Ringmaster range General contents
Presentation 3
Ring main units 15
Circuit breaker, metering and switches 35
Remote control 83
Installation drawings 87
Schematic diagrams 99
Accessories 141
Schneider Electric, an overview and order form 149
2 AMTED399086EN.indd
3AMTED399086EN.indd
Presentation Contents
Applications 4
Switchgear description 5
VIP protection relays 7
Sepam series 10 8
Network remote control 12
Ringmaster selection guide 14
4 AMTED399086EN.indd
Presentation Applications
Ringmaster is the ideal choice for all your MV applications. From simple transformer protection, or sectionalising with remote control, to multi-panel metered consumer switchboards, the Ringmaster range from Schneider Electric offers a solution.
Quality engineering for extreme climates enables Ringmaster to provide fl exibility for any location.
Covering a wide range of options with an indoor and outdoor IP54 design and ratings up to 13.8 kV, 630 A and 21 kA, Ringmaster has proved successful in markets around the world.
Product advantages Simple, clear operation combined with compact size, high functionality and reliability extends the applications of the Ringmaster range.
Safety to personnelFully certifi ed internal arc design.
Indoor/outdoor designNo need for expensive switchrooms.
Self powered protectionNot reliant on costly battery chargers.
CompactReduced dimensions, gives reduced civil costs.
Virtually maintenance freeLow lifetime costs.
Modular designQuick, simple & easy to install.
Proven designAssured consistent quality.ISO 9001 quality certifi cation.
EnvironmentalManufactured to ISO 14001 environmental standards.P
E40
438
5AMTED399086EN.indd
Presentation Switchgear description
PE
5706
1
A variety of different panel types are available for each unit within the range, together with a number of optional accessories enabling Ringmaster to satisfy the most complex system specifi cation.
A multitude of confi gurations
Free standing, non-extensible, cable connected ring main unit.
Transformer mounted, non-extensible ring main unit, incorporated in a packaged substation.
Free standing, extensible cable connected ring main unit
Transformer mounted, extensible ring main unit, incorporated in a packaged substation.
Free standing, non-extensible circuit breaker.
Cable connected extensible switchboard.
PE
5706
4
PE
5706
2
PE
5706
5
PE
5706
3
PE
5706
6
6 AMTED399086EN.indd
Presentation Switchgear description
General characteristics b Gas pressure indicator as standard b Anti-refl ex operating handle with facilities for electrical operation b Interlocked MV cable test access (no need to remove cable terminations or use
loose earthing devices)
b Integral self-powered protection with TFL, adjustable curve & relay options b IP54 enclosure b Simple to follow mimic providing user-friendly operation b Earth screened cast-resin gas module
b Range of dry type metering units b Mechanical tripped on-fault indication b Resin encapsulated busbars in air bus chamber for extensible version b Direct coupling to transformers or cable connection.
Standard and quality assuranceManufactured to BS EN ISO 9001. Ringmaster meets the following standards and has obtained approval from the UK Electricity Association: IEC 62271-100, IEC 60265, IEC 62271-200, BS EN 60265 and ENA TS 41-36.Environmental Management System BSEN ISO 14001 OHSAS 18001 Management of Health and Safety.
PE
5706
7
7AMTED399086EN.indd
Presentation VIP protection relays Self-powered reliability
PE
5716
0
VIP 300 b Pick-up current ranges: RN2c, RE2c, CN2, CE2
Overcurrent: 20-200 A. Earth fault: 2-160 A. CE6 and RN6c Overcurrent: 80-800 A. Earth fault: 8 A to 640 A.Hardened electronics Certifi ed EMC performance to IEC 60255 and EN 50061, EN50082.
b Separate overcurrent and earth fault trip indication. b Flashing LED’s indicate when the relay is operating under
fault conditions.
PE
5715
9
VIP 35provides protection against phase-to-phase faults and earth faults.
PE
5682
6
VAP 6
VIP 300 - the leading protection relay providing a wide range of selectivity and quality of supplyThe VIP 300 is a three phase overcurrent and earth fault protection device, providing protection for networks and equipment. Being an integral part of the highly successful Ringmaster range, its main function is to detect phase and earth faults within the network and to trip the circuit breaker.
FlexibilityThe relay provides for a wide range of protection settings for most applications. The IDMT characteristics employed for both the overcurrent and earth fault elements can be easily adjusted to provide discrimination with upstream MV and downstream LV protective devices. Fast power-up of the VIP 300 also provides immediate protection and can detect faults instructing the CB to trip in less than 40 ms.
ReliabilityThe relay has a self monitoring device and diagnostic routine that constantly checks the operation of the relay automatically.
Self-powered reliabilityThe VIP 300 protection relay is a self powered microprocessor based device which requires no external DC power source or batteries, making it the ideal solution for location in remote areas where auxiliary supplies are not readily available.
Ease of useVIP 300 has improved operation and control with the relay settings being clearly displayed on the front panel. Manual reset fl ags show separate ‘tripped on fault’ for either phase or earth fault conditions.
TestingThe VAP 6 hand held test unit, is available to provide a simple check of the integrity of the relay and can also be used to perform trip tests on the circuit breaker. The circuit breaker “trip inhibit” facility allows the relay to be tested without tripping the circuit breaker. Secondary injection can be carried out using conventional test equipment.
The VIP 30 and VIP 35 are self-powered devices, requiring no external DC power source or batteries. They are designed for use in distribution networks providing protection for transformers.
8 AMTED399086EN.indd
Presentation Sepam series 10P
B10
3446
Sepam series 10
Sepam series 10 is a high-quality protection relay that represents the most cost-effective solution available for essential protection functions. Highly ergonomic, it is easy to install and set up.
Sepam series 10 specifi csSepam series 10 monitors phase and/or earth-fault currents. Three models meet a wide range of different needs :
b N: Sepam series 10 N protects against earth faults b B: Sepam series 10 B protects against overloads, phase-to-phase faults and earth
faults b A: Sepam series 10 A provides the same functions as Sepam series 10 B, with
also a communication port, more inputs and outputs, and additional protection and monitoring functions.Simplicity
b Easy operation - screen, keys, pictograms, etc., good ergonomics b Fast set-up - installation, wiring, parameter setting directly on the relay without a PC.
Reliability b Guaranteed protection of life and property - high-quality product, compliance
with standards, continuous self-test b Safety of operating personnel - all accessible parts are made of insulating
materials, light and compact product with no sharp edges b Environmentally friendly - compliance with the European RoHS directive, low
energy consumption, manufacture in factory certifi ed ISO 14001 and recyclable to more than 85%.Productivity
b Attractive, cost-effective product - easy to understand, no unnecessary complications, suited to user needs
b Improved availability of electricity - precise tripping set points and times, logic discrimination, detailed information made spontaneously available to operator following tripping.
b Reduced maintenance costs - continuous self-tests to extend periods between maintenance.Functions ANSI
codeSepam series 10 N B A
ProtectionsEarth-fault protection Standard 50N/51N v v v
Sensitive v vHigh sensitivity v v v
Phase-overcurrent protection 50/51 b bThermal overload protection 49RMS b b
Phase-overcurrent and earth fault protection cold load pick-up
b b
Logic discrimination
Blocking send 68 b b bBlocking reception b
External tripping bMeasurements
Earth-fault current b b bPhase currents b bPeak demand currents b bControl and supervision
Circuit breaker tripping and lockout 86 b b bTripping indication b b bTrip-circuit supervision bRemote circuit-breaker control bRecord of last fault b bRecord of last fi ve events bCommunication
Modbus bIEC 60870-5-103 b
Inputs/Outputs (number)Earth-fault current inputs 1 1 1Phase-current inputs - 2 or 3 3Logic relay outputs 3 3 7Logic inputs - - 4Communication port - - 1 b Function available.v Function availability depends on the Sepam model.
9AMTED399086EN.indd
Presentation Sepam series 10User-machine interface and dimensions
DE
5345
1_S
E
Dimensions
DE
5345
0_S
E
1 Back-lit display2 Status LEDs3 Fault LEDs4 Button for Sepam reset and maximeter reset5 Battery housing (Sepam series 10 A)6 Protection cover for settings7 Identifi cation zone8 Lead-seal accessory9 Button for setting selection and confi rmation10 Buttons for selection in a menu11 Button to cancel entry12 Buttons for setting adjustments13 Button for menu selection and LED test14 Menu pictograms15 Cursor for menu selection
User-machine interface
Characteristics Applicable to ValueDimensions series 10 • •• • 180 x 140 x 90 mm / 7.09" x 5.51" x 3.54"Weight depending on number of current inputs
series 10 N 1• •series 10 B 3• •series 10 A 4• •
1.15 kg/2.53 pounds1.26 kg/2.78 pounds1.46 kg/3.22 pounds
Type of battery series 10 A •• • 1/2 AA Li 3.6 V
10 AMTED399086EN.indd
Presentation Sepam series 10Protection functions
Earth-fault protection (ANSI 50N-51N)Earth-fault protection detects overcurrents caused by phase-to-earth faults. It uses measurements of the fundamental component of the earth-fault current.2 independent set points (Io> and Io>>)
b The low set point (Io>) offers defi nite time (DT) or IDMT settings with various types of standardized curves (IEC, IEEE, RI) and it is possible to enable an IDMT timer hold.
b The high set point (Io>>) offers only the defi nite time (DT) setting. The minimum setting results in instantaneous operation (ANSI 50).Depending on the required level of sensitivity, there are three types of Sepam relays.Sensitivity Sensor Setting range
Standard 3 phase CTs or 1 earth-fault protection CT,with rated primary current Ino
0.1...24 Ino
Sensitive (1) 3 phase CTs or 1 earth-fault protection CT, with rated primary current Ino
0.01...2.4 Ino
High sensitivity
Special core balance CSH or GO, with ratio of 470/1 0.2...240 A primary, i.e. 0.0004...0.5 Ino
(1) Setting not available with Sepam series 10N.
Phase-overcurrent protection (ANSI 50-51)Phase-overcurrent protection detects overcurrents caused by phase-to-phase faults. It uses the measurements of the fundamental component of currents drawn from two or three phase CTs, with a secondary rating of 1 A or 5 A.2 independent set points (I> and I>>)
b The low set point (I>) offers defi nite time (DT) or IDMT settings with various types of standardized curves (IEC, IEEE, RI) and it is possible to enable an IDMT timer hold.
b The high set point (I>>) offers only the defi nite time (DT) setting.The minimum setting results in instantaneous operation (ANSI 50).
Thermal image overload protection (ANSI 49 RMS) This protection function is used to protect cables and HV/LV transformers against overloads, based on measurement of the current drawn.The function is based on a thermal model which calculates the temperature rise from current measurements. The current measured is an RMS 3-phase current which takes into account harmonics up to number 13.Two protection settings
b The continuous maximum permissible current setting which corresponds to the maximum thermal withstand of the protected devices (the continuous permissible current corresponds to a temperature rise of 100%).
b The setting for the equipment heating and cooling time constant.
DE
5322
9
t
IoIo>>Io>
DE
5322
8 t
II>>I>Ith
11AMTED399086EN.indd
Presentation Sepam series 10Protection functions
Protection function 50/51, 50N/51N Tripping curve
b DT: Defi nite time b SIT/A: IEC standard inverse b VIT/B: IEC very inverse b LTI/B: IEC long-time inverse b EIT/C: IEC extremely inverse b MI/D: IEEE moderately inverse b VI/E: IEEE very inverse b EI/F: IEEE extremely inverse b RI
I>, I>> set pointsDT curve 0.1...24 In (minimum: 1 A)IDMT curves 0.1...2.4 In (minimum: 1 A)Accuracy ±5% or ±0.02 InDrop out/pick up ratio 95% Transient overshoot < 10%
Io>, Io>> set pointsDT curve Standard version Setting range: 0.1…24 Ino
(minimum: 1 A)Sensitive version Setting range: 0.01…2.4 Ino
(minimum: 0.1 A)High sensitivity version
Rating 0.2…24 A Setting range: 0.0004…0.05 Ino(Ino = 470 A)
Rating 2.0…240 A Setting range: 0.004…0.5 Ino(Ino = 470 A)
IDMT curves Standard version Setting range: 0.2…2.4 Ino(minimum: 1 A)
Sensitive version Setting range: 0.01…0.24 Ino(minimum: 0.1 A)
High sensitivity version
Rating 0.2…24 A Setting range: 0.0004…0.005 Ino(Ino = 470 A)
Rating 2.0…240 A Setting range: 0.004…0.05 Ino(Ino = 470 A)
Accuracy ±5% or ±0.02 InoDrop out/pick up ratio 95%
Transient overshoot < 10% Time delayDT curve 0.05...300 s
IEC, RI curves TMS: 0.02...2 (step: 0.01)IEEE curve TD: 0.5...15 (step: 0.1)Accuracy DT curve: ±2% or ±20 ms
IDMT curves: ±5% or ±20 ms
Timer hold Selection: ON/OFF. Common setting for I> and Io> set points
Accuracy ±2% or ±20 ms
Characteristic timesOperation time < 40 ms at 2 x set point (typically 25 ms)
Overshoot time < 40 ms at 2 x set point
Reset time < 50 ms at 2 x set point
Protection function 49RMS Set pointsAlarm set point Setting range 50...100% of permissible thermal capacityTrip set point Setting range 0.1...2.4 In (value of permissible current)
Accuracy ±5% or ±0.02 InDrop out/pick up ratio 95%
Time delayTime constant Setting range 1...120 min in 1 min steps
Tripping-time accuracy ±2% or ±2 s
DE
5319
5
1 1052 20 I/I>
orIo/Io>
0.1
1
10
100
1000Sec
RISIT/A
VIT/B
LTI/B
EIT/C
IEC curves SI, VI, LTI, EI and RI curve
DE
5319
4
MIVI
EI
1 1052 20 I/I>orIo/Io>
0.1
Sec
1
10
100
1000
IEEE curves MI, VI, EI
12 AMTED399086EN.indd
Presentation Network remote controlT200E telecontrol
Ringmaster and T200EControl your Ringmaster from a remote position The Schneider Electric Easergy T200E telecontrol cabinet, which links the Ringmaster to a control centre’s automation system, allows you to manage a secondary distribution network from a remote point. Network faults can be identifi ed and isolated and the network reconfi gured in seconds without manual intervention, which substantially improves the quality of supply. The small and compact Easergy T200E can be easily mounted directly onto the Ringmaster, saving installation costs and valuable fl oor space.Telecontrol equipment can be added any time after installation. This makes Ringmaster RMU’s even more cost-effective to install, since a control system can be bought separately if needed at a later date. Other RTUs can also be integrated if required.
PE
5706
9
PE
5707
1
Internal view of Easergy T200E
Ringmaster C with Easergy T200E
13AMTED399086EN.indd
Presentation Network remote control Easergy L500
Continuity of service guaranteed by an overall telecontrol offerSchneider Electric offers you a complete solution, including:
b the Easergy T200 E telecontrol interface, b MT switchgear that is adapted for telecontrol.
PE
5631
2
L500 network monitoring screen
DE
4090
1EN
PE
5707
3EN
RN2C RN2C RN2C
RN2CRN2C RN2C
Network control centre
HV/MV
Communication network
MV ring
Easergy L500, a low cost solution to immediately improve your SAIDI (1)(1) SAIDI: system average interruption duration index
Easergy L500 is a SCADA providing all the functions needed to operate the MV network in real time
b Pre-confi gured with Easergy range products: v MV/LV substations equipped with T200 E or Flair 200C v overhead line equipped with Flite 116/G200 b Broad range of transmission supports: Radio, GSM, GPRS, PSTN, LL, FO.
Advantages b Simple implementation: v one to two weeks only for 20 MV/LV substations v confi guration, training and handling within a few days b Short return on investment b Simple and fast evolutions by operations managers b Service quality and operations rapidly improved.
14 AMTED399086EN.indd
Key to product referencesRingmaster is available as standard panel types, allowing easy selection and specifi cation. The product references are made up as follows:
R Ring main unit 2 200 AC Circuit breaker 6 630 AS Switch 16 16 kAN Non-Extensible 21 21 kAE ExtensibleMU Metering unitExample: CN2-T1/16 = circuit breaker, non extensible, 200 A, 16 kA fault rating.
The Ringmaster catalogue allows easy selection and specifi cation, based on a broad range of worldwide applications. Included in this publication is:
b panel type specifi cations b details of optional accessories b schematic diagrams b Installation drawings.
AccessoriesAccessories for the Ringmaster range are supplied either fi tted or loose, where stated enabling simple panel confi guration on site. Details of accessories are contained within the panel type pages.
General arrangement drawingsGeneral arrangement drawings are given for each panel type. This allows you to quickly size up switchrooms and calculate external connections at the pre-order stage.
