUNCTIONALIT Y
39/110
Step value 1%
TOL Trip Level
Setting range 60-100%
Default value 100%
Step value 1%
TOL Reset Level
Setting range 10-60%
Default value 50%
Step value 1%
TOL bypass
Setting range 0=Disabled 1=Enabled
Default value 0
Trip Reset Mode
Setting range 1=Auto 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Ambient Temperature
Setting range 0-80°C
Default value 40°C
Step value 5°C
Table 24 TOL protection parameters
1 The user can trigger the protection bypass command through the input of the digital
or the command from the fieldbus. Then all the options allow the protection bypass are
actived, even if the trip level is reached, MC510 still only sends out the corresponding
alarm information and does not execute the trip command.
2 When Standard thermal model is selected
3 When EEx e thermal model is selected
Stall Protection
Stall protection is used to protect the driven mechanical system from jams and excessive over-
load. Stall protection function uses Imax as the criterion. There are other parameters to be deter-
mined as followed.
FUNCTIONALIT Y
40/110
Function
Setting range 0=Disable 1=Enable 4=Protection bypass
Default value 0
Step value 1
Trip Level
Setting range 120-800%
Default value 400%
Step value 10%
Trip Delay
Setting range 0.0-25.0s
Default value 0.5s
Step value 0.1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 25 Stall protection parameters
The user can trigger the protection bypass command through the input of the digital
or the command from the fieldbus. Then all the options allow the protection bypass are
actived, even if the trip level is reached, MC510 still only sends out the corresponding
alarm information and does not execute the trip command.
Fig 24 Stall protection
FUNCTIONALIT Y
41/110
Stall function activates after motor nominal startup time has elapsed.
The highest measured phase current (ILmax) is compared against the Trip level. When ILmax remains
over the trip level at a time longer than Trip delay, a “Stall” alarm is issued and the contactor
tripped.
Long Start protection
The long start protection protects motor against locked or stalled rotor in starting state. MC510
detects the current after a start command, and signals a fault when current continuously exceeds
a separately set threshold of the period of start time.
Fig 25 Long start protection
Function Enable/Disable
Setting range 0=Disable 1=Enable 4=Protection bypass
Default value 0
Step value 1
Locked rotor Level
Setting range 120-800%
Default value 120%
Step value 10%
Locked Rotor Delay
Setting range 0-250s
Default value 10s
Step value 1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
FUNCTIONALIT Y
42/110
Default value 4
Step value 1
Table 26 Long Start protection parameters
1 The user can trigger the protection bypass command through the input of the digital
or the command from the fieldbus. Then all the options allow the protection bypass are
actived, even if the trip level is reached, MC510 still only sends out the corresponding
alarm information and does not execute the trip command.
Long Start protection activates during motor nominal startup time and disables automatically
after predefined startup time.
The highest measured phase current (ILmax) is compared against the Locked rotor level. When ILmax
remains over the trip level at a time longer than Locked Rotor delay, a “Long Start” alarm is issued
and the contactor tripped.
Phase failure protection
MC510 protects the motor against phase current loss condition. Phase failure protection function uses
ILmin/ILmax (the ratio of lowest ILmin and highest measured phase value ILmax) as the criterion. Function is
suppressed by parameters Motor startup time, Number of phases and Softstart ramp time.
Function
Setting range 0=Disable 1=Enable 4=Protection bypass
Default value 0
Step value 1
Alarm Level
Setting range 10-90%
Default value 80%
Step value 1%
Trip Level
Setting range 5-90%
Default value 70%
Step value 1%
Trip Delay
Setting range 0-60s
Default value 10s
Step value 1s
Trip Reset Mode
FUNCTIONALIT Y
43/110
Setting range 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 27 Phase failure parameters
The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are
actived, even if the trip level is reached, MC510 still only sends out the corresponding
alarm information and does not execute the trip command.
Fig 26 Phase failure protection
ILmin/ILmax is compared against the phase failure Alarm level. When ILmin/ILmax decreases below the Alarm
level, a “Phase failure alarm” alarm is issued.
ILmin/ILmax is compared against the phase failure Trip level. When ILmin/ILmax remains below the Trip level
at a time longer the Trip delay, a “Phase failure trip” alarm is issued and the contactor tripped.
Unbalance protection
MC510 protects the motor against unbalance condition. Unbalance protection function also uses
ILmin/ILmax as the criterion. Function is suppressed by parameters Motor startup time, Number of phas-
es and softstart ramp time.
Function
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass
FUNCTIONALIT Y
44/110
Default value 0
Step value 1
Alarm Level
Setting range 50-90%
Default value 90%
Step value 1%
Trip Level
Setting range 50-90%
Default value 85%
Step value 1%
Trip Delay
Setting range 0-60s
Default value 10s
Step value 1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 28 Unbalance protection parameters
The user can trigger the protection bypass command through the input of the digital or the
command from the fieldbus. Then all the options allow the protection bypass are actived,
even if the trip level is reached, MC510 still only sends out the corresponding alarm infor-
mation and does not execute the trip command.
Fig 27 Unbalance protection
FUNCTIONALIT Y
45/110
ILmin/ILmax is compared against the unbalance Alarm level. When ILmin/ILmax decreases below the Alarm
level, a “Unbalance alarm” alarm is issued.
ILmin/ILmax is compared against the unbalance Trip level. When ILmin/ILmax remain below the Trip level at a
time longer the Trip delay, an “Unbalance Trip” alarm is issued and the contactor tripped.
Underload protection
MC510 protects the motor against underload condition. Underload protection function uses ILmax/In
(the ratio of highest measured phase value ILmax and the rated current of the motor In) as the criterion.
There are other parameters to be determined, such as alarm level, trip level and trip delay. The protec-
tion characteristic is as follows:
Function Enable/Disable
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass
Default value 0
Step value 1
Alarm Level
Setting range 20-90%
Default value 30%
Step value 1%
Trip Level
Setting range 5-90%
Default value 20%
Step value 1%
Trip Delay
Setting range 0-1800s
Default value 10s
Step value 1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 29 Underload protection parameters
FUNCTIONALIT Y
46/110
1 The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are ac-
tived, even if the trip level is reached, MC510 still only sends out the corresponding alarm
information and does not execute the trip command.
Fig 28 Underload protection
The ILmax/In is compared against the Underload Alarm level. When ILmax/In decreases below the
Alarm level an “Underload alarm” alarm is issued.
The ILmax/In is compared against the Underload trip level. When ILmax/In remains below the Trip level
at a time longer than underload Trip delay, a “ Underload trip” alarm is issued and the contactor
tripped.
Noload protection
MC510 protects the motor against no load condition. Practically no load protection is the same func-
tion as underload protection. The function also uses ILmax/In as the criterion.
Function
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass
Default value 0
Step value 1
Alarm Level
Setting range 5-50%
Default value 20%
Step value 1%
Trip Level
FUNCTIONALIT Y
47/110
Setting range 5-50%
Default value 15%
Step value 1%
Trip Delay
Setting range 0-1800s
Default value 5s
Step value 1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 30 Noload protection parameters
1 The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are ac-
tived, even if the trip level is reached, MC510 still only sends out the corresponding alarm
information and does not execute the trip command.
Fig 29 Noload protection
The ILmax/In is compared against the Noload Alarm level. When ILmax/In decreases below the Alarm level a
“Noload alarm” alarm is issued.
The ILmax/In is compared against the Noload trip level. When ILmax/In remains below the Trip level at a
time longer than Noload Trip delay, a “Noload trip” alarm is issued and the contactor tripped.
FUNCTIONALIT Y
48/110
Earth fault protection
There are two ways of earth fault protection in MC510 protects the motor against the earth fault con-
dition.
Direct measurement of zero sequence current through an external RCT
Calculation of zero sequence current by internal calculation through measurement current values
The function is by default suppressed by parameters “Motor startup time” and “Softstarter ramp up
time” to avoid nuisance tripping due to harmonics caused by saturation of the current transformers. In
some cases, it may be required to be switched on during startup in specific project requirements.
This protection is neither intended to be used for pre-emptive isolation supervision nor for
personnel protection against electrical shock. For these applications ABB recommends the
usage of external protection devices (PRCDs / RCDs).
Earth fault protection uses parameters as in the following table.
