protec - aei cablesaeicables.com/literature/protecleaflet.pdf · however protec cables are capable...
TRANSCRIPT
www.aeicables.co.uk
Screened Wiring CablePROTEC
Updated to meet newrequirements of BS 8436:2011
BASEC approved
PROTEC CABLESManufactured and designed to BS 8436 and IS 273
Independently tested by and fully BASEC approved
Protec Low Smoke Zero Halogen screenedwiring cables are available in two options:
(i) Protec - A screened 300/500V cable for usein walls, partitions and voids. Designed to meetthe requirements of IET wiring regs 17th edition(incorporating amendment No 1 2011) Section 522.6
Operates up to 40 amp type B current breakerin the event of a nail penetrating, protectingagainst personal injury.
(ii) Protec Power - A screened 600/1000V cable foruse in general power applications offering increasedcurrent rating and a wider range of conductor sizes.
Designed to meetthe Requirements ofthe BS 7671 17th EditionIET Wiring Regulationsincorporating amendment No 1: 2011.
ISO 9001 Quality Management System
• Multipurposeapplications
• Impact resistant• Abrasion resistant• Reduced
electromagneticinterference
• Reducedinstallation time
• Small• Robust• Lightweight• Easy to bend• Easy to dress• Retains its shape• Full size CPC• LSZH sheath
The new Protec Power Cable
Protec and ProtecPower cables meet
the requirements of BS 8436 and IS 273
respectively, includingthe nail penetration test
PROTEC Manufactured and designed to BS 8436
300/500 volts.Voltage Rating
Screened cable for use in walls, partitions andbuilding voids where there is a risk of damageor penetration from nails, screw fixings etc.
Description
Solid or stranded plain copper conductors, XLPEinsulation, full size earth, aluminium tubed screen,LSZH sheath.
Construction
-25ºC to +90ºCOperatingTemperature
6 x overall diameterMinimumBending Radius
2 core Bn, Be. 3 core Bn, Blk, Gy. 4 core Bn, Blk, Gy, Be.CoreIdentification
100m. Other lengths availableLengths
White. Other colours availableSheath Colour
ManufacturingStandard
Code of Practice
BS EN 50267 (IEC 60754) Acid Gas EmissionBS EN 50268 (IEC 61034) Smoke EmissionBS EN 50265, 50266 (IEC 60332) Flame Propagation
Fire PerformanceEmissionsand Flame
Propagation
Minimum temperature for installation purposes is 0ºCOnce installed and fixed can operate to -25ºC
Special Notes
BS 8436
BS 7671
PROTECTechnical Data
General Notes
1 The above current ratings are taken from Table 4D2 (max conductor operatingtemperature of 70ºC) as required by the 17th Edition of the IET Wiring Regulations.However Protec cables are capable of operating at 90ºC in which case the higher currentratings of Table 4E2 can be used providing it has been ascertained that the equipmentconnected to the conductor is suitable for the higher conductor operating temperature.
2 Protective devices used for these cables shall be either Type B to BS EN 60898 orType B RCBO to BS EN 61009-1. The protective devices shall have a maximum letthrough energy (l2t) of 42000A2s when used with 1.0mm2 or 1.5mm2 cable and 60000A2s when used with 2.5mm2 or 4.0mm2 cable.
3 AEI Cables reserves the right to amend the product information without noticeor liability. The information is considered accurate at the time of going to print.
4 For larger sizes and power cable applications please refer to our Protec Powercable overleaf.
No. ofCores & Current Rating
Voltage DropNominal (Clipped Direct)
Cross Maximum dcSectional Single Three Single Three Conductor NominalArea of Phase Phase Phase Phase Resistance Overall Nominal Gland
Conductor ac or dc ac dc ac ac @ 20ºC Diameter Weight Ref
no x mm2 Amps Amps mV/A/M mV/A/M mV/A/M Ω/Km mm Kg/Km
2 x 1.00+ 15 - 44 44 - 18.10 7.1 71 FG1
2 x 1.50+ 19.5 - 29 29 - 12.10 8.0 88 FG1
2 x 2.50+ 27 - 18 18 - 7.41 9.0 127 FG1
2 x 4.00 36 - 11 11 - 4.61 10.4 181 FG2
3 x 1.00+ - 13.5 - - 38 18.10 7.5 85 FG1
3 x 1.50+ - 17.5 - - 25 12.10 8.5 112 FG1
3 x 2.50+ - 24 - - 15 7.41 9.4 154 FG2
3 x 4.00 - 32 - - 9.5 4.61 11.2 230 FG2
4 x 1.00+ - 13.5 - - 38 18.10 8.3 107 FG1
4 x 1.50+ - 17.5 - - 25 12.10 9.4 139 FG2
4 x 2.50+ - 24 - - 15 7.41 10.5 191 FG2
4 x 4.00 - 32 - - 9.5 4.61 12.4 285 FG3
+ Solid conductors
PROTEC POWERManufactured and designed to IS 273
600/1000 volts.Voltage Rating
A light, robust, screened cable for use in powerapplications, which require a moderate level ofmechanical protection and a cleaner power supplyfor EMC purposes.
