quincy rotary screw sales manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf ·...

78
SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This specification is for a fluid-flooded rotary screw compressor with a minimum capacity of 245 CFM (total package rated performance measured in accordance with CAGI-PNEUROP Test Code PN2CPTC2) at a full load pressure rating of 110 PSIG. This compressor shall be capable of full load operation at 110 PSIG and have a maximum pressure capability of 125 PSIG. 2. Airend. 2.1 The airend shall have a 4-6 lobe combination with both male and female rotors being identical in diameter. 2.2 The discharge end of the rotors shall be supported by a triplex bearing arrangement on the male rotor and a duplex bearing arrangement on the female rotor. The suction end of the rotors shall be supported by a single row of cylindrical roller bearings. 2.3 The airend shall have an axial flow inlet housing to allow incoming air to enter the compression area over the entire face of the rotors. Radial inlet arrangements will not be accepted. This inlet housing shall bolt directly to a "C"-faced drive motor to maintain permanent rotor shaft to motor shaft alignment. 2.4 The discharge bearings must be housed in the main rotor housing to maintain permanent rotor alignment within the rotor housing. Separate, bolt-on castings for discharge bearings will not be accepted. 2.5 The area around the bearings shall be free of any obstruction to the free flow of fluid. Pockets or reservoirs where fluid might collect in the bearing area shall have a magnetic drain plug to trap metallic contamination. This drain plug shall be of sufficient size and conveniently located to allow the regular cleaning of pockets or reservoirs in the bearing area. 2.6 Male rotor RPM shall be identical to the actual speed of the main drive motor. The tip speed of the driven rotor shall not exceed 19 meters per second. 2.7 The motor and airend shall be directly coupled through a flexible drop-out type coupling. No belts or gears shall be included in the drive arrangement. 2.8 The drive rotor shall have a redundant shaft sealing arrangement. Should the primary shaft seal fail, a secondary seal shall be capable of preventing fluid from leaking out of the _________Quincy Rotary Screw Sales Manual____________ Rev.3.15.97 QSI - 11 Back to TOC

Upload: others

Post on 04-Aug-2020

4 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245

1. Scope of supply.

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 245 CFM (total package rated performance measured in accordance withCAGI-PNEUROP Test Code PN2CPTC2) at a full load pressure rating of 110 PSIG.This compressor shall be capable of full load operation at 110 PSIG and have a maximumpressure capability of 125 PSIG.

2. Airend.

2.1 The airend shall have a 4-6 lobe combination with both male and female rotors beingidentical in diameter.

2.2 The discharge end of the rotors shall be supported by a triplex bearing arrangementon the male rotor and a duplex bearing arrangement on the female rotor. The suction endof the rotors shall be supported by a single row of cylindrical roller bearings.

2.3 The airend shall have an axial flow inlet housing to allow incoming air to enter thecompression area over the entire face of the rotors. Radial inlet arrangements will not beaccepted. This inlet housing shall bolt directly to a "C"-faced drive motor to maintainpermanent rotor shaft to motor shaft alignment.

2.4 The discharge bearings must be housed in the main rotor housing to maintainpermanent rotor alignment within the rotor housing. Separate, bolt-on castings fordischarge bearings will not be accepted.

2.5 The area around the bearings shall be free of any obstruction to the free flow of fluid.Pockets or reservoirs where fluid might collect in the bearing area shall have a magneticdrain plug to trap metallic contamination. This drain plug shall be of sufficient size andconveniently located to allow the regular cleaning of pockets or reservoirs in the bearingarea.

2.6 Male rotor RPM shall be identical to the actual speed of the main drive motor. Thetip speed of the driven rotor shall not exceed 19 meters per second.

2.7 The motor and airend shall be directly coupled through a flexible drop-out typecoupling. No belts or gears shall be included in the drive arrangement.

2.8 The drive rotor shall have a redundant shaft sealing arrangement. Should the primaryshaft seal fail, a secondary seal shall be capable of preventing fluid from leaking out of the

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 11

Back to TOC

Page 2: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

airend. A method of detecting a primary shaft seal failure while the machine is inoperation shall be provided.

3. Drive motor.

3.1 The main drive motor shall be 50 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

3.2 The main drive motor shall have an ODP enclosure.

3.3 The main drive motor shall be of a "C"-faced design so that it can be rigidly bolted tothe airend assembly.

4. Cooling system.

4.1 The compressor shall be air-cooled.

4.2 The cooling system shall be capable of maintaining proper compressor temperaturesin ambient conditions up to 110oF.

4.3 Coolers shall be vertical draft.

4.4 Fluid circulation shall be by positive displacement pump.

5. Aftercooler.

5.1 An air-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to have an approach temperature of not more than5oF at standard conditions.

5.2 A 99.9% efficient moisture separator and trap shall be included.

6. Compressor Fluid.

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use.

6.2 The fluid shall contain no chemical substances that would require it to be treated ashazardous according to the appropriate laws in effect at the time of sale. Used fluid shallbe suitable for recycling along with other waste petroleum oil.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 12

Back to TOC

Page 3: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

6.3 Fluid carryover into the downstream air system shall not exceed 3 PPM by weightwith new elements.

6.4 A fluid filter shall be provided with a 10 micron absolute rating. The filter media mustbe microfiberglass. Paper media will not be accepted.

7. Compressor controls.

7.1 The compressor controls shall allow for full range modulation to match compressorcapacity to system demand. If system demand should fall below a user adjustable percentof compressor capacity, the compressor shall go into an unloaded condition. Anadjustable timer shall be provided to shutdown the compressor if it runs in the unloadedmode for a predetermined length of time. The compressor shall automaticallyreload/restart if the system pressure falls below the set point. A selector switch on thecontrol panel shall be provided to allow the user to bypass the automatic shutdown featureand elect a continuous run mode should the system demand dictate.

7.2 Gauges or indicators shall also be provided to indicate:A) Compressor discharge temperatureB) Discharge air pressure C) Percent capacity D) Operating modeE) Power onF) Running hours

7.3 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown (Probes must be provided at the compressordischarge and the air/fluid separator reservoir to monitor high temperatureconditions)B) Motor overload (This should alert a motor overload for all motors on thecompressor package)C) Change inlet filterD) Change fluid filterE) Change Separator Element

This shutdown and maintenance annunciator panel shall be constructed in such a way thatconnections for remote annunciation can easily be made.

8. Electrical controls.

8.1 All electrical controls shall be designed and constructed in accordance with NationalElectrical Code (NEC) guidelines.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 13

Back to TOC

Page 4: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.2 The main starter control box shall be NEMA 1 design and contain starters for themain drive motor and fan motor along with other electrical controls.

8.3 All components within the main starter control box shall be UL and/or CSA approvedor listed.

8.4 The main starter control box shall be UL and/or CSA approved or listed.

8.5 Remote mounted starter control panel boxes will not be accepted.

9. Safety system.

9.1 Pressure vessels shall be ASME coded.

9.2 A pressure relief safety valve shall be provided. This valve shall be sized to handle thefull capacity of the compressor. It shall have a single, directed outlet. Multidirectionalvalves will not be accepted.

9.3 A high air/fluid temperature shutdown system shall be provided. This system shalloperate with a minimum of two temperature sensors. One sensor must be located directlyin the discharge air stream of the airend. One sensor must be located on the dry side ofthe air/fluid separator element. This system must be designed to prevent the compressorfrom running with a failed sensor.

10. Sound levels.

10.1 Sound levels shall not exceed 82 dB(A) when measured in free field conditions, 1meter away from the compressor.

OPTIONSReplace section in main bid spec with appropriate section below for desired option.

**** AUTO DEMAND CONTROL

7.1 In the "LOCAL" control mode, the compressor controls shall allow for full rangemodulation to match compressor capacity to system demand. If system demand shouldfall below a predetermined percentage of compressor capacity, the compressor shall gointo an unloaded condition. An adjustable timer shall be provided to shutdown thecompressor if it runs in the unloaded mode for a predetermined length of time. Thecompressor shall automatically restart if the system pressure falls below the set point. In

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 14

Back to TOC

Page 5: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

the "REMOTE" control mode, control of the compressor shall be transferred to a remotecontroller that shall operate the compressor in conjunction with one or more othercompressors. The actual operation of the compressor will be identical to the "LOCAL"mode except the remote controller will determine pressure set points.

**** 200 VOLT

3.1 The main drive motor shall be 50 nameplate horsepower rated for 200 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 230 VOLT

3.1 The main drive motor shall be 50 nameplate horsepower rated for 230 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 575 VOLT

3.1 The main drive motor shall be 50 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** NEMA 4

8.2 The main control box shall be NEMA 4 design and contain starters for the main drivemotor and fan motor along with other electrical controls.

**** NEMA 12 (use NEMA 4)

8.2 The main control box shall be NEMA 4 design and contain starters for the main drivemotor and fan motor along with other electrical controls.

**** FOOD GRADE FLUID

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use. It shall meet FDA CFR 178.3570 spec for food grade lubricants.

**** FULL CANOPY

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 15

Back to TOC

Page 6: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

1.2 The compressor shall have a full metal enclosure with quick release panels for easyaccess to service and maintenance items.

(WITHOUT SHROUDS)

10.1 Sound levels shall not exceed 77 dB(A) when measured in free field conditions, 1meter away from the compressor.

(WITH LOW SOUND SHROUDS)

10.1 Sound levels shall not exceed 73 dB(A) when measured in free field conditions, 1meter away from the compressor.

(WATER-COOLED)

10.1 Sound levels shall not exceed 73 dB(A) when measured in free field conditions, 1meter away from the compressor.

**** WATER-COOLED

4.1 The compressor shall be water-cooled.

4.3 Coolers shall be shell and tube type water-cooled coolers. The coolers shall be sizedto maintain normal operating temperatures with inlet water temperatures as high as 100oF.Water pressure drop through the cooling system shall be no more than 3 PSIG.

5.1 A water-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to cool the discharge air temperature to within15oF of the inlet water temperature.

10.1 Sound levels shall not exceed 80 dB(A) when measured in free field conditions, 1meter away from the compressor.

**** SOLID STATE REDUCED VOLTAGE STARTERS

8.2 The main starter control box shall be NEMA 1 and shall contain provisions to connecta remotely mounted solid state reduced voltage starter for the main drive motor. Motorprotection shall include:

a) Shorted SCR detectionb) Phase lossc) Overloadd) Current flow sensinge) Short circuit protection

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 16

Back to TOC

Page 7: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

f) Anti-oscillation circuitTorque, ramp time and current limit shall be adjustable. An LED display shall indicate thefollowing:

a) Power Onb) Startc) Current Flowd) Run e) At Speed f) Over Temperatureg) Overloadh) Phase Lossi) Shorted SCRj) Short Circuitk) Shunt Trip

Output relays shall be provided to indicate the following:a) Run b) Shunt Trip c) Programmable Status Relay - Will energize on any one of the followingconditions (jumper selectable): At Speed, Phase Loss, Over Temperature,Overload, Shorted SCR and Over Current

8.5 Remote mounted control panel boxes will be accepted.

**** 125 PSIG FULL LOAD OPERATION

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 243 CFM (measured in accordance with CAGI-PNEUROP Test CodePN2CPTC2) at a full load pressure rating of 125 PSIG. This compressor shall be capableof full load operation at 125 PSIG and have a maximum pressure capability of 140 PSIG.

3.1 The main drive motor shall be 60 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 200 VOLT

3.1 The main drive motor shall be 60 nameplate horsepower rated for 200 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 230 VOLT

3.1 The main drive motor shall be 60 nameplate horsepower rated for 230 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 17

Back to TOC

Page 8: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

**** 575 VOLT

3.1 The main drive motor shall be 60 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** Power$ync®

2.9 The airend shall have a method of controlling displacement at operating speed thatdoes not introduce areas of unswept volume or clearance pockets into the rotor bores.Lift valves that extend into the rotor bore prior to final machining and are machined to theexact tolerance of the rotor bore as the rotor bore is being machined are the preferredmethod of capacity control. Lift valves must be double acting to use air pressure to bothopen and close.

7.1 The compressor controls shall be microprocessor-based. There shall be threeuser-selectable control methods.

A) Constant Run Mode -- This method shall allow the operator to set anoperating pressure range within which the compressor will adjust its capacity tosatisfy the system demand or unload during periods of no demand. B) Auto Dual Mode -- This method shall allow the operator to set an operatingpressure range within which the compressor will adjust its capacity to satisfy thesystem demand or unload during periods of no demand. After a user-definedperiod of unloaded operation, the compressor will automatically shutdown andassume a standby mode. Should system demand return, the compressor willautomatically restart. C) Network Mode -- In place of the pressure deadband, the Network Mode shalluse a target pressure and a variable response rate. The control shall maintain thesystem pressure to within two or three pounds of the target pressure. In the upper50% of the capacity range, the control shall match system demand withoutrestricting the inlet air flow. In the lower 50% of the capacity range, the controlshall select either a load/no load or modulating control method, based onuser-defined parameters.

7.2 A complete, redundant electro-mechanical control system shall be included that willsafely operate the compressor in the event of a microprocessor failure. This system shallbe user selectable from a switch mounted in the main electrical control enclosure.

