– Read and Save These Instructions – This manual is provided to acquaint you with the Quest DEH 3000R so that installation, operation, and maintenance can proceed successfully. Ultimate satisfaction depends on the quality of installation and a thorough understanding of this equipment. Installation, Operation and Maintenance Instructions 4201 Lien Rd Madison, WI 53704 1-800-533-7533 www.QuestProtect.com [email protected] – Read and Save These Instructions – Specifications subject to change without notice. TS-721 08/11 1 Quest DEH 3000R Digital Control Quest DEH 3000R Digital Control: Digital control of relative humidity (Digital Set-Point) Fan/Filter operation Programmable ventilation timer Sleek design Large, easy-to-read backlit LCD display High temperature cut-out Dryout cycle timer Auto reboot quest quest

Upload: others

Post on 30-Jul-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

  • Installation, Operation and Maintenance Instructions

    – Read and Save These Instructions –

    This manual is provided to acquaint you with the Quest DEH 3000R so that installation, operation, and maintenance can proceed successfully. Ultimate satisfaction depends on the quality of installation and a thorough understanding of this equipment.

    Quest DRY 150

    Installation, Operation and Maintenance Instructions

    4201 Lien RdMadison, WI 53704 1-800-533-7533www.QuestProtect.com [email protected]

    – Read and Save These Instructions –

    Specifications subject to change without notice.TS-721

    08/111

    Quest DEH 3000R Digital Control

    Quest DEH 3000R Digital Control:

    • Digitalcontrolofrelativehumidity(DigitalSet-Point)

    • Fan/Filteroperation

    • Programmableventilationtimer

    • Sleekdesign

    • Large,easy-to-readbacklitLCDdisplay

    • Hightemperaturecut-out

    • Dryoutcycletimer

    • Autoreboot

    questquest

  • questquest1-800-533-7533

    2www.QuestProtect.com

    [email protected]

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    Table of Contents

    1.Specifications.................................................................. 32.Installation...................................................................... 3 2.1 ControlPanelInstallInstructions............................. 3 2.2 RemoteSensorInstallInstructions........................... 4 2.3 RemoteSensorUsage............................................. 4 2.4 RemoteSensorWiringInstructions.......................... 4 2.5 ControlPanelWiringInstructions............................ 5 2.6 AuxiliaryRelayOperation....................................... 6 2.7 Dehumidifierlock-OFForlock-ON........................ 7 2.8 Testing.................................................................... 83.Operation........................................................................ 9 3.1 Display................................................................... 9 3.2 Setting.................................................................. 10 3.3 PersonalSettingsReferenceList............................ 10 3.4 On/OffandDisplaySettings.................................. 10 3.5 SettingClock........................................................ 10 3.6 AdjustingtheRelativeHumidity............................ 11 3.7 FanSettingandOperation.................................... 11 3.8 DamperOperationandSetting(Ventilation)......... 12 3.9 TemperatureCutoutProgramming........................ 14 Warranty............................................................... 15

  • 1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    3www.QuestProtect.com

    [email protected]

    questquest

    24VACYellowWire 24VACRedWire

    DamperWhiteWire(Optional.See

    warningbelow)

    DehumidifierBlueWire

    FanGreenWire

    ON-Detect

    Common

    OFF-Detect

    NormallyOpen

    Common

    NormallyClosed

    OptionalUse

    OptionalUse

    MountingHole

    MountingHole

    1. SpecificationsPart#(P/N) 4028531Model: QuestDEH3000RDigitalControl

    Electrical: 24VAC

    MaxCurrent–DMP,COMP,FAN: 1Ampeach

    HumidityOperatingRange: 10–95%

    HumidityControlRange: 35–70%

    HumidityAccuracy: ±5%Output: 3Amps24VACAux.RelayCapacity 5AmpsTempRange/ 30°-90°F,2%AccuracySize 4.95"Lx1.06"Wx4.19"H

    FOR HVAC INSTALLER ONLY:

    2. InstallationInstalltheQuestDEH3000Rremotesensorinacentralareaofthestructurewhereitwillsensetherelativehumidityofthestructureaccurately.DonotinstalltheremotesensorwhereitmaynotaccuratelysensetherelativehumiditysuchasnearHVACsupplyregisters,nearexteriordoorsandwindows,ornearapoolorspa.Installinaccordancewithallapplicablecodesandstandards.

