Process pressure/Hydrostatic
Pressure transmitter
VEGABAR 51, 52, 53, 54, 55
Product Information
Contents
2 Process pressure/Hydrostatic – Pressure transmitter
Contents
1 Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Type overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Selection criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Housing overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
6 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Electronics - 4 … 20 mA - two-wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
8 Electronics - 4 … 20 mA/HART - two-wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
9 Electronics - Profibus PA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10 Electronics - Foundation Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
11 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
12 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Take note of safety instructions for Ex applications
Pleasenote theEx specific safety informationwhichyoucanfindonourhomepagewww.vega.com»Downloads»Approvalsandwhichcome
with every instrument. In hazardous areas you should take note of the corresponding regulations, conformity and type approval certificates of
the sensors and power supply units. The sensors must only be operated on intrinsically safe circuits. The permissible electrical values are
stated in the certificate.
37528-EN-100415
1 Measuring principle
VEGABAR 51
The sensor element for measuring ranges up to 60 bar is the CERTEC®
measuring cell with rugged ceramic diaphragm.The hydrostatic pressure
of the product or the process pressure causes a capacitance change in
the measuring cell via the metal process diaphragm and the isolating
system. This change is converted into a corresponding output signal.
The sensor element for measuring ranges from 100 bar is a wire strain
gauge (DMS) on the back side of the process diaphragm. There, the
process pressure causes a resistance change, which is converted into
an appropriate output signal.
VEGABAR 52, 54
The sensor element is the CERTEC® measuring cell with flush, abrasion
resistant ceramic diaphragm. The hydrostatic pressure of the medium or
the process pressure causes a capacitance change in themeasuring cell
via the diaphragm. This change is converted into an appropriate output
signal.
16
µm 1
2
3
Fig. 1: Configuration of the CERTEC® measuring cell in VEGABAR 52
1 Diaphragm
2 Soldered glass bond
3 Base element
The CERTEC® measuring cell is also equipped with a temperature sen-
sor.The temperature value canbedisplayed via the indicatingandadjust-
ment module or processed via the signal output.
VEGABAR 52, 54 - climate compensated
The sensor element is an encapsulated CERTEC® absolute pressure
measuring cell with front-flush, abrasion-resistant ceramic diaphragm.
The hydrostatic pressure of the medium or the process pressure causes
a capacitance change in the measuring cell via the ceramic diaphragm.
This capacitance change is converted into an electrical signal, checked
against an integrated reference pressure measurement and outputted as
measured value via the output signal.
VEGABAR 53
The process pressure acts on the sensor element via the stainless steel
diaphragm. The process pressure causes a resistance change which is
converted into a corresponding output signal and outputted asmeasured
value.
For measuring ranges up to 16 bar, a piezoresistive sensor element with
internal transmission liquid is implemented, for measuring ranges from
25 bar, a strain gauge (DMS) sensor element on the back side of the
stainless steel diaphragm (dry).
1
4 3
2
Fig. 2: Configuration of the piezoresistive measuring cell in VEGABAR 53
1 Sensor element
2 Base element
3 Diaphragm
4 Silicone oil filling
VEGABAR 55
The METEC® measuring cell is the measuring unit. It consists of the
ceramic-capacitive CERTEC® measuring cell and a special, tempera-
ture-compensating isolating system.
The hydrostatic pressure of the product or the process pressure causes a
capacitance change in the measuring cell via the metallic process dia-
phragm and the isolating liquid. This change is converted into a corre-
sponding output signal.
