proKlima introduction 1
• proKlima is the further development of underfloor heating
• Tailored to fit in with modern building technology, the system fulfils the functions of heating-cooling and ventilation and also allows the laying of cables
• The floor construction height is only 125 mm to the upper edge of the screed
• proKlima is the most cost-efficient alternative to cooling ceilings and provides a whole range of additional options and functions!
proKlima
proKlima introduction 2
• As a result of the ventilation duct beneath the heated (or ventilated) floor construction, the floor screed acts as a large additional heat exchanger.
• When either heating or cooling
is required, the usual temperature differences are reduced for output transfer.
The Principle
proKlima introduction 3
• Heat transfer takes place from the pipes to the screed AND to the airflow.
• This unique principle offers
great advantages for heating-cooling and ventilation
The Principle
• Parts of the floor construction are left hollow..
• Whilst the upper side is fitted with heating and cooling pipes, the underside serves the purpose of ventilating with help from the 30 mm gaps.
• We call this part of the floor the dynamic surface.
The Construction
proKlima introduction 4
Presentation of the air connection Heating- Cooling - Ventilation
proKlima introduction 5
Dynamic and static surfaces
• Dynamic surfaces are located in rooms with supply air inlet. The size is based on the air treatment (heating, cooling of the air in the floor).
Dynamic surface
Static surface
Differentiation
proKlima introduction 6
The following construction is required above the upper edge of the floor:• min. 125 mm with cement screed• min. 115 mm with floating screed
.
Assembly Variation 1
proKlima introduction 7
Cable and pipes intersect air passages
The following construction is required above the upper edge of the floor:• min. 155 mm with cement screed• min. 145 mm with floating screed
Assembly Variation 2
proKlima introduction 8
• The cooled floor surface acts as thermal mass cooling in the conventional sense.
• However, by inserting air into the floor area, the performance-reducing “cold air pocket” is omitted.
• Consequently, the cooling capacity is considerably beneath the values of thermal mass activation!
Cooling
proKlima introduction 9
The regulator can take over the fundamental regulating functions to supply the heating and cooling surfaces in accordance with load.
A switch between heating and cooling takes place automatically. In addition, the corresponding supply temperature is regulated. To ensure the cooling function, a dew point sensor is connected.
System wiring
proKlima introduction 10
• During the cooling procedure, the heat transfer coefficient α on the floor amounts to about 5 W/m2K.
• By inserting air into the floor area, this value increases to approx. 8 W/m2K.
Cooling
Cooling capacity
When Vzu = 5 m3/m2h and Δt = 4 K, qK is approx. 50-70 W/m2.
proKlima introduction 11
• Near floor-to-ceiling windows, slot outlets ensure a thermally optimal compensation of the glass surfaces.
• Furthermore, round inlet openings can also be provided as induction or air outlets.
• For a curtaining effect on large window surfaces, our system partner Krantz TKT can fit special outlets.
Air outlets
proKlima introduction 12
• Floor displacement diffuser
• Stainless steel outlet
• Slot outlet
• Round outlet
• Window covering outlet
• Special productions
Air outlets
proKlima introduction 13
• In August 2006, a 2001 system was examined by TÜV Rheinland.
• The system performed outstandingly and without complaint
Hygiene
proKlima introduction 14
WETENSCHAPPELIJK EN TECHNISCHE CENTRUM VOOR
HET BOUWBEDADARF
Materialprüfanstalt für das Bauwesen Dresden
Materialprüfungs- und Versuchsanstalt Neuwied
Rheinland PfalzLandesuntersuchungsamt
Institut für Hygiene und Infektionsschutz
Tested and certified
Example office building:Electro- and Air-distribution
proKlima introduction 15
proKlima introduction 16
Further references
• Office building in Frankfurt
• BV Knepper, Kern-Haus Wegberg.
• Boarding house of the Commerzbank, Frankfurt
• Health centre in Wilbertoord (NL)
Reference projects
proKlima introduction 17
• Single family house in Cologne with conservatory
• Special outlets were manufactured to cover the approx.7m high glass facade
• Planning Arch. Luczak
Reference project
proKlima introduction 18
Doctor´s surgery in Cologne
Planning: Arch. Luczak
Reference projectLobbe Holding, G.A. Edelhoff in Menden
Planning Arch. Hilker, Iserlohn
Office lofts in the Brügger Mühle in ErkrathPlanning Haustechnik PBS und Partner
proKlima introduction 19
Headquarters of Bode Energie- und Sicherheitstechnik, Göttingen
In this case, the projected cooling capacity of the system is approx. 55 W/m2.
The system also has a complex cable network of data carrying cables in the floor
Pre-assembled system with mounting units for power supply units
Reference project
20
Headquarters of Kern-Haus in Ransbach-Baumbach
Reference project
Serviced apartments in Neuwied (AWH)
Example:proKlima in the Hotel Dormylle
• Highest level of comfort and innovative system
• No additional loss of space through visible technology
• Energy management with optimised energy and CO2 consumption
• Cosy and comfortable,living, sleeping and working in a hotel
• Heating, cooling and an adequate supply of fresh air must be ensured
• Simple and comfortable control of the technology by the hotel guest
• Architect must be able to design the rooms freely
• Easy maintenance
• Simple cleaning
Assignment and requirements set out by the investor and operator
HeatingUntil recently, this is what heating looked like.
CoolingAttractive internal and external units?
The solution to this complex problem?
BuildingYear of construction 2006Heated and cooled area 1100m² 42 Luxury rooms
Planning All 42 rooms are equipped with proKlima
Control proKlima Lisa control unit
Heat and cooling generator 40 kW2 water/water heat pumps in cascade with 20 kW
VentilationCentral device with 4000m³/h
Hotel Dormylle
Comfort
To obtain comfortable living, sleeping and working in a hotel, an adequate air circulation must be ensured.