    2.1 Control Panel Install Instruc-tions1. Separatethefrontpanelfromtheback

    panelbydepressingthemiddlesectionsofthetopandbottomofthefrontpanel.

    2. Locatethewiringaccessholeinthewallorotherflatmountingsurface.Placethebackpanelintopositionanddrilltheappropriatemountingholes.

    3. Insertthescrewsandtighten.Levelasnecessary.

    4. Maketheelectricalconnectionstotheterminalsonthebackpanelasshownintheapplicablewiringdiagram(seeSections2.2-2.4).

    5. Testtheinstallation(seeSection2.5).

  • questquest1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    4www.QuestProtect.com

    [email protected]

    2.2 Remote Sensor Install InstructionsThis section is applicable only to customers who have purchased a remote sensor package. The standard DEH 3000 controller does not offer remote functionality.

    2.3 Remote Sensor Usage

    IMPORTANT!•Theuseofspraypaintonthesensorhousingmaydamagethesensorandisnotcoveredbytheproductwarranty.

    Theremotesensingoptionisusedwhenaninstallationrequiresmountingthehumidityandtemperaturesensoroutoftheconditionedspaceorwhenitisdesiredtospecificallymonitorandcontroltheconditionsataparticularlocationinalargerconditionedspace.

    Boththeneedforandlocationoftheremotesensorshouldbedeterminedbyaheating/coolingprofessional.

    2.4 Remote Sensor Wiring Instructions1.Routingsignalwires:

    Youwillberequiredtosupplyandroute24gauge,4conductorsolidwire(2-linetelephonewire)betweentheDEH3000Rcontrollerandtheremotesensorlocation.•Donotrunwireslongerthan100ft.

    •Theuseof24gaugewireisoptimal.Thinnergaugewiremaylimitsensordistance.Thickergaugeswillnotworkwithspliceconnectorsprovided.

    •Avoidroutingparalleltohighvoltagewiring.

    •Maintainadistanceof2ft.ormorefromhighvoltagelines.

    2.Sensorconnection:

    Thesensorcanbemountedtoawallorceilingsurface.Idealsensorlocationis5ft.abovethefloor.Wiresshouldexitthrougha½”diameterholeinthemountingsurfaceatthemountinglocation.Usetheprovidedsplice

  • 1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    5www.QuestProtect.com

    [email protected]

    questquest

    connectorstoconnectthe4wiresfromtheremotesensortotheuser-suppliedinterconnectwire.Besuretokeeppropercolorsattachedtoeachother.

    3.Sensormounting:

    Youwillneedtwoscrewstomountthesensor.Usethetwoslottedholestomountthebaseofthesensortothewallandthensnapthecoverintoplace.

    4.Controllerconnection:

    Usetheprovidedspliceconnectorstoconnectthe4wiresfromtheDEH3000Rtotheuser-suppliedinterconnectwire.Besuretokeepthepropercolorsattachedtoeachother.

    Continuewiththeinstallationasdescribedintherestofthismanual.

    2.5 Control Panel Wiring Instructions

    WARNING! DO NOT ALLOW THE YELLOW WIRE FROM THE QUEST DEHUMIDIFIER TO CONTACT THE RED OR WHITE WIRES FROM THE QUEST DEHUMIDIFIER, DAMAGE TO THE 24-VOLT TRANSFORMER WILL RESULT.

    WARNING! THE QUEST DEH 3000R DIGITAL CONTROL OPERATES ON A LOW VOLTAGE CIRCUIT (24 VAC) AND MUST NEVER CONTACT OR BE CONNECTED TO A HIGH VOLTAGE CIRCUIT.

    WARNING! UNPLUG THE QUEST DEHUMIDIFIER BEFORE WIRING THE DEH 3000R.Theinstallermustsupplyallfieldwiring,includingthewiringbetweentheQUESTdehumidifierandtheQuestDEH3000R.SomeofthecontrolwiresleavingtheQUESTdehumidifiermaynotbeusedinsomecontrolsituationsandshouldbeleftdisconnectedwithwirenutstapedontothestrippedends.

    BesuretoconsulttheelectricalschematicinthismanualortheinternalelectricalboxoftheQuestdehumidifierbeforemakinganycontrolconnections.