7.3 LED displays shall be provided that will constantly indicate discharge temperature andsystem pressure.

7.4 A four-line by forty-character LCD display shall be provided that will allow access tothe following information:

Power-Up Warning Displays:A) Sump Pressure Sensor Failure

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 18

Back to TOC

Page 9: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

B) Line Pressure Sensor FailureC) Discharge Temperature Sensor FailureD) Sump Temperature Sensor FailureE) Tripped Motor OverloadF) Relay Board Communication FailureG) Diagnostic FailureH) Setup Memory FailureI) Control Relay Not DisengagedJ) Main Motor Contactor Not DisengagedK) Wye Contactor Not Disengaged (on Wye-Delta starters)L) Deadband Data ErrorM) Setup Memory ErrorN) Setup Data Not InitializedO) Air Filter Vacuum Switch FaultyP) Fluid Filter Delta-P Switch FaultyQ) An Element Needs ServicingR) Minor Diagnostic FailureS) Machine ID Error

Operational Displays: A) Sump Pressure Too High For RestartB) Compressor Is Starting

C) **Warning** Possible Reverse RotationD) Compressor Is Running In Auto-Dual ModeE) Compressor Is UnloadedF) Time Left To ShutdownG) Compressor Has Timed Out And Shut Down **Warning** Will

Automatically RestartH) Running In Continuous Run ModeI) Running In Network Mode Position __ Of __J) Programmed ShutdownK) **Warning** An Element Needs ServicingL) Emergency Stop Button Has Been PressedM) ** Warning** Setup Memory FailureN) ** Warning** Sequence Data ErrorO) ** Warning** Schedule Data ErrorP) ** Warning** Compressor ID Already In UseQ) ** Warning** High Discharge TemperatureR) ** Warning** High Sump TemperatureS) ** Warning** High Sump PressureT) ** Warning** Motor OverloadU) ** Warning** Contactor Is Not EngagingV) ** Warning** Contactor is Not DisengagingW) Discharge RTD Faulty Or Disconnected

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 19

Back to TOC

Page 10: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

X) Sump RTD Faulty Or DisconnectedY) Line Pressure Sensor FaultyZ) Sump Pressure Sensor FaultyAA) ** Warning** Communication FailureBB) ** Warning** Firmware FailureCC) Compressor Not In Scheduled Sequence

Adjustable Operating Parameters: A) Compressor Unloaded PressureB) Compressor Loaded PressureC) Timed Stop Delay In MinutesD) Cycle CountE) Short Cycle Time In SecondsF) Target PressureG) Network Unloaded PressureH) Network Loaded PressureI) Modulation Turn Off Delay In MinutesJ) Machine IDK) Sequence Number To Change L) Day To ChangeM) Clear SequenceN) Clear Sequence And ScheduleO) Set Delayed Unload ModeP) Set Immediate Unload Mode

Maintenance Displays:A) Loaded HoursB) Unloaded HoursC) Hours Since Last Fluid ChangeD) Control Line Filter HoursE) Intake Filter HoursF) Fluid Filter HoursG) Separator Element HoursH) View Current Time And DateI) Set Time And Date J) Compressor Control TestK) Serial NumberL) Software Version NumberM) Compressor ModelN) Drive Motor HorsepowerO) VoltageP) Starter TypeQ) Cooling TypeR) Airend Type S) High Air Temperature Shutdown Setting

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 20

Back to TOC

Page 11: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

T) High Sump Pressure Shutdown SettingU) Maximum Unloaded Pressure Setting V) Minimum Loaded Pressure SettingW) Current Loaded Pressure SettingX) Current Unloaded Pressure SettingY) Current Target Pressure SettingZ) Machine IDAA) Auto Dual Shutdown Timer SettingBB) Wye Delta Transition Time SettingCC) Modulation Cycle Count SettingDD) Modulation Time SettingEE) Sump Temperature FF) Pressure Transducer Calibration DateGG) Temperature Sensor Calibration DateHH) Unit Configuration DateII) Current Time And DateJJ) Modem Baud RateKK) Shutdown LogLL) Network Diagnostics

7.5 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown B) Motor overload C) High Sump Pressure ShutdownD) Change inlet filterE) Change lubricant filterF) Change Separator Element

7.6 The control shall have the built-in capability to network up to 16 similar compressorsof various sizes. In this network configuration, the sequence in which the compressorsoperate as base load and trim shall be user selectable. The control shall be able to store nofewer than nine different sequences. An internal clock and calendar shall be included thatwill allow different sequences to be scheduled no fewer than nine times per day. Thecontroller shall have the ability to schedule each day of the week differently.

7.7 The controller shall include a shutdown log that will allow the operator to viewservice and shutdown alarms in the reverse order of occurrence. The log shall give plainEnglish messages that will identify the source of the alarm.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 21

Back to TOC

Page 12: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

SAMPLE BID REQUEST SPECIFICATION FOR A QSI 370

1. Scope of supply.

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 370 CFM (total package rated performance measured in accordance withCAGI-PNEUROP Test Code PN2CPTC2) at a full load pressure rating of 110 PSIG.This compressor shall be capable of full load operation at 110 PSIG and have a maximumpressure capability of 125 PSIG.

2. Airend.

2.1 The airend shall have a 4-6 lobe combination with both male and female rotors beingidentical in diameter.

2.2 The discharge end of the rotors shall be supported by a triplex bearing arrangementon the male rotor and a duplex bearing arrangement on the female rotor. The suction endof the rotors shall be supported by a single row of cylindrical roller bearings.

2.3 The airend shall have an axial flow inlet housing to allow incoming air to enter thecompression area over the entire face of the rotors. Radial inlet arrangements will not beaccepted. This inlet housing shall bolt directly to a "C"-faced drive motor to maintainpermanent rotor shaft to motor shaft alignment.

2.4 The discharge bearings must be housed in the main rotor housing to maintainpermanent rotor alignment within the rotor housing. Separate, bolt-on castings fordischarge bearings will not be accepted.

2.5 The area around the bearings shall be free of any obstruction to the free flow of fluid.Pockets or reservoirs where fluid might collect in the bearing area shall have a magneticdrain plug to trap metallic contamination. This drain plug shall be of sufficient size andconveniently located to allow the regular cleaning of pockets or reservoirs in the bearingarea.

2.6 Male rotor RPM shall be identical to the actual speed of the main drive motor. Thetip speed of the driven rotor shall not exceed 19 meters per second.

2.7 The motor and airend shall be directly coupled through a flexible drop-out typecoupling. No belts or gears shall be included in the drive arrangement.

2.8 The drive rotor shall have a redundant shaft sealing arrangement. Should the primaryshaft seal fail, a secondary seal shall be capable of preventing fluid from leaking out of the

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 22

Back to TOC

Page 13: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

airend. A method of detecting a primary shaft seal failure while the machine is inoperation shall be provided.

3. Drive motor.

3.1 The main drive motor shall be 75 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

3.2 The main drive motor shall have an ODP enclosure.

3.3 The main drive motor shall be of a "C"-faced design so that it can be rigidly bolted tothe airend assembly.

4. Cooling system.

4.1 The compressor shall be air-cooled.

4.2 The cooling system shall be capable of maintaining proper compressor temperaturesin ambient conditions up to 110oF.

4.3 Coolers shall be vertical draft.

4.4 Fluid circulation shall be by positive displacement pump.

5. Aftercooler.

5.1 An air-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to have an approach temperature of not more than5oF at standard conditions.

5.2 A 99.9% efficient moisture separator and trap shall be included.

6. Compressor Fluid.

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use.

6.2 The fluid shall contain no chemical substances that would require it to be treated ashazardous according to the appropriate laws in effect at the time of sale. Used fluid shallbe suitable for recycling along with other waste petroleum oil.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 23

Back to TOC

Page 14: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

6.3 Fluid carryover into the downstream air system shall not exceed 3 PPM by weightwith new elements.

6.4 A fluid filter shall be provided with a 10 micron absolute rating. The filter media mustbe microfiberglass. Paper media will not be accepted.

7. Compressor controls.

7.1 The compressor controls shall allow for full range modulation to match compressorcapacity to system demand. If system demand should fall below a user adjustable percentof compressor capacity, the compressor shall go into an unloaded condition. Anadjustable timer shall be provided to shutdown the compressor if it runs in the unloadedmode for a predetermined length of time. The compressor shall automaticallyreload/restart if the system pressure falls below the set point. A selector switch on thecontrol panel shall be provided to allow the user to bypass the automatic shutdown featureand elect a continuous run mode should the system demand dictate.

7.2 Gauges or indicators shall also be provided to indicate:A) Compressor discharge temperatureB) Discharge air pressure C) Percent capacity D) Operating modeE) Power onF) Running hours

7.3 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown (Probes must be provided at the compressordischarge and the air/fluid separator reservoir to monitor high temperatureconditions)B) Motor overload (This should alert a motor overload for all motors on thecompressor package)C) Change inlet filterD) Change fluid filterE) Change Separator Element

This shutdown and maintenance annunciator panel shall be constructed in such a way thatconnections for remote annunciation can easily be made.

8. Electrical controls.

8.1 All electrical controls shall be designed and constructed in accordance with NationalElectrical Code (NEC) guidelines.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 24

Back to TOC

Page 15: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.2 The main starter control box shall be NEMA 1 design and contain starters for themain drive motor and fan motor along with other electrical controls.

8.3 All components within the main starter control box shall be UL and/or CSA approvedor listed.

8.4 The main starter control box shall be UL and/or CSA approved or listed.

8.5 Remote mounted starter control panel boxes will not be accepted.

9. Safety system.

9.1 Pressure vessels shall be ASME coded.

9.2 A pressure relief safety valve shall be provided. This valve shall be sized to handle thefull capacity of the compressor. It shall have a single, directed outlet. Multidirectionalvalves will not be accepted.

9.3 A high air/fluid temperature shutdown system shall be provided. This system shalloperate with a minimum of two temperature sensors. One sensor must be located directlyin the discharge air stream of the airend. One sensor must be located on the dry side ofthe air/fluid separator element. This system must be designed to prevent the compressorfrom running with a failed sensor.

10. Sound levels.

10.1 Sound levels shall not exceed 85 dB(A) when measured in free field conditions, 1meter away from the compressor.

OPTIONSReplace section in main bid spec with appropriate section below for desired option.

**** AUTO DEMAND CONTROL

7.1 In the "LOCAL" control mode, the compressor controls shall allow for full rangemodulation to match compressor capacity to system demand. If system demand shouldfall below a predetermined percentage of compressor capacity, the compressor shall gointo an unloaded condition. An adjustable timer shall be provided to shutdown thecompressor if it runs in the unloaded mode for a predetermined length of time. Thecompressor shall automatically restart if the system pressure falls below the set point. In

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 25

Back to TOC

Page 16: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

the "REMOTE" control mode, control of the compressor shall be transferred to a remotecontroller that shall operate the compressor in conjunction with one or more othercompressors. The actual operation of the compressor will be identical to the "LOCAL"mode except the remote controller will determine pressure set points.

**** 200 VOLT

3.1 The main drive motor shall be 75 nameplate horsepower rated for 200 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 230 VOLT

3.1 The main drive motor shall be 75 nameplate horsepower rated for 230 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 575 VOLT

3.1 The main drive motor shall be 75 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** NEMA 4

8.2 The main control box shall be NEMA 4 design and contain starters for the main drivemotor and fan motor along with other electrical controls.

**** NEMA 12 (use NEMA 4)

8.2 The main control box shall be NEMA 4 design and contain starters for the main drivemotor and fan motor along with other electrical controls.

**** FOOD GRADE FLUID

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use. It shall meet FDA CFR 178.3570 spec for food grade lubricants.

**** FULL CANOPY

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 26

Back to TOC

Page 17: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

1.2 The compressor shall have a full metal enclosure with quick release panels for easyaccess to service and maintenance items.

(WITHOUT SHROUDS)

10.1 Sound levels shall not exceed 83 dB(A) when measured in free field conditions, 1meter away from the compressor.

(WITH LOW SOUND SHROUDS)

10.1 Sound levels shall not exceed 77 dB(A) when measured in free field conditions, 1meter away from the compressor.

(WATER-COOLED)

10.1 Sound levels shall not exceed 79 dB(A) when measured in free field conditions, 1meter away from the compressor.

**** WATER-COOLED

4.1 The compressor shall be water-cooled.

4.3 Coolers shall be shell and tube type water-cooled coolers. The coolers shall be sizedto maintain normal operating temperatures with inlet water temperatures as high as 100oF.Water pressure drop through the cooling system shall be no more than 3 PSIG.

5.1 A water-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to cool the discharge air temperature to within15oF of the inlet water temperature.

10.1 Sound levels shall not exceed 85 dB(A) when measured in free field conditions, 1meter away from the compressor.

**** SOLID STATE REDUCED VOLTAGE STARTERS

8.2 The main starter control box shall be NEMA 1 and shall contain provisions to connecta remotely mounted solid state reduced voltage starter for the main drive motor. Motorprotection shall include:

a) Shorted SCR detectionb) Phase lossc) Overloadd) Current flow sensinge) Short circuit protection

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 27

Back to TOC

Page 18: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

f) Anti-oscillation circuitTorque, ramp time and current limit shall be adjustable. An LED display shall indicate thefollowing:

a) Power Onb) Startc) Current Flowd) Run e) At Speed f) Over Temperatureg) Overloadh) Phase Lossi) Shorted SCRj) Short Circuitk) Shunt Trip

Output relays shall be provided to indicate the following:a) Run b) Shunt Trip c) Programmable Status Relay - Will energize on any one of the followingconditions (jumper selectable): At Speed, Phase Loss, Over Temperature,Overload, Shorted SCR and Over Current

8.5 Remote mounted control panel boxes will be accepted.

**** 125 PSIG FULL LOAD OPERATION

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 368 CFM (measured in accordance with CAGI-PNEUROP Test CodePN2CPTC2) at a full load pressure rating of 125 PSIG. This compressor shall be capableof full load operation at 125 PSIG and have a maximum pressure capability of 140 PSIG.

3.1 The main drive motor shall be 100 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 200 VOLT

3.1 The main drive motor shall be 100 nameplate horsepower rated for 200 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 230 VOLT

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 28

Back to TOC

Page 19: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

3.1 The main drive motor shall be 100 nameplate horsepower rated for 230 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 575 VOLT

3.1 The main drive motor shall be 100 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** Power$ync®

2.9 The airend shall have a method of controlling displacement at operating speed thatdoes not introduce areas of unswept volume or clearance pockets into the rotor bores.Lift valves that extend into the rotor bore prior to final machining and are machined to theexact tolerance of the rotor bore as the rotor bore is being machined are the preferredmethod of capacity control. Lift valves must be double acting to use air pressure to bothopen and close.