Need more information?If your requirements are not listed, please contact your local Schneider Electric representative, or contact us on:Tel: +44 (0) 113 290 3500Email: [email protected]
Electronic catalogue requestsElectronic copies of this selection guide are available free of charge upon request. For this, and other MV literature, please email your full contact details to Email: [email protected]
RN2c RE2c RN6c MU2 or MU6 CN2 SN6 CE2 CE6 SE6200 A non extensiblering main unit
200 A extensiblering main unit
630 A non extensiblering main unit
200 A or 630 A feedermetering unit
200 A non extensiblecircuit breaker
630 Anon extensibleswitch
200 A extensiblecircuit breaker
630 A extensiblecircuit breaker
630 Aextensibleswitch
PE
5707
2Presentation Ringmaster selection guide
15AMTED399086EN.indd
Ring main units Contents
Non-extensible ring main unitsSpecifi cation Accessories
16
Non-extensible ring main units 200 ARN2c-T1, RN2c-T2, RN2c-T3, RN2c-T4, RN2c-T5, RN2c-T25
19
Non-extensible ring main units 630 ARN6c-T1, RN6c-T25
25
Extensible ring main unitsSpecifi cation Accessories
27
Extensible ring main units 200 ARE2c-T1, RE2c-T2, RE2c-T3, RE2c-T4, RE2c-T25
30
16 AMTED399086EN.indd
Ring main units Non-extensible ring main unitsSpecification
RN2c-T1TFL
RN2c-T2VIP 300
RN2c-T3VIP 30
RN2c-T4VIP 35
RN2c-T5Glass TFL
RN2c-T25Sepam 10
RN6c-T1VIP 300
RN6c-T25Sepam 10
EnvironmentIndoor / outdoor b b b b b b b b
IP54 b b b b b b b b
Transformer mounted b b b b b b
Freestanding O O O O O O b b
RatingsBusbars 630 A b b b b b b b b
Circuit breaker normal rated current 200 A b b b b b b
Circuit breaker normal rated current 630 A b b
Switch normal rated current 630 A b b b b b b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O
Ring switch cable earth switch 16 kA 3 seconds b b b b b b b b
Ring switch cable earth switch 21 kA 3 seconds O O O O O O O O
Circuit breaker earth switch 3.15 kA b b b b b b b b
MechanismIndependent manual b b b b b b b b
Provision for motorised mechanism LH ring switch b b b b b b b b
Provision for motorised mechanism RH ring switch b b b b b b b b
Provision for motorised mechanism circuit breaker O O O O O O O O
Protection & control - circuit breakerCT’s dual ratio - 100/50/5 A class X b b
CT’s ratio - 200/1 A class X b
CT’s ratio - 200/100/1 5P20 b
CT’s ratio - 500/200/1 A class X b b
CT’s ratio - 800/400/1 A class X b
CT’s ratio - 800/400/1 5P20 b
Overcurrent & earth fault CT operated trip coils - TFL b
Overcurrent & earth fault CT operated trip coils - glass TFL
b b
Overcurrent relay - VIP 30 b
Overcurrent & earth fault relay - VIP 35 b
IDMT overcurrent & earth fault relay - VIP 300 b b
IDMT Relay Sepam 10 b b
Multi voltage shunt trip coil (see accessories page 17) O O O O O b O b
IndicationMechanical ON/OFF b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b
VPIS indication 3.3 - 13.8 kV O O O O O O O O
Gas pressure indicator (-25°C to +55°C) b b b b b b b b
RSW aux contacts 1NO & 1NC O O O O O O O O
Test facilityIntegral ring cable test facility b b b b b b b b
Integral circuit breaker test facility O O O O O O b b
Standard featuresOperating handle b b b b b b b b
Cable (see available cable kit accessories)Bottom entry up 1 x 3C 300 mm2 b b b b b b b b
Bottom entry up 3 x 1C 630 mm2 b b b b b b b b
Top entry cables (indoor only) O O O O O O O O
Order codes12 kV, 16 kA, 75 kV BIL, 0.55bG RN2c-T1/16 RN2c-T2/16 RN2c-T3/16 RN2c-T4/16 RN2c-T5/16 RN6c-T1/1613.8 kV, 21 kA, 95 kV BIL, 0.8bG RN2c-T1/21 RN2c-T2/21 RN2c-T3/21 RN2c-T4/21 RN2c-T5/21 RN2c-T25/21 RN6c-T1/21 RN6c-T25/21General arrangement drawing - transformer mounted RMINST-06
Page 95RMINST-06 Page 95
RMINST-06 Page 95
RMINST-06 Page 95
RMINST-06 Page 95
RMINST-06 Page 95
RMINST-06 Page 95
RMINST-06 Page 95
General arrangement drawing - freestanding RMINST-05 Page 144
RMINST-05 Page 144
RMINST-05 Page 144
RMINST-05 Page 144
RMINST-05 Page 144
RMINST-05 Page 144
RMINST-05 Page 144
RMINST-05 Page 144
Schematic diagram - TFL RMSCH-01 Page 104
RMSCH-01 Page 104
Schematic diagram - VIP 30 RMSCH-02 Page 105
Schematic diagram - VIP 35 RMSCH-15 Page 107
Schematic diagram - VIP 300 RMSCH-03 Page 106
RMSCH-42 Page 112
Schematic diagram - Sepam 10 RMSCH-43-46 Pages 108-111
RMSCH-43-46 Pages 108-111
Key: b Standard feature O Optional feature
17AMTED399086EN.indd
Ring main units Non-extensible ring main units Accessories
RN2c-T1TFL
RN2c-T2VIP 300
RN2c-T3VIP 30
RN2c-T4VIP 35
RN2c-T5Glass TFL
RN2c-T25Sepam 10
RN6c-T1VIP 300
RN6c-T25Sepam 10
Kit no.
Cable kitsCircuit breaker cable box v v v v v v RMR-A/F47Circuit breaker cable box with integral cable test facility v v v v v v b b RMR-F325Gland plate 1 x 3C O O O O O O O O RMR-A316Gland plate 3 x 1C O O O O O O O O RMR-A319Small gland plate 1 x 3C O O O O O O O O RMR-A322Blank aluminium gland plate O O O O O O O O RMR-A320Brass wiping gland 1 x 3C O O O O O O RMR-A10Brass wiping gland 3 x 1C O O O O O O O O RMR-A11Small brass wiping gland 1 x 3C O O O O O O O O RMR-A105Tubular gland 1 x 3C O O O O O O O O RMR-A12Tubular gland 3 x 1C O O O O O O O O RMR-A13Small tubular gland O O O O O O O O RMR-A106CES5 gland O O O O O O O O RMR-A120CES5 gland plate 1 x 3C O O O O O O O O RMR-A321CES5 gland adaptor O O O O O O O O RMR-A5256 x ECON cable termination kit O O O O O O O O RMR-A3143 x STD ECON end cap O O O O O O O O RMR-A3703 x ECON cable termination kit O O O O O O O O RMR-A315Top entry cables RH cable box (indoor only) v v v v v v v v RMR-F303Top entry cables LH cable box (indoor only) v v v v v v v v RMR-F302Rsw extension box for 2 x 3C cables (left hand) v v v v v v v v RMR-F523Rsw extension box for 2 x 3C (right hand) v v v v v v v v RMR-F522Angled gland plate 1 x 3C O O O O O O O O RMR-A317Split gland plate 1 x 3C O O O O O O O O RMR-A318Installation itemsTransformer mounting kit v v v v v v v v RMR-A/F323Extension trunking (to clear transformer radiators) O O O O O O O O RMR-A20Set of padlocks - 11 no O O O O O O O O RMR-A343Anti-vandal fi xings, including tool O O O O O O O O RMR-A344Foundation bolts (not required for transformer mounting) O O O O O O O O RMR-A22Multicore pilot glands O O O O O O O O RMR-A342Time limit fuses (set of 2 - specify rating as table page 143) O O O O O O O O RMR-A17RN2c to MU2 installation kit v v v v v v v v RMR-A350Ariel mounting bracket O O O O O O O O RMR-A201Operational itemsOperating handle b b b b b b b b RMR-F345LH ring switch control auxiliary sw for motorised mechanism provision
v v v v v v v v RMR-F328
LH ring switch termination block for motorised mechanism provision (not Easergy)
v v v v v v v v RMR-F363
RH ring switch control auxiliary sw for motorised mechanism provision
v v v v v v v v RMR-F329
RH ring switch termination block for motorisedmechanism provision (not Easergy)
v v v v v v v v RMR-F364
Provision for motorised mechanism circuit breaker v v v v v v b b RMR-F543Motorised mechanism - specify voltage v v v v v v v v RMR-F507CB Termination block for motorisedmechanism provision (not Easergy)
v v v v v v v v RMR-F365
Shunt trip coil (20-250 V DC, 110-250 V AC) TLF v v v v v v v v RMR-F581Shunt trip coil (20-250 V DC, 110-250 V AC) VIP v v v v v v v v RMR-F582Ring switch cable VPIS indication (3.3-13.8 kV) v v v v v v v v RMR-F341Circuit breaker cable VPIS indication (11-13.8 kV) v v v v v v v v RMR-F340Circuit breaker cable VPIS indication (3.3-7.2 kV) v v v v v v v v RMR-F347Phase indication device O O O O O O O O RMR-A374VAP 6 test unit for VIP 300/30/35 O O O O O O O O RMR-A202Emergency trip push button v v v v v v v v RMR-F339Gas pressure switch for remote indication only v v v v v v v v RMR-F368Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site
18 AMTED399086EN.indd
Ring main units Non-extensible ring main unitsAccessories
RN2c-T1TFL
RN2c-T2VIP 300
RN2c-T3VIP 30
RN2c-T4VIP 35
RN2c-T5Glass TFL
RN2c-T25Sepam 10
RN6c-T1VIP 300
RN6c-T25Sepam 10
Kit no.
Mechanical interlocksCircuit breaker - key free, EARTH ON v v v v v v v v RMR-F337Circuit breaker - key free, MAIN OFF v v v v v v v v RMR-F338Switch - key free, SWITCH OFF LH v v v v v v v v RMR-F335Switch - key free, SWITCH OFF RH v v v v v v v v RMR-F336N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanismsEarth fault passage indication (choose provision kit and an EFPI required if not using Easergy T200E)Phase & earth fault provision for Easergy T200E O O O O O O O O RMR-F310EFPI provision kit, inside cable box O O O O O O O O RMR-A304EFPI provision kit, CT outside cable box O O O O O O O O RMR-A305EFPI provision kit, inside cable box, top entry O O O O O O O O RMR-A308EFPI provision kit, outside cable box, top entry O O O O O O O O RMR-A309Bowden “RR” EFPI and CT O O O O O O O O RMR-A422Bowden STD EFPI type NB O O O O O O O O RMR-A277Bowden LV reset EFPI type NB1 O O O O O O O O RMR-A278Bowden LV reset & alarm type NB2 O O O O O O O O RMR-A279Fundamentals ER “FIND” EFPI and CT O O O O O O O O RMR-A57N. B. above CT’s are ring type for split core - please consult Schneider ElectricKey: v Factory fi tted accessory O Loose accessory, assembled on site
19AMTED399086EN.indd
Ring main units Non-extensible ring main unit 200 A RN2c-T1
Transformer protection up to 1.6 MVA at 11 kVProtection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links Protection CT’s - 100/50/5 A class XTransformer ratingsSee table - page 147DocumentsTransformer mounted installation drawing ref: RMINST-06Freestanding installation drawing ref: RMINST-05Schematic drawing ref: RMSCH-01EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manual Standard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kA 3 sAnti-refl ex operating handleProvision for motorised mechanism LH/RH ring switch with plug interfaceIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 17CB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)Transformer mounting kitFreestanding tee-off cable boxOrder informationCode Rating
RN2c-T1/16 16 kA, 12 kV, 75 kV BILRN2c-T1/21 21 kA, 13.8 kV, 95 kV BIL
DE
6018
0D
E60
181
20 AMTED399086EN.indd
Ring main units Non-extensible ring main unit 200 A RN2c-T2
Transformer protection up to 3.5 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142Protection CT’s - 200/1 A class X
b Setting range: v Overcurrent: 20-200 A v Earth fault: 2-160 A
Transformer ratingsSee table - page 147DocumentsTransformer mounted installation drawing ref: RMINST-06Freestanding installation drawing ref: RMINST-05Schematic drawing ref: RMSCH-03EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kA 3 sAnti-refl ex operating handleProvision for motorised mechanism LH/RH ring switch with plug interfaceIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 17CB LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)Transformer mounting kitFreestanding tee-off cable boxOrder informationCode Rating
RN2c-T2/16 16 kA, 12 kV, 75 kV BILRN2c-T2/21 21 kA, 13.8 kV, 95 kV BIL
DE
6018
0D
E60
185
21AMTED399086EN.indd
MV transformer protectionProtection & control - CBSelf powered overcurrent relay, VIP 30. Protection CT’s - 500/200/1 A class X
b Setting range: 500/1 A v Overcurrent: 20-200 A b Setting range: 200/1 A v Overcurrent: 8-80 A
Transformer ratingsSee table - page 147DocumentsTransformer mounted installation drawing ref: RMINST-06Freestanding installation drawing ref: RMINST-05Schematic drawing ref: RMSCH-02EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kA 3 sAnti-refl ex operating handleProvision for motorised mechanism LH/RH ring switch with plug interfaceIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 17CB, LH, RH motor kitLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable box (indoor only)Transformer mounting kitFreestanding tee-off cable boxOrder informationCode Rating
RN2c-T3/16 16 kA, 12 kV, 75 kV BILRN2c-T3/21 21 kA, 13.8 kV, 95 kV BIL
Ring main units Non-extensible ring main unit 200 A RN2c-T3
DE
6018
0D
E60
182
22 AMTED399086EN.indd
MV transformer protectionProtection & control - CBSelf powered overcurrent and earth fault relay, VIP 35.Protection CT’s - 500/200/1 A class XCH30 core balance CT
b Setting range: 500/1 A v Overcurrent: 20-200 A v Earth fault: 25-300 A b Setting range: 200/1 A v Overcurrent: 8-80 A v Earth fault: 10-120 A
Transformer ratingsSee table - page 147DocumentsTransformer mounted installation drawing ref: RMINST-06Freestanding installation drawing ref: RMINST-05Schematic drawing ref: RMSCH-15EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kA 3 sAnti-refl ex operating handleProvision for motorised mechanism LH/RH ring switch with plug interfaceIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 17CB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)Transformer mounting kitFreestanding tee-off cable boxOrder informationCode Rating
RN2c-T4/16 16 kA, 12 kV, 75 kV BILRN2c-T4/21 21 kA, 13.8 kV, 95 kV BIL
Ring main units Non-extensible ring main unit 200 A RN2c-T4
DE
6018
0D
E60
183
23AMTED399086EN.indd
Transformer protection up to 1.6 MVA at 11 kVProtection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links (glass fuse link)Protection CT’s - 100/50/5 A class XTransformer ratingsSee table - page 147DocumentsTransformer mounted installation drawing ref: RMINST-06Freestanding installation drawing ref: RMINST-05Schematic drawing ref: RMSCH-01EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kA 3 sAnti-refl ex operating handleProvision for motorised mechanism LH/RH ring switch with plug interfaceIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 17CB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)Transformer mounting kitFreestanding tee off cable boxOrder informationCode Rating
RN2c-T5/16 16 kA, 12 kV, 75 kV BILRN2c-T5/21 21 kA, 13.8 kV, 95 kV BIL
Ring main units Non-extensible ring main unit 200 A RN2c-T5
DE
6018
0D
E60
184
24 AMTED399086EN.indd
Ring main units Non-extensible ring main unit 200 A RN2c-T25
Transformer protection up to 3.5 MVA at 11 kVProtection & control - CBIDMT overcurrent, earth-fault and thermal overload relay,Sepam series 10. In accordance with IEC 60255Power supply 24-48 VDC requiredProtection CT’s - 200/100/1 A 5P20Setting range (200/1): overcurrent: 20 - 200 A, earth-fault: 2 - 480 A, sensitive earth-fault: 0.2 - 24 ASetting range (100/1):overcurrent: 10 - 200 A, earth-fault: 1 - 240 A, sensitive earth-fault: 0.2 - 24 ADocuments (1)
Schematic drawing ref:RN2c-T25B: RMSCH-43RN2c-T25BS: RMSCH-44RN2c-T25A: RMSCH-45RN2c-T25AS: RMSCH-46EnvironmentIndoor/outdoorIP54RatingsBusbar 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-refl ex operating handleProvision for motorised mechanism LH/RH ring switchMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCIndicationMechanical tripped on fault fl ag indicationMechanical ON/OFF indicationMechanical earth/main indicationGas pressure indicationCB auxiliary contacts 1NO 1NC (3)
CB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm²Bottom entry up to 3 x 1C 630 mm²Accessories - see table, page 17CB, LH, RH motor kitRH and LH ring switch indication auxiliary contacts 1NO 1NCEarth ON auxiliary contact 1NOVPIS indicationInverted cable box (indoor only)Transformer mounting kit (4)
Freestanding tee-off cable boxOrder informationCode (1) Rating
RN2c-T25B/21 21 kA, 13.8 kV, 95 kV BILRN2c-T25BS/21 21 kA, 13.8 kV, 95 kV BILRN2c-T25A/21 21 kA, 13.8 kV, 95 kV BILRN2c-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
Sepam 10 functions ANSI code
RN2c-T25 (1)
B BS A ASProtection
Earth-fault protection
Standard 0.01…2.4 In (2)
50N/51N b b
Sensitive 0.2…24 A
50G/51G b b
Phase-overcurrent protection0.1…24 I (3)
50/51 b b b b
Thermal overload protection 49RMS b b b b
Phase-overcurrent and earth-fault cold load pick-up
b b b b
Logic discrimination
Blocking send 68 b b b b
Blocking reception b b
External tripping via digital input b b
MeasurementEarth-fault current b b b b
Phase currents b b b b
Peak demand currents b b b b
Control and supervisionCircuit breaker tripping and lockout
86 b b b b
Tripping annunciation 30 b b b b
Tripped on fault, volt free contact b b b b
Relay watchdog contact b b
Remote CB position monitoring b b
Record of last fault b b b b
Record of last fi ve events b b
CommunicationsModbus b b
IEC 60870-5-103 b b
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced), AS (advanced + sensitive earth-fault)(2) In = Primary CT ratio(3) Only with T25B and T25BS(4) BS + AS not available with transformer mounted units.
DE
6018
0D
E59
800
50/5150N/51N49RMS
25AMTED399086EN.indd
Network sectionalising up to 12 MVA 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142Protection CT’s - 800/400/1 A class X
b Setting range: 800/1 A ratio v Overcurrent: 80-800 A v Earth fault: 8-640 A b Setting range: 400/1 A v Overcurrent: 40-400 A v Earth fault: 4-320 A
DocumentsFreestanding installation drawing ref: RMINST-05Schematic drawing ref: RMSCH-42EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCircuit breaker earth switch 16/21 kARing cable earth switch, 16/21 kA 3 sAnti-refl ex operating handleProvision for motorised mechanism LH/RH ring switch and circuit breaker with plug interfaceIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch and circuit breaker test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 17CB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes (indoor only)FreestandingOrder informationCode Rating
RN6c-T1/16 16 kA, 12 kV, 75 kV BILRN6c-T1/21 21 kA, 13.8 kV, 95 kV BIL
Ring main units Non-extensible ring main unit 630 A RN6c-T1
DE
6018
0D
E60
186
26 AMTED399086EN.indd
Ring main units Non-extensible ring main unit 630 A RN6c-T25
Network sectionalising up to 12 MVA at 11 kVProtection & control - CBIDMT overcurrent, earth-fault and thermal overload relay,Sepam series 10. In accordance with IEC 60255Power supply 24-48 VDC requiredProtection CT’s - 800/400/1 A 5P20Setting range (800/1): overcurrent: 80 - 630 A, earth-fault: 8 - 1920 A, sensitive earth-fault: 0.2 - 24 ASetting range (400/1):overcurrent: 40 - 630 A, earth-fault: 4 - 960 A, sensitive earth-fault: 0.2 - 24 ADocuments (1)
Schematic drawing ref:RN6c-T25B: RMSCH-43RN6c-T25BS: RMSCH-44RN6c-T25A: RMSCH-45RN6c-T25AS: RMSCH-46EnvironmentIndoor/outdoorIP54RatingsBusbar 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-refl ex operating handleProvision for motorised mechanism LH/RH ring switchMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCIndicationMechanical tripped on fault fl ag indicationMechanical ON/OFF indicationMechanical earth/main indicationGas pressure indicationCB auxiliary contacts 1NO 1NC (3)
CB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm²Bottom entry up to 3 x 1C 630 mm²Accessories - see table, page 17CB, LH, RH motor kitRH and LH ring switch indication auxiliary contacts 1NO 1NCEarth ON auxiliary contact 1NOVPIS indicationInverted cable box (indoor only)Transformer mounting kit (4)
Freestanding tee-off cable boxOrder informationCode (1) Rating
RN6c-T25B/21 21 kA, 13.8 kV, 95 kV BILRN6c-T25BS/21 21 kA, 13.8 kV, 95 kV BILRN6c-T25A/21 21 kA, 13.8 kV, 95 kV BILRN6c-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
Sepam 10 functions ANSI code
RN6c-T25 (1)
B BS A ASProtection
Earth-fault protection
Standard 0.01…2.4 In (2)
50N/51N b b
Sensitive 0.2…24 A
50G/51G b b
Phase-overcurrent protection0.1…24 In (2)
50/51 b b b b
Thermal overload protection 49RMS b b b b
Phase-overcurrent and earth-fault cold load pick-up
b b b b
Logic discrimination
Blocking send 68 b b b b
Blocking reception b b
External tripping via digital input b b
MeasurementEarth-fault current b b b b
Phase currents b b b b
Peak demand currents b b b b
Control and supervisionCircuit breaker tripping and lockout
86 b b b b
Tripping annunciation 30 b b b b
Tripped on fault, volt free contact b b b b
Relay watchdog contact b b
Remote CB position monitoring b b
Record of last fault b b b b
Record of last fi ve events b b
CommunicationsModbus b b
IEC 60870-5-103 b b
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced), AS (advanced + sensitive earth-fault)(2) In = Primary CT ratio(3) Only with T25B and T25BS(4) BS + AS not available with transformer mounted units.
