re-bid: dodie anderson academic enrichment center...
TRANSCRIPT
SHEET
# REVISIONDATE
PHASE:
PROJECT NO.
ISSUE DATE
STATE PROJECT NO. H27-Z302
STA
TE P
RO
JEC
T N
O. H
27-Z
302
T1.00
TITLE SHEET
CONSTRUCTION DOCUMENTS
1316 Washington Street
Suite 100
Columbia, SC 29201
803.799.5181
www.watsontatesavory.com
Watson Tate Savory, Inc.
RE-BID: DODIE ANDERSON ACADEMIC ENRICHMENT CENTER NUTRITION STATIONUNIVERSITY OF SOUTH CAROLINA ATHLETICS
1302 Heyward StreetColumbia SC, 29208
CONSTRUCTION DOCUMENTS MARCH 20, 2017
Architect:
743 Greene Street
Columbia, SC 29208
803.777.5500
www.sc.edu
University of South CarolinaOwner:
4403 Broad River Road
Columbia, SC 29210
803.731.9834
Mechanical Design, Inc.Mechanical / Plumbing / Fire Protection:
7 Clusters Court
Suite 201
Columbia, SC 29210
803.731.0650
Belka Engineering Assoc.Electrical:
1627
MARCH 20, 2017
RE-
BID
: DO
DIE
AN
DER
SO
N A
CA
DEM
IC E
NR
ICH
MEN
T
CEN
TER
NU
TRIT
ION
STA
TIO
N
ALTERNATES:
ONE (1): At Base Bid: provide Painted Steel Overhead
Coiling Counter Shutters. At Alternate No. 1: provide
Wood Overhead Coiling Counter Shutters. See
specification 08 3323.
TWO (2): At Base Bid: Do not include wall cabinets on
the wall behind the Nurtition Station. At Alternate No.
2, Provide wall cabinets as shown in detail 4/A2.01.
THREE (3): At Base Bid: Leave existing cabinets in
Office 103. At Alternate No. 3, remove existing
cabinets and provide new as shown in detail 7/A2.01.
INDEX OF DRAWINGS:D1.01 DEMOLITION PLANS
A1.01 FLOOR PLAN & REFLECTED CEILING PLANA2.01 FINISH PLAN & INTERIOR ELEVATIONSA3.01 MILLWORK DETAILS
M1.01 FLOOR PLAN AND REFLECTED CEILING PLANM2.01 HVAC SPECIFICATIONS
P1.00 PLUMBING FLOOR PLANSP1.00 SPRINKLER FLOOR PLAN
E0.01 ELECTRICAL NOTES & LEGENDSE1.01 FIRST FLOOR LIGHTING PLANE1.02 FIRST FLOOR POWER PLAN
DD
DUMPST
ER
TRANSF
.
UPUP
DN
UP
UP
REMOVE EXISTING WINDOW & PORTION OF WALL
REMOVE EXISTING STOREFRONT SYSTEM & PORTION OF WALL. SALAVAGE & REINSTALL EXISTING DOOR WHERE POSSIBLE (TYP.)
BASE BID: EXISTING CASEWORK TO REMAIN. AT ALTERNATE NO. THREE (3) REMOVE EXISTING CASEWORK
REMOVE EXISTING STOREFRONT SYSTEM & PORTION OF WALL. SALVAGE & REINSTALL EXISTING DOOR AT OPENING 102
REMOVE EXISTING CARPETING
REMOVE PORTION OF WALL FOR INSTALLATION OF NEW DOOR
REMOVE EXISTING CARPETING
REMOVE EXISTING STOREFRONT SYSTEM & PORTION OF WALL.
SALAVAGE & REINSTALL EXISTING DOOR WHERE POSSIBLE (TYP.)
REMOVE WALL
REMOVE OPERABLE PARTITION
REMOVE DRINKING FOUNTAIN
REMOVE WALLS
REMOVE PORTION OF EXISTING CARPETING
REMOVE EXISTING TILE
TEMPORARY PARTITIONS (SHOWN w/ GREY FILL)
WORK OUTSIDE OF TEMPORARY PARTITIONS TO BE COMPLETED w/ OWNER'S SCHEDULE
MAINTAIN MIN. ADA CLEARANCE
A1.01
J2
REMOVE EXISTING CARPET TILE AS REQUIRED TO COMPLETE
CONSTRUCTION. STORE AND PROTECT TILE FOR OWNER TO
REINSTALL
REWORK EXISTING GRID, TILES, & FIXTURES WHERE POSSIBLE
REWORK EXISTING FIXTURES IN EXISTING GRID THIS ROOM
REWORK/RESUSE EXISTING GRID & TILES WHERE POSSIBLE
REWORK/RESUSE EXISTING GRID & TILES WHERE POSSIBLE
REMOVE EXISTING GWB SOFFITS
REMOVE EXISTING GWB SOFFITS
REMOVE PORTION OF EXISTING ACT, REWORK GRID & FIXTURES
REMOVE OPERABLE PARTITION TRACK, PATCH GWB AS REQUIRED
EXISTING CAN LIGHTS AT SOFFIT, TO REMAIN
KEY PLAN:
AREA OF WORK
REMOVE EXISTING TRACK FOR OPERABLE PARTITION (12'-0" AFF), FULL LENGTH (+/- 39'-0" LF). PATCH SOFFIT, REPAINT.
AREA MAPAREA MAPAREA MAPAREA MAP VICINITY MAPVICINITY MAPVICINITY MAPVICINITY MAP
DODIE ENRICHMENT CENTER
MAIN
ST.
ASSEMBLY ST.
WHALEY.
HEYWARD
DODIE ENRICHMENT CENTER
PROJECT NO. SHEET NO.
# REVISIONDATE
PHASE:
Thes
e dr
awin
gs a
re th
e pr
oper
ty o
f Wat
son
Tate
Sav
ory,
Inc.
and
may
not
be
used
in w
hole
or i
n pa
rt w
ithou
t writ
ten
cons
ent o
f the
arc
hite
cts
and
any
infri
ngem
ent i
s su
bjec
t to
lega
l act
ion.
ISSUE DATE
C:\
Use
rs\g
bell\
Doc
umen
ts\1
627-
US
C-D
odie
Nut
ritio
n_A
17_
gbel
l.rvt
3/13
/201
7 3:
24:1
4 P
M
D1.011627
DEMOLITIONPLANS
RE-
BID
: DO
DIE
AN
DER
SO
N A
CA
DEM
IC E
NR
ICH
MEN
TC
ENTE
R N
UTR
ITIO
N S
TATI
ON
CONSTRUCTION DOCUMENTS
MARCH 20, 2017 1/4" = 1'-0"D1.01
1 DEMOLITION PLAN - FIRST FLOOR 1/4" = 1'-0"D1.01
2 DEMOLITION REFLECTED CEILING PLAN - FIRST FLOOR
DD
DUMPST
ER
TRANSF
.
UPUP
DN
UP
UP
A2.01 1
A2.01 4
A2.017
OFFICE
105
STOR.
105A
SEMINAR
104
SEMINAR
107
OFFICE
106
MENS
111
WOMENS
112
DINING RM
113NUTRITION STATION
103
NEW WATER COOLER w/ BOTTLE FILLING STATION
SOLID SURFACE COUNTERTOP w/ BYPASS DOOR
DOUBLE DOOR REFRIGERATED BEVERAGE DISPLAY CASE, OWNER
FURNISHED, OWNER INSTALLED
COUNTERTOP w/ BASE CABINETS, STORAGE BELOW
SINK
COUNTERTOP w/ BASE & DISPLAY WALL CABINETS -STORAGE ABOVE & BELOW
14" DEEP SHELVING, BY OWNER
JANITOR
111A
CORRIDOR
H102
105A
106
102
REF
NEW DOOR & SIDELIGHT
2
6
D300-a
D300-a
D300-a
D300-a
A3-S00-a
A300-a
A3-S00-a
A3-S00-a
A3-S00-a
108B
A3-S00-a
6' - 6" 9' - 4"
A3-S00-a
3' -
4"
1' -
10"
3' -
1"
4' -
5 1
/8"
4' -
6"
3' -
5 3
/4"
13' -
3"
EQ. EQ.
103
HINGED COUNTERTOP
A2.01
5
A3.01
7
D300-a
D300-a ALIGN
ALIGN
A3-S00-a
D3-S00-a
D300-aD3
00-a
8' - 0 5/8" 1' - 0 5/8"
11 3
/4"
NEW MINI BLINDS TO MATCH EXISTING
A3.01
9
A1.01
J2
AT BASE BID: EXISTING CASEWORK TO REMAIN.THIS CASEWORK PROVIDED BY ALTERNATE NO. THREE (3)
ACT112' - 0" A.F.F.
ACT112' - 8" A.F.F.
ACT112' - 8" A.F.F.
GWB112' - 0" A.F.F.
ACT110' - 5" A.F.F.
ACT110' - 5" A.F.F.
ACT110' - 5" A.F.F.
GWB19' - 0" A.F.F.
ACT110' - 5" A.F.F.
GWB19' - 0" A.F.F.
NEW GWB SOFFIT
NEW GWB SOFFIT, SHOWN HATCHED (TYP.)
NEW ACT, REWORK EXISTING GRID
NEW ACT, REWORK EXISTING GRID AS REQUIRED
NEW ACT, REWORK EXISTING GRID AS REQUIRED
ROLLING COUNTER SHUTTER
SEE ELECTRICAL FOR EXISTING LIGHTS REMOVED IN SOFFIT,
PATCH SOFFIT, REPAINT
REMOVE EXISTING TRACK FOR OPERABLE WALL (FULL LENGTH),
PATCH SOFFIT, REPAINT
EXISTING LIGHT FIXTURES, TO REMAIN
GWB110' - 3" A.F.F.
PARTITION TYPE LEGEND:
CATEGORYA-E METAL STUD WALLS
TYPESEE SCHEDULE THIS SHEET
FIRE RATINGSEE SCHEDULE THIS SHEET
INSULATIONSEE DESCRIPTION THIS SHEET
20 = 20 MIN30 = 30 MIN45 = 45 MIN
01 = 1 HOUR02 = 2 HOUR03 = 3 HOUR
HEIGHT CONDITION CODESEE DESCRIPTION THIS SHEET
A3-S01-a
4 7/8"
5/8" GWB
PLAN
SILL
3 5/8" MTL STUD FRAMING
SOUND ATTEN BLANKET, WHERE SCHEDULED
1/2" SEALANT (BOTH SIDES), TYP.
EXISTING CONCRETE SLAB-ON-GRADE
3 5/8" MTL STUD FRAMING
5/8" GWB
SOUND ATTEN BLANKET, WHERE SCHEDULED
4 1/4"
5/8" GWB
PLAN
SILL
3 5/8" MTL STUD FRAMING
SOUND ATTEN BLANKET, WHERE SCHEDULED
1/2" SEALANT, TYP.
EXISTING CONCRETE SLAB-ON-GRADE
3 5/8" MTL STUD FRAMING
5/8" GWB
SOUND ATTEN BLANKET, WHERE SCHEDULED
KEY PLAN:
AREA OF WORK
REMOVE EXISTING TRACK FOR OPERABLE PARTITION (12'-0" AFF), FULL LENGTH (+/- 39'-0" LF). PATCH SOFFIT, REPAINT.