7.1 The compressor controls shall be microprocessor-based. There shall be threeuser-selectable control methods.

A) Constant Run Mode -- This method shall allow the operator to set anoperating pressure range within which the compressor will adjust its capacity tosatisfy the system demand or unload during periods of no demand. B) Auto Dual Mode -- This method shall allow the operator to set an operatingpressure range within which the compressor will adjust its capacity to satisfy thesystem demand or unload during periods of no demand. After a user-definedperiod of unloaded operation, the compressor will automatically shutdown andassume a standby mode. Should system demand return, the compressor willautomatically restart. C) Network Mode -- In place of the pressure deadband, the Network Mode shalluse a target pressure and a variable response rate. The control shall maintain thesystem pressure to within two or three pounds of the target pressure. In the upper50% of the capacity range, the control shall match system demand withoutrestricting the inlet air flow. In the lower 50% of the capacity range, the controlshall select either a load/no load or modulating control method, based onuser-defined parameters.

7.2 A complete, redundant electro-mechanical control system shall be included that willsafely operate the compressor in the event of a microprocessor failure. This system shallbe user selectable from a switch mounted in the main electrical control enclosure.

7.3 LED displays shall be provided that will constantly indicate discharge temperature andsystem pressure.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 29

Back to TOC

Page 20: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

7.4 A four-line by forty-character LCD display shall be provided that will allow access tothe following information:

Power-Up Warning Displays:A) Sump Pressure Sensor FailureB) Line Pressure Sensor FailureC) Discharge Temperature Sensor FailureD) Sump Temperature Sensor FailureE) Tripped Motor OverloadF) Relay Board Communication FailureG) Diagnostic FailureH) Setup Memory FailureI) Control Relay Not DisengagedJ) Main Motor Contactor Not DisengagedK) Wye Contactor Not Disengaged (on Wye-Delta starters)L) Deadband Data ErrorM) Setup Memory ErrorN) Setup Data Not InitializedO) Air Filter Vacuum Switch FaultyP) Fluid Filter Delta-P Switch FaultyQ) An Element Needs ServicingR) Minor Diagnostic FailureS) Machine ID Error

Operational Displays: A) Sump Pressure Too High For RestartB) Compressor Is Starting

C) **Warning** Possible Reverse RotationD) Compressor Is Running In Auto-Dual ModeE) Compressor Is UnloadedF) Time Left To ShutdownG) Compressor Has Timed Out And Shut Down **Warning** Will

Automatically RestartH) Running In Continuous Run ModeI) Running In Network Mode Position __ Of __J) Programmed ShutdownK) **Warning** An Element Needs ServicingL) Emergency Stop Button Has Been PressedM) ** Warning** Setup Memory FailureN) ** Warning** Sequence Data ErrorO) ** Warning** Schedule Data ErrorP) ** Warning** Compressor ID Already In UseQ) ** Warning** High Discharge TemperatureR) ** Warning** High Sump TemperatureS) ** Warning** High Sump PressureT) ** Warning** Motor Overload

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 30

Back to TOC

Page 21: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

U) ** Warning** Contactor Is Not EngagingV) ** Warning** Contactor is Not DisengagingW) Discharge RTD Faulty Or DisconnectedX) Sump RTD Faulty Or DisconnectedY) Line Pressure Sensor FaultyZ) Sump Pressure Sensor FaultyAA) ** Warning** Communication FailureBB) ** Warning** Firmware FailureCC) Compressor Not In Scheduled Sequence

Adjustable Operating Parameters: A) Compressor Unloaded PressureB) Compressor Loaded PressureC) Timed Stop Delay In MinutesD) Cycle CountE) Short Cycle Time In SecondsF) Target PressureG) Network Unloaded PressureH) Network Loaded PressureI) Modulation Turn Off Delay In MinutesJ) Machine IDK) Sequence Number To Change L) Day To ChangeM) Clear SequenceN) Clear Sequence And ScheduleO) Set Delayed Unload ModeP) Set Immediate Unload Mode

Maintenance Displays:A) Loaded HoursB) Unloaded HoursC) Hours Since Last Fluid ChangeD) Control Line Filter HoursE) Intake Filter HoursF) Fluid Filter HoursG) Separator Element HoursH) View Current Time And DateI) Set Time And Date J) Compressor Control TestK) Serial NumberL) Software Version NumberM) Compressor ModelN) Drive Motor HorsepowerO) VoltageP) Starter Type

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 31

Back to TOC

Page 22: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

Q) Cooling TypeR) Airend Type S) High Air Temperature Shutdown SettingT) High Sump Pressure Shutdown SettingU) Maximum Unloaded Pressure Setting V) Minimum Loaded Pressure SettingW) Current Loaded Pressure SettingX) Current Unloaded Pressure SettingY) Current Target Pressure SettingZ) Machine IDAA) Auto Dual Shutdown Timer SettingBB) Wye Delta Transition Time SettingCC) Modulation Cycle Count SettingDD) Modulation Time SettingEE) Sump Temperature FF) Pressure Transducer Calibration DateGG) Temperature Sensor Calibration DateHH) Unit Configuration DateII) Current Time And DateJJ) Modem Baud RateKK) Shutdown LogLL) Network Diagnostics

7.5 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown B) Motor overload C) High Sump Pressure ShutdownD) Change inlet filterE) Change lubricant filterF) Change Separator Element

7.6 The control shall have the built-in capability to network up to 16 similar compressorsof various sizes. In this network configuration, the sequence in which the compressorsoperate as base load and trim shall be user selectable. The control shall be able to store nofewer than nine different sequences. An internal clock and calendar shall be included thatwill allow different sequences to be scheduled no fewer than nine times per day. Thecontroller shall have the ability to schedule each day of the week differently.

7.7 The controller shall include a shutdown log that will allow the operator to viewservice and shutdown alarms in the reverse order of occurrence. The log shall give plainEnglish messages that will identify the source of the alarm.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 32

Back to TOC

Page 23: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

SAMPLE BID REQUEST SPECIFICATION FOR A QSI 500

1. Scope of supply.

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 500 CFM (total package rated performance measured in accordance withCAGI-PNEUROP Test Code PN2CPTC2) at a full load pressure rating of 110 PSIG.This compressor shall be capable of full load operation at 110 PSIG and have a maximumpressure capability of 125 PSIG.

2. Airend.

2.1 The airend shall have a 4-6 lobe combination with both male and female rotors beingidentical in diameter.

2.2 The discharge end of the rotors shall be supported by a triplex bearing arrangementon the male rotor and a duplex bearing arrangement on the female rotor. The suction endof the rotors shall be supported by a single row of cylindrical roller bearings.

2.3 The airend shall have an axial flow inlet housing to allow incoming air to enter thecompression area over the entire face of the rotors. Radial inlet arrangements will not beaccepted. This inlet housing shall bolt directly to a "C"-faced drive motor to maintainpermanent rotor shaft to motor shaft alignment.

2.4 The discharge bearings must be housed in the main rotor housing to maintainpermanent rotor alignment within the rotor housing. Separate, bolt-on castings fordischarge bearings will not be accepted.

2.5 The area around the bearings shall be free of any obstruction to the free flow of fluid.Pockets or reservoirs where fluid might collect in the bearing area shall have a magneticdrain plug to trap metallic contamination. This drain plug shall be of sufficient size andconveniently located to allow the regular cleaning of pockets or reservoirs in the bearingarea.

2.6 Male rotor RPM shall be identical to the actual speed of the main drive motor. Thetip speed of the driven rotor shall not exceed 24 meters per second.

2.7 The motor and airend shall be directly coupled through a flexible drop-out typecoupling. No belts or gears shall be included in the drive arrangement.

2.8 The drive rotor shall have a redundant shaft sealing arrangement. Should the primaryshaft seal fail, a secondary seal shall be capable of preventing fluid from leaking out of the

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 33

Back to TOC

Page 24: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

airend. A method of detecting a primary shaft seal failure while the machine is inoperation shall be provided.

3. Drive motor.

3.1 The main drive motor shall be 100 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

3.2 The main drive motor shall have an ODP enclosure.

3.3 The main drive motor shall be of a "C"-faced design so that it can be rigidly bolted tothe airend assembly.

4. Cooling system.

4.1 The compressor shall be air-cooled.

4.2 The cooling system shall be capable of maintaining proper compressor temperaturesin ambient conditions up to 110oF.

4.3 Coolers shall be vertical draft.

4.4 Fluid circulation shall be by positive displacement pump.

5. Aftercooler.

5.1 An air-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to have an approach temperature of not more than5oF at standard conditions.

5.2 A 99.9% efficient moisture separator and trap shall be included.

6. Compressor Fluid.

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use.

6.2 The fluid shall contain no chemical substances that would require it to be treated ashazardous according to the appropriate laws in effect at the time of sale. Used fluid shallbe suitable for recycling along with other waste petroleum oil.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 34

Back to TOC

Page 25: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

6.3 Fluid carryover into the downstream air system shall not exceed 3 PPM by weightwith new elements.

6.4 A fluid filter shall be provided with a 10 micron absolute rating. The filter media mustbe microfiberglass. Paper media will not be accepted.

7. Compressor controls.

7.1 The compressor controls shall allow for full range modulation to match compressorcapacity to system demand. If system demand should fall below a user adjustable percentof compressor capacity, the compressor shall go into an unloaded condition. Anadjustable timer shall be provided to shutdown the compressor if it runs in the unloadedmode for a predetermined length of time. The compressor shall automaticallyreload/restart if the system pressure falls below the set point. A selector switch on thecontrol panel shall be provided to allow the user to bypass the automatic shutdown featureand elect a continuous run mode should the system demand dictate.

7.2 Gauges or indicators shall also be provided to indicate:A) Compressor discharge temperatureB) Discharge air pressure C) Percent capacity D) Operating modeE) Power onF) Running hours

7.3 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown (Probes must be provided at the compressordischarge and the air/fluid separator reservoir to monitor high temperatureconditions)B) Motor overload (This should alert a motor overload for all motors on thecompressor package)C) Change inlet filterD) Change fluid filterE) Change Separator Element

This shutdown and maintenance annunciator panel shall be constructed in such a way thatconnections for remote annunciation can easily be made.

8. Electrical controls.

8.1 All electrical controls shall be designed and constructed in accordance with NationalElectrical Code (NEC) guidelines.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 35

Back to TOC

Page 26: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.2 The main starter control box shall be NEMA 1 design and contain starters for themain drive motor and fan motor along with other electrical controls.

8.3 All components within the main starter control box shall be UL and/or CSA approvedor listed.

8.4 The main starter control box shall be UL and/or CSA approved or listed.

8.5 Remote mounted starter control panel boxes will not be accepted.

9. Safety system.

9.1 Pressure vessels shall be ASME coded.

9.2 A pressure relief safety valve shall be provided. This valve shall be sized to handle thefull capacity of the compressor. It shall have a single, directed outlet. Multidirectionalvalves will not be accepted.

9.3 A high air/fluid temperature shutdown system shall be provided. This system shalloperate with a minimum of two temperature sensors. One sensor must be located directlyin the discharge air stream of the airend. One sensor must be located on the dry side ofthe air/fluid separator element. This system must be designed to prevent the compressorfrom running with a failed sensor.

10. Sound levels.

10.1 Sound levels shall not exceed 87 dB(A) when measured in free field conditions, 1meter away from the compressor.

OPTIONSReplace section in main bid spec with appropriate section below for desired option.

**** AUTO DEMAND CONTROL

7.1 In the "LOCAL" control mode, the compressor controls shall allow for full rangemodulation to match compressor capacity to system demand. If system demand shouldfall below a predetermined percentage of compressor capacity, the compressor shall gointo an unloaded condition. An adjustable timer shall be provided to shutdown thecompressor if it runs in the unloaded mode for a predetermined length of time. Thecompressor shall automatically restart if the system pressure falls below the set point. In

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 36

Back to TOC

Page 27: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

the "REMOTE" control mode, control of the compressor shall be transferred to a remotecontroller that shall operate the compressor in conjunction with one or more othercompressors. The actual operation of the compressor will be identical to the "LOCAL"mode except the remote controller will determine pressure set points.

**** 200 VOLT

3.1 The main drive motor shall be 100 nameplate horsepower rated for 200 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

8.2 The main electrical control box shall be NEMA 1 design and contain starters for thefan motor (air-cooled main cooling fan or water-cooled canopy vent fan) along with otherelectrical controls.

**** 230 VOLT

3.1 The main drive motor shall be 100 nameplate horsepower rated for 230 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 575 VOLT

3.1 The main drive motor shall be 100 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** NEMA 4

8.2 The main control box shall be NEMA 4 design and contain starters for the main drivemotor and fan motor along with other electrical controls.

**** NEMA 12 (use NEMA 4)

8.2 The main control box shall be NEMA 4 design and contain starters for the main drivemotor and fan motor along with other electrical controls.

**** FOOD GRADE FLUID

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use. It shall meet FDA CFR 178.3570 spec for food grade lubricants.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 37

Back to TOC

Page 28: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

**** FULL CANOPY

1.2 The compressor shall have a full metal enclosure with quick release panels for easyaccess to service and maintenance items.

(WITHOUT SHROUDS)

10.1 Sound levels shall not exceed 83 dB(A) when measured in free field conditions, 1meter away from the compressor.

(WITH LOW SOUND SHROUDS)

10.1 Sound levels shall not exceed 80 dB(A) when measured in free field conditions, 1meter away from the compressor.

(WATER-COOLED)

10.1 Sound levels shall not exceed 80 dB(A) when measured in free field conditions, 1meter away from the compressor.

**** WATER-COOLED

4.1 The compressor shall be water-cooled.

4.3 Coolers shall be shell and tube type water-cooled coolers. The coolers shall be sizedto maintain normal operating temperatures with inlet water temperatures as high as 100oF.Water pressure drop through the cooling system shall be no more than 6 PSIG.

5.1 A water-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to cool the discharge air temperature to within15oF of the inlet water temperature.