Function
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass3
Default value 0
Step value 1
Protection based on
Setting range 0=External RCT 1=Internal Calculation
Default valuez 0
Step value 1
Earth Fault Primary
Setting range 1000mA, 5000mA
Default value 1000mA
Step value -
Alarm Level
Setting range 100-3000mA (Earth Fault Primary = 1A) 1
500-15000mA (Earth Fault Primary = 5A) 1
20%-50% In2
Default value 500mA1
20%In2
Step value 100mA1
0.1%In2
Trip Level
Setting range 100-3000mA (Earth Fault Primary = 1A) 1
500-15000mA (Earth Fault Primary = 5A) 1
FUNCTIONALIT Y
49/110
20%-80% In2
Default value 800mA1
50%In2
Step value 100mA1
0.1%In2
Trip Delay
Setting range 0.2-60.0s
Default value 10.0s
Step value 0.1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Earth fault protection is activated during motor startup time
Setting range 0=Disabled 1=Enabled
Default value 0
Step value 1
Table 31 Earth fault protection parameters
1 When “Protection based on = External RCT“ is selected
2 When “Protection based on = Internal Calculation“ is selected
3 The user can trigger the protection bypass command through the input of the digital or the
command from the fieldbus. Then all the options allow the protection bypass are actived,
even if the trip level is reached, MC510 still only sends out the corresponding alarm infor-
mation and does not execute the trip command.
Fig 30 Earth fault protection (I0 = Measured Earth Fault Current)
FUNCTIONALIT Y
50/110
I0 is compared against the earth fault current fault Alarm level. When I0 exceeds above the Alarm level,
an “Earth fault alarm” alarm is issued.
I0 is compared against the earth fault current Trip level. When I0 remains above the earth fault current
Trip level at a time longer than Trip delay, an “Earth fault trip” alarm is issued and the contactor
tripped.
Undervoltage protection
MC510 protects the motor against undervoltage condition as “voltage dip”. The undervoltage protec-
tion function uses ULmin as the criterion. There are other parameters to be determined, such as alarm
level, trip level and trip delay, reset voltage level. The protection characteristic is as follows:
3
Fig 31 Undervoltage protection
The lowest measured main line voltage (ULmin) is compared against the undervoltage alarm level. When
ULmin decreases below the undervoltage alarm level, an “Undervoltage alarm” alarm is issued.
The lowest measured main line voltage (ULmin) is compared against the undervoltage Trip level and
voltage restore level. When ULmin recovers above undervoltage Restore level before Trip delay expires
and motor continues running. If ULmin remains below the restore level at a time longer than Trip delay,
“Undervoltage trip” is issued and contactor will be opened.
When “Autorestart” function is active, “Undervoltage trip delay” will be same as “Max. power
down time” automatically.
Function Enable/Disable
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass
Default value 0
FUNCTIONALIT Y
51/110
Step value 1
Alarm Level
Setting range 50-100%
Default valuez 80%
Step value 1%
Trip Level
Setting range 30-100%
Default value 65%
Step value 1%
Trip Delay
Setting range 0.2-5.0s
Default value 1.0s
Step value 0.1s
Reset Level
Setting range 50-100%
Default value 90%
Step value 1%
Trip Reset Mode
Setting range 1=Auto 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 32 Undervoltage protection parameters
1 The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are ac-
tived, even if the trip level is reached, MC510 still only sends out the corresponding alarm
information and does not execute the trip command.
Overvoltage protection
MC510 protects the motor against overvoltage condition. The overvoltage protection function uses
ULmax as the criterion. There are other parameters to be determined, such as alarm level, trip level
and trip delay, reset voltage level. The protection characteristic is as follows:
FUNCTIONALIT Y
52/110
Fig 32 Overvoltage protection
The maximum measured main line voltage (ULmax) is compared against the overvoltage alarm level.
When ULmax increases bigger than the overvoltage alarm level, an “Overvoltage alarm” alarm is issued.
The maximum measured main line voltage (ULmax) is compared against the overvoltage Trip level and
voltage restore level. When ULmax recovers below overvoltage Restore level before Trip delay expires and
motor continues running. If ULmax remains bigger than the restore level at a time longer than Trip delay,
“Overvoltage trip” is issued and contactor will be opened.
Function Enable/Disable
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass
Default value 0
Step value 1
Alarm Level
Setting range 100-200%
Default valuez 100%
Step value 1%
Trip Level
Setting range 100-200%
Default value 120%
Step value 1%
Trip Delay
Setting range 0.2-5.0s
Default value 1.0s
Step value 0.1s
Reset Level
Setting range 100-200%
Default value 100%
Step value 1%
FUNCTIONALIT Y
53/110
Trip Reset Mode
Setting range 1=Auto 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 33 Overvoltage protection parameters
1 The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are ac-
tived, even if the trip level is reached, MC510 still only sends out the corresponding alarm
information and does not execute the trip command.
Under power protection
MC510 protects the motor against under power condition. Under power protection function uses P/Pn
(the ratio of measured power value P and the rated power the motor Pn) as the criterion.
Alarm level
1. warning 2. start trip delay 3. clear trip delay 4. start trip delay
5. trip 6. trip reset
Trip level
1
.
(P / Pn)
t
Trip delay
2
. 3
. 4
. 5
. 6
.
Fig 33 Under power protection
The P/Pn is compared against the Alarm level. When P/Pn decreases below the Alarm level a “Under
power alarm” alarm is issued.
The P/Pn is compared against the trip level. When P/Pn remains below the Trip level at a time longer
than Trip delay, a “Under power trip” alarm is issued and the contactor tripped.
There are other parameters to be determined, such as alarm level, trip level and trip delay. The protec-
tion characteristic is as follows:
FUNCTIONALIT Y
54/110
Function Enable/Disable
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass
Default value 0
Step value 1
Alarm Level
Setting range 50-100%
Default valuez 50%
Step value 1%
Trip Level
Setting range 30-100%
Default value 30%
Step value 1%
Trip Delay
Setting range 0.2-5.0s
Default value 1.0s
Step value 0.1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 34 Under power protection parameters
1 The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are ac-
tived, even if the trip level is reached, MC510 still only sends out the corresponding alarm
information and does not execute the trip command.
Over power protection
MC510 protects the motor against over power condition. Over power protection function uses P/Pn
(the ratio of measured power P and the rated power of the motor Pn) as the criterion.
FUNCTIONALIT Y
55/110
Fig 34 Over power protection
The P/Pn is compared against the alarm level. When P/Pn increases above the Alarm level an “Over pow-
er alarm” alarm is issued.
The P/Pn is compared against the trip level. When P/Pn remains above the Trip level at a time longer
than Trip delay, a “Over power trip” alarm is issued and the contactor tripped.
There are other parameters to be determined, such as alarm level, trip level and trip delay. The protec-
tion characteristic is as follows:
Function Enable/Disable
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass
Default value 0
Step value 1
Alarm Level
Setting range 100-800%
Default valuez 100%
Step value 1%
Trip Level
Setting range 100-800%
Default value 150%
Step value 1%
Trip Delay
Setting range 0.2-50s
Default value 0.2s
FUNCTIONALIT Y
56/110
Step value 0.1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
Default value 4
Step value 1
Table 35 Over power protection parameters
1 The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are ac-
tived, even if the trip level is reached, MC510 still only sends out the corresponding alarm
information and does not execute the trip command.
Under power factor protection
MC510 protects the motor against underload condition based on power factor. Under power factor
protection function uses measured power factor as the criterion. The protection is masked by motor
startup time or softstarter start time. There are other parameters to be determined, such as alarm
level, trip level and trip delay. The protection characteristic is as follows:
Function Enable/Disable
Setting range 0=Disabled 1=Enabled 3=Alarm only 4=Protection
bypass
Default value 0
Step value 1
Alarm Level
Setting range 1-100%
Default valuez 60%
Step value 1%
Trip Level
Setting range 1-100%
Default value 50%
Step value 1%
Trip Delay
Setting range 0-60s
Default value 10s
Step value 1s
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
FUNCTIONALIT Y
57/110
Default value 4
Step value 1
Table 36 Under power factor protection parameters
1 The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are ac-
tived, even if the trip level is reached, MC510 still only sends out the corresponding alarm
information and does not execute the trip command.
Alarm level
1. warning 2. start trip delay 3. clear trip delay 4. start trip delay
5. trip 6. trip reset
Trip level
1
.
Power factor
t
Trip delay
2
. 3
. 4
. 5
. 6
.
Fig 35 Under power factor protection
The power factor is compared against the Alarm level. When power factor decreases below the Alarm
level a “Under power alarm” alarm is issued.
The power factor is compared against the trip level. When it remains below the Trip level at a time
longer than Trip delay, a “Under power trip” alarm is issued and the contactor tripped.
Phase sequence protection
MC510 protects the motor against wrong phase sequence condition. The protection bases on the
sequence of voltage input while motor is stopped. And while motor is started, it bases on the se-
quence of current. The predefined phase sequence as following,
Voltage: VL1,VL2, VL3
Current: IL1, IL2, IL3
While the protection is enabled, there will be a trip while the measured phase sequence is different
from the predefined sequence.
