EXTG ROOF RIDGERL + 35225
PROP L01 - B5-13FFL + 25450
EXTG ROOF VALLEYRL + 30725
FRAMELESS GLASS CLADDING BARRIER
LOW HEIGHT GLASS BARRIER TO RUN BETWEEN HERITAGE COLUMNS AND CONNECT INTO WALL
FRAMELESS GLASS SLIDING DOORS
PANEL TO CONCEAL FLOOR MOUNTED DOOR GEAR
08
EXTG ROOF RIDGERL + 35225
PROP L01 - B5-13FFL + 25450
EXTG ROOF VALLEYRL + 30725
FRAMELESS GLASS PANELS TO CONNEXT INTO WALL BEHIND
FRAMELESS SLIDING DOORS
08
HJ
LOW HEIGHT GLAZING TO 1200MM
FRAMELESS GLAZING
CAPPING PIECE TO CAPTURE SLIDING DOORS
FRAMELESS SLIDING DOORS WITH CARD READER
B1 0 DO NOT SCALE DIMENSIONS FROM DRAWING10 20 30 40 50 60 70 80 90 100 110 120 130 140 150
Nort
h
original sheet size B1 = 1000 x 707mm
SISSONSSISSONS ARCHITECTS Pty Ltd ABN: 31 621 375 129NOMINATED ARCHITECT: NICK SISSON NSW ARB 7210
Project Project No.
Client Drawing Title Issue DateScale
Drawing No.
17
/01/
2020
11:
5 0:1
0 A
M
1 : 50 @B1 GRID 8 GLAZING STUDY 10/17/19
SK_0851LOCOMOTIVE WORKSHOP 16-002
MIRVAC
1 : 50
SK_0851 ELEVATION - GRID 8 GLAZING1 1 : 50
SK_0851 SECTION - GRID 8 GLASS2
1 : 50
SK_0851 GRID 8 GLAZING - GROUND FLOOR PLAN3
SK_0851 GRID 8 GLAZING - ISO5
FRAMELESS GLAZING PANELS TO CONNECT INTO WALL BETWEEN HERITAGE COLUMNS
SOLID PANEL TO CONCEAL FLOOR MOUNTED DOOR GEAR
FRAMELESS GLASS SLIDING DOORS
CAPPING PIECE TO CAPTURE SLIDING DOORS
B C D E F G H JA
PROP L01 - B5-13FFL + 25450
EXTG TRUSS CHORDRL + 31100
PROP L00 - B8-13FFL + 21850
EXTG ROOF VALLEYRL + 30725
PROP L02 - B5-13FFL + 28510
AMENITIES
WALL HEIGHT TOTHE UNDERSIDEOF CRANE BEAM
GLAZING HEIGHTTO THEUNDERSIDE OFTHE ROOF
STRUCTURAL SUPPORT TOINTERTENANCY WALL &GLAZING ABOVE
HERITAGESTRUCTURAL ZONE
WALL HEIGHT TO THEUNDERSIDE OFSTRUCTURAL SLAB
STRUCTURAL SUPPORTTO INTERTENANCY WALL& GLAZING ABOVE
DOUBLELAYERS OFSKYLIGHT
HERITAGESTRUCTURAL ZONE
STRUCTURAL SUPPORT TOINTERTENANCY WALL &GLAZING ABOVE
FFL + 25440
FFL + 21840
P-I9-002PK5IWS-311
IWS-312
IWS-311
IWS-312
STRUCTURALTENSION ROD
6100 6100 6100 6100 6100 6100 6100 6100
GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101
IWS-301
IWS-301
HERITAGESTRUCTURALFRAMINGTRUSS
GL-101GL-101
EXTG L00 - B3-7RL + 21650
DEMO L01 - B5-8RL + 25070
PROP L01 - B5-13FFL + 25450
EXTG TRUSS CHORDRL + 31100
09
PROP L00 - B8-13FFL + 21850
EXTG ROOF VALLEYRL + 30725
PROP L00 - B3-7FFL + 21800
PROP L02 - B5-13FFL + 28510
DOUBLE 92 STUD WALL WITHPLASTERBOARD FINISH. REFER TODRAWING SA-AR-DWG-BB-B4-5340FOR WALL DETAILIWS-311
IWS-312