10' -
0"
5' - 8"
2"2'
- 8
"2"
6' -
10"
2"
2" 2' - 2" 2" 2"
SCHED DOOR
HOLLOW METAL (MATCH EXISTING, V.I.F.)
F02
GLAZING, MATCH EXISTING
FLUSH
P01
SC
HED
ULE
D H
EIG
HT
WIDTH
SCHD
DOOR TYPE ELEVATIONS:
HOLLOW METAL
F01
2"S
CH
ED H
EIG
HT
2"
WIDTH
SCHED 2"
5/8" GWB
MTL STUD FRAMING
SCHED SOUND ATTEN BLANKET
MTL STUD HEADER
1/4" SEALANT& BACKER ROD (BOTH SIDES) TYP.
SCHED HM FRAME
SCHED WD DOOR
SEE PLAN
SCHED PARTITION
1/2" 1/2"
SCHED SOUND ATTEN BLANKET
TRANSOM AT 106 (SIM.)
5/8" GWB
MTL STUD FRAMING
SCHED SOUND ATTEN BLANKET
1/4" SEALANT& BACKER ROD (BOTH SIDES) TYP.
SCHED HM FRAME
SCHED WD DOOR
SEE PLAN
SCHED PARTITION
FRAME ANCHOR
HARDWOOD DOOR STOP
WD BLOCKING
1 3/4" CUSTOM WD DOOR
COUNTERTOP ABOVE
STAINED WD VENEER PANEL
1/2" STAINLESS STL FIN END PANEL
STAINED WD VENEER PANEL
HARDWOOD DOOR FRAME
PLAM FINISH
PROJECT NO. SHEET NO.
# REVISIONDATE
PHASE:
Thes
e dr
awin
gs a
re th
e pr
oper
ty o
f Wat
son
Tate
Sav
ory,
Inc.
and
may
not
be
used
in w
hole
or i
n pa
rt w
ithou
t writ
ten
cons
ent o
f the
arc
hite
cts
and
any
infri
ngem
ent i
s su
bjec
t to
lega
l act
ion.
ISSUE DATE
C:\
Use
rs\g
bell\
Doc
umen
ts\1
627-
US
C-D
odie
Nut
ritio
n_A
17_
gbel
l.rvt
3/13
/201
7 12
:44:
45 P
M
A1.011627
FLOOR PLAN &REFLECTED
CEILING PLAN
RE-
BID
: DO
DIE
AN
DER
SO
N A
CA
DEM
IC E
NR
ICH
MEN
TC
ENTE
R N
UTR
ITIO
N S
TATI
ON
CONSTRUCTION DOCUMENTS
MARCH 20, 2017 1/4" = 1'-0"A1.01
2 FIRST FLOOR PLAN 1/4" = 1'-0"A1.01
1 REFLECTED CEILING PLAN - FIRST FLOOR
DOOR SCHEDULE
MARK
DIMENSIONS
RATING
PANEL FRAME DETAILS
HDWR SET REMARKSWIDTH HEIGHT THICKNESS TYPE MATL FINISH TYPE MATL FINISH HEAD JAMB
102 3' - 0" 7' - 0" 1 3/4" -- P01 WD ST F01 HM PT H1 J1 1
103 3' - 0" 3' - 5 1/4" 1 3/4" -- P01 WD ST --- HM PT --- J2 2 CUSTOM WD BYPASS DOOR
105A 3' - 0" 7' - 0" 1 3/4" -- P01 WD ST F01 HM PT H1 J1 3
106 3' - 0" 7' - 0" 1 3/4" -- P01 WD ST F02 HM PT H1 (SIM) J1 EXISTING
108B 3' - 0" 7' - 0" 1 3/4" -- P01 WD ST F01 HM PT H1 J1 4
FINISH SCHEDULEROOM FINISHES NORTH WALL EAST WALL SOUTH WALL WEST WALL CEILING
REMARKSNO. NAME FLOOR BASE MATL. FINISH MATL. FINISH MATL. FINISH MATL. FINISH MATL. FINISH
103 NUTRITION STATION CFT CWT GWB PT GWB PT EXISTING EXISTING GWB PT ACT/GWB ---/PT
105 OFFICE CPT2 RB EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING GWB PT EXISTING EXISTING
105A STOR. VCT RB EXISTING EXISTING GWB PT EXISTING EXISTING EXISTING EXISTING ACT ---
106 OFFICE CPT2 RB EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING EXISTING/GWB PT EXISTING EXISTING
113 DINING RM CPT1 RB EXISTING EXISTING EXISTING/GWB PT EXISTING EXISTING EXISTING EXISTING ACT/GWB ---/PT
H102 CORRIDOR EXISTING RB GWB PT --- --- EXISTING EXISTING GWB PT EXISTING EXISTING
a PARTITIONTO EXTEND TO UNDERSIDE OF STRUCTURE ABOVE (FIRE RATED, NON-RATED,AND SOUND BARRIER PARTITION ASSEMBLIES)
b PARTITION METAL STUDS TO EXTEND TO STRUCTURE ABOVE, GYPSUM WALLBOARD ONONE SIDE OF METAL STUD TO EXTEND TO STRUCTURE ABOVE, OPPOSITE SIDE OF METALSTUD GYPSUM WALLBOARD TERMINATES 6" ABOVE HIGHEST ADJACENT CEILING
1. WHERE FIRE TESTS ARE INDICATED IN PARTITION DESCRIPTION, CONFIGURE ANDINSTALL PARTITION PER TESTING AGENCY CRITERIA OR OTHER TESTS APPROVED BYLOCAL CODE OFFICIALS. TESTING AGENCY CRITERIA MAY INCLUDE ADDITIONALCOMPONENTS NOT SPECIFICALLY INDICATED ON THIS SCHEDULE OR REFERENCEDDETAILS.
2. DO NOT SCALE DRAWINGS, WRITTEN DIMENSIONS SHALL ESTABLISH LOCATION OFALL PARTITIONS. LARGER SCALE DRAWINGS HAVE PRIORITY OVER SMALLER SCALEDRAWINGS. CONTRACTOR SHALL NOTIFY THE ARCHITECT OF ANY DISCREPANCIES INTHE DRAWINGS BEFORE PROCEEDING WITH CONSTRUCTION.
3. GYP BD IS 5/8 INCH TYPE X FIRE RATED GYP BD, TYPICAL.
4. GYP BD PARTITION CONTROL JOINTS ARE REQUIRED AT APPROXIMATELY 30'-0" O.C.FOR STRAIGHT AND CONTINUOUS WALLS, AT OPENING LOCATIONS, OR AS NOTEDOTHERWISE ON DRAWINGS. WHERE NOT SPECIFICALLY INDICATED ON THE DRAWINGSSUBMIT CONTRACTOR'S PROPOSED CONTROL JOINT LOCATIONS TO ARCHITECT FORAPPROVAL.
5. DO NOT PLACE MECHANICAL AND/OR ELECTRICAL DEVICES BACK TO BACK IN SOUNDBARRIER PARTITIONS. ALL DEVICES TO BE PLACED IN SEPARATE STUD SPACES WITH 8"O.C. MIN. SEPARATION.
6. DUCT PENETRATIONS THROUGH SOUND BARRIER PARTITIONS TO RECIEVE PERIMETER SOUND SEAL BETWEEN DUCT AND WALL FRAMING ON BOTH SIDES OF GYPSUM
WALLBOARD LAYER MEETING DUCT SURFACES.
7. OUTER LAYER OF ALL INTERIOR GYP. BD. PARTITIONS ADJACENT OR EXPOSED TOHUMID CONDITIONS SHALL BE CONSTRUCTED WITH WATER RESISTANT GYP. BD. OREQUAL AS THE SUBSTRATE. PREPARE SUBSTRATE TO RECEIVE SCHEDULED CERAMICOR STONE TILE, WATER RESISTANT WALL PANELS OR HIGH PERFORMANCE PAINTFINISHES. HUMID SPACES INCLUDE BUT ARE NOT LIMITED TO TOILET ROOM WALLS,KITCHEN WALLS AND WALLS ADJACENT TO WATER FEATURES. USE GLASS-MAT TILEBACKING PANELS AT ALL WALLS IN DIRECT CONTACT WITH WATER, FOR EXAMPLE,SHOWERS, STEAM ROOMS, ETC. U.N.O
8. FINISH ALL EXPOSED GYP BD CONSTRUCTION. ALL GYP BD CONSTRUCTION SHALL BETAPED AND FLOATED. ALL EXPOSED CONSTRUCTION WILL BE SANDED SMOOTH TOREMOVE ALL INDICATION OF THE JOINT WITH A VISUAL INSPECTION AND PREPARED TORECIEVE THE APPROPRRIATE SCHEDULED WALL FINISH. FINISH SHALL BE INACCORDANCE WITH THE ROOM FINISH SCHEDULE AND/OR FINISH LEVELS NOTED INTHE GYPSUM BOARD SPECIFICATION.
9. PARTITIONS ARE DIMENSIONED TO FACE OF GYP BD, FACE OF MASONRY AND TO FACEOF EXISTING CONSTRUCTION. ANY INTERIOR PARTITIONS DIMENSIONED TO FACE OFMETAL STUD ARE NOTED - FOS (FACE OF STUD).
10. PERIMETER DIMENSIONS ARE TO FACE OF WALL BELOW SILL U.O.N.
11. PROVIDE 0.0312" METAL BLOCKING AS SHOWN OR AS REQUIRED FOR ATTACHMENT OFWALL MOUNTED HARDWARE, TOILET ACCESSORIES, CASEWORK, MILLWORK, FINISHCARPENTRY ETC. AS MAY BE REQUIRED FOR THE SECURE ATTACHMENT OF ADJOININGWORK.
12. PROVIDE A 1/4 " WIDE SOFT JOINT AT ALL INTERSECTIONS OF INTERIOR PARTITIONSWITH EXTERIOR WALLS. SEE TYPICAL DETAIL.
S SOUND BARRIER PARTITIONS ARE NOTED AS SUFFIX "S" AT SOUND BARRIERPARTITIONS. PROVIDE SOUND ATTENUATION BLANKET AS INDICATED IN THE TABLEBELOW. FILL VOIDS BETWEEN OVERHEAD TRACK AND STRUCTURE WITH SOUNDATTENUATION BLANKET AND SEAL PERIMETER. REFER TO SPECIFICATIONS FORADDITIONAL INFORMATION AND REQUIREMENTS.