The function is by default suppressed by parameters “Motor startup time” and “Softstarter ramp up
time” to avoid nuisance tripping due to harmonics caused by saturation of the current transformers. In
some cases, it may be required to be switched on during startup in specific project requirements.
FUNCTIONALIT Y
58/110
Function Enable/Disable
Setting range 0=Disabled 1=Enabled 4=Protection bypass
Default value 0
Step value 1
Trip Reset Mode
Setting range 2=Local 3=Remote 4=Remote&Local
Default valuez 4
Step value 1
Table 37 Phase sequence protection parameters
1 The user can trigger the protection bypass command through the input of the digital or
the command from the fieldbus. Then all the options allow the protection bypass are ac-
tived, even if the trip level is reached, MC510 still only sends out the corresponding alarm
information and does not execute the trip command.
Start limitation
Start limitation helps to protect the motor and also the process against excess number of starts in a
given interval. When the number of starts is reached and the motor is switched off, a new start is pre-
vented. The time interval starts from the first start. After the elapse of the time interval the counter is
reset to the pre-set value. The permissible motor starts per hour can be obtained from the manufac-
turers motor and apparatus data sheet. However, the minimum waiting time between two starts shall
be complied.
The parameterization of the protection function can be the number of starts per time interval or the
time between two consecutive starts. In the first case the user must wait after the trip for the reset to
take place before making a start.
Independent of this function, the motor is protected by TOL function and a start is possible only if the
thermal capacity is below the startup inhibit level. If motor data specifies the number of starts during
a certain time span the advantage of this protection function can be taken of supervising the number
of starts. On some other cases process may put requirements for the motor start number thus this
protection can be employed.
Functionality is presented in the following example. Fig. 36 presents the start limitation protection
with 3 starts allowed.
1) Normal situation, after stop command motor can be started normally, “Start 2”. Every start activates
an internal timer for the time defined by time interval parameter. The number of active timers are
reviewed after every stop command and compared to value of number of starts parameter. Stop
command can thus exist during active or elapsed timer.
2) Two timers are still active, thus stop command generates alarm message "Start limitation alarm"
and one more start “Start 3” is allowed.
FUNCTIONALIT Y
59/110
3) The 3rd start has been executed. A contactor trip and trip message "Start Limitation Trip" alarm will
follow when motor is stopped while there are two active timers, here starting from “Start 1”.
4) Trip can be automatically reset when the first timer from “Start 1” is finished. Motor start is possible
when all pending trips are reset. Supervision continues with a new timer from “Start 4”
Fig 36 Start limitation protection
Function Enable/Disable
Setting range 0=Disable 1=Enable 4=Protection bypass
Default value 0
Step value 1
Time interval
Setting range 1-600min
Default valuez 1min
Step value 1
Number of starts
Setting range 1-100
Default value 2
Step value 1
Trip Reset Mode
Setting range 1=Auto
Default value 1
Step value 1
Table 38 Start limitation parameters
FUNCTIONALIT Y
60/110
1 The user can trigger the protection bypass command through the input of the digital or the
command from the fieldbus. Then all the options allow the protection bypass are actived,
even if the trip level is reached, MC510 still only sends out the corresponding alarm infor-
mation and does not execute the trip command.
Loop environment Temperature protection
MC510 extends the module hotspots module MT561 to monitor the ambient temperature inside the
drawer and prevent the drawer components from being too high, thus causing the drawer to burn
down. MC510 monitors the temperature of drawer environment to decide whether to trigger environ-
mental temperature protection alarm.
For details, please refer to the hotspots module MT561 section of the extended module user guide.
When MT561 is only used for loop environment temperature protection, there is no need to
configure hotspots temperature sensor.
Hotspots temperature protection
By extending the module hotspots module MT561, MC510 monitors the temperature of the inserting in
the drawer to prevent the temperature of the drawer from being too high, which leads to the burnout
of the drawer.
The single insertion temperature measurement is realized by inserting a fixed temperature infrared
sensor IR. MC510 monitors the temperature of one primary connector to decide whether to trigger a
temperature protection.
Fig 37 Hotspots temperature protection
FUNCTIONALIT Y
61/110
For details, please refer to the hotspots module MT561 section of the extended module user guide.
Busbar temperature protection
MC510 monitors the copper temperature in the switchgear by extending the module MT564 to moni-
tor the copper temperature in the switchgear, including the main busbar, the copper platoon of the
ACB cabinet, and the copper row of the fixed circuit.
The bus temperature measurement is realized by self-powered wireless temperature measurement
module WT01, and transmitted to MT564 through Zigbee. MC510 monitors the temperature of the bus
bar to decide whether or not to trigger the bus temperature protection.
Fig 38 WTM temperature protection
For details, please refer to the wireless temperature module MT564 in the user guide of the extended
module.
Thermal protection of motor (PTC/PT100/PT1000)
The thermal protection of the motor is used as a protective condition to determine the protection
function of the PTC/PT100/PT1000 thermistor detector, which is pre buried on the stator winding or
bearing of the motor.
MC510 realizes motor thermal protection through analog input and output module MA552. MC510
according to the measured resistance value, decide whether to turn on the corresponding motor
thermal protection.
FUNCTIONALIT Y
62/110
Fig 39 PTC/PT100/PT1000 temperature protection
For details, please refer to the MA552 section of the analog input and output module in the extended
module user guide.
Analog input signal monitoring function
MC510 monitors the input of analog input in analog input and output module MA552 in real time, and
sends out corresponding signal according to the preset alarm level value and trip level value.
For details, please refer to the MA552 section of the analog input and output module in the extended
module user guide.
Autorestart Function
The line voltage (UL1L3) is supervised continuously. It is possible to automatically restart the motor after
momentary power loss. Two alternative models of auto restart function are provided in MC510: Stand-
ard and enhanced.
When any DI is set to "main switch state" and the main switch state is not input, the auto-
matic restart function will automatically fail.
Function Enable/Disable
Setting range 0=Disabled 1=Enabled
Default value 0
Step value 1
Function mode
Setting range 0=standard 1=enhanced
Default valuez 0
FUNCTIONALIT Y
63/110
Step value 1
Max. autoreclose time
Setting range 0-5000ms
Default value 200ms
Step value 100ms
Max. power down time
Setting range 0-1200s
Default value 5s
Step value 0.1s
Staggered start delay
Setting range 0-1200s
Default value 5s
Step value 0.1s
Table 39 Autorestart function parameters
Autorestart function (standard)
In standard mode, the reaction of the auto restart function depends on the length of the voltage dip.
The following cases show the different reactions of MC510 in different voltage dip situations.
Case 1: Voltage dip< autoreclose time
Fig 40 Autorestart (Voltage dip< autoreclose time)
FUNCTIONALIT Y
64/110
If voltage is restored within the autoreclose time, the motor will be restarted immediately.
Case 2: autoreclose time<voltage dip< Max. power down time
Fig 41 Autorestart (autoreclose time<voltage dip< Max. power down time)
If power is restored after autoreclose time but before max power down time, motor will be restarted
after the staggered start delay time.
Case 3: Voltage dip> Max. power down time
Fig 42 Restart (Voltage dip> Max. power down time)
FUNCTIONALIT Y
65/110
If supply voltage remains below restore level long enough and exceeds max power down time, no au-
tomatic restart will be initiated.
Autorestart function (enhanced)
If the voltage dip is taken more serious, the enhanced autorestart function can be applied.
In the enhanced mode, the reaction of the auto restart function not only depends on the length of the
voltage dip, but also the number of voltage dips within short period of time.
The following cases show the different reactions of MC510 in different voltage dip situations.
Case1: Voltage dip< autoreclose time
Identical to Case1 of standard mode
Case2: autoreclose time<voltage dip< Max. power down time
Identical to Case2 of standard mode
Case3: Voltage dip> Max. power down time
Identical to Case3 of standard mode
Case4: 2xdip<200ms within 1s
Fig 43 Restart (2xdip<200ms within 1s)
If the interval between two voltage dips (which length less than 200ms) is less than 1 second. Auto-
matic delay restart is triggered after second voltage restore.
FUNCTIONALIT Y
66/110
Modbus TCP Failsafe Functionality
MC510 failsafe function supervises the network interface and connection to the remote devices con-
trolling the motor/starter equipment by MC510. Remote device have to refresh the certain MC510
network input variable to indicate that the control is operating normally and the network interface is in
good condition.
If a loss of Modbus/TCP communications for preset timeout value (1-25 seconds) is detected, the
failsafe activates with the parameterized function as follows:
• No operation
• Start motor direction 1
• Start motor direction 2
• Stop motor
When communication failure is detected and activated by MOSBUS TCP failsafe mode, MC510 will
automatically release remote control permissions (if remote control authority has been selected).