HERITAGE BEAM
STRUCTURAL COLUMN
STRUCTURAL TENSION ROD
STRUCTURAL COLUMN
HERITAGE METAL BEAM
HERITAGE STRUCTURAL FRAMING TRUSS
20mm MINIMUM CLEARANCE
GL-101
DOUBLE 92 STUD WALL WITHPLASTERBOARD FINISH. REFER TODRAWING SA-AR-DWG-BB-B4-5340FOR WALL DETAIL
NOM 120mm - C.O.S
METAL INFILL SHEET
RL + 25100
PROVIDE FIXING BRACKETSTO EXITING STRUCTURE
DOUBLE LAYERED ALUMINUM TRIMS TO CLOSETHE GAP BETWEEN GLAZING UNIT AND EXISTINGROOF WITH ACOUSTIC INSULATION FILLED
HERITAGE ROOF STRUCTURALFRAMING TRUSS
WALL NOT TO BE STRUCTURALLYDEPENDENT ON PLATFORM. Note:DETAILS TBC
EXISTING TIMBER WALKWAYSTRUCTURE. COORDINATECONNECTIONS OF WALL AND GLAZINGWITH EXISTING HERITAGE STRUCTURETO MINIMISE IMPACT
BCDEFGHJ A
PROP L01 - B5-13FFL + 25450
EXTG TRUSS CHORDRL + 31100 EXTG ROOF VALLEY
RL + 30725
PROP L00 - B3-7FFL + 21800
PROP L02 - B5-13FFL + 28510
6100 6100 6100 6100 6100 6100 6100 6100
IWS-311
IWS-312
IWS-311
IWS-312
S-05-011PK5
AMENITIES
GLAZING HEIGHTTO THEUNDERSIDE OFTHE ROOF
STRUCTURAL SUPPORT TOINTERTENANCY WALL &GLAZING ABOVE
HERITAGESTRUCTURAL ZONE
WALL HEIGHT TO THEUNDERSIDE OFSTRUCTURAL SLAB
STRUCTURAL SUPPORTTO INTERTENANCY WALL& GLAZING ABOVE
DOUBLELAYERS OFSKYLIGHT
HERITAGESTRUCTURALZONE
STRUCTURAL SUPPORT TOINTERTENANCY WALL &GLAZING ABOVE
STRUCTURALTENSION ROD
IWS-301
GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101
WALL HEIGHT TOTHE UNDERSIDEOF CRANE BEAM
HERITAGESTRUCTURALFRAMINGTRUSS
GL-101
IWS-301IWS-301
EXITING SERVICE PIPES (C.O.S)
BCDEFGHJ A
09
44220 2
4220
34220
61006100610061006100610061006100
AMENITIES
IWS-301 IWS-301
IWS-301
MirvacDesignarchitectsplannersinteriordesigners
Level 28, 200 GeorgeSt.Sydney NSW, 2000tel. 02 9090 8000fax. 02 9080 8181
Mirvac Design Pty. LtdABN 78 003 359 153
B1
key plan
revdrawing no.
ALL EXISTING CONDITIONS TO BE CHECKED ON SITE.ALL DIMENSIONS AND SETOUTS TO BE VERIFIED PRIOR TOCOMMENCEMENT ON SITE.ALL OMISSIONS OR DISCREPANCIES TO BE NOTIFIED TO THEARCHITECT.
COPYRIGHTTHE COPYRIGHT OF THIS DRAWING TOGETHER WITH ANY OTHERDOCUMENTS PREPARED BY SISSONS ARCHITECTS (SA) REMAINSTHE PROPERTY OF SA.SA GRANTS LICENCE FOR THE USE OF THIS DOCUMENT FOR THEPURPOSE FOR WHICH IT IS INTENDED. THE LICENCE IS NOTTRANSFERABLE WITHOUT THE PERMISSION OF SA.
0 DO NOT SCALE DIMENSIONS FROMDRAWING
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
notes
retail architect
Level 1, 7 Kelly St, UltimoNSW 2007
Tel. 02 9566 16112 Locomotive St, Eveleigh NSW 2015
project no.