GENERAL PARTITION NOTES:
INSULATION NOTES:
HEIGHT CONDITIONS:
3" = 1'-0"A3PARTITION DETAIL
3" = 1'-0"D3PARTITION DETAIL
3" = 1'-0"H1HEAD DETAIL
3" = 1'-0"J1JAMB DETAIL
1 1/2" = 1'-0"J2JAMB DETAIL
FINISH SCHEDULE NOTES: CPT 1 AND CPT 2 ARE TO BE PROVIDED AND INSTALLED BY OWNER; BASE BY CONTRACTORFINISH SCHEDULE NOTES: CPT 1 AND CPT 2 ARE TO BE PROVIDED AND INSTALLED BY OWNER; BASE BY CONTRACTORFINISH SCHEDULE NOTES: CPT 1 AND CPT 2 ARE TO BE PROVIDED AND INSTALLED BY OWNER; BASE BY CONTRACTORFINISH SCHEDULE NOTES: CPT 1 AND CPT 2 ARE TO BE PROVIDED AND INSTALLED BY OWNER; BASE BY CONTRACTOR
REF
+/- 2" 3' - 0" 1' - 9" 1' - 6" 1' - 0" 2' - 1"
+/- 1" 3' - 0" +/-1" +/-1" 3' - 0" 1' - 5" +/- 1"
EX. UNDERCOUNTER REFRIGERATOR, RELOCATE TO THIS LOCATION. COORD SIZE
SOLID SURFACE COUNTERTOP w/ BACKSPLASH & SIDESPLASH
ADJ
WD VENEER BASE CABINETS w/ ADJUSTABLE SHELVING
WD VENEER WALL CABINETS w/ ADJUSTABLE SHELVING
2
A3.01
ADJ
ADJ
ADJ
RESILIENT BASE
ADJ
ADJ
ADJ
ADJ
3' -
0"
1' -
6"
3' -
0"
4
A3.01
EXISTING GWB PARTITION. REMOVE EXISTING GWB & PATCH AS REQUIRED TO INSTALL CASEWORK & BLOCKING
ADJ
ADJ
WD VENEER FILLER PANEL
BASE BID: NO CASEWORK AT THIS LOCATION; ALTERNATE NO. THREE (3) PROVIDE CASEWORK SHOWN
5
A3.01
108B113
EXISTING TV RELOCATED (REMOVE EXISTING TV ON WALL MOUNT AT THIS LOCATION
WALL GRAPHICS (SHOWN HATCHED), BY OTHERS
5/8" GWB REVEAL, BY FRY REGLET OR EQUAL (TYP.)
5/8" GWB REVEAL, BY FRY REGLET OR EQUAL (TYP.)
5/8" GWB REVEAL
SCHED BASE (MATCH EXISTING)
FULL HEIGHT SOLID SURFACE AT RETURN
ALUM SIGNAGE, BY OTHERS
AWNING, MTL STUD FRAMING w/ PLYWOOD & GWB FINISH
STAINED WD PANELS w/ STAINLESS STL RODS (SIM. TO EXISTING)
NEW 5/8" GWB PARTITIONS (SHOWN w/ HATCH). PATCH EXISTING GWB AS REQUIRED
EQ. EQ. EQ. EQ. EQ. EQ.
2' - 0"2 1/2"2' - 0"
2 1/2"2' - 0"
2 1/2"2' - 0"
2 1/2"2' - 0"
2 1/2"2' - 0"
PLAM FINISH
4" STAINLESS STL BASE
1/2" STAINLESS STL FIN
STAINLESS STL END PANEL
8
A3.011/2" STAINLESS STL FIN END PANEL EA END, SEE DETAIL
102
TV(OFOI)
TV(OFOI)
3' - 0" 7' - 0" 3' - 0" 3' - 0"
3' - 0" 7' - 0" 3' - 0" 3' - 0"
2' -
10"
1
A3.01
3
A3.01
NEW GWB PARTITION, SHOWN HATCH.PATCH/FINISH EXISTING AS REQUIRED
TV (OFOI), PROVIDE WALL BLOCKING FOR SUPPORT. COORD. w/ OWNER. SEE ELECTRICAL FOR POWER & DATA REQUIREMENTS
WD VENEER BASE CABINETS w/ ADJUSTABLE SHELVING
WD VENEER WALL CABINET w/ ADJUSTABLE SHELVING
2' -
10"
1' -
6"
2' -
0"
SOLID SURFACE FRAME w/ SLOPED MTL SHELVING
SCHED DOOR & FRAME
A3.01
6
J2
A1.01
5
A3.01
108B
+/- 1 1/2" 2' - 0" 3' - 0" 3' - 0" 3' - 0" 2' - 0"
+/- 1 1/2"3'
- 0
"6"
5' -
6"
COILING COUNTER SHUTTER
SOLID SURFACE COUNTERTOP w/ BYPASS DOOR.
ROLLING COUNTER SHUTTER. FULL WIDTH OF OPENINGS
GWB SOFFITS
WD VENEER BASE CABINETS w/ SOLID SURFACE COUNTERTOP
SCHED BASE (MATCH EXISTING)
NEW DRINKING FOUNTAIN w/ BOTTLE FILLER
A3.01
6
WD GUIDE AT JAMB
SOLID SURFACE (FULL HEIGHT)7
A3.01
18" DEEP WD VENEER SHELVING
2' - 8"
SOLID SURFACE COUNTERTOP
CUSTOM WD BYPASS DOOR
SCHED BASE (MATCH EXISTING)
WD VENEER FACE BACK PANEL
COILING COUNTER SHUTTER
LIFT UP COUNTERBALANCE HARDWARE
HARDWOOD FRAME
HINGED SOLID SURFACE COUNTERTOP
A2.01 4
A2.017
2
6
SEMINAR
104
SEMINAR
107
WOMENS
112
JANITOR
111A
MENS
111
CORRIDOR
H102
VCT1 CPT2
CPT2
CT2
CPT1
OFFICE
106
OFFICE
105
STOR.
105A
EXISTING FLOORING TO REMAIN
EXISTING CARPETING TO REMAIN
PROTECT EXISTING CARPETING DURING CONSTRUCTION, REMOVE TILES AS NECESSARY AND PROTECT AND STORE FOR REINSTALL AT COMPLETION OF CONSTRUCTION. OWNER WILL PROVIDE ADDITIONAL TILES FOR THE CONTRACTOR TO INSTALL WHERE NEEDED DUE TO REMOVAL OF EXISTING WALLS
EXISTING TILE, TO REMAIN
EXISTING TILE, TO REMAIN
EXIS
TIN
G T
ILE
NEW
TIL
E
NEW TILE PROVIDED BY OWNER, INSTALLED BY CONTRACTOR 12 x 24. (CT-2)
A2.01
5
ACCENT TILE PROVIDED BY OWNER, INSTALLED BY CONTRACTOR (SHOWN GREY) - CT-1
EXISTING GARNET CARPET BORDER TO REMAIN
SCHLUTER RENO-U TRANSITION STRIP,
TYP. AT VCT
SCHLUTER RENO-TK TRANSITION STRIP, TYP. AT CARPET
A1.01
J2
2 1/2" 4' - 3 3/8" 2 1/2"
STAINED WD VENEER PANELS w/ STAINLESS STL EXPOSED FASTENERS (SIM, TO EXISTING)
4" STAINLESS STL BASE
SOLID SURFACE COUNTERTOP
GWB SOFFIT
CUSTOM WD BYPASS DOOR
1/2" STAINLESS STL FIN END PANEL, SEE DETAIL
3' -
6"
9' -
0"
COILING COUNTER SHUTTER
J2
A1.01
PROJECT NO. SHEET NO.
# REVISIONDATE
PHASE:
Thes
e dr
awin
gs a
re th
e pr
oper
ty o
f Wat
son
Tate
Sav
ory,
Inc.
and
may
not
be
used
in w
hole
or i
n pa
rt w
ithou
t writ
ten
cons
ent o
f the
arc
hite
cts
and
any
infri
ngem
ent i
s su
bjec
t to
lega
l act
ion.
ISSUE DATE
C:\
Use
rs\g
bell\
Doc
umen
ts\1
627-
US
C-D
odie
Nut
ritio
n_A
17_
gbel
l.rvt
3/13
/201
7 12
:44:
47 P
M
A2.011627
FINISH PLAN &INTERIOR
ELEVATIONS
RE-
BID
: DO
DIE
AN
DER
SO
N A
CA
DEM
IC E
NR
ICH
MEN
TC
ENTE
R N
UTR
ITIO
N S
TATI
ON
CONSTRUCTION DOCUMENTS
MARCH 20, 2017
3/8" = 1'-0"A2.01
7 WEST ELEVATION - OFFICE 106
3/8" = 1'-0"A2.01
1 EAST ELEVATION - DINING RM 113
3/8" = 1'-0"A2.01
4 EAST ELEVATION - NUTRITION STATION 103
3/8" = 1'-0"A2.01
2 WEST ELEVATION - NUTRITION STATION 103
3/8" = 1'-0"A2.01
6 NORTH ELEVATION - NUTRITION STATION 103
1/4" = 1'-0"A2.01
3 FINISH PLAN - FIRST FLOOR
3/8" = 1'-0"A2.01
5 SOUTH ELEVATION
BASE BID" DO NOT PROVIDE WALL CABINETS AT THIS LOCATION; ALTERNATE NO. TWO (2): PROVIDE WALL CABINETS AS SHOWN
3' -
0"
1' -
8"
2' -
10"
2' - 0"
4"1' - 8"
1 1/
2"1/
2"6"
1' -
10"
4"
EX. CONC SLAB
SCHED BASESCHED FLOOR FINISH
WD VENEER BASE CABINET
SOLID SURFACE COUNTERTOP & BACKSPLASH
WD VENEER ADJUSTABLE SHELVES w/ HARDWOOD EDGE, TYP.
WD VENEER WALL CABINET
WD VENEER ADJUSTABLE SHELVES w/ HARDWOOD EDGE, TYP.
PULL
PULL
ADJUSTABLE SHELF INSERTS
1/4" PLYWOOD BACKING PANEL
ADJUSTABLE SHELF INSERT
PULL
1/4" PLYWOOD BACKING PANEL
WD SHIM
WD BLOCKING
HARDWOOD EDGE AT DOORS, COUNTERTOP & BACKSPLASH, TYP.
SCHED PARTITION, SEE PLAN
ALIGN
1/2" RADIUS
1' - 0"
2' -
0"
1' - 0"
WD VENEER WALL CABINET
WD VENEER ADJUSTABLE SHELVES w/ HARDWOOD EDGE, TYP.
1/4" PLYWOOD BACKING PANEL
ADJUSTABLE SHELF INSERT
DOOR PULL
HARDWOOD EDGE AT DOORS, COUNTERTOP & BACKSPLASH, TYP.
SCHED PARTITION, SEE PLAN
1' -
6"
2' -
10"
2' - 0"
4"1' - 8"
1 1/
2"1/
2"6"
1' -
10"
4"
EX. CONC SLAB
1/2" UNDERCUTSCHED FLOOR FINISH
WD VENEER BASE CABINET
SOLID SURFACE COUNTERTOP
PULL
ATTACH TOE KICK TO MATCH CABINET
1' - 0"
1/2"
FAUCET & SINK, SEE PLUMBING
INSULATE ALL EXPOSEDPIPES, TYP.
ADA CLEARANCE AT SINK
SCHED BASE
1/4" SOLID SURFACE BACKSPLASH (FULL HEIGHT)
3' -
0"
11 1/4"
4"7 1/4"
1 1/
2"1/
2"6"
1/4"
7 3/
4"1/
4"7
3/4"
1/4"
7 3/
4"4"
EX. CONC SLAB
SCHED BASE
SCHED FLOOR FINISH
WD VENEER BASE CABINET
SOLID SURFACE COUNTERTOP & BACKSPLASH
PULL
WD VENEER DRAWERS w/ HARDWOOD EDGE, TYP.
