RICE ENGINEERING
105 School Creek Trail | Luxemburg, WI 54217 (P) 920.617.1042 | (F) 920.617.1100
Panel Grip 2 - Fascia Mount Guardrail
Testing to Conform ASTM E985
Project Location:
Milwaukee, Wisconsin
Prepared for:
R&B Wagner, Inc. - Milwaukee, WI REI Project # R16-02-285 5/17/2016
Disclaimer:
This Certification is limited to the structural design of
structural components of this handrail or divider system.
It does NOT include responsibility for:
• Structural design of misc. hardware (latches, hinges, etc.).
• Structural design of concrete slabs and other masonry units
• Structural design of wood blocking or wood framing
• Structural design of all other anchorage substrates
• Glass breakage due to airborne debris or foreign objects
• The manufacture, assembly, or installation of the system.
• Quantities of materials or dimensional accuracy of drawings
Cover Page 1 of 2
Engineer Prepared And Witnessed Approval Stamp:
Pr��ect Sc�pe�
Rice E�gi�eeri�g was c �tacted by R&B Wag�er� I�c� t wit�ess testi�g f their Pa�e� Grip 2 fascia sh e guardrai� syste � specifica��y the a u�t f def�ecti � that w u�d ccur i�!
3#4% thic& � �ithic te pered g�ass
3#4% thic& te pered SGP �a i�ated g�ass
3#4% thic& te pered PVB �a i�ated g�ass
5#8% thic& te pered SGP �a i�ated g�ass (Thic& -ut)� 5#8% thic& te pered SGP �a i�ated g�ass (Thi� -ut)
5#8% thic& te pered PVB �a i�ated g�ass (Thic& -ut)� 5#8% thic& te pered PVB �a i�ated g�ass (Thi� -ut)
21�5 thic& te pered SGP �a i�ated g�ass
21�5 thic& te pered PVB �a i�ated g�ass
Whe� pu��ed t desig� � ads as described i� AST1 E985�
-� 1arch 29� 2016 Tauri� Garcia� P�E� f Rice E�gi�eeri�g wit�essed testi�g f r the �i�e differe�t c �figurati �s� The testi�g was perf r ed �5site at the R&B Wag�er faci�ity a�d was c �ducted by 6e��y Bauser a� a�d 7usti� Wesser�
This rep rt is ��y i�te�ded t a�a�y8e the def�ecti � f the vari us g�ass types� The structura� i�tegrity f the base sh e� a�ch rs a�d a�ch r substrate is utside the sc pe f this rep rt� It sh u�d be � ted that up � bservati �� � visua� da age t the sh e� a�ch rs r c �crete barrier was bserved after a�� testi�g was c p�eted�
C� c�usi� s�
See sheets! A3 53#4% thic& � �ithic te pered g�ass� A5 5 3#4% thic& te pered SGP �a i�ated g�ass� A7 5 3#4% thic& te pered PVB �a i�ated g�ass� A9 – 5#8% thic& te pered SGP �a i�ated g�ass (Thic& -ut)� A11 5 5#8% thic& te pered SGP �a i�ated g�ass (Thi� -ut)� A13 5 5#8% thic& te pered PVB �a i�ated g�ass (Thic& -ut)� A15 5 5#8% thic& te pered PVB �a i�ated g�ass (Thi� -ut)�A17 521�5 thic& te pered SGP �a i�ated g�ass a�d A19 521�5 thic& te pered PVB �a i�ated g�ass�
RICE ENGINEERING
105 School Creek Trail | Luxemburg, WI 54217 (P) 920.617.1042 | (F) 920.617.1100
Panel Grip 2 - Fascia Mount Guardrail
Testing to Conform ASTM E985
Project Location:
Milwaukee, Wisconsin
Prepared for:
R&B Wagner, Inc. - Milwaukee, WI REI Project # R16-02-285 5/17/2016
Disclaimer:
This Certification is limited to the structural design of
structural components of this handrail or divider system.
It does NOT include responsibility for:
• Structural design of misc. hardware (latches, hinges, etc.).
• Structural design of concrete slabs and other masonry units
• Structural design of wood blocking or wood framing
• Structural design of all other anchorage substrates
• Glass breakage due to airborne debris or foreign objects
• The manufacture, assembly, or installation of the system.
• Quantities of materials or dimensional accuracy of drawings
Cover Page 2 of 2
Engineer Prepared And Witnessed Approval Stamp:
Page: Description: Date: Revision:
A1 Master Table
-3/4” thick monolithic
tempered glass
-3/4” thick tempered SGP
laminated glass
-3/4” thick tempered PVB
laminated glass
-5/8” thick tempered SGP
laminated glass (Thick Out)
-5/8” thick tempered SGP
laminated glass (Thin Out)
-5/8” thick tempered PVB
laminated glass (Thick Out) -
5/8” thick tempered PVB
laminated glass (Thin Out)
5/6/16
A2 Master Table
21.5 mm SGP Glass
21.5 mm PVB Glass
5/6/16
A3 Railing System Load /
Deflection Testing
3/4” monolithic glass
5/6/16
A4 Test Photos
3/4” monolithic glass
A5 Railing System Load /
Deflection Testing
3/4” SGP Glass
5/6/16
A6 Test Photos
3/4” SGP Glass
5/6/16
A7 Railing System Load /
Deflection Testing
3/4” PVB Glass
5/6/16
A8 Test Photos
3/4” PVB Glass
5/6/16
Page: Description: Date: Revision:
A9 Railing System Load /
Deflection Testing
5/8” SGP Glass (Thick Out)
5/6/16
A10 Test Photos
5/8” SGP Glass (Thick Out)
5/6/16
A11 Railing System Load /
Deflection Testing
5/8” SGP Glass (Thin Out)
5/6/16
A12 Test Photos
5/8” SGP Glass (Thin Out)
5/6/16
A13 Railing System Load /
Deflection Testing
5/8” PVB Glass (Thick Out)
5/6/16
A14 Test Photos
5/8” PVB Glass (Thick Out)
5/6/16
A15 Railing System Load /
Deflection Testing
5/8” PVB Glass (Thin Out)
5/6/16
A16 Test Photos
5/8” PVB Glass (Thin Out)
5/6/16
A17 Railing System Load /
Deflection Testing
21.5 mm SGP Glass
5/6/16
A18 Test Photos
21.5 mm SGP Glass
5/6/16
A19 Railing System Load /
Deflection Testing
21.5 mm PVB Glass
5/6/16
A20 Test Photos
21.5 mm SGP Glass
5/6/16
Sheet A1
Sheet A2
Sheet A3
Sheet A4
Sheet A5
Sheet A6
Sheet A7
Sheet A8
Sheet A9
Sheet A10
Sheet A11
Sheet A12
Sheet A13
Sheet A14
Sheet A15
Sheet A16
Sheet A17
Sheet A18
Sheet A19
Sheet A20