4321
Fig. 3: Configuration of theMETEC® measuring cell in VEGABAR 55
1 Process diaphragm
2 Isolating liquid
3 FeNi adapter
4 CERTEC® measuring cell
Measuring principle
Process pressure/Hydrostatic – Pressure transmitter 3
37528-EN-100415
2 Type overview
VEGABAR 51 VEGABAR 52 VEGABAR 53
Measuring cell Piezoresistive/DMS CERTEC®
Piezoresistive
Diaphragm Metal Ceramic Metal
Media gases, vapours and liquids, also
aggressive ones, at high temper-
atures
gases, vapours and liquids, also with
abrasive substances
Gas, vapours and liquids, also vis-
cous
Process fitting Thread from ½", flanges from DN 20,
boltings, isolating diaphragms each
from DN 25
Thread from 1", flanges from DN 25,
fittings for the food processing and
paper industry
Manometer connection G½ A or
½ NPT, connection G1 A or G½ A
front-flush, hygienic fittings
Material
Process fitting
316L 316L, PVDF, Hastelloy C-22, Has-
telloy C-276
316Ti
Diaphragm material 316L, Hastelloy C276, Tantalum,
gold on 316L
Al2O3 ceramic 316Ti, Elgiloy 2.4711
Measuring cell seal - FKM, EPDM, FFKM -
Isolating liquid Silicone oil, high temperature oil,
halocarbon oil, med. white oil
- Silicone oil, Halocarbon oil
Measuring range -1 … +400 bar/-100 … +4000 kPa (-
-14.5 … +5802 psig)
-1 … +72 bar/-100 … +7200 kPa (-
-14.5 … +1044 psig)
-1 … +600 bar/-100 … +6000 kPa (-
-14.5 … +8702 psig)
Smallest measuring
range
0.4 bar/40 kPa (5.802 psig) 0.1 bar/10 kPa (1.45 psig) 0.4 bar/40 kPa (5.802 psig)
Process temperature -40 … +400 °C (-40 … +752 °F) -40 … +150 °C (-40 … +302 °F) -40 … +150 °C (-40 … +302 °F)
Deviation < 0.2 % < 0.05 % < 0.075 %
Signal output l 4 … 20 mA
l 4 … 20 mA/HART
l Profibus PA
l Foundation Fieldbus
l 4 … 20 mA
l 4 … 20 mA/HART
l Profibus PA
l Foundation Fieldbus
l 4 … 20 mA
l 4 … 20 mA/HART
l Profibus PA
l Foundation Fieldbus
Indication/Adjustment l PLICSCOM
l PACTware
l VEGADIS 61
l VEGADIS 62
l PLICSCOM
l PACTware
l VEGADIS 61
l VEGADIS 62
l PLICSCOM
l PACTware
l VEGADIS 61
l VEGADIS 62
Approvals l Shipbuilding
l ATEX
l IEC
l Overfill protection
l FM
l CSA
l GOST
l Shipbuilding
l ATEX
l IEC
l Overfill protection
l FM
l CSA
l GOST
l Shipbuilding
l ATEX
l IEC
l Overfill protection
l FM
l CSA
l GOST
Type overview
4 Process pressure/Hydrostatic – Pressure transmitter
37528-EN-100415
VEGABAR 54 VEGABAR 55
Measuring cell CERTEC®
METEC®
Diaphragm Ceramic Metal
Media gases, vapours and liquids, also with abrasive substan-
ces
gases, vapours and liquids also with higher temperatures
Process fitting Thread from 1", flanges from DN 25, fittings for the food
processing and paper industry
Thread from 1½", flanges from DN 20, fittings for the food
processing industry
Material
Process fitting
316L 316L
Diaphragm material Al2O3 ceramic Hastelloy C-276, gold-coated, gold/rhodium-coated
Measuring cell seal FKM, EPDM, FFKM -
Isolating liquid - Med. white oil
Measuring range -1 … +72 bar/-100 … +7200 kPa (-14.5 … +1044 psig) -1 … +25 bar/-100 … +2500 kPa (-14.5 … +362.6 psig)
Smallest measuring
range
0.1 bar/10 kPa (1.45 psig) 0.1 bar/10 kPa (1.45 psig)
Process temperature -40 … +120 °C (-40 … +248 °F) -12 … +200 °C (-10 … +392 °F)
Deviation < 0.1 % < 0.075 %
Signal output l 4 … 20 mA
l 4 … 20 mA/HART
l Profibus PA
l Foundation Fieldbus
l 4 … 20 mA
l 4 … 20 mA/HART
l Profibus PA
l Foundation Fieldbus
Indication/Adjustment l PLICSCOM
l PACTware
l VEGADIS 61
l VEGADIS 62
l PLICSCOM
l PACTware
l VEGADIS 61
l VEGADIS 62
Approvals l Shipbuilding
l ATEX
l IEC
l Overfill protection
l FM
l CSA
l GOST
l Shipbuilding
l ATEX
l IEC
l Overfill protection
l FM
l CSA
l GOST
Type overview
Process pressure/Hydrostatic – Pressure transmitter 5
37528-EN-100415
3 Device selection
Application areas
VEGABAR 51
The VEGABAR is a pressure transmitter with isolating diaphragm for
pressure measurement of highly corrosive and hot liquids.
