pryda trussed
TRANSCRIPT
-
7/24/2019 Pryda Trussed
1/24
PRYDA FLOOR TRUSS SYSTEMS ................2
INTRODUCTION ............................................................................3
FACTORS AFFECTING FLOOR PERFORMANCE ........................4
PERMANENT LOADS....................................................................5
SERVICEABILITY...........................................................................6
SPAN TABLES ................................................................................7
RESIDENTIAL FLOORS ....................................................................7
COMMERCIAL FLOORS...................................................................8
INTERNAL WALLS.........................................................................9
INTERNAL NON-LOAD BEARING WALLS .......................................9
NON-LOAD BEARING WALLS UNDER ..........................................10
LOAD BEARING WALLS UNDER ...................................................10
EXTERNAL WALLS .....................................................................11
FLOOR OPENINGS......................................................................12
DUCTS FOR MECHANICAL SERVICES ..................................14
CANTILEVERS..............................................................................14
STRONGBACKS ..........................................................................15
STABILITY BRACING................... ..................................... ......17
SUPPORT AND CONNECTION DETAILS ................................17
FIXING AT SUPPORTS ...............................................................20
PRODUCT BENEFITS .................................................................20
PRYDA RAFTER TRUSS SYSTEMS.............21
INTRODUCTION ..........................................................................21
PRODUCT BENEFITS .................................................................21
LOADING.......................................................................................21
SPAN TABLES ..............................................................................22
SERVICES .....................................................................................23
TIE DOWN AND FIXING DETAILS ............................................23
FACTORS AFFECTING PERFORMANCE ................................23
BRACING ......................................................................................24
Information for designers on the principles behind the design of Pryda open web parallel
truss floor and rafter truss systems and to incorporate relevant details within their specifications.
CONTENTS
P R Y D A T R U S S S Y S T E M S
GUIDE TO SPECIFICATIONPRYDA FLOOR TRUSS & RAFTER TRUSS SYSTEMS
P R Y D A T R U S S S Y S T E M S
October 2004
-
7/24/2019 Pryda Trussed
2/24
TOP CHORD SUPPORTEND DETAIL(Page 19)
END DETAIL
(Page 17)
STANDARDEND DETAIL
(Page 17)
STRONGBACKS
(Page 15)
STAIR OPENING DETAILS
(Page 12)
DUCTS/SERVICES
(Page 14)
EXTERNALCANTILEVERS
(Page 14)
STABILITY BRACING
(Page 17)
PRYDA LONGREACH TRUSS
(Page 3)
PRYDA SPAN TRUSS
(Page 3)
INTERNAL SUPPORTS
(Page 10)
INTERNALCANTILEVERS
(Page 14)
INTERNAL BRACING
WALLS (Page 9)PRYDA FLOOR TRUSS SYSTEMS
NOTE: Illustrations used in this gui de showing only Pryda Longreach details also apply to Pryda Span.Where Pryda Longreach and Pryda Span are shown together in the same illustration it signifies that thedetails apply to both products, but the two products should not be used together as il lustrated.
-
7/24/2019 Pryda Trussed
3/24
Right Way Up Wrong Way Up
P R Y D A F L O O R T R U S S S Y S T E M S 3
Pryda Floor Truss Systems are a complete structural
system for timber floors made up of flooring material,
floor trusses, strongbacks, connections and bracing.
They have been proven over many years and provide
occupiers with floors that have an excellent andpredictably reliable performance.
The timber for these trusses is on flat, which provides a
stable platform during installation and minimises theoverall depth required. All trusses use commonly
available timber and most floor trusses in Australia are
made from 70 mm or 90 mm dry timber.
There are two different types of web systems for these
trusses. Both have timber chords but Pryda Longreach
uses all-timber webs, while Pryda Span uses metal webs
for the diagonals and timber webs for the verticals.
Both systems of Pryda floor trusses are generally made toorder by licenced fabricators. While there are standard end
details that allow trusses to be trimmed on site, this
practice is not common. This is not only because alltrusses are designed for an exact span for economic
reasons, but the interaction between the true span of the
trusses and the flooring should be considered for proper
dynamic performance assessment.
INTRODUCTION
Pryda Longreach TrussesLongreach trusses are a premium performance product
using nailplated, all-timber trusses of any depth, but
typically 300 mm deep for residential floors and 400mm deep for commercial floors.
Pryda Longreach trusses are referenced as FT200,FT250, FT300, FT350 and FT400, where FT means
Floor Truss, and 200 is the nominal overall depth
(mm). The actual depth dimensions are in nominal size
steps, or may be individually specified as required for
the particular project.
Right Way Up Wrong Way Up
Pryda Span TrussesPryda Span trusses have metal diagonal webs for lightweight and economy. They are ideal for shallower trusses
where there is more clearance room to accommodate the
plumbing than with timber webs, and for trusses where
the chord design has some reserve capacity, as is often
the case. In some instances, a few diagonal metal webs
may have to be replaced by timber webs in these trusses,
as load or geometry considerations dictate.
Webs may be on both sides of the truss, or just on
alternate sides, and in the latter case this allows for the
webs to overlap.
Pryda Span trusses are referenced as PS20, PS25,
PS30, and PS40, where PS means Pryda Span, and
20 is the nominal overall depth (cm). The overalldepths are in specific steps, but are nominally 200 to
400 mm deep in 50 mm increments. The actual depth
dimensions are in nominal size steps according to the
metal web used, and if required, the specific depth
should be obtained from the Pryda licenced fabricator.
Timber Webs
Metal Webs
PRYDA LONGREACH TRUSS
PRYDA SPAN TRUSS
-
7/24/2019 Pryda Trussed
4/24
Floor liveliness, or bounce, has been an intermittent
issue over the years with lightweight residential floors -
for all forms of timber and steel construction. To
eliminate these problems, Pryda Floor Systems are
designed to stringent dynamic performance criteria.Pryda Floor Systems have three options for floor
performance that can be selected by the designer.
AS1684.1 as the minimum criteria
Pryda Normal is more stringent Extra Stiff criteria used for those who want a superior
performance overall, or for tiled areas where cracks in
the grouting due to floor movement is to be
minimised.
The floor truss is only one component that can affectthe floor performance. On-site conditions are always
important and proper attention to detail must be taken
at the time of installation.
Flooring MaterialThe flooring material has a significant effect on the
perceived bounciness of a floor. It has the ability to
spread human impact loads depending on the material
and the thickness. Plywood acts differently to
particleboard, and T&G acts differently to both. A simpleway to improve floor performance is to select flooring
that is stiffer (e.g. thicker) than the minimum for your
chosen application.
StrongbacksThese are timber members, e.g. 140 x 35 mm running
at right angles to the trusses. There is generally onerow down the centre, but there could be more with
larger spans. Their main function is to help the flooring
spread footfall impacts to adjacent trusses. They aremost effective with the thinner particleboard floors used
in residential construction and become unnecessary as
the flooring becomes more substantial for the higher
commercial loads. It is important that strongbacks be
properly attached to the truss vertical webs as detailed,
as poor fixing techniques, such as having large gaps
between the strongback and the web, can reduce the
strongback effectiveness considerably.
BearingTrusses must bear directly on their supports and not beheld above them by the flooring. This may sound odd,
but where the support top plate is not level, and the
flooring is nailed to the truss top chord, the flooring itself
can lift the lower truss(es) by a few millimetres and this
considerably worsens the perception of floor bounce.
This situation is difficult to observe during the early
stages of construction and in any instance of potentialfloor performance complaint it should be checked using
a piece of card to see if there are any gaps between the
trusses and their supports.