drawing title status
scale date
original sheet size B1 = 1000 x707mm
C
Level 28, 200 George St,Sydney, NSW 2000 Tel.+61 2
9080 8000
design architectSuite 5.01,
53 Berry St,North Sydney
NSW 2060Tel. 02 8904 1853
DRAWING MUST BE PRINTED IN COLOUR
STAGE 2 STAGE 1 project architect
07/1
1/2 0
191:
07:4
6PM
F
As indicated @B1
PRELIMINARY
SA-AR-DWG-BB-B4-4220LOCOMOTIVE WORKSHOP
16-002
INTERTENANCY WALLSINTERNAL - ELEVATIONS /SECTION
1 : 100INTERTENANCY WALL -ELEVATION 012
1 : 25INTERTENANCY WALL SECTION4
INTERTENANCY WALL - PERSPECTIVE5
(QUANTIUM & HOIST)
1 : 100INTERTENANCY WALL -ELEVATION 023
1 : 100INTERTENANCY WALL PLAN1
rev date description by chkA 02.03.18 TYPE C/D COST PLAN ISSUE LYC CCB 13.04.18 TYPE C/D COST PLAN ISSUE FOR TENDER LYC CCC 01.06.18 TYPE C/D COST PLAN ISSUE FOR TENDER AR CCD 02.11.18 ISSUED FOR TENDER - GA PACKAGE LYC CCE 23.11.18 ISSUED FOR TENDER - FACADE ACF 07.11.19 ISSUED FOR INFORMATION HY RD
GENERAL NOTES:
1. Drawing ReferencesThe Contractor must refer to other relevant documents including but not limited to the following:Refer to 3000 series drawings for GA Plans, Elevations & SectionsRefer to 5300 series drawings for Wall details
2. Other ReferencesStructural Adequacy Compliance: refer to Consultants wind report and structural performance briefDesign Compliance: refer to relevant Architectural &/or Consultant specificationMaterial Selection: refer finishes scheduleInstallation Compliance: refer Manufacturers specificationAcoustic Compliance: refer Acoustic Consultant reportThermal Compliance: refer ESD / BASIX reportProduct Specific Compliance: refer to Manufacturers recommendation and required FRL
3. Drawing rules, setout and dimensioning3.1 Setout dimensions relate to the face of finish (plasterboard/villaboard or tiles) not the face of framing.3.2 In setting out walls give preference to alignment of stud walls with fixed elements such as masonry walls, concrete columns or glazingframes, where the drawing indicates this intent. If the setout dimension does not concur with this intent verify dimension before proceeding.
EXTG L00 - B9-13+15RL + 21700
10
DEMO L01 - B5-8RL + 25070
PROP L01 - B5-13FFL + 25450
EXTG TRUSS CHORDRL + 31100
PROP L00 - B8-13FFL + 21850
EXTG ROOF VALLEYRL + 30725
PROP L02 - B5-13FFL + 28510
DOUBLE 92 STUD WALL WITHPLASTERBOARD FINISH. REFER TODRAWING SA-AR-DWG-BB-B4-5340FOR WALL DETAIL
STRUCTURAL COLUMN
STRUCTURAL TENSION ROD
HERITAGE STRUCTURAL FRAMING TRUSS
IWS-311
STRUCTURAL COLUMN
DOUBLE 92 STUD WALL WITHPLASTERBOARD FINISH. REFER TODRAWING SA-AR-DWG-BB-B4-5340FOR WALL DETAIL
IWS-311
IWS-301
GL-101
WALL CAPPING
EXITING SERVICE PIPES (C.O.S)
EXITING SERVICE PIPES (C.O.S)
HERITAGE BEAM
EXTG L00 - B9-13+15RL + 21700
SRPH J K L M N
PROP L01 - B5-13FFL + 25450
EXTG TRUSS CHORDRL + 31100
PROP L00 - B8-13FFL + 21850
EXTG ROOF VALLEYRL + 30725
PROP L02 - B5-13FFL + 28510
IWS-311
IWS-311
IWS-311
IWS-311IWS-311
IWS-311
6100 6100 6100 6100 6100 6100 6100 6100
WALL HEIGHT TOTHE UNDERSIDE OFTHE ROOF
STRUCTURAL SUPPORT TOINTERTENANCY WALL &GLAZING ABOVE
WALL HEIGHT TO THEUNDERSIDE OFSTRUCTURAL SLAB
STRUCTURAL SUPPORTTO INTERTENANCY WALL& GLAZING ABOVE
DOUBLELAYERS OFSKYLIGHT
HERITAGESTRUCTURALZONE
STRUCTURAL SUPPORT TOINTERTENANCY WALL &GLAZING ABOVE
STRUCTURALTENSION ROD
HERITAGESTRUCTURALFRAMING TRUSS
1A095. A
S R P HJKLMN
PROP L01 - B5-13FFL + 25450
EXTG TRUSS CHORDRL + 31100
PROP L00 - B8-13FFL + 21850
EXTG ROOF VALLEYRL + 30725
PROP L02 - B5-13FFL + 28510
6100 6100 6100 6100 6100 6100 6100 6100
IWS-311
IWS-311
IWS-311
IWS-301
GL-101 GL-101 GL-101 GL-101 GL-101 GL-101 GL-101
EXITING SERVICE PIPES (C.O.S)
GL-101 GL-101 GL-101 GL-101 GL-101
WALL HEIGHT TOTHE UNDERSIDEOF THE ROOF
WALL HEIGHT TO THEUNDERSIDE OFSTRUCTURAL SLAB
STRUCTURAL SUPPORTTO INTERTENANCY WALL& GLAZING ABOVE
DOUBLELAYERS OFSKYLIGHT
HERITAGESTRUCTURALFRAMINGTRUSSES
10
S R P HJKLMN
44221
24221
34221
61006100610061006100610061006100
IWS-311
SF42
MirvacDesignarchitectsplannersinteriordesigners
Level 28, 200 GeorgeSt.Sydney NSW, 2000tel. 02 9090 8000fax. 02 9080 8181
Mirvac Design Pty. LtdABN 78 003 359 153
B1
key plan
revdrawing no.