DE
6018
0D
E59
800
50/5150N/51N49RMS
27AMTED399086EN.indd
Ring main units Extensible ring main unitsSpecification
RE2c-T1TFL
RE2c-T2VIP 300
RE2c-T3VIP 30
RE2c-T4VIP 35
RE2c-T25Sepam 10
EnvironmentIndoor / outdoor b b b b b
IP54 b b b b b
Transformer mounted b b b b b
Freestanding b b b b b
Extensible (RHS) O O O O O
RatingsBusbars 630 A b b b b b
Circuit breaker normal rated current 200 A b b b b b
Circuit breaker normal rated current 630 ASwitch normal rated current 630 A b b b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O
Ring switch cable earth switch 16 kA 3 seconds b b b b b
Ring switch cable earth switch 21 kA 3 seconds O O O O O
Circuit breaker earth switch 3.15 kA b b b b b
Extensible rmu busbar chamber 630 A O O O O O
MechanismIndependent manual b b b b b
Provision for motorised mechanism LH ring switch b b b b b
Provision for motorised mechanism RH ring switch b b b b b
Provision for motorised mechanism circuit breaker O O O O O
Protection & control - circuit breakerCT’s dual ratio - 100/50/5 A class X b
CT’s ratio - 200/1 A class X b
CT’s dual ratio 200/100/1 A 5P20 b
CT’s ratio - 500/200/1 A class X b b
Overcurrent & earth fault CT operated trip coils - TFL b
Overcurrent relay - VIP 30 b
Overcurrent & earth fault relay - VIP 35 b
IDMT overcurrent & earth fault relay - VIP 300 b
IDMT relay Sepam 10 b
Multi voltage shunt trip coil (see accessories) O O O O b
IndicationMechanical ON/OFF b b b b b
Mechanical EARTH/MAIN b b b b b
VPIS indication 3.3 - 13.8 kV O O O O O
Gas pressure indicator (-25°C to +55°C) b b b b b
RSW aux contacts 1NO & 1NC O O O O O
Test facilityIntegral ring cable test facility b b b b b
Standard featuresOperating handle b b b b b
Cable (see available cable kit accessories)Bottom entry up 1 x 3C 300 mm2 b b b b b
Bottom entry up 3 x 1C 630 mm2 b b b b b
Top entry cables (indoor only) (left hand side only) O O O O O
Order codes12 kV, 16 kA, 75 kV BIL, 0.35bG RE2c-T1/16 RE2c-T2/16 RE2c-T3/16 RE2c-T4/1613.8 kV, 21 kA, 95 kV BIL, 0.8bG RE2c-T1/21 RE2c-T2/21 RE2c-T3/21 RE2c-T4/21 RE2c-T25/21General arrangement drawing - freestanding RMINST-22
Page 94RMINST-22 Page 94
RMINST-22 Page 94
RMINST-22 Page 94
RMINST-22 Page 94
Schematic diagram - TFL RMSCH-01 Page 104
Schematic diagram - VIP 30 RMSCH-02 Page 105
Schematic diagram - VIP 35 RMSCH-15 Page 107
Schematic diagram - VIP 300 RMSCH-03 Page 106
Schematic diagram Sepam 10 RMSCH-43-46Pages 108-111
Key: b Standard feature O Optional feature
28 AMTED399086EN.indd
Ring main units Extensible ring main unitsAccessories
RE2c-T1TFL
RE2c-T2VIP 300
RE2c-T3VIP 30
RE2c-T4VIP 35
RE2c-T25Sepam 10
Kit no.
Cable kitsExtensible ring main units v v v v v RMR-A/F47Gland plate 1 x 3C O O O O O RMR-A316Gland plate 3 x 1C O O O O O RMR-A319Small gland plate 1 x 3C O O O O O RMR-A322Blank aluminium gland plate O O O O O RMR-A320Brass wiping gland 1 x 3C O O O O O RMR-A10Brass wiping gland 3 x 1C O O O O O RMR-A10Small brass wiping gland 1 x 3C O O O O O RMR-A105Tubular gland 1 x 3C O O O O O RMR-A12Tubular gland 3 x 1C O O O O O RMR-A13Small tubular gland 1 x 3C O O O O O RMR-A106CES5 gland O O O O O RMR-A120CES5 gland plate 1 x 3C O O O O O RMR-A321CES5 gland plate adaptor O O O O O RMR-A5256 x ECON cable termination kit O O O O O RMR-A3143 x STD ECON end cap O O O O O RMR-A3703 x ECON cable termination kit O O O O O RMR-A3153 x ECON end cap capacitors O O O O O RMR-A371Top entry cables LH cable box (indoor only) v v v v v RMR-F302Angled gland plate 1 x 3C O O O O O RMR-A317Split gland plate 1 x 3C O O O O O RMR-A318Installation itemsTransformer mounting kit v v v v v RMR-A/F323Extension trunking (to clear radiators) O O O O O RMR-A20Set of padlocks - 11 no O O O O O RMR-A343Anti-vandal fi xings, including tool O O O O O RMR-A344Foundation bolts (not required for transformer mounting) O O O O O RMR-A22Multicore pilot glands O O O O O RMR-A342Time limit fuses (set of 2 - specify rating as table page 115) O O O O O RMR-A17RE2c to MU2 installation kit v v v v v RMR-A350Extensible busbar chamber 630 A O O O O O RMR-F369Ariel mounting bracket O O O O O RMR-A201Operational itemsOperating handle b b b b b RMR-F345LH ring switch control auxiliary sw for motorised mechanism provision
v v v v v RMR-F328
LH ring switch termination block for motorised mechanism provision (not Easergy)
v v v v v RMR-F363
RH ring switch control auxiliary sw for motorised mechanism provision
v v v v v RMR-F329
RH ring switch termination block for motorised mechanism provision (not Easergy)
v v v v v RMR-F364
Provision for motorised mechanism circuit breaker v v v v v RMR-F543Motorised mechanism - specify voltage v v v v v RMR-F507Shunt trip coil (20-250 V DC, 110-250 V AC) TLF v v v v v RMR-F581Shunt trip coil (20-250 V DC, 110-250 V AC) VIP v v v v v RMR-F582Ring switch cable VPIS indication (3.3-13.8 kV) v v v v v RMR-F341Circuit breaker VPIS indication (11-13.8 kV) v v v v v RMR-F340Circuit breaker VPIS indication (3.3-7.2 kV) v v v v v RMR-F347VAP 6 test unit for VIP 300/30/35 v v v v v RMR-A202Emergency trip push button v v v v v RMR-F339Gas pressure switch for remote indication only v v v v v RMR-F368Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site
29AMTED399086EN.indd
Ring main units Extensible ring main unitsAccessories
RE2c-T1TFL
RE2c-T2VIP 300
RE2c-T3VIP 30
RE2c-T4VIP 35
RE2c-T25Sepam 10
Kit no.
Mechanical interlocksCircuit breaker - key free, earth on v v v v v RMR-F337Circuit breaker - key free, main off v v v v v RMR-F338Switch - key free, switch off LH v v v v v RMR-F335Switch - key free, switch off RH v v v v v RMR-F336N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanismsEarth fault passage indication (choose provision kit and an EFPI required if not using Easergy T200E)Phase & earth fault provision for Easergy T200E O O O O O RMR-F310EFPI provision kit, inside cable box O O O O O RMR-A304EFPI provision kit, CT outside cable box O O O O O RMR-A305EFPI provision kit, inside cable box, top entry O O O O O RMR-A308EFPI provision kit, outside cable box, top entry O O O O O RMR-A309Bowden “RR” EFPI and CT O O O O O RMR-A422Bowden STD EFPI type NB O O O O O RMR-A277Bowden LV reset EFPI type NB1 O O O O O RMR-A278Bowden LV reset & alarm type NB O O O O O RMR-A279Fundamentals ER “FIND” EFPI and CT O O O O O RMR-A57N. B. above CT’s are ring type for split core - please consult Schneider ElectricKey: v Factory fi tted accessory O Loose accessory, assembled on site
30 AMTED399086EN.indd
Ring main units Extensible ring main unit 200 A RE2c-T1
Multiple transformer feeders or network switching pointsProtection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links.Protection CT’s - 100/50/5 A class XTransformer ratingsSee table - page 147DocumentsFreestanding installation drawing ref: RMINST-22Schematic drawing ref: RMSCH-01EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kA 3 sAnti-refl ex operating handleExtensible (RHS)Extensible (LHS and RHS)Provision for motorised mechanism LH/RH ring switch with plug interfaceIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 28 CB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC earth On 1NOMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationIntegral circuit breaker test facilityInverted cable boxes LH, CB (indoor only)Transformer mounting kitFreestanding tee-off cable boxOrder informationCode Rating
RE2c-T1/16 16 kA, 12 kV, 75 kV BILRE2c-T1/21 21 kA, 13.8 kV, 95 kV BIL
DE
6021
1D
E60
187
31AMTED399086EN.indd
Ring main units Extensible ring main unit 200 A RE2c-T2
Multiple transformer feeders or network switching pointsProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS 142.Protection CT’s - 200/1 A class X
b Setting range: v Overcurrent: 20-200 A v Earth fault: 2-160 A
Transformer ratingsSee table - page 147DocumentsInstallation drawing ref: RMINST-22Schematic drawing ref: RMSCH-03EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kA 3 sAnti-refl ex operating handleExtensible (RHS)Provision for motorised mechanism LH/RH ring switch IndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 28 CB, LH, RH motor kitsLH, RH ring switch indication 1NO 1NC Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable box LH CB (indoor only)Transformer mounting kitFreestanding tee-off cable boxOrder informationCode Rating
RE2c-T2/16 16 kA, 12 kV, 75 kV BILRE2c-T2/21 21 kA, 13.8 kV, 95 kV BIL
DE
6021
1D
E60
188
32 AMTED399086EN.indd
Ring main units Extensible ring main unit 200 A RE2c-T3
MV transformer protectionProtection & control - CBSelf powered overcurrent relay, VIP 30.Protection CT’s - 500/200/1 A class X
b Setting range: 500/1 A v Overcurrent: 20-200 A b Setting range: 200/1 A v Overcurrent: 8-80 A
Transformer ratingsSee table - page 147DocumentsInstallation drawing ref: RMINST-22Schematic drawing ref: RMSCH-02EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kAAnti-refl ex operating handleExtensible (RHS)Provision for motorised mechanism LH/RH ring switch IndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCCB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table, page 28CB, LH, RH motor kitLH, RH ring switch indication 1NO 1NCMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes LH, CB (indoor only)Transformer mounting kitFreestanding tee-off cable boxOrder informationCode Rating
RE2c-T3/16 16 kA, 12 kV, 75 kV BILRE2c-T3/21 21 kA, 13.8 kV, 95 kV BIL
DE
6021
1D
E60
189
33AMTED399086EN.indd
Ring main units Extensible ring main unit 200 A RE2c-T4
MV transformer protectionProtection & control - CBProtection & control - CBSelf powered overcurrent and earth fault relay, VIP 35.Protection CT’s - 500/200/1 A class with CH30 core balance CT
b Setting range: 500/1 A v Overcurrent: 20-200 A v Earth fault 25-300 A b Setting range: 200/1 A v Overcurrent: 8-80 A v Earth fault 10-120 A
Transformer ratingsSee table - page 147DocumentsInstallation drawing ref: RMINST-22Schematic drawing ref: RMSCH-15EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 3.15 kA 3 sAnti-refl ex operating handleExtensible (RHS)Provision for motorised mechanism LH/RH ring switch IndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 1NCEarth position selected 1NOEarth ON, 1NOTest facilityIntegral ring switch test facilityCableBottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
Accessories - see table page 28CB, LH, RH motor kit LH, RH ring switch indication 1NO 1NCMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCVPIS indicationInverted cable boxes LH, CB (indoor only)Transformer mountingFreestanding tee-off cable boxOrder informationCode Rating
RE2c-T4/16 16 kA, 12 kV, 75 kV BILRE2c-T4/21 21 kA, 13.8 kV, 95 kV BIL
DE
6021
1D
E60
190
34 AMTED399086EN.indd
Ring main units Extensible ring main unit 200 A RE2c-T25
MV transformer protectionProtection & control - CBIDMT overcurrent, earth-fault and thermal overload relay,Sepam series 10. In accordance with IEC 60255Power supply 24-48 VDC requiredProtection CT’s - 200/100/1 A 5P20Setting range (200/1): overcurrent: 20 - 200 A, earth-fault: 2 - 480 A, sensitive earth-fault: 0.2 - 24 ASetting range (100/1):overcurrent: 40 - 200 A, earth-fault: 1 - 240 A, sensitive earth-fault: 0.2 - 24 ADocuments (1)
Schematic drawing ref:RN2c-T25B: RMSCH-43RN2c-T25BS: RMSCH-44RN2c-T25A: RMSCH-45RN2c-T25AS: RMSCH-46EnvironmentIndoor/outdoorIP54RatingsBusbar 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 A/200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRing switch cable earth switch, 16/21 kA 3 sTransformer earth switch, 16/21 kA 3 sAnti-refl ex operating handleExtensible RHSProvision for motorised mechanism LH/RH ring switchMulti voltage shunt trip coil 20-48 V DC - 110-250 V AC/DCIndicationMechanical tripped on fault fl ag indicationMechanical ON/OFF indicationMechanical earth/main indicationGas pressure indicationCB auxiliary contacts 1NO 1NC (3)
CB earth position selected 1NOCB earth ON, 1NOTest facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm²Bottom entry up to 3 x 1C 630 mm²Accessories - see table, page 28CB, LH, RH motor kitRH and LH ring switch indication auxiliary contacts 1NO 1NCEarth ON auxiliary contact 1NOVPIS indicationInverted cable box (indoor only)Transformer mounting kit (4)
Freestanding tee-off cable boxOrder informationCode (1) Rating
RN2c-T25B/21 21 kA, 13.8 kV, 95 kV BILRN2c-T25BS/21 21 kA, 13.8 kV, 95 kV BILRN2c-T25A/21 21 kA, 13.8 kV, 95 kV BILRN2c-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
Sepam 10 functions ANSI code
RE2c-T25 (1)
B BS A ASProtection
Earth-fault protection
Standard 0.01…2.4 In (2)
50N/51N b b
Sensitive 0.2…24 A
50G/51G b b
Phase-overcurrent protection0.1…24 In (2)
50/51 b b b b
Thermal overload protection 49RMS b b b b
Phase-overcurrent and earth-fault cold load pick-up
b b b b
Logic discrimination
Blocking send 68 b b b b
Blocking reception b b
External tripping via digital input b b
MeasurementEarth-fault current b b b b
Phase currents b b b b
Peak demand currents b b b b
Control and supervisionCircuit breaker tripping and lockout
86 b b b b
Tripping annunciation 30 b b b b
Tripped on fault, volt free contact b b b b
Relay watchdog contact b b
Remote CB position monitoring b b
Record of last fault b b b b
Record of last fi ve events b b
CommunicationsModbus b b
IEC 60870-5-103 b b
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced), AS (advanced + sensitive earth-fault)(2) In = Primary CT ratio(3) Only with T25B and T25BS(4) BS + AS not available with transformer mounted units.
