Process pressure/Hydrostatic Pressure transmitter VEGABAR 51, 52, 53, 54, 55 Product Information

Upload: others

Post on 28-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

Process pressure/Hydrostatic

Pressure transmitter

VEGABAR 51, 52, 53, 54, 55

Product Information

Page 2: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

Contents

2 Process pressure/Hydrostatic – Pressure transmitter

Contents

1 Measuring principle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2 Type overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

3 Device selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

4 Selection criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

5 Housing overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

6 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

7 Electronics - 4 … 20 mA - two-wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

8 Electronics - 4 … 20 mA/HART - two-wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

9 Electronics - Profibus PA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

10 Electronics - Foundation Fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

11 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

12 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

Take note of safety instructions for Ex applications

Pleasenote theEx specific safety informationwhichyoucanfindonourhomepagewww.vega.com»Downloads»Approvalsandwhichcome

with every instrument. In hazardous areas you should take note of the corresponding regulations, conformity and type approval certificates of

the sensors and power supply units. The sensors must only be operated on intrinsically safe circuits. The permissible electrical values are

stated in the certificate.

37528-EN-100415

Page 3: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

1 Measuring principle

VEGABAR 51

The sensor element for measuring ranges up to 60 bar is the CERTEC®

measuring cell with rugged ceramic diaphragm.The hydrostatic pressure

of the product or the process pressure causes a capacitance change in

the measuring cell via the metal process diaphragm and the isolating

system. This change is converted into a corresponding output signal.

The sensor element for measuring ranges from 100 bar is a wire strain

gauge (DMS) on the back side of the process diaphragm. There, the

process pressure causes a resistance change, which is converted into

an appropriate output signal.

VEGABAR 52, 54

The sensor element is the CERTEC® measuring cell with flush, abrasion

resistant ceramic diaphragm. The hydrostatic pressure of the medium or

the process pressure causes a capacitance change in themeasuring cell

via the diaphragm. This change is converted into an appropriate output

signal.

16

µm 1

2

3

Fig. 1: Configuration of the CERTEC® measuring cell in VEGABAR 52

1 Diaphragm

2 Soldered glass bond

3 Base element

The CERTEC® measuring cell is also equipped with a temperature sen-

sor.The temperature value canbedisplayed via the indicatingandadjust-

ment module or processed via the signal output.

VEGABAR 52, 54 - climate compensated

The sensor element is an encapsulated CERTEC® absolute pressure

measuring cell with front-flush, abrasion-resistant ceramic diaphragm.

The hydrostatic pressure of the medium or the process pressure causes

a capacitance change in the measuring cell via the ceramic diaphragm.

This capacitance change is converted into an electrical signal, checked

against an integrated reference pressure measurement and outputted as

measured value via the output signal.

VEGABAR 53

The process pressure acts on the sensor element via the stainless steel

diaphragm. The process pressure causes a resistance change which is

converted into a corresponding output signal and outputted asmeasured

value.

For measuring ranges up to 16 bar, a piezoresistive sensor element with

internal transmission liquid is implemented, for measuring ranges from

25 bar, a strain gauge (DMS) sensor element on the back side of the

stainless steel diaphragm (dry).

1

4 3

2

Fig. 2: Configuration of the piezoresistive measuring cell in VEGABAR 53

1 Sensor element

2 Base element

3 Diaphragm

4 Silicone oil filling

VEGABAR 55

The METEC® measuring cell is the measuring unit. It consists of the

ceramic-capacitive CERTEC® measuring cell and a special, tempera-

ture-compensating isolating system.

The hydrostatic pressure of the product or the process pressure causes a

capacitance change in the measuring cell via the metallic process dia-

phragm and the isolating liquid. This change is converted into a corre-

sponding output signal.