Supporting BeamsIf any floor system is supported on beams e.g. steel ortimber lintels/beams the amount of floor bounce in that
area can become unacceptable if it is not properly
assessed at design time. The dynamics of anysupporting beam and the dynamics of the truss must be
considered simultaneously as they interact with each
other. Each can be satisfactory in its own right, but not
satisfactory in combination.
Pryda Longreach TrussesPryda Longreach can be designed for all common floor
loads, including commercial loadings up to 5 kPa orpoint loads up to 6.7 kN. These trusses are slightly
heavier than Pryda Span trusses and being all-timber
generally have a stiffer performance as they can
dissipate floor vibrations very well, and the nailplates
connecting the webs and chords are quite substantial.
Pryda Span TrussesPryda Span are manufactured using light gauge metal
webs and are lighter than Longreach, but this is
considered during the design process. The metal websystem can be very cost-effective, especially if the truss
chords have reserve capacity, as is often the case.
FACTORS AFFECTING FLOOR PERFORMANCE
P R Y D A F L O O R T R U S S S Y S T E M S4
-
7/24/2019 Pryda Trussed
5/24P R Y D A F L O O R T R U S S S Y S T E M S 5
Permanent (dead) loads which are considered during the
design process include:
Self-weight of the truss
Flooring (particleboard, T&G, plywood, etc)
Floor covering (carpet, ceramic tiles, etc) Ceiling (plasterboard, battens, etc) Temporary (live) loads such as furniture which may be
in place for long periods of time. These are taken as
500 Pa irrespective of the magnitude of actual design
live load.
Typically, the flooring, floor covering, self-weight andceiling under amount to approximately 410 Pa for
residential floor truss designs.
Spa BathsThe load imposed by a standard bath can be ignored
when selecting floor trusses, but spa baths need special
attention due to the higher loads that can be imposed.The self-weight of the spa shell and the support base
also adds to the load on a floor truss. Reducing the floor
truss spacing may cause issues with plumbing and sothe alternative is to select a design span which is
greater than the actual span when estimating from the
span tables.
A large corner spa (1.5m x 1.5m x 0.5m) has a water
capacity of approximately 250 litres. A design span
that is 1.3 times longer than the actual span can be
adopted. A feature spa (1.5m x 1.5m x 0.6m) has a water
capacity of approximately 450 litres.
For actual spans of less than 3.0m - adopt adesign span equal to 2 times the length of the
actual span.
For actual spans between 3.0m and 4.5m - adopt
a design span equal to 1.7 times the length of the
actual span.
For actual spans greater than 4.5m - adopt a
design span equal to 1.4 times the length of theactual span.
These rules are illustrated by the following example:
Feature spa bath loaded on a FT300 floor truss
with a span of 3500 mm.
From Longreach Residential Span Table: Normally
the top and bottom chord sizes are 90 x 35
MGP10.
Using the design rule: 3500 mm x 1.7 = 5950 mm.
Refer to Table again: Chord sizes are increased to
90 x 35 MGP12 to allow for spa load.
If these rules for spa baths are not appropriate because
they require an increase in floor truss depth as well as
change in chord grade and size, then an alternative
method may be used. Spa bath loads may be allowed
for by simply reducing the spacing to a third of the
original spacing under normal conditions. Therefore, in a
floor truss layout with a spa bath over, the spacingshould be reduced to 150 mm (for 450 mm crs) or 200
mm (for 600 mm crs) for the width of the bath.
Water BedsA queen size waterbed is expected to weighapproximately 450 kg. For waterbeds with a holding
capacity of up to 600 litres adopt the same design rules
as for feature spas.
Other Heavy LoadsWhere special load cases are to be applied to the floor
trusses such as heavy ceramic tiles, extra stiffness may
be desired in the flooring system to minimise potential
cracking in the tile grout. This can be achieved by
adopting a design span equal to at least 25% greater
than the actual span of the truss.
Generally, other heavy furniture items, such as a grand
piano, could be allowed for in a similar manner, howevercheck with a Pryda design office first, as large point
loads can be critical.
Designers should advise the Pryda licensed fabricatoron the magnitude of these loads once they have
identified the size and capacity of the feature.
Temporary LoadsTemporary (live) loads are the transient loads that are
placed on the floor and are mainly due to construction
loads, people, furniture, storage, etc. These loads are an
estimation of the temporary occupancy and the
associated use of the room that the floor supports.
Typically, the trusses are designed for a distributed live
load and a concentrated load, taken separately whichever produces the most adverse effect.
Typical live loads in AS1170.1-1989 are:
Houses general areas: 1.5 kPa / 1.8 kN (see
span tables)
balconies: 3.0 kPa / 1.8 kN
Bedrooms and private rooms in apartment buildings:
2.0 kPa / 1.8 kN
Offices in retail or industrial premises: 3.0 kPa / 6.7
kN (see span table)
Public corridors in institutional buildings such as
schools: 4.0 kPa / 4.5 kN
Assembly areas without fixed seating in institutionalbuildings: 5.0 kPa / 3.6 kN
PERMANENT LOADS
-
7/24/2019 Pryda Trussed
6/24
Deflection LimitsPryda floor trusses are designed to be within deflectionlimits set out in AS1684.1-1999. Further deflection limits
have been adopted based on research and experience
to produce trusses that exhibit greater stiffness than theminimum. It is believed that unsatisfactory floor vibration
issues can be minimised by designing trusses under a
normal or extra stiff classification in the Pryda Floor
software. The domestic live load span table is designed
according to AS1684.1-1999 criteria.
Load Condition AS1684.1 Normal Extra stiff
Design live load L/300 L/480 L/600
1500 Pa live load 9.0 mm 9.0 mm 7.0 mm
Dynamic CriteriaDynamic limits have been established to further ensure
that the floor trusses are acceptable with regard to
springiness or bounce. Along with the deflection
limits, these dynamic limits are based on extensive
research and scientific investigation in Australia and
overseas to ensure the comfort of the building
occupants.
Load Condition AS1684.1 Normal Extra stiff
300 Pa live load Freq > 8Hz Freq > 10Hz Freq > 12Hz
1 kN live load 2.0 mm 2.0 mm 1.5 mm
Special Note: The dynamics of a flooring system are
characterised by the perceived frequency of vibration in
the floor under a specific load. The rigidity of thesupporting structure can have a significant effect on the
dynamics of a flooring system. For example, a joist
supported by rigid walls will seem to exhibit less bounce
when walked upon than the same joist supported by
flexible beams that permit some level of support
movement.
It is the responsibility of the building designer to ensure
that the combined frequency of vibration of the flooring
system is adequate. The Span Tables assume a rigid
and adequately designed supporting structure. Providinga less than adequate supporting structure will have an
impact on the serviceability qualities of the flooring
system.
Pryda design offices use software that can check the
effect of trusses which are sitting on flexible supports,
and advice in this area is available to specifiers.
SPECIAL CONDITIONS
Residential, Commercial or Essential Building
Importance
The classification of building importance according toAS1720.1-1997 is a means of providing different
capacity factors for primary structural elements in
buildings other than houses. In most cases a floor joist
is not a primary structural element in any of these
building classifications, and this is the assumption usedin the span tables.
Pryda Floor software utilises the different capacity
factors in cases where floor trusses support significantadditional roof and/or floor loads in a commercial or
essential services building. For example, a floor truss
supporting a concentrated girder load from an internal
loadbearing wall needs special consideration.
Bearing at SupportsIt is important that floor trusses bear over the support
wall plate or beam with a minimum of 30 mm for
residential floors and 40 mm for commercial floors.