VEGABAR 52, 54
VEGABAR is a pressure transmitter for use in the paper, food processing
and pharmaceutical industries as well as in water/sewage water plants.
Depending on the version, it is used for level, gauge, absolute pressure or
vacuum measurement. Measured products are gases, vapours and
liquids, also those containing abrasive substances.
VEGABAR 52, 54 - climate compensated
The version 4 … 20 mA/HART - climate-compensated is suitable for
applications under difficult conditions (cold medium and humid environ-
ment).
VEGABAR 53
VEGABAR is a pressure transmitter for measurement of overpressure,
absolute pressure or vacuum. Measured products are gases, vapours
and liquids inmeasuring ranges up to4000bar (400MPa);with front-flush
version also viscous liquids in measuring ranges up to 600 bar (60MPa).
VEGABAR 55
VEGABAR is a pressure transmitter for use in thechemical, foodprocess-
ingandpharmaceutical industries.Dependingon the version, it is used for
level, gauge, absolute pressure or vacuum measurement. Measured
products are gases, vapours and liquids, also those with higher temper-
atures.
Configuration and housing protection classes
1
2
3
Fig. 4: Example of a VEGABAR 52 with connectionG1½ A and plastic housing in
protection IP 66/IP 67
1 Housing cover with integrated indicating and adjustment module (optional)
2 Housing with electronics
3 Process fitting with measuring cell
1
2
3
45
Fig. 5: Example of a VEGABAR 51with flange and aluminiumhousing in protection
IP 66/IP 68, 1 bar
1 Housing cover with integrated indicating and adjustment module (optional)
2 Housing with electronics
3 Process fitting with measuring cell
4 Cable gland
5 Connection cable
1
2
3
5
4
Fig. 6: Example of a VEGABAR 51 with flange and stainless steel housing in pro-
tection IP 68 and external electronics
1 Housing cover with integrated indicating and adjustment module (optional)
2 Housing with electronics
3 Housing socket
4 Connection cable
5 Process fitting with measuring cell
Device selection
6 Process pressure/Hydrostatic – Pressure transmitter
37528-EN-100415
4 Selection criteria
VEGABAR
51
VEGABAR
52
VEGABAR
53
VEGABAR
54
VEGABAR
55
Front-flush version ● ● ● ● ●
Dry measuring system – ● – ● –
Oil filled measuring system ● – ● – ●
Abrasive wear – ● – ● –
Aggressive products ● – ● – ●
Max. process temperature
120 °C (248 °F) ● ● ● ● ●
150 °C (302 °F) ● ● ● – ●
200 °C (302 °F) ● – – – ●
400 °C (752 °F) ● – – – –
Hygienic process fittings ● ● ● – ●
Measuring ranges greater than 25 bar
(2500 kPa)
● ● ● ● –
Measuring ranges greater than 72 bar
(7200 kPa)
● – ● – –
Small measuring range 0.1 bar
(10 kPa)
– ● – ● ●
Vacuum applications up to 1 mbarabs(100 Pa)
– ● – – –
Suitability for industry-specific ap-
plications
Aggregates and min-
ing industry
– ● – – ●
Chemical ● ● – – –
Power generation ● ● – – –
Sanitary ● ● ● – ●
Metal generation – ● ● – –
Offshore ● ● – – –
Paper ● ● ● ● ●
Petrochemistry ● ● – – ●
Pharmaceutical ● ● – – ●
Shipbuilding – ● ● ● –
Environment and recy-
cling industry
– ● – – –
Water and waste water
industry
– ● – – –
Cement industry – ● – – ●
Selection criteria
Process pressure/Hydrostatic – Pressure transmitter 7
37528-EN-100415
5 Housing overview
Plastic PBT
Protection rating IP 66/IP 67 IP 66/IP 67
Version Single chamber Double chamber
Application area Industrial environment Industrial environment
Aluminium
Protection rating IP 66/IP 67, IP 66/IP 68 (1 bar) IP 66/IP 67, IP 66/IP 68 (1 bar)
Version Single chamber Double chamber
Application area Industrial environment with increased
mechanical wear
Industrial environment with increased
mechanical wear
Stainless steel 316L
Protection rating IP 66/IP 67 IP 66/IP 67, IP 66/IP 68 (1 bar) IP 66/IP 67, IP 66/IP 68 (1 bar)
Version Single chamber electropolished Single chamber precision casting Double chamber precision casting
Application area Aggressive environment, food pro-
cessing, pharmaceutical
Aggressive environment, strong me-
chanical wear
Aggressive environment, strong me-
chanical wear
Separate version
Material Stainless steel 316L plastic PBT
Protection rating IP 68 (25 bar) IP 65
Function Transmitter External electronics
Application area Extremely moist environment Industrial environment
Housing overview
8 Process pressure/Hydrostatic – Pressure transmitter
37528-EN-100415
6 Mounting
Mounting positionThe instruments function in any installation position. But the installation
position can influence the measurement, depending on the measuring
system. This can be compensated by a position correction.