1/4" PLYWOOD BACKING PANEL
WD SHIM
WD BLOCKING
EXISTING COLUMN
1/2" RADIUS
1 5/8" MTL STUD FRAMING
5/8" GWB
WD BLOCKING
Level 10' - 0"
Level 29' - 0"
2 1/2" MTL STUD FRAMING
5/8" GWB AT SOFFIT
FULL WIDTH ROLLING COUNTER SHUTTER
SCHED ACT CEILING
1/4" SOLID SURFACE(FULL HEIGHT AT JAMB)
SCHED TILE FLOOR
SCHED TILE BASE
ALUM SIGNAGE, BY OTHERS
5/8" GWB
11 3/8"1' - 3"7 1/8"2' - 0"
2 3/
4"4"
5' -
6"
3' -
6"
TRIMMED 2x8 WD STUDS
EX. CONC SLAB
WD VENEER BASE CABINET
SOLID SURFACE COUNTERTOP & BACKSPLASH
WD VENEER ADJUSTABLE SHELVES w/ HARDWOOD EDGE, TYP.
PULL
ADJUSTABLE SHELF INSERTS
1/4" PLYWOOD BACKING PANEL
1/2" RADIUS
2x4 WD STUD FRAMING w/ 2x WD BLOCKING FOR CABINETS
SCHED CARPET
4" STAINLESS STL BASE
1' - 6 1/2"1' - 6"
1"2'
- 6
3/8
"10
5/8
"
2' - 6"
STAINED WD PANELS. MATCH EXISTING
EXPOSED STAINLESS STL FASTENERS, MATCH EXISTING
PLAM FINISH
2x8 WD BLOCKING IN WALL TO SUPPORT SHUTTER
2x WD BLOCKING 6" MTL STUD FRAMING
COORD. w/ MFGR 4"
WD GUIDE AT JAMB
SCHED LIGHT FIXTURE,SEE ELECTRICAL
SCHED LIGHT FIXTURE, SEE ELECTRICAL
1/2" PLYWOOD
NUTRITION STATION
103
PLAM FINISH
STAINLESS STL FIN, BEYOND
1' - 0 3/8"
2' -
7 1
/2"
21°
2' -
7 3
/4"
1/2"
5/8"
END PANEL DETAIL
8
A3.01
9' -
0"
DELEGATED DESIGN COLD-FORMED MTL STUD HEADER,PROVIDED BY CFMF MANUFACTURER
PROVIDE SLOTTED CONNECTION, EXTEND TO STRUCTURE ABOVE
11 1
/4"
1 1/2"
1/2" STAINLESS STEEL PANEL NO. 4 FINISH WITH COUNTERSUNK FASTENERS ONLY WHERE REQUIRED, FASTENERS SHALL BE FULLY CONCEALED TO THE GREATEST EXTENT POSSIBLE
2' -
0"
1' -
6"
2' -
10"
2' - 0"
4"1' - 8"
1 1/
2"1/
2"6"
1' -
10"
4"
EX. CONC SLAB
SCHED BASESCHED FLOOR FINISH
WD VENEER BASE CABINET
SOLID SURFACE COUNTERTOP
WD VENEER ADJUSTABLE SHELVES w/ HARDWOOD EDGE, TYP.
SLOPED 1/8" MTL SHELVING w/ 1" BENT LIP
PULL
PULL
ADJUSTABLE SHELF INSERTS
1/2" SOLID SURFACE BACKING
1" SOLID SURFACE FRAME
WD BLOCKING
1/4" PLYWOOD BACKING PANEL
WD SHIM
WD BLOCKING
1/4" SOLID SURFACE BACKSPLASH (FULL HEIGHT)
1/2" RADIUS
1"
1' - 0"
1' - 3" 1' - 10"
1' -
5"
6"
SCHED ACT CEILING
6" MTL STUD FRAMING
5/8" GWB SOFFIT
FULL WIDTH ROLLING COUNTER SHUTTER
WD GUIDE RAIL w/ RECESSED 2x8 WD BLOCKING IN WALLS (PATCH EXISTING WALLS AS NEEDED)
9' - 0" AFF
5/8" 1 1/2"
1' -
11
1/4"
3 5/8" MTL STUD FRAMING
SOLID SURFACE (FULL HEIGHT ABOVE COUNTER)
SCHED SOUND ATTEN BLANKET
5/8" GWB
5/8" GWB REVEAL
3" 1" 1/2" 1" 3"
WD BLOCKING
3/4" PLYWOOD w/ PLAM FINISH
STAINED WD PANELS w/ STAINLESS STL EXPOSED FASTENERS
1/2" STAINLESS STL FIN ANGLE,BOLT TO WD BLOCKING
5/8" GWB
3 5/8" MTL STUD FRAMING
BRAKE MTL WRAP (MATCH WALL PAINT COLOR)
2x WD BLOCKING
EXISTING GLAZING
CONT. CLEAR SEALANT (BOTH SIDES)
PROJECT NO. SHEET NO.
# REVISIONDATE
PHASE:
Thes
e dr
awin
gs a
re th
e pr
oper
ty o
f Wat
son
Tate
Sav
ory,
Inc.
and
may
not
be
used
in w
hole
or i
n pa
rt w
ithou
t writ
ten
cons
ent o
f the
arc
hite
cts
and
any
infri
ngem
ent i
s su
bjec
t to
lega
l act
ion.
ISSUE DATE
C:\
Use
rs\g
bell\
Doc
umen
ts\1
627-
US
C-D
odie
Nut
ritio
n_A
17_
gbel
l.rvt
3/13
/201
7 12
:44:
47 P
M
A3.011627
MILLWORKDETAILS
RE-
BID
: DO
DIE
AN
DER
SO
N A
CA
DEM
IC E
NR
ICH
MEN
TC
ENTE
R N
UTR
ITIO
N S
TATI
ON
CONSTRUCTION DOCUMENTS
MARCH 20, 2017
1 1/2" = 1'-0"A3.01
2 MILLWORK SECTION 1 1/2" = 1'-0"A3.01
1 MILLWORK SECTION
1 1/2" = 1'-0"A3.01
4 MILLWORK SECTION
1 1/2" = 1'-0"A3.01
5 MILLWORK SECTION 1 1/2" = 1'-0"A3.01
3 MILLWORK SECTION
1 1/2" = 1'-0"A3.01
6 HEAD DETAIL 1 1/2" = 1'-0"A3.01
7 JAMB DETAIL 3" = 1'-0"A3.01
8 DETAIL 1 1/2" = 1'-0"A3.01
9 PLAN DETAIL
ELECTRICAL SYMBOL LEGENDELECTRICAL SYMBOL LEGENDELECTRICAL SYMBOL LEGENDELECTRICAL SYMBOL LEGEND
DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTIONSYMBOLSYMBOLSYMBOLSYMBOL SYMBOLSYMBOLSYMBOLSYMBOL
SINGLE RECEPTACLE (WALL MOUNTED @ 18"AFF)
DUPLEX RECEPTACLE (WALL MOUNTED @ 18"AFF)
PHONE OR DATA OUTLET (WALL MOUNTED @ 18"AFF)
MOTOR CONNECTION (AS NOTED)
JJJJ JUNCTION BOX (WALL MTD)
JJJJ JUNCTION BOX (FLOOR MOUNTED)
DUPLEX RECEPTACLE (FLOOR MOUNTED)
QUADPLEX RECEPTACLE (FLOOR MOUNTED)
DISCONNECT SWITCH, (REFER TO EQUIPMENT
CONNECTION SCHEDULE)
DISCONNECT SWITCH, (NON PROTECTED)
DUPLEX RECEPTACLE (CEILING MOUNTED)
QUADPLEX RECEPTACLE (CEILING MOUNTED)
R SECURITY CARD READER
A FIRE ALARM AUDIBLE DEVICE (WALL MOUNTED @
7'-6" AFF)
AIUADDRESSABLE INTERFACE UNIT (MONITOR OR
CONTROL TYPE)
DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION
FSD FIRE / SMOKE DAMPER
PUSH BUTTON CONTROL
H HEAT DETECTOR (CEILING MOUNTED)
CABLE TRAY
DUPLEX RECEPTACLE (@ 6" ABOVE COUNTER)
DUPLEX RECEPTACLE (GFI TYPE @ 18"AFF)
QUAD RECEPTACLE (WALL MOUNTED @ 18"AFF)
JJJJ JUNCTION BOX (CEILING)
PHONE OR DATA OUTLET (MTD ABOVE COUNTER)
V FIRE ALARM VISUAL DEVICE (WALL MOUNTED @ 7'-6"
AFF)
A/V FIRE ALARM SPEAKER/VISUAL DEVICE (WALL MOUNTED @
7'-6" AFF)
FIRE ALARM AUDIBLE DEVICE (CEILING MOUNTED)
FIRE ALARM VISUAL DEVICE (CEILING MOUNTED)
FIRE ALARM SPEAKER/VISUAL DEVICE (CEILING MOUNTED)
A
V
A/V
SSSS SMOKE DETECTOR (CEILING MOUNTED)
FIRE ALARM PULL STATION (WALL MOUNTED @ 48"
AFF TOP OF BOX)F
MULTI-PHASE RECEPTACLE (AS NOTED ON PLAN)
CONDUIT CALLOUT (# INDICATES DIAMETER)#" C.
K SECURITY KEY PAD
PANELBOARD (SURFACE MOUNTED)
PANELBOARD (RECESS MOUNTED)
PIV PRESSURE INDICATING VALVE
#
LIGHT SWITCH, SINGLE POLE
LIGHT SWITCH, 3 WAY TYPE
LIGHT SWITCH, DIGITALLY TIMED (0-30 MINUTES)
LIGHT SWITCH, DIMMER TYPE
LOWER CASE SUBSCRIPT INDICATES SWITCH-LEGa
T
D
3
OS OCCUPANCY SENSOR (CEILING MOUNTED)
OS OCCUPANCY SENSOR (WALL MOUNTED)
KEY NOTE CALLOUT (REFER TO KEY NOTES ON SHEET)#
CONTROL PANEL (SURFACE MOUNTED)
CONTROL PANEL (RECESS MOUNTED)
MMOTOR RATED SNAP SWITCH IN NEMA 1 ENCLOSURE
MULTI-LEVEL SWITCHING CONFIGURATION
DUPLEX RECEPTACLE (GFI TYPE @ 6" ABOVE
COUNTER)
GTD GENERATOR TRANSFER DEVICE
EXISTING
TRANSFORMER
EXISTING
PANEL 'H1'
EXISTING
PANEL 'L1'
FIRST FLOOR ELECTRICAL ROOMFIRST FLOOR ELECTRICAL ROOMFIRST FLOOR ELECTRICAL ROOMFIRST FLOOR ELECTRICAL ROOM
FIRST FLOORFIRST FLOORFIRST FLOORFIRST FLOOR
PANEL
'L1A'
4-#8, #10(G)
IN 1"C
PROVIDE NEW 50-AMP BREAKER
TO FEED NEW PANEL "L1A".
RELOCATE 3 20-AMP, 1 POLE
CIRCUITS FROM "L1" TO "L1A"
TO MAKE FROM FOR THIS NEW
BREAKER.
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
WT21603WT21603WT21603
No. 26181
R
A
NILORACHT
UO
S
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.H
ERA
No. 26181
R
A
NILORACHT
UO
S
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.H
ERA
No. 26181
R
A
NILORACHT
UO
S
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.H
ERA
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHT
UO
S
CE
RT
IF
I CATE
OF AUTHOR
I ZA
TIO
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHT
UO
S
CE
RT
IF
I CATE
OF AUTHOR
I ZA
TIO
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHT
UO
S
CE
RT
IF
I CATE
OF AUTHOR
I ZA
TIO
N
PROJECT NO. SHEET NO.