This requirement is implemented to ensure that localisedcrushing of the top plate or bottom chord does not
occur. It also encourages suitable load transference
between upper loadbearing wall frames and lower wall
frames.
No Ceiling UnderneathIf there is no ceiling fixed directly underneath the
trusses, install 90 x 35 F5 (on flat) lateral ties to the
bottom chord, located approximately at the third points
of the span. This will prevent one type of undesirabledynamic response which is otherwise normally
prevented by the ceiling (if fixed directly to the truss
bottom chords) or ceiling battens.
SERVICEABILITY
P R Y D A F L O O R T R U S S S Y S T E M S6
-
7/24/2019 Pryda Trussed
7/24P R Y D A F L O O R T R U S S S Y S T E M S 7
These span tables are for indicative purposes and
represent only a small selection of the possibilities.
Specific designs can be prepared on request for different
timber choices or for different loading requirements.
FlooringThe span tables have been developed using a design
method that assumes the minimum flooring requirement
for the associated load criteria. Although the self-weight
of the flooring material contributes to the dead load onthe truss, it is the stiffness of the flooring that has a
significant effect on the performance of the trusses
under live loading. It is assumed that there is no
composite action between the floor and truss however
the floor fixings do offer lateral restraint to the top chord.
All the trusses shown are assumed to be bottom chord
supported. If the truss is required to be supported by
the top chord, select 45 mm minimum chord thickness
for the top chord to allow sufficient area to fit the end
vertical nailplates.
Australian StandardsThe span tables in this Guide to Specification and the
designs produced by the Pryda Floor software comply
with the following standards:
AS1170.1-1989 SAA Loading Code. Part 1: Dead and
live loads and load combinations
AS1684.1-1999 Residential timber-framed construction.
Part 1: Design criteria.
AS1720.1-1997 Timber Structures. Part 1: Design Methods
SPAN TABLES
PRYDA LONGREACH FLOOR TRUSSES - MAXIMUM SPANS
Residential loads (1.5 kPa / 1.8 kN)
Truss Chord size and grade (TC and BC) Clear depth Max. pipe dia O/A O/A
Reference90x35 P10 90x35 P12 90x45 F17
between within web depth depth
450 crs 600 crs 450 crs 600 crs 450 crs 600 crschords (mm) profile (mm) 35/35 45/45
FT200 4200 3300 4700 4200 5300 4800 120 80 190 210
FT250 5000 4100 5400 4900 6100 5500 170 130 240 260
FT300 5400 4400 6000 5400 6700 6100 220 180 290 310
FT350 5700 5200 6600 6000 7400 6600 270 230 340 360FT400 6400 5400 7100 6400 7900 7200 320 280 390 410
PRYDA SPAN FLOOR TRUSSES - MAXIMUM SPANS
Residential loads (1.5 kPa / 1.8 kN)
Truss Chord size and grade (TC and BC) Clear depth Max. pipe dia O/A O/A
Reference90x35 P10 90x35 P12 90x45 F17
between within web depth depth
450 crs 600 crs 450 crs 600 crs 450 crs 600 crschords (mm) profile (mm) 35/35 45/45
PS25 4900 4200 5300 4800 6000 5200 170 150 240 260
PS30 5400 4500 5900 5300 6700 5800 220 190 290 310
PS40 N/S N/S N/S N/S 8000 7000 332 260 N/S 422
N/S = not suitable
RESIDENTIAL FLOORS
The trusses here have been designed to the followingcriteria:
1.5 kPa distributed load, or 1.8 kN concentrated load
applied over 19 mm x 19 mm
19 mm particleboard flooring (450 mm crs) and 22
mm (600 mm crs) with 10-13 mm plasterboard ceiling
Top chord panel lengths should not exceed 550 mm
for Longreach trusses. Panel lengths for Pryda Spantrusses are preset at about 600mm.
Deflection limits as for solid floor joists in AS1684.
A 10% reduction in maximum span will increase thefloor stiffness by 30%.
All timber webs are 35 mm thick. Metal webs are
generally as pairs at the truss ends, but are reduced
to singles on alternating faces if the force in the webs
is small enough to warrant it.
Any duct space must not exceed 500 mm in length,
and must be located within the centre half of the span.
Prefix P denotes MGP, e.g. P10 means MGP10 F17 and P15 chords of the same size are
interchangeable.
-
7/24/2019 Pryda Trussed
8/24
COMMERCIAL FLOORS
The trusses here have been designed to the following
criteria:
3.0 kPa distributed load, or 6.7 kN concentratedload applied over 100 mm x 100 mm
25 mm F11 plywood flooring diaphragm. Any
substitute should have a similar or better stiffness. 10-13 mm plasterboard ceiling.
Top chord panel lengths should not exceed 550 mm
for Longreach trusses, except that for 90 x 35 P12
chords it must not exceed 450 mm. Panel lengths for
Pryda Span trusses are preset at about 600mm.
All diagonal timber webs are 45 mm thick. All metal
webs are in pairs.
Any duct space must not exceed 300 mm in length,
and be located within the centre half of the span.
Prefix P denotes MGP, e.g. P10 means MGP10
F17 and P15 chords of the same size areinterchangeable.
These trusses are inherently much stiffer than the
residential designs, and will not produce any perceived
bounce problems.
P R Y D A F L O O R T R U S S S Y S T E M S8
PRYDA LONGREACH FLOOR TRUSSES - MAXIMUM SPANS
Commercial loads (3.0 kPa / 6.7 kN); 450 mm centres
Truss Chord size and grade (TC and BC) Clear depth Max. pipe dia O/A O/A
Reference90x35 P12 90x35 F17 90x45 P12 90x45 F17
between within web depth depth
chords (mm) profile (mm) 35/35 45/45
FT250/3 4500* 4600 4900 5200 170 130 240 260
FT300/3 5200* 5400 5600 6000 220 180 290 310
FT350/3 5800* 6100 6400 6700 270 230 340 360
FT400/3 6300* 6700 6900 7400 320 280 390 410
FT450/3 6900* 7300 7600 7900 370 330 440 460
* TC panel length not to exceed 450mm
PRYDA SPAN FLOOR TRUSSES - MAXIMUM SPANS
Commercial loads (3.0 kPa / 6.7 kN); 450 mm centres
Truss Chord size and grade (TC and BC) Clear depth Max. pipe dia O/A O/A
Reference90x35 F17 90x45 P12 90x45 F17
between within web depth depth
chords (mm) profile (mm) 35/35 45/45
PS25/3 4400 4600 4800 170 150 240 260
PS30/3 5100 5300 5500 220 190 290 310
PS40/3 N/S N/S 7000 332 260 N/S 422
N/S = not suitable
-
7/24/2019 Pryda Trussed
9/24P R Y D A F L O O R T R U S S S Y S T E M S 9
INTERNAL WALLS
These details refer to all internal walls which are non-
loadbearing for gravity loads, but which may also be
wind bracing walls. If the floor is to carry loadbearing
internal walls, do not use these Span Tables and check
with a Pryda design office for a specific design.
The floor truss system requires no additional stiffening
when supporting non-loadbearing walls, however
special consideration is required for non-loadbearingwalls acting as wind bracing walls. Specifiers should
notify the Pryda licenced fabricator of wall bracing
positions and capacities.