It is useful to select an installation position you can easily reach formount-
ing and connecting as well as later retrofitting of an indicating and adjust-
ment module. For this purpose, the housing can be rotated by 330° with-
out the use of any tools.You can also install the indicating andadjustment
module in four different positions (each displaced by 90°).
Mounting examplesThe following illustrations show mounting examples and measurement
setups.
Reaction vessel
Fig. 7: Level measurement in reaction vessel with VEGABAR 51
VEGABAR 51 can be also used under high temperatures.The instrument
measures the hydrostatic pressure of the liquid column independent of
foam on the product surface. Its advantages are the high resistance dia-
phragm materials and the low oil volume of the isolating diaphragm.
Hence the temperature influence of the isolating diaphragm is kept low.
Drinking water network
Fig. 8: Pressure measurement on the drinking water network with VEGABAR 52
Thewater pressure in drinkingwater networks is continuouslymonitored.
Because pumping stations are often situated in remote areas, there is a
great demand for maintenance free, reliable measurement technology.
The VEGABAR 52 pressure transmitter meets these requirements.With
its robust ceramic CERTEC® measuring cell, VEGABAR 52 is the best
choice for monitoring pressure in pipeline systems.
Chemical pump
Fig. 9: Dry run protection on a chemical pump with VEGABAR 53
TheVEGABAR53pressure transmitterwithpiezoresistivemeasuringcell
andmetal diaphragm is deployed as dry run protection system for chem-
ical pumps. Its strengths are the small, front-flush process fitting, also for
small tube diameters, as well as the chemically resistant process dia-
phragm.
Storage tower
Fig. 10: Level measurement on storage towers with VEGABAR 54
In thepaper industry, the prepared stock is stored in large storage towers.
Level measurement in the lower section prevents the agitator from run-
ningdry.For thispurpose, theVEGABAR54pressure transmitterwithball
valve fitting is used. The advantages are: front-flush mounting in the ball
valve fitting, mounting and dismounting without emptying the storage
tower.
Mounting
Process pressure/Hydrostatic – Pressure transmitter 9
37528-EN-100415
Bitumen vessel
Fig. 11: Level measurement in a bitumen vessel with VEGABAR 55
VEGABAR 55 pressure transmitters are particularly suitable for hydro-
static level measurement of hot bitumen. The special configuration of its
metalMETEC®measuringcell ensures temperature decouplingbetween
process fitting and electronics and thus enables application up to 200 °C
(392 °F).
Mounting
10 Process pressure/Hydrostatic – Pressure transmitter
37528-EN-100415
7 Electronics - 4… 20mA - two-wire
Configuration of the electronicsThe pluggable electronics is mounted in the electronics compartment of
the instrument and can be exchanged by the user when servicing is re-
quired. The electronics is completely encapsulated to protect against
vibration and moisture.
The terminals for voltage supply as well as the plug with I²C interface for
parameter adjustment are located on the upper side of the electronics.
With thedouble chamberhousing, theseconnectionelementsare located
in the separate connection compartment.
Voltage supplyDepending on the version, the supply voltage and the current signal are
carried on the same two-wire connection cable.
The VEGA power supply units VEGATRENN 149AEx, VEGASTAB 690,
VEGADIS 371 as well as VEGAMET signal conditioning instruments are
suitable for power supply. When one of these instruments is used, a
reliable separation of the supply circuits from themains circuits according
to DIN VDE 0106 part 101 is ensured for the sensor.
l Operating voltage
- 12… 36 V DC
l Permissible residual ripple
- Upp < 1 V (< 100 Hz)
- Upp < 10mV (100… 10 kHz)
Connection cableThe sensors are connected with standard cable without screen. An outer
cable diameter of 5 … 9 mm ensures the seal effect of the cable entry.