4321

Fig. 3: Configuration of theMETEC® measuring cell in VEGABAR 55

1 Process diaphragm

2 Isolating liquid

3 FeNi adapter

4 CERTEC® measuring cell

Measuring principle

Process pressure/Hydrostatic – Pressure transmitter 3

37528-EN-100415

Page 4: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

2 Type overview

VEGABAR 51 VEGABAR 52 VEGABAR 53

Measuring cell Piezoresistive/DMS CERTEC®

Piezoresistive

Diaphragm Metal Ceramic Metal

Media gases, vapours and liquids, also

aggressive ones, at high temper-

atures

gases, vapours and liquids, also with

abrasive substances

Gas, vapours and liquids, also vis-

cous

Process fitting Thread from ½", flanges from DN 20,

boltings, isolating diaphragms each

from DN 25

Thread from 1", flanges from DN 25,

fittings for the food processing and

paper industry

Manometer connection G½ A or

½ NPT, connection G1 A or G½ A

front-flush, hygienic fittings

Material

Process fitting

316L 316L, PVDF, Hastelloy C-22, Has-

telloy C-276

316Ti

Diaphragm material 316L, Hastelloy C276, Tantalum,

gold on 316L

Al2O3 ceramic 316Ti, Elgiloy 2.4711

Measuring cell seal - FKM, EPDM, FFKM -

Isolating liquid Silicone oil, high temperature oil,

halocarbon oil, med. white oil

- Silicone oil, Halocarbon oil

Measuring range -1 … +400 bar/-100 … +4000 kPa (-

-14.5 … +5802 psig)

-1 … +72 bar/-100 … +7200 kPa (-

-14.5 … +1044 psig)

-1 … +600 bar/-100 … +6000 kPa (-

-14.5 … +8702 psig)

Smallest measuring

range

0.4 bar/40 kPa (5.802 psig) 0.1 bar/10 kPa (1.45 psig) 0.4 bar/40 kPa (5.802 psig)

Process temperature -40 … +400 °C (-40 … +752 °F) -40 … +150 °C (-40 … +302 °F) -40 … +150 °C (-40 … +302 °F)

Deviation < 0.2 % < 0.05 % < 0.075 %

Signal output l 4 … 20 mA

l 4 … 20 mA/HART

l Profibus PA

l Foundation Fieldbus

l 4 … 20 mA

l 4 … 20 mA/HART

l Profibus PA

l Foundation Fieldbus

l 4 … 20 mA

l 4 … 20 mA/HART

l Profibus PA

l Foundation Fieldbus

Indication/Adjustment l PLICSCOM

l PACTware

l VEGADIS 61

l VEGADIS 62

l PLICSCOM

l PACTware

l VEGADIS 61

l VEGADIS 62

l PLICSCOM

l PACTware

l VEGADIS 61

l VEGADIS 62

Approvals l Shipbuilding

l ATEX

l IEC

l Overfill protection

l FM

l CSA

l GOST

l Shipbuilding

l ATEX

l IEC

l Overfill protection

l FM

l CSA

l GOST

l Shipbuilding

l ATEX

l IEC

l Overfill protection

l FM

l CSA

l GOST

Type overview

4 Process pressure/Hydrostatic – Pressure transmitter

37528-EN-100415

Page 5: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

VEGABAR 54 VEGABAR 55

Measuring cell CERTEC®

METEC®

Diaphragm Ceramic Metal

Media gases, vapours and liquids, also with abrasive substan-

ces

gases, vapours and liquids also with higher temperatures

Process fitting Thread from 1", flanges from DN 25, fittings for the food

processing and paper industry

Thread from 1½", flanges from DN 20, fittings for the food

processing industry

Material

Process fitting

316L 316L

Diaphragm material Al2O3 ceramic Hastelloy C-276, gold-coated, gold/rhodium-coated

Measuring cell seal FKM, EPDM, FFKM -

Isolating liquid - Med. white oil

Measuring range -1 … +72 bar/-100 … +7200 kPa (-14.5 … +1044 psig) -1 … +25 bar/-100 … +2500 kPa (-14.5 … +362.6 psig)

Smallest measuring

range

0.1 bar/10 kPa (1.45 psig) 0.1 bar/10 kPa (1.45 psig)

Process temperature -40 … +120 °C (-40 … +248 °F) -12 … +200 °C (-10 … +392 °F)

Deviation < 0.1 % < 0.075 %

Signal output l 4 … 20 mA

l 4 … 20 mA/HART

l Profibus PA

l Foundation Fieldbus

l 4 … 20 mA

l 4 … 20 mA/HART

l Profibus PA

l Foundation Fieldbus

Indication/Adjustment l PLICSCOM

l PACTware

l VEGADIS 61

l VEGADIS 62

l PLICSCOM

l PACTware

l VEGADIS 61

l VEGADIS 62

Approvals l Shipbuilding

l ATEX

l IEC

l Overfill protection

l FM

l CSA

l GOST

l Shipbuilding

l ATEX

l IEC

l Overfill protection

l FM

l CSA

l GOST

Type overview

Process pressure/Hydrostatic – Pressure transmitter 5

37528-EN-100415

Page 6: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

3 Device selection

Application areas

VEGABAR 51

The VEGABAR is a pressure transmitter with isolating diaphragm for

pressure measurement of highly corrosive and hot liquids.

