protection 101
TRANSCRIPT
Substation Protection and Control
• Substations:• Connect Transmission and Distribution lines to form the
“Grid”
• Transform Voltage for maximum efficiency of power delivery
• Provide locations of equipment for control and monitoring of the grid
Substation Protection and Control
Transmission Lines
Bus
Transformers
Distribution Lines
Breakers
Miscellaneous
Substation Protection and Control
• Intelligent digital relays calculate fault location based on impedance
• Potential Overreach Transfer Trip (POTT) scheme used to increase accuracy
• Line Current Differential provides high speed tripping for faults on the line
• Reclosing allows minimal down time for lines when faults are short-term
Protection examples– Transmission Lines
Substation Protection and Control
Protection examples– Transmission Lines– Potential Overreach Transfer Trip
Substation Protection and Control
Protection examples– Transformers
• Intelligent digital relays dedicated to High voltage and Low voltage protection• These relays are required to work in harmony for all
around protection
• Transformer Differential provides high speed tripping for faults occurring in the windings
Substation Protection and Control
Protection examples– Bus
• Various Bus configurations provide unique requirements to ensure every segment of the system is protected• Single Bus
• Dual Bus
• Ring Bus
• Bus Differential measures and compares current on each of the connections to the bus
Substation Protection and Control
Protection examples– Breaker Failure
• Scheme trips electrically adjacent breakers to interrupt the path from power sources to the fault
• Older methods used electromechanical, manually resettable lockout switch to apply a trip to the electrically adjacent breakers
• Through substation modernization and IEC 61850, messages can be sent electronically through the network to have neighboring relays trip breakers in failure conditions
• For breaker failure on transmission lines, BFTT schemes utilize fiber or other communication methods to send a signal to the remote end of the line to trip the remote breaker to isolate the fault
Substation Protection and Control
Protection examples– Breaker Failure on a One-and-a-Half Breaker Scheme
Substation Protection and Control
Protection examples– Substation Controls
• Breaker Bay Control and Protection utilizes a digital relay to provide overcurrent
• The aforementioned relay also asserts “Open” and “Close” commands to the breaker and line / bypass switches that are motor operated
• These commands are sent manually from SCADA networks or the local station HMI
Substation Protection and Control
Recent Projects
• 115kV and 34kV Breaker Replacements
- Line and Breaker Protection Upgrades
- P&C Elementary and Wiring Design
• 115/34kV Substation Protection and Integration Upgrade
• Steam Generation 34kV Intertie & Generator Protection, Integration and Control engineering support
• Hydro Generator Protection & Automation Upgrades
• Coordination, Equipment Rating and Arc Flash Studies
• References• IEEE C37 Series• “Protective Relaying Principles and
Applications” by J.L. Blackburn• Casco Systems Engineering
• Graphics Provided by:• Electrical 4 u – Electrical Bus System And
Electrical Substation Layout• Atlantic City Electric• Casco Systems Engineering
P r o t e c t i o n 1 0 1C a s c o S y s t e m s L L C
C h r i s M c G o n a g l e
Thanks for Listening