# REVISIONDATE
PHASE:
Thes
e dr
awin
gs a
re th
e pr
oper
ty o
f Wat
son
Tate
Sav
ory,
Inc.
and
may
not
be
used
in w
hole
or i
n pa
rt w
ithou
t writ
ten
cons
ent o
f the
arc
hite
cts
and
any
infri
ngem
ent i
s su
bjec
t to
lega
l act
ion.
ISSUE DATE
3-20-17
C:\
Use
rs\L
uke\
Doc
umen
ts\W
T216
03_
DO
DIE
NU
TRIT
ION
_C
ENTR
AL_
2017
_Ste
phen
.rvt
3/13
/201
7 10
:50:
29 A
M
E0.01WT21603
ELECTRICALNOTES &LEGENDS
RE-
BID
: DO
DIE
AN
DER
SO
N A
CA
DEM
IC E
NR
ICH
MEN
TC
ENTE
R N
UTR
ITIO
N S
TATI
ON
SCHEMATIC DESIGN
3/20/17
GENERAL EXISTING CONDITION NOTESGENERAL EXISTING CONDITION NOTESGENERAL EXISTING CONDITION NOTESGENERAL EXISTING CONDITION NOTES1 AREAS OF WORK EXIST FOR THIS PROJECT WHICH ARE NOT ACCESSIBLE OR HAVE LIMITED ACCESS DURING
DESIGN. AS SUCH CONTRACTOR SHALL VERIFY ALL UTILITIES IN AREA OF WORK BEFORE DEMOLITION OF ANY
SERVICE. ANY ELECTRICAL COMPONENTS NOT SHOWN SHALL BE IDENTIFIED AND THE ARCHITECT AND
ENGINEER SHALL BE NOTIFIED AS SOON AS POSSIBLE. NO ELECTRICAL REWORK SHALL BE COMMENCED
WITHOUT COORDINATION OF BOTH ARCHITECT AND ENGINEER.
2 IN AREAS WHERE THE EXISTING CEILINGS ARE NOT SLATED TO BE REMOVED, THE CONTRACTOR SHALL WORK
THRU THE EXISTING CEILINGS (SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR AREA OF WORK). THE
CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING ANY DAMAGED TILE OR GRID THAT IS A RESULT OF
THEIR WORK.
3 REFER TO ARCHITECTURAL PLANS FOR PHASING OF CONSTRUCTION.
4 THE CONTRACTOR SHALL BE RESPONSIBLE FOR INSTALLING A FIRESTOP SYSTEM IN ALL PENETRATIONS OF
FIRE-RATED WALLS CREATED BY THE REMOVAL OF EXISTING ELECTRICAL CONDUIT OR CABLES, AS WELL AS
THOSE CREATED BY NEWLY INSTALLED CONDUITS AND SLEEVES.
5 WHERE INSTALLATION REQUIRES CUTTING OR DRILLING OF THE EXISTING FLOOR SLAB, THE CONTRACTOR
SHALL X-RAY THE EXISTING SLAB PRIOR TO WORK TO ENSURE THAT NO EXISTING UTILITIES OR STRUCTURAL
ELEMENTS IN THE SLAB WILL BE COMPROMISED BY THE WORK. NOTIFY THE ARCHITECT/ENGINEER OF ANY
CONFLICTS THAT WILL REQUIRE RELOCATING THE PROPOSED SLAB WORK. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE REPAIR OF ANY DAMAGED UTILITIES OR STRUCTURAL ELEMENTS CAUSED BY THE SLAB
DEMOLITION.
6 SUPPORT ALL EXISTING CONDUITS AND JUNCTION BOXES ABOVE THE CEILING PER NEC IN THE
CONSTRUCTION AREA.
7 REMOVE ALL ABANDONED CONDUIT, WIRE, AND COMMUNICATION CABLES ABOVE THE CEILING IN THE
CONSTRUCTION AREA.
8 PROVIDE JUNCTION BOX COVER PLATES ON ALL EXISTING JUNCTION BOXES ABOVE THE CEILING IN THE
CONSTRUCTION AREA.
9 SUPPORT ALL EXISTING COMMUNICATION CABLES ABOVE THE CEILING IN THE CONSTRUCTION AREA
10 WHERE INFORMATION SHOWN ON THESE DRAWINGS CONFLICTS WITH VERIFIED FIELD CONDITIONS, IT SHALL BE
BROUGHT TO THE ATTENTION OF THE ENGINEER
GENERAL "ELECTRICAL" NOTESGENERAL "ELECTRICAL" NOTESGENERAL "ELECTRICAL" NOTESGENERAL "ELECTRICAL" NOTES1 BRANCH CIRCUIT WIRING SHALL BE NO. 12 AWG UNLESS NOTED OTHERWISE. WHERE CONDUCTOR AND
RACEWAY SIZE ARE SHOWN AT HOMERUN, SUCH SIZE SHALL BE USED FOR THE ENTIRE CIRCUIT.
EXCEPTION: FINAL CONNECTION TO DEVICES, IN OUTLET BOXES, IS NOT REQUIRED TO BE LARGER THAN NO.
12 AWG.
2 20A/120V BRANCH CIRCUITS EXCEEDING 100' IN LENGTH FROM PANEL TO FARTHEST DEVICE OR FIXTURE
SHALL USE NO. 10 CONDUCTORS AND 3/4"C.
3 PRIOR TO ROUGH-IN, COORDINATE THE LOCATION AND MOUNTING HEIGHT OF ALL WALL AND CEILING
MOUNTED DEVICES WITH THE ARCHITECTURAL ELEVATIONS, MILLWORK SHOP DRAWINGS, AND EXISTING
CONDITIONS. IN THE EVENT OF A CONFLICT, NOTIFY THE ARCHITECT. MINOR ADJUSTMENTS IN DEVICE
LOCATION, I.E. 5'-0" IN ANY DIRECTION SHALL BE DONE AT NO ADDITIONAL COST TO THE OWNER.
4 PROVIDE FLEXIBLE CONDUIT FOR ALL CONDUITS CROSSING EXPANSION JOINTS. REFER TO ARCHITECTURAL
DRAWINGS FOR LOCATION OF EXPANSION JOINTS.
5 OUTLET BOXES FOR SWITCHES, RECEPTACLES, ETC MOUNTED ON OPPOSITE SIDES OF FIRE RATED PARTITIONS
SHALL NOT BE MOUNTED IN THE SAME WALL CAVITY. SEPARATE WALL PENETRATIONS BY MOUNTING ON
OPPOSITE SIDES OF WALL STUDS OR OTHER VERTICAL STRUCTURAL MEMBER IN THE WALL.
6 RACEWAYS SHALL BE INSTALLED CONCEALED IN NEW WALL CONSTRUCTION ABOVE CEILINGS, BELOW FLOOR,
AND IN OTHER CAVITIES TO THE GREATEST EXTENT POSSIBLE. WHERE EXPOSED RACEWAYS MUST BE USED,
LAYOUT RACEWAYS TO MINIMIZE THE NUMBER OF VERTICAL RUNS.
7 FEEDER CONDUITS, BRANCH CIRCUITS AND CABLE TRAY ROUTING SHALL COMPLY WITH DETAILS ON DRAWINGS
AND SHALL BE COORDINATED WITH THE WORK OF OTHER TRADES BEFORE AND DURING CONSTRUCTION.
8 WHERE LIGHT SWITCH AND ABOVE COUNTER RECEPTACLES ARE INDICATED TO BE MOUNTED ADJACENT TO
EACH OTHER, THE DEVICES SHALL BE MOUNTED AT THE SAME HEIGHT UNDER A COMMON DEVICE PLATE.
9 REFER TO THE ARCHITECTURAL DRAWINGS FOR PROJECT PHASING.
10 THE ARRANGEMENT, GROUPING, AND ROUTING OF BRANCH CIRCUITS SHALL BE PROVIDED AT THE
CONTRACTOR'S DISCRETION IN ACCORDANCE WITH GENERALLY ACCEPTED PRACTICE FOR ELECTRICAL WORK,
THE NATIONAL ELECTRICAL CODE REQUIREMENTS, LOCAL ORDINANCES, AND THE FOLLOWING:
11.1 A COMMON NEUTRAL MAY BE INSTALLED IN A HOMERUN FOR 2 OR 3 BRANCH CIRCUITS ONLY IF A MEANS
TO SIMULTANEOUSLY DISCONNECT ALL UNGROUNDED CONDUCTORS AT THE POINT WHERE THE BRANCH
CIRCUITS ORIGINATE IS PROVIDED PER ARTICLE 210.4(B) OF THE NATIONAL ELECTRICAL CODE.
11.2 MULTIPLE SINGLE-POLE BRANCH CIRCUITS (UP TO 3 HOTS, 3 NEUTRALS, 1 GROUND) RATED FOR 30-AMPS
OR LESS MAY BE PULLED INTO A SINGLE RACEWAY. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SIZING
THE RACEWAYS AND DERATING CONDUCTORS PER NEC ARTICLE 310.15.
11.3 BRANCH CIRCUIT, FEEDER & COMMUNICATION CIRCUITS SHALL BE ROUTED OVERHEAD UNLESS PRIOR
APPROVAL HAS BEEN GRANTED BY THE ARCHITECT AND ENGINEER.
11.4 A GROUND CONDUCTOR SHALL BE PROVIDED IN ALL RACEWAYS UNLESS NOTED OTHERWISE.
12 THE USE OF MC CABLE IS NOT ALLOWED.
13 SEAL ALL EXISTING AND NEW FIRE RATED WALL AND FLOOR PENETRATIONS IN THE CONSTRUCTION AREA
14 SEE THE ARCHITECTURAL DRAWINGS FOR ALL LOCATIONS OF FIRE RATED WALLS.
15 WHEREVER ON THE ELECTRICAL DRAWINGS THE WORD "PROVIDE" IS USED, IT SHALL BE INFERRED TO MEAN
"FURNISH AND INSTALL".
16 WHERE CARD READERS AND / OR DOOR CONTACTS ARE SHOWN ON DRAWINGS, COORDINATE WITH ACCESS
CONTROL AND DOOR HARDWARE SUPPLIER TO ENSURE THAT ALL RACEWAYS AND BOXES FOR POWER,
SIGNALING, AND DATA ARE PROVIDED TO CARD READER LOCATIONS, DOOR FRAME, POWER SUPPLIES, AND
CABLE-TRAY.
GENERAL "POWER" NOTESGENERAL "POWER" NOTESGENERAL "POWER" NOTESGENERAL "POWER" NOTES1 ALL BRANCH CIRCUITS INDICATED ON THESE PLANS TO BE LARGER THAN NO. 12 AWG SHALL BE SIZED AS
INDICATED FOR THE ENTIRE LENGTH OF THE CIRCUIT.
2 WHEN A RECEPTACLE IS INDICATED TO BE MOUNTED ADJACENT TO A COMPUTER/TELEPHONE/ TELEVISION
OUTLET, THE DEVICE(S) SHALL BE MOUNTED WITHIN 6" CENTER-TO-CENTER.
3 STUB-UP (6) 3/4-INCH SPARE CONDUITS FROM EACH FLUSH MOUNTED PANELBOARD TO ABOVE FINISHED
CEILING.