IO BUS Failsafe Functionality
MC510 failsafe function supervises the network interface and connection to the extension modules by
MC510. Remote device have to refresh the certain MC510 network input variable to indicate that the
control is operating normally and the network interface is in good condition.
If a loss of IO BUS communications for 200ms is detected, the failsafe activates with the parameter-
ized function as follows:
• No operation
• Start motor direction 1
• Start motor direction 2
• Stop motor
Main Switch Protection Function
When ‘Main switch’ or ‘Test switch’ function is enabled, main switch protection function is enabled
accordingly. Below tables show the logic relationship of main switch protection functions:
‘Main switch’ function is enabled, and ‘Test switch’ function is disabled:
Motor status Main switch status
ON OFF OFF ON
Running Trip Remark*
Stop No operation No operation
Remark*:When main switch status is ‘OFF’, motor can’t be started, i.e. motor status couldn’t be ‘Run-
FUNCTIONALIT Y
67/110
ning’ status.
‘Main switch’ function is disabled, and ‘Test switch’ function is enabled:
Motor status Test switch status
ON OFF OFF ON
Running Stop Stop
Stop No operation No operation
Both ‘Main switch’ and ‘Test switch’ function are enabled
Motor status
Main switch status Test switch status Both main switch and
test switch are ON ON OFF OFF ON ON OFF OFF ON
Running Trip Remark* Trip Remark* Trip
Stop No operation No operation No operation No operation Trip
Remark*:When main switch status is ‘OFF’, motor can’t be started, i.e. motor status couldn’t be ‘Run-
ning’ status.
MC510 Control Authority
Control Authority
MC510 Control Authority is the term describing the privileges on allowing motor control operation
through MC510. It is also a setting parameter in MC510 to define which control access group has privi-
lege to operate the motor via MC510.
Control Access
There are three control access groups defined in MC510,
Local Hardwiring: MC510 accepts its commands from the hardwired inputs
Remote Fieldbus: MC510 accepts its commands from PLC or higher control system via fieldbus, i.e.
MODBUS/TCP.
MP Control: MC510 accepts its commands from operator panel MP5x which locates on the front panel
of each starter unit on switchgear.
CHMI Control: MC510 accepts its commands from CHMI (MV570).
Assign Control Authority
FUNCTIONALIT Y
68/110
There are several means in MC510 to assign control authority and decide which control access group
has the privilege to control.
Local/Remote control authority assignment
Parameter Setting:
Select the access group from parameter setting window (Fig 44). This is the most direct option where
control access is defined by parameterization software.
Fig 44 Parameter Setting of Local/Remote of Control Authority
Multi control access group is supported!
For MC510, only when no DI is assigned Loc/R, Soft Local/Remote could be selected.
Local/Remote Selector Switch
MC510 supports hardwired local remote selector switch function which allows selecting control access
groups via hardwired inputs. To enable this function, one of the digital inputs has to be defined as
‘Loc/R’ in MC510 (Fig45).
FUNCTIONALIT Y
69/110
Fig 45 Assign “Local/Remote” function to Digital Input
Local/Remote Selector Switch will then define if control access goes to “Local “(Local Hardwired) or
“Remote” (Remote Fieldbus). This function does not include the selection of operator panel MP control
which is independent of either “Local” or “Remote” and has to be further defined in this case.
Loc/R Selector
Switch Input
Control Authority
Local Hardwiring Remote Fieldbus MP Enabled in Local MP Enabled in Remote
False input Disabled Enabled Disabled Enabled
True input Enabled Disabled Enabled Disabled
Table 40 “Local/Remote” Selector Switch
MP control authority assignment
The selection of operator panel MP5x control which is independent of either “Local” or “Remote” and
has to be further defined in this case. There are two ways of defining MP5x control access i.e. through
“parameter setting” in parameterization software or through hardwired input.
Parameter Setting
FUNCTIONALIT Y
70/110
Fig 46 MP Control
Select the access group from parameter setting window (Fig 46). This is the most direct option where
control access is defined by parameterization software.
Hardwired Input
Use external selector switch to select MP control. Same as in Local/Remote Selector Switch function,
one of the digital inputs has to be defined as ‘MP Control” to enable the function.
Fig 47 Set DI as “MP Control”
When “MP control” is enabled in one of the DIs, the MP control access option will be gray out.
In another word, Hardwired Selection has privilege over Soft in terms of assigning control
authority.
CHMI control authority assignment
The choice of CHMI control permissions is completely independent of local / remote selection. MC510
provides 2 ways to define control permissions for CHMI human-machine interface, such as parameter
setting through software or input signals through hard wire switches.
Parameter Setting
FUNCTIONALIT Y
71/110
Fig 47-1 CHMI Control Authority
As shown in Fig 47-1, this is the most direct way to set up CHMI control permissions in the local / re-
mote switch input state.
Hardwired Input
Use external selector switch to select CHMI control. Same as in Local/Remote Selector Switch func-
tion, one of the digital inputs has to be defined as ‘CHMI Control” to enable the function.
Fig 47-2 Set DI as “CHMI Control”
When “CHMI control” is enabled in one of the DIs, the CHMI control access option will be gray
out. In another word, Hardwired Selection has privilege over Soft in terms of assigning con-
trol authority.
Main switch protection function
The main switch protection function is based on the protection function of MNS drawer handle opera-
tion. This function monitors the state of the main switch under different motor circuits and enhances
the functional safety of the MNS system.
If you want to turn on the protection, you need to connect the main switch status and the test position
status to the DI of MC510. In this case, the action performance of MC510 is as follows:
Motor
Status
Main Switch State Test Switch State* Close Main Switch &
Test position CloseOpen OpenClose Close CloseOpen OpenClose
Running
(Current
feedback)
Main switch trip -- Current
feedback
trip
Stop Stop Main switch trip
Running
(contactor
feedback)
Main swich trip -- Normal Stop Stop Main switch trip
Stop Normal Normal Normal Normal Normal Main switch trip
FUNCTIONALIT Y
72/110
When MC510 monitors the test position, the "T" will appear on the top right corner of the
MP51 LCD.
The main switch state can be individually connected to MC510 without the need to access the test
position. In this case, MC510 only monitors the state of the DI, and the performance of MC510 is as
follows:
Motor Status Main Switch State
CloseOpen OpenClose
Running(Current feedback) Main Switch trip --
Running(contactor feedback) Main Switch trip --
Stop Normal Normal
The test position state can be accessed to MC510 individually without requiring access to the main
switch state. In this case, MC510 monitors the main switch in real time. When the main switch is in the
test position, MC510 monitors the three-phase current and the "I/O" point state, and allows the con-
tactor control loop to be controlled, but all protection functions based on current and voltage are
invalid. When the input of the switch is defined as the "test position", if the input point is the same as
the set state, the main switch is in the normal working position; on the contrary, the main switch is in
the test position. For example, if the contact type is normally closed, when the input is high, the main
switch is in the normal working position and the high level is cancelled. However, when the main switch
is in the test position but MC510 detects the current (>5% Ie), all the protection functions will be au-
tomatically opened according to the set parameters, while ignoring the "test position". The action
performance of MC510 is as follows:
Motor Status
Test position
Close CloseOpen OpenClose
Running(Current
feedback)
Current feedback trip Stop Stop
Running(contactor
feedback)
Normal Stop Stop
Stop Normal Normal Normal
*When MC510 monitors the test position, the "T" will appear on the top right corner of the
MP51 LCD.
Logic Block
MC510 provides freely programmable logic block functions to carry out additional logic functions for
FUNCTIONALIT Y
73/110
your application.
Logic block function provides several logic modules:
•True table 2I/1O
The function block is used to define the logical relationship between 2 input signals and 1 output sig-
nals.
•True table 3I/1O
The function block is used to define the logical relationship between 3 input signals and 1 output sig-
nals.
•Timer
The function block consists of three modes: power delay output (TON), power off delay output (TOFF)
and pulse output (TP).
Timer Type Time sequence diagram Remark
TP
PT:the pulse time of the TP type
TON
DT:the delay time of the TON type
TOFF
DT:the delay time of the TOFF type
Fig 48 time sequence diagram of timer
•Counter
The function block will change according to the input signal, each effective count input signal, and the
counter value will be increased by 1 or reduced by 1 according to the set counter mode.
FUNCTIONALIT Y
74/110
•Flashing
When the input signal is valid, the function block will output the signal according to the set duty ratio
and frequency. For example, the duty cycle is 50%, the frequency is 0.5 Hz, the output duty cycle is
50%, and the frequency is 0.5 Hz.
Logic block function also provides below operation modules:
•F_Ca/F_Cb/F_Cc
•This function is used to monitor the feedback state of the contactor CCA/CCB/CCC (R1), and is the
level detection mode.Start1/Start2
The local control authority should be opened beforehand before use.