Bracing walls parallel to thefloor trussesIf the wall is positioned between two floor trusses and is
a wind bracing element with a capacity of no more than1.5kN/m and does not exceed 2.7m high, fix noggings
at each end of the bracing element to transfer wind
forces to the adjacent trusses. Use 2/14gx100mm
Timberfixx screws to fix the bottom plate of the bracingelement into the nogging, and 12gx65mm Timberfixx
screws to fix the bottom plate to the flooring at 450mm
centres along the length of the bracing element. For
wind bracing wall capacities of up to 3.0kN/m fix a
120x45 MGP10 strongback to the vertical web nearest
the end of the bracing element. The strongback will
pass through two trusses either side of the wall and fixto the webs with 2/12gx65mm
Timberfixx screws. The flooring
material shall be nailed andglued to all floor trusses in the
flooring system.
If a bracing wall sits directly over
a floor truss then fix 14gx100mm
Timberfixx screws into the truss
at 450mm centres along the
length of the bracing elementalong with 2/14g x 100mm
screws at each end for 1.5kN/m
wind bracing capacities. Use 4
screws at each end with the
strongback detail as outlined
above for up to 3.0kN/m windbracing capacities.
Bracing walls perpendicular to thefloor trussesFor wind bracing walls of up to 1.5kN/m wind bracing
capacity with the element no higher than 2.7m, use
14gx100mm Timberfixx screws to fix the bottom plate of
the bracing element to each perpendicular floor truss. If
the end of the bracing element finishes directly above a
floor truss use 2/14gx100mm Timberfixx screws, and ifnot then use the same screws into the nogging as
previously mentioned. For wind bracing walls of up to
3.0kN/m capacity adopt the same details as for bracingwalls parallel to the floor trusses. The flooring material
shall be nailed and glued to all floor trusses in the
flooring system.
Platform FlooringWhere a structural platform floor has been constructed
over the trusses, any non-loadbearing wall parallel tothe trusses does not require additional support other
than that of the platform flooring.
INTERNAL NON-LOADBEARING WALLS
Max. Wind Brace
Capacity of 1.5kN/m
Internal Bracing Wall
Fix Bracing Wall to Nogging
Using 2/14g x 100mm
Timberfixx Screws at
Each Floor Truss Crossing
Under Bracing Element
3/3.75 x 90mm Nails Fixing
Nogging to Upright Member
3/3.75 x 90mm Nails
Fixing Upright to Top
And Bottom Chords2/12g x 65mmTimberfixx Screws
to Strongback120 x 45mm F5or
MGP Upright Member
End of
Bracing
Element
Fix Bracing Wall to Nogging Using 2/14g
x 100mm Timberfixx Screws
120 x 45mm F5orMGP Nogging
PARALLEL BRACING WALL
PERPENDICULAR BRACING WALL
Max. Wind Brace Capacity of 1.5kN/m
Internal Bracing Wall
Fix Bracing Wall to Nogging Using 2/14gx 100mm Timberfixx Screws
3/3.75 x 90mm Nails Fixing
Nogging to Upright Member3/3.75 x 90mm Nails Fixing
Nogging to Top And Bottom Chords
For wind bracing capacities of up to 3.0kN/m extend a 120 x 45mm
MGP10 strongback through two trusses either side of bracing wall
at the nearest vertical web. In the 3.0kN/m case adopt an M10 bolt
connection through nogging rather than screws and use 12g x
65mm Timberfixx screws elsewhere instead of 3.75 x 90mm nails.
2/12g x 65mm Timberfixx Screws
120 x 45mm F5orMGP
Upright Member
Length of
Bracing ElementMax.
2700mm
HighWall
75mm Nails @
150mm Centres
120 x 45mm F5orMGP10 Nogging
-
7/24/2019 Pryda Trussed
10/24
Important: Should an internal wall be required tosupport floor trusses, this intention should be made
abundantly clear on both the trusses and the truss
layout. The supporting structure, footings, etc. should
then be designed to cope with the high wall loads that
can result.
Internal lower storey walls can be used for support tocreate single length trusses across the width of the
building. Preferably, a double web with a gap will cater
for small deviations in support positions, while a block
insert of up to 600 mm in length will accommodate
larger deviations. Alternatively, if the exact location of
the support is known, then a vertical web can bedetailed at the support point.
P R Y D A F L O O R T R U S S S Y S T E M S1 0
NON-LOADBEARING WALLS UNDER
Floor trusses must be adequately supported on the
loadbearing supports nominated in the design. There
may be a detrimental effect on the walls and the flooringsystem if the trusses bear on a non-loadbearing wall.The tops of internal non-loadbearing walls need lateral
stabilising by fixing to the truss bottom chords. The
trusses must be allowed to deflect downwards, so
Pryda Partition Hitches have been developed for thispurpose, which should be nailed to the truss near thetop of the slots.
LOADBEARING WALLS UNDER
Internal Support Types
Fitted FlooringWhere a fitted floor is being used,
locate a double truss under each
wall to provide support to both the
wall and flooring. Alternatively, usesupplementary ledger plates fixed
to the side of the floor trusses.
Fitted Flooring
Non-Loadbearing Wall
Fitted Flooring
Non-Loadbearing Wall
FITTED FLOOR FIXING
DOUBLE TRUSS
FITTED FLOOR FIXING
SUPPLEMENTARY LEDGER PLATES
Single Web
Internal Support Wall
SINGLE WEB SUPPORT
Double Web
Internal Support Wall
DOUBLE WEB SUPPORT
45mm Thick Block
(Solid or Claw Joined)
250
or DeeperMax. 600mm
Internal
Support Wall
NAILED BLOCK SUPPORT
-
7/24/2019 Pryda Trussed
11/24P R Y D A F L O O R T R U S S S Y S T E M S 1 1
These details are for floors that support external
walls loadbearing and non-loadbearing
WALL DETAILS
Fully Supported End TrussWhere the end floor truss is supported along
its full length by a lower storey wall or bycontinuous base brickwork or footing while
carrying an upper storey wall above, a
simplified floor truss, as shown, may be used.
End Truss Under Gable RoofWhere the end floor truss is located under a gable end
roof and is free spanning, it is appropriate to use a
single floor truss as it is carrying a non-loadbearing walland floor only.
End Truss Carrying RoofLoads OverWhere a free spanning end floor truss is carrying roof
loads along its length transferred from the wall above
then it is necessary to use one or more special floor
trusses under this wall. This will depend upon the RoofLoad Width (RLW) being carried and the weight of the
roof materials. A guide to floor truss requirements for
these conditions are in the following table, otherwisethese trusses must be specially designed and require
further consultation with a Pryda design office.
No. of floor trusses required
Maximum RLW Concrete Tiles Metal Roofing
1800* 2 1
* Refer to AS1684-1999 for RLW description
EXTERNAL WALLS
Offset Loadbearing WallsPryda floor trusses selected using this Guide are not
designed to support offset loadbearing walls. If these
walls supported by floor trusses are required to carry
roof or other loads, please refer to a Pryda licensedfabricator for an individual design.
Diagonal Webs at Max.
6000mm Centres
Additional Block Required
For Loadbearing Jamb Stud Above
Modified Floor Trusses
Jamb Studs With Lintel Over
FULLY SUPPORTED END TRUSS
-
7/24/2019 Pryda Trussed
12/24P R Y D A F L O O R T R U S S S Y S T E M S1 2
Pryda floor trusses can be
detailed to suit an opening
in a floor, eg as required to
accommodate stairways.
A header beam is normallyrequired to support the
incoming trusses while adouble lamination standard
truss is often suitable to carry
each end of the header beam.
Block DetailAlternatively, a solid block (600 mm long) fixed to the
side of the trusses may support the header beam. The
header beam may be notched into the solid block or
fixed to the block using a Pryda Joist Hanger as shown.