    WARNING! ONLY CONNECT THE WHITE WIRE TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH AN ELECTRIC DAMPER, OTHERWISE TRANSFORMER DAMAGE MAY RESULT.

  • questquest1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    6www.QuestProtect.com

    [email protected]

    TheWhitewirecontrolstheoptionalmotorizeddamperthatcanbeinstalledintoafreshairduct.ThisdamperprovidestheabilitytocontrolfreshairventilationusingtheventilationtimerfunctionoftheQuestDEH3000Randtheterminallabeled“DMP” (SeeSection3.8).Leavethe“DMP”terminalunusedifamotorizeddamperisnotused,andcapofftheWhitewirefromtheQuestdehumidifier.

    Standard wire colors for thermostats are as follows:

    Description Color Terminal code

    24VAC Red R

    CallforHeat White WorW1

    ForceFanOn Green G

    CompressorCallforCooling Yellow YorY1

    2.6 Auxiliary Relay OperationItmaybedesirabletocoordinatefanoperationofthecentralheating/coolingsystemwithdehumidifieroperation.TheQuestDEH3000Rcontainsarelaythatprovidesthisability.

    TherelayterminalslabeledNC,COMandNOoperateaccordingtothefollowingchart:

    DEHUMIDIFIER COM to NO COM to NC

    ON CONNECTED OPEN

    OFF OPEN CONNECTED

    Commonuses(assumingstandardthermostatwiringcolorsasnoted):

    NO

    COM

    NC

  • 1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    7www.QuestProtect.com

    [email protected]

    questquest

    Lock-out the A/C during dehumidificationThiswillturnofftheA/Cwheneverthedehumidifierruns.

    1.WiretheYellowthermostatterminaltotheNCterminalontheQuestDEH3000R.TheinstallermustsupplythewiringbetweentheQuestdehumidifierandthecontrolpanel.Besuretosafelyroutethecontrolwirestopreventdamageduringinstallation.BecarefulnottocrossthewireswhenconnectingtheQuestdehumidifierandtheremotecontrolpanelordamagetothetransformermayresult.

    2.RuntheYellowwirefromtheA/CunittotheCOMterminalontheQuestDEH3000R.

    Energize the A/C central fan during dehumidificationToautomaticallyruntheA/CFANwhenthedehumidifierruns.1.AttachasecondGreenwiretotheGreenfanwire

    terminalonthethermostat.2.ConnectthenewGreenwiretotheCOMterminalonthe

    QuestDEH3000R.3.RunawirefromtheRedterminalonthethermostatto

    theNO(NormallyOpen)terminalontheQuestDEH3000R.

    2.7 Dehumidifier lock-OFF or lock-ON:A/C sensor featureToautomaticallyactivateordeactivatethedehumidifierwhentheairconditionerruns.

    Activate dehumidification when the air-conditioner is running.A voltmeter is required for the next steps to ensure the correct wiring from the A/C transformer is used to set up the Lock-in dehumidifier function.

    1.ThecommonwirefromtheexistingA/Ctransformer(usuallyBlack)mustbeattachedtothe“COM”sensorterminalbetween“ON-D”and“OFF-D”ontheDEH3000R.

    TIP: The common wire can be identified as the wire from the A/C transformer that reads 0 volts between it and the Yellow air conditioning call for cooling wire.The incorrect wire will give a 20 to 28 volt reading.

    2.AnotherYellowwiremustbeaddedtothethermostatYellowterminalandruntothe“ON-D” sensorterminalontheQuestDEH3000R.

    A/C Unit

    Red

    Green

    Yellow

    A/C Unit

    Red

    Green

    Yellow

    A/C Unit

    Red

    Green

    Yellow

    A/C Unit

    Red

    Green

    YellowON-D

    COM

    OFF-D

    TO A/C

    TO A/C

  • questquest1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    8www.QuestProtect.com

    [email protected]

    Deactivate dehumidification when the air-conditioner is running.AvoltmeterisrequiredforthenextstepstoensurethecorrectwiringfromtheA/CtransformerisusedtosetuptheLock-outdehumidifierfunction.