VEGABAR 52, 54

VEGABAR is a pressure transmitter for use in the paper, food processing

and pharmaceutical industries as well as in water/sewage water plants.

Depending on the version, it is used for level, gauge, absolute pressure or

vacuum measurement. Measured products are gases, vapours and

liquids, also those containing abrasive substances.

VEGABAR 52, 54 - climate compensated

The version 4 … 20 mA/HART - climate-compensated is suitable for

applications under difficult conditions (cold medium and humid environ-

ment).

VEGABAR 53

VEGABAR is a pressure transmitter for measurement of overpressure,

absolute pressure or vacuum. Measured products are gases, vapours

and liquids inmeasuring ranges up to4000bar (400MPa);with front-flush

version also viscous liquids in measuring ranges up to 600 bar (60MPa).

VEGABAR 55

VEGABAR is a pressure transmitter for use in thechemical, foodprocess-

ingandpharmaceutical industries.Dependingon the version, it is used for

level, gauge, absolute pressure or vacuum measurement. Measured

products are gases, vapours and liquids, also those with higher temper-

atures.

Configuration and housing protection classes

1

2

3

Fig. 4: Example of a VEGABAR 52 with connectionG1½ A and plastic housing in

protection IP 66/IP 67

1 Housing cover with integrated indicating and adjustment module (optional)

2 Housing with electronics

3 Process fitting with measuring cell

1

2

3

45

Fig. 5: Example of a VEGABAR 51with flange and aluminiumhousing in protection

IP 66/IP 68, 1 bar

1 Housing cover with integrated indicating and adjustment module (optional)

2 Housing with electronics

3 Process fitting with measuring cell

4 Cable gland

5 Connection cable

1

2

3

5

4

Fig. 6: Example of a VEGABAR 51 with flange and stainless steel housing in pro-

tection IP 68 and external electronics

1 Housing cover with integrated indicating and adjustment module (optional)

2 Housing with electronics

3 Housing socket

4 Connection cable

5 Process fitting with measuring cell

Device selection

6 Process pressure/Hydrostatic – Pressure transmitter

37528-EN-100415

Page 7: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

4 Selection criteria

VEGABAR

51

VEGABAR

52

VEGABAR

53

VEGABAR

54

VEGABAR

55

Front-flush version ● ● ● ● ●

Dry measuring system – ● – ● –

Oil filled measuring system ● – ● – ●

Abrasive wear – ● – ● –

Aggressive products ● – ● – ●

Max. process temperature

120 °C (248 °F) ● ● ● ● ●

150 °C (302 °F) ● ● ● – ●

200 °C (302 °F) ● – – – ●

400 °C (752 °F) ● – – – –

Hygienic process fittings ● ● ● – ●

Measuring ranges greater than 25 bar

(2500 kPa)

● ● ● ● –

Measuring ranges greater than 72 bar

(7200 kPa)

● – ● – –

Small measuring range 0.1 bar

(10 kPa)

– ● – ● ●

Vacuum applications up to 1 mbarabs(100 Pa)

– ● – – –

Suitability for industry-specific ap-

plications

Aggregates and min-

ing industry

– ● – – ●

Chemical ● ● – – –

Power generation ● ● – – –

Sanitary ● ● ● – ●

Metal generation – ● ● – –

Offshore ● ● – – –

Paper ● ● ● ● ●

Petrochemistry ● ● – – ●

Pharmaceutical ● ● – – ●

Shipbuilding – ● ● ● –

Environment and recy-

cling industry

– ● – – –

Water and waste water

industry

– ● – – –

Cement industry – ● – – ●

Selection criteria

Process pressure/Hydrostatic – Pressure transmitter 7

37528-EN-100415

Page 8: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

5 Housing overview

Plastic PBT

Protection rating IP 66/IP 67 IP 66/IP 67

Version Single chamber Double chamber

Application area Industrial environment Industrial environment

Aluminium

Protection rating IP 66/IP 67, IP 66/IP 68 (1 bar) IP 66/IP 67, IP 66/IP 68 (1 bar)