This function is used for hard wiring starting motor. After receiving the starting 1 instructions, the
motor will be running or running at low speed. After receiving the 2 instructions, the motor will reverse
or run at high speed. The function is an edge trigger mode.
•Stop (edge triggering) / Stop (level trigger)
The local control authority should be opened beforehand before use. This function is used for hard
wiring stop motor.Limit1/Limit2
This function is used to install the limit switch. When the function is activated, the motor stops, and
the motor can only reverse control. That is, the limit switch 1, which limits the positive or low speed
operation of the motor, and the limit switch 2, which limits the motor reversing or the high speed
operation of the motor. The function is a level trigger mode.
•Trip Reset
The local reset authority should be opened before use. This function is used to reset the tripping sig-
nal for the edge triggered mode.
•PLC Control1/2
When the function is set to "PLC control 1" or "PLC control 2", and when the action signal is monitored,
the motor will continue to run in one direction or at a given speed until the opposite stop signal is
received.
"PLC control 1" allows the motor to rotate or run at low speed.
"PLC control 2" allows the motor to reverse or run at high speed.
If you want to turn on the PLC control function, you need to set the control authority to local hard wir-
ing.
•Torque Switch
When the function is set to torque switch, when the input signal is opposite to the setting state,
MC510 will release all control relays to stop the motor. This function is a level trigger mode.
•External Trip
FUNCTIONALIT Y
75/110
This function is used to define the external tripping signal, which will cause the motor to trip. When
the signal is effective, the motor is tripped and needs to wait until the signal is lost before it can be
restarted. The signal is a level detection mode.
When the input point does not detect the external tripping input signal, MC510 will reset
automatically.
• MP Control
This function is used to decide whether the operation panel can control the motor. When the function
is set to "MP control", the control authority of MP can’t be changed by parameter settings, and is de-
termined by the state of the input signal of the function. If the input signal is effective, the operation
panel MP can control the motor and vice versa. The signal is a level detection mode.
• Loc/R
This function is used for local / remote state control.
For MC510, if the local / remote input function is valid, the control permissions are local hard wiring; if
the signal is invalid, it is a remote bus. The signal is a level detection mode.
• Test Switch
This function is used to monitor whether the main switch is in the test position. If the main switch is in
the test position, MC510 monitors the three-phase voltage and the various "I/O" point states. MC510
can control contactors, but all protection functions based on current and voltage are automatically
closed, and only the control loop is tested.
When the current value of the monitor is not 0, all protection functions set by the parameter will au-
tomatically turn on. This function protects the motor in the case of contact failure.
The contact is a level trigger mode.
Opening the "test position" function will trigger the monitoring function of the main switch to turn on.
The function of the main switch can be seen in detail as the main switch protection function.
• Main Switch
When the function is set to "main switch state", the monitoring and protection functions of the main
switch will be switched on immediately. The input is the level detection mode.
• Process Interlock1
The process interlock 1 function is used to specify the time to allow the interlocking switch state to
change.
When the motor starts, if MC510 detects that there is no interlocking signal input, and the duration
exceeds the set time, MC510 will operate according to the defined execution mode. When this parame-
ter is set to 0, the interlocking signal must be active before starting the motor. The signal is a level
trigger mode.
FUNCTIONALIT Y
76/110
Fig 49-1 Process interlock1
Case 1: When t1>t2, motor can run normally.
Case 2: When t1<t2, a trip or stop will be performed according to the predefined operation.
If the signal is detected active, the trip will be reset automatically.
• Process Interlock2
The process interlock 2 function is used to specify the time to allow the interlocking switch state to
change.
When the motor starts, if MC510 detects interlocking signal input, and the duration exceeds the time
set by this parameter, MC510 will operate according to the defined execution mode. When this param-
eter is set to 0, the interlocking signal must be inactive before starting the motor.
FUNCTIONALIT Y
7 7/110
Fig 49-2 Process interlock2
Case 1: when t1>t2, motor can run normally.
Case 2: when t1<t2, a trip or stop will be performed according to the predefined operation.
If the signal is detected active, the trip will be reset automatically.
• Emergency Stop
It is used to define the emergency stop device. When the motor is running, once the emergency shut-
down input is effective, the motor will stop running or trip immediately according to the set execution
mode. The motor is not allowed to restart until the input point is cancelled.
The input signal is a level trigger mode.
1)Emergency stop function is not used for functional safety.
2)When the function block does not detect the emergency stop input signal, MC510 will
reset automatically.
•CHMI Control
This function is used to decide whether CHMI can control the motor. When the function is set to "CHMI
control", the control authority of CHMI can’t be changed by the parameter settings, and is determined
by the state of the input signal of the function. If the input signal is effective, CHMI can control the
motor and vice versa. The signal is a level detection mode.
•TOL Bypass
If the thermal overload bypass function is selected and the signal input function block is detected by
MC510, the thermal overload bypass instruction of the motor is issued.
When the TOL bypass function is activated, MC510 allows the thermal capacity trip level to rise to
200% temporarily, that is, the motor can run continuously when the heat capacity is less than 200%,
and does not trip the motor, or allows the motor to start immediately when the heat capacity is less
than 200%.
If the TOL bypass function is to be activated, TOL bypass function must be enabled at TOL protection
window in MCUSetup, and then TOL bypass signal should be given to TOL bypass function block or
from fieldbus. The signal is a level detection mode.
FUNCTIONALIT Y
78/110
TOL bypass function increases the thermal capacity trip level value, which may cause the
equipment to overheat or even burn down.
• Protection Bypass
If the protection bypass function is selected, MC510 will detect the signal input function block and
issue the protection bypass instruction. At this time:
Motor is running. When MC510 detects the protection bypass signal input, all protection functions that
allow the protection bypass are switched to alarm only mode automatically. When the protection by-
pass signal disappears, all the protection functions that allow the protection bypass are restored.
Protection with protection bypass is during trip delay time. When MC510 detects the protection by-
pass signal input, the delay calculation will stop immediately. When the protection bypass signal is
lost, the delay calculation will restart if trip signal is still available.
The motor is tripped, but the trip is not cleared. When MC510 detects the protection bypass signal
input, the trip will be reset immediately. When the protection bypass signal disappears, the trip infor-
mation is redisplayed if the judgment condition of the trip is still available.
After the bypass is protected, the motor may run under dangerous conditions. Please be
careful when using it.
•Digital output relay
This function maps the signal status to the output relay of MC510, and the digital output relay will be
ON or OFF according to the state of the input signal.
All kinds of signals/variables are provides for the input signals of logic modules and operation mod-
ules:
•True/False
•Clock signal
•DI status
•Output of Truth2I1O
•Output of Truth3I1O
•Output of Counter
•Output of Timer
•Output of Flashing
•Alarm signal
•Trip signal
FUNCTIONALIT Y
79/110
•Control authority status
•Motor status
•Switch position
Logic block function could be edited in MConfig and CHMI. Below picture shows an example of logic
block function. For more details of logic block, please refer the ‘MC510 parameter description’ docu-
ment.
Fig 50 Example of Logic Block Program
Maintenance Function
MC510 provides maintenance function for motor by supervising running hours, start numbers, trip
numbers and SOE.
When the maintenance parameter over the predefined alarm level, MC510 will trigger an alarm signal
accordingly. The operation of separate maintenance functions is independent thus these functions can
be active and given an alarm at the same time.
Number of Starts
MC510 counts number of starts. For each startup, MC510 updates the number of starts in memory
map. When start number alarm level exceeds, MC510 will issues an alarm.
Motor running time
MC510 counts motors running hours. When running hours exceeds, MC510 will issue a “running time”
alarm.
FUNCTIONALIT Y
80/110
Insertion cycles
MC510 gets the value of insertion cycles via counting control power cycles. When times of
Insertion cycles exceeds alarm level, MC510 issues an alarm.
MC510 also provides some other maintenance information of motor, which will convenience users to
get the report of motor.
Number of Trips
MC510 counts number of trips and updates in memory map.
Parameter change counters
MC510 counts times of parameter change and updates them in a memory map.
SOE
MC510 provides event recorder data for up to 256 events with time stamp.
Metering and Monitoring
MC510 provides an extensive range of motor operation supervisory functions. Supervisory data are
transmitted via MODBUS TCP to the upper level system for centralized management and also can
directly displayed on the operator panel MP51 if installed on the front of the motor starter module.