    1. ThecommonwirefromtheexistingA/Ctransformer(usuallyBlack)mustbeattachedtothe“COM”sensorterminalbetween“ON-D”and“OFF-D”ontheDEH3000R.

    TIP: The common wire can be identified as the wire from the A/C transformer that reads 0 volts between it and the Yellow air conditioning call for cooling wire. The incorrect wire will give a 20 to 28 volt reading.

    2.AnotherYellowwiremustbeaddedtothethermostatYellowterminalandruntothe“OFF-D”sensorterminalontheDEH3000R.

    2.8 TestingVerifythewiringconnections.

    WARNING! ONLY CONNECT THE WHITE WIRE TO THE CONTROL IF IT IS WIRED IN A CIRCUIT THROUGH AN ELECTRIC DAMPER, OTHERWISE TRANSFORMER DAMAGE MAY RESULT.

    Aftercheckingthewiring,thisshorttestwillconfirmproperhook-up.

    1. InstallfrontcoveroftheQuestDEH3000R;connectthetopfirst,thenthebottom.2.PlugintheQUESTdehumidifier.TheQuestDEH3000Rshouldpowerup.3.TurntheQuestDEH3000RONbypressingthe“ON/OFF”button.4.VerifydehumidificationoperationbyadjustingtheRH“SETPOINT”tobelowthe“%RH”

    readingonthedisplay.Usethedown“RH”button.ConfirmQuestfanandcompressoroperation.BothshouldbeONnow.

    IncreasetheRH“SETPOINT”onthedisplaytowellabovethe“%RH”readingonthedisplay.Pressthe“RH”uparrowtoincreasetheRH“SETPOINT”.

    AfterrunningthedehumidifiercompressortheQuestDEH3000Rappliesa10minuterestartlockoutonallfunctions.Youwillhavetowaitfortherestartlockouttoexpire.

    5.VerifyFAN-onlyoperation:a.Checkthe“VENT”modeonthedisplay,itwilleitherbe“CLOSED”or“OPEN”.Ifitis“CLOSED”gotothenextstep.Ifitis“OPEN”,pressandholdthe“VENT”keyuntil“OPEN”flashesonthedisplay,releasethekeyandthenpressitonemoretime.“OPEN”willchangeto“CLOSED”.Don’ttouchthekeysforseveralsecondsuntilitstopsflashing.

    b.Pressandholdthe“FAN”buttonuntil“AUTO”beginsflashingonthedisplay,releaseit,andthenpressitagaintoswitchthefantothe“ON”setting.

    c.ConfirmthattheQUESTfanisON.QuestcompressormustbeOFF.Ventilationdamper(ifused)shouldbeCLOSED.

    6.VerifyoptionalVENToperation(ifelectricdamperisinstalled):a.Pressandholdthe“FAN”buttonuntil“ON”flashesonthedisplay.

    b.Releasethe“FAN”button,thenpressitagaintoswitchfanoperationto“AUTO”.

    TO A/C

    TO A/C

  • 1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    9www.QuestProtect.com

    [email protected]

    questquest

    c.Pressandholdthe“VENT”buttonuntil“CLOSED”flashesonthedisplay.

    d.Releasethe“VENT”button,thenpressitagaintoswitchventmodeto“OPEN”.

    e.ConfirmthattheQuestfanisON.VentilationdamperisOPEN.QUESTcompressormustbeOFF.

    f.Pressandholdthe“VENT”buttonuntilthe“OPEN”flashesonthedisplay.

    g.Releasethe“VENT”button,thenpressitagaintoswitchventmodeto“CLOSED”.

    Troubleshooting:Ifanyfunctionsarenotworkingproperly,checkthewiringandconnections.Avoltmetermaybeusedacrossterminalstoverifyvoltage.Ifthereisconcernaboutthedehumidifiernotoperatingproperly,theleadsexitingtheQUESTdehumidifiermaybeconnectedaccordingtothefollowingchart:

    Wire connections Operation

    Yellow&Blue Fan&Compressor

    Yellow&Green FanOnly

    WARNING!DO NOT MAKE ANY OTHER CONNECTIONS OR TRANSFORMER DAMAGE MAY RESULT.

    7.VerifyanyadditionaloptionalcontroloperationssuchasfaninterlockorA/Clockout.

    8.ProceedtotheOperationsection.