DE
6021
1D
E59
801
50/5150N/51N49RMS
50/5150N/51N49RMS
35AMTED399086EN.indd
Circuit breaker, metering and switches
Contents
Non-extensible circuit breakers 200 ASpecifi cation - Accessories CN2-T1, CN2-T6, CN2-T25
3638
Non-extensible switches 630 ASpecifi cation - Accessories SN6-S1, SN6-S2
4143
Non-extensible metering units 200 ASpecifi cation - Accessories MU2-M1, MU2-M2, MU2-M3
4547
Non-extensible metering units 630 ASpecifi cation - Accessories MU6-N**
5052
Extensible circuit breakers 200 ASpecifi cation - AccessoriesCE2-T2, CE2-T7, CE2-T*, CE2-T12, CE2-T**, CE2-T13, CE2-T15, CE2-T16, CE2-T25
535661
Extensible circuit breakers 630 A Specifi cation - AccessoriesCE6-T4, CE6-T*, CE6-T8, CE6-T25, CE6-T**
6567
Extensible switches 630 A Specifi cation - AccessoriesSE6-S1, SE6-S2, SE6-E1
7274
Extensible bus-section 630 ASpecifi cation - AccessoriesSE6-B1, CE6-B3, CE6-B5
7779
36 AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible circuit breakers 200 ASpecification
CN2-T1 CN2-T6 CN2-T25EnvironmentIndoor / outdoor b b b
IP54 b b b
RatingsNormal rated current 200 A b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O
Cable earth switch 16 kA 3 seconds b b b
Cable earth switch 21 kA 3 seconds O O O
Transformer earth switch 3.15 kA 3 seconds b b b
MechanismIndependent manual b b b
Protection & control - circuit breakerCT’s dual ratio - 100/50/5 A class X b b
CT’s ratio - 200/1 A class X b
CT’s dual ratio 200/100/1 A 5P20 b
Overcurrent & earth fault CT operated trip coils b b
Time fuse Link O O
IDMT overcurrent & earth fault relay - VIP 300 b
IDMT overcurrent and earth fault relay Sepam 10 b
20 V-250 shunt trip coil b b b
Circuit breaker auxiliary switch 1NO 2NC b b b
IndicationMechanical ON/OFF b b b
Mechanical EARTH/MAIN b b b
VPIS indication (6.6 - 13.8 kV) O O O
Auxiliary switch contacts 1NO 2NC b b b
Gas pressure indicator b b b
Test facilityIntegral cable test facility b b b
Standard featuresOperating handle b b b
Transformer earth switch 3.15 kA 3 seconds b b b
Cable (see available cable kit accessories)Bottom entry up 300 mm2 1 x 3C b b b
Bottom entry up 630 mm2 3 x 1C b b b
Key: b Standard feature O Optional feature
37AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible circuit breakers 200 AAccessories
CN2-T1 CN2-T6 CN2-T25 Kit no.Cable kitsTee-off cable box v v v RMR-F47Gland plate 1 x 3C O O O RMR-A48Gland plate 3 x 1C O O O RMR-A49Angled gland plates (RMR) O O O RMR-A50 BlankBlank aluminium gland plate O O O RMR-A52Brass wiping gland 1 x 3C O O O RMR-A10Brass wiping gland 3 x 1C O O O RMR-A11Tubular gland 1 x 3C O O O RMR-A12Tubular gland 3 x 1C O O O RMR-A13CES5 gland plate 1 x 3C O O O RMR-A132Installation itemsSet of padlocks - 6 no O O O RMR-A18/6Anti-vandal fi xings, including tool O O O RMR-A19Foundation bolts (not required for transformer mounting) O O O RMR-A22Multicore pilot glands O O O RMR-A16Time limit fuses (set of 2 - specify rating as table page 115) O O RMR-A17Operational itemsOperating handle b b b RMR-A23VPIS indication (6.6-13.8 kV) v v v RMR-F108Neon lamp test unit (including lamp) O O O RMR-A24Neon lamp O O O RMR-A81VAP 6 test unit for VIP 300 O RMR-A202Mechanical interlocksKey free, earth on v v v RMR-F85Key free, unit off v v v RMR-F86Transformer earth switch, key free, earth on v v v RMR-F110N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanismsOrder codes12 kV, 16 kA, 75 kV BIL, 0.35bG CN2-T1/16 CN2-T6/1613.8 kV, 21 kA, 95 kV BIL, 0.55bG CN2-T1/21 CN2-T6/21 CN2-T25/21General arrangement drawing - transformer mounted RMINST-04 Page 93 RMINST-04 Page 93 RMINST-04 Page 93General arrangement drawing - freestanding RMINST-09 Page 145 RMINST-09 Page 145 RMINST-09 Page 145Schematic diagram RMSCH-26 Page 119 RMSCH-11 Page 118 RMSCH-47 to 50
Page 114 to 117Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site
38 AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible circuit breaker 200 A CN2-T1
Transformer protection up to 3.5 MVAProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142Protection CT’s - 200/1 A class X
b Setting range: v Overcurrent: 20-200 A v Earth fault: 2-160 A
Shunt trip coil, 20 V DC-250 V ACTransformer ratingsSee table - page 147DocumentsTransformer mounted installation drawing ref: RMINST-04Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09Schematic drawing ref: RMSCH-26EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresTee-off earth switch, 3.15 kA 3 sCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 2 NCTest facilityIntegral cable test facilitiesCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesTee-off cable boxGlands and platesInterlocksSee page 37 for detailsOrder informationCode Rating
CN2-T1/16 16 kA, 12 kV, 75 kV BILCN2-T1/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
0
39AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible circuit breaker 200 A CN2-T6
Transformer protection up to 1.5 MVAProtection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links.Protection CT’s - 100/50/5 A class XShunt trip coil, 20 V DC-250 V ACTransformer ratingsSee table - page 147DocumentsTransformer mounted installation drawing ref: RMINST-04Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09Schematic drawing ref: RMSCH-11EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresTransformer earth switch, 3.15 kA 3 sCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorCB auxiliary contacts 1NO 2 NCTest facilityIntegral cable test facilitiesCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesTee-off cable boxGlands and platesInterlocksSee page 37 for detailsOrder informationCode Rating
CN2-T6/16 16 kA, 12 kV, 75 kV BILCN2-T6/21 21 kA, 13.8 kV, 95 kV BIL
DE
6019
2
40 AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible circuit breaker 200 A CN2-T25
Transformer protection up to 3.5 MVAProtection & control - CBIDMT overcurrent, earth-fault and thermal overload relay,Sepam series 10. In accordance with IEC 60255Power supply 24-48 VDC requiredProtection CT’s - 200/100/1 A 5P20Setting range (200/1): overcurrent: 20 - 200 A, earth-fault: 2 - 480 A, sensitive earth-fault: 0.2 - 24 ASetting range (100/1):overcurrent: 10 - 200 A, earth-fault: 1 - 240 A, sensitive earth-fault: 0.2 - 24 ADocuments (1)
Schematic drawing ref:CN2-T25B: RMSCH-47CN2-T25BS: RMSCH-48CN2-T25A: RMSCH-49CN2-T25AS: RMSCH-50EnvironmentIndoor/outdoorIP54RatingsBusbar 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresTransformer earth switch, 3.15 kA 3 sCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicationMechanical ON/OFF indicationMechanical earth/main indicationGas pressure indicationCB auxiliary contacts 1NO 1NC (3
Test facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm²Bottom entry up to 3 x 1C 630 mm²Accessories - see table, page 37Tee-off cable boxGlands and platesInterlocksOrder informationCode (1) Rating
CN2-T25B/21 21 kA, 13.8 kV, 95 kV BILCN2-T25BS/21 21 kA, 13.8 kV, 95 kV BILCN2-T25A/21 21 kA, 13.8 kV, 95 kV BILCN2-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
Sepam 10 functions ANSI code
CN2-T25 (1)
B BS A ASProtection
Earth-fault protection
Standard 0.01…2.4 In (2)
50N/51N b b
Sensitive 0.2…24 A
50G/51G b b
Phase-overcurrent protection0.1…24 In (2)
50/51 b b b b
Thermal overload protection 49RMS b b b b
Phase-overcurrent and earth-fault cold load pick-up
b b b b
Logic discrimination
Blocking send 68 b b b b
Blocking reception b b
External tripping via digital input b b
MeasurementEarth-fault current b b b b
Phase currents b b b b
Peak demand currents b b b b
Control and supervisionCircuit breaker tripping and lockout
86 b b b b
Tripping annunciation 30 b b b b
Tripped on fault, volt free contact b b b b
Relay watchdog contact b b
Remote CB position monitoring b b
Record of last fault b b b b
Record of last fi ve events b b
CommunicationsModbus b b
IEC 60870-5-103 b b
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced), AS (advanced + sensitive earth-fault)(2) In = Primary CT ratio(3) Only with T25B and T25BS.
DE
5980
2
50/5150N/51N49RMS
41AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible switches 630 ASpecification
SN6-S1 SN6-S2EnvironmentIndoor / outdoor b b
IP54 b b
RatingsNormal rated current 630 A b b
13.8 kV 21 kA 3 seconds 95 kV BIL b b
Cable earth switch 21 kA 3 seconds b b
Transformer earth switch 3.15 kA 3 seconds b b
MechanismIndependent manual b b
Provision for actuator 24 V DC b
Actuator 24 V DC O
IndicationMechanical ON/OFF b b
Mechanical EARTH/MAIN b b
VPIS indication (6.6 - 13.8 kV) O O
Auxiliary switch contacts 1NO 2NC b
Phase and earth fault detection CT’s for Easergy 200E O
Provision for EFPI O O
Test facilityIntegral cable test facility b b
Standard featuresOperating handle b b
Transformer earth switch 3.15 kA 3 seconds b b
Cable (see available cable kit accessories)Bottom entry up 300 mm2 1 x 3C b b
Bottom entry up 630 mm2 3 x 1C b b
Key: b Standard feature O Optional feature
42 AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible switches 630 AAccessories
SN6-S1 SN6-S2 Kit no.Cable kitsTee-off cable box v v RMR-F47Gland plate 1 x 3C O O RMR-A48Gland plate 3 x 1C O O RMR-A49Angled gland plates (RMR) O O RMR-A50 Blank aluminium gland plate O O RMR-A52Brass wiping gland 1 x 3C O O RMR-A10Brass wiping gland 3 x 1C O O RMR-A11Tubular gland 1 x 3C O O RMR-A12Tubular gland 3 x 1C O O RMR-A13CES5 gland plate 1 x 3C O O RMR-A132Installation itemsSet of padlocks - 6 no O O RMR-A18/6Anti-vandal fi xings, including tool O O RMR-A19Foundation bolts (not required for transformer mounting) O O RMR-A22Multicore pilot glands O O RMR-A16Operational itemsOperating handle b b RMR-A23VPIS indication (6.6-13.8 kV) v v RMR-F108Neon lamp test unit (including lamp) O O RMR-A24Neon lamp O O RMR-A81Actuator 24 V DC v RMR-F67Mechanical interlocksKey free, earth on v RMR-F85Key free, unit off v RMR-F86Transformer earth switch, key free, earth on v v RMR-F110N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanismsOrder codes13.8 kV, 21 kA, 95 kVBIL, 0.35bG SN6-S1/21 SN6-S2/21General arrangement drawing - transformer mounted RMINST-04 Page 93 RMINST-04 Page 93General arrangement drawing - freestanding RMINST-09 Page 145 RMINST-09 Page 145Schematic diagram N/A RMSCH-28 Page 137Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site
43AMTED399086EN.indd
Switch disconnectorProtection & control - CBNon-automaticDocumentsInstallation drawing ref: RMINST-04Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09Schematic drawing ref: N/AEnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kVOperating mechanismIndependent manualStandard featuresTransformer earth switch, 3.15 kA 3 sCable earth switch, 21 kA 3 sAnti-refl ex operating handleIndicationMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorTest facilityIntegral cable test facilitiesCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesTee-off cable boxVPIS indicationGlands and platesInterlocksSee page 42 for detailsOrder informationCode Rating
SN6-S1/21 21 kA, 13.8 kV, 95 kV BIL
Circuit breaker, metering and switches
Non-extensible switch 630 A SN6-S1
DE
6019
3
44 AMTED399086EN.indd
Switch disconnectorProtection & control - CBNon-automaticDocumentsInstallation drawing ref: RMINST-04Installation drawing for freestanding unit with tee-off cable box ref: RMINST-09Schematic drawing ref: RMSCH-28EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kVOperating mechanismIndependent manualProvision for actuator, 24 V DCStandard featuresTransformer earth switch, 3.15 kA 3 sCable earth switch, 21 kA 3 sAnti-refl ex operating handleIndicationMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorAuxiliary contacts 1NO 2NC Earth selected auxiliary contact 1NOTest facilityIntegral cable test facilitiesCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesTee-off cable boxActuator, 24 V DCVPIS indicationGlands and platesSee page 42 for detailsOrder informationCode Rating
SN6-S2/21 21 kA, 13.8 kV, 95 kV BIL
Circuit breaker, metering and switches
Non-extensible switch 630 A SN6-S2
DE
6019
4
45AMTED399086EN.indd
MU2-M1 MU2-M2 MU2-M3EnvironmentIndoor / outdoor b b b
IP54 b b b
RatingsNormal rated current 200 A b b b
12 kV 16 kA 1 second 75 kV BIL b b b
Metering (1)
CT’s -50/25/5 A 0.5s 7.5 VA b
CT’s -100/50/5 A 0.5s 10 VA b
CT’s -200/100/5 A 0.5s 10 VA b
VT’s -11 kV/110 V 0.5 50 VA b b b
Cable (see available cable kit accessories)Bottom entry up 300 mm2 1 x 3C O O O
Bottom entry up 630 mm2 3 x 1C O O O
Key: b Standard feature O Optional feature(1) CT’s - 2 phases (R & B), VT’s phase to phase. 6.6 kV VT’s are available - Contact Schneider Electric
Circuit breaker, metering and switches
Non-extensible metering unit 200 ASpecification
46 AMTED399086EN.indd
MU2-M1 MU2-M2 MU2-M3 Kit no.Cable kitsTee-off cable box v v v RMR-F47Gland plate 1 x 3C O O O RMR-A48Gland plate 3 x 1C O O O RMR-A49Angled gland plates (RMU) O O O RMR-A51 BlankBlank aluminium gland plate O O O RMR-A52Brass wiping gland 1 x 3C O O O RMR-A10Brass wiping gland 3 x 1C O O O RMR-A11Tubular gland 1 x 3C O O O RMR-A12Tubular gland 3 x 1C O O O RMR-A13CES5 gland plate 1 x 3C O O O RMR-A132Installation itemsSet of padlocks - XX no O O O RMR-A18/6Foundation bolts (not required for transformer mounting) O O O RMR-A22Multicore pilot glands O O O RMR-A16RMU - MU2 installation kit O O O RMR-A350Freestanding installation kit O O O RMR-A90Order codes12 kV, 16 kA, 75 kV BIL, 0.35bG MU2-M1/16 MU2-M2/16 MU2-M3/16General arrangement drawing - transformer mounted RMINST-07/08
Pages 97 - 96RMINST-07/08 Pages 97 - 96
RMINST-07/08 Pages 97 - 96
Schematic diagram RMSCH-14 Page 113 RMSCH-14 Page 113 RMSCH-14 Page 113Key: v Factory fi tted accessory O Loose accessory, assembled on site
Circuit breaker, metering and switches
Non-extensible metering unit 200 AAccessories
47AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible metering unit 200 A MU2-M1
Non-extensible metering unitProtection & control - CBN/AMetering transformers
b Metering CT’s R & B phases v 50/25/5 A v 7.5 VA class 0.5s b Metering VT ph - ph v 11 kV/110 V 50 VA v class 0.5
DocumentsInstallation drawing ref: RMINST-07/08Schematic drawing ref: RMSCH-14EnvironmentIndoor/outdoorIP54RatingsShort time withstand 16 kA 1 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12 kVNormal rated BIL 75 kVStandard featuresDirect coupling between RMU and transformer (optional freestanding cable connection)Cable connectionBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesCable boxGlands and platesInstallation kitsSee page 46 for detailsOrder informationCode Rating
MU2-M1/16 16 kA, 12 kV, 75 kV BIL
DE
6021
0
48 AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible metering unit 200 A MU2-M2
Non-extensible metering unitProtection & control - CBN/AMetering transformers
b Metering CT’s R & B phases v 100/50/5 A v 10 VA class 0.5s b Metering VT ph - ph v 11 kV/110 V 50 VA v class 0.5
DocumentsInstallation drawing ref: RMINST-07/08Schematic drawing ref: RMSCH-14EnvironmentIndoor/outdoorIP54RatingsShort time withstand 16 kA 1 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12 kVNormal rated BIL 75 kVStandard featuresDirect coupling between RMU and transformer (optional freestanding cable connection)Cable connectionBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessories Cable boxGlands and platesInstallation kitsSee page 46 for detailsOrder informationCode Rating
MU2-M2/16 16 kA, 12 kV, 75 kV BIL
DE
6021
0
49AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible metering unit 200 A MU2-M3
Non-extensible metering unitProtection & control - CBN/AMetering transformers
b Metering CT’s R & B phases v 200/100/5 A v 10 VA class 0.5s b Metering VT ph - ph v 11 kV/110 V 50 VA v class 0.5
DocumentsInstallation drawing ref: RMINST-07/08Schematic drawing ref: RMSCH-14EnvironmentIndoor/outdoorIP54RatingsShort time withstand 16 kA 1 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12 kVNormal rated BIL 75 kVStandard featuresDirect coupling between RMU and transformer(optional freestanding cable connection)Cable connectionBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesCable boxGlands and platesInstallation kitsSee page 46 for detailsOrder informationCode Rating
MU2-M3/16 16 kA, 12 kV, 75 kV BIL
DE
6021
0
50 AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible metering units 630 ASpecification
MU6-N1 MU6-N2 MU6-N3 MU6-N5EnvironmentIndoor / outdoor b b b b
IP54 b b b b
RatingsNormal rated current 630 A b b b b
12 kV 16 kA 1 second 75 kV BIL b b b b
Metering (1)
CT’s - 400/600/5 A 10 VA b
CT’s - 600/5 A 10 VA b
CT’s - 400/5 A 10 VA b
CT’s - 600/300/5 A 10 VA b
VT’s - 11 kV/110 V 0.5 50 VA b b b
VT’s - 11 kV/6.6 kV/110 V 0.5 50 VA b
Cable (see available cable kit accessories)Bottom entry up 300 mm2 1 x 3C O O O O
Bottom entry up 630 mm2 3 x 1C O O O O
Key: b Standard feature O Optional feature(1) CT’s - 2 phases (R&B), VT’s phase to phase 6.6 kV VT’s are available - Contact Schneider Electric
51AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible metering units 630 AAccessories
MU6-N1 MU6-N2 MU6-N3 MU6-N5 Kit no.Cable kitsTee-off cable box v v v v RMR-F47Gland plate 1 x 3C O O O O RMR-A48Gland plate 3 x 1C O O O O RMR-A49Angled gland plates (RMU) O O O O RMR-A51 Blank Blank aluminium gland plate O O O O RMR-A52Brass wiping gland 1 x 3C O O O O RMR-A10Brass wiping gland 3 x 1C O O O O RMR-A11Tubular gland 1 x 3C O O O O RMR-A12Tubular gland 3 x 1C O O O O RMR-A13CES5 gland plate 1 x 3C O O O O RMR-A132Installation itemsSet of padlocks - XX no O O O O RMR-A18/6Foundation bolts (not required for transformer mounting) O O O O RMR-A22Multicore pilot glands O O O O RMR-A16RMU - MU6 installation kit O O O O RMR-A350Freestanding installation kit O O O O RMR-A90Order codes12 kV, 16 kA, 75 kVBIL, 0.35bG MU6-N1/16 MU6-N2/16 MU6-N3/16 MU6-N5/16General arrangement drawing - transformer mounted RMINST-07/08
Pages 97 - 96RMINST-07/08 Pages 97 - 96
RMINST-07/08 Pages 97 - 96
RMINST-07/08 Pages 97 - 96
Schematic diagram RMSCH-14 Page 113
RMSCH-14 Page 113
RMSCH-14 Page 113
RMSCH-14 Page 113
Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site
52 AMTED399086EN.indd
Circuit breaker, metering and switches
Non-extensible metering units 630 A MU6-N**
Non-extensible metering unitProtection & control - CBN/AMetering transformers
b Metering CT’s R & B phases (16 kA, 12 kV, 75 kV BIL)10 VA class 0.5s N1/16 N2/16 N3/16 N5/16400/200/5 A b
600/5 A b
400/5 A b
600/300/5 A b
b Metering VT ph - ph (16 kA, 12 kV, 75 kV BIL)50 VA class 0.5 N1/16 N2/16 N3/16 N5/1611 kV/110 V b b b
11 kV/6.6 kV/110 V b
DocumentsInstallation drawing ref: RMINST-07/08Schematic drawing ref: RMSCH-14EnvironmentIndoor/outdoorIP54RatingsShort time withstand 16 kA 1 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12 kVNormal rated BIL 75 kVStandard featuresDirect coupling between RMU and transformer(optional freestanding cable connection)Cable connectionBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesCable boxGlands and platesInstallation kitsSee page 51 for detailsOrder informationCode Rating
MU6-N** 16 kA, 12 kV, 75 kV BIL
DE
6021
0
53AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breakers 200 ASpecification
CE2-T2
CE2-T3
CE2-T7
CE2-T11
CE2-T12
CE2-T13
CE2-T14
CE2-T15
CE2-T16
CE2-T19
CE2-T20
CE2-T21
CE2-T25
EnvironmentIndoor / outdoor b b b b b b b b b b b b b
IP54 b b b b b b b b b b b b b
RatingsBusbars 630 A b b b b b b b b b b b b b
Circuit breaker normal rated current 200 A b b b b b b b b b b b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b b b b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O O O O O O
Cable earth switch 16 kA 3 seconds b b b b b b b b b b b b b
Cable earth switch 21 kA 3 seconds O O O O O O O O O O O O O
MechanismIndependent manual b b b b b b b b b b b b b
Provision for actuator 24 V DC b b b b
Actuator 24 V DC O O O OOperating handle b b b b b b b b b b b b b
Protection systemCT’s dual ratio - 500/200/1 A class x b b
Overcurrent relay - VIP 30 b
CT’s dual ratio - 100/50/5 A class X b
CT’s dual ratio 200/100/1 A 5P20 b
CT ratio - 200/1 A class X b b b b b b b b b
Overcurrent & earth fault CT operated trip coils b
Overcurrent & earth fault relay VIP 35 b
Time fuse link OIDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b b
IDMT overcurrent and earth fault relay Sepam 10 b
20 V-250 shunt trip coil b b b b b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b b b b b
MeteringCT’s -200/100/5 A 0.5s 10 VA b b b b b b b
VT’s -13.8 kV/110 V 0.5 10 VA 13.8/110 V/110 V 0.5 50 VA 3P 20 VA b b
VT’s -11 kV/110 V 0.5 50 VA b b b
VT’s -6.6 kV/110 V 0.5 50 VA b b
VT’s phase - phase, CT’s R & B b b b b
VT’s phase - earth, CT’s RYB b b b
IndicationMechanical ON/OFF b b b b b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b b b b b
Cable VPIS indication (6.6 - 13.8 kV) O O O O O O O O O O O O OAuxiliary switch contacts 1NO 2NC b b b b b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b b
Test facilityIntegral cable test facility b b b b b b b b b b b b b
Cable Bottom entry up to 300 mm2 1 x 3C b b b b b b b b b b b b b
Bottom entry up to 630 mm2 3 x 1C b b b b b b b b b b b b b
Top entry cables O O O O O O O O O O O O O
Key: b Standard feature O Optional feature
54 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breakers 200 AAccessories
CE2-T2
CE2-T3
CE2-T7
CE2-T11
CE2-T12
CE2-T13
CE2-T14
CE2-T15
CE2-T16
CE2-T19
CE2-T20
CE2-T21
CE2-T25
Kit no.