If electromagnetic interference is expectedwhich is above the test values
of EN 61326 for industrial areas, screened cable should be used.
Cable screening and groundingIf screened cable is necessary, the cable screen must be connected on
both ends to ground potential. If potential equalisation currents are ex-
pected, the connectionon theevaluationsidemustbemadevia aceramic
capacitor (e.g. 1 nF, 1500 V).
Connection single chamber housing
I²C
Display
1 2 5 6 7 8
3
4
1
2
Fig. 12: Electronics and connection compartment with single chamber housig
1 Plug connector for VEGACONNECT (I²C interface)
2 Spring-loaded terminals for connection of the external indicationVEGADIS 61
3 Ground terminal for connection of the cable screen
4 Spring-loaded terminals for voltage supply
Connection double chamber housing
3
1
2
Dis
play
1 2 I²C
Fig. 13: Connection compartment, double chamber housing
1 Plug connector for VEGACONNECT (I²C interface)
2 Ground terminal for connection of the cable screen
3 Spring-loaded terminals for voltage supply
Electronics - 4 … 20 mA - two-wire
Process pressure/Hydrostatic – Pressure transmitter 11
37528-EN-100415
8 Electronics - 4… 20mA/HART - two-wire
Configuration of the electronicsThe pluggable electronics is mounted in the electronics compartment of
the instrument and can be exchanged by the user when servicing is re-
quired. The electronics is completely encapsulated to protect against
vibration and moisture.
The terminals for voltage supply as well as the plug with I²C interface for
parameter adjustment are located on the upper side of the electronics.
With thedouble chamberhousing, theseconnectionelementsare located
in the separate connection compartment.
Voltage supplyDepending on the version, the supply voltage and the current signal are
carried on the same two-wire connection cable.
The VEGA power supply units VEGATRENN 149AEx, VEGASTAB 690,
VEGADIS 371 as well as VEGAMET signal conditioning instruments are
suitable for power supply. When one of these instruments is used, a
reliable separation of the supply circuits from themains circuits according
to DIN VDE 0106 part 101 is ensured for the sensor.
l Operating voltage
- 12… 36 V DC
l Permissible residual ripple
- Upp < 1 V (< 100 Hz)
- Upp < 10mV (100… 10 kHz)
Connection cableThe sensors are connected with standard cable without screen. An outer
cable diameter of 5 … 9 mm ensures the seal effect of the cable entry.
If electromagnetic interference is expectedwhich is above the test values
ofEN61326 for industrial areas, screenedcable shouldbeused. InHART
multidrop mode the use of screened cable is generally recommended.
Cable screening and groundingIf screened cable is necessary, the cable screen must be connected on
both ends to ground potential. If potential equalisation currents are ex-
pected, the connectionon theevaluationsidemustbemadevia aceramic
capacitor (e.g. 1 nF, 1500 V).
Connection single chamber housing
I²C
Display
1 2 5 6 7 8
3
4
1
2
Fig. 14: Electronics and connection compartment with single chamber housig
1 Plug connector for VEGACONNECT (I²C interface)
2 Spring-loaded terminals for connection of the external indicationVEGADIS 61
3 Ground terminal for connection of the cable screen
4 Spring-loaded terminals for voltage supply
Connection double chamber housing
3
1
2
Dis
play
1 2 I²C
Fig. 15: Connection compartment, double chamber housing
1 Plug connector for VEGACONNECT (I²C interface)
2 Ground terminal for connection of the cable screen
3 Spring-loaded terminals for voltage supply
Electronics - 4 … 20 mA/HART - two-wire
12 Process pressure/Hydrostatic – Pressure transmitter
37528-EN-100415
9 Electronics - Profibus PA
Configuration of the electronicsThe pluggable electronics is mounted in the electronics compartment of
the instrument and can be exchanged by the user when servicing is re-
quired. The electronics is completely encapsulated to protect against
vibration and moisture.
The terminals for voltage supply as well as the plug with I²C interface for
parameter adjustment are located on the upper side of the electronics.
With thedouble chamberhousing, theseconnectionelementsare located
in the separate connection compartment.