ALL EXISTING CONDITIONS TO BE CHECKED ON SITE.ALL DIMENSIONS AND SETOUTS TO BE VERIFIED PRIOR TOCOMMENCEMENT ON SITE.ALL OMISSIONS OR DISCREPANCIES TO BE NOTIFIED TO THEARCHITECT.
COPYRIGHTTHE COPYRIGHT OF THIS DRAWING TOGETHER WITH ANY OTHERDOCUMENTS PREPARED BY SISSONS ARCHITECTS (SA) REMAINSTHE PROPERTY OF SA.SA GRANTS LICENCE FOR THE USE OF THIS DOCUMENT FOR THEPURPOSE FOR WHICH IT IS INTENDED. THE LICENCE IS NOTTRANSFERABLE WITHOUT THE PERMISSION OF SA.
0 DO NOT SCALE DIMENSIONS FROMDRAWING
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
notes
Nor
th
retail architect
Level 1, 7 Kelly St, UltimoNSW 2007
Tel. 02 9566 16112 Locomotive St, Eveleigh NSW 2015
project no.
drawing title status
scale date
original sheet size B1 = 1000 x707mm
D
Level 28, 200 George St,Sydney, NSW 2000 Tel.+61 2
9080 8000
design architectSuite 5.01,
53 Berry St,North Sydney
NSW 2060Tel. 02 8904 1853
DRAWING MUST BE PRINTED IN COLOUR
STAGE 2 STAGE 1 project architect
07/1
1/2 0
191:
22:3
5PM
A
As indicated @B1
PRELIMINARY
SA-AR-DWG-BB-B4-4221LOCOMOTIVE WORKSHOP
16-002
INTERTENANCY WALLSINTERNAL - ELEVATIONS /SECTION 11/04/19
(QUANTIUM & M&C SAATCHI)
rev date description by chkA 07.11.19 ISSUED FOR INFORMATION HY RD
1 : 25INTERTENANCY WALL - SECTION4
1 : 100INTERTENANCY WALL - ELEVATION 012
1 : 100INTERTENANCY WALL - ELEVATION 023
1 : 100INTERTENANCY WALL PLAN.1
GENERAL NOTES:
1. Drawing ReferencesThe Contractor must refer to other relevant documents including but not limited to the following:Refer to 3000 series drawings for GA Plans, Elevations & SectionsRefer to 5300 series drawings for Wall details
2. Other ReferencesStructural Adequacy Compliance: refer to Consultants wind report and structural performance briefDesign Compliance: refer to relevant Architectural &/or Consultant specificationMaterial Selection: refer finishes scheduleInstallation Compliance: refer Manufacturers specificationAcoustic Compliance: refer Acoustic Consultant reportThermal Compliance: refer ESD / BASIX reportProduct Specific Compliance: refer to Manufacturers recommendation and required FRL
3. Drawing rules, setout and dimensioning3.1 Setout dimensions relate to the face of finish (plasterboard/villaboard or tiles) not the face of framing.3.2 In setting out walls give preference to alignment of stud walls with fixed elements such as masonry walls, concrete columns or glazingframes, where the drawing indicates this intent. If the setout dimension does not concur with this intent verify dimension before proceeding.
INTERTENANCY WALL - PERSPECTIVE5