Cable kitsGland plate 1 x 3C O O O O O O O O O O O O O RMR-A48Gland plate 3 x 1C O O O O O O O O O O O O O RMR-A49Angled gland plates (RMR) O O O O O O O O O O O O O RMR-A50Blank aluminium gland plate O O O O O O O O O O O O O RMR-A52Brass wiping gland 1 x 3C O O O O O O O O O O O O O RMR-A10Brass wiping gland 3 x 1C O O O O O O O O O O O O O RMR-A11Tubular gland 1 x 3C O O O O O O O O O O O O O RMR-A12Tubular gland 3 x 1C O O O O O O O O O O O O O RMR-A13CES5 gland plate 1 x 3C O O O O O O O O O O O O O RMR-A132Top entry cables standard panels v v v v v v RMR-F93Top entry cables MU6 only v v v v v v v RMR-F94Installation items3 phase busbars 630 A O O O O O O RMR-A143 phase busbars 630 A O O O O O O O RMR-A78Busbar end kit O O O O O O O O O O O O O RMR-A15Set of padlocks - 6 no O O O O O O O O O O O O O RMR-A18/6Foundation bolts (not required for transformer mounting)
b b b b b b b b b b b b b RMR-A22
Multicore pilot glands O O O O O O O O O O O O O RMR-A16Time limit fuses (set of 2 - specify rating as table page 115)
O RMR-A17
Operational itemsOperating handle b b b b b b b b b b b b b RMR-A23Cable VPIS indication (6.6 - 13.8 kV)
v v v v v v v v v v v v v RMR-F108
Neon lamp test unit (including lamp)
v v v v v v v v v v v v v RMR-A24
Neon lamp O O O O O O O O O O O O RMR-A81VAP 6 test unit for VIP 300 O O O O O O O O O O O O RMR-A202Actuator 24 V DC v v v RMR-F67Polarity conversion kit (1) v v v RMR-F391Mechanical interlocksKey free, EARTH ON v v v v v v v RMR-F85Key free, MAIN OFF v v v v v v v RMR-F86N. B. specify lock symbol at time of ordering (3 digits max) not available with motor mechanismsKey: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site (1) Only required when unit is used with RE2c ring main units and automation.
55AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breakers 200 AAccessories
CE2-T2
CE2-T3
CE2-T7
CE2-T11
CE2-T12
CE2-T13
CE2-T14
CE2-T15
CE2-T16
CE2-T19
CE2-T20
CE2-T21
CE2-T25
Kit no.
Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy 200E)EFPI provision kit, inside cable box
O O O O O O O O O O O O O RMR-F30
Bowden STD EFPI type NB O O O O O O O O O O O O O RMR-A277Bowden LV reset EFPI type NB1 O O O O O O O O O O O O O RMR-A278Bowden LV reset & alarm type NB2
O O O O O O O O O O O O O RMR-A279
Bowden “RR” EFPI and CT O O O O O O O O O O O O O RMR-A56Fundamentals ER “FIND” EFPI and CT
O O O O O O O O O O O O O RMR-A57
Ancillary itemsTool box O O O O O O O O O O O O O RMR-A80Order code12 kV, 16 kA, 75 kV BIL, 0.35bG CE2-
T2/16CE2-T3/16
CE2-T7/16
CE2-T11/16
CE2-T12/16
CE2-T13/16
CE2-T14/16
CE2-T15/16
CE2-T16/16
N/A CE2-T20/16
N/A N/A
13.8 kV, 21 kA, 95 kV BIL, 0.55bG CE2-T2/21
CE2-T3/21
CE2-T7/21
CE2-T11/21
CE2-T12/21
CE2-T13/21
CE2-T14/21
CE2-T15/21
CE2-T16/21
CE2-T19/21
N/A CE2-T21/21
CE2-T25/21
General arrangement drawing RMINST-03Page 92
RMINST-02Page 91
RMINST-03Page 92
RMINST-02Page 91
RMINST-03Page 92
RMINST-02Page 91
RMINST-02Page 91
RMINST-03Page 92
RMINST-03Page 92
RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
RMINST-03Page 92
Schematic drawing RMSCH-07Page 121
RMSCH-09Page 123
RMSCH-06Page 120
RMSCH-09Page 123
RMSCH-19Page 127
RMSCH-20Page 128
RMSCH-20Page 128
RMSCH-07Page 121
RMSCH-07Page 121
RMSCH-35Page 133
RMSCH-35Page 133
RMSCH-36Page 134
RMSCH-47 to 50Pages 114 to 117
Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site
56 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T2
Feeder protection up to 3.5 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 20-200 A v Earth fault: 2-160 A
DocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-07EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicatorTest facilityIntegral cable test facilitiesCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesSee page 54 for detailsOrder informationCode Rating
CE2-T2/16 16 kA, 12 kV, 75 kV BILCE2-T2/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
1
57AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T7
Transformer protection up to 1.5 MVA at 11 kVProtection & control - CBOvercurrent and earth fault protection using CT operated trip coils with provision for time fuse links.Protection CT’s - 100/50/5 A class XShunt trip coil, 20 V DC-250 V ACDocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-06EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesSee page 54 for detailsOrder informationCode Rating
CE2-T7/16 16 kA, 12 kV, 75 kV BILCE2-T7/21 21 kA, 13.8 kV, 95 kV BIL
DE
6019
6
58 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T*
Feeder protection up to 3.5 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 20-200 A v Earth fault: 2-160 A
Metering transformers b Metering CT’s R & B phases v 200/100/5 A v 10 VA class 0.5s b Metering VT v see below
EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualAnti-refl ex operating handleStandard featuresCable earth switch, 16/21 kA 3 sIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessories VPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesSee page 54 for detailsOrder code16 kA, 12 kV, 75 kV BIL21 kA, 13.8 kV, 95 kV BIL
CE2-T3/16CE2-T3/21
CE2-T11/16CE2-T11/21
N/ACE2-T19/21
CE2-T20/16N/A
Metering VT information:Phase to phase
b b
Phase to earth b b
6.6 kV/110 V b
11 kV/110 V (1) b b
13.8 kV/110 V b
General arrangement drawing RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
Schematic diagram RMSCH-09Page 123
RMSCH-09Page 123
RMSCH-35Page 133
RMSCH-35Page 133
(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage Tel: +44 (0)113 290 3500
DE
6025
2
(Select VT rating and switchgear rating from table below).
59AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T12
Feeder protection up to 3.5 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142. Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 20-200 A v Earth fault: 2-160 A
DocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-19EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualProvision for actuator, 24 V DCStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCEarth selected auxiliary contact1NOGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesSee page 54 for detailsOrder informationCode Rating
CE2-T12/16 16 kA, 12 kV, 75 kV BILCE2-T12/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
3
60 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T**
Feeder protection up to 3.5 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 20-200 A v Earth fault: 2-160 A
Metering transformers b Metering CT’s v 200/100/5 A v 10 VA class 0.5s b Metering VT v see below
EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualProvision for actuator, 24 V DCStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCEarth selected auxiliary contact1NOGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesSee page 54 for detailsOrder code16 kA, 12 kV, 75 kV BIL21 kA, 13.8 kV, 95 kV BIL
CE2-T14/16CE2-T14/21
N/ACE2-T21/21
Metering VT information:Phase to phase
b
Phase to earth b
6.6 kV/110 V b
11 kV/110 V (1)
13.8 kV/110 V b
General arrangement drawing RMINST-02Page 91
RMINST-02Page 91
Schematic diagram RMSCH-20Page 128
RMSCH-36Page 134
(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage Tel: +44 (0)113 290 3500
DE
6025
4
(Select VT rating and switchgear rating from table below).
61AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T13
Feeder protection up to 3.5 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 200/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 20-200 A v Earth fault: 2-160 A
Metering transformers b Metering CT’s v 200/100/5 A v 10 VA class 0.5s b Metering VT ph - ph v 11 kV/110 V 50 VA v class 0.5
DocumentsInstallation drawing ref: RMINST-02Schematic drawing ref: RMSCH-20EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualActuator, 24 V DCStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCEarth selected auxiliary contact1NOGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesSee page 54 for detailsOrder informationCode Rating
CE2-T13/16 16 kA, 12 kV, 75 kV BILCE2-T13/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
4
62 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T15
Feeder protection up to 2.5 MVA at 11 kVProtection & control - CBSelf powered overcurrent relay, VIP 30.Protection CT’s - 500/200/1 A class X
b Setting range: 500/1 A v Overcurrent: 20-200 A b Setting range: 200/1 A v Overcurrent: 8-80 A
DocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-12EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicatorTest facilityIntegral cable test facilitiesCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesSee page 54 for detailsOrder informationCode Rating
CE2-T15/16 16 kA, 12 kV, 75 kV BILCE2-T15/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
1
63AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T16
Feeder protection up to 2.5 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 35. Protection CT’s - 500/200/1 A class XCH30 core balance CT
b Setting range: 500/1 A v Overcurrent: 20-200 A v Earth fault: 25-300 A b Setting range: 200/1 A v Overcurrent: 8-80 A v Earth fault: 10-120 A
DocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-13EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCGas pressure indicatorTest facilityIntegral cable test facilitiesCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesVPIS indicationGlands and platesInterlocksOperating handleBusbar kitTop entry cablesSee page 54 for detailsOrder informationCode Rating
CE2-T16/16 16 kA, 12 kV, 75 kV BILCE2-T16/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
5
64 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 200 A CE2-T25
Transformer protection up to 3.5 MVA at 11 kVProtection & control - CBIDMT overcurrent, earth-fault and thermal overload relay,Sepam series 10. In accordance with IEC 60255Power supply 24-48 VDC requiredProtection CT’s - 200/100/1 A 5P20Setting range (200/1): overcurrent: 20 - 200 A, earth-fault: 2 - 480 A, sensitive earth-fault: 0.2 - 24 ASetting range (100/1):overcurrent: 10 - 200 A, earth-fault: 1 - 240 A, sensitive earth-fault: 0.2 - 24 ADocuments (1)
Schematic drawing ref:CE2 – T25B: RMSCH-47CE2 – T25BS: RMSCH-48CE2 – T25A: RMSCH-49CE2 – T25AS: RMSCH-50EnvironmentIndoor/outdoorIP54RatingsBusbar 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 200 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicationMechanical ON/OFF indicationMechanical earth/main indicationGas pressure indicationCB auxiliary contacts 1NO 1NC (3)
Test facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm²Bottom entry up to 3 x 1C 630 mm²Accessories - see table, page 54Tee-off cable boxGlands and platesInterlocksOrder informationCode (1) Rating
CE2-T25B/21 21 kA, 13.8 kV, 95 kV BILCE2-T25BS/21 21 kA, 13.8 kV, 95 kV BILCE2-T25A/21 21 kA, 13.8 kV, 95 kV BILCE2-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
Sepam 10 functions ANSI code
CE2-T25 (1)
B BS A ASProtection
Earth-fault protection
Standard 0.01…2.4 In (2)
50N/51N b b
Sensitive 0.2…24 A
50G/51G b b
Phase-overcurrent protection0.1…24 In (2)
50/51 b b b b
Thermal overload protection 49RMS b b b b
Phase-overcurrent and earth-fault cold load pick-up
b b b b
Logic discrimination
Blocking send 68 b b b b
Blocking reception b b
External tripping via digital input b b
MeasurementEarth-fault current b b b b
Phase currents b b b b
Peak demand currents b b b b
Control and supervisionCircuit breaker tripping and lockout
86 b b b b
Tripping annunciation 30 b b b b
Tripped on fault, volt free contact b b b b
Relay watchdog contact b b
Remote CB position monitoring b b
Record of last fault b b b b
Record of last fi ve events b b
CommunicationsModbus b b
IEC 60870-5-103 b b
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced), AS (advanced + sensitive earth-fault)(2) In = Primary CT ratio(3) Only with T25B and T25BS.
DE
5980
3
50/5150N/51N49RMS
65AMTED399086EN.indd
CE6-T4
CE6-T5
CE6-T6
CE6-T8
CE6-T9
CE6-T10
CE6-T22
CE6-T23
CE6-T24
CE6-T25
EnvironmentIndoor / outdoor b b b b b b b b b b
IP54 b b b b b b b b b b
RatingsBusbars 630 A b b b b b b b b b b
Circuit breaker normal rated current 630 A b b b b b b b b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O O OCable earth switch 16 kA 3 seconds b b b b b b b b b b
Cable earth switch 21 kA 3 seconds O O O O O O O O O O
MechanismIndependent manual b b b b b b b b b b
Provision for actuator 24 V DC b b b b
Actuator 24 V DC O O O OOperating handle b b b b b b b b b b
Protection systemCT ratio - 800/1 A class X b b b b b b b b b
CT dual ratio 800/400/1 A 5P20 b
IDMT overcurrent & earth fault relay - VIP 300 b b b b b b b b b
IDMT overcurrent & earth fault relay Sepam 10 b
20 V-250 V shunt trip coil b b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b b
MeteringCT’s - 400/200/5 A 0.5s 10 VA b b b b b b b
VT’s - 13.8 kV/110 V/110 V/ 0.5 50 VA 3P 20 VA b b
VT’s - 11 V/110 V 0.5 50 VA b b b
VT’s - 6.6 kV/110 V 0.5 50 VA b b
VT’s - phase - phase, CT’s R & B b b b b
VT’s phase - earth, CT’s RYB b b b
IndicationMechanical ON/OFF b b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b b
Cable VPIS indication (6.6 - 13.8 kV) O O O O O O O O O OAuxiliary switch contacts 1NO 2NC b b b b b b b b b b
Indication CT 600/5 A 5 VA CLS 1 Yph b b b b b b b b b
Ammeter 0-600 A b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b
Gas pressure indicator b b b b b b b b b b
Test facilityIntegral cable test facility b b b b b b b b b b
Cable Bottom entry up to 300 mm2 1 x 3C b b b b b b b b b b
Bottom entry up to 630 mm2 3 x 1C b b b b b b b b b b
Top entry cables O O O O O O O O O OKey: b Standard feature O Optional feature
Circuit breaker, metering and switches
Extensible circuit breakers 630 ASpecification
66 AMTED399086EN.indd
CE6-T4
CE6-T5
CE6-T6
CE6-T8
CE6-T9
CE6-T10
CE6-T22
CE6-T23
CE6-T24
CE6-T25
Kit no.
Cable kitsGland plate 1 x 3C O O O O O O O O O O RMR-A48Gland plate 3 x 1C O O O O O O O O O O RMR-A49Angled gland plates (RMR) O O O O O O O O O O RMR-A50Blank aluminium gland plate O O O O O O O O O O RMR-A52Brass wiping gland 1 x 3C O O O O O O O O O O RMR-A10Brass wiping gland 3 x 1C O O O O O O O O O O RMR-A11Tubular gland 1 x 3C O O O O O O O O O O RMR-A12Tubular gland 3 x 1C O O O O O O O O O O RMR-A13CES5 gland plate 1 x 3C O O O O O O O O O O RMR-A132Top entry cables standard panels v v v RMR-F93Top entry cables MU6 only v v v v v v v RMR-F94Installation items3 phase busbars 630 A O O O RMR-A143 phase busbars 630 A O O O O O O O RMR-A78Busbar end kit O O O O O O O O O O RMR-A15Set of padlocks - 6 no O O O O O O O O O O RMR-A18/6Foundation bolts (not required for transformer mounting)
b b b b b b b b b b RMR-A22
Multicore pilot glands O O O O O O O O O O RMR-A16Operational itemsOperating handle b b b b b b b b b b RMR-A23Cable VPIS indication (6.6 - 13.8 kV) v v v v v v v v v v RMR-A108Neon lamp test unit (including lamp) O O O O O O O O O O RMR-A24Neon lamp O O O O O O O O O O RMR-A81VAP 6 test unit for VIP 300 O O O O O O O O RMR-A202Actuator 24 V DC v v v v RMR-F67Polarity conversion kit (1) v v v v RMR-F391Mechanical interlocksKey free, EARTH ON v v v v v v RMR-F85Key free, MAIN OFF v v v v v v RMR-F86N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanismsEarth fault passage indication (choose provision kit and an EFPI required if not using Easergy T200E)EFPI provision kit, inside cable box O O O O O O O O O O RMR-F30Bowden STD EFPI type NB O O O O O O O O O O RMR-A277Bowden LV reset EFPI type NB1 O O O O O O O O O O RMR-A278Bowden LV reset & alarm type NB2 O O O O O O O O O O RMR-A279Bowden “RR” EFPI and CT O O O O O O O O O O RMR-A56Fundamentals ER “FIND” EFPI and CT O O O O O O O O O O RMR-A57Ancillary itemsTool box O O O O O O O O O O RMR-A80Order code12 kV, 16 kA, 75 kV BIL, 0.35bG CE6-
T4/16CE6-T5/16
CE6-T6/16
CE6-T8/16
CE6-T9/16
CE6-T10/16
N/A N/A CE6-T24/16
13.8 kV, 21 kA, 95 kV BIL, 0.55bG CE6-T4/21
CE6-T5/21
CE6-T6/21
CE6-T8/21
CE6-T9/21
CE6-T10/21
CE6-T22/21
CE6-T23/21
N/A CE6-T25/21
General arrangement drawing RMINST-03Page 92
RMINST-02Page 91
RMINST-02Page 91
RMINST-03Page 92
RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
RMINST-03Page 92
Schematic drawing RMSCH-08Page 122
RMSCH-10Page 124
RMSCH-10Page 124
RMSCH-23Page 131
RMSCH-24Page 132
RMSCH-24Page 132
RMSCH-37Page 135
RMSCH-38Page 136
RMSCH-37Page 135
RMSCH-47 to 50Pages 114 to 117
Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site (1) Only required when unit is used with RE2c ring main units and automation.