FLOOR OPENINGS
Beam Pocket DetailThe trusses need to be detailed with a beam pocket wide enough
to fit the header beam as shown. The header beam should be
blocked hard up against the underside of the carrying floor trussesand nailed to each vertical web with 4/3.15 x 75 mm nails.
Stairway Parallelto TrussesUse the following charts to
determine header beam
specifications and also chordspecifications for the double
lamination floor truss for Load
Case 1 only. The header beam
(max. 2000mm span) supports
the curtailed floor trusses and
stair loadings from the upper
flight of stairs.
Curtailed Truss Span
Double Truss
Header Beam
Opening
FLOOR OPENINGS
Solid Packing Under
Header Beam
BEAM POCKET
Header Beam
35mm Solid Block Fixed To Side
of Truss With 75 x 3.75mm Dia.
Nails at 50mm Centres
Pryda Joist Hanger
PRYDA JOIST HANGER SUPPORT Header Beam
Pryda Triplegrip
35mm Solid Block Fixed
to Side of Truss With 75 x
3.75mm Dia. Nails at
50mm Centres
600mm
NOTCHED HEADER SUPPORT
Double Supporting Truss
Max. 2000mm
Header BeamSupported byDouble Floor Truss
Header Beam Carrying Curtailed
Floor Trusses And Stair Load From
Upper Flight of Stairs Only
Max. 3000mm
Max. 7500mm
LOAD CASE 1 STAIRWAY PARALLEL TO TRUSSES
-
7/24/2019 Pryda Trussed
13/24
StairwayPerpendicularto TrussesUse the following charts
to determine header
beam specifications
and also chord
specifications for the
double lamination floor
truss for Load Case 2only. The 900mm wide
stairway runsperpendicular to the
curtailed floor trusses
and the header beam
(max. 3500mm span)
supports the trusses.
P R Y D A F L O O R T R U S S S Y S T E M S 1 3
HEADER BEAM SELECTION CHART
Maximum floor truss span (mm) onto header beam
Maximum Header beam
Supported Floor (max. 3500mm)
Truss Span (mm)
1000 190 x 45 F17 or 200 x 45 Hyspan LVL
2000 240 x 45 F17 or 240 x 45 Hyspan LVL
3000 2/240 x 35 F17 or 240 x 63 Hyspan LVL
4000 2/240 x 45 F17 or 2/240 x 45 Hyspan LVL
5000 2/290 x 45 F17 or 2/300 x 45 Hyspan LVL
HEADER BEAM
SELECTION CHART
Maximum Header beam
Supported Floor (max. 2000 mm span)
Truss Span (mm)
1500 190x45 P12 or 200x45 Hyspan LVL
2500 190x45 F17 or 200x45 Hyspan LVL
3500 190x45 F17 or 240x45 Hyspan LVL
4500 240x45 F17 or 240x45 Hyspan LVL
5500 240x45 F17 or 240x45 Hyspan LVL
SUPPORTING FLOOR TRUSS SELECTION CHART
Chord selection requirements for double floor truss
Truss Supported floor truss span (mm)
depth1500 2500 3500
250 90 x 45 P12 N/A N/A
300 90 x 35 P12 90 x 45 F17 N/A
350 90 x 35 P12 90 x 45 F17 N/A
400 90 x 35 P12 90 x 45 P12 90 x 45 F17
Note: In this load case the header beam and the supporting floor trusses have been designed to support stair loadings
however the stairs must be self- supported at the mid-landing level. MGP15 may be used in place of F17 timber. These
tables are only applicable to load case 1.
SUPPORTING FLOOR TRUSS SELECTION CHART
Chord selection requirements for double floor truss
Truss
Supported floor truss span (mm)
depth 2000 3000 4000 5000
250 90x45 P12 90x45 P12 N/A N/A
300 90x35 P12 90x45 P12 90x45 F17 N/A
350 90x35 P10 90x45 P10 90x45 P12 90x45 F17
400 90x35 P10 90x45 P10 90x45 P12 90x45 F17
Note: Stair load on to double lamination floor truss is
considered. MGP15 may be used in place of F17 grade
timber. These tables are only applicable to Load Case 2.
(mm)
Double Trusses
Header Beam Supported
by Floor Trusses
Curtailed
Trusses
Max. 3500mm
900mm
Max. 6000mm
Beam Pocket
LOAD CASE 2 STAIRWAY PERPENDICULAR TO TRUSSES
-
7/24/2019 Pryda Trussed
14/24P R Y D A F L O O R T R U S S S Y S T E M S1 4
External Cantilevered BalconiesThese details concern the cantilever which forms a
balcony generally outside the room. Cantilevered
balconies can be used with the standard floor trusses
under certain conditions. If these conditions cannot be
met, the trusses will need specific design. The live load
on balconies is twice as high (3 kPa) as the normal
residential floor loads (1.5 kPa).
Pryda floor trusses can be designed to cantilever as a
continuous truss, or alternatively a timber joist may be
fixed to the side on site as shown below. It is importantthat the fabricator is notified prior to manufacture.
Balcony cantilever joists should be sized according to
the framing manuals, but must be restricted to a length
of no more than one quarter of the internal truss span.
DUCTS FOR
MECHANICAL
SERVICES
The open web configuration of Pryda floor trussespermits ductwork and mechanical services to pass
through the depth of the truss. Under domestic loads,
Pryda Span and Longreach floor trusses may be
detailed with voids up to 500 mm long near the centre
of the span. The span tables show depth clearances
and the maximum pipe diameter that can beaccommodated without special designs being required.
Pryda Floor software permits duct spaces to be detailed
anywhere along the length of the truss, under specificdesign.
There are three common types of cantilevered balconies
internal, external, and those which support offset walls
above.
Internal CantileversFound in two-storey construction where the first floor
trusses are cantilevered only a small amount as an
architectural feature. These cantilevers are built as a
simple extension to the truss, with vertical webs
introduced at the point of support.
CANTILEVERS
Max. 500mm
Max. Pipe Dia. Permitted In-Between
Web Profiles (Refer Span Tables)
Max. Clear
Depth
CENTRE GAP FOR MECHANICAL SERVICES
Floor Truss
Span
Cantilever Length
INTERNAL CANTILEVER DETAIL
Cantilever Balcony
Beam to Suit75mm x 3.75mm Dia. Nails at Max. 200mm
Centres Along Chords and Webs
Floor Trusses
Balcony
Joists to Suit
Not Less Than
Balcony Cantilever
BalconyCantilever
EXTERNAL CANTILEVER
-
7/24/2019 Pryda Trussed
15/24P R Y D A F L O O R T R U S S S Y S T E M S 1 5
The cantilever balcony beam shall run a similar distance
back into the floor truss and at least to the next vertical
web past that distance. The cantilever joists are to be
fixed to the truss bottom chord and vertical webs with
3.75 mm dia nails (75 mm long into 35 mm joists and 90mm long into 45 mm joists) at maximum 200 mm centres.
Note: These cantilever details are not intended for
cantilevers carrying loadbearing walls over. In thisinstance, refer to a Pryda design office for special
design.
Offset Wall CantileverA common cantilever issue encountered is one in which
the timber clad second storey frame is offset 150 mm
outside the lower storey frame. This permits the upper
storey external wall cladding to finish flush with the
lower storey brickwork. As a result, the floor trusses are
cantilevered to support the upper storey roof loads andtransfer these down to the foundations via the lower
storey walls. Often this issue occurs parallel and
perpendicular to the span of the floor trusses.