Voltage supplyPower supply via the H1 Fieldbus cable.
l Operating voltage
- 9… 32 V DC
l Max. number of sensors with DP/PA segment coupler
- 32
l Max. number of sensors with VEGALOG 571 EP input card
- 10
Connection cableConnection is made with screened cable according to Profibus specifi-
cation. A cable diameter of 5… 9mmensures the seal effect of the cable
gland.
Make sure that the entire installation is carried out according to the Pro-
fibus specification. In particular,make sure that the termination of the bus
is done with appropriate terminating resistors.
Cable screening and groundingInsystemswithpotential equalisation,connect thecable screendirectly to
groundpotential at the power supply unit, in the connection box andat the
sensor. The screen in the sensor must be connected directly to the inter-
nal ground terminal. The ground terminal outside on the housing must be
connected to the potential equalisation (low impedance).
In systems without potential equalisation, connect the cable screen di-
rectly to groundpotential at the power supply unit and at the sensor. In the
connection box or T-distributor, the screen of the short stub to the sensor
must not be connected togroundpotential or to another cable screen.The
cable screens to the power supply unit and to the next distributor must be
connected to each other and also connected to ground potential via a
ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equal-
isationcurrents are thussuppressed,but theprotectiveeffectagainsthigh
frequency interference signals remains.
Connection single chamber housing
I²C
Display
1 2 5 6 7 8
3
4
1
2
Fig. 16: Electronics and connection compartment with single chamber housig
1 Plug connector for VEGACONNECT (I²C interface)
2 Spring-loaded terminals for connection of the external indicationVEGADIS 61
3 Ground terminal for connection of the cable screen
4 Spring-loaded terminals for voltage supply
Connection double chamber housing
3
1
2
Dis
play
1 2 I²C
Fig. 17: Connection compartment, double chamber housing
1 Plug connector for VEGACONNECT (I²C interface)
2 Ground terminal for connection of the cable screen
3 Spring-loaded terminals for voltage supply
Electronics - Profibus PA
Process pressure/Hydrostatic – Pressure transmitter 13
37528-EN-100415
10 Electronics - Foundation Fieldbus
Configuration of the electronicsThe pluggable electronics is mounted in the electronics compartment of
the instrument and can be exchanged by the user when servicing is re-
quired. The electronics is completely encapsulated to protect against
vibration and moisture.
The terminals for voltage supply as well as the plug with I²C interface for
parameter adjustment are located on the upper side of the electronics.
With thedouble chamberhousing, theseconnectionelementsare located
in the separate connection compartment.
Voltage supplyPower supply via the H1 Fieldbus cable.
l Operating voltage
- 9… 32 V DC
l max. number of sensors
- 32
Connection cableConnection is made with screened cable according to Fieldbus specifi-
cation. A cable diameter of 5… 9mmensures the seal effect of the cable
gland.
Make sure that the entire installation is carried out according to the Field-
bus specification. Inparticular,makesure that the terminationof thebus is
done with appropriate terminating resistors.
Cable screening and groundingInsystemswithpotential equalisation,connect thecable screendirectly to
groundpotential at the power supply unit, in the connection box andat the
sensor. The screen in the sensor must be connected directly to the inter-
nal ground terminal. The ground terminal outside on the housing must be
connected to the potential equalisation (low impedance).
In systems without potential equalisation, connect the cable screen di-
rectly to groundpotential at the power supply unit and at the sensor. In the
connection box or T-distributor, the screen of the short stub to the sensor
must not be connected togroundpotential or to another cable screen.The
cable screens to the power supply unit and to the next distributor must be
connected to each other and also connected to ground potential via a
ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equal-
isationcurrents are thussuppressed,but theprotectiveeffectagainsthigh
frequency interference signals remains.
Connection single chamber housing
I²C
3
4
5 1
2
Display
Typ:
1 2 5 6 7 8
Bus
Sim
.
Fig. 18: Electronics and connection compartment with single chamber housig
1 Plug connector for VEGACONNECT (I²C interface)
2 Spring-loaded terminals for connection of the external indicationVEGADIS 61
3 Ground terminal for connection of the cable screen
4 Spring-loaded terminals for Foundation Fieldbus connection
5 Simulation switch ("on" = mode for simulation release)
Connection double chamber housing
3
1
2
Dis
play
1 2 I²C
Fig. 19: Connection compartment, double chamber housing
1 Plug connector for VEGACONNECT (I²C interface)
2 Ground terminal for connection of the cable screen
3 Spring-loaded terminals for voltage supply
Electronics - Foundation Fieldbus
14 Process pressure/Hydrostatic – Pressure transmitter
37528-EN-100415
11 Operation
11.1 Overview
The sensors can be adjusted with the following adjustment media:
l with indicating and adjustment module
l an adjustment software according to FDT/DTM standard, e.g.