Heating and cooling and an adequate supply of fresh air with a high level of comfort is guaranteed by proKlima
Via simple setting of the required room temperature on the room thermostat in every hotel room
Simple control of room temperature
Example:Brügger Mühle in Erkrath
Developing the grounds with the old production halls of a paper factory in an excellent spatial location into a modern energy-efficient industrial and office estate.
• Freedom of architectural design
• Sustainable increase in the building‘s value
• Lowering the operating costs
• High level of living and working comfort
• Quick and flexible room specific temperature changes possible
Task
The implementation
• Use of surface rainwater
• Active cooling via heat pumps
• Heating capacity of the heat pumps 260 kW (mono-valent operation)
• proKlima-Application in the complete office area of 3.300 m²
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
CO2-BalanceBrügger Mühle in Erkrath
0
20.000
40.000
60.000
80.000
100.000
34.503
83.982
CO2-Balance Heating and Cooling in kg/a
erneuerbare Energie Gasbrennstoff
Saving approx. 59%
Equivalent to 250.000 kilometres driven in a private car!!!
Source: CommonCunsult
Improvement of the COP of heat pumps in association with proKlima
Living and working in “Siebengebirge”
A new district developsOver 100 years after the opening of Cologne’s Rheinauhafen, this once lively handling site is experiencing an ambitious conversion.
Living in the “Siebengebirge”The building is divided into individual houses in accordance with the gables. Each has its own development core. On the upper storeys, a total of 138 apartments were created with a view of the Rhine.
Working in “Siebengebirge ”The ground floors of the building are reserved for purely commercial purposes.
In a building with demanding tenants, contemporary building services are:
• Thermal comfort in winter and in summer.
• Supplying the offices and conference areas with fresh and filtered air.
• Installation of an electrical and media supply which is as invisible as possible.
The release speed of the air is max. 0.2 m/s and is nearly unnoticeable.
Living and working in „Siebengebirge“
proKlima® in the office
proKlima® in the office Conference room
proKlima® in the office Standard office in modular dimensions
proKlima introduction 46
Centre for Integrative Medicine
in Koblenz
Medical centre and care unit
approx. 4800m²
Rheinland PfalzLandesuntersuchungsamt
Institut für Hygiene und Infektionsschutz
Hygiene certification and building inspection and approval:
Reference project
47
The North Rhine-Westphalian federal state government is creating a new state prize for architecture, residential development and urban planning. The state prize is to be awarded at regular intervals in the future for current focal topics. The first federal prize concentrates on the issue of “Energy-efficient Construction for the Future”. The contractors are the Ministerium für Bauen und Verkehr (ministry of construction and transport) together with the Ministerium für Wirtschaft, Mittelstand und Energie (ministry for Economic Affairs and Energy) of North Rhine-Westphalia of the state of North Rhine-Westphalia. Firm cooperative partners for this award procedure are the Architektenkammer Nordrhein-Westfalen (chamber of architects) and the Ingenieurkammer Bau Nordrhein-Westfalen (North Rhine-Westphalian chamber of engineers) for this year’s topical prize.
State prize for architecture, residential development and urban planning North Rhine-Westphalia 2008
“Energy efficient buildng for the future”
Experience proKlima in Cologne Basic conditionsArea : ca. 180 m²Window 26m² East(Single glazing) 26m² WestSteel frames (Total 52 m²)
Flat roof 10cm Glass woolFloor: Unheated cellar
Technical data:proKlima: 120m²Stat. surface 88m²Dyn. surface : 32m²Air volume VRoom: 450m³
48
Experience proKlima in Cologne
49
From 15.3°C to 21.5 °C in approx.2 to 2.5 hours
Experience proKlima in Cologne
50
From 16°C to 22 °C room temperature in approx. 3 hours
Experience proKlima in Cologne
51
16.3 Kelvin heating of the supply air with proKlima as a reheater
03.12.2008
proKlima
Passive cooling from proKlima with only ventilation
With a temperature difference of 6 Kelvin and an air flow rate of 1600 m³/h, this corresponds to a passive cooling capacity of 3000W or 25 Watt/m² as peak value.
Diagram of passive cooling capacity by proKlima without the use of cooling through a water cycle or supply air.
Active cooling from proKlima
proKlima
Heating simulation
Cooling simulation
EnvironmentPossibly the most important goal!
Consumption of less energy whilst maintaining the highest level of living and working comfort has become possible.
In heating operationThrough low system temperatures in comparison to convectors or underfloor heating
In cooling operationBy using geothermal probes or groundwater for passive cooling without aditional cooling devices
Economical and ecological advantages of proKlima
Optimal conditions for the operation of heat pumps
This sets proKlima apart from other systems
Hygiene:Statement by the state laboratory of Rhineland-Palatinate concerning our proKlima system (here: surgery rooms of a doctors’ practice in Koblenz).
Fire Prevention: Statement by the MPA Dresden concerning our proKlima Flexakanal duct system (here: escape routes / corridors)
Coefficient of longitudinal sound damping near the floor-mounted ventilation ducts: Test report of the ITA; (crosstalk attenuation / telephony noise in the Flexakanal, reduction of sound transmission by the duct system, here the inspection with stationary air as the most critical case). Impact sound reduction near the floor-mounted ventilation ducts: Test report by the Institute for noise and heat insulation, (impact sound improvement of the Flexaboden duct system)
Structural analysis: Test report by the WTGB for the stationary load of the duct system