    FOR INSTALLER & OWNER:3. OperationOnthedisplayscreen,asolid“O”infrontofanyofthe3functions(SETPOINT,VENT,FAN)indicatesthefunctionisoperating.Aflashing“O”indicatesitisinawaitmodeandnotavailableatthemoment.No“O”indicatesthefunctioniscurrentlyOFF.

    Solid“O”before Indicates

    SETPOINT Dehumidifieron

    VENT Freshairventilationcycleinprogress

    FAN Fanon

    Waitmodeisafactory-programmedtimeperiodmeanttopreventshortcycles.Thisextendsthelifeofthedehumidifier.Whenaflashing“O”isencountered,theunitisinwaitmodeandIT COULD BE UP TO 10 MINUTES BEFORE OPERATION RESUMES.

    3.1 Display•Wheneverthereispowertothecontrol,itwilldisplaythetime,theday,%relativehumidity,andtemperature.

    •WhenthecontrolisactuallyswitchedON,the%RHsetpoint,fanstatus,runmode(programorhold),andfreshairventilationstatusisdisplayed.

    •Whenakeyispressedthedisplaywilllightforapproximately½aminute.

    •TheTimeandDayisdisplayedatthetopofthescreen.

  • questquest1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    10www.QuestProtect.com

    [email protected]

    •RHandTemperaturearedisplayedinrealtime.

    •Asolid“O”beforetheSETPOINT,VENT,ORFANindicatesthefunctionisoperating.

    •Aflashing“O”beforetheSETPOINT,VENT,ORFANindicatestheunitisinwaitmode.

    3.2 SettingDuringtheset-upprocess,ifyoumakeamistake,simplycontinue.Youcanalwaysgobacktoadjustthesettings.Ifyouleavethecontrolaloneanddon’ttouchanybuttonsfor10seconds,thecontrolwillrememberanychangesmadeandreturntothenormaldisplayscreen,allowingyoutoproceedtothenextstep.

    3.3 Personal Settings reference listPlease record your settings here.

    Function Factory setting My Setting

    SETPOINT(%RH) 50%

    VENT Closed

    FAN Auto

    TEMPCUTOUT 99°

    3.4 On/Off and display itemsPressthe“ON/OFF”buttontoturnthesystemONorOFF.

    WhenthesystemisON,thesetpoint,fanstatus,operationmode(RUNorHOLD),andfreshairventstatusisdisplayed.

    WhenthesystemisOFF,thecontrolwilldisplaythetime,day,%RH,andtemperature.

    Whentheunitisshipped,itisinmanual(hold)mode.

    3.5 Setting Clock Time1.Pressandholdthe“CLOCK”button.Thehourdisplaywillflash.Releasethebutton.

    2.Usetheup/down“RH”buttonstochangethevalue.

    3.Pressthe“CLOCK”buttonagainandtheminutedisplaywillflash.Usethe“RH”buttonstochangethevalue.

    4.Pressthe“CLOCK”buttonagainandAMorPMwillflash.Usethe“RH”buttonstochangethevalue.

    5.Pressthe“CLOCK”buttonagainandthedaydisplaywillflash.Usethe“RH”buttonstochangethevalue.

    6.Don’ttouchanybuttonsforseveralsecondsuntilthedisplaystopsflashing,thiswillsaveyoursettings.Ifyouneedtochangeanythinggobacktostep#1.

  • 1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    11www.QuestProtect.com

    [email protected]

    questquest

    3.6 Adjusting the relative humidity “SETPOINT” TheQuestDEH3000Rsensestheambientrelativehumidity(%RH)ofthespaceinwhichitislocated,itcomesfactorypresettohold50%relativehumidity.

    Therelativehumidity“SETPOINT”(desiredRHtobemaintained)operatesthedehumidifierfunctionoftheQuestdehumidifier.IthasnoeffectontheoptionalVENT(freshairventilation)orFAN(airrecirculation)functionsiftheyarebeingused.

    OperationThestandardrangethatthedehumidifierholdsaroundyour“SETPOINT”is3%.Withasetpointof50%,thedehumidifierwillrununtiltherelativehumidityreaches47%.Thedehumidifierwillthenswitchoffuntiltherelativehumidityreaches53%.

    Ifthesetpointishigherthantheambientrelativehumidity,thespacedoesnotneedtobedehumidifiedsothedehumidifierwillnotrun.