4 PROVIDE AND INSTALL AN ENGRAVED LAMINATED PLASTIC NAMEPLATE ON EACH ITEM OF ELECTRICAL
EQUIPMENT SERVING MECHANICAL EQUIPMENT WHICH MATCH MECHANICAL DESCIPTIONS, TO INDICATE THE
DESIGNATION OF THE UNIT ON THE PLANS & THE BRANCH CIRCUIT SERVING THE EQUIPMENT.
5 PROVIDE NEMA CONFIGURATION RECEPTACLES TO MATCH PLUGS ON EQUIPMENT FURNISHED.
6 WHERE SPEED CONTROLLER IS INDICATED TO BE PROVIDED WITH FANS, IT SHALL BE PROVIDED BY
MECHANICAL CONTRACTOR AND INSTALLED BY ELECTRICAL CONTRACTOR.
7 PROVIDE ENGRAVED FACEPLATES USING 1/8" HIGH BLACK LETTERS ON COVER PLATE OF ALL RECEPTACLES,
SWITCHES & WALL MOUNTED DEVICES INDICATING PANEL AND BRANCH CIRCUIT TO WHICH EACH DEVICE IS
CONNECTED.
GENERAL "SIGNAL" NOTESGENERAL "SIGNAL" NOTESGENERAL "SIGNAL" NOTESGENERAL "SIGNAL" NOTES1 EXTEND A 1" CONDUIT WITH PULL WIRE FROM EACH COMMUNICATIONS OUTLET TO NEAREST CABLE-TRAY OR
THE COMMUNICATION BACKBOARD AND TERMINATE WITH AN INSULATED PROTECTIVE BUSHING. COMMUNICATION
OUTLET BOX SHALL BE 4" SQUARE WITH SINGLE GANG RING.
2 PROVIDE ALL DUCT SMOKE DETECTORS AND ACCESSORIES NECESSARY FOR INTERLOCKING WITH MECHANICAL
EQUIPMENT (AHU'S, SMOKE DAMPERS, ETC). COORDINATE WITH MECHANICAL PLANS FOR LOCATIONS AND
REQUIREMENTS. DETECTORS SHALL BE FURNISHED BY ELECTRICAL CONTRACTOR, INSTALLED BY MECHANICAL
CONTRACTOR, WIRED TO FIRE ALARM SYSTEM BY ELECTRICAL CONTRACTOR, AND TIED TO MECHANICAL
CONTROLS FOR AHU SHUTDOWN BY MECHANICAL CONTRACTOR.
3 OUTLET BOXES SHALL BE EXTRA DEEP. BOX DEPTH SHALL BE WALL THINCKNESS IF POSSIBLE. INDUSTRY
STANDARDS SHALL BE USED IF WALL THICKNESS DEPTH IS NOT POSSIBLE
4 ALL FIRE ALARM CABLE SHALL BE INSTALLED IN METALLIC CONDUIT. COORDINATES WITH FIRE ALARM SYSTEM
MANUFACTURER FOR CABLE ROUTING AND QUANTITIES.
5 CABLE SHALL BE CONCEALED IN ALL FINISHED AREAS AND ROUTED PARALLEL OR PERPENDICULAR TO THE
BUILDING STRUCTURE.
GENERAL "LIGHTING" NOTESGENERAL "LIGHTING" NOTESGENERAL "LIGHTING" NOTESGENERAL "LIGHTING" NOTES1 SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR THE EXACT LOCATION OF ALL CEILING MOUNTED LIGHTING
FIXTURES.
2 LIGHTING FIXTURE CATALOG NUMBERS ARE INDICATIVE OF THE STYLE OF FIXTURE REQUIRED. CONTRACTOR
SHALL PROVIDE FIXTURES WITH THE PROPER TRIM, VOLTAGE AND OPTIONS NECESSARY FOR INSTALLATION.
3 DOUBLE-FACED EXIT FIXTURES SHALL BE OF THE SAME MANUFACTURER & SERIES AS THE SINGLE TYPE
SPECIFIED.
4 ALL EXIT SIGNS SHALL BE CONNECTED TO LOCAL LIFE SAFETY LIGHTING CIRCUIT AHEAD OF ALL SWITCHING.
5 ALL FLUORESCENT FOUR FOOT LIGHT FIXTURES SHALL BE EQUIPPED WITH PROGRAMMABLE START ELECTRONIC
BALLASTS.
6 WHERE INBOARD/OUTBOARD SWITCHING IS INDICATED, OUTBOARD LAMP(S) SHALL BE KEYED FROM ONE
SWITCH AND INBOARD LAMP(S) FROM THE OTHER. THE SWITCH NEAREST THE DOOR SHALL SWITCH THE
OUTBOARD LAMPS.
7 REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING DETAILS OF LIGHT FIXTURE TO ACOUSTICAL CEILING
SYSTEM AND STRUCTURE.
GENERAL "DEMOLITION" NOTESGENERAL "DEMOLITION" NOTESGENERAL "DEMOLITION" NOTESGENERAL "DEMOLITION" NOTES1 ALL ELECTRICAL EQUIPMENT TO BE REMOVED SHALL REMAIN THE PROPERTY OF THE OWNER. THE
CONTRACTOR SHALL NOT DISPOSE OF ANY MATERIALS UNTIL RELEASED BY OWNER'S PROJECT MANAGER.
MATERIALS THAT OWNER'S PROJECT MANAGER CHOOSES TO RETAIN SHALL BE DELIVERED BY THE
CONTRACTOR TO A LOCATION DESIGNATED BY THE PROJECT MANAGER. ALL OTHER MATERIALS SHALL BE
PROPERLY DISPOSED OF BY THE CONTRACTOR.
2 REMOVE ALL EXPOSED ABANDONED COMMUNICATION CABLE FOUND DURING THE CONSTRUCTION PROCESS.
SUPPORT ALL EXISTING REMAINING CABLE PER THE NEC.
3 ELECTRICAL DEVICES NOT SHOWN ON WALLS TO BE DEMOLISHED SHALL BE DEMOLISHED AT NO ADDITIONAL
COST TO OWNER.
4 ELECTRICAL DEVICES NOT SHOWN ON CEILINGS OR WALLS TO REMAIN SHALL REMAIN IN PLACE. PROTECT
FROM DAMAGE DURING CONSTRUCTION
5 ELECTRICAL DEVICES NOT SHOWN ON CEILINGS TO BE REMOVED SHALL BE TEMPORARILY DISCONNECTED AND
REMOVED DURING DEMOLITION AND RE-INSTALLED ON NEW CEILING IN SAME LOCATION.
ABBREVIATIONSABBREVIATIONSABBREVIATIONSABBREVIATIONS
ABRABRABRABR DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTIONAFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
cd CANDELA
EF EXHAUST FAN
FACP FIRE ALARM CONTROL PANEL
GFCI GROUND-FAULT CIRCUIT-INTERRUPTING
GFI GROUND-FAULT INTERRUPTING
IG ISOLATED GROUND
NEC NATIONAL ELECTRIC CODE
SD SMOKE DETECTOR
SPD SURGE PROTECTION DEVICE
WP WEATHERPROOF
ELECTRICAL DRAWING INDEXELECTRICAL DRAWING INDEXELECTRICAL DRAWING INDEXELECTRICAL DRAWING INDEX
#### SHEET NAMESHEET NAMESHEET NAMESHEET NAMEE0.01 ELECTRICAL NOTES & LEGENDS
E1.01 FIRST FLOOR LIGHTING PLAN
E1.02 FIRST FLOOR POWER PLAN
DEMOLITION/RENOVATION NOTATIONDEMOLITION/RENOVATION NOTATIONDEMOLITION/RENOVATION NOTATIONDEMOLITION/RENOVATION NOTATIONIF NO ANNOTATION IS SHOWN ASSUME EXISTING TO REMAIN IN
PLACE FOR SOLID LINES AND DEMOLISH FOR DASHED LINES.
DEVICES AND EQUIPMENT NOT SHOWN SHALL BE ASSUMED TO
BE EXISTING TO REMAIN IN PLACE.
E EXISTING FIXTURE OR DEVICE TO REMAIN IN PLACE. REPLACE
ANY BROKEN DEVICES OR PLATES; COLOR TO MATCH EXISTING.
R EXISTING FIXTURE OR DEVICE TO BE REMOVED BY THE
ELECTRICAL CONTRACTOR. MAINTAIN CONTINUITY OF REMAINING
PORTIONS OF BRANCH CIRCUIT.
RE EXISTING DEVICE TO BE REMOVED BY THE ELECTRICAL
CONTRACTOR. EXISTING CIRCUIT SHALL BE RETAINED. PROVIDE
NEW DEVICE AS SHOWN ON RENOVATION PLANS.
RN RELOCATED FIXTURE (NEW LOCATION).
RR EXISTING FIXTURE TO BE RELOCATED BY THE ELECTRICAL
CONTRACTOR TO NEW LOCATION SHOWN ON RENOVATION PLAN.
SCALE: NOT TO SCALEE0.01
1
PARTIAL POWER SINGLE-LINEPARTIAL POWER SINGLE-LINEPARTIAL POWER SINGLE-LINEPARTIAL POWER SINGLE-LINE
DIAGRAMDIAGRAMDIAGRAMDIAGRAM
* GFCI TYPE BREAKER
NOTES:NOTES:NOTES:NOTES:
TOTAL PER PHASE AMPACITY:TOTAL PER PHASE AMPACITY:TOTAL PER PHASE AMPACITY:TOTAL PER PHASE AMPACITY: 14 4 3 CONNECTED AMPACITY:CONNECTED AMPACITY:CONNECTED AMPACITY:CONNECTED AMPACITY: 7
TOTAL PER PHASE KVA:TOTAL PER PHASE KVA:TOTAL PER PHASE KVA:TOTAL PER PHASE KVA: 1.7 0.5 0.4 CONNECTED KVA:CONNECTED KVA:CONNECTED KVA:CONNECTED KVA: 2.5
-- 23 SPARE 20 1 0.0 0.0 1 20 SPARE 24 --
-- 21 SPARE 20 1 0.0 0.0 1 20 SPARE 22 --
-- 19 SPARE 20 1 0.0 0.0 1 20 SPARE 20 --
-- 17 SPARE 20 1 0.0 0.0 1 20 SPARE 18 --
-- 15 SPARE 20 1 0.0 0.0 1 20 SPARE 16 --
-- 13 SPARE 20 1 0.0 0.0 1 20 SPARE 14 --
-- 11 RELOCATED CIRCUITS FROM PANEL "L1" 20 1 0.0 0.0 1 20 RELOCATED CIRCUITS FROM PANEL "L1" 12 --
1-#12, 1-#12, 1-#12 9 * JBOX - UC DISPOSAL 20 1 0.1 0.0 1 20 RELOCATED CIRCUITS FROM PANEL "L1" 10 --
1-#12, 1-#12, 1-#12 7 RECP. - BLENDER 20 1 0.2 0.2 1 20 RECP. - BLENDER 8 1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12 5 RECP. - BLENDER 20 1 0.2 0.2 1 20 RECP. - BLENDER 6 1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12 3 * RECP. - BEVERAGE CASE 20 1 0.2 0.2 1 20 * RECP. - BEVERAGE CASE 4 1-#12, 1-#12, 1-#12
1-#12, 1-#12, 1-#12 1 RECP. - TVS 20 1 1.0 0.4 1 20 RECP. - COUNTER TOP 2 1-#12, 1-#12, 1-#12
WIRE SIZEWIRE SIZEWIRE SIZEWIRE SIZE CKTCKTCKTCKT DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION BKRBKRBKRBKR PPPP AAAA BBBB CCCC PPPP BKRBKRBKRBKR DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION CKTCKTCKTCKT WIRE SIZEWIRE SIZEWIRE SIZEWIRE SIZE
MOUNTING:MOUNTING:MOUNTING:MOUNTING: SURFACE ENCLOSURE:ENCLOSURE:ENCLOSURE:ENCLOSURE: Type 1
SUPPLIED FROM:SUPPLIED FROM:SUPPLIED FROM:SUPPLIED FROM: L1, 120 V/208 V, Three Phas... WIRES:WIRES:WIRES:WIRES: 4 MCB RATING:MCB RATING:MCB RATING:MCB RATING: 225 A
PHASES:PHASES:PHASES:PHASES: 3 MAINS RATING:MAINS RATING:MAINS RATING:MAINS RATING: 250 A
PANELBOARD:PANELBOARD:PANELBOARD:PANELBOARD:
L1AL1AL1AL1ADISTRIBUTION:DISTRIBUTION:DISTRIBUTION:DISTRIBUTION: 120/208 Wye A.I.C. RATING:A.I.C. RATING:A.I.C. RATING:A.I.C. RATING: 10,000
OS
OS
OS
OS
OS
OS
OS
OS
OS
JJJJGTD
OS
OS
OS
OS
OS
OS
OS
OS
E E E E E
E
E
EE
RN
E
E E E
106106106106OFFICEOFFICEOFFICEOFFICE 107107107107
SEMINARSEMINARSEMINARSEMINAR
105105105105OFFICEOFFICEOFFICEOFFICE
104104104104SEMINARSEMINARSEMINARSEMINAR
103A103A103A103ASEMINARSEMINARSEMINARSEMINAR
H102H102H102H102CORRIDORCORRIDORCORRIDORCORRIDOR
112112112112WOMENSWOMENSWOMENSWOMENS
111A111A111A111AJANITORJANITORJANITORJANITOR
111111111111MENSMENSMENSMENS
108A108A108A108ADATADATADATADATA
108108108108ELEC.ELEC.ELEC.ELEC.