10.1 Sound levels shall not exceed 86 dB(A) when measured in free field conditions, 1meter away from the compressor.

**** SOLID STATE REDUCED VOLTAGE STARTERS

8.2 The main starter control box shall be NEMA 1 and shall contain provisions to connecta remotely mounted solid state reduced voltage starter for the main drive motor. Motorprotection shall include:

a) Shorted SCR detectionb) Phase lossc) Overload

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 38

Back to TOC

Page 29: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

d) Current flow sensinge) Short circuit protection f) Anti-oscillation circuit

Torque, ramp time and current limit shall be adjustable. An LED display shall indicate thefollowing:

a) Power Onb) Startc) Current Flowd) Run e) At Speed f) Over Temperatureg) Overloadh) Phase Lossi) Shorted SCRj) Short Circuitk) Shunt Trip

Output relays shall be provided to indicate the following:a) Run b) Shunt Trip c) Programmable Status Relay - Will energize on any one of the followingconditions (jumper selectable): At Speed, Phase Loss, Over Temperature,Overload, Shorted SCR and Over Current

8.5 Remote mounted control panel boxes will be accepted.

**** 125 PSIG FULL LOAD OPERATION

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 496 CFM (measured in accordance with CAGI-PNEUROP Test CodePN2CPTC2) at a full load pressure rating of 125 PSIG. This compressor shall be capableof full load operation at 125 PSIG and have a maximum pressure capability of 140 PSIG.

3.1 The main drive motor shall be 125 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 200 VOLT

3.1 The main drive motor shall be 125 nameplate horsepower rated for 200 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

8.2 The main electrical control box shall be NEMA 1 design and contain starters for thefan motor (air-cooled main cooling fan or water-cooled canopy vent fan) along with otherelectrical controls.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 39

Back to TOC

Page 30: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

**** 230 VOLT

3.1 The main drive motor shall be 125 nameplate horsepower rated for 230 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

8.2 The main electrical control box shall be NEMA 1 design and contain starters for thefan motor (air-cooled main cooling fan or water-cooled canopy vent fan) along with otherelectrical controls.

**** 575 VOLT

3.1 The main drive motor shall be 125 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** Power$ync®

2.9 The airend shall have a method of controlling displacement at operating speed thatdoes not introduce areas of unswept volume or clearance pockets into the rotor bores.Lift valves that extend into the rotor bore prior to final machining and are machined to theexact tolerance of the rotor bore as the rotor bore is being machined are the preferredmethod of capacity control. Lift valves must be double acting to use air pressure to bothopen and close.

7.1 The compressor controls shall be microprocessor-based. There shall be threeuser-selectable control methods.

A) Constant Run Mode -- This method shall allow the operator to set anoperating pressure range within which the compressor will adjust its capacity tosatisfy the system demand or unload during periods of no demand. B) Auto Dual Mode -- This method shall allow the operator to set an operatingpressure range within which the compressor will adjust its capacity to satisfy thesystem demand or unload during periods of no demand. After a user-definedperiod of unloaded operation, the compressor will automatically shutdown andassume a standby mode. Should system demand return, the compressor willautomatically restart. C) Network Mode -- In place of the pressure deadband, the Network Mode shalluse a target pressure and a variable response rate. The control shall maintain thesystem pressure to within two or three pounds of the target pressure. In the upper50% of the capacity range, the control shall match system demand withoutrestricting the inlet air flow. In the lower 50% of the capacity range, the controlshall select either a load/no load or modulating control method, based onuser-defined parameters.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 40

Back to TOC

Page 31: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

7.2 A complete, redundant electro-mechanical control system shall be included that willsafely operate the compressor in the event of a microprocessor failure. This system shallbe user selectable from a switch mounted in the main electrical control enclosure.

7.3 LED displays shall be provided that will constantly indicate discharge temperature andsystem pressure.

7.4 A four-line by forty-character LCD display shall be provided that will allow access tothe following information:

Power-Up Warning Displays:A) Sump Pressure Sensor FailureB) Line Pressure Sensor FailureC) Discharge Temperature Sensor FailureD) Sump Temperature Sensor FailureE) Tripped Motor OverloadF) Relay Board Communication FailureG) Diagnostic FailureH) Setup Memory FailureI) Control Relay Not DisengagedJ) Main Motor Contactor Not DisengagedK) Wye Contactor Not Disengaged (on Wye-Delta starters)L) Deadband Data ErrorM) Setup Memory ErrorN) Setup Data Not InitializedO) Air Filter Vacuum Switch FaultyP) Fluid Filter Delta-P Switch FaultyQ) An Element Needs ServicingR) Minor Diagnostic FailureS) Machine ID Error

Operational Displays: A) Sump Pressure Too High For RestartB) Compressor Is Starting

C) **Warning** Possible Reverse RotationD) Compressor Is Running In Auto-Dual ModeE) Compressor Is UnloadedF) Time Left To ShutdownG) Compressor Has Timed Out And Shut Down **Warning** Will

Automatically RestartH) Running In Continuous Run ModeI) Running In Network Mode Position __ Of __J) Programmed ShutdownK) **Warning** An Element Needs ServicingL) Emergency Stop Button Has Been PressedM) ** Warning** Setup Memory Failure

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 41

Back to TOC

Page 32: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

N) ** Warning** Sequence Data ErrorO) ** Warning** Schedule Data ErrorP) ** Warning** Compressor ID Already In UseQ) ** Warning** High Discharge TemperatureR) ** Warning** High Sump TemperatureS) ** Warning** High Sump PressureT) ** Warning** Motor OverloadU) ** Warning** Contactor Is Not EngagingV) ** Warning** Contactor is Not DisengagingW) Discharge RTD Faulty Or DisconnectedX) Sump RTD Faulty Or DisconnectedY) Line Pressure Sensor FaultyZ) Sump Pressure Sensor FaultyAA) ** Warning** Communication FailureBB) ** Warning** Firmware FailureCC) Compressor Not In Scheduled Sequence

Adjustable Operating Parameters: A) Compressor Unloaded PressureB) Compressor Loaded PressureC) Timed Stop Delay In MinutesD) Cycle CountE) Short Cycle Time In SecondsF) Target PressureG) Network Unloaded PressureH) Network Loaded PressureI) Modulation Turn Off Delay In MinutesJ) Machine IDK) Sequence Number To Change L) Day To ChangeM) Clear SequenceN) Clear Sequence And ScheduleO) Set Delayed Unload ModeP) Set Immediate Unload Mode

Maintenance Displays:A) Loaded HoursB) Unloaded HoursC) Hours Since Last Fluid ChangeD) Control Line Filter HoursE) Intake Filter HoursF) Fluid Filter HoursG) Separator Element HoursH) View Current Time And DateI) Set Time And Date

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 42

Back to TOC

Page 33: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

J) Compressor Control TestK) Serial NumberL) Software Version NumberM) Compressor ModelN) Drive Motor HorsepowerO) VoltageP) Starter TypeQ) Cooling TypeR) Airend Type S) High Air Temperature Shutdown SettingT) High Sump Pressure Shutdown SettingU) Maximum Unloaded Pressure Setting V) Minimum Loaded Pressure SettingW) Current Loaded Pressure SettingX) Current Unloaded Pressure SettingY) Current Target Pressure SettingZ) Machine IDAA) Auto Dual Shutdown Timer SettingBB) Wye Delta Transition Time SettingCC) Modulation Cycle Count SettingDD) Modulation Time SettingEE) Sump Temperature FF) Pressure Transducer Calibration DateGG) Temperature Sensor Calibration DateHH) Unit Configuration DateII) Current Time And DateJJ) Modem Baud RateKK) Shutdown LogLL) Network Diagnostics

7.5 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown B) Motor overload C) High Sump Pressure ShutdownD) Change inlet filterE) Change lubricant filterF) Change Separator Element

7.6 The control shall have the built-in capability to network up to 16 similar compressorsof various sizes. In this network configuration, the sequence in which the compressorsoperate as base load and trim shall be user selectable. The control shall be able to store nofewer than nine different sequences. An internal clock and calendar shall be included thatwill allow different sequences to be scheduled no fewer than nine times per day. Thecontroller shall have the ability to schedule each day of the week differently.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 43

Back to TOC

Page 34: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

7.7 The controller shall include a shutdown log that will allow the operator to viewservice and shutdown alarms in the reverse order of occurrence. The log shall give plainEnglish messages that will identify the source of the alarm.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 44

Back to TOC

Page 35: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

SAMPLE BID REQUEST SPECIFICATION FOR A QSI-750

1. Scope of supply.

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 757 CFM (total package rated performance measured in accordance withCAGI-PNEUROP Test Code PN2CPTC2) at a full load pressure rating of 110 PSIG.This compressor shall be capable of full load operation at 110 PSIG and have a maximumpressure capability of 125 PSIG.

2. Airend.

2.1 The airend shall have a 4-6 lobe combination with both male and female rotors beingidentical in diameter.

2.2 The discharge end of the rotors shall be supported by a triplex bearing arrangementon the male rotor and a duplex bearing arrangement on the female rotor. The suction endof the rotors shall be supported by a single row of cylindrical roller bearings.

2.3 The airend shall have an axial flow inlet housing to allow incoming air to enter thecompression area over the entire face of the rotors. Radial inlet arrangements will not beaccepted. This inlet housing shall bolt directly to a "C"-faced drive motor to maintainpermanent rotor shaft to motor shaft alignment.

2.4 The discharge bearings must be housed in the main rotor housing to maintainpermanent rotor alignment within the rotor housing. Separate, bolt-on castings fordischarge bearings will not be accepted.

2.5 The area around the bearings shall be free of any obstruction to the free flow of fluid.Pockets or reservoirs where fluid might collect in the bearing area shall have a magneticdrain plug to trap metallic contamination. This drain plug shall be of sufficient size andconveniently located to allow the regular cleaning of pockets or reservoirs in the bearingarea.

2.6 Male rotor RPM shall be identical to the actual speed of the main drive motor. Thetip speed of the driven rotor shall not exceed 24 meters per second.

2.7 The motor and airend shall be directly coupled through a flexible drop-out typecoupling. No belts or gears shall be included in the drive arrangement.

2.8 The drive rotor shall have a redundant shaft sealing arrangement. Should the primaryshaft seal fail, a secondary seal shall be capable of preventing fluid from leaking out of theairend. A method of detecting a primary shaft seal failure while the machine is inoperation shall be provided.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 45

Back to TOC

Page 36: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

3. Drive motor.

3.1 The main drive motor shall be 150 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

3.2 The main drive motor shall have an ODP enclosure.

3.3 The main drive motor shall be of a "C"-faced design so that it can be rigidly bolted tothe airend assembly.

4. Cooling system.

4.1 The compressor shall be air-cooled.

4.2 The cooling system shall be capable of maintaining proper compressor temperaturesin ambient conditions up to 110oF.

4.3 Coolers shall be horizontal draft.

4.4 Fluid circulation shall be by positive displacement pump.

5. Aftercooler.

5.1 An air-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to have an approach temperature of not more than5oF at standard conditions.

5.2 A 99.9% efficient moisture separator and trap shall be included.

6. Compressor Fluid.

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use.

6.2 The fluid shall contain no chemical substances that would require it to be treated ashazardous according to the appropriate laws in effect at the time of sale. Used fluid shallbe suitable for recycling along with other waste petroleum oil.

6.3 Fluid carryover into the downstream air system shall not exceed 3 PPM by weightwith new elements.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 46

Back to TOC

Page 37: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

6.4 A fluid filter shall be provided with a 10 micron absolute rating. The media must bemicrofiberglass. Paper media filters will not be accepted.

7. Compressor controls.

7.1 The compressor controls shall allow for full range modulation to match compressorcapacity to system demand. If system demand should fall below a user adjustable percentof compressor capacity, the compressor shall go into an unloaded condition. Anadjustable timer shall be provided to shutdown the compressor if it runs in the unloadedmode for a predetermined length of time. The compressor shall automaticallyreload/restart if the system pressure falls below the set point. A selector switch on thecontrol panel shall be provided to allow the user to bypass the automatic shutdown featureand elect a continuous run mode should the system demand dictate.

7.2 Gauges or indicators shall also be provided to indicate:A) Compressor discharge temperatureB) Discharge air pressure C) Percent capacity D) Operating modeE) Power onF) Running hours

7.3 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown (Probes must be provided at the compressordischarge and the air/fluid separator reservoir to monitor high temperatureconditions)B) Motor overload (This should alert a motor overload for all motors on thecompressor package)C) Change inlet filterD) Change fluid filterE) Change Separator Element

This shutdown and maintenance annunciator panel shall be constructed in such a way thatconnections for remote annunciation can easily be made.

8. Electrical controls.

8.1 All electrical controls shall be designed and constructed in accordance with NationalElectrical Code (NEC) guidelines.

8.2 The main starter control box shall be NEMA 1 design and contain starters for themain drive motor and fan motor along with other electrical controls.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 47

Back to TOC

Page 38: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.3 All components within the main starter control box shall be UL and/or CSA approvedor listed.

8.4 The main starter control box shall be UL and/or CSA approved or listed.

8.5 Remote mounted starter control panel boxes will not be accepted.

9. Safety system.

9.1 Pressure vessels shall be ASME coded.

9.2 A pressure relief safety valve shall be provided. This valve shall be sized to handle thefull capacity of the compressor. It shall have a single, directed outlet. Multidirectionalvalves will not be accepted.

9.3 A high air/fluid temperature shutdown system shall be provided. This system shalloperate with a minimum of two temperature sensors. One sensor must be located directlyin the discharge air stream of the airend. One sensor must be located on the dry side ofthe air/fluid separator element. This system must be designed to prevent the compressorfrom running with a failed sensor.

10. Sound levels.

10.1 Sound levels shall not exceed 89 dB(A) when measured in free field conditions, 1meter away from the compressor.

OPTIONSReplace section in main bid spec with appropriate section below for desired option.