    Example:Setpoint:50%RH

    Currentcondition:45%RH–Thedehumidifierwillbeoff(no“O”indicatorwillbedisplayed).

    Ifyoursetpointisbelowtheambientcondition,thedehumidifierwillbeonand“O”willdisplay.

    Example:Setpoint:50%RH

    Currentcondition:55%RH–Thedehumidifierwillbeon(“O”displayed).

    3.7 Fan Setting and OperationUsethe“FAN”buttontochangethefanoperation.Thereare2choicesforfanoperation:“ON”or“AUTO”.Thefactorypresetis“AUTO”.

    “ON”–ThefanintheQuestdehumidifierwillruncontinuously.Thisdoesnotaffecteitherthedehumidificationorventilationfunctionsofthesystem.Thesystemmayormaynotbeventilatingordehumidifyingwhilethefanisrunning.Thissettingiscommonlyusedformaximumairfiltrationand/orairrecirculation.

    “AUTO”–IndicatesthefanwillrunwhentheQuestDEH3000Rcallsfordehumidificationorventilation.Ifthecontrolhasnotcalledfordehumidificationfor3hours,thecontrolwillautomaticallyrunthedehumidifierfanfor10minutes.

    Afteradehumidificationcycle,thefanautomaticallyshutsofffor10minutes.Thispauseallowsthewatertodrainfromthedehumidifier.

    Asolid“O”indicatesthefanisoperating.Aflashing“O”indicatesthefanisinawaitmode.No“O”indicatesthefanisOFF.

    Tosettheoperation:1.Pressandholdthe“FAN”button.Thecurrentfansettingwillbegintoflashonthedisplay.Releasethebutton.

    2.Pressthe“FAN”buttontotogglebetweenthe“ON”and“AUTO”modes.

    Withthefaninthe“AUTO”mode,thefanwilloperateonlywhenneededbyotherfunctionsofthesystem.ThefanwillremainOFFunlessthesystemisdehumidifyingorventilating.Thefanalwaysrunsduringdehumidificationandventilationandthefan“O”iconwillbelit.TocompletelyturnthesystemOFF,usethe“ON/OFF”buttonasdescribedearlier.

  • questquest1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    12www.QuestProtect.com

    [email protected]

    3.8 Damper Operation and Ventilation, Manual (Hold) ModeThe“VENT”settingcontrolstheventilationfunctionofthesystem.Ithasnocontroloverthedehumidificationfunction.Inordertoprovideventilation,themotorizeddampermustbeopenandthefanmustberunning.Thecontrollertakescareofthesetwofunctionsautomaticallysothatwheneverthedamperisopen,thefanisrunning.

    Theventilationindicator“O”willbedisplayedwhenevertheunitisventilating.Thefanoperationindicator“O”willalsobelit.

    Therearethreedamperoperationmodes:1.“OPEN”–holdmode:Thedamperwillbeopenandthedehumidifierfanwillbecontinuouslyoperatingtointroducefreshairintothespace.Usethismodeforcontinuousfreshairventilation.Thefanisalwaysonwhenthedamperisopen.

    2.“CLOSED”–holdmode:Thedamperwillneveropen,andthedehumidifierwillnotventilate.Thefanwillstilloperatenormallyforrecirculationanddehumidification.

    3.“PROGRAMMED”mode:TheQuestDEH3000Rwilloperatethemotorizeddamperandthedehumidifierfanaccordingtotheprogrammedventilationschedule(Section3.9).

    Thefactorypresetforthe“VENT”settingis“CLOSED”.

    Toset“OPEN”–holdor“CLOSED”–holdventilationoperation:1.Pressthe“VENT”button.Thecurrentsettingwillbegintoflashonthedisplay.Releasethebutton.

    2.Pressthe“VENT”buttonagaintoswitchbetween“OPEN”and“CLOSED”.

    3.Leavethecontrolalonefor10secondsandyoursettingswillbesaved.

    Damper Operation and Ventilation, Programmed VentilationThisexampleshowsthesysteminprogrammode(denotedbytheschedule15minuteson,5minutesoffandthewordRUNinthelowerrightcornerofthedisplay).