Strongback beams run perpendicular to the trusses and
are used to spread footfall impact loads to adjacent
trusses. They are required for all residential floors and
some of the lighter commercial floors.
Strongbacks are not required for trusses up to 3.5m inspan. For trusses 3.6m to 7m span, use one row of
strongbacks located close to midspan. For trusses
above 7m span use 3 rows of strongbacks located onerow at midspan, and two further rows located at each of
the quarter points.
Strongbacks should be fixed hard up against the vertical
web, but may be fixed up against the top chord or the
bottom chord to suit. Fixings may be hand hammered
75 x 3.75 nails, or power driven 75 x 2.9 nails, or 12g
11 x 65 Timberfixx screws. While screws are more
expensive, they provide the best performance as theyare more rigid, they clamp the timber components
together, and they prevent squeaks due to various floor
components loosening over time.
Where Pryda Span trusses have been used, and there is
no vertical web close to the desired location of the
strongback, a supplementary vertical web may be nailed
to the side of the truss instead with 2 nails to the top
chord and to the bottom chord, to provide a fixing for
the strongback.
STRONGBACKS
Upper Storey
Loadbearing Wall
Min.
250mm
150mm
Solid Blocking
(Min. F5)
Min.300mm
CANTILEVER PERPENDICULAR OFFSET
UPPER LOADBEARING WALL
Solid Block to Suit Truss
Depth (Min. F5) Trimmer Plate
Upper Storey
Loadbearing Wall
- Max.5000mm RLW
- Conc.Tile Roof
600mm
Skew Nail
Pryda Triple Grips
Floor Truss
90 x 35mm F5 Pole Plate
Fixed to Top Chord And
Vertical Webs With 75 x
3.75mm Dia. Nails (200mm
Centres Into Chord)
Lower Storey
Loadbearing Wall
150mm
Min.
250mm
CANTILEVER PARALLEL OFFSET UPPER LOADBEARING WALL
Strongback Size
as Per Table
LONGREACH STRONGBACK
Strongback Size
as Per Table
PRYDA SPAN STRONGBACK
-
7/24/2019 Pryda Trussed
16/24
Strongback Size Selection
STRONGBACK BEAM SELECTION
Nominal truss Strongback depth and No. of fixingsdepth (mm) grade (all 35 mm thick) per connection
200 90 F5/P10 or 70 F17 2/nails or 1/screw
250 120 F5/P10 or 90 F17 3/nails or 2/screws
300 140 F5/P10 or 120 F17 3/nails or 2/screws
350 140 F5/P10 or 120 F17 3/nails or 2/screws
400 140 F5/P10 or 120 F17 3/nails or 2/screws
In locations where the strongback needs to be joined,
either of the following methods may be used:
Non-aligned StrongbacksIn cases where different adjacent spans cause thestrongbacks to be out of alignment, the following detail
may be adopted. Vertical blocks of 90 x 35 mm are fixed
with 2/3.75 dia x 75 mm nails to both top and bottomchords. Strongbacks are then fixed into the side of the
block and the preceding vertical web with the number of
nails specified in the table.
Strongbacks Not Required
Strongbacks may be omitted from floors when:
The floor has been designed for live load of 3000 Pa
and 4.5 kN, or greater.
Either 25 mm F11 plywood, or 2 layers of 19 mm F11
plywood (or better) has been used
In these situations, either the truss will be very stiff dueto the high design load, or the flooring itself is capable
of dissipating human footfall impacts.
Instead, use 90 x 35 F5 (on flat) lateral ties fixed to thebottom chord, located 3000 mm apart (max.).
P R Y D A F L O O R T R U S S S Y S T E M S1 6
Overlap
Strongback at
Vertical Webs
STRONGBACK SPLICE
Min. 5/3.75mm Nails
Each Side of Joint
Splice Strongback Together
With Cleat on Side
ALTERNATE STRONGBACK SPLICE
Additional Block
Max. 600mm
Vertical Web
NON-ALIGNED STRONGBACKS
-
7/24/2019 Pryda Trussed
17/24
Pryda floor trusses must be braced back to their
supporting structure for stability in a similar manner to the
bracing stipulated by AS1684-1999 for solid deep joists.
Use diagonally placed Pryda Strapbrace or timber braces
(minimum thickness of 25 mm) at 2700 mm centresmaximum at the ends of trusses and at any internal wall
supports. Alternatively, a continuous trimming beam maybe used at the end of each truss see End Type 3 - with
diagonal bracing at the end bays only. This bracing does
not substitute for wind bracing.
Pryda floor trusses are braced laterally at the top chordlevel by the flooring material and at the bottom chord level
by the ceiling lining. If there is no ceiling fixed directly (or
by battens) then 90 x 35 binders must be provided on thebottom chord at 3000 mm centres maximum.
Pryda floor trusses have the advantage of adapting to
a range of different on-site support conditions.
The dimensions of the 12 standard end types can varyto meet most detailing requirements. The joint details
shown in this manual are intended as a guide only.
Variations to these may be required and should be
verified.
End Type Details
End Type 1
Most common end type for bottom chord bearing on
wall plate or steel section while also permitting upper
wall frame to bear directly above. May also be used for
connection to framing brackets.
End Type 2
Similar purpose as End Type 1, however permits timber
end bracing trimmers to provide lateral stability. It also
accommodates minor site variations by allowing the
setbacks to be curtailed if need be.
P R Y D A F L O O R T R U S S S Y S T E M S 1 7
STABILITY BRACING SUPPORT AND
CONNECTION DETAILS
Length of Pryda Strapbrace to Suit Height of Trusses
Min. 2/3.15mm x 30mm Pryda Nails
Into Side of Top Wall Plate
and 2 Nails to Underside
Max. 2700mm Centres
90 x 35mm F5
2/75mm Nails
Into Vertical
Web
Max. 1800mm Centres
Fix Trimmer to Ends of Floor Trusses With
2/3.15mm Dia. x 75mm Nails
End Trimmer
Note: End Brace Requires Diagonal
Bracing Down to Wall at Each End
of a Bay of Trusses
Min. Bearing 30mmWall Plate
CANTILEVER SUPPORT
-
7/24/2019 Pryda Trussed
18/24P R Y D A F L O O R T R U S S S Y S T E M S1 8
Block
Supporting
Trimmer
End TrimmerLoadbearing Wall
Top Chord Extension of Any
Length to Maintain Floor Level
Primary Bearing
Point Min. 30mm
End Type 3
Accommodates ease of installation of timber end
bracing trimmers while also supporting upper
loadbearing wall frame. It acts as an additional bottom
plate and supports the edge of the sheet flooring.
End Type 4
Suitable for bottom chord bearing on the bottom flange
of a steel channel or universal beam while also
maintaining floor level above top flange.
End Type 5-1
Flexible end type that comprises of a solid block insert
nailed into position through top and bottom chords. The
resulting I-beam end is bottom chord supported and
can be cut back on an angle to suit steel sections.
End Type 5-2
This version of End Type 5 has a full width end block
that is cut back to accommodate an upper storey
loadbearing wall set back from the lower storey.
End Type 5-3
Alternatively, End Type 5 with a full width end block is
suitable for cantilevering over lower storey walls and
carrying upper storey load bearing walls.
End Type 6-1
Standard bottom chord bearing with the capacity totransfer high loads from upper loadbearing walls.
High Load Wall
Max. 300mm
Min. 100mm
Max. 80mm
Max.
150mm
Max.