**** AUTO DEMAND CONTROL

7.1 In the "LOCAL" control mode, the compressor controls shall allow for full rangemodulation to match compressor capacity to system demand. If system demand shouldfall below a predetermined percentage of compressor capacity, the compressor shall gointo an unloaded condition. An adjustable timer shall be provided to shutdown thecompressor if it runs in the unloaded mode for a predetermined length of time. Thecompressor shall automatically restart if the system pressure falls below the set point. Inthe "REMOTE" control mode, control of the compressor shall be transferred to a remotecontroller that shall operate the compressor in conjunction with one or more other

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 48

Back to TOC

Page 39: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

compressors. The actual operation of the compressor will be identical to the "LOCAL"mode except the remote controller will determine pressure set points.

**** 200 VOLT

3.1 The main drive motor shall be 150 nameplate horsepower rated for 200 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

8.2 The main electrical control box shall be NEMA 1 design and contain starters for thefan motor (air-cooled main cooling fan or water-cooled canopy vent fan) along with otherelectrical controls.

**** 230 VOLT

3.1 The main drive motor shall be 150 nameplate horsepower rated for 230 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

8.2 The main electrical control box shall be NEMA 1 design and contain starters for thefan motor (air-cooled main cooling fan or water-cooled canopy vent fan) along with otherelectrical controls.

**** 575 VOLT

3.1 The main drive motor shall be 150 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** NEMA 4

8.2 The main control box shall be NEMA 4 design and contain starters for the main drivemotor and fan motor along with other electrical controls.

**** NEMA 12 (use NEMA 4)

8.2 The main control box shall be NEMA 4 design and contain starters for the main drivemotor and fan motor along with other electrical controls.

**** FOOD GRADE FLUID

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 49

Back to TOC

Page 40: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use. It shall meet FDA CFR 178.3570 spec for food grade lubricants.

**** FULL CANOPY

1.2 The compressor shall have a full metal enclosure with quick release panels for easyaccess to service and maintenance items.

(WITHOUT SHROUDS)

10.1 Sound levels shall not exceed 87 dB(A) when measured in free field conditions, 1meter away from the compressor.

(WITH LOW SOUND SHROUDS)

10.1 Sound levels shall not exceed 80 dB(A) when measured in free field conditions, 1meter away from the compressor.

(WATER-COOLED)

10.1 Sound levels shall not exceed 80 dB(A) when measured in free field conditions, 1meter away from the compressor.

**** WATER-COOLED

4.1 The compressor shall be water-cooled.

4.3 Coolers shall be shell and tube type water-cooled coolers. The coolers shall be sizedto maintain normal operating temperatures with inlet water temperatures as high as 100oF.Water pressure drop through the cooling system shall be no more than 8 PSIG.

5.1 A water-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to cool the discharge air temperature to within15oF of the inlet water temperature.

10.1 Sound levels shall not exceed 87 dB(A) when measured in free field conditions, 1meter away from the compressor.

**** SOLID STATE REDUCED VOLTAGE STARTERS

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 50

Back to TOC

Page 41: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.2 The main starter control box shall be NEMA 1 and shall contain provisions to connecta remotely mounted solid state reduced voltage starter for the main drive motor. Motorprotection shall include:

a) Shorted SCR detectionb) Phase lossc) Overloadd) Current flow sensinge) Short circuit protection f) Anti-oscillation circuit

Torque, ramp time and current limit shall be adjustable. An LED display shall indicate thefollowing:

a) Power Onb) Startc) Current Flowd) Run e) At Speed f) Over Temperatureg) Overloadh) Phase Lossi) Shorted SCRj) Short Circuitk) Shunt Trip

Output relays shall be provided to indicate the following:a) Run b) Shunt Trip c) Programmable Status Relay - Will energize on any one of the followingconditions (jumper selectable): At Speed, Phase Loss, Over Temperature,Overload, Shorted SCR and Over Current

8.5 Remote mounted control panel boxes will be accepted.

**** 125 PSIG FULL LOAD OPERATION

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 751 CFM (measured in accordance with CAGI-PNEUROP Test CodePN2CPTC2) at a full load pressure rating of 125 PSIG. This compressor shall be capableof full load operation at 125 PSIG and have a maximum pressure capability of 140 PSIG.

3.1 The main drive motor shall be 200 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

8.2 The main electrical control box shall be NEMA 1 design and contain starters for thefan motor (air-cooled main cooling fan or water-cooled canopy vent fan) along with otherelectrical controls.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 51

Back to TOC

Page 42: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

**** 575 VOLT

3.1 The main drive motor shall be 200 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** Power$ync®

2.9 The airend shall have a method of controlling displacement at operating speed thatdoes not introduce areas of unswept volume or clearance pockets into the rotor bores.Lift valves that extend into the rotor bore prior to final machining and are machined to theexact tolerance of the rotor bore as the rotor bore is being machined are the preferredmethod of capacity control. Lift valves must be double acting to use air pressure to bothopen and close.

7.1 The compressor controls shall be microprocessor-based. There shall be threeuser-selectable control methods.

A) Constant Run Mode -- This method shall allow the operator to set anoperating pressure range within which the compressor will adjust its capacity tosatisfy the system demand or unload during periods of no demand. B) Auto Dual Mode -- This method shall allow the operator to set an operatingpressure range within which the compressor will adjust its capacity to satisfy thesystem demand or unload during periods of no demand. After a user-definedperiod of unloaded operation, the compressor will automatically shutdown andassume a standby mode. Should system demand return, the compressor willautomatically restart. C) Network Mode -- In place of the pressure deadband, the Network Mode shalluse a target pressure and a variable response rate. The control shall maintain thesystem pressure to within two or three pounds of the target pressure. In the upper50% of the capacity range, the control shall match system demand withoutrestricting the inlet air flow. In the lower 50% of the capacity range, the controlshall select either a load/no load or modulating control method, based onuser-defined parameters.

7.2 A complete, redundant electro-mechanical control system shall be included that willsafely operate the compressor in the event of a microprocessor failure. This system shallbe user selectable from a switch mounted in the main electrical control enclosure.

7.3 LED displays shall be provided that will constantly indicate discharge temperature andsystem pressure.

7.4 A four-line by forty-character LCD display shall be provided that will allow access tothe following information:

Power-Up Warning Displays:A) Sump Pressure Sensor Failure

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 52

Back to TOC

Page 43: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

B) Line Pressure Sensor FailureC) Discharge Temperature Sensor FailureD) Sump Temperature Sensor FailureE) Tripped Motor OverloadF) Relay Board Communication FailureG) Diagnostic FailureH) Setup Memory FailureI) Control Relay Not DisengagedJ) Main Motor Contactor Not DisengagedK) Wye Contactor Not Disengaged (on Wye-Delta starters)L) Deadband Data ErrorM) Setup Memory ErrorN) Setup Data Not InitializedO) Air Filter Vacuum Switch FaultyP) Fluid Filter Delta-P Switch FaultyQ) An Element Needs ServicingR) Minor Diagnostic FailureS) Machine ID Error

Operational Displays: A) Sump Pressure Too High For RestartB) Compressor Is Starting

C) **Warning** Possible Reverse RotationD) Compressor Is Running In Auto-Dual ModeE) Compressor Is UnloadedF) Time Left To ShutdownG) Compressor Has Timed Out And Shut Down **Warning** Will

Automatically RestartH) Running In Continuous Run ModeI) Running In Network Mode Position __ Of __J) Programmed ShutdownK) **Warning** An Element Needs ServicingL) Emergency Stop Button Has Been PressedM) ** Warning** Setup Memory FailureN) ** Warning** Sequence Data ErrorO) ** Warning** Schedule Data ErrorP) ** Warning** Compressor ID Already In UseQ) ** Warning** High Discharge TemperatureR) ** Warning** High Sump TemperatureS) ** Warning** High Sump PressureT) ** Warning** Motor OverloadU) ** Warning** Contactor Is Not EngagingV) ** Warning** Contactor is Not DisengagingW) Discharge RTD Faulty Or DisconnectedX) Sump RTD Faulty Or Disconnected

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 53

Back to TOC

Page 44: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

Y) Line Pressure Sensor FaultyZ) Sump Pressure Sensor FaultyAA) ** Warning** Communication FailureBB) ** Warning** Firmware FailureCC) Compressor Not In Scheduled Sequence

Adjustable Operating Parameters: A) Compressor Unloaded PressureB) Compressor Loaded PressureC) Timed Stop Delay In MinutesD) Cycle CountE) Short Cycle Time In SecondsF) Target PressureG) Network Unloaded PressureH) Network Loaded PressureI) Modulation Turn Off Delay In MinutesJ) Machine IDK) Sequence Number To Change L) Day To ChangeM) Clear SequenceN) Clear Sequence And ScheduleO) Set Delayed Unload ModeP) Set Immediate Unload Mode

Maintenance Displays:A) Loaded HoursB) Unloaded HoursC) Hours Since Last Fluid ChangeD) Control Line Filter HoursE) Intake Filter HoursF) Fluid Filter HoursG) Separator Element HoursH) View Current Time And DateI) Set Time And Date J) Compressor Control TestK) Serial NumberL) Software Version NumberM) Compressor ModelN) Drive Motor HorsepowerO) VoltageP) Starter TypeQ) Cooling TypeR) Airend Type S) High Air Temperature Shutdown SettingT) High Sump Pressure Shutdown Setting

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 54

Back to TOC

Page 45: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

U) Maximum Unloaded Pressure Setting V) Minimum Loaded Pressure SettingW) Current Loaded Pressure SettingX) Current Unloaded Pressure SettingY) Current Target Pressure SettingZ) Machine IDAA) Auto Dual Shutdown Timer SettingBB) Wye Delta Transition Time SettingCC) Modulation Cycle Count SettingDD) Modulation Time SettingEE) Sump Temperature FF) Pressure Transducer Calibration DateGG) Temperature Sensor Calibration DateHH) Unit Configuration DateII) Current Time And DateJJ) Modem Baud RateKK) Shutdown LogLL) Network Diagnostics

7.5 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown B) Motor overload C) High Sump Pressure ShutdownD) Change inlet filterE) Change lubricant filterF) Change Separator Element

7.6 The control shall have the built-in capability to network up to 16 similar compressorsof various sizes. In this network configuration, the sequence in which the compressorsoperate as base load and trim shall be user selectable. The control shall be able to store nofewer than nine different sequences. An internal clock and calendar shall be included thatwill allow different sequences to be scheduled no fewer than nine times per day. Thecontroller shall have the ability to schedule each day of the week differently.

7.7 The controller shall include a shutdown log that will allow the operator to viewservice and shutdown alarms in the reverse order of occurrence. The log shall give plainEnglish messages that will identify the source of the alarm.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 55

Back to TOC

Page 46: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

SAMPLE BID REQUEST SPECIFICATION FOR A QSI-1000

1. Scope of supply.

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 1010 CFM (total package rated performance measured in accordance withCAGI-PNEUROP Test Code PN2CPTC2) at a full load pressure rating of 110 PSIG.This compressor shall be capable of full load operation at 110 PSIG and have a maximumpressure capability of 125 PSIG.

2. Airend.

2.1 The airend shall have a 4-6 lobe combination with both male and female rotors beingidentical in diameter.

2.2 The discharge end of the rotors shall be supported by triplex bearings on the malerotor and duplex tapered roller bearings on the female rotor. The suction end of the rotorsshall be supported by a single row of cylindrical roller bearings.

2.3 The airend shall have an axial flow inlet housing to allow incoming air to enter thecompression area over the entire face of the rotors. Radial inlet arrangements will not beaccepted.

2.4 The discharge bearings must be housed in the main rotor housing to maintainpermanent rotor alignment within the rotor housing. Separate, bolt-on castings fordischarge bearings will not be accepted.

2.5 The area around the bearings shall be free of any obstruction to the free flow of fluid.Pockets or reservoirs where fluid might collect in the bearing area shall have a magneticdrain plug to trap metallic contamination. This drain plug shall be of sufficient size andconveniently located to allow the regular cleaning of pockets or reservoirs in the bearingarea.

2.6 Male rotor RPM shall be identical to the actual speed of the main drive motor. Thetip speed of the driven rotor shall not exceed 31 meters per second.

2.7 The motor and airend shall be directly coupled through a flexible drop-out typecoupling. No belts or gears shall be included in the drive arrangement.

2.8 The drive rotor shall have a redundant shaft sealing arrangement. Should the primaryshaft seal fail, a secondary seal shall be capable of preventing fluid from leaking out of theairend. A method of detecting a primary shaft seal failure while the machine is inoperation shall be provided.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 56

Back to TOC

Page 47: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

3. Drive motor.

3.1 The main drive motor shall be 200 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

3.2 The main drive motor shall have an ODP enclosure.

4. Cooling system.

4.1 The compressor shall be air-cooled.

4.2 The cooling system shall be capable of maintaining proper compressor temperaturesin ambient conditions up to 110oF.

4.3 Coolers shall be horizontal draft.

4.4 Fluid circulation shall be by positive displacement pump.

5. Aftercooler.

5.1 An air-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to have an approach temperature of not more than5oF at standard conditions.

5.2 A 99.9% efficient moisture separator and trap shall be included.

6. Compressor Fluid.

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use.

6.2 The fluid shall contain no chemical substances that would require it to be treated ashazardous according to the appropriate laws in effect at the time of sale. Used fluid shallbe suitable for recycling along with other waste petroleum oil.

6.3 Fluid carryover into the downstream air system shall not exceed 5 PPM by weightwith new elements.

6.4 A fluid filter shall be provided with a 10 micron absolute rating. The filter media mustbe microfiberglass. Paper media will not be accepted.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 57

Back to TOC

Page 48: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

7. Compressor controls.

7.1 The compressor controls shall allow for full range modulation to match compressorcapacity to system demand. If system demand should fall below a user adjustable percentof compressor capacity, the compressor shall go into an unloaded condition. Anadjustable timer shall be provided to shutdown the compressor if it runs in the unloadedmode for a predetermined length of time. The compressor shall automaticallyreload/restart if the system pressure falls below the set point. A selector switch on thecontrol panel shall be provided to allow the user to bypass the automatic shutdown featureand elect a continuous run mode should the system demand dictate.