Circuit breaker, metering and switches
Extensible circuit breakers 630 AAccessories
67AMTED399086EN.indd
Feeder protection up to 12 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 80-800 A v Earth fault: 8-640 A
DocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-08EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCAmmeter 0-600 AIndication CT Y ph - 600/5 A class 1.0, 5 VAGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesSee page 66 for detailsOrder informationCode Rating
CE6-T4/16 16 kA, 12 kV, 75 kV BILCE6-T4/21 21 kA, 13.8 kV, 95 kV BIL
Circuit breaker, metering and switches
Extensible circuit breaker 630 A CE6-T4
DE
6025
6
68 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 630 A CE6-T*
Feeder protection up to 12 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 80-800 A v Earth fault: 8-640 A
Metering transformers b Metering CT’s v 400/200/5 A v 10 VA class 0.5s b Metering VT v see below
EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCAmmeter 0-600 AIndication CT Y ph - 600/5 A class 1.0, 5 VAGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesSee page 66 for detailsOrder code16 kA, 12 kV, 75 kV BIL21 kA, 13.8 kV, 95 kV BIL
CE6-T5/16CE6-T5/21
CE6-T6/16CE6-T6/21
N/ACE6-T22/21
CE6-T24/16N/A
Metering VT information:Phase to phase
b b
Phase to earth b b
6.6 kV/110 V b
11 kV/110 V (1) b b
13.8 kV/110 V b
General arrangement drawing RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
Schematic diagram RMSCH-10Page 124
RMSCH-10Page 124
RMSCH-37Page 135
RMSCH-37Page 135
(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage Tel: +44 (0)113 290 3500
DE
6019
7
(Select VT rating and switchgear rating from table below).
69AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 630 A CE6-T8
Feeder protection up to 12 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 80-800 A v Earth fault: 8-640 A
DocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-23EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualProvision for actuator, 24 V DCStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCEarth selected auxiliary contact1NOAmmeter 0-600 AIndication CT Y ph - 600/5 A class 1.0, 5 VAGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesSee page 66 for detailsOrder informationCode Rating
CE6-T8/16 16 kA, 12 kV, 75 kV BILCE6-T8/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
7
70 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 630 A CE6-T25
Feeder protection up to 12 MVA at 11 kVProtection & control - CBIDMT overcurrent, earth-fault and thermal overload relay,Sepam series 10. In accordance with IEC 60255Power supply 24-48 VDC requiredProtection CT’s - 800/400/1 A 5P20Setting range (800/1): overcurrent: 80 - 630 A, earth-fault: 8 - 1920 A, sensitive earth-fault: 0.2 - 24 ASetting range (400/1):overcurrent: 40 - 630 A, earth-fault: 4 - 960 A, sensitive earth-fault: 0.2 - 24 ADocuments (1)
Schematic drawing ref:CE6 – T25B: RMSCH-47CE6 – T25BS: RMSCH-48CE6 – T25A: RMSCH-49CE6 – T25AS: RMSCH-50EnvironmentIndoor/outdoorIP54RatingsBusbar 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicationMechanical ON/OFF indicationMechanical earth/main indicationGas pressure indicationCB auxiliary contacts 1NO 1NC (3)
Test facilityIntegral ring switch cable test facilityCableBottom entry up to 1 x 3C 300 mm²Bottom entry up to 3 x 1C 630 mm²Accessories - see table, page 66Tee-off cable boxGlands and platesInterlocksOrder informationCode (1) Rating
CE6-T25B/21 21 kA, 13.8 kV, 95 kV BILCE6-T25BS/21 21 kA, 13.8 kV, 95 kV BILCE6-T25A/21 21 kA, 13.8 kV, 95 kV BILCE6-T25AS/21 21 kA, 13.8 kV, 95 kV BIL
Sepam 10 functions ANSI code
CE6-T25 (1)
B BS A ASProtection
Earth-fault protection
Standard 0.01…2.4 In (2)
50N/51N b b
Sensitive 0.2…24 A
50G/51G b b
Phase-overcurrent protection0.1…24 In (2)
50/51 b b b b
Thermal overload protection 49RMS b b b b
Phase-overcurrent and earth-fault cold load pick-up
b b b b
Logic discrimination
Blocking send 68 b b b b
Blocking reception b b
External tripping via digital input b b
MeasurementEarth-fault current b b b b
Phase currents b b b b
Peak demand currents b b b b
Control and supervisionCircuit breaker tripping and lockout
86 b b b b
Tripping annunciation 30 b b b b
Tripped on fault, volt free contact b b b b
Relay watchdog contact b b
Remote CB position monitoring b b
Record of last fault b b b b
Record of last fi ve events b b
CommunicationsModbus b b
IEC 60870-5-103 b b
(1) B (basic), BS (basic + sensitive earth-fault), A (advanced), AS (advanced + sensitive earth-fault)(2) In = Primary CT ratio(3) Only with T25B and T25BS.
DE
5980
3
50/5150N/51N49RMS
71AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible circuit breaker 630 A CE6-T**
Feeder protection up to 12 MVA at 11 kVProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 80-800 A v Earth fault: 8-640 A
Metering transformers b Metering CT’s v 400/200/5 A v 10 VA class 0.5s b Metering VT v see below
EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 12/13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCEarth selected auxiliary contactsAmmeter 0-600 AIndication CT Y ph- 600/5 A class 1.0, 5 VAGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesSee page 66 for detailsOrder code16 kA, 12 kV, 75 kV BIL21 kA, 13.8 kV, 95 kV BIL
CE6-T9/16CE6-T9/21
CE6-T10/16CE6-T10/21
N/ACE6-T23/21
Metering VT information:Phase to phase
b b
Phase to earth b
6.6 kV/110 V b
11 kV/110 V (1) b
13.8 kV/110 V b
General arrangement drawing RMINST-02Page 91
RMINST-02Page 91
RMINST-02Page 91
Schematic diagram RMSCH-24Page 132
RMSCH-24Page 132
RMSCH-38Page 136
(1) Please consult Schneider Electric when ordering units with 95 kV BIL voltage Tel: +44 (0)113 290 3500
DE
6019
9
(Select VT rating and switchgear rating from table below).
72 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible switches 630 ASpecification
SE6-S1 SE6-S2 SE6-E1EnvironmentIndoor / outdoor b b b
IP54 b b b
RatingsBusbars 630 A b b b
Switch normal rated current 630 A b b b
13.8 kV 21 kA 3 seconds 95 kV BIL b b b
Cable earth switch 21 kA 3 seconds b b
MechanismIndependent manual b b b
Provision for actuator 24 V DC b
Actuator 24 V DC OOperating handle b b b
IndicationMechanical ON/OFF b b
Mechanical EARTH/MAIN b b b
Cable VPIS indication (6.6-13.8 kV) v v
Busbar VPIS indication (6.6-13.8 kV) v v
Auxiliary switch contacts1NO 1 NC v
Phase and earth fault detection CT’s for Easergy T200E OEFPI provision only CT inside box O O b
Gas pressure indicator b b b
Test facilityIntegral cable test facility b b
Integral test facilityRH/LH busbar earthing b
Cable (see available cable kit accessories)Bottom entry up to 300 mm2 1 x 3C b b
Bottom entry up to 630 mm2 3 x 1C b b
Top entry cables O OKey: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site
73AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible switches 630 AAccessories
SE6-S1 SE6-S2 SE6-E1 Kit no.Cable kitsGland plate 1 x 3C O O RMR-A48Gland plate 3 x 1C O O RMR-A49Angled gland plates (RMR) O O RMR-A50Blank aluminium gland plate O O RMR-A52Brass wiping gland 1 x 3C O O RMR-A10Brass wiping gland 3 x 1C O O RMR-A11Tubular gland 1 x 3C O O RMR-A12Tubular gland 3 x 1C O O RMR-A13CES5 gland plate 1 x 3C O O RMR-A132Top entry cables v v RMR-F93Installation items3 phase busbars 630 A O O v RMR-A14Set of padlocks - 6 no O O O RMR-A18/6Busbar end kit (1 end kit required per switchboard) O O O RMR-A15Foundation bolts (not required for transformer mounting) b b b RMR-A22Multicore pilot glands O RMR-A16Operational itemsOperating handle b b b RMR-A23Cable VPIS indication (6.6-13.8 kV) v v RMR-F108Cable and busbar VPIS indication (6.6-13.8 kV) v v RMR-F92Neon lamp test unit (including lamp) O O RMR-A24Neon lamp O O RMR-A81Actuator 24 V DC v RMR-F67Polarity conversion kit (1) v RMR-F391Mechanical interlocksKey free, earth ON v v RMR-F85Key free, main OFF v RMR-F86N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanismsIndication EFPI provision kit, inside cable box O O RMR-F30Bowden STD EFPI NB O O RMR-A277Bowden LV reset EFPI type NB1 O O RMR-A278Bowden LV reset & alarm type NB2 O O RMR-A279Bowden “RR” EFPI and CT O O RMR-A56Fundamentals ER “FIND” EFPI and CT O O RMR-A57Ancillary itemsTool box O O O RMR-A80Order code13.8 kV, 21 kA, 95 kV BIL, 0.55bG SE6-S1/21 SE6-S2/21 SE6-E1/21General arrangement drawing RMINST-03
Page 92RMINST-03Page 92
RMINST-03Page 92
Schematic drawing N/A RMSCH-29Page 138
N/A
Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site (1) Only required when unit is used with RE2c ring main units and automation.
74 AMTED399086EN.indd
Switch disconnectorProtection & control - CBNon-automaticDocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-N/AEnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 21 kA 3 sAnti-refl ex operating handlesIndicationMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesSee page 73 for detailsOrder informationCode Rating
SE6-S1/21 21 kA, 13.8 kV, 95 kVBIL
Circuit breaker, metering and switches
Extensible switch 630 A SE6-S1
DE
6020
1
75AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible switch 630 A SE6-S2
Switch disconnectorProtection & control - CBNon-automaticDocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-29EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kVOperating mechanismIndependent manualProvision for actuator, 24 V DCStandard featuresCable earth switch, 21 kA 3 sAnti-refl ex operating handleIndicationMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2NCEarth selected auxiliary contact 1NOGas pressure indicatorTest facilityIntegral cable test facilityCableBottom entry up to 300 mm2 1 x 3CBottom entry up to 630 mm2 3 x 1CAccessoriesActuator, 24 V DCVPIS indicationGlands and platesInterlocksBusbar kitTop entry cablesSee page 73 for detailsOrder informationCode Rating
SE6-S2/21 21 kA, 13.8 kV, 95 kV BIL
DE
6020
2
76 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible switch 630 A SE6-E1
Busbar earthing switchDocumentsInstallation drawing ref: RMINST-03Schematic drawing ref: RMSCH-N/AEnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kVOperating mechanismIndependent manualStandard featuresCable earth switch, 21 kA 3 sAnti-refl ex operating handleIndicationMechanical earth/main indicatorGas pressure indicatorTest facilityN/ACableN/AAccessoriesInterlocksBusbar kitSee page 73 for detailsOrder informationCode Rating
SE6-E1/21 21 kA, 13.8 kV, 95 kV BIL
DE
6020
3
77AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible bus-section 630 ASpecification
SE6-B1 CE6-B3 CE6-B5EnvironmentIndoor / outdoor b b b
IP54 b b b
RatingsBusbars 630 A b b b
Circuit breaker normal rated current 630 A b b
Switch normal rated current 630 A b
12 kV 16 kA 3 seconds 75 kV BIL b b
13.8 kV 21 kA 3 seconds 95 kV BIL b O ORH busbar earth switch 16 kA 3 seconds b b
RH busbar earth switch 21 kA 3 seconds b O O
MechanismIndependent manual b b b
Provision for actuator 24 V DC b
Actuator 24 V DC O
Operating handle b b b
Protection systemCT ratio - 800/1 A class X b b
IDMT overcurrent & earth fault relay - VIP 300 b b
20- 250 V shunt trip coil b b
Auxiliary switch1NO 2 NC b b
MeteringCT’s - 400/200/5 A 0.5s 10 VA b b
VT’s - 11 kA/110 V 0.5 50 VA b b
VT’s phase - phase, CT’s R & B b b
IndicationMechanical ON/OFF b b b
Mechanical EARTH/MAIN b b b
Earth selected auxiliary contact1NO b
RH busbar VPIS indication O O O
Auxiliary switch contacts1NO 2NC b b
Indication CT 600/5 A 5 VA CLS 1 Y phase b b
Ammeter 0-600 A b b
Gas pressure indicator b b b
Integral test facilityRH busbar earthing b b b
LH busbar earthing ( using SE6-E1) O O O
Key: b Standard feature O Optional feature
78 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible bus-section 630 AAccessories
SE6-B1 CE6-B3 CE6-B5 Kit no.Installation items3 phase busbars 630 A RMR-A143 phase busbars 630 A (Joggle metering) v v v RMR-A793 phase busbars 630 A double width (metering) v v v RMR-A78Set of padlocks - XX no O O O RMR-A18/6Busbar end kit (1 end kit required per switchboard) O O O RMR-A15Foundation bolts (not required for transformer mounting) b b b RMR-A22Multicore pilot glands O O RMR-A16Operational itemsOperating handle b b b RMR-A23LH and RH busbar VPIS indication v v v RMR-F92Neon lamp test unit (including lamp) O O RMR-A24Neon lamp O O O RMR-A81VAP6 test unit for VIP 300 O O RMR-A202Actuator 24 V DC v RMR-F67Polarity conversion kit (1) v RMR-F391Mechanical interlocksKey free, earth ON v v RMR-F85Key free, main OFF v v RMR-F86N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanismsAncillary itemsTool box O O O RMR-A80Order code12 kV, 16 kA, 75 kV BIL, 0.35bG N/A CE6-B3/16 CE6-B5/1613.8 kV, 21 kA, 95 kV BIL, 0.55bG SE6-B1/21 CE6-B3/21 CE6-B5/21General arrangement drawing RMINST-01
Page 90RMINST-01Page 90
RMINST-01Page 90
Schematic drawing N/A RMSCH-21Page 129
RMSCH-22Page 130
Key: b Standard feature v Factory fi tted accessory O Loose accessory, assembled on site (1) Only required when unit is used with RE2c ring main units and automation.
79AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible bus-section 630 A SE6-B1
Bus-section disconnectorProtection & control Non-automaticDocumentsInstallation drawing ref: RMINST-01Schematic drawing ref: N/AEnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 95 kVOperating mechanismIndependent manualStandard featuresRH busbar earth switch, 21 kA 3 sAnti-refl ex operating handleIndicationMechanical ON/OFF indicatorMechanical earth/main indicatorGas pressure indicatorTest facilityIntegral RH busbar test facilityCableN/AAccessoriesVPIS indicationInterlocksBusbarsSee page 78 for detailsOrder informationCode Rating
SE6-B1/21 21 kA, 13.8 kV, 95 kV BIL
DE
6020
4
80 AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible bus-section 630 A CE6-B3
Bus-section circuit breakerProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142. Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 80-800 A v Earth fault: 8-640 A
Metering transformers b Metering CT’s v 400/200/5 A v 10 VA class 0.5s b Metering VT ph-ph v 11 kV/110 V 50 VA v class 0.5
DocumentsInstallation drawing ref: RMINST-01Schematic drawing ref: RMSCH-21EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualStandard featuresRH busbar earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCAmmeter 0-600 AIndication CT Y ph- 600/5 A class 1.0 5 VAGas pressure indicatorTest facilityIntegral RH busbar test facilityCableN/AAccessoriesVPIS indicationInterlocksBusbarsSee page 78 for detailsOrder informationCode Rating
CE6-B3/16 16 kA, 12 kV, 75 kV BILCE6-B3/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
8
81AMTED399086EN.indd
Circuit breaker, metering and switches
Extensible bus-section 630 A CE6-B5
Bus-section circuit breakerProtection & control - CBSelf powered IDMT overcurrent and earth fault relay, VIP 300. In accordance with IEC 60255 and BS142.Protection CT’s - 800/1 A class XShunt trip coil, 20 V DC-250 V AC
b Setting range: v Overcurrent: 80-800 A v Earth fault: 8-640 A
Metering transformers b Metering CT’s v 400/200/5 A v 10 VA class 0.5s b Metering VT ph-ph v 11 kV/110 V 50 VA v class 0.5
DocumentsInstallation drawing ref: RMINST-01Schematic drawing ref: RMSCH-22EnvironmentIndoor/outdoorIP54RatingsBusbars 630 AShort time withstand 16/21 kA 3 sInternal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure onlyNormal current rating 630 ANormal rated voltage 13.8 kVNormal rated BIL 75/95 kVOperating mechanismIndependent manualProvision for actuator, 24 V DCStandard featuresRH busbar earth switch, 16/21 kA 3 sAnti-refl ex operating handleIndicationMechanical tripped on fault fl ag indicatorMechanical ON/OFF indicatorMechanical earth/main indicatorAuxiliary contacts,1NO 2 NCEarth selected auxiliary contacts1NOAmmeter 0-600 AIndication CT Y ph- 600/5 A class 1.0 5 VAGas pressure indicatorTest facilityIntegral RH busbar test facilityCableN/AAccessoriesActuator, 24 V DCVPIS indicationInterlocksBusbarsSee page 78 for detailsOrder informationCode Rating
CE6-B5/16 16 kA, 12 kV, 75 kV BILCE6-B5/21 21 kA, 13.8 kV, 95 kV BIL
DE
6025
9
82 AMTED399086EN.indd
83AMTED399086EN.indd
Remote control Contents
Telecontrol cabinet Easergy T200 E - Specifi cation Easergy T200-E02M Easergy T200-E04M
848585
84 AMTED399086EN.indd
Remote control Telecontrol cabinet Easergy T200 E - Specification
Easergy T200-E02M2 functions
Easergy T200-E04M 4 functions
EnvironmentIndoor / outdoor b b
IP54 b b
CommunicationModbusIEC 870-5-101 and IEC 870-5-104 b b
DNP3 b b
2 additional modem ports with GSM or GPRS b b
Standard featuresFreestanding/wall mounted/ switchgear mounted b b
Removable radio bracket ( no radio supplied) b b
Inputs to cabinetSwitch open - per switch b b
Switch closed - per switch b b
Earth selector earth/mains - per switch b b
1 spare - per switch b b
Control output to switchgearTo switch- Open switch b b
- Close switch b b
- Reset external FPI b b
Output to SCADA- Switch open b b
- Switch closed b b
- Earth selector earth/main b b
- Fault passage indication - phase and/or earth fault b b
From cabinet- Local/remote failure b b
- Mains/equipment failure b b
- Battery and charger alarms b b
Local controlPush button open/close switch b b
Local/remote selector b b
Reset/test integral FPI b b
Power restart b b
Local indicationMains present b b
Battery fault b b
Internal supplies on b b
Switch status - open/closed b b
FPI operated b b
Local/remote mode selected b b
Equipment fault (watchdog) b b
Battery and chargerTelecomms equipment - 12 V DC b b
Control unit - 12 V DC b b
Power supply 90-270 V AC 50 Hz 120 VA b b
Switchgear 24 V DC b b
1 x 24 Ah sealed lead acid b b
20 degrees C, 3 hours after loss of supply b b
5 c/o switch operations b b
Key: b Standard feature O Optional feature
85AMTED399086EN.indd
Remote control Telecontrol cabinet Easergy T200-E02MEasergy T200-E04M
Telecontrol cabinet - Up to 2 switch control (T200-E02M)Telecontrol cabinet - Up to 4 switch control (T200-E04M)Local indicationMains failure, battery fault, internal supplies on,Switch status - open/closed, FPI operated, local/remote mode selected, equipment fault (Watchdog)Inputs to cabinetSwitch openSwitch closedEarth selector earth/mains3 spare Control outputs to switchgear
b To switch v Open switch v Close switch v Reset FPI
Local controlPush button open/close switchLocal/remote selectorReset/test integral FPIOptional features
b Integral phase and earth fault passage indicator b 3 phase RMS current measurement b Wall mounted/freestanding
DocumentsInstallation drawing ref: RMINST-11Schematic drawing ref: RMSCH-17EnvironmentIndoor/outdoorIP54Dimensions480 x 370 x 280 mmCommunication
b Modbus v IEC 870-5-101 and IEC 870-5-104 v DNP3 v 2 additional modem ports with GSM or GPRS
Standard featuresSwitchgear mounted removable radio bracket ( no radio/modem supplied)Outputs to SCADA
b Switch open b Switch closed b Earth selector earth/main b Fault passage indication - phase and/or earth fault b From cabinet v Local/remote mode v Mains/equipment failure v other confi gurable alarms
Batteries and chargerTelecomms equipment - 12 V DCControl unit - 12 V DCSwitchgear - 24 V DC1 x 24 Ah sealed lead acidPower supply90-270 V AC 50 Hz 120 VAAutonomy20°C 5 hours after loss of supply5 C/O switch operationsDeep discharge protectionOrder informationT200-E02M T200-E04M
DE
6019
5
86 AMTED399086EN.indd
87AMTED399086EN.indd
Installation drawings Contents
Summary 88
Typical switchboard 89
Extensible unitsref RMINST-01, RMINST-02, RMINST-03
90
Non-extensible unitref RMINST-04
93
Extensible ring main unitc/w tee off cable box - ref RMINST-22
94
Non-extensible ring main unitsfor transformer mounting unit - ref RMINST-06c/w MU2 metering unit & tee off cable box - ref RMINST-08
95
Non-extensible metering unitref RMINST-07
97
Telecontrol cabinetref RMINST-11
98
88 AMTED399086EN.indd
Installation drawings Summary
Non-extensible equipmentSchematicdiagram
Page number General arrangementdrawing
Page number
Ring main units 200 A RN2c-T1RN2c-T2RN2c-T3RN2c-T4RN2c-T5RN2c-T25BRN2c-T25BSRN2c-T25ARN2c-T25AS
RMSCH-01RMSCH-03RMSCH-02RMSCH-15RMSCH-01RMSCH-43RMSCH-44RMSCH-45RMSCH-46
104106105107104108109110111
RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06
959595959595959595
Ring main units 630 A RN6c-T1RN6c-T25BRN6c-T25BSRN6c-T25ARN6c-T25AS
RMSCH-42RMSCH-43RMSCH-44RMSCH-45RMSCH-46
112108109110111
RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06
9595959595
Circuit breakers 200 A CN2-T1CN2-T6CN2-T25BCN2-T25BSCN2-T25ACN2-T25AS
RMSCH-26RMSCH-11RMSCH-47RMSCH-48RMSCH-49RMSCH-50
119118114115116117
RMINST-04RMINST-06RMINST-03RMINST-03RMINST-03RMINST-03
939592929292
Switches 630 A SN6-S1SN6-S2
N/ARMSCH-28
-137
RMINST-04RMINST-04
9393
Metering units MU2-M1, MU2-M2, MU2-M3MU6-N1, MU6-N2, MU6-N3MU6-N5
RMSCH-14RMSCH-14RMSCH-14
113113113
RMINST-07/08RMINST-07/08RMINST-07/08
97-9697-9697-96
Telecontrol cabinets Easergy T200-E02MEasergy T200-E04M
RMSCH-17RMSCH-17
139139
RMINST-11RMINST-11
9898
Extensible equipmentSchematicdiagram
Page number General arrangementdrawing
Page number
Ring main units 200 A RN2c-T1RN2c-T2RN2c-T3RN2c-T4RE2c-T25BRE2c-T25BSRE2c-T25ARE2c-T25AS
RMSCH-01RMSCH-03RMSCH-02RMSCH-15RMSCH-43RMSCH-44RMSCH-45RMSCH-46
104106105107108109110111
RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06RMINST-06
9595959595959595
Circuit breakers 200 A CE2-T2CE2-T3CE2-T7CE2-T11CE2-T12CE2-T13CE2-T14CE2-T15CE2-T16CE2-T19CE2-T20CE2-T21CE2-T25BCE2-T25BSCE2-T25ACE2-T25AS
RMSCH-07RMSCH-09RMSCH-06RMSCH-09RMSCH-19RMSCH-20RMSCH-20RMSCH-12RMSCH-13RMSCH-35RMSCH-35RMSCH-36RMSCH-47RMSCH-48RMSCH-49RMSCH-50
121123120123127128128125126133133134114115116117
RMINST-03RMINST-02RMINST-03RMINST-02RMINST-03RMINST-02RMINST-02RMINST-03RMINST-03RMINST-02RMINST-02RMINST-02RMINST-02RMINST-02RMINST-02RMINST-02
92919291929191929291919191919191
Circuit breakers 630 A CE6-T4CE6-T5CE6-T6CE6-T8CE6-T9CE6-T10CE6-T22CE6-T23CE6-T24CE6-T25BCE6-T25BSCE6-T25ACE6-T25AS
RMSCH-08RMSCH-10RMSCH-10RMSCH-23RMSCH-24RMSCH-24RMSCH-37RMSCH-38RMSCH-37RMSCH-47RMSCH-48RMSCH-49RMSCH-50
122124124131132132135136135114115116117
RMINST-03RMINST-02RMINST-02RMINST-03RMINST-02RMINST-02RMINST-02RMINST-02RMINST-02RMINST-02RMINST-02RMINST-02RMINST-02
92919192919191919191919191
Switches 630 A SE6-S1SE6-S2SE6-E1
N/ARMSCH-29N/A
-138-
RMINST-03RMINST-03RMINST-03
929292
Bus sections 630 A SE6-B1CE6-B3CE6-B5
N/ARMSCH-21RMSCH-22
-129130
RMINST-01RMINST-01RMINST-01
909090
89AMTED399086EN.indd
Installation drawings Typical switchboard
799
DE
5980
6
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
90 AMTED399086EN.indd
DE
5980
7
Panel type Page numberSE6-B1 79CE6-B3 80CE6-B5 81Approximate weight: 450 kg
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
799
Installation drawings Extensible unit ref RMINST-01
91AMTED399086EN.indd
DE
5980
8
Installation drawings Extensible unit ref RMINST-02
799
Panel type Page numberCE2-T3 58CE2-T11 58CE2-T13 61CE2-T14 60CE2-T19 58CE2-T20 58CE2-T21 60CE6-T5 68CE6-T6 68CE6-T9 71CE6-T10 71CE6-T22 68CE6-T23 71CE6-T24 68Approximate weight: 450 kg
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
92 AMTED399086EN.indd
Installation drawings Extensible unit ref RMINST-03
799
DE
5980
9
Panel type Page numberCE2-T2 56CE2-T7 57CE2-T12 59CE6-T4 67CE6-T8 69SE6-S1 74SE6-S2 75SE6-E1 76Approximate weight: 250 kg
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
93AMTED399086EN.indd
Installation drawings Non-extensible unit ref RMINST-04
DE
5981
1
Panel type Page numberCN2-T1 38CN2-T6 39SN6-S1 43SN6-S2 44Approximate weight: 250 kg
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
94 AMTED399086EN.indd
Installation drawings Extensible ring main unitc/w tee off cable box ref RMINST-22
985
DE
5981
0
Panel type Page numberRE2c-T1 30RE2c-T2 31RE2c-T3 32RE2c-T4 33Approximate weight: 300 kg
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
95AMTED399086EN.indd
Installation drawings Non-extensible ring main unitfor transformer mounting unit ref RMINST-06
DE
5981
2D
E60
268
Panel type Page numberRN2c-T1 19RN2c-T2 20RN2c-T3 21RN2c-T4 22RN2c-T5 23RN6c-T1 25Approximate weight: 300 kg
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
96 AMTED399086EN.indd
Installation drawings Non-extensible ring main unitc/w MU2 metering unit & tee off cable box ref RMINST-08
DE
5981
4
Panel type Page numberMU2-M1 47MU2-M2 48MU2-M3 49MU6-N1 52MU6-N2 52MU6-N3 52MU6-N5 52Approximate weight: 200 kg (MU2 only)MU2 shown connected to a non-extensible ring main unit
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
97AMTED399086EN.indd
Installation drawings Non-extensible metering unit ref RMINST-07
DE
5981
3
Panel type Page numberMU2-M1 47MU2-M2 48MU2-M3 49MU6-N1 52MU6-N2 52MU6-N3 52MU6-N5 52Approximate weight: 450 kg
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
98 AMTED399086EN.indd
Installation drawings Telecontrol cabinet ref RMINST-11
DE
5981
5D
E60
268
Panel type Page numberEasergy T200-E02 85Easergy T200-E04 85Approximate weight: 30 kg (Easergy only)
Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric Tel: +44 (0)113 290 3500
99AMTED399086EN.indd
Schematic diagrams Contents
Schematic legendsSpecifi cation
100
Ring main units accessories 102
Non-extensible / extensible ring main unitsref RMSCH-01, RMSCH-02, RMSCH-03, RMSCH-15, RMSCH-43, RMSCH-44, RMSCH-45, RMSCH-46
104
Non-extensible ring main unitRMSCH-42
112
Non-extensible metering unitref RMSCH-14
113
Non-extensible / extensible circuit breaker unitsref RMSCH-47, RMSCH-48, RMSCH-49, RMSCH-50
114
Non-extensible circuit breaker unitsref RMSCH-11, RMSCH-26
118
Extensible circuit breaker unitsref RMSCH-06, RMSCH-07, RMSCH-08, RMSCH-09, RMSCH-10, RMSCH-12, RMSCH-13, RMSCH-19, RMSCH-20, RMSCH-21, RMSCH-22, RMSCH-23, RMSCH-24RMSCH-35, RMSCH-36, RMSCH-37, RMSCH-38
120
Non-extensible switch unitsref RMSCH-28, RMSCH-29
137
Telecontrol unit block diagramref RMSCH-17
139
100 AMTED399086EN.indd
Schematic diagrams Schematic legendsSpecification
Fuse scheduleF1F2
VT secondary 16 A/link meteringVT secondary 2 A/link metering
Legends
EPSMRRL1RL2528996TFL/b/a/cASTCITC505150N51NINCMEFPIEPSREPSLESRESLTRS
earth position selected auxiliarymechanism reset switchclose relayopen relaycircuit breakerswitchdirect acting trip coiltime fuse linknormally closed auxiliary contactnormally open auxiliary contactnormally open make auxiliary contactammetershunt trip coilintegral trip coilinstantaneous overcurrenttime delayed overcurrentinstantaneous earth faulttime delayed earth faultminimum operating currentactuatorearth fault passage indicatorearth position selector rightearth position selector leftearth switch rightearth switch lefttrip reset spring
Symbols
DE
6026
9
CT & VT Ratios Panel type CT1 CT2 CT3 CT4 VT1 VT2RN2c-T1 100/50/5 A
Class X
RN2c-T2 200/1 AClass X
RN2c-T3 500/200/1 AClass X
RN2c-T4 500/200/1 AClass X
RN2c-T5 100/50/5 AClass X
RN2c-T25 200/100/1 A5P20
RN6c-T1 800/400/1 AClass X
RN6c-T25 800/400/1 A5P20
RE2c-T1 100/50/5 AClass X
RE2c-T2 200/1 AClass X
RE2c-T3 500/200/1 AClass X
RE2c-T4 500/200/1 AClass X
RE2c-T25 200/100/1 A5P20
MU2-M1 50/25/5 A7.5 VA Class 0.5s
11000/110 V50 VA Class 0.5
MU2-M2 100/50/5 A10 VA Class 0.5s
11000/110 V50 VA Class 0.5
MU2-M3 200/100/5 A10 VA Class 0.5s
11000/110 V50 VA Class 0.5
CN2-T1 200/1 AClass X
CN2-T6 100/50/5 AClass X
CN2-T25 200/100/1 A5P20
CE2-T7 100/50/5 AClass X
CE2-T2 200/1 AClass X
CE2-T3 200/1 AClass X
200/100/5 A10 VA Class 0.5s
11000/110 V50 VA Class 0.5
CE2-T11 200/1 AClass X
200/100/5 A10 VA Class 0.5s
6600/110 V50 VA Class 0.5
CE2-T12 200/1 AClass X
CE2-T13 200/1 AClass X
200/100/5 A10 VA Class 0.5s
11000/110 V50 VA Class 0.5
CE2-T14 200/1 AClass X
200/100/5 A10 VA Class 0.5s
6600/110 V50 VA Class 0.5
CE2-T15 200/1 AClass X
CE2-T16 200/1 AClass X
CE2-T19 200/1 AClass X
200/100/5 A10 VA Class 0.5s
13800/110 V/110 V50 VA Class 0.520 VA class 3 P
CE2-T20 200/1 AClass X
200/100/5 A10 VA Class 0.5s
11000/110 V/110 V50 VA Class 0.520 VA class 3 P
CE2-T21 200/1 AClass X
200/100/5 A10 VA Class 0.5s
13800/110 V/110 V50 VA Class 0.520 VA class 3 P
CE2-T25 200/100/1 A5P20
101AMTED399086EN.indd
Schematic diagrams Schematic legendsSpecification
Conditions1. All relays de-energised2. Switches shown in open position3. Auxiliary switch only operated between main ‘ON’ and main ‘OFF’ position (i.e. does not operate in earth position).