    TheQuestDEH3000Rwilloperatefreshairventilationaccordingtoyourventilationprogram.ThecontrolneedstobeprogrammedtoturntheventilationfunctionONandOFFatthedesiredintervals.Thisisdonebyprogrammingtheventilationtimer.

    Therearetwoprogramsavailableforventilation:1.MondaythroughSunday

    2.MondaythroughFriday&Saturday/Sunday

    Eachblockofdayshasamorningscheduleandanightschedule.Morningisthefirst12hoursofthedayandnightisthesecond12hours.

    Eachschedulehas:

    •A“START”timewhentheventilationschedulebegins,

    •An“OPEN FOR”durationfortheamountoftimethedamperstaysopenin5minuteintervals,from0to60,

    •And“CLOSED FOR”durationwhichclosesthedamperforaspecifiedtimein5minuteintervalsfrom0to60.

  • 1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    13www.QuestProtect.com

    [email protected]

    questquest

    Setting the Ventilation Program:

    1.Pressthe“PROGRAM ENTER”buttonuntilthefollowingmenuappears:

    2.Usingtheup/down“RH”buttons,highlight“PROGRAM”andselectitbypressingthe“PROGRAM ENTER”button.Thefollowingmenuappears:

    Youcanselectfrom:“MON-FRI”“SAT-SUN”forseparateweekdayandweekendschedules,or“MON-SUN”whichgivesyouequalweekdayandweekendschedules.

    3.UsingtheUp/Down“RH”buttons,highlightandthenselectoneofthetwochoices.Theexamplegivenshowshowtoprogramseparateweekdayandweekendschedules.Thesamemethodisusedifyouchoosetheotherprogram.

    Example:menuwhenyouselect“MON-FRI”“SAT-SUN”:

    1.Enterthestartingtimeforweekdaysusingtheup/down“RH”buttonstochangethetime.

    2.Pressthe“PROGRAM ENTER”buttontoswitchtothe“OPEN FOR”setting.Usingtheup/down“RH”buttons,changethedurationthatthedamperwillventilatefreshair.

    3.Pressthe“PROGRAMENTER”buttontoswitchtothe“CLOSEDFOR”setting.Usingtheup/down“RH”buttons,changethedurationthatthedamperwillremainclosedbetweenventilationcycles.

    Fortheexamplegiven,startingat8:00AMinthemorning,thecontrolwillventilatefreshairfor15minutesthenstopfor15minutes.Thisscheduleof15minutesopen,15minutesclosedwillcontinueuntilthestarttimeofthenightschedule.

    Morningscheduleisavailableanytimefrom12:00AMuntil11:59AM.

    Nightscheduleisavailableanytimefrom12:00PMuntil11:59PM.

    4.Press“PROGRAMENTER”againtogotothe“MON-FRI”nightschedule.Repeatthestepslistedaboveforthisandthe“SAT-SUN”dayandnightschedules.

  • questquest1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    14www.QuestProtect.com

    [email protected]

    Whenyouhavefinishedprogrammingyourschedule(eitherthe7-dayversionortheweekday/weekendsplitversion),usethedown“RH”buttontohighlighttheEXIToptionandthenpress“PROGRAM ENTER”toselectit.

    RunningtheVentilationProgram

    Pressandholdthe“PROGRAM ENTER”buttonuntilthe“PROGRAM”screenappears.

    Usethedown“RH”buttontohighlight“RUN PROGRAM”:

    Thenpress“PROGRAMENTER”toselectit.Thedisplaywillappearasfollows:

    3.9 Temperature Cutout ProgrammingDehumidifiersproduceheatwhendehumidifyinganddependinguponoutsideconditions,theventilationfunctionmayalsointroducewarmair.Someconditionsmayintroduceenoughheattodrivetemperaturesup.TheQuestDEH3000RtemperaturecutoutfeaturedisablesallQuestoperationsiftemperaturesreachthecutoutsetpoint.

    Inmostinstallationsthisfeaturewillnotneedtobeused(thecutoutisfactorysetto99°F).Ifalowertemperaturecutoutisdesired,programthesetpointbypressingandholdingthe“PROGRAMENTER”buttonuntilthe“PROGRAM”screenappears.Presstheup/down“RH”buttonsuntil“TEMPCUTOUT”highlighted.Thenpressthe“PROGRAMENTER”buttonagaintoselectit.Nowusethe“RH”upor“RH”downbuttonstoadjustthesetpoint.Press“PROGRAMENTER”toreturntothehomescreen.