7.2 Gauges or indicators shall also be provided to indicate:A) Compressor discharge temperatureB) Discharge air pressure C) Percent capacity D) Operating modeE) Power onF) Running hours

7.3 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown (Probes must be provided at the compressordischarge and the air/fluid separator reservoir to monitor high temperatureconditions)B) Motor overload (This should alert a motor overload for all motors on thecompressor package)C) Change inlet filterD) Change fluid filterE) Change Separator Element

This shutdown and maintenance annunciator panel shall be constructed in such a way thatconnections for remote annunciation can easily be made.

8. Electrical controls.

8.1 All electrical controls shall be designed and constructed in accordance with NationalElectrical Code (NEC) guidelines.

8.2 The main starter control box shall be NEMA 1 design and contain the starter for thefan motor along with other electrical controls.

8.3 All components within the main starter control box shall be UL and/or CSA approvedor listed.

8.4 The main starter control box shall be UL and/or CSA approved or listed.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 58

Back to TOC

Page 49: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.5 Remote mounted control panel boxes will not be accepted.

9. Safety system.

9.1 Pressure vessels shall be ASME coded.

9.2 A pressure relief safety valve shall be provided. This valve shall be sized to handle thefull capacity of the compressor. It shall have a single, directed outlet. Multidirectionalvalves will not be accepted.

9.3 A high air/fluid temperature shutdown system shall be provided. This system shalloperate with a minimum of two temperature sensors. One sensor must be located directlyin the discharge air stream of the airend. One sensor must be located on the dry side ofthe air/fluid separator element. This system must be designed to prevent the compressorfrom running with a failed sensor.

10. Sound levels.

10.1 Sound level shall average 89 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

OPTIONSReplace section in main bid spec with appropriate section below for desired option.

**** AUTO DEMAND CONTROL

7.1 In the "LOCAL" control mode, the compressor controls shall allow for full rangemodulation to match compressor capacity to system demand. If system demand shouldfall below a predetermined percentage of compressor capacity, the compressor shall gointo an unloaded condition. An adjustable timer shall be provided to shutdown thecompressor if it runs in the unloaded mode for a predetermined length of time. Thecompressor shall automatically restart if the system pressure falls below the set point. Inthe "REMOTE" control mode, control of the compressor shall be transferred to a remotecontroller that shall operate the compressor in conjunction with one or more othercompressors. The actual operation of the compressor will be identical to the "LOCAL"mode except the remote controller will determine pressure set points.

**** 575 VOLT

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 59

Back to TOC

Page 50: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

3.1 The main drive motor shall be 200 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** NEMA 4

8.2 The main control box shall be NEMA 4 design and contain the starters for the fanmotor along with other electrical controls.

**** NEMA 12 (use NEMA 4)

8.2 The main control box shall be NEMA 4 design and contain the starter for the fanmotor along with other electrical controls.

**** FOOD GRADE FLUID

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use. It shall meet FDA CFR 178.3570 spec for food grade lubricants.

**** FULL CANOPY

1.2 The compressor shall have a full metal enclosure with quick release panels for easyaccess to service and maintenance items.

(WITHOUT SHROUDS)

10.1 Sound level shall average 85 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

(WITH LOW SOUND SHROUDS)

10.1 Sound level shall average 82 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

(WATER-COOLED)

10.1 Sound level shall average 79 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

**** WATER-COOLED

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 60

Back to TOC

Page 51: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

4.1 The compressor shall be water-cooled.

4.3 Coolers shall be shell and tube type water-cooled coolers. The coolers shall be sizedto maintain normal operating temperatures with inlet water temperatures as high as 100oF.Water pressure drop through the cooling system shall be no more than 10 PSIG.

5.1 A water-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to cool the discharge air temperature to within15oF of the inlet water temperature.

10.1 Sound level shall average 86 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

**** SOLID STATE REDUCED VOLTAGE STARTERS

8.2 The main starter control box shall be NEMA 1 and shall contain provisions to connecta remotely mounted solid state reduced voltage starter for the main drive motor. Motorprotection shall include:

a) Shorted SCR detectionb) Phase lossc) Overloadd) Current flow sensinge) Short circuit protection f) Anti-oscillation circuit

Torque, ramp time and current limit shall be adjustable. An LED display shall indicate thefollowing:

a) Power Onb) Startc) Current Flowd) Run e) At Speed f) Over Temperatureg) Overloadh) Phase Lossi) Shorted SCRj) Short Circuitk) Shunt Trip

Output relays shall be provided to indicate the following:a) Run b) Shunt Trip c) Programmable Status Relay - Will energize on any one of the followingconditions (jumper selectable): At Speed, Phase Loss, Over Temperature,Overload, Shorted SCR and Over Current

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 61

Back to TOC

Page 52: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.5 Remote mounted control panel boxes will be accepted.

**** 125 PSIG FULL LOAD OPERATION

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 1003 CFM (measured in accordance with CAGI-PNEUROP Test CodePN2CPTC2) at a full load pressure rating of 125 PSIG. This compressor shall be capableof full load operation at 125 PSIG and have a maximum pressure capability of 140 PSIG.

3.1 The main drive motor shall be 250 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 575 VOLT

3.1 The main drive motor shall be 250 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** Power$ync®

2.9 The airend shall have a method of controlling displacement at operating speed thatdoes not introduce areas of unswept volume or clearance pockets into the rotor bores.Lift valves that extend into the rotor bore prior to final machining and are machined to theexact tolerance of the rotor bore as the rotor bore is being machined are the preferredmethod of capacity control. Lift valves must be double acting to use air pressure to bothopen and close.

7.1 The compressor controls shall be microprocessor-based. There shall be threeuser-selectable control methods.

A) Constant Run Mode -- This method shall allow the operator to set anoperating pressure range within which the compressor will adjust its capacity tosatisfy the system demand or unload during periods of no demand. B) Auto Dual Mode -- This method shall allow the operator to set an operatingpressure range within which the compressor will adjust its capacity to satisfy thesystem demand or unload during periods of no demand. After a user-definedperiod of unloaded operation, the compressor will automatically shutdown andassume a standby mode. Should system demand return, the compressor willautomatically restart. C) Network Mode -- In place of the pressure deadband, the Network Mode shalluse a target pressure and a variable response rate. The control shall maintain thesystem pressure to within two or three pounds of the target pressure. In the upper50% of the capacity range, the control shall match system demand without

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 62

Back to TOC

Page 53: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

restricting the inlet air flow. In the lower 50% of the capacity range, the controlshall select either a load/no load or modulating control method, based onuser-defined parameters.

7.2 A complete, redundant electro-mechanical control system shall be included that willsafely operate the compressor in the event of a microprocessor failure. This system shallbe user selectable from a switch mounted in the main electrical control enclosure.

7.3 LED displays shall be provided that will constantly indicate discharge temperature andsystem pressure.

7.4 A four-line by forty-character LCD display shall be provided that will allow access tothe following information:

Power-Up Warning Displays:A) Sump Pressure Sensor FailureB) Line Pressure Sensor FailureC) Discharge Temperature Sensor FailureD) Sump Temperature Sensor FailureE) Tripped Motor OverloadF) Relay Board Communication FailureG) Diagnostic FailureH) Setup Memory FailureI) Control Relay Not DisengagedJ) Main Motor Contactor Not DisengagedK) Wye Contactor Not Disengaged (on Wye-Delta starters)L) Deadband Data ErrorM) Setup Memory ErrorN) Setup Data Not InitializedO) Air Filter Vacuum Switch FaultyP) Fluid Filter Delta-P Switch FaultyQ) An Element Needs ServicingR) Minor Diagnostic FailureS) Machine ID Error

Operational Displays: A) Sump Pressure Too High For RestartB) Compressor Is Starting

C) **Warning** Possible Reverse RotationD) Compressor Is Running In Auto-Dual ModeE) Compressor Is UnloadedF) Time Left To ShutdownG) Compressor Has Timed Out And Shut Down **Warning** Will

Automatically RestartH) Running In Continuous Run ModeI) Running In Network Mode Position __ Of __

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 63

Back to TOC

Page 54: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

J) Programmed ShutdownK) **Warning** An Element Needs ServicingL) Emergency Stop Button Has Been PressedM) ** Warning** Setup Memory FailureN) ** Warning** Sequence Data ErrorO) ** Warning** Schedule Data ErrorP) ** Warning** Compressor ID Already In UseQ) ** Warning** High Discharge TemperatureR) ** Warning** High Sump TemperatureS) ** Warning** High Sump PressureT) ** Warning** Motor OverloadU) ** Warning** Contactor Is Not EngagingV) ** Warning** Contactor is Not DisengagingW) Discharge RTD Faulty Or DisconnectedX) Sump RTD Faulty Or DisconnectedY) Line Pressure Sensor FaultyZ) Sump Pressure Sensor FaultyAA) ** Warning** Communication FailureBB) ** Warning** Firmware FailureCC) Compressor Not In Scheduled Sequence

Adjustable Operating Parameters: A) Compressor Unloaded PressureB) Compressor Loaded PressureC) Timed Stop Delay In MinutesD) Cycle CountE) Short Cycle Time In SecondsF) Target PressureG) Network Unloaded PressureH) Network Loaded PressureI) Modulation Turn Off Delay In MinutesJ) Machine IDK) Sequence Number To Change L) Day To ChangeM) Clear SequenceN) Clear Sequence And ScheduleO) Set Delayed Unload ModeP) Set Immediate Unload Mode

Maintenance Displays:A) Loaded HoursB) Unloaded HoursC) Hours Since Last Fluid ChangeD) Control Line Filter HoursE) Intake Filter Hours

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 64

Back to TOC

Page 55: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

F) Fluid Filter HoursG) Separator Element HoursH) View Current Time And DateI) Set Time And Date J) Compressor Control TestK) Serial NumberL) Software Version NumberM) Compressor ModelN) Drive Motor HorsepowerO) VoltageP) Starter TypeQ) Cooling TypeR) Airend Type S) High Air Temperature Shutdown SettingT) High Sump Pressure Shutdown SettingU) Maximum Unloaded Pressure Setting V) Minimum Loaded Pressure SettingW) Current Loaded Pressure SettingX) Current Unloaded Pressure SettingY) Current Target Pressure SettingZ) Machine IDAA) Auto Dual Shutdown Timer SettingBB) Wye Delta Transition Time SettingCC) Modulation Cycle Count SettingDD) Modulation Time SettingEE) Sump Temperature FF) Pressure Transducer Calibration DateGG) Temperature Sensor Calibration DateHH) Unit Configuration DateII) Current Time And DateJJ) Modem Baud RateKK) Shutdown LogLL) Network Diagnostics

7.5 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown B) Motor overload C) High Sump Pressure ShutdownD) Change inlet filterE) Change lubricant filterF) Change Separator Element

7.6 The control shall have the built-in capability to network up to 16 similar compressorsof various sizes. In this network configuration, the sequence in which the compressors

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 65

Back to TOC

Page 56: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

operate as base load and trim shall be user selectable. The control shall be able to store nofewer than nine different sequences. An internal clock and calendar shall be included thatwill allow different sequences to be scheduled no fewer than nine times per day. Thecontroller shall have the ability to schedule each day of the week differently.

7.7 The controller shall include a shutdown log that will allow the operator to viewservice and shutdown alarms in the reverse order of occurrence. The log shall give plainEnglish messages that will identify the source of the alarm.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 66

Back to TOC

Page 57: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

SAMPLE BID REQUEST SPECIFICATION FOR A QSI-1250

1. Scope of supply.

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 1264 CFM (total package rated performance measured in accordance withCAGI-PNEUROP Test Code PN2CPTC2) at a full load pressure rating of 110 PSIG.This compressor shall be capable of full load operation at 110 PSIG and have a maximumpressure capability of 125 PSIG.

2. Airend.

2.1 The airend shall have a 4-6 lobe combination with both male and female rotors beingidentical in diameter.

2.2 The discharge end of the rotors shall be supported by triplex bearings on the malerotor and duplex tapered roller bearings on the female rotor. The suction end of the rotorsshall be supported by a single row of cylindrical roller bearings.

2.3 The airend shall have an axial flow inlet housing to allow incoming air to enter thecompression area over the entire face of the rotors. Radial inlet arrangements will not beaccepted.

2.4 The discharge bearings must be housed in the main rotor housing to maintainpermanent rotor alignment within the rotor housing. Separate, bolt-on castings fordischarge bearings will not be accepted.

2.5 The area around the bearings shall be free of any obstruction to the free flow of fluid.Pockets or reservoirs where fluid might collect in the bearing area shall have a magneticdrain plug to trap metallic contamination. This drain plug shall be of sufficient size andconveniently located to allow the regular cleaning of pockets or reservoirs in the bearingarea.

2.6 Male rotor RPM shall be identical to the actual speed of the main drive motor. Thetip speed of the driven rotor shall not exceed 31 meters per second.

2.7 The motor and airend shall be directly coupled through a flexible drop-out typecoupling. No belts or gears shall be included in the drive arrangement.

2.8 The drive rotor shall have a redundant shaft sealing arrangement. Should the primaryshaft seal fail, a secondary seal shall be capable of preventing fluid from leaking out of theairend. A method of detecting a primary shaft seal failure while the machine is inoperation shall be provided.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 67

Back to TOC

Page 58: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

3. Drive motor.

3.1 The main drive motor shall be 250 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

3.2 The main drive motor shall have an ODP enclosure.

4. Cooling system.

4.1 The compressor shall be air-cooled.

4.2 The cooling system shall be capable of maintaining proper compressor temperaturesin ambient conditions up to 110oF.

4.3 Coolers shall be horizontal draft.

4.4 Fluid circulation shall be by positive displacement pump.

5. Aftercooler.

5.1 An air-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to have an approach temperature of not more than5oF at standard conditions.

5.2 A 99.9% efficient moisture separator and trap shall be included.

6. Compressor Fluid.

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use.

6.2 The fluid shall contain no chemical substances that would require it to be treated ashazardous according to the appropriate laws in effect at the time of sale. Used fluid shallbe suitable for recycling along with other waste petroleum oil.