Metering and Monitoring
Power Information
Current L1,L2,L3 (A)
Current L1,L2,L3 (%)1
Current Unbalance(%)2
Thermal Capacity (%)
Power Factor
Line Voltages (V)
Frequency (Hz)
Earth Fault Current (A)
Active Power (kW)
Apparent Power (kVA)
Energy (kWh)
Time to TOL trip
Time to TOL reset
Actual Startup Time
Contactor Temperature3
FUNCTIONALIT Y
81/110
Environment Temperature3
Busbar Temperature4
PTC Resistance5
PT100/PT1000 Temperature Value5
Analog input (0-10V) 5
Analog output5
Motor status
Motor status
DI status
Diagnosis
Alarm/Trip for each function
Maintenance
Motor Running Hours
Motor Stop Time
Number of Starts
Number of trips
Number of insertion cycles
Parameter change counter
Pre Trip Phase A/B/C current
Pre Trip Earth Fault Current
SOE
Table 41 Monitoring and metering by MC510
1)Current% measured current compares with nominal current.
For expmple, Current% of L1 = IL1 / In*100%
2)Current Unbalance measured the max. difference between current and average current
with average current. The formula is :
Iave=(IL1+IL2+IL3)/3
Current Unbalance = max(IL1- Iave , IL2- Iave , IL3- Iave )/ Iave *100%
3)Need extended MT561 module.
4)Need extended MT564 module.
5)Need extended MA552 module.
FUNCTIONALIT Y
82/110
Extension modules
Max.4 extension modules are allowed to connect with MC510 basic unit. All extension modules have
the same enclosure dimension design. All extension modules are powered from the basic unit. The
type of extension modules will be automatic detected by the basic unit after they are configured in
parameter setting. The following extension modules are available:
1)DIDO modules MB550/MB551 —— DI/DO extension
2)AIAO module MA552 ¬—— AI/AO extension or motor thermal protection (PTC/PT100/PT1000)
3)Hotspots module MT561 ¬—— Contactor and Environment Temperature Supervision
4)Wireless temperature module MT564 ¬—— Bus bar Temperature Supervision
Fig 51 Max.4 extension modules with MC510 module
For more details, please refer to the document ‘Extension Module User Manual’.
The extension module connected the closest to the basic unit via IO-BUS will be identified as
extension module 1. The modules that follow behind will be identified as extension module 2,
extension module 3, and extension module 4.
FUNCTIONALIT Y
83/110
Communication
MC510 provides two 10/100Mbps Ethernet interfaces. Several protocols are supported, such as Mod-
bus/TCP, SNMP, SNTP, HTTP, TFTP and MRP etc.
Communication interface
Designation Description
Physical interface 10/100 BASE-T
Connector RJ45
Speed 10 /100Mbps
(Yellow LED of RJ45 connector lighted means
communication speed =100Mbps)
Table 42 Ethernet interface
Fig 52 RJ45 pin assignment
Pin no. Signal Description
1 TD+ Transmit +
2 TD- Transmit -
3 RD+ Receive+
4 No connection -
5 No connection -
6 RD- Receive-
7 No connection -
8 No connection -
Table 43 RJ45 pin assignment
Pin 4, 5 are internally shorted, Pin 7, 8 are internally shorted.
FUNCTIONALIT Y
84/110
MODBUS/TCP
MODBUS/TCP is MODBUS over TCP/IP protocol. It is mainly used the monitoring and control of auto-
mation.
MODBUS/TCP implemented in MC510 follows the specification below,
- Modbus application protocol V1.1b
- Modbus Messaging on TCP/IP Implementation Guide V1.0b
Refer to 1TNC928207M0201 for the MODBUS command supported by MC510.
MC510 supports 4 ODBUS/TCP master at the same time.
Modbus/TCP connection
Two-port Ethernet switches are integrated inside MC510. It makes system integration flexible and
econic. Three topologies are supported,
-Start
-Daisy chain
-Ring
Network characteristics
Designation Description
Type of cable Straight or crossed category 5 shielded twisted
pair
Maximum cable length between two adjacent devices 100 m
Maximum number of devices per network segment 160
Maximum number of devices per ring 50
Table 44 Network characteristics
The same network segment must have the same network identifier. For example,
192.168.1.x is in the same network segment, while 192.168.1.x and 192.168.2.x are not in the
same network segment.
FUNCTIONALIT Y
85/110
Topologies
Following figure illustrate the typical topology support by MC510.
Fig 53 Topology
Using ring topology in withdrawable cubicle
The drawers have the characteristics of low downtime. In the low voltage switchgear, the protection
and control equipment of a motor starter are all installed in the same drawer. When the circuit fails, the
user can replace the equipment quickly and conveniently to reduce maintenance hours. Moreover, ring
topology will ensure that replacing any one drawer will not affect the communication quality of the
whole system.
But if two drarwes are withdrawn, as shown in right part of fig 54, even if the system has MRP redun-
dancy function, the situation is totally different. Devices between these two drawers cannot be ac-
cessed anymore.
Here MS571 should be used to ensure stable communication even if two or more drawers are with-
drawn, as shown in left part of fig 54.The MS571 is mounted in the cable compartment instead of
mounted inside the drawer. When draws are withdrawn, MS571 will bypass the withdrawn drawer au-
tomatically to keep communication working in ring.
When the drawer withdraws, the network will spend less than 200ms to re-organize a new
network.
FUNCTIONALIT Y
86/110
Fig 54 Ring topology in withdrawable cubicle
No more than 5 consecutive drawers can be withdrawn in the same ring, otherwise, the
quality of communication will be affected.
Loop switch MS571
The loop switch is used for keeping the Ethernet loop healthy while the withdrawable module with
MC510 is removed. As shown in left part of fig 55, there are 4 RJ45 ports in MS571, 2 ports with MCU
mark are MCU interface to connect to MC510, 2 ports with BUS mark are BUS interface to connect in
Ethernet loop. The principle is shown as right part of fig 55, MC510 is introduced into the Ethernet
loop via MS571. When MC510 is removed, MC510 will be auto bypassed by MS571, so that the ring
Ethernet loop is still available.
FUNCTIONALIT Y
87/110
Fig 55 Loop switch MS571
The power supply of MS571 is provided from the BUS interface. As shown in fig 54, TA60
should be use for connecting the first and last MS571 to external device in one loop. Directly
connecting MS571 to external device may damage the device!
Accessary TA60
Fig 56 TA60
FUNCTIONALIT Y
88/110
The power supply of MS571 can be provided via TA60, there are 3 ports in TA60: RJ45 modular
plug, RJ45 modular jack, and two pair’s redundancy power cables. RJ45 modular plug is used to
connect to external device. RJ45 modular jack is used to connect to MS571 to provide power sup-
ply and Ethernet loop signals. Two power cables should be connected to two redundancy 24VDC
power supplies. The red core is 24VDC+ while the black core is 24VDC-. In case there is only one
power supply, both power cables should be connected to this power supply.
SD card interface
If SD card is detected during MC510 power up, below operation will be executed according to the
preset function in SDFunction.INI file, which is stored in SD card.
Function code Description File name
0x00000000 No operation
0x00000001 Upgrade MC510 boot firmrware from SD card Boot.bin
0x00000002 Upload parameter from MC510 module to SD
card
Para_upload.csv
0x00000004 Upgrade MC510 application firmrware from
SD card
User.bin
0x00000008 No operation
0x00000010 Upgrade extention module firmware of slot1
from SD card Hotspotsmeasurement.bin
/PT100.bin
/PTC.bin
/AIAO.bin
/DIDO.bin
0x00000020 Upgrade extention module firmware of slot2
from SD card
0x00000040 Upgrade extention module firmware of slot3
from SD card
0x00000080 Upgrade extention module firmware of slot4
from SD card
0x00000100 Upgrade operator panel firmware from MP.bin
Table 45 Function code of SD card
PARAMETERIZATION
89/110
—
Parameterization
MC510 can be configured with MP51 or MP52 operator panel keypad, via MCUSetup software, and
through fieldbus if the communication network is available.
Parameterization via MP51
By pressing keypad on MP51 panel, most of the parameters can be set or changed through operator
panel MP51. Details of the parameters menu structure, please refer to “MP51/MP52 Operator Panel’
Chapter.
Parameterization via MConfig Software
Via mini USB-Pin physical interface on MP51 or MP52, users can connect MC510 with computer where
MConfig software is installed and running to complete the parameters setting.
Parameterization via CHMI
All parameters of MC510 are stored in registers, and users can set parameters through CHMI (human
machine interface).
Parameterization via Fieldbus
MC510 parameters are listed in the memory map. The user can parameterize MC510 by MODBUS/TCP
refer to the “MC510 MODBUS/TCP Protocol Implementation”.
MC510 Parameters
MC510 Parameters are listed together with explanations, ranges and default values in separate docu-
ment “MC510 Parameter Description”.