Version Single chamber Double chamber

Application area Industrial environment with increased

mechanical wear

Industrial environment with increased

mechanical wear

Stainless steel 316L

Protection rating IP 66/IP 67 IP 66/IP 67, IP 66/IP 68 (1 bar) IP 66/IP 67, IP 66/IP 68 (1 bar)

Version Single chamber electropolished Single chamber precision casting Double chamber precision casting

Application area Aggressive environment, food pro-

cessing, pharmaceutical

Aggressive environment, strong me-

chanical wear

Aggressive environment, strong me-

chanical wear

Separate version

Material Stainless steel 316L plastic PBT

Protection rating IP 68 (25 bar) IP 65

Function Transmitter External electronics

Application area Extremely moist environment Industrial environment

Housing overview

8 Process pressure/Hydrostatic – Pressure transmitter

37528-EN-100415

Page 9: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

6 Mounting

Mounting positionThe instruments function in any installation position. But the installation

position can influence the measurement, depending on the measuring

system. This can be compensated by a position correction.

It is useful to select an installation position you can easily reach formount-

ing and connecting as well as later retrofitting of an indicating and adjust-

ment module. For this purpose, the housing can be rotated by 330° with-

out the use of any tools.You can also install the indicating andadjustment

module in four different positions (each displaced by 90°).

Mounting examplesThe following illustrations show mounting examples and measurement

setups.

Reaction vessel

Fig. 7: Level measurement in reaction vessel with VEGABAR 51

VEGABAR 51 can be also used under high temperatures.The instrument

measures the hydrostatic pressure of the liquid column independent of

foam on the product surface. Its advantages are the high resistance dia-

phragm materials and the low oil volume of the isolating diaphragm.

Hence the temperature influence of the isolating diaphragm is kept low.

Drinking water network

Fig. 8: Pressure measurement on the drinking water network with VEGABAR 52

Thewater pressure in drinkingwater networks is continuouslymonitored.

Because pumping stations are often situated in remote areas, there is a

great demand for maintenance free, reliable measurement technology.

The VEGABAR 52 pressure transmitter meets these requirements.With

its robust ceramic CERTEC® measuring cell, VEGABAR 52 is the best

choice for monitoring pressure in pipeline systems.

Chemical pump

Fig. 9: Dry run protection on a chemical pump with VEGABAR 53

TheVEGABAR53pressure transmitterwithpiezoresistivemeasuringcell

andmetal diaphragm is deployed as dry run protection system for chem-

ical pumps. Its strengths are the small, front-flush process fitting, also for

small tube diameters, as well as the chemically resistant process dia-

phragm.

Storage tower

Fig. 10: Level measurement on storage towers with VEGABAR 54

In thepaper industry, the prepared stock is stored in large storage towers.

Level measurement in the lower section prevents the agitator from run-

ningdry.For thispurpose, theVEGABAR54pressure transmitterwithball

valve fitting is used. The advantages are: front-flush mounting in the ball

valve fitting, mounting and dismounting without emptying the storage

tower.

Mounting

Process pressure/Hydrostatic – Pressure transmitter 9

37528-EN-100415

Page 10: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

Bitumen vessel

Fig. 11: Level measurement in a bitumen vessel with VEGABAR 55

VEGABAR 55 pressure transmitters are particularly suitable for hydro-

static level measurement of hot bitumen. The special configuration of its

metalMETEC®measuringcell ensures temperature decouplingbetween

process fitting and electronics and thus enables application up to 200 °C

(392 °F).

Mounting

10 Process pressure/Hydrostatic – Pressure transmitter

37528-EN-100415

Page 11: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

7 Electronics - 4… 20mA - two-wire

Configuration of the electronicsThe pluggable electronics is mounted in the electronics compartment of

the instrument and can be exchanged by the user when servicing is re-

quired. The electronics is completely encapsulated to protect against

vibration and moisture.

The terminals for voltage supply as well as the plug with I²C interface for

parameter adjustment are located on the upper side of the electronics.

With thedouble chamberhousing, theseconnectionelementsare located

in the separate connection compartment.

Voltage supplyDepending on the version, the supply voltage and the current signal are

carried on the same two-wire connection cable.

