project epq

Upload: farhan-liefa

Post on 08-Apr-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/7/2019 Project EPQ

    1/6

  • 8/7/2019 Project EPQ

    2/6

    As we know, once a supply is connected to a

    three phase induction motor a rotating

    magneticfield will be set up in the stator, this

    will link and cut the rotor bars which in turn will

    induce rotorcurrents and create a rotor field

    which will interact with the stator field and produce rotation. Ofcourse this means that the

    three phase induction motor is entirely capable

    of self-starting.The need for a starter therefore is

    not, conversely enough, to provide starting but

    to reduceheavy starting currents and provide

    overload and no-voltage protection.There are a

    number of different types of starter including

    The Direct On-line Starter, The Star- Delta

    Starter, Auto-Transformer and Rotor

    resistance.

    IV. Direct-on-LineDirect-on-line (DOL) is the simplest form motor

    starting method had being used. It is a traditionally

    started and stopped by applying and removing the

    supply from the circuit. During starting, the full

    voltage are acceptable to used, but to avoid large

    starting current from occur, the voltage starter need to

    be reduced. The DOL starter comprises a switch and

    an overload protection relay as shown in figure1.

    Figure 1.Direct-On-Line motor starter.

    The switch may be manual or automatically depends

    on the user. In previous, manually operated load

    break switch are used, but more commonly an

    electromagnetic contactor are used which can be

    opened by thermal overload relay. Contactors

    arecontrol by separated star and stop button and

    auxiliary contact used to hold the supply when the

    start button is release. By applying full line voltage to

    the motor winding during motor starting, it will draw

    a very high inrush current up to 6 to 7 times rated

    motor current and sometimes it may increase up to 9

    to 10 times the rated current exist. Using this starting

    method, will produce a very high starting torque and

    usually higher than required for most application.For

    a very short time, to establish the magnetic field in

    the iron. This inrush current are valued in between

    V. Star-DeltaStar-delta motor starting method are also known as

    soft starting method. Star-delta starting is when the

    motor in connected in STAR connection during

    starting sequence. The motor then connected to

    DELTA when it accelerated to close to the normal

    running speed. In order to allow the motor to start,

    the motor windings are configured in a star formation

    to the supply voltage. The voltage is supply to the

    individual motor windings therefore it reduced by a

    factor of this connection amounts to

    approximately 30% of the delta values. By using this,

    it reduced to one third of the direct starting current

    (DOL). Due to the reduction of starting torque, the

    star-delta connection is suitable for drives with high

    inertia mass but a resistance torque which is low or

    only increased speed. After motor run-up, in most

    cases an automatic timing relay controls the switch-over from star to delta. The run-up using star

    connection should last until the motor reach the

    operational value. During the switching from star to

    delta, the will be an occurrence of high current as

    seen with direct-on-line starting. During delta

    connection, the full mains voltage is applied to the

    motor windings. To enable a switch-over from star to

    delta, the six ends of the motor winding are

    connected onto terminals. Figure 2 shows the star-

    delta motor starting wiring.

  • 8/7/2019 Project EPQ

    3/6

    Figure 2: Star-delta motor starting wiring

    This method can only be used if when the starting

    works is light loaded. If the motor start in heavily

    loaded there will not be enough torque to accelerate

    the motor up to speed required.

    VI. AutotransformerAn autotransformer starter uses an auto transformer

    to reduce the voltage applied to a motor during start.

    By having a number of output taps such as 50%, 65%

    and 80% to be set-up to provide a single stage starter

    or a multistage starter enable the motor to be started

    at one or more of these settings. There are two ways

    of connecting an autotransformer starter, first, by

    applying full voltage to the transformer via a

    contactor and connect the motor to the tap by means

    of the contactor. The tap contactors will opens or

    disconnecting the motor from the transformer and

    another contactor closes connecting the motor to the

    supply when the motor has accelerated to full speed

    or has run out of acceleration torque. This is known

    as an open transition starter and it is less than ideal

    due to the fact that the motor is disconnect for a short

    period of time during the start period. While the

    motor is connected and accelerating, it also acts as a

    generator until the rotor field decays. The voltage

    generated by the motor is not synchronized to the

    supply, and so on reconnection to the supply, the

    voltage across the contactor at closure can be as

    much as twice the supply voltage resulting in a veryhigh current and torque transient. The transition

    switching or known as auto-reclose effect as it yields

    similar characteristic to opening and closing a

    breaker on a supply to the motor. By using

    autotransformer motor starting method, it can reduce

    the torque as the square of the applied voltage. Figure

    3 shows the autotransformer motor starting wiring.

    Figure 3. Autotransformer motor starting wiring

    VII. Result & Discussion

    In this paper the power quality event that occur in

    the system due to the different motor starting are

    review by using the PSCAD (Power System CAD)

    software.There are three type of motor starting are

    being consider in this paper which is Direct-On-

    Line(DOL), Star-Delta and Autotransformer.

    During DOL motor starting, the motor are connected

    direct to the load and having a breaker function as a

    switch and a transformer used to isolate the motor

    circuit from the power supply as shown in figure 4

    below. The motor torque are fixed to 5NM and speed

    of motor van be varied from 0 to 10 rad/s.