PACTware and PC
and, depending on the signal output, also with:
l A HART handheld (4 … 20 mA/HART)
l The adjustment program AMS (4 … 20 mA/HART and Foundation
Fieldbus)
l The adjustment program PDM (Profibus PA)
l A configuration tool (Foundation Fieldbus)
The enteredparameters are generally saved in the sensor,optionally also
in the indicating and adjustment module or in the adjustment program.
11.2 Adjustment with the indicating and adjust-
ment module PLICSCOM
The pluggable indicating and adjustment module is used for measured
value indication, adjustment and diagnosis with level and pressure sen-
sors. It is equippedwithadisplaywith full dotmatrix aswell as four keys for
adjustment. An integrated background lighting can be adjusted via the
adjustment menu.
Fig. 20: Indicating and adjustment module PLICSCOM
The indicating and adjustment module is integrated in the respective
sensor housing or in the external indicating and adjustment unit. After
mounting, the sensor and the indicating and adjustment module are
splash-proof even without housing cover.
11.3 Adjustment with PACTware
PACTware/DTMIndependent of the respective signal output 4 … 20 mA/HART, Profibus
PA or Foundation Fieldbus, the sensors can be adjusted with PACTware
directly on site. The sensors with signal output 4… 20mA/HART can be
also operated via the HART signal on the signal cable.
A VEGACONNECT interface adapter as well as an instrument driver for
the respective sensor is necessary for adjustment with PACTware. All
currently available VEGA DTMs are included as a DTM Collection with
the current PACTware version on a CD. They can be purchased for a
token fee from the responsible VEGA agency. In addition, this DTM Col-
lection incl. the basic version of PACTware can be downloaded free of
charge from the Internet.
To use the entire range of functions of aDTM, includingproject documen-
tation, aDTM licence is required for that particular instrument family. This
licence can be bought from the VEGA agency serving you.
Connection of the PC via VEGACONNECT
2
4
3
1
Fig. 21: Connection via I²C connection cable
1 I²C bus interface on the sensor
2 I²C cable of VEGACONNECT
3 VEGACONNECT
4 USB cable to the PC
5 PC
Necessary components:
l VEGABAR
l PC with PACTware and suitable VEGA DTM
l VEGACONNECT
l Power supply unit or processing system
11.4 Adjustment with other adjustment pro-
grams
PDM
For VEGA Profibus PA sensors, instrument descriptions for the adjust-
ment program PDM are available as EDD. The instrument descriptions
arealready implemented in thecurrent versionofPDM.For older versions
of PDM, a free-of-charge download is available via Internet.
AMS
For VEGA Foundation Fieldbus sensors, instrument descriptions for the
adjustment programAMS™ are available asDD.The instrument descrip-
tions are already implemented in the current version of AMS™. For older
versions of AMS™, a free-of-charge download is available via Internet.