The VEGA power supply units VEGATRENN 149AEx, VEGASTAB 690,

VEGADIS 371 as well as VEGAMET signal conditioning instruments are

suitable for power supply. When one of these instruments is used, a

reliable separation of the supply circuits from themains circuits according

to DIN VDE 0106 part 101 is ensured for the sensor.

l Operating voltage

- 12… 36 V DC

l Permissible residual ripple

- Upp < 1 V (< 100 Hz)

- Upp < 10mV (100… 10 kHz)

Connection cableThe sensors are connected with standard cable without screen. An outer

cable diameter of 5 … 9 mm ensures the seal effect of the cable entry.

If electromagnetic interference is expectedwhich is above the test values

of EN 61326 for industrial areas, screened cable should be used.

Cable screening and groundingIf screened cable is necessary, the cable screen must be connected on

both ends to ground potential. If potential equalisation currents are ex-

pected, the connectionon theevaluationsidemustbemadevia aceramic

capacitor (e.g. 1 nF, 1500 V).

Connection single chamber housing

I²C

Display

1 2 5 6 7 8

3

4

1

2

Fig. 12: Electronics and connection compartment with single chamber housig

1 Plug connector for VEGACONNECT (I²C interface)

2 Spring-loaded terminals for connection of the external indicationVEGADIS 61

3 Ground terminal for connection of the cable screen

4 Spring-loaded terminals for voltage supply

Connection double chamber housing

3

1

2

Dis

play

1 2 I²C

Fig. 13: Connection compartment, double chamber housing

1 Plug connector for VEGACONNECT (I²C interface)

2 Ground terminal for connection of the cable screen

3 Spring-loaded terminals for voltage supply

Electronics - 4 … 20 mA - two-wire

Process pressure/Hydrostatic – Pressure transmitter 11

37528-EN-100415

Page 12: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

8 Electronics - 4… 20mA/HART - two-wire

Configuration of the electronicsThe pluggable electronics is mounted in the electronics compartment of

the instrument and can be exchanged by the user when servicing is re-

quired. The electronics is completely encapsulated to protect against

vibration and moisture.

The terminals for voltage supply as well as the plug with I²C interface for

parameter adjustment are located on the upper side of the electronics.

With thedouble chamberhousing, theseconnectionelementsare located

in the separate connection compartment.

Voltage supplyDepending on the version, the supply voltage and the current signal are

carried on the same two-wire connection cable.

The VEGA power supply units VEGATRENN 149AEx, VEGASTAB 690,

VEGADIS 371 as well as VEGAMET signal conditioning instruments are

suitable for power supply. When one of these instruments is used, a

reliable separation of the supply circuits from themains circuits according

to DIN VDE 0106 part 101 is ensured for the sensor.

l Operating voltage

- 12… 36 V DC

l Permissible residual ripple

- Upp < 1 V (< 100 Hz)

- Upp < 10mV (100… 10 kHz)

Connection cableThe sensors are connected with standard cable without screen. An outer

cable diameter of 5 … 9 mm ensures the seal effect of the cable entry.

If electromagnetic interference is expectedwhich is above the test values

ofEN61326 for industrial areas, screenedcable shouldbeused. InHART

multidrop mode the use of screened cable is generally recommended.

Cable screening and groundingIf screened cable is necessary, the cable screen must be connected on

both ends to ground potential. If potential equalisation currents are ex-

pected, the connectionon theevaluationsidemustbemadevia aceramic

capacitor (e.g. 1 nF, 1500 V).

Connection single chamber housing

I²C

Display

1 2 5 6 7 8

3

4

1

2

Fig. 14: Electronics and connection compartment with single chamber housig

1 Plug connector for VEGACONNECT (I²C interface)

2 Spring-loaded terminals for connection of the external indicationVEGADIS 61

3 Ground terminal for connection of the cable screen

4 Spring-loaded terminals for voltage supply

Connection double chamber housing

3

1

2

Dis

play

1 2 I²C

Fig. 15: Connection compartment, double chamber housing

1 Plug connector for VEGACONNECT (I²C interface)

2 Ground terminal for connection of the cable screen

3 Spring-loaded terminals for voltage supply

Electronics - 4 … 20 mA/HART - two-wire

12 Process pressure/Hydrostatic – Pressure transmitter

37528-EN-100415

Page 13: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

9 Electronics - Profibus PA

Configuration of the electronicsThe pluggable electronics is mounted in the electronics compartment of

the instrument and can be exchanged by the user when servicing is re-

quired. The electronics is completely encapsulated to protect against

vibration and moisture.

The terminals for voltage supply as well as the plug with I²C interface for

parameter adjustment are located on the upper side of the electronics.