Description
Stranded plain copper conductors, XLPE insulation,full size earth, aluminium tubed screen, LSZH sheath.Construction
-25ºC to +90ºCOperatingTemperature
6 x overall diameterMinimumBending Radius
2 core Bn, Be. 3 core Bn, Blk, Gy. 4 core Bn, Blk, Gy, Be.CoreIdentification
100m (other lengths available)Lengths
Black. Other colours availableSheath Colour
ManufacturingStandard
Code of Practice
BS EN 50267 (IEC 60754) Acid Gas EmissionBS EN 50268 (IEC 61034) Smoke EmissionBS EN 50265, 50266 (IEC 60332) Flame Propagation
Fire PerformanceEmissionsand Flame
Propagation
Minimum temperature for installation purposes is 0ºCOnce installed and fixed can operate to -25ºC
Special Notes
IS 273
BS 7671
PROTEC POWERTechnical Data
General Notes
1 The above current ratings are taken from Table 4E2 (max conductor operatingtemperature of 90ºC). It must be ascertained that the equipment connected to theconductor is suitable for the higher conductor operating temperature.
2 AEI Cables reserves the right to amend the product information without noticeor liability. The information is considered accurate at the time of going to print.
3 For information on screened cables to BS 8436 for use in partitions and buildingvoids, please refer to our range of Protec cables on the previous page.
No. ofCores & Current Rating
Voltage DropNominal (Clipped Direct)
Cross Maximum dcSectional Single Three Single Three Conductor NominalArea of Phase Phase Phase Phase Resistance Overall Nominal Gland
Conductor ac or dc ac dc ac ac @ 20ºC Diameter Weight Ref
no x mm2 Amps Amps mV/A/M mV/A/M mV/A/M Ω/Km mm Kg/Km
2 x 1.00 19 - 46 46 - 18.10 7.3 82 FG1
2 x 1.50 24 - 31 31 - 12.10 8.9 102 FG1
2 x 2.50 33 - 19 19 - 7.41 10.0 140 FG2
2 x 4.00 45 - 12 12 - 4.61 10.7 184 FG2
2 x 6.00 58 - 7.9 7.9 - 3.08 12.7 272 FG3
3 x 1.00 - 17 - - 40 18.10 8.7 107 FG1
3 x 1.50 - 22 - - 27 12.10 9.5 123 FG2
3 x 2.50 - 30 - - 16 7.41 10.4 166 FG2
3 x 4.00 - 40 - - 10 4.61 12.5 253 FG3
3 x 6.00 - 52 - - 6.8 3.08 13.5 349 FG3
4 x 1.00 - 17 - - 40 18.10 9.4 127 FG2
4 x 1.50 - 22 - - 27 12.10 10.3 148 FG2
4 x 2.50 - 30 - - 16 7.41 12.5 231 FG3
4 x 4.00 - 40 - - 10 4.61 13.1 290 FG3
4 x 6.00 - 52 - - 6.8 3.08 14.9 431 FG3
* Larger sizes available on request
About us
AEI Cables has been making cable for over 170 years,satisfying many diverse markets and applications around the world.
With a reputation for product excellence and ourcapability to deliver the goods to global projects,AEI Cables has an enviable position as a worldclass manufacturer.
Online
Visit us online and find out more about AEI Cables:
• View all of our products and technical data
• Use our popular ‘Cable Wizards’
• Get useful information from our ‘Click & Learn’section or test your cable knowledge and play‘AEI Cable Trumps’
• Register to receive all the latest company andindustry news via E-Bulletin
www.aeicables.co.uk
Product Range
• Fire Protection Cables
• Bespoke Customer Cables
• Industrial Cables
• Mining Cables
• Oil and Gas Cables
• Defence Cables
• Power Cables
• Rail Cables
PROTEC CABLESManufactured and designed to BS 8436 and IS 273
AEI CABLES, DURHAM ROAD, BIRTLEY, CO DURHAM. DH3 2RA
Tel: +44 (0)191 410 3111 Fax: +44 (0)191 410 8312 E-mail: [email protected]