CT and VT types
CTICT2CT3CT4VT1VT2
3 phase protection CT’s1 phase indication CT2 phase metering CTEasergy 200E phase & earth fault CtPh-Ph metering VT (2 phases)Ph-E metering VT (3 phases)
CT & VT Ratios Panel type CT1 CT2 CT3 CT4 VT1 VT2
CE6-T4 800/1 AClass X
600/5 A5 VA Class 1.0
CE6-T5 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
11000/110 V50 VA Class 0.5
CE6-T6 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
6600/110 V50 VA Class 0.5
CE6-T8 800/1 AClass X
600/5 A5 VA Class 1.0
CE6-T9 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
11000/110 V50 VA Class 0.5
CE6-T10 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
6600/110 V50 VA Class 0.5
CE6-T22 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
13800/110 V/110 V50 VA Class 0.520 VA class 3 P
CE6-T23 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
13800/110 V/110 V50 VA Class 0.520 VA class 3 P
CE6-T24 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
11000/110 V/110 V50 VA Class 0.520 VA class 3 P
CE6-T25 800/400/1 A5P20
CE6-B3 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
11000/110 V50 VA Class 0.5
CE6-B5 800/1 AClass X
600/5 A5 VA Class 1.0
400/200/5 A10 VA Class 0.5s
11000/110 V50 VA Class 0.5
SE6-S2 800/1 AClass X
600/5 A5 VA Class 1.0
500/1 AClass X
SN6-S2 800/1 AClass X
600/5 A5 VA Class 1.0
500/1 AClass X
102 AMTED399086EN.indd
L1 L2 L3
DE
5982
0
Schematic diagrams Ring main units accessories
103AMTED399086EN.indd
Schematic diagrams Ring main units accessories
DE
5982
1
Circuit breaker
104 AMTED399086EN.indd
L1
L 2
L3
DE
5982
2Schematic diagrams Non-extensible / extensible
ring main unit ref RMSCH-01
Panel type Page numberRN2c-T1 19RE2c-T1 30For explanation of symbols see page 100
105AMTED399086EN.indd
DE
5982
4
Panel type Page numberRN2c-T3 21RE2c-T3 32For explanation of symbols see page 100
Schematic diagrams Non-extensible / extensible ring main unit ref RMSCH-02
L1
L 2
L3
106 AMTED399086EN.indd
DE
5982
3
Panel type Page numberRN2c-T2 20RE2c-T2 31For explanation of symbols see page 100
Schematic diagrams Non-extensible / extensible ring main unit ref RMSCH-03
L1
L 2
L3
107AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible ring main unit ref RMSCH-15
DE
5982
5
Panel type Page numberRN2c-T4 22RE2c-T4 33For explanation of symbols see page 100
L1
L 2
L3
108 AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible ring main unit ref RMSCH-43
DE
5985
3
Panel type Page numberRN2c-T25 24RE2c-T25 34For explanation of symbols see page 100
109AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible ring main unit ref RMSCH-44
DE
5985
4
Panel type Page numberRN2c-T25 24RE2c-T25 34For explanation of symbols see page 100
110 AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible ring main unit ref RMSCH-45
DE
5985
5
Panel type Page numberRN2c-T25 24RE2c-T25 34For explanation of symbols see page 100
111AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible ring main unit ref RMSCH-46
DE
5985
6
Panel type Page numberRN2c-T25 24RE2c-T25 34For explanation of symbols see page 100
112 AMTED399086EN.indd
Schematic diagrams Non-extensible ring main unit ref RMSCH-42
DE
5982
6
Panel type Page numberRN6c-T1 25For explanation of symbols see page 100
L1
L 2
L3
113AMTED399086EN.indd
Schematic diagrams Non-extensible metering unit ref RMSCH-14
DE
5983
4
Panel type Page numberMU2-M1 47MU2-M2 48MU2-M3 49MU6-N1 52MU6-N2 52MU6-N3 52MU6-N5 52For explanation of symbols see page 100
L1 L3
114 AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible circuit breaker units ref RMSCH-47
DE
5985
7
Panel type Page numberCN2-T25 40CE2-T25 64CE6-T25 70For explanation of symbols see page 100
115AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible circuit breaker units ref RMSCH-48
DE
5985
8
Panel type Page numberCN2-T25 40CE2-T25 64CE6-T25 70For explanation of symbols see page 100
116 AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible circuit breaker units ref RMSCH-49
DE
5985
9
Panel type Page numberCN2-T25 40CE2-T25 64CE6-T25 70For explanation of symbols see page 100
117AMTED399086EN.indd
Schematic diagrams Non-extensible / extensible circuit breaker units ref RMSCH-50
DE
5986
0
Panel type Page numberCN2-T25 40CE2-T25 64CE6-T25 70For explanation of symbols see page 100
118 AMTED399086EN.indd
Schematic diagrams Non-extensible circuit breaker units ref RMSCH-11
DE
5983
3
Panel type Page numberCN2-T6 39For explanation of symbols see page 100
L1 L 2 L3
119AMTED399086EN.indd
Schematic diagrams Non-extensible circuit breaker units ref RMSCH-26
DE
5984
3
Panel type Page numberCN2-T1 38For explanation of symbols see page 100
L1 L 2 L3
120 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-06
DE
5982
8
Panel type Page numberCE2-T7 57For explanation of symbols see page 100
L1 L 2 L3
121AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-07
DE
5982
9
Panel type Page numberCE2-T2 56For explanation of symbols see page 100
L1 L 2 L3
122 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-08
DE
5983
0
Panel type Page numberCE6-T4 67For explanation of symbols see page 100
L1 L 2
L 2
L3
123AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-09
DE
5983
1
Panel type Page numberCE2-T3 58CE2-T11 58For explanation of symbols see page 100
L1 L 2 L3
L1 L3
124 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-10
DE
5983
2
Panel type Page numberCE6-T5 68CE6-T6 68For explanation of symbols see page 100
L1 L 2
L 2
L 2
L3
L1 L3
125AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-12
DE
5983
5
Panel type Page numberCE2-T15 62For explanation of symbols see page 100
L1
L 2
L3
126 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-13
DE
5983
5
Panel type Page numberCE2-T16 63For explanation of symbols see page 100
L1
L 2
L3
127AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-19
DE
5983
7
Panel type Page numberCE2-T12 59For explanation of symbols see page 100
L1 L 2 L3
128 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-20
DE
5983
8
Panel type Page numberCE2-T13 61CE2-T14 60For explanation of symbols see page 100
L1 L 2 L3
L1 L3
129AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-21
DE
5983
9
Panel type Page numberCE6-B3 80For explanation of symbols see page 100
L1 L 2
L 2
L3
L1 L3
130 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-22
DE
5984
0
Panel type Page numberCE6-B5 81For explanation of symbols see page 100
L1 L 2
L 2
L3
L1 L3
131AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-23
DE
5984
1
Panel type Page numberCE6-T8 69For explanation of symbols see page 100
L1 L 2
L 2
L3
132 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-24
DE
5984
2
Panel type Page numberCE6-T9 71CE6-T10 71For explanation of symbols see page 100
L1
L 2
L 2 L3
L1 L3
133AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-35
DE
5984
6
Panel type Page numberCE2-T19 58CE2-T20 58For explanation of symbols see page 100
L1 L3
L1 L 2
L 2
L3
134 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-36
DE
5984
7
Panel type Page numberCE2-T21 60For explanation of symbols see page 100
L1 L 2
L 2
L3
L1 L3
135AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-37
DE
5984
8
Panel type Page numberCE6-T22 68CE6-T24 68For explanation of symbols see page 100
L1 L 2
L 2
L 2
L3
L1 L3
136 AMTED399086EN.indd
Schematic diagrams Extensible circuit breaker units ref RMSCH-38
DE
5984
9
Panel type Page numberCE6-T23 71For explanation of symbols see page 100
L1 L 2
L 2
L 2
L3
L1 L3
137AMTED399086EN.indd
Schematic diagrams Non-extensible switch units ref RMSCH-28
DE
5984
4
Panel type Page numberSN6-S2 44For explanation of symbols see page 100
L1 L 2 L3
138 AMTED399086EN.indd
Schematic diagrams Non-extensible switch units ref RMSCH-29
DE
5984
5
Panel type Page numberSE6-S2 75For explanation of symbols see page 100
L1 L 2 L3
139AMTED399086EN.indd
Schematic diagrams Telecontrol unit block diagram ref RMSCH-17
DE
5982
7
Panel type Page numberEasergy T200-E02M 85Easergy T200-E04M 85For explanation of symbols see page 100
L1
L2
90-230 V AC 50 Hz
L3
140 AMTED399086EN.indd
141AMTED399086EN.indd
Accessories Contents
Summary 142
Description 143
Non-extensible ring main unit c/w angled ring cable gland plates - ref RMINST-05
144
Tee-off cable box fi tted to SN6/CN2ref RMINST-09
145
Ringmaster range cabling accessoriesref RMINST-10
146
Protection options 147
142 AMTED399086EN.indd
Accessories Summary
Schneider Electric are able to provide a number of accessories to enhance the basic unit specifi cations. These accessories are detailed within the panel type specifi cations
AccessoriesThese are dispatched either:b Fitted to the unit within the works - these are accessories that are either too bulky, or need testing prior to despatchie; RMR-F47 - tee-off cable boxb Loose, boxed, for you to assemble on site. These items are either those that need to be supplied loose to ease installation: ie RMR-A48 which is a gland plate, or test equipment such as RMR-A202, VAP6.
OptionsThe following pages clarify options:RMR-F47 - Tee-off cable box (drawing RMINST 05/09)RMR-A50 - Angled gland tray (drawing RMINST 10)RMR-A317 - Angled gland tray (drawing RMINST 05)
143AMTED399086EN.indd
Accessories Description
RMR-A14/A15/A78/A79Busbar assemblies
b Each kit comprises a three phase set of busbars, 630 A b Specify at time of ordering: v 1 off RMR-A15 - end panel kit, plus busbar kits v Quantity required = No. of panels - 1
Note: Different busbar kits are required for metering units and bus-sectionsBusbars are dispatched loose.
RMR-A17Time fuse links
b 2 off time fuse links for overcurrent protectionOrder code Rating
RMR-A17/3 3 ampRMR-A17/5 5 ampRMR-A17/7 7.5 ampRMR-A17/10 10 ampRMR-A17/12 12.5 ampRMR-A17/15 15 amp
RMR-A202VAP 6 test unit
b Check operation of VIP 300, VIP 30 & VIP35 IDMT relays, unit injects 20 x Is to verify operation of microprocessor and outputs, and trip the CB.Complete with batteries.
DE
6024
5D
E60
270
PE
5831
0
144 AMTED399086EN.indd
Accessories Non-extensible ring main unit c/w angled ring cable gland plates ref RMINST-05
DE
6024
6
Panel type Page numberRN2c-T1 19RN2c-T2 20RN2c-T3 21RN2c-T4 22RN2c-T5 23Approximate weight: 300 kgThe above drawings refer to RMR-F324 tee-off cable box and RMR-A317 angled gland plate.Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
208208
145AMTED399086EN.indd
Accessories Tee-off cable box fitted to SN6/CN2 ref RMINST-09
DE
6024
7
Panel type Page numberCN2-T1 38CN2-T6 39SN6-S1 43SN6-S2 44Note: for installation where overpressure relief of the equipment is required please contact Schneider Electric Tel: +44 (0)113 290 3500
146 AMTED399086EN.indd
Accessories Ringmaster range cabling accessories ref RMINST-10
DE
5985
0
Panel type Page numberCE2 53-64CE6 65-71SE6 72-79CN2 36-40SN6 41-44Approximate weight: 250 kg
799
147AMTED399086EN.indd
DE
6024
9
Three types of protection systems are available for Ringmaster b Time Fuse Links - CT operated trip coils with provision for Time Fuse Links (TFL). b VIP Protection relays - self-powered IDMT, DT overcurrent and earth fault relays. b Sepam series 10 - IDMT, DT overcurrent, earth fault and thermal overload with
advanced functions and Modbus.
TFL protectionAn effective low cost option without compromising reliability.CT operated trip coils (with TFL) provides phase overcurrent and earth fault inverse time protection, the characteristic being given by a Time Fuse Link (TFL).This option is suitable for transformer protection up to 1600 kVA.
Recommended Time Fuse Link (TFL) settings to ESI 12-6Voltage Transformer rated power (kVA)
(kV) 200 315 500 800 1000 1250 1600CT ratio = 50/5 3.3 10 A TFLearth fault setting = 25 A (instantaneous trip)
150 A LV fuse6.6 5 A 10 A 15 A TFL
150 A 250 A 400 A LV fuse11 3 A 5 A 10 A 15 A TFL
200 A 300 A 400 A 560 A LV fuse13.8 3 A 5 A 10 A 15 A TFL
200 A 300 A 400 A 560 A LV fuseCT ratio = 100/5 3.3 5 A 10 A 15 A TFLearth fault setting = 30 A (instantaneous trip)
150 A 250 A 400 A LV fuse6.6 5 A 7.5 A 12.5 A 15 A TFL
250 A 400 A 560 A 560 A LV fuse11 5 A 7.5 A 10 A 12.5 A 15 A TFL
400 A 560 A 630 A 630 A 630 A LV fuse13.8 5 A 7.5 A 10 A 12.5 A 15 A TFL
400 A 560 A 630 A 630 A 630 A LV fuse
Benefi ts b Low cost b Fast clearance of LV faults b Simple to replace b Proven protection to EA standards b Fast tripping for MV earth faults b Improved discrimination with LV fuse
Principle of operationThe current transformer feeds a trip coil that is normally shunted by a time fuse link. In the event of a fault the fuse ruptures, diverting all the fault current through the trip coil, tripping the breaker. A residually connected trip coil provides instantaneous earth fault protection.
Protection application guideProduct CE2, CN2, RN2c, RE2c CE6, RN6cApplication Transformers Transformers Ring feeders Incomers
200-1600 kVA 400-3800 kVA 1900-12000 kVA 1900-12000 kVA 1900-12000 kVATime fuse Link b
IDMT VIP 300 b b b b
Note: a protection co-ordination study may be necessary to verify the type of protection. Consult your local Schneider Electric sales engineer if in doubt.
Protection selection guidePrimary current (A) 10 20 80 100 125 200 630Equivalent transformer rating at 11 kV 200 kVA 400 kVA 1600 kVA 1900 kVA 2400 kVA 3800 kVA 12000 kVAApplication Panel Protection
Transformer protection
CE2/CN2 Time Fuse Link b b b
RE2c/RN2c IDMT - VIP 30/35 b b b b b
RE2c/RN2c IDMT - VIP 300 b b b b b
Feeder protection
CE6/RN6c IDMT - VIP 300 b b b b
Accessories Protection options
148 AMTED399086EN.indd
149AMTED399086EN.indd
Schneider Electric, an overview and order form
Contents
OverviewBuilding systems and solutionsIndustrial systems and solutionsEnergy and infrastructure systems and solutions
150
Order formRing Main Unit (RMU)Ring Modular Range (RMR)
154
Index 156
150 AMTED399086EN.indd
Schneider Electric, an overview and order form
Overview
With over 100 years experience in the electrical industry, Schneider Electric has established itself as a world leader in the supply and manufacture of products for the distribution, monitoring and control of electrical power.
Schneider Electric regards its customers as commercial partners, who, like us, demand the highest standards of excellence in terms of products, projects and services.
Schneider Electric is proud to provide the solutions to meet their needs.
Schneider Electric operates the largest, dedicated sales force in the electrical industry.Sales engineers have specialist expertise and an understanding of the customer needs within each of the following market sectors:
b Building systems and solutions b Industrial systems and solutions b Energy and infrastructure systems and solutions.
PE
5831
1
151AMTED399086EN.indd
Schneider Electric, an overview and order form
Overview Building systems and solutions
The real reason for putting technology into buildings is to simplify tasks, enhance safety and improve the quality of life. Schneider Electric knows this and has created attractive, functional products for the residential building sector. Well being comfort and entertainment are key concepts in this area.
The same objectives apply to commercial buildings such as offi ces, hotels, shopping centres, hospitals, schools and care facilities for the elderly. Schneider Electric offer a wide range of solutions in the area of building management services and uses its expertise in all of these buildings to protect people and equipment.
Schneider Electric means greater comfort, lower operating costs and enhanced safety.Related industries
b Retail b Education b Health b Entertainment centres b Offi ces b Warehouses b Agriculture b Factory b Private residential b Public residential.
Principal customers in the construction market b Contracting authorities b Main contractors b Building engineers.
PE
5831
2P
E58
313
152 AMTED399086EN.indd
Schneider Electric, an overview and order form
Overview Industrial systems and solutions
Schneider Electric focus on performance in all areas of industry.Our products and services adapt to each specifi c business and environment, from discrete manufacturing and production lines to continuous processes in a wide variety of industries such as:
b Automotive b Food and beverage b Pharmaceuticals b Construction materials b Waste management.
Across a wide range of applications including: b Conveyors b Packaging b Materials handling b Hoisting.
PE
5831
4
PE
5700
8
153AMTED399086EN.indd
Schneider Electric, an overview and order form
Overview Energy and infrastructure systems and solutions
Schneider Electric is involved in the entire electrical distribution chain from power plants to end users. Customer demand for complete availability, uncompromising quality and absolute safety has made the search for excellence our key mission.Today, electrical substation and network protection, monitoring and control are highly effective in reducing outage time.Proven technologies offer a wide range of simple, effi cient and fl exible solutions for optimised, step by step investments.InfrastructureSchneider Electric is involved in developing infrastructure and transportation systems around the world. In areas where no failures can be tolerated, such as road and rail equipment, harbour installations and airports, Schneider Electric provides solutions in electrical distribution, control and monitoring, automation and supervision.Key markets
b Electricity distribution b Water b Rail b Airports b Seaports b Defence b Gas b Telecommunications b Road.
Principal customers in the electric power market b Power suppliers involved in generation and distribution b Utility companies b Major contractors b Large end user sites b Government departments.
PE
5831
5P
E58
316
154 AMTED399086EN.indd
Schneider Electric, an overview and order form
Order form Ring Main Unit (RMU)
Only one of the boxes (ticked X or fi lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic RMU confi guration Quantity
Rated voltage Ur (kV)
Impulse rating and short-time withstand 21 kA 3 s, 95 kVbil
RMU confi guration and protectionRN2c RE2c RE2c RN6c
200 A CB 200 A CB 200 A CB 630 A CBnon extensible left and right right extensible non extensible
Protection extensibleTLF VIP 30 VIP 35 VIP 300 Sepam 10
Metering (when the metering option is chosen, the impulse rating and short-time withstand are reduced at 16 kA 1 s, 75 kVbil)
Options for circuit breakerTransformer Freestanding Freestanding
mounted top bottomRN2c and RE2c RN6c
Operational itemsShunt trip coil 20-48 Vdc, 110-250 Vac/dc Motor pack (remote electrical operation) 24 Vdc 30 Vdc Mechanical key interlock (not available with motor option)
key free main OFF Key free earth ON Circuit breaker cable test facility Low gas pressure switch Mechanical trip push button VPIS (only with freestanding option) 3.3-7.2 kV 15-13.8 kV
Options for ring switch 1 - left hand sideRemote electrical indication (auxiliary switch) 1 x N/O, 1x N/C Motor pack (remote electrical operation) 24 Vdc 30 Vdc Mechanical key interlock (not available with motor option)
Key free main OFF Key free earth ON MV cable entry RN2c and RE2c Top Bottom
RN6c Bottom Earth fault passage indication (includes external current transformer)
Bardin Flair 212 Horstman Earth/M 2.0 Easergy T200 current transformers Voltage Presence Indication VPIS 3.3-7.2 kV 15-13.8 kV
Options for ring switch 2 - right hand sideRemote electrical indication (auxiliary switch) 1 x N/O, 1x N/C Motor pack (remote electrical operation) 24 Vdc 30 Vdc Mechanical key interlock (not available with motor option)
Key free main OFF Key free earth ON MV cable entry RN2c Top Bottom
RE2c and RN6c Bottom Earth fault passage indication (includes external current transformer)
Bardin Flair 212 Horstman Earth/M 2.0 Easergy T200 current transformers Voltage Presence Indication VPIS 3.3-7.2 kV 15-13.8 kV Busbar extension trunking (for RE2c to RMR circuit breaker or switch) RE2c only
AccessoriesPhase comparitor VAP6 TLF fuses (A) 3 5 7.5 10 12.5 15 Connection for Easergy - RMU Enter number of functions required
155AMTED399086EN.indd
Schneider Electric, an overview and order form
Order form Ring Modular Range (RMR)
Only one of the boxes (ticked X or fi lled by the needed value) have to be considered between each horizontal line. Green box X corresponds to none priced functions.
Basic RMR confi guration Quantity
Rated voltage Ur (kV)
Short-circuit current Isc (kA)
Load of circuit (A)
Panel confi guration and protectionNON EXTENSIBLE I EXTENSIBLE
CN2 SN6 MU2 CE2 CE6 SE6200 A 630 A 200 A 200 A 630 A 200 A
CB Switch Metering CB CB SwitchProtection No protection
TLF VIP 300 Sepam 10 Bus section Metering
OptionsNON EXTENSIBLE I EXTENSIBLE
CN2 SN6 MU2 CE2 CE6 SE6200 A 630 A 200 A 200 A 630 A 200 A
CB Switch Metering CB CB SwitchFreestanding Top
Bottom Transformer mounted (direct connection)
Shunt trip coil (multi ac/dc voltage range)
Remote electrical operation (actuator 24 Vdc)
Mechanical key free earth ON key interlock key free mean OFF Remote electrical operation (low gas pressure switch)
VPIS 3.3-7.2 kV 15-13.8 kV EFPI (includes external EFPI CT) Bardin Flair 212 Horstman Earth / M 2.0
AccessoriesBusbar End panel Phase comparitor VAP6 TLF fuses (A) 3 5 7.5 10 12.5 15 Connection for Easergy - RMR Enter number of functions required
156 AMTED399086EN.indd
Schneider Electric, an overview and order form
Index
A PageAccessories 142Actuator panel types 41, 42, 53, 54, 65Angled gland trays 142, 144Applications 150BBusbar options sections 143Bus sections 77, 78C200 A 36, 37600 A 65, 66Circuit breakers 53, 54Control & protection 7, 147DDrawing index 88EEasergy telecontrol unit 84EATS 6IIDMT protection 147IEC/BS standards 6MMetered CB’s 53, 54, 65, 66Metering units 45, 46Motor retrofi t 27, 28, 53, 54PProtection selection 7, 147Protection - TFL 7, 147Protection - VI 7, 147RRing main units extensible 53, 54Ring main units non-extensible 16, 17SSchematics 100Selection guide 14Self powered protection 147Switchboard GA 89Switches 41, 42, 72, 73TTelecontrol 84Telephone communication 84TFL protection 147Time fuse links 147VVIP protection 7, 147
Please