  • 1-800-533-7533

    Quest DEH 3000R Installation, Operation and Maintenance Instructions

    15www.QuestProtect.com

    [email protected]

    questquest

    WARRANTOR: Therma-StorLLC4201LienRdMadison,WI53704Telephone:1-800-533-7533

    WHO IS COVERED: Thiswarrantyextendsonly to theoriginalresidentialend-userof theQuestDEH3000RDehumidifier&VentilationSystemController,andmaynotbeassignedortransferred.

    FIRST YEAR WARRANTY: Therma-StorLLCwarrantsthat,forone(1)yeartheQuestDEH3000RDehumidifier&VentilationSystemControllerwilloperatefreefromanydefects inmaterialsandworkmanship,orTherma-StorLLCwill,atitsoption,repairorreplacethedefectivepart(s),freeofanycharge.

    END-USER RESPONSIBILITIES:WarrantyservicemustbeperformedbyaServicerauthorizedbyTherma-StorLLC.Iftheend-userisunabletolocateorobtainwarrantyservicefromanauthorizedServicer,heshouldcallTherma-StorLLC at theabovenumberandask for theTherma-StorLLCServiceDepartment,whichwillthenarrangeforcoveredwarrantyservice.Warrantyservicewillbeperformedduringnormalworkinghours.

    TheEnd-usermustpresentproofofpurchase(lease)uponrequest,byuseofthewarrantycardorotherreasonableandreliablemeans.Theend-userisresponsiblefornormalcare.Thiswarrantyonlyappliestoresidentialapplicationsanddoesnotcoveranydefect,malfunction,etc.resultingfrommisuse,abuse,lackofnormalcare,corrosion,freezing,tampering,modification,unauthorizedorimproperrepairorinstallation,accident,actsofnatureoranyothercausebeyondTherma-StorLLC'sreasonablecontrol.

    LIMITATIONS AND EXCLUSIONS:IfanyQuestDEH3000RDehumidifier&VentilationSystemControllerpartisrepairedorreplaced,thenewpartshallbewarrantedforonlytheremainderoftheoriginalwarrantyperiodapplicablethereto(butallwarrantyperiodswillbeextendedbytheperiodoftime,ifany,thattheQuestDEH3000RDehumidifier&VentilationSystemControllerisoutofservicewhileawaitingcoveredwarrantyservice).

    UPONTHEEXPIRATIONOFTHEWRITTENWARRANTYAPPLICABLETOTHEQuestDEH3000RDehumidifier&VentilationSystemControllerORANYPARTTHEREOF,ALLOTHERWARRANTIESIMPLIED BY LAW, INCLUDING MERCHANTABILITY AND FITNESS FOR A PARTICULARPURPOSE, SHALLALSO EXPIRE. ALLWARRANTIESMADEBYTHERMA-STOR LLC ARE SETFORTHHEREIN,ANDNOCLAIMMAYBEMADEAGAINSTTHERMA-STORLLCBASEDONANYORALWARRANTY. INNO EVENT SHALLTHERMA-STOR LLC, IN CONNECTIONWITHTHESALE,INSTALLATION,USE,REPAIRORREPLACEMENTOFANYQuestDEH3000RDehumidifier&VentilationSystemControllerORPARTTHEREOFBELIABLEUNDERANYLEGALTHEORYFORANYSPECIAL,INDIRECTORCONSEQUENTIALDAMAGESINCLUDINGWITHOUTLIMITATIONWATER DAMAGE (THE END-USER SHOULD TAKE PRECAUTIONS AGAINST SAME), LOSTPROFITS,DELAY,ORLOSSOFUSEORDAMAGETOANYREALORPERSONALPROPERTY.

    Somestatesdonotallowlimitationsonhowlonganimpliedwarrantylasts,andsomedonotallowtheexclusionorlimitationofincidentalorconsequentialdamages,sooneorbothoftheselimitationmaynotapplytoyou.

    LEGAL RIGHTS: Thiswarrantygivesyouspecificlegalrights,andyoumayalsohaveotherrightswhichvaryfromstatetostate.