With thedouble chamberhousing, theseconnectionelementsare located

in the separate connection compartment.

Voltage supplyPower supply via the H1 Fieldbus cable.

l Operating voltage

- 9… 32 V DC

l Max. number of sensors with DP/PA segment coupler

- 32

l Max. number of sensors with VEGALOG 571 EP input card

- 10

Connection cableConnection is made with screened cable according to Profibus specifi-

cation. A cable diameter of 5… 9mmensures the seal effect of the cable

gland.

Make sure that the entire installation is carried out according to the Pro-

fibus specification. In particular,make sure that the termination of the bus

is done with appropriate terminating resistors.

Cable screening and groundingInsystemswithpotential equalisation,connect thecable screendirectly to

groundpotential at the power supply unit, in the connection box andat the

sensor. The screen in the sensor must be connected directly to the inter-

nal ground terminal. The ground terminal outside on the housing must be

connected to the potential equalisation (low impedance).

In systems without potential equalisation, connect the cable screen di-

rectly to groundpotential at the power supply unit and at the sensor. In the

connection box or T-distributor, the screen of the short stub to the sensor

must not be connected togroundpotential or to another cable screen.The

cable screens to the power supply unit and to the next distributor must be

connected to each other and also connected to ground potential via a

ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equal-

isationcurrents are thussuppressed,but theprotectiveeffectagainsthigh

frequency interference signals remains.

Connection single chamber housing

I²C

Display

1 2 5 6 7 8

3

4

1

2

Fig. 16: Electronics and connection compartment with single chamber housig

1 Plug connector for VEGACONNECT (I²C interface)

2 Spring-loaded terminals for connection of the external indicationVEGADIS 61

3 Ground terminal for connection of the cable screen

4 Spring-loaded terminals for voltage supply

Connection double chamber housing

3

1

2

Dis

play

1 2 I²C

Fig. 17: Connection compartment, double chamber housing

1 Plug connector for VEGACONNECT (I²C interface)

2 Ground terminal for connection of the cable screen

3 Spring-loaded terminals for voltage supply

Electronics - Profibus PA

Process pressure/Hydrostatic – Pressure transmitter 13

37528-EN-100415

Page 14: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

10 Electronics - Foundation Fieldbus

Configuration of the electronicsThe pluggable electronics is mounted in the electronics compartment of

the instrument and can be exchanged by the user when servicing is re-

quired. The electronics is completely encapsulated to protect against

vibration and moisture.

The terminals for voltage supply as well as the plug with I²C interface for

parameter adjustment are located on the upper side of the electronics.

With thedouble chamberhousing, theseconnectionelementsare located

in the separate connection compartment.

Voltage supplyPower supply via the H1 Fieldbus cable.

l Operating voltage

- 9… 32 V DC

l max. number of sensors

- 32

Connection cableConnection is made with screened cable according to Fieldbus specifi-

cation. A cable diameter of 5… 9mmensures the seal effect of the cable

gland.

Make sure that the entire installation is carried out according to the Field-

bus specification. Inparticular,makesure that the terminationof thebus is

done with appropriate terminating resistors.

Cable screening and groundingInsystemswithpotential equalisation,connect thecable screendirectly to

groundpotential at the power supply unit, in the connection box andat the

sensor. The screen in the sensor must be connected directly to the inter-

nal ground terminal. The ground terminal outside on the housing must be

connected to the potential equalisation (low impedance).

In systems without potential equalisation, connect the cable screen di-

rectly to groundpotential at the power supply unit and at the sensor. In the

connection box or T-distributor, the screen of the short stub to the sensor

must not be connected togroundpotential or to another cable screen.The

cable screens to the power supply unit and to the next distributor must be

connected to each other and also connected to ground potential via a

ceramic capacitor (e.g. 1 nF, 1500 V). The low frequency potential equal-

isationcurrents are thussuppressed,but theprotectiveeffectagainsthigh

frequency interference signals remains.

Connection single chamber housing

I²C

3

4

5 1

2

Display

Typ:

1 2 5 6 7 8

Bus

Sim

.