6.3 Fluid carryover into the downstream air system shall not exceed 5 PPM by weightwith new elements.

6.4 A fluid filter shall be provided with a 10 micron absolute rating. The filter media mustbe microfiberglass. Paper media will not be accepted.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 68

Back to TOC

Page 59: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

7. Compressor controls.

7.1 The compressor controls shall allow for full range modulation to match compressorcapacity to system demand. If system demand should fall below a user adjustable percentof compressor capacity, the compressor shall go into an unloaded condition. Anadjustable timer shall be provided to shutdown the compressor if it runs in the unloadedmode for a predetermined length of time. The compressor shall automaticallyreload/restart if the system pressure falls below the set point. A selector switch on thecontrol panel shall be provided to allow the user to bypass the automatic shutdown featureand elect a continuous run mode should the system demand dictate.

7.2 Gauges or indicators shall also be provided to indicate:A) Compressor discharge temperatureB) Discharge air pressure C) Percent capacity D) Operating modeE) Power onF) Running hours

7.3 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown (Probes must be provided at the compressordischarge and the air/fluid separator reservoir to monitor high temperatureconditions)B) Motor overload (This should alert a motor overload for all motors on thecompressor package)C) Change inlet filterD) Change fluid filterE) Change Separator Element

This shutdown and maintenance annunciator panel shall be constructed in such a way thatconnections for remote annunciation can easily be made.

8. Electrical controls.

8.1 All electrical controls shall be designed and constructed in accordance with NationalElectrical Code (NEC) guidelines.

8.2 The main starter control box shall be NEMA 1 design and contain the starter for thefan motor along with other electrical controls.

8.3 All components within the main starter control box shall be UL and/or CSA approvedor listed.

8.4 The main starter control box shall be UL and/or CSA approved or listed.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 69

Back to TOC

Page 60: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.5 Remote mounted control panel boxes will not be accepted.

9. Safety system.

9.1 Pressure vessels shall be ASME coded.

9.2 A pressure relief safety valve shall be provided. This valve shall be sized to handle thefull capacity of the compressor. It shall have a single, directed outlet. Multidirectionalvalves will not be accepted.

9.3 A high air/fluid temperature shutdown system shall be provided. This system shalloperate with a minimum of two temperature sensors. One sensor must be located directlyin the discharge air stream of the airend. One sensor must be located on the dry side ofthe air/fluid separator element. This system must be designed to prevent the compressorfrom running with a failed sensor.

10. Sound levels.

10.1 Sound level shall average 95 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

OPTIONSReplace section in main bid spec with appropriate section below for desired option.

**** AUTO DEMAND CONTROL

7.1 In the "LOCAL" control mode, the compressor controls shall allow for full rangemodulation to match compressor capacity to system demand. If system demand shouldfall below a predetermined percentage of compressor capacity, the compressor shall gointo an unloaded condition. An adjustable timer shall be provided to shutdown thecompressor if it runs in the unloaded mode for a predetermined length of time. Thecompressor shall automatically restart if the system pressure falls below the set point. Inthe "REMOTE" control mode, control of the compressor shall be transferred to a remotecontroller that shall operate the compressor in conjunction with one or more othercompressors. The actual operation of the compressor will be identical to the "LOCAL"mode except the remote controller will determine pressure set points.

**** 575 VOLT

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 70

Back to TOC

Page 61: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

3.1 The main drive motor shall be 250 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** NEMA 4

8.2 The main control box shall be NEMA 4 design and contain the starters for the fanmotor along with other electrical controls.

**** NEMA 12 (use NEMA 4)

8.2 The main control box shall be NEMA 4 design and contain the starter for the fanmotor along with other electrical controls.

**** FOOD GRADE FLUID

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use. It shall meet FDA CFR 178.3570 spec for food grade lubricants.

**** FULL CANOPY

1.2 The compressor shall have a full metal enclosure with quick release panels for easyaccess to service and maintenance items.

(WITHOUT SHROUDS)

10.1 Sound level shall average 91 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

(WITH LOW SOUND SHROUDS)

10.1 Sound level shall average 85 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

(WATER-COOLED)

10.1 Sound level shall average 84 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

**** WATER-COOLED

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 71

Back to TOC

Page 62: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

4.1 The compressor shall be water-cooled.

4.3 Coolers shall be shell and tube type water-cooled coolers. The coolers shall be sizedto maintain normal operating temperatures with inlet water temperatures as high as 100oF.Water pressure drop through the cooling system shall be no more than 13 PSIG.

5.1 A water-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to cool the discharge air temperature to within15oF of the inlet water temperature.

10.1 Sound level shall average 92 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

**** SOLID STATE REDUCED VOLTAGE STARTERS

8.2 The main starter control box shall be NEMA 1 and shall contain provisions to connecta remotely mounted solid state reduced voltage starter for the main drive motor. Motorprotection shall include:

a) Shorted SCR detectionb) Phase lossc) Overloadd) Current flow sensinge) Short circuit protection f) Anti-oscillation circuit

Torque, ramp time and current limit shall be adjustable. An LED display shall indicate thefollowing:

a) Power Onb) Startc) Current Flowd) Run e) At Speed f) Over Temperatureg) Overloadh) Phase Lossi) Shorted SCRj) Short Circuitk) Shunt Trip

Output relays shall be provided to indicate the following:a) Run b) Shunt Trip c) Programmable Status Relay - Will energize on any one of the followingconditions (jumper selectable): At Speed, Phase Loss, Over Temperature,Overload, Shorted SCR and Over Current

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 72

Back to TOC

Page 63: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.5 Remote mounted control panel boxes will be accepted.

**** 125 PSIG FULL LOAD OPERATION

1.1 This specification is for an oil-flooded rotary screw compressor with a minimumcapacity of 1255 CFM (measured in accordance with CAGI-PNEUROP Test CodePN2CPTC2) at a full load pressure rating of 125 PSIG. This compressor shall be capableof full load operation at 125 PSIG and have a maximum pressure capability of 140 PSIG.

3.1 The main drive motor shall be 300 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 575 VOLT

3.1 The main drive motor shall be 300 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** Power$ync®

2.9 The airend shall have a method of controlling displacement at operating speed thatdoes not introduce areas of unswept volume or clearance pockets into the rotor bores.Lift valves that extend into the rotor bore prior to final machining and are machined to theexact tolerance of the rotor bore as the rotor bore is being machined are the preferredmethod of capacity control. Lift valves must be double acting to use air pressure to bothopen and close.

7.1 The compressor controls shall be microprocessor-based. There shall be threeuser-selectable control methods.

A) Constant Run Mode -- This method shall allow the operator to set anoperating pressure range within which the compressor will adjust its capacity tosatisfy the system demand or unload during periods of no demand. B) Auto Dual Mode -- This method shall allow the operator to set an operatingpressure range within which the compressor will adjust its capacity to satisfy thesystem demand or unload during periods of no demand. After a user-definedperiod of unloaded operation, the compressor will automatically shutdown andassume a standby mode. Should system demand return, the compressor willautomatically restart. C) Network Mode -- In place of the pressure deadband, the Network Mode shalluse a target pressure and a variable response rate. The control shall maintain thesystem pressure to within two or three pounds of the target pressure. In the upper50% of the capacity range, the control shall match system demand without

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 73

Back to TOC

Page 64: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

restricting the inlet air flow. In the lower 50% of the capacity range, the controlshall select either a load/no load or modulating control method, based onuser-defined parameters.

7.2 A complete, redundant electro-mechanical control system shall be included that willsafely operate the compressor in the event of a microprocessor failure. This system shallbe user selectable from a switch mounted in the main electrical control enclosure.

7.3 LED displays shall be provided that will constantly indicate discharge temperature andsystem pressure.

7.4 A four-line by forty-character LCD display shall be provided that will allow access tothe following information:

Power-Up Warning Displays:A) Sump Pressure Sensor FailureB) Line Pressure Sensor FailureC) Discharge Temperature Sensor FailureD) Sump Temperature Sensor FailureE) Tripped Motor OverloadF) Relay Board Communication FailureG) Diagnostic FailureH) Setup Memory FailureI) Control Relay Not DisengagedJ) Main Motor Contactor Not DisengagedK) Wye Contactor Not Disengaged (on Wye-Delta starters)L) Deadband Data ErrorM) Setup Memory ErrorN) Setup Data Not InitializedO) Air Filter Vacuum Switch FaultyP) Fluid Filter Delta-P Switch FaultyQ) An Element Needs ServicingR) Minor Diagnostic FailureS) Machine ID Error

Operational Displays: A) Sump Pressure Too High For RestartB) Compressor Is Starting

C) **Warning** Possible Reverse RotationD) Compressor Is Running In Auto-Dual ModeE) Compressor Is UnloadedF) Time Left To ShutdownG) Compressor Has Timed Out And Shut Down **Warning** Will

Automatically RestartH) Running In Continuous Run ModeI) Running In Network Mode Position __ Of __

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 74

Back to TOC

Page 65: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

J) Programmed ShutdownK) **Warning** An Element Needs ServicingL) Emergency Stop Button Has Been PressedM) ** Warning** Setup Memory FailureN) ** Warning** Sequence Data ErrorO) ** Warning** Schedule Data ErrorP) ** Warning** Compressor ID Already In UseQ) ** Warning** High Discharge TemperatureR) ** Warning** High Sump TemperatureS) ** Warning** High Sump PressureT) ** Warning** Motor OverloadU) ** Warning** Contactor Is Not EngagingV) ** Warning** Contactor is Not DisengagingW) Discharge RTD Faulty Or DisconnectedX) Sump RTD Faulty Or DisconnectedY) Line Pressure Sensor FaultyZ) Sump Pressure Sensor FaultyAA) ** Warning** Communication FailureBB) ** Warning** Firmware FailureCC) Compressor Not In Scheduled Sequence

Adjustable Operating Parameters: A) Compressor Unloaded PressureB) Compressor Loaded PressureC) Timed Stop Delay In MinutesD) Cycle CountE) Short Cycle Time In SecondsF) Target PressureG) Network Unloaded PressureH) Network Loaded PressureI) Modulation Turn Off Delay In MinutesJ) Machine IDK) Sequence Number To Change L) Day To ChangeM) Clear SequenceN) Clear Sequence And ScheduleO) Set Delayed Unload ModeP) Set Immediate Unload Mode

Maintenance Displays:A) Loaded HoursB) Unloaded HoursC) Hours Since Last Fluid ChangeD) Control Line Filter HoursE) Intake Filter Hours

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 75

Back to TOC

Page 66: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

F) Fluid Filter HoursG) Separator Element HoursH) View Current Time And DateI) Set Time And Date J) Compressor Control TestK) Serial NumberL) Software Version NumberM) Compressor ModelN) Drive Motor HorsepowerO) VoltageP) Starter TypeQ) Cooling TypeR) Airend Type S) High Air Temperature Shutdown SettingT) High Sump Pressure Shutdown SettingU) Maximum Unloaded Pressure Setting V) Minimum Loaded Pressure SettingW) Current Loaded Pressure SettingX) Current Unloaded Pressure SettingY) Current Target Pressure SettingZ) Machine IDAA) Auto Dual Shutdown Timer SettingBB) Wye Delta Transition Time SettingCC) Modulation Cycle Count SettingDD) Modulation Time SettingEE) Sump Temperature FF) Pressure Transducer Calibration DateGG) Temperature Sensor Calibration DateHH) Unit Configuration DateII) Current Time And DateJJ) Modem Baud RateKK) Shutdown LogLL) Network Diagnostics

7.5 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown B) Motor overload C) High Sump Pressure ShutdownD) Change inlet filterE) Change lubricant filterF) Change Separator Element

7.6 The control shall have the built-in capability to network up to 16 similar compressorsof various sizes. In this network configuration, the sequence in which the compressors

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 76

Back to TOC

Page 67: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

operate as base load and trim shall be user selectable. The control shall be able to store nofewer than nine different sequences. An internal clock and calendar shall be included thatwill allow different sequences to be scheduled no fewer than nine times per day. Thecontroller shall have the ability to schedule each day of the week differently.

7.7 The controller shall include a shutdown log that will allow the operator to viewservice and shutdown alarms in the reverse order of occurrence. The log shall give plainEnglish messages that will identify the source of the alarm.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 77

Back to TOC

Page 68: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

SAMPLE BID REQUEST SPECIFICATION FOR A QSI-1500

1. Scope of supply.

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 1515 CFM (total package rated performance measured in accordance withCAGI-PNEUROP Test Code PN2CPTC2) at a full load pressure rating of 110 PSIG.This compressor shall be capable of full load operation at 110 PSIG and have a maximumpressure capability of 125 PSIG.

2. Airend.

2.1 The airend shall have a 4-6 lobe combination with both male and female rotors beingidentical in diameter.

2.2 The discharge end of the rotors shall be supported by triplex bearings on the malerotor and duplex tapered roller bearings on the female rotor. The suction end of the rotorsshall be supported by a single row of cylindrical roller bearings.

2.3 The airend shall have an axial flow inlet housing to allow incoming air to enter thecompression area over the entire face of the rotors. Radial inlet arrangements will not beaccepted.

2.4 The discharge bearings must be housed in the main rotor housing to maintainpermanent rotor alignment within the rotor housing. Separate, bolt-on castings fordischarge bearings will not be accepted.

2.5 The area around the bearings shall be free of any obstruction to the free flow of fluid.Pockets or reservoirs where fluid might collect in the bearing area shall have a magneticdrain plug to trap metallic contamination. This drain plug shall be of sufficient size andconveniently located to allow the regular cleaning of pockets or reservoirs in the bearingarea.

2.6 Male rotor RPM shall be identical to the actual speed of the main drive motor. Thetip speed of the driven rotor shall not exceed 31 meters per second.

2.7 The motor and airend shall be directly coupled through a flexible drop-out typecoupling. No belts or gears shall be included in the drive arrangement.