EE E
E
E
E E E
E
E
E E E E
E E
E
E E E
E
E
E
E
EE
E
E
E
E
EE E
E
105A105A105A105ASTOR.STOR.STOR.STOR.
C
B
RN
A
AE
RN
RN
RN
C
RN
EE E
E
E
E
E
E
E
E
E
E
E
E
E
E
b
b
a
D D 3a b c
c
c 3c
1
C
C
C
b
b
b
22
2
3
2
4
4
4
4
4 4
2
E
SHADING INDICATES EMERGENCY FIXTURE USED BY GENERATOR
CE = UPPERCASE LETTER / LETTERS INDICATE FIXTURE TYPEd = LOWERCASE LETTER INDICATES SWITCH IDENTIFICATION NL or EM = INDICATES NON SWITCHED "NIGHT LIGHT" / "EMERGENCY"A:9 = DESIGNATES PANEL NAME: CIRCUIT NUMBER
NOTE:
ALL "EM" FIXTURES INDICATED IN PLAN CONTAIN CONNECTION TO GENERATOR. WHERE GTD OR GTD-20 IS SHOWN, CONNECT EMERGENCY FIXTURES THROUGH GTD WITH A GENERATOR-BACKED (CONSTANT HOT) CIRCUIT AND THE NORMAL POWER SWITCHLEG ASSOICATED WITH THAT SPACE SO THAT FIXTURE IS CONTROLLED WITH NORMAL FIXTURES BUT TRANSFER TO GENERATOR CIRCUIT AT 100% OUTPUT DURING AN OUTAGE.
NL A:2
CE
LIGHT FIXTURE PLAN KEYLIGHT FIXTURE PLAN KEYLIGHT FIXTURE PLAN KEYLIGHT FIXTURE PLAN KEY
d
E E E E E
E
E
EE
RR
RR
R
R
RR
E E E E
111111111111MENSMENSMENSMENS
111A111A111A111AJANITORJANITORJANITORJANITOR
108A108A108A108ADATADATADATADATA
108108108108ELEC.ELEC.ELEC.ELEC.
106106106106OFFICEOFFICEOFFICEOFFICE
107107107107SEMINARSEMINARSEMINARSEMINAR
112112112112WOMENSWOMENSWOMENSWOMENS
H102H102H102H102CORRIDORCORRIDORCORRIDORCORRIDOR
105A105A105A105ASTOR.STOR.STOR.STOR.
105105105105OFFICEOFFICEOFFICEOFFICE
104104104104SEMINARSEMINARSEMINARSEMINAR
103A103A103A103ASEMINARSEMINARSEMINARSEMINAR
E E E E
E
E E E
EE E
EE
E E E
E
E
E
E
E
EE
E
E
E
E
E
EEEE
E E
E
R
RR
RR
RR
R
R
EE
E
E
E
R
E
E
E
E
E
E
E
E
E
E
E
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
WT21603WT21603WT21603
No. 26181
R
ANILORACHTUOS
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.HERA
No. 26181
R
ANILORACHTUOS
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.HERA
No. 26181
R
ANILORACHTUOS
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.HERA
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CAT E OF AUTHOR
I ZA
TI O
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CAT E OF AUTHOR
I ZA
TI O
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHTU
O
S
CE
RT
I FI CAT E OF AUTHOR
I ZA
TI O
N
PROJECT NO. SHEET NO.
# REVISIONDATE
PHASE:
Thes
e draw
ings
are th
e prop
erty of W
atso
n Ta
te Savory, In
c. and
may
not be us
ed in
who
le or in pa
rt with
out w
ritten co
nsen
t of the
architects an
d an
y infring
emen
t is su
bjec
t to lega
l action.
ISSUE DATE
3-20-17
C:\Use
rs\Jas
on\D
ocum
ents\W
T216
03_DODIE NUTR
ITION_C
ENTR
AL_
2017
_Jaso
n.rvt
3/13
/201
7 3:15
:37 PM
E1.01WT21603
FIRST FLOORLIGHTING PLAN
RE-
BID: D
ODIE ANDER
SON ACADEM
IC ENRICHMEN
TCEN
TER NUTR
ITION STA
TION
SCHEMATIC DESIGN
3/20/17
SCALE: 1/4" = 1'-0"E1.01
3 FIRST FLOOR LIGHTING RENOVATION PLANFIRST FLOOR LIGHTING RENOVATION PLANFIRST FLOOR LIGHTING RENOVATION PLANFIRST FLOOR LIGHTING RENOVATION PLAN
KEY NOTESKEY NOTESKEY NOTESKEY NOTES
1 PROVIDE REMOTE POWER SUPPLY FOR TYPE "C" FIXTURES MOUNT
ABOVE ACCESSIBLE CEILING IN THIS LOCATION.
2 CONNECT TO EXISTING NORMAL POWER LIGHTING CIRCUIT IN EXISTING
CORRIDOR, (H1-6). BYPASS ALL EXISTING SWITCHLEGS AND CONNECT
THROUGH DIMMER.
3 CONNECT TO EXISTING EMERGENCY POWER LIGHTING CIRCUIT IN
EXISTING CORRIDOR, (LHB-14). BYPASS ALL EXISTING SWITCHLEGS
AND CONNECT THROUGH GTD.
4 EXTEND EXISTING BRANCH CIRCUIT TO RELOCATED FIXTURE.
GENERAL NOTESGENERAL NOTESGENERAL NOTESGENERAL NOTES
1 ALL NORMAL POWER LIGHTING SHOWN ON THIS PLAN IS SERVED
FROM PANEL "H1" UNLESS NOTED OTHERWISE.
2 ALL EMERGENCY POWER LIGHTING ON THIS PLAN IS SERVED FROM
PANEL "LHB" UNLESS OTHERWISE NOTED.
SCALE: 1/4" = 1'-0"E1.01
90 FIRST FLOOR LIGHTING DEMOLITION PLANFIRST FLOOR LIGHTING DEMOLITION PLANFIRST FLOOR LIGHTING DEMOLITION PLANFIRST FLOOR LIGHTING DEMOLITION PLAN
LIGHT FIXTURE SCHEDULE NOTESLIGHT FIXTURE SCHEDULE NOTESLIGHT FIXTURE SCHEDULE NOTESLIGHT FIXTURE SCHEDULE NOTES1 LUMENS LISTED IN SCHEDULE REPRESENT DELIVERED LUMENS OF FIXTURES.
2 THREE DIGIT NUMBERS LISTED IN LAMP COLUMN REPRESENT CRI AND COLOR TEMPERATURE. FIRST DIGIT
INDICATES MINIMUM CRI AND LAST TWO DIGITS INDICATE COLOR TEMPERATURE. EXAMPLE: 830 INDICATES
MINIMUM CRI OF 80 AND A COLOR TEMPERATURE OF 3000K.
3 SEE ARCHITECTURAL RCP AND ELEVATIONS FOR EXACT LOCATION AND MOUNTING HEIGHTS.
4 CONFIRM QUANTITIES OF FIXTURES SHOWN IN RCP MATCH QUANTITIES SHOWN ON ELECTRICAL PLANS PRIOR
TO BID. IF NO DISCREPANCIES ARE NOTED PRIOR TO BID THE HIGHEST QUANTITY OF EACH FIXTURE TYPE
SHOWN SHALL BE PROVIDED.
LIGHT FIXTURE SCHEDULELIGHT FIXTURE SCHEDULELIGHT FIXTURE SCHEDULELIGHT FIXTURE SCHEDULE
SYMBOLSYMBOLSYMBOLSYMBOL
FIXTURE SPECIFICATIONSFIXTURE SPECIFICATIONSFIXTURE SPECIFICATIONSFIXTURE SPECIFICATIONS LAMPINGLAMPINGLAMPINGLAMPING ELECTRICALELECTRICALELECTRICALELECTRICAL
MOUNTING REMARKSMOUNTING REMARKSMOUNTING REMARKSMOUNTING REMARKS NOTESNOTESNOTESNOTESTYPETYPETYPETYPE
FIXTUREFIXTUREFIXTUREFIXTURE
DESCRIPTIONDESCRIPTIONDESCRIPTIONDESCRIPTION MANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER CAT. #CAT. #CAT. #CAT. # NO.NO.NO.NO. LAMP TYPELAMP TYPELAMP TYPELAMP TYPE
FIXT.FIXT.FIXT.FIXT.
LOADLOADLOADLOAD VOLTSVOLTSVOLTSVOLTS.
.
A FLUORESCENT 2X4 H.E. WILLIAMS LPT-24-332-SA12125-EB
3-UNV
3 T8, 840 96 277 V RECESSED IN CEILING 2,3,4
.
.