Operation
Process pressure/Hydrostatic – Pressure transmitter 15
37528-EN-100415
Dimensions
16 Process pressure/Hydrostatic – Pressure transmitter
12 Dimensions
Plastic housing
1 2
~ 69 mm(2.72")
ø 77 mm(3.03")
11
2 m
m (
4.4
1")
M20x1,5/½ NPT
~ 87 mm (3.43")
M16x1,5
ø 84 mm(3.31")
12
0 m
m (
4.7
2")
M20x1,5/½ NPT
1 Single chamber housing
2 Double chamber housing
Aluminium housing
~ 116 mm (4.57")
ø 84 mm (3.31")
11
6 m
m (
4.5
7")
M20x1,5M20x1,5/½ NPT
21
~ 87 mm (3.43")
M16x1,5
ø 84 mm(3.31")
12
0 m
m (
4.7
2")
M20x1,5/½ NPT
1 Single chamber housing
2 Double chamber housing
Stainless steel housing
~ 69 mm(2.72")
ø 77 mm(3.03")
11
7 m
m (
4.6
1")
M20x1,5/½ NPT
~ 59 mm(2.32")
ø 80 mm(3.15")
11
2 m
m (
4.4
1")
M20x1,5/½ NPT
321
~ 87 mm (3.43")
M16x1,5
ø 84 mm(3.31")
12
0 m
m (
4.7
2")
M20x1,5/½ NPT
1 Single chamber housing electropolished
2 Single chamber housing precision casting
2 Double chamber housing precision casting
VEGABAR 51
Rd
78
x1,6
10
6 m
m (
4.1
7")
50
mm
(1.9
7")
156 mm(6.14")
12
2 m
m (
4.8
0")
1 2
1 Flange version
2 Version with tube isolating diaphragm
VEGABAR 52
21 3
SW 27 mm(1.06")G½ A
G¼
23
mm
(0.9
1")
73
mm
(2.8
7")
70
mm
(2.7
6")
17
mm
(0.6
7")
3 m
m(0
.12
")
20
mm
(0.7
9")
3 m
m(0
.12
")
ø 3 mm (0.12")
ø 6 mm (0.24")
ø 17,5 mm (0.69")
ø 40 mm (0.69")
SW 46 mm(1.81")
G1½ A
50
mm
(1.9
7")
22
mm
(0.8
7")
ø 55 mm (2.17")
1 Threaded versionG½ A,manometer connectionEN 837
2 Threaded versionG½ A, innerG¼ A
3 Threaded versionG½ A, innerG¼ A, PVDF
VEGABAR 53
1 2 3
G½ A 63
mm
(2.4
8")
65
mm
(2.5
6")
65
mm
(2.5
6")
20
,5 m
m(0
.81
")1
0 m
m(0
.39
")
20
,5 m
m(0
.81
")
10
mm
(0.3
9")
ø 18 mm (0.71")
ø 30 mm (1.18")
G½ A
G1 A
SW 41 mm(1.61")
SW 27 mm(1.06")
23
mm
(0.9
1")
3 m
m(0
.12
") ø 3 mm (0.12")
ø 6 mm (0.24")
ø 40 mm (0.69")
1 Threaded versionG½ A,manometer connectionEN 837
2 Threaded versionG½ A, front-flush
3 Threaded versionG1 A, front-flush
37528-EN-100415
Process pressure/Hydrostatic – Pressure transmitter 17
VEGABAR 54
SW 36 mm(1.42")
ø 29,3 mm (1.15")
30
mm
(1.1
8")
10
4,8
mm
(4
.13
")ø 24,7 mm
(0.97")
1" NPT
1 2
3
SW 27 mm(1.06")
G½A
ø 27 mm (1.06")2
0,8
mm
(0.8
2")
45
mm
(1.7
7")
ø 18,4 mm (0.72")
ø 27,4 mm (1.08")
29
mm
(1.1
4")
48
mm
(1.8
9")
ø 25 mm (0.98")
SW 32 mm(1.26")
M30 x 1,5
1 Threaded versionG½ A,manometer connectionEN 837
2 Threaded versionG1 A, absolutely front-flush
3 Threaded version 1" suitable for PASVE
VEGABAR 55
12
3
SW 46 mm(1.81")
G1½ A
78
mm
(3.0
7")
11
8 m
m(4
.65
")4
6 m
m(1
.81
")
22
mm
(0.8
7")
ø 55 mm(2.17")
78
mm
(3.0
7")
ø 64 mm(2.52")
ø 84 mm(3.31")
1 Threaded versionG1½ A
2 Threaded versionG1½ A, 200 °C
3 Tri-Clamp version 2"
The listed drawings are only an excerpt of the available process fittings.
You can find further drawings on our homepage www.vega.
com » Downloads » Drawings.
37528-EN-100415
18 Process pressure/Hydrostatic – Pressure transmitter
37528-EN-100415
Process pressure/Hydrostatic – Pressure transmitter 19
37528-EN-100415
VEGA Grieshaber KG
Am Hohenstein 113
77761 Schiltach
Germany
Phone +49 7836 50-0
Fax +49 7836 50-201
E-Mail: [email protected]
www.vega.com
You can find at www.vega.com
l operating instructions manuals
l specification sheet
l Software
l drawings
l certificates
l approvals
and much, much more
Subject to change without prior notice 37528-EN-100415