ACCESSORIES
90/110
—
Accessories
MP51/MP52 Operator Panel
Overview
MC510 device provides an operator panel as optional accessory for local operating and parameters
setting to individual motor starter. There are two types of operator panels available, i.e. MP51 and
MP52. MP51 is the operator panel with control buttons, LED indicators and LCD display. MP52 is more
compact in size with control buttons and LED indicators only. Both operator panel types are equipped
with communication port (mini USB connector) in the front for remote parameterizing via engineering
station.
Operator panel is connected to main MC510 device via RJ12 interface (RS485 port) which is located on
the back of the panel.
Fig 57 MP51 Operator Panel
Fig 58 MP52 Operator Panel
ACCESSORIES
91/110
LED Indicators
There are 4 sets of LEDs available in the front of MP5x panel. All LEDs’ color are configurable. Following
table describes LEDs functions and configuration.
LEDs Configurable color Configurable functions
LED1
Power, Running, Stop, Fault, Start1, Start2, Ready to Start,
DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, ready/fault(default, color
can’t be configured), temperature
LED2
Power, Running, Stop, Fault, Start1(default), Start2, Ready to
Start, DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, ready/fault, tem-
perature (default)
LED3
Power, Running, Stop, Fault, Start1, Start2(default), Ready to
Start, DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, ready/fault, tem-
perature (default)
LED4 Power, Running, Stop, Fault, Start1, Start2, Ready to Start,
DI0, DI1, DI2, DI3, DI4, DI5, DI6, DI7, ready/fault, tempera-
ture(default, color can’t be configured)
Table 46 LED configuration
LED functions Meaning of the function
Power MC510 unit is powered up and ready for operation
Running Motor is running CW/N1 or CCW/N2 or feeder is closed.
Stop Motor is stopped or feeder is open
Fault Motor is in faulty status
Start1 Motor is running CW/N1
Start2 Motor is running CCW/N2
Ready to Start Motor is ready to start, i.e. there is no active internal or external trip, motor is not
under emergency stop state (if defined) & Main Switch is ON (if defined)
DIx The status of DIx
Ready/fault LED color for ‘Ready/fault’ function can’t be configured. When motor is ready to
start, the LED turns green; When motor is in faulty status, the LED turns yellow.
Temperature LED color for ‘Temperature’ function can’t be configured. When the temperature
measured by hotspots monitor is in normal range, the LED turns green; Once the
temperature is above the alarm level or MT561 communication failure with the
Basic Unit, the LED turns yellow; once the temperature is above trip level the LED
turns red. If MC510 does not configure hotspot monitoring module MT561, LED
does not display.
Table 47 LED indicator function definition
ACCESSORIES
92/110
LED Status Explanation
On Assigned function is activated.
Wink Alarm active or device is initializing
Off Inactive or off power
Table 48 LED indicator message
i)If MP5x is under parameterization with parametering cable plugged on or scrolling
through setting menus, all LEDs in the front panel wink at the same time.
ii)Additional label of LED should be prepared, if LED is not assigned to default function.
Control Buttons
MP51 provides 7 buttons and MP52 provides 3.
Customer could control motor via buttons on MP51 and MP52. And customer can control motor, do
monitoring and parameterization via buttons on MP51.
Button Function Remark
Start 1 button, to Start motor CW/N1
Start 2 button, to Start motor CCW/N2
Stop button, to Stop motor Also used to reset fault trip
Enter button, to enter selected menu Only in MP51
Down button, to show next messages or menus Only in MP51
Up button, to show past messages or menus Only in MP51
Back button, to exit selected menu or go back one step. Only in MP51
Table 49 MP51/52 Button Icons
ACCESSORIES
93/110
Monitoring value display
After power on, MP51 initially enters Monitoring Values display stage, during which all values, alarms,
trips and control authority can be displayed here.
Fig 59 View of monitoring value display window
•Page Title: At the top of the LCD to show the tag name.
•Main display Area: Main display area to display process data.
•Test Switch: show test switch is active.
•Indication Type: At the left side of the bottom of the LCD to show the type of the indication
(Alarm/Trip).
•Indication text: Following Indication Type to show the detail alarm/trip message
•Control Authority: show control access
Icon Meaning
Alarm
Trip
Local control is active
Remote control is active
Test switch is active
01, highlighted, DI1* status is closed
02, not highlighted, DI2* status is open
Table 50 Description of icons displayed on MP51
ACCESSORIES
94/110
*) The number stands for the port of DI. Status of each DI is available on MP51.
Displaying parameters
MP51 supports up to 16 running parameter windows/pages. Users are free to choose any or all of the
parameters to be shown on MP panel and masked out unwanted information.
User can navigate through displaying pages by pressing “Up” or “Down” button.
Page No. Meaning
1 Current (A)
2 Current (%)
3 Line Voltage
4 Power Related (include Power, Apparent Power, Power factor)
5 Thermal Capacity
6 Frequency
7 Energy
8 Ground Current
9 Time to TOL Trip/Reset
10 DI Status
11 Startup Time
12 Current Unbalance
13 Extension Module 1
14 Extension Module 2
15 Extension Module 3
16 Extension Module 4
Table 51 Parameters on different displaying page
i)“Enter” button is NOT active when scrolling through running parameter windows.
ii) Table 51 shows the actual sequence of displaying pages on MP51.
Alarm message
Alarm message will come up on the bottom of the display window as shown in fig 59 with indication
icon whenever there is an alarm active. Possible alarm messages include the following,
ACCESSORIES
95/110
Thermal Capacity Overload Phase Failure
Phase unbalance Underload Noload
Earth Fault Undervoltage Overvoltage
Autoreclose Feedback Welded Contactor
Start limitation Communication failure Running time
Start number Watchdog Ready to trip reset
Hotspots Temperature Drawer Environment Temperature WTM CH1 Temperature
WTM CH2 Temperature WTM CH3 Temperature WTM CH4 Temperature
More detail alarm information, please refer to 1TNC928207M MC510 Modbus TCP Protocol
Implementation.
Trip message
Trip message will come up on the bottom of the display window as shown in fig 59 with indication icon
whenever there is a trip active. Possible trip messages include the following,
TOL Stalled rotor Phase Failure
Phase unbalance Underload Noload
Earth fault Undervoltage Overvoltage
Feedback Communication failure Start Limitation
Feeder Trip Long start Emergency Stop
External Trip Current Feedback Main switch off
Hotspots Temperature WTM CH1 Temperature WTM CH2 Temperature
WTM CH3 Temperature WTM CH4 Temperature
More detail trip information, please refer to 1TNC928207M MC510 Modbus TCP Protocol
Implementation.
ACCESSORIES
96/110
The Menu Tree
Press “Back" button at monitoring value display window to enter the main configuration menu
Fig 60 View of menu
Press “Back" button at the main configuration menu to enter running parameter window.
•Page Title: At the top of the LCD to show the tag name or submenu table
•Highlighted Item: The current active menu item
•Current Number: At the right of the top of the LCD to show the number of the current selected menu
item
•Total Number: At the right of the top of the LCD to show total menu item numbers in the current
page.
•Hint: At the bottom of the LCD to describe the current highlighted item or the related value of the
highlighted item.
Press Up/Down button, could move the highlight to previous/next items.
Press “Enter” button to enter next level of menu.
Press “Back” button to go back to previous level of menu.
ACCESSORIES
97/110
Fig 61 View of main configuration menu tree
ACCESSORIES
98/110
•Parameter
Within this submenu all motor related parameters can be configured.
More details about parameter, please refer to “MC510 parameter description” document.
•Operator Panel
Within this submenu LCD display and LED indication can be configured.
More details about parameter, please refer to “MC510 parameter description” document.
•Time Setting
Within this submenu actual time can be configured. Below table shows the organization of the
different parameter masks in the menu tree.
Level 1 Level 2
Time Setting Year
Month
Day
Hour
Minute
Second
Week
Table 52 Menu tree of time setting
•Maintenance
Within this submenu all motor related maintenance can be configured. Below table shows the
organization of the different parameter masks in the menu tree.
Level 1 Level 2
Maintenance SOE
Running Time
Stop Time
Start Number
Stop Number
Trip Number
ACCESSORIES
99/110
Last Trip Current (%)
Last Trip Current (A)
Last Earth Fault Trip Current
Insertion cycle counters
Parameter change counters
Table 53 Menu tree of maintenance
•Product Info.
Within this submenu, information of MC510 and MP51 can be read. Below table shows the organization
of the different parameter masks in the menu tree.
Level 1 Level 2
Maintenance MC510 Firmware version
MP51 Firmware version
IP Address
Subnet Mask
Gateway Address
Type of Extension Module 1
Firmware Version of Extension Module 1
Type of Extension Module 2
Firmware Version of Extension Module 2
Type of Extension Module 3
Firmware Version of Extension Module 3
Type of Extension Module 4
Firmware Version of Extension Module 4
Table 54 Menu tree of product info
•Backup & Download
“Backup” feature is to read the parameters from MC510 device and create a backup file in MP panel.