300mm
Max. 300mm
Max. 200mm
-
7/24/2019 Pryda Trussed
19/24P R Y D A F L O O R T R U S S S Y S T E M S 1 9
Skew Nails Preferable Into
Beam to Restrain Bottom Chord
Min. Bearing 30mm
Min. Top Chord Bearing 30mm
Max. 110mm
Max. 35mm
Min. Bearing 30mm on
Primary Bearing Point
Min. Bearing 30mm on
Primary Bearing Point
Overhang Any Length
End Type 6-2
End Type 6 also provides extra timber nailing area when
supporting trusses in Pryda joist hangers.
End Type 7-1
Top chord support on wall frames, floor beams andwaling plates. Promotes easy installation. It is advised
that bottom chord should be restrained (skew nailsminimum) to obtain best results.
End Type 7-2
Top chord support on wall frames, floor beams and
waling plates. Promotes easy installation. It is advisedthat bottom chord should be restrained (skew nails
minimum) to obtain best results.
End Type 8
Similar purpose to End Type 7 however the level ofthis truss is not governed by the supporting member.
This end type also permits the floor trusses to support
higher loads.
End Type 9
Permits the floor trusses to be supported on the top
chord while also housing the supporting beam within the
depth of the truss. Encourages continuous ceiling lines
under trusses.
End Type 10
This end type is suitable for short internal cantilevers
alongside stair openings.
End Type 11Permits support into steel channels and universal beams
while maintaining a floor and ceiling level that finishes
flush with the top and bottom flange.
End Type 12
Permits bottom chord support into steel channels and
universal beams with the bottom chord finishing flush
with the bottom flange while also maintaining a floor
level above the top flange.
Waling Plate
Min. Bearing 30mm
on Waling Plate
Timber Beam
Pryda Joist
Hanger Supporting Truss
End Web Should be Max. 5mm
From Edge of Supporting Member
-
7/24/2019 Pryda Trussed
20/24
Each truss shall be held onto its supporting plate/bearer
by a minimum of 2/75 x 3.15 mm dia nails. If preferred,
a better fixing may be achieved by using one Pryda
Minigrip with 3/35 x 3.15 mm dia Pryda nails per tab.
When supporting trusses on steel or timber beams via
top chords it is preferable to restrain the bottom chord
using skew nails while the top chord should be fixed to
the supporting beam using screws or Pryda Triplegrips.
This practice improves the stiffness of the floor by
minimising movement and vibration at the supports.
FIXINGS AT SUPPORTS
P R Y D A F L O O R T R U S S S Y S T E M S2 0
2/75mm x 3.15mm Dia.Skewed Nails
75mm x 3.15mmDia. Skewed Nails
Preferred
Pryda fully engineered open-web timber floor truss
systems with timber webs (Pryda Longreach) or metal
webs (Pryda Span) have many advantages:
Designed to eliminate the problem of bouncy floors
commonly found with some solid timber joists andprovide a floor that feels and acts rock-solid.
The open webs allow easy fixing of electrical,
plumbing, ducts and energy services. There is no
need for drilling or notching, saving time on site.
Greater design flexibility. Extra long spans and large
cantilevers can be provided, with the ability to
support high loads. Can also eliminate the need forsome interior support walls and beams, giving more
scope to architects and designers thus reducing the
cost of the support structure.
Eliminates uneven ceiling levels or complex ceilingsupport systems and allows a consistent depth
throughout the job at no extra cost.
Lightweight compared to solid timber, making
handling and lifting on site much easier. Computer designed for optimum strength and accuracy.
Fully kiln dried timber ensures stability, free from
movement due to shrinkage
Manufactured to size and ready to install, eliminating
the need to trim on site. No material or labour wastage.
Each truss is job specific, minimising waste
More end types for fast fixing to steel, concrete,masonry or timber.
Wide and stable surface for fixing floor and ceiling
materials. Provides a stable surface for tradesmenmoving around the elevated areas of a job
More efficient use of natural resources than solid
timber joists
Standard data and design details available on CAD
PRODUCT BENEFITS
OPTION 2
Pryda Minigrip With Min. 3/35 x
3.15mm Dia. Pryda Nails Per Tab
OPTION 1
2/75 x 3.15mm
Dia. Skewed Nails
TYPICAL PLATE SUPPORT FIXING
75mm x 3.15mm
Dia. Skewed Nails
Preferred
Screw, Bolt orDrive Pin Fixing
TYPICAL BEAM SUPPORT FIXING OPTION 1
TYPICAL BEAM SUPPORT FIXING OPTION 2
Service PipesBetween Webs
Void Used For Service Duct
VOIDS ACCOMMODATING SERVICES
CANTILEVER SUPPORT
-
7/24/2019 Pryda Trussed
21/24P R Y D A R A F T E R T R U S S S Y S T E M S 2 1
PRYDA RAFTER TRUSS SYSTEMSPRYDA LONGREACH OR
PRYDA SPAN TRUSSES
AS ROOF PURLINSINTRODUCTION
Pryda Longreach and Pryda Span trusses are alsoavailable for use as part of the Pryda Roof Truss
System. The design and manufacturing principles use
similar standards to the floor trusses and therefore the
benefits associated with Longreach and Pryda Span can
be also be attained in roof construction.
Longreach and Pryda Span trusses are suitable as roof
purlins or rafters for all roof materials. Pryda roof trusses
are generally made to order with special fixingrequirements for stability and tie-down against wind
uplift.
LOADING
Permanent LoadsPermanent loads which are considered during the
design process include:
Self-weight of truss
Roof material (sheet steel, slate, tile, battens etc)
Ceiling material (plasterboard, battens)
Temporary LoadsTemporary (live) loads are those associated with non-trafficable roofs and are the result of stacked materials
or equipment used in repair and maintenance
operations. The minimum live load level stipulated inAS1170.1-1989 is 250 Pa on the plan projection of the
roof. However, the intensity of the load on a truss willincrease when the area supported by the truss is less
than 14 square metres. The design also considers the
concentrated load of a single person standing on the
cladding.
Wind LoadsCalculated in accordance with the Loading Code Part 2:
Wind Loads 1989 for the ultimate limit state.
Pryda Longreach or Pryda Span trusses are lightweight
and easy to handle compared to solid purlins/rafters and
this is an advantage when lifting into hard-to-get roofpositions.
Longreach can be manufactured to any depth to meet
height restrictions or match existing roof features.
The open web truss profile allows mechanical services
to pass through while special duct spaces may beincorporated into the profile for larger service pipes and
ducts.
Pryda trusses can be manufactured to suit any on-siteconfiguration using the numerous truss end-type details.
They may also be designed to incorporate box gutters.
Pryda roof trusses are manufactured in 70mm and
90mm wide timber which improves resistance to
buckling under wind loads and reduces the number ofrequired lateral restraints to the bottom chord.
In the same manner as floor trusses, the Pryda RoofSystem eliminates uneven ceiling levels or complex
ceiling support systems and allows a consistent depth
throughout the job.
PRODUCT BENEFITS
-
7/24/2019 Pryda Trussed
22/24P R Y D A R A F T E R T R U S S S Y S T E M S2 2
SPAN TABLES
There are two types of roof truss designs shown here Purlin trusses and Rafter trusses. The criteria for overall
heights, clear heights and construction is the same as for floor trusses.
Purlin Trusses
Purlin trusses run parallel to the ridge and are perpendicular to the plane of the roof. The steel sheeting is fixed directlyto the top of the chord, and a ceiling is assumed to be attached directly (or with battens) to the bottom chord.