AE FLUORESCENT 2X4 H.E. WILLIAMS LPT-24-332-SA12125-EB
3-UNV
3 T8, 840 96 277 V RECESSED IN CEILING 2,3,4
B LED LINEAR FINELITE HP-2R-12-S-8-40-F-2
77V-SC-SF
- LED, 4032
LUMENS 840
43 277 V RECESSED IN CEILING 1,2,3,4
C ANGLED LED LINEAR (5') LUMINII PSV-96-24-UZDIM-D - LED, 1265
LUMENS 835
16 277 V SURFACE MOUNTED ON TOP
PF CANOPY
1,2,3,4
LIGHTING FIXTURE PRIOR APPROVED SCHEDULELIGHTING FIXTURE PRIOR APPROVED SCHEDULELIGHTING FIXTURE PRIOR APPROVED SCHEDULELIGHTING FIXTURE PRIOR APPROVED SCHEDULE
TYPETYPETYPETYPE MANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER CAT #CAT #CAT #CAT # MANUFACTURERMANUFACTURERMANUFACTURERMANUFACTURER CAT #CAT #CAT #CAT #A LITHONIA 2GT8 SERIES COLUMBIA JT824 SERIES
AE LITHONIA 2GT8 SERIES COLUMBIA JT824 SERIES
B MARK ARCH
LIGHTING
SL2L SERIES BIRCHWOOD LIGHTING JAKE LED SERIES
C DESIGN PLAN PF460 SERIES ACOLYTE RAC SERIES
JJJJ
JJJJ
S
S
S S
S
S
S
S
A/V A/V
A/V
A/V
A/V
A/V
A/VV
V
A/V
A/V
A/V
R
SS SS
JJJJ
JJJJ
S
S
S S
S
S
S
S
A/V
A/V
A/V
A/VV
V
A/V
A/V
A/V
A/V
A/V
R
SS SS
A/V
TVTVTVTV
TVTVTVTV
JJ JJ
TVTVTVTV
JJJJ
HOOD HOOD
G
CR
S
CGD
CR
S
UP
DOWN UP
DOWN
111111111111MENSMENSMENSMENS
111A111A111A111AJANITORJANITORJANITORJANITOR
112112112112WOMENSWOMENSWOMENSWOMENS
108A108A108A108ADATADATADATADATA
108108108108ELEC.ELEC.ELEC.ELEC.
106106106106OFFICEOFFICEOFFICEOFFICE
107107107107SEMINARSEMINARSEMINARSEMINAR
H102H102H102H102CORRIDORCORRIDORCORRIDORCORRIDOR
105A105A105A105ASTOR.STOR.STOR.STOR.
105105105105OFFICEOFFICEOFFICEOFFICE
104104104104SEMINARSEMINARSEMINARSEMINAR
103A103A103A103ASEMINARSEMINARSEMINARSEMINAR
E
RR
E
E
R
R
RR
RR
R
RR
+66"
+66"
+66"
+66"
TV
TV
EXISTING
'L1'
EXISTING
'LCP'
EXISTING
'EL1'
EXISTING
'H1'
EXISTING
XFMR
E
E
E
E
E
E E
E
EE
E
E
E1E
E
E
3
R+66"
TV
5
RR
7
10
EXISTING 12" CABLE
TRAY ABOVE CEILING
TO REMAIN IN PLACE
111111111111MENSMENSMENSMENS
111A111A111A111AJANITORJANITORJANITORJANITOR
108A108A108A108ADATADATADATADATA
108108108108ELEC.ELEC.ELEC.ELEC.
112112112112WOMENSWOMENSWOMENSWOMENS
107107107107SEMINARSEMINARSEMINARSEMINAR
106106106106OFFICEOFFICEOFFICEOFFICE
H102H102H102H102CORRIDORCORRIDORCORRIDORCORRIDOR
103A103A103A103ASEMINARSEMINARSEMINARSEMINAR
104104104104SEMINARSEMINARSEMINARSEMINAR
105105105105OFFICEOFFICEOFFICEOFFICE
105A105A105A105ASTOR.STOR.STOR.STOR.
RN
EXISTING
'L1'
L1A
RN
15cd
TV
E
E
E+66"
+66"
E
1
2
E
EE
E
EE
E
E
E
E
E
E
E
E
E
E
EXISTING
'EL1'
EXISTING
'LCP'
EXISTING
'H1'
EXISTING
XFMR
E1.02
E1.02
3
4
30cd
4
6
6
6
7
RN
9
EXISTING 12" CABLE
TRAY ABOVE CEILING
TO REMAIN IN PLACE
2222
2222
5555
4444
3333
6666
7777
8888
9999
1111
1111
RN
10
11
12
RN RN
C C
RN
CC C
DISPOSAL
SWITCH
DISPOSAL
E
T1-17
L1-34
ET1-18
L1-34
T1-19
L1-348
ENLARGED
PLANS
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
(803) 731-0650 p | (803) 731-2880 f
ENGINEERING
7 CLUSTERS COURT, SUITE 201 | COLUMBIA, SC | 29210
ASSOCIATES, INC.
BELKA
CONTACT: JASON AREHEART
WT21603WT21603WT21603
No. 26181
R
A
NILORACHT
UO
S
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.H
ERA
No. 26181
R
A
NILORACHT
UO
S
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.H
ERA
No. 26181
R
A
NILORACHT
UO
S
J EE
NI
GN
E
LANOISSEFO
R
PD
ES
NE
CIL
AS
ON E
AR
T
L.H
ERA
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHT
UO
S
CE
RT
IF
I CATE
OF AUTHOR
I ZA
TIO
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHT
UO
S
CE
RT
IF
I CATE
OF AUTHOR
I ZA
TIO
N
No. C00953
ASSOC. INC.
BELKA
ENGINEERING
A
NILORACHT
UO
S
CE
RT
IF
I CATE
OF AUTHOR
I ZA
TIO
N
PROJECT NO. SHEET NO.
# REVISIONDATE
PHASE:
Thes
e dr
awin
gs a
re th
e pr
oper
ty o
f Wat
son
Tate
Sav
ory,
Inc.
and
may
not
be
used
in w
hole
or i
n pa
rt w
ithou
t writ
ten
cons
ent o
f the
arc
hite
cts
and
any
infri
ngem
ent i
s su
bjec
t to
lega
l act
ion.
ISSUE DATE
3-20-17
C:\
Use
rs\L
uke\
Doc
umen
ts\W
T216
03_
DO
DIE
NU
TRIT
ION
_C
ENTR
AL_
2017
_Ste
phen
.rvt
3/13
/201
7 10
:50:
32 A
M
E1.02WT21603
FIRST FLOORPOWER PLAN
RE-
BID
: DO
DIE
AN
DER
SO
N A
CA
DEM
IC E
NR
ICH
MEN
TC
ENTE
R N
UTR
ITIO
N S
TATI
ON
SCHEMATIC DESIGN
3/20/17
SCALE: 1/4" = 1'-0"E1.02
1 ENLARGED POWER DEMOLITION PLANENLARGED POWER DEMOLITION PLANENLARGED POWER DEMOLITION PLANENLARGED POWER DEMOLITION PLANSCALE: 1/4" = 1'-0"E1.02
2 ENLARGED POWER RENOVATION PLANENLARGED POWER RENOVATION PLANENLARGED POWER RENOVATION PLANENLARGED POWER RENOVATION PLAN
KEY NOTESKEY NOTESKEY NOTESKEY NOTES
1 COORDINATE LOCATION OF NEW WALL WITH OWNER/ARCHITECT TO
ENSURE NO CONFLICT WITH EXISTING FLOORBOX.
2 COORDINATE EXACT LOCATION OF UNDER COUNTER REFRIGERATOR WITH
ARCH/OWNER AND LOCATE RECEPTACLE IN A LOCATION THAT IS
ACCESSIBLE WITHOUT REMOVING APPLIANCE.
3 EXISTING TV SHALL BE RELOCATED TO NEW LOCATION SHOWN ON
RENOVATION PLAN REFERENCED TO KEY NOTE 4. EXISTING BRANCH
CIRCUIT SHALL BE EXTENDED TO NEW LOCATION. COORDINATE WITH
OWNER FOR A/V SYSTEM MODIFICATION. EXTEND EXISTING RACEWAYS
FOR LOW-VOLTAGE CABLING TO NEW LOCATION.
4 PROVIDE A CHIEF (MODEL: PAC526) RECESSED WALL BOX WITH DUPLEX
RECEPTACLE MOUNTED INTEGRAL TO BOX. COORDINATE EXACT
MOUNTING LOCATIN WITH ARCHITECT / OWNER PRIOR TO ROUGH-IN.
CONNECT TO EXISTING BRANCH CIRCUIT REFERENCED IN KEYED NOTE
3. EXISTING LOW-VOLTAGE RACEWAYS SHALL BE EXTEND TO THIS
BOX.
5 EXISTING TV HAS HDMI CONNECTION FROM OFFICE 106. EXISTING TV
SHALL BE REMOVED BY OWNER. DISCONNECT AND REMOVE EXISTING
POWER AND A/V SYSTEM CABLING COMPLETELY BACK TO SOURCE.
6 PROVIDE AN A/V WALL BOX (CHIEF MODEL: PAC526) RECESSED WALL
BOX WITH DUPLEX RECEPTACLE MOUNTED INTEGRAL TO BOX. PROVIDE
A 1-1/4" CONDUIT FROM A/V WALL BOX TO A 4" SQUARE BOX
MOUNTED NEAR COMPUTER WORKSTATION IN OFFICE 106. PROVIDE
ANOTHER 1-1/4" CONDUIT FROM A/V WALL BOX TO CABLE-TRAY FOR
ANY FUTURE A/V REQUIREMENTS.
7 RELOCATE EXISTING WALL SWITCH FOR PROJECTION SCREEN TO
LOCATION SHOWN ON RENOVATION PLAN REFERENCED TO THIS NOTE.
8 EXTEND EXISTING BRANCH CIRCUIT CIRCUIT "L1-34" FROM EXISTING
VAV-T1-17 TO NEW VAV-T1-19 LOCATION. SEE MECHANICAL PLANS
FOR EXACT LOCATION.
9 CHANGE CANDELA RATING ON EXISTING WALL MOUNT SPEAKER/STROBE
TO 110cd. CONFIRM CIRCUIT MEETS ALL VOLTAGE DROP AND BATTERY
REQUIREMENTS.
10 RELOCATE EXISTING BRANCH CIRCUIT TO NEW LOCATION OF WATER
FOUNTAIN.
11 EXTEND EXISTING BRANCH CIRCUIT IN OFFICE 105 TO NEW RECEPTACLE
LOCATION.
12 EXTEND EXISTING BRANCH CIRCUIT THAT FEEDS EXISTING UC
REFRIGERATOR TO NEW UC RERIGERATOR LOCATION.
SCALE: 1/4" = 1'-0"E1.02
3 NUTRITION BAR SERVING COUNTER ELEVATIONNUTRITION BAR SERVING COUNTER ELEVATIONNUTRITION BAR SERVING COUNTER ELEVATIONNUTRITION BAR SERVING COUNTER ELEVATIONSCALE: 1/4" = 1'-0"E1.02
4 NUTRITION BAR PREP AREA ELEVATIONNUTRITION BAR PREP AREA ELEVATIONNUTRITION BAR PREP AREA ELEVATIONNUTRITION BAR PREP AREA ELEVATION
GENERAL NOTESGENERAL NOTESGENERAL NOTESGENERAL NOTES
1 BRANCH CIRCUITS SHOWN ON THIS SHEET SHALL SERVED FROM
PANEL "L1A" UNLESS NOTED OTHERWISE.
SCALE: 1/16" = 1'-0"E1.02
5 OVERALL FIRST FLOOR POWER PLANOVERALL FIRST FLOOR POWER PLANOVERALL FIRST FLOOR POWER PLANOVERALL FIRST FLOOR POWER PLAN