Fig. 18: Electronics and connection compartment with single chamber housig

1 Plug connector for VEGACONNECT (I²C interface)

2 Spring-loaded terminals for connection of the external indicationVEGADIS 61

3 Ground terminal for connection of the cable screen

4 Spring-loaded terminals for Foundation Fieldbus connection

5 Simulation switch ("on" = mode for simulation release)

Connection double chamber housing

3

1

2

Dis

play

1 2 I²C

Fig. 19: Connection compartment, double chamber housing

1 Plug connector for VEGACONNECT (I²C interface)

2 Ground terminal for connection of the cable screen

3 Spring-loaded terminals for voltage supply

Electronics - Foundation Fieldbus

14 Process pressure/Hydrostatic – Pressure transmitter

37528-EN-100415

Page 15: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

11 Operation

11.1 Overview

The sensors can be adjusted with the following adjustment media:

l with indicating and adjustment module

l an adjustment software according to FDT/DTM standard, e.g.

PACTware and PC

and, depending on the signal output, also with:

l A HART handheld (4 … 20 mA/HART)

l The adjustment program AMS (4 … 20 mA/HART and Foundation

Fieldbus)

l The adjustment program PDM (Profibus PA)

l A configuration tool (Foundation Fieldbus)

The enteredparameters are generally saved in the sensor,optionally also

in the indicating and adjustment module or in the adjustment program.

11.2 Adjustment with the indicating and adjust-

ment module PLICSCOM

The pluggable indicating and adjustment module is used for measured

value indication, adjustment and diagnosis with level and pressure sen-

sors. It is equippedwithadisplaywith full dotmatrix aswell as four keys for

adjustment. An integrated background lighting can be adjusted via the

adjustment menu.

Fig. 20: Indicating and adjustment module PLICSCOM

The indicating and adjustment module is integrated in the respective

sensor housing or in the external indicating and adjustment unit. After

mounting, the sensor and the indicating and adjustment module are

splash-proof even without housing cover.

11.3 Adjustment with PACTware

PACTware/DTMIndependent of the respective signal output 4 … 20 mA/HART, Profibus

PA or Foundation Fieldbus, the sensors can be adjusted with PACTware

directly on site. The sensors with signal output 4… 20mA/HART can be

also operated via the HART signal on the signal cable.

A VEGACONNECT interface adapter as well as an instrument driver for

the respective sensor is necessary for adjustment with PACTware. All

currently available VEGA DTMs are included as a DTM Collection with

the current PACTware version on a CD. They can be purchased for a

token fee from the responsible VEGA agency. In addition, this DTM Col-

lection incl. the basic version of PACTware can be downloaded free of

charge from the Internet.

To use the entire range of functions of aDTM, includingproject documen-

tation, aDTM licence is required for that particular instrument family. This

licence can be bought from the VEGA agency serving you.

Connection of the PC via VEGACONNECT

2

4

3

1

Fig. 21: Connection via I²C connection cable

1 I²C bus interface on the sensor

2 I²C cable of VEGACONNECT

3 VEGACONNECT

4 USB cable to the PC

5 PC

Necessary components:

l VEGABAR

l PC with PACTware and suitable VEGA DTM

l VEGACONNECT

l Power supply unit or processing system

11.4 Adjustment with other adjustment pro-

grams

PDM

For VEGA Profibus PA sensors, instrument descriptions for the adjust-

ment program PDM are available as EDD. The instrument descriptions

arealready implemented in thecurrent versionofPDM.For older versions

of PDM, a free-of-charge download is available via Internet.

AMS

For VEGA Foundation Fieldbus sensors, instrument descriptions for the

adjustment programAMS™ are available asDD.The instrument descrip-

tions are already implemented in the current version of AMS™. For older

versions of AMS™, a free-of-charge download is available via Internet.

Operation

Process pressure/Hydrostatic – Pressure transmitter 15

37528-EN-100415

Page 16: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

Dimensions

16 Process pressure/Hydrostatic – Pressure transmitter

12 Dimensions

Plastic housing

1 2

~ 69 mm(2.72")

ø 77 mm(3.03")

11

2 m

m (

4.4

1")

M20x1,5/½ NPT

~ 87 mm (3.43")

M16x1,5

ø 84 mm(3.31")

12

0 m

m (

4.7

2")

M20x1,5/½ NPT

1 Single chamber housing

2 Double chamber housing

Aluminium housing

~ 116 mm (4.57")

ø 84 mm (3.31")

11

6 m

m (

4.5

7")

M20x1,5M20x1,5/½ NPT

21

~ 87 mm (3.43")

M16x1,5

ø 84 mm(3.31")

12

0 m

m (

4.7

2")

M20x1,5/½ NPT

1 Single chamber housing

2 Double chamber housing

Stainless steel housing

~ 69 mm(2.72")