PRYDA LONGREACH PURLIN TRUSSES - MAXIMUM SPANS
Steel roofing @ 900mm CRS; roof pitch 10 - 30 degrees
Truss Chord Size (TC and BC)
Reference 90x35 P10 90x35 P12 90x45 F17
Wind N1, N2 Wind N3 Wind N1, N2 Wind N3 Wind N1, N2 Wind N3
FT200P 5200 4200 5700 5000 6300 5900
FT250P 6500 4800 6600 6100 8200 7000
FT300P 6600 5500 7600 7000 9400 8100
FT350P 7500 6000 8500 8000 10500 9000
FT400P 8300 6600 9000 8800 11600 10000
PRYDA SPAN PURLIN TRUSSES - MAXIMUM SPANS
Steel roofing @ 900mm CRS; roof pitch 10 - 30 degrees
Truss Chord Size (TC and BC)
Reference 90x35 P10 90x35 P12 90x45 F17
Wind N1, N2 Wind N3 Wind N1, N2 Wind N3 Wind N1, N2 Wind N3
PS25P 6900 6000 7700 6600 8200 7900
PS30P 7600 6700 8900 7700 9400 9000
PS40P N/S N/S N/S N/S 13000 10500
N/S = not suitable
Rafter TrussesRafter trusses are often laid horizontally (like floor trusses), and are overlaid with graded purlins which provide a fall to
the roofing material. However, a small pitch may also be given to the rafter trusses with battens overlaid in the normal
manner. The steel sheeting is fixed to the purlins, and a ceiling is assumed to be attached directly (or with battens) to
the bottom chord.
PRYDA LONGREACH RAFTER TRUSSES - MAXIMUM SPANS
Steel roofing @ 900mm CRS; roof pitch 0 - 10 degrees
Truss Chord Size (TC and BC)
Reference 90x35 P10 90x35 P12 90x45 F17
Wind N1, N2 Wind N3 Wind N1, N2 Wind N3 Wind N1, N2 Wind N3
FT200R 5300 4700 6400 5400 7600 6500
FT250R 7000 5700 7700 6600 9100 7800
FT300R 7700 6300 8900 6700 10500 9000FT350R 8800 6600 9800 7500 11800 10100
FT400R 9500 7100 10800 8200 13100 11100
PRYDA SPAN RAFTER TRUSSES - MAXIMUM SPANSSteel roofing @ 900mm CRS; roof pitch 0 - 10 degrees
Truss Chord Size (TC and BC)
Reference 90x35 P10 90x35 P12 90x45 F17
Wind N1, N2 Wind N3 Wind N1, N2 Wind N3 Wind N1, N2 Wind N3
PS25R 7300 5800 7800 6700 9200 7900
PS30R 8300 6500 9000 7700 10000 9000
PS40R N/S N/S N/S N/S 12500 10500
N/S = not suitable
Note: For design specifications outside the scope of these tables (e.g. cyclonic wind zones) contact a Pryda design office.
-
7/24/2019 Pryda Trussed
23/24P R Y D A R A F T E R T R U S S S Y S T E M S 2 3
FACTORS AFFECTING
PERFORMANCE
The performance of Pryda Roof Trusses may be limitedby a number of factors including deflection under dead
load and timber strength capacity under a dead, live or
wind load case.
Deflection limitsLongreach and Pryda Span Roof Trusses are designed
according to deflection limits set out in AS1684.1.
Load Condition Max. Deflection Ratio
Permanent load span/300
Temporary live load span/250
Ultimate wind load span/150
Special loading conditionsAir conditioning units and other mechanical equipment
can add significant loads to roof trusses. Theintroduction of an increased truss spacing to incorporate
a skylight will also produce a special loading condition.The truss fabricator should be informed of these
conditions to accommodate special designs.
SERVICES
The span tables list the clear depth between chords if a
duct space is made available within the web profile,
while also indicating the maximum pipe diameter that
may be passed through the webs.
ALLOWABLE SPACE FOR SERVICES
End ConfigurationsThe full range of end configurations available tofloor trusses may also be incorporated into
Longreach and Pryda Span roof trusses. In
addition to this the end configuration may be
designed to fit a box gutter. This option is
available to all truss depths however the
dimensions of the box gutter may be limited.
BOX GUTTER OPTIONS
Pryda roof trusses must be fixed down to the supporting
structure using connections that match or exceed the
magnitude of the wind uplift forces on each truss. Eachtruss shall be held onto its supporting plate/bearer by a
minimum of 2/75x3.15mm skew nails, or one PrydaMinigrip or Multigrip with 3/35x3.15mm nails per tab.
Refer to AS1684-1999 for further guidance on fixings
and tie down requirements.
Pryda roof trusses shall also be braced laterally at the
ends of the trusses using Pryda Strap Braces at each
end of a run of trusses.
TIE DOWN AND
FIXING DETAILS
END BRACING AND TIE DOWN
Block Insert Option
On Site Construction Option
Max. 500mm
Max. Pipe Dia. Permitted In-Between
Web Profiles (Refer Span Tables)
Max. Clear
Depth
Minimum Tie Down 2/75 x 3.15mm
Skew Nails or Minigrip/Multigrip
With 3/35 x 3.15mm Nails in Each
Tab. Refer AS1684 For Minimum
Tie Down Requirements.Bend Steel Brace Over And
Fix With 3/35 x 3.15mm Nails
to Side And 2 Nails Over
Lateral Bracing at Ends of Trusses
Using Pryda Strap Brace or
Equivalent. Cross Brace at Each
End of a Run of Trusses.
-
7/24/2019 Pryda Trussed
24/24
Roof Battens Continuousin This Area
Roof Battens
Continuous in This Area
OBracing Between 30And 45O to Top Plate
When Viewed in Plan
Steel Brace
Box Gutter
End Type 1
Loadbearing
Wall Frame
Brick Parapet
Wall
30O-45O
Bottom chord bracingStrongbacks are not required forLongreach or Pryda Span roof trusses.
For suspended ceilings, or exposedbottom chords, or where ceiling battensdo not provide restraint to bottom
chords under wind uplift conditions,
it is recommended that bottom chord
ties are introduced in accordance
with AS4440 1999: Installation of
Nailplated Timber Roof Trusses. In
addition to this, Pryda Speed or StrapBraces shall be fixed to the truss
bottom chords to transfer bracing
loads back to the supporting structure
according to AS4440-1999: Installation
of Nailplated Timber Roof Trusses.
In circumstances where the ceilingmaterial and battens do provide effective
restraint then bottom chord ties shall not
be required.
BRACING
BRACING REQUIREMENTS FOR SUSPENDED CEILINGS AND
UNRESTRAINED BOTTOM CHORDS
TOP CHORD BRACING REQUIREMENTS
Top chord bracingThe forces generated by resistance to buckling of thetop chord and wind loading perpendicular to the span of
the trusses must also be transferred back to the
supporting structure by steel braces. It is recommended
that Pryda Speed Brace or Strap Brace be applied to
the top chord in conjunction with adequately spacedroof battens in accordance with AS4440 1999:
Installation of Nailplated Timber Trusses. The steel brace
shall be continuous over the ends of the trusses and be
anchored down to the top plate.
Steel Brace to Underside
of Bottom Chord to
Transfer Bracing Loads to
Structure
Longreach orPryda Span as
Roof TrussesBottom Chord Ties
Suspended
Ceiling
Note: Refer AS4440 -1947 Installation of
Nailplated Timber Trusses For Further Guidanceon Bottom Chord Restraint Requirements
45O
PRYDA AUSTRALIA
Head Office: 29 Healey Road, Dandenong, Vic 3175Tel: (03) 9706 5488 Fax: (03) 9706 5499
Website: www.pryda.com.au
Offices in Sydney Brisbane and Perth