    Figure4. Direct-On-Line motor starting circuit

    From figure 4, loads are connected in parallel to the

    motor. A volt meter and ammeter are connected to

    the load and when motor starting it results voltage

    sag to the loads. During motor starting, the inrush

    current occurs in the induction motor starting and it

  • 8/7/2019 Project EPQ

    4/6

    causes the voltage and current terminal to drop in

    magnitude. Graph 1 and 2 shows the voltage and

    current output at load.

    Graph1. Voltage Sag occur in DOL motor starting

    Graph2. Current Sag occur in DOL motor starting

    In star-delta motor starting connection, the same load,

    motor and transformer are used from DOL motor

    starting connection as shown in figure 5. The

    difference is that, these circuits are using two breaker

    functions as switch to change connection from star

    supply for motor starting and to delta supply when

    the motor reach the operation speed.

    Figure 5.Star-Delta motor starting circuit

    Once again a volt meter and ammeter are connected

    to the load connection to measure the voltage and

    current flow through load. As shown in graph 3 and

    4, the voltage and current sag are still occur but this

    time it less than the DOL voltage and current sag.

    Graph 3 and 4 also shows that waveform drop for a

    moment and then back to the normal when the motor

    already reach the operational speed.

    Graph 3.Voltage sag occur in star-delta motor starting

    Graph 4. Current sag occur in star-delta motor starting

    Same as star-delta starting connection, this circuit

    still using same motor, transformer, breaker and load.But this time, three autotransformer are added to the

    circuit function as a supply to the motor as shown in

    6.

  • 8/7/2019 Project EPQ

    5/6

    Figure 6.Autotransformer motor starting circuit

    As shown in graph 5 and 6, the voltage and currentsag still occur at the load but this time drop value are

    less compare with the other two starting method.

    Graph 5. Voltage sag occur in autotransformer motor starting

    Graph 5.Current sag occur in autotransformer motor starting

    VIII. ConclusionElectrical power quality which is one of the topics for

    several power utilities all over the world, and its

    becoming an important and challenging issue for the

    power engineers. There is no unique model can be

    used to assess the power quality problem and to

    identify and classify them properly.

    By using PSCAD software to create power quality

    event (voltage sag) due to different motor starting

    method, shows that out of three methods, the star-delta method are the one that only method that

    produce small amount of voltage and current sags

    and at the same time it repair back the signal compare

    with the other two method.

    In order to repair or solve back this problem, a few

    solutions have being suggested due to problem

    occurred. By installing an Uninterruptable Power

    Supply (UPS) will help the system to maintain the

    supply when there is any disturbances occur in the

    system. There is several types of UPS are available

    depending on the problem such as Standby UPS,

    Online UPS, and Hybrid UPS. Each UPS has its own

    advantage and disadvantage but Standby UPS are

    commonly used out of the other two types of UPS.

  • 8/7/2019 Project EPQ

    6/6

    REFERENCES

    [1] D.Saxena, K.S. Verma and S.N. Singh, Power Quality Event

    Classification: An Overview and Key Issues,

    InternationalJournal of Engineering, Science and Technology,

    Vol.2, No. 3, 2010, pp.186-199.

    [2]John Stones and Alan Collinson , Special Feature: IntroductionPower Quality, Power Engineering Journal April 2001.

    [3] Amaya Barona, Francisco Ferrandis, Javier Olarte and Jose L.

    Iribarren, New Power Quality Solutions Especially Designed for

    Industrial Application, 9th

    International Conference, Electrical

    Power Quality and Utilization, Barcelona, 9-11 October 2007.

    [4] T.L. Tan, S. Chen, S.S. Choi, An Overview of Power Quality

    State Estimation.

    [5] Christopher J. Melhorn, Mark F. McGranaghan, Interpretation

    and Analysis of Power Quality Measurement.

    [6] MasoudAliakbarGolkar, Electric Power Quality: Types and

    Measurement, 2004 IEEE International Conference on Electric

    Utility Deregulation, Restructuring and Power Technologies

    (DRPT2004) April 2004 Hong Kong

    [7] DharshanaMuthumuni, PSCAD Essential Tutorials: Getting

    Started and Basic Features, dm/Tutorial_gettingstarted.doc,

    Revision 2, Feb 16, 2007

    [8] A. El Saeed, M. Tantawi, K. Youssef, Power Quality

    Phenomena in Academic Building, Paper accepted for

    presentation at PPT 2001,2001 IEEE Porto Power Tech

    Conference, 10th

    13th

    September,Porto,Portugal.

    [9] Barry W. Kennedy, Power Quality Primer McGraw-Hill,2000

    [10]Henk de Swardt,Star-DeltaStarting and Dual VoltageMotors

    Explained.Vector is the Journal of the Institution of Certified

    Mechanical and Electrical Engineers and the Journalof South

    African Institute of Electrical Technician Engineer,10/2007

    [11] Rockwell Automation,Basic for pratical operation: Motor

    Starting.

    [12]Allen-Bradley, Rockwell Software,WYE-DELTA AND SOLIDSTATE STARTER APPLICATIONGUIDEEXPLANATION AND

    ASSISTANCE FOR APPLYINGSOLID STATE SOFT STARTERS IN

    TRADITIONALREDUCED VOLTAGE APPLICATIONS

    [13]Ana Iacob,Electrical Power Quality Improvement

    using a DSP Controlled Active Power Filter,9th

    International

    Conference, Electrical Power Quality and Utilisation.

    Barcelona,9-11 Oct 2007