“Download’ feature is to download the backup file from MP panel to MC510 device.
This feature can be quite useful when similar parameters are required for several MC510 devices. It is
easy to operate on site.
Table 57 shows the organization of the different parameter masks in the menu tree.
ACCESSORIES
100/110
Level 1 Level 2
Backup & download Backup Parameter
Download Default Parameter
Download Backup1
Table 55 Menu tree of backup & download
1)Download Backup' option will not be available until the 'Backup Parameter' function has
been executed.
2)Remember to change slave address after copying parameters from other device to avoid
communication problem.
Backup Parameter: save current parameter to backup register in MP51.
Download Backup: download the parameter in backup register into MC510
•Test
Select this submenu, MC510 will test itself for a few seconds and feedback.
Test function is only for manufactory.
Adjusting Parameters
Select the item at the last level of Parameter and press enter, a window for password input will appear.
Input the correct password to enter the parameter adjusting window.
Fig 62 Process of enter parameter adjusting window
1)Default password is 1111.
ACCESSORIES
101/110
It is recommended to change the default password after first login.
There are two types of parameter adjusting window: Numerical Value adjusting window
and Option Selecting window.
When finish, press “Back" button to confirm window. Then select confirm and press enter to download
new parameter to MC510.
Fig 63 Process of confirm parameter adjusting
The slave address could be revised and downloaded to MC510 via MP51.
•Adjusting a Numerical Value
This type of window allows a numerical value to be specified within the given limits. Press up/down
button will increase/decrease the digit. Once the value is set, press “enter” button to acknowledge it.
i)The information of given limits of parameters is provided in ‘MC510 parameter
description’ document.
ii) Keep pressing up/down button will changing the speed of increase/decrease the digits.
iii)When the value reaches the limit, it will automatically count backwards even if the same
button is pressed.
The following example shows how to set the startup time to 10s.
Fig 64 Example of numerical value adjusting
ACCESSORIES
102/110
Start editing the value by pressing the “Up” button. If reach 10, press enter button.
•Selecting an Option from a List
This type of window allows an item to be selected from a given list of options. With the up/down keys
you can scroll through the list. The highlighted selection shows current position within the list.
Pressing “Enter” button to confirm and then press ‘Back’ button to exit.
Pressing ‘Back’ button exits the dialog and discards the selection.
i)The details of given options of parameter are available in ‘MC510 parameter description’
document.
The following example shows how to set the starter type to NR_2N Dahlander
Fig 65 Example of options selecting
Parameterization port
The parameterization port on MP5x panel is a mini USB type of interface. Once this port is connected
with parametering cable, the communication between MC510 main device and MP5x panel is
temporarily stopped with a ‘parameterizing’ status message shown on LCD. No operation is allowed
during parameterizing.
ACCESSORIES
103/110
Fig 66 Parameterizing message
MC510 parameters can be uploaded and downloaded from the parameterization device via the
interface.
Rememer to cover up the mini USB port after parameterization finished.
Connection
Operator panel is connected to the terminal on MC510 via RJ12 interface. The connection shown below
includes power supply and communication.
Fig 67 Connection between MC510 and MP5x
If MP51 can’t get information from MC510, “No Comm.” will be shown in LCD the window.
Fig 68 No Communication message
ACCESSORIES
104/110
If MP51 does not get correct information from MC510, “Comm. Error” will be shown in LCD the window.
Fig 69 Communication error message
Parameterization Software: MConfig
MConfig software is used to set parameter. It exchanges data with MC510 via RS485.
Fig 70 Parameterization interface
Fig 71 MConfig window
ACCESSORIES
105/110
The parameterization software available with following function:
•Edit parameters
•Export parameter to a file
•Import parameter from a file
•Update MC510’s parameters
•Download MC510’s parameters
•Read MC510’s parameters
•User management
The parameterization software can run on all of the following PC operation system:
Windows 2000, Windows XP, Win 7 and Win 8.
For more information on how to do the parameter setting through MConfig software,
please refer to separate document “MConfig User Guide“
APPENDI A TECHNICA L DATA
106/110
—
Appendi A Technical Data
A.1 Common Technical Data
Environmental conditions
Installation DIN rail, or M4 screwing mounting
Storage -40 ~ +85℃
Operation -10 ~ +60℃
Humidity 15% up to 95% without dew
Degree of protection IP20
Derating accepted operating altitude 4500m
Without derating operating altitude 2000m
EMC Environment 1) Equipments in the system comply with EMC requirement of
CE / CCC certificate.
2) Power supply system complies with IEC61000-2-1,
IEC61000-2-2, especially the system in which VSD / Frequency
Converters are used.
EMC Standards
Electrostatic discharge IEC61000-4-2 Level 3
Electromagnetic field immunity IEC61000-4-3 Level 3
Electrical fast transient/burst immunity IEC61000-4-4
Power supply, Level 4
Others, Level 3
Surge immunity IEC61000-4-5 Level 3
Conducted disturbance immunity IEC61000-4-6 Level 3
Radiated disturbance EN55011/CISPR 11, Class A
A.2 Technical Data of the Basic Unit MC510
Low voltage switchgears
IEC60947-1 Low voltage switchgear and controlgear” Part1: General rules
IEC60947-4-1 Low voltage switchgear and controlgear” Part4: Contactors
and motor-starters, Section one-Electromechanical
contactors and motor-starters
APPENDI A TECHNICA L DATA
107/110
Main circuit
Rated operation voltage (Ue) up to 400/690VAC
Rated insulation voltage (Ui) 800VAC
Rated impulse withstand voltage (Uimp) 8KV, overvoltage category III
Degree of pollution 3
Rated operation current (Ie) 0.24-63A
Trip rating 115% of TFLC
Rated frequency 50/60Hz
Control circuit
Rated operational voltage (Ue) 24V DC ,110 or 240 VAC
Rated insulation voltage (Ui) 250VAC
Rate impulse withstand voltage (Uimp) 4kV for AC circuit
Rated operational current (Ie)
relay output 2A /24VDC(DC-13)
4A/120VAC(AC-15)
2A/240VAC(AC-15)
Rated frequency 50/60Hz
Response timing accuracy
TOL protection ±5% of tripping time (I≤3Ie)
±20% of tripping time (I>3Ie)
Stall protection 200 ~ 350ms
Earth fault protection
Others
-30 ~ +30ms
0 ~ 150ms
Power supply
Rated operational voltage (Ue) 24VDC , 110 or 240VAC
Voltage operation range 85%-110% Ue
Power consumption
24VDC 110VAC 240VAC
Typical 3W 6VA 16VA
Maximum starting current 600mA
APPENDI A TECHNICA L DATA
108/110
Digital input(DC)
Number of digital input 8 with one common connection
Logic 1 15…30V
Logic0 0…5V
Digital input (AC)
Number of digital input 8 with one common connection
Logic 1 110VAC type, 79…110V
240VAC type, 164…240V
Logic0 110VAC type, 0…20V
240VAC type, 0…40V
Communication interface
Protocol Modbus/TCP
Baud-rate 10/100M bps
Installation
Mounting DIN rail: On TS35 DIN
Screw: with 3 rolling screws M4 (max. tightening torque
2Nm)
Dimension 123mm(W) X 121mm(H) X 72mm(D)
Terminal wiring size 0.2…2.5mm2
Terminal tightening torque M3 /0.5…0.6Nm
Metering accuracy
Phase current Range: 0.4-8 ×phase CT primary amps
Accuracy: ±2% or ±0.01A, whichever is greater
Earth fault current Measurement:
Full scale: 1.2 × RCT nominal current
Accuracy: ±2% RCT primary
Internal Calculation:
Full scale: 2 × In
Accuracy: ±2% In
Line voltage Voltage metering range: 110V - 690V
Accuracy: ±2%
Power Accuracy: ±5% or ±0.1kW, whichever is greater
APPENDI A TECHNICA L DATA
109/110
A.3 Technical Data of the Operation panel MP51/52
Installation Front panel or door installation
Degree of protection IP54 from front
LEDs 4, function and color configurable
Buttons MP51: 7
MP52: 3
A.4 Technical Data of the Loop Switch MS571
Installation DIN rail
Max. continuous bypass number 5
Power supply 24VDC, through TA60
Power consumption 0.1W
APPENDI A TECHNICA L DATA
—
Visit us
https://new.abb.com/low-voltage/products/ switchgear
1TN
C9282
05M
0202 R
EV
B 2
018.8
© Copyright 2018 ABB. All rights reserved.
Specifications subject to change without notice.