2.8 The drive rotor shall have a redundant shaft sealing arrangement. Should the primaryshaft seal fail, a secondary seal shall be capable of preventing fluid from leaking out of theairend. A method of detecting a primary shaft seal failure while the machine is inoperation shall be provided.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 78

Back to TOC

Page 69: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

3. Drive motor.

3.1 The main drive motor shall be 300 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

3.2 The main drive motor shall have an ODP enclosure.

4. Cooling system.

4.1 The compressor shall be air-cooled.

4.2 The cooling system shall be capable of maintaining proper compressor temperaturesin ambient conditions up to 110oF.

4.3 Coolers shall be horizontal draft.

4.4 Fluid circulation shall be by positive displacement pump.

5. Aftercooler.

5.1 An air-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to have an approach temperature of not more than5oF at standard conditions.

5.2 A 99.9% efficient moisture separator and trap shall be included.

6. Compressor Fluid.

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use.

6.2 The fluid shall contain no chemical substances that would require it to be treated ashazardous according to the appropriate laws in effect at the time of sale. Used fluid shallbe suitable for recycling along with other waste petroleum oil.

6.3 Fluid carryover into the downstream air system shall not exceed 5 PPM by weightwith new elements.

6.4 A fluid filter shall be provided with a 10 micron absolute rating. The filter media mustbe microfiberglass. Paper media will not be accepted.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 79

Back to TOC

Page 70: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

7. Compressor controls.

7.1 The compressor controls shall allow for full range modulation to match compressorcapacity to system demand. If system demand should fall below a user adjustable percentof compressor capacity, the compressor shall go into an unloaded condition. Anadjustable timer shall be provided to shutdown the compressor if it runs in the unloadedmode for a predetermined length of time. The compressor shall automaticallyreload/restart if the system pressure falls below the set point. A selector switch on thecontrol panel shall be provided to allow the user to bypass the automatic shutdown featureand elect a continuous run mode should the system demand dictate.

7.2 Gauges or indicators shall also be provided to indicate:A) Compressor discharge temperatureB) Discharge air pressure C) Percent capacity D) Operating modeE) Power onF) Running hours

7.3 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown (Probes must be provided at the compressordischarge and the air/fluid separator reservoir to monitor high temperatureconditions)B) Motor overload (This should alert a motor overload for all motors on thecompressor package)C) Change inlet filterD) Change fluid filterE) Change Separator Element

This shutdown and maintenance annunciator panel shall be constructed in such a way thatconnections for remote annunciation can easily be made.

8. Electrical controls.

8.1 All electrical controls shall be designed and constructed in accordance with NationalElectrical Code (NEC) guidelines.

8.2 The main starter control box shall be NEMA 1 design and contain the starter for thefan motor along with other electrical controls.

8.3 All components within the main starter control box shall be UL and/or CSA approvedor listed.

8.4 The main starter control box shall be UL and/or CSA approved or listed.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 80

Back to TOC

Page 71: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.5 Remote mounted control panel boxes will not be accepted.

9. Safety system.

9.1 Pressure vessels shall be ASME coded.

9.2 A pressure relief safety valve shall be provided. This valve shall be sized to handle thefull capacity of the compressor. It shall have a single, directed outlet. Multidirectionalvalves will not be accepted.

9.3 A high air/fluid temperature shutdown system shall be provided. This system shalloperate with a minimum of two temperature sensors. One sensor must be located directlyin the discharge air stream of the airend. One sensor must be located on the dry side ofthe air/fluid separator element. This system must be designed to prevent the compressorfrom running with a failed sensor.

10. Sound levels.

10.1 Sound level shall average 96 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

OPTIONSReplace section in main bid spec with appropriate section below for desired option.

**** AUTO DEMAND CONTROL

7.1 In the "LOCAL" control mode, the compressor controls shall allow for full rangemodulation to match compressor capacity to system demand. If system demand shouldfall below a predetermined percentage of compressor capacity, the compressor shall gointo an unloaded condition. An adjustable timer shall be provided to shutdown thecompressor if it runs in the unloaded mode for a predetermined length of time. Thecompressor shall automatically restart if the system pressure falls below the set point. Inthe "REMOTE" control mode, control of the compressor shall be transferred to a remotecontroller that shall operate the compressor in conjunction with one or more othercompressors. The actual operation of the compressor will be identical to the "LOCAL"mode except the remote controller will determine pressure set points.

**** 575 VOLT

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 81

Back to TOC

Page 72: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

3.1 The main drive motor shall be 300 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** NEMA 4

8.2 The main control box shall be NEMA 4 design and contain the starters for the fanmotor along with other electrical controls.

**** NEMA 12 (use NEMA 4)

8.2 The main control box shall be NEMA 4 design and contain the starter for the fanmotor along with other electrical controls.

**** FOOD GRADE FLUID

6.1 The fluid used in this compressor shall be a PAO synthetic specifically designed forcompressor use. It shall meet FDA CFR 178.3570 spec for food grade lubricants.

**** FULL CANOPY

1.2 The compressor shall have a full metal enclosure with quick release panels for easyaccess to service and maintenance items.

(WITHOUT SHROUDS)

10.1 Sound level shall average 93 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

(WITH LOW SOUND SHROUDS)

10.1 Sound level shall average 85 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

(WATER-COOLED)

10.1 Sound level shall average 84 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

**** WATER-COOLED

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 82

Back to TOC

Page 73: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

4.1 The compressor shall be water-cooled.

4.3 Coolers shall be shell and tube type water-cooled coolers. The coolers shall be sizedto maintain normal operating temperatures with inlet water temperatures as high as 100oF.Water pressure drop through the cooling system shall be no more than 16 PSIG.

5.1 A water-cooled aftercooler shall be included as an integral part of the compressorpackage. The aftercooler shall be sized to cool the discharge air temperature to within15oF of the inlet water temperature.

10.1 Sound level shall average 84 dB(A) when measured in free field conditions, 1 meteraway from the compressor.

**** SOLID STATE REDUCED VOLTAGE STARTERS

8.2 The main starter control box shall be NEMA 1 and shall contain provisions to connecta remotely mounted solid state reduced voltage starter for the main drive motor. Motorprotection shall include:

a) Shorted SCR detectionb) Phase lossc) Overloadd) Current flow sensinge) Short circuit protection f) Anti-oscillation circuit

Torque, ramp time and current limit shall be adjustable. An LED display shall indicate thefollowing:

a) Power Onb) Startc) Current Flowd) Run e) At Speed f) Over Temperatureg) Overloadh) Phase Lossi) Shorted SCRj) Short Circuitk) Shunt Trip

Output relays shall be provided to indicate the following:a) Run b) Shunt Trip c) Programmable Status Relay - Will energize on any one of the followingconditions (jumper selectable): At Speed, Phase Loss, Over Temperature,Overload, Shorted SCR and Over Current

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 83

Back to TOC

Page 74: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

8.5 Remote mounted control panel boxes will be accepted.

**** 125 PSIG FULL LOAD OPERATION

1.1 This specification is for a fluid-flooded rotary screw compressor with a minimumcapacity of 1504 CFM (measured in accordance with CAGI-PNEUROP Test CodePN2CPTC2) at a full load pressure rating of 125 PSIG. This compressor shall be capableof full load operation at 125 PSIG and have a maximum pressure capability of 140 PSIG.

3.1 The main drive motor shall be 350 nameplate horsepower rated for 460 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** 575 VOLT

3.1 The main drive motor shall be 350 nameplate horsepower rated for 575 volt, 60 cycle,3 phase operation with no more than a 1.15 service factor.

**** Power$ync®

2.9 The airend shall have a method of controlling displacement at operating speed thatdoes not introduce areas of unswept volume or clearance pockets into the rotor bores.Lift valves that extend into the rotor bore prior to final machining and are machined to theexact tolerance of the rotor bore as the rotor bore is being machined are the preferredmethod of capacity control. Lift valves must be double acting to use air pressure to bothopen and close.

7.1 The compressor controls shall be microprocessor-based. There shall be threeuser-selectable control methods.

A) Constant Run Mode -- This method shall allow the operator to set anoperating pressure range within which the compressor will adjust its capacity tosatisfy the system demand or unload during periods of no demand. B) Auto Dual Mode -- This method shall allow the operator to set an operatingpressure range within which the compressor will adjust its capacity to satisfy thesystem demand or unload during periods of no demand. After a user-definedperiod of unloaded operation, the compressor will automatically shutdown andassume a standby mode. Should system demand return, the compressor willautomatically restart. C) Network Mode -- In place of the pressure deadband, the Network Mode shalluse a target pressure and a variable response rate. The control shall maintain thesystem pressure to within two or three pounds of the target pressure. In the upper

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 84

Back to TOC

Page 75: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

50% of the capacity range, the control shall match system demand withoutrestricting the inlet air flow. In the lower 50% of the capacity range, the controlshall select either a load/no load or modulating control method, based onuser-defined parameters.

7.2 A complete, redundant electro-mechanical control system shall be included that willsafely operate the compressor in the event of a microprocessor failure. This system shallbe user selectable from a switch mounted in the main electrical control enclosure.

7.3 LED displays shall be provided that will constantly indicate discharge temperature andsystem pressure.

7.4 A four-line by forty-character LCD display shall be provided that will allow access tothe following information:

Power-Up Warning Displays:A) Sump Pressure Sensor FailureB) Line Pressure Sensor FailureC) Discharge Temperature Sensor FailureD) Sump Temperature Sensor FailureE) Tripped Motor OverloadF) Relay Board Communication FailureG) Diagnostic FailureH) Setup Memory FailureI) Control Relay Not DisengagedJ) Main Motor Contactor Not DisengagedK) Wye Contactor Not Disengaged (on Wye-Delta starters)L) Deadband Data ErrorM) Setup Memory ErrorN) Setup Data Not InitializedO) Air Filter Vacuum Switch FaultyP) Fluid Filter Delta-P Switch FaultyQ) An Element Needs ServicingR) Minor Diagnostic FailureS) Machine ID Error

Operational Displays: A) Sump Pressure Too High For RestartB) Compressor Is Starting

C) **Warning** Possible Reverse RotationD) Compressor Is Running In Auto-Dual ModeE) Compressor Is UnloadedF) Time Left To ShutdownG) Compressor Has Timed Out And Shut Down **Warning** Will

Automatically RestartH) Running In Continuous Run Mode

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 85

Back to TOC

Page 76: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

I) Running In Network Mode Position __ Of __J) Programmed ShutdownK) **Warning** An Element Needs ServicingL) Emergency Stop Button Has Been PressedM) ** Warning** Setup Memory FailureN) ** Warning** Sequence Data ErrorO) ** Warning** Schedule Data ErrorP) ** Warning** Compressor ID Already In UseQ) ** Warning** High Discharge TemperatureR) ** Warning** High Sump TemperatureS) ** Warning** High Sump PressureT) ** Warning** Motor OverloadU) ** Warning** Contactor Is Not EngagingV) ** Warning** Contactor is Not DisengagingW) Discharge RTD Faulty Or DisconnectedX) Sump RTD Faulty Or DisconnectedY) Line Pressure Sensor FaultyZ) Sump Pressure Sensor FaultyAA) ** Warning** Communication FailureBB) ** Warning** Firmware FailureCC) Compressor Not In Scheduled Sequence

Adjustable Operating Parameters: A) Compressor Unloaded PressureB) Compressor Loaded PressureC) Timed Stop Delay In MinutesD) Cycle CountE) Short Cycle Time In SecondsF) Target PressureG) Network Unloaded PressureH) Network Loaded PressureI) Modulation Turn Off Delay In MinutesJ) Machine IDK) Sequence Number To Change L) Day To ChangeM) Clear SequenceN) Clear Sequence And ScheduleO) Set Delayed Unload ModeP) Set Immediate Unload Mode

Maintenance Displays:A) Loaded HoursB) Unloaded HoursC) Hours Since Last Fluid ChangeD) Control Line Filter Hours

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 86

Back to TOC

Page 77: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

E) Intake Filter HoursF) Fluid Filter HoursG) Separator Element HoursH) View Current Time And DateI) Set Time And Date J) Compressor Control TestK) Serial NumberL) Software Version NumberM) Compressor ModelN) Drive Motor HorsepowerO) VoltageP) Starter TypeQ) Cooling TypeR) Airend Type S) High Air Temperature Shutdown SettingT) High Sump Pressure Shutdown SettingU) Maximum Unloaded Pressure Setting V) Minimum Loaded Pressure SettingW) Current Loaded Pressure SettingX) Current Unloaded Pressure SettingY) Current Target Pressure SettingZ) Machine IDAA) Auto Dual Shutdown Timer SettingBB) Wye Delta Transition Time SettingCC) Modulation Cycle Count SettingDD) Modulation Time SettingEE) Sump Temperature FF) Pressure Transducer Calibration DateGG) Temperature Sensor Calibration DateHH) Unit Configuration DateII) Current Time And DateJJ) Modem Baud RateKK) Shutdown LogLL) Network Diagnostics

7.5 The control panel shall include a flow diagram with properly located lights to indicatethe following maintenance and shutdown conditions:

A) High temperature shutdown B) Motor overload C) High Sump Pressure ShutdownD) Change inlet filterE) Change lubricant filterF) Change Separator Element

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 87

Back to TOC

Page 78: Quincy Rotary Screw Sales Manualairenergy.com/files/products/quincy-qsi-540-bid-spec.pdf · 2016-01-26 · SAMPLE BID REQUEST SPECIFICATION FOR A QSI 245 1. Scope of supply. 1.1 This

7.6 The control shall have the built-in capability to network up to 16 similar compressorsof various sizes. In this network configuration, the sequence in which the compressorsoperate as base load and trim shall be user selectable. The control shall be able to store nofewer than nine different sequences. An internal clock and calendar shall be included thatwill allow different sequences to be scheduled no fewer than nine times per day. Thecontroller shall have the ability to schedule each day of the week differently.

7.7 The controller shall include a shutdown log that will allow the operator to viewservice and shutdown alarms in the reverse order of occurrence. The log shall give plainEnglish messages that will identify the source of the alarm.

_________Quincy Rotary Screw Sales Manual____________

Rev.3.15.97 QSI - 88

Back to TOC