ø 77 mm(3.03")

11

7 m

m (

4.6

1")

M20x1,5/½ NPT

~ 59 mm(2.32")

ø 80 mm(3.15")

11

2 m

m (

4.4

1")

M20x1,5/½ NPT

321

~ 87 mm (3.43")

M16x1,5

ø 84 mm(3.31")

12

0 m

m (

4.7

2")

M20x1,5/½ NPT

1 Single chamber housing electropolished

2 Single chamber housing precision casting

2 Double chamber housing precision casting

VEGABAR 51

Rd

78

x1,6

10

6 m

m (

4.1

7")

50

mm

(1.9

7")

156 mm(6.14")

12

2 m

m (

4.8

0")

1 2

1 Flange version

2 Version with tube isolating diaphragm

VEGABAR 52

21 3

SW 27 mm(1.06")G½ A

23

mm

(0.9

1")

73

mm

(2.8

7")

70

mm

(2.7

6")

17

mm

(0.6

7")

3 m

m(0

.12

")

20

mm

(0.7

9")

3 m

m(0

.12

")

ø 3 mm (0.12")

ø 6 mm (0.24")

ø 17,5 mm (0.69")

ø 40 mm (0.69")

SW 46 mm(1.81")

G1½ A

50

mm

(1.9

7")

22

mm

(0.8

7")

ø 55 mm (2.17")

1 Threaded versionG½ A,manometer connectionEN 837

2 Threaded versionG½ A, innerG¼ A

3 Threaded versionG½ A, innerG¼ A, PVDF

VEGABAR 53

1 2 3

G½ A 63

mm

(2.4

8")

65

mm

(2.5

6")

65

mm

(2.5

6")

20

,5 m

m(0

.81

")1

0 m

m(0

.39

")

20

,5 m

m(0

.81

")

10

mm

(0.3

9")

ø 18 mm (0.71")

ø 30 mm (1.18")

G½ A

G1 A

SW 41 mm(1.61")

SW 27 mm(1.06")

23

mm

(0.9

1")

3 m

m(0

.12

") ø 3 mm (0.12")

ø 6 mm (0.24")

ø 40 mm (0.69")

1 Threaded versionG½ A,manometer connectionEN 837

2 Threaded versionG½ A, front-flush

3 Threaded versionG1 A, front-flush

37528-EN-100415

Page 17: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

Process pressure/Hydrostatic – Pressure transmitter 17

VEGABAR 54

SW 36 mm(1.42")

ø 29,3 mm (1.15")

30

mm

(1.1

8")

10

4,8

mm

(4

.13

")ø 24,7 mm

(0.97")

1" NPT

1 2

3

SW 27 mm(1.06")

G½A

ø 27 mm (1.06")2

0,8

mm

(0.8

2")

45

mm

(1.7

7")

ø 18,4 mm (0.72")

ø 27,4 mm (1.08")

29

mm

(1.1

4")

48

mm

(1.8

9")

ø 25 mm (0.98")

SW 32 mm(1.26")

M30 x 1,5

1 Threaded versionG½ A,manometer connectionEN 837

2 Threaded versionG1 A, absolutely front-flush

3 Threaded version 1" suitable for PASVE

VEGABAR 55

12

3

SW 46 mm(1.81")

G1½ A

78

mm

(3.0

7")

11

8 m

m(4

.65

")4

6 m

m(1

.81

")

22

mm

(0.8

7")

ø 55 mm(2.17")

78

mm

(3.0

7")

ø 64 mm(2.52")

ø 84 mm(3.31")

1 Threaded versionG1½ A

2 Threaded versionG1½ A, 200 °C

3 Tri-Clamp version 2"

The listed drawings are only an excerpt of the available process fittings.

You can find further drawings on our homepage www.vega.

com » Downloads » Drawings.

37528-EN-100415

Page 18: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

18 Process pressure/Hydrostatic – Pressure transmitter

37528-EN-100415

Page 19: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

Process pressure/Hydrostatic – Pressure transmitter 19

37528-EN-100415

Page 20: &REF prod info EN; VEGABAR 51, 52, 53, 54, 55 - …...2 Housingwith electronics 3 Process fittingwith measuringcell 4 Cable gland 5 Connectioncable 1 2 3 5 4 Fig. 6: Example of a

VEGA Grieshaber KG

Am Hohenstein 113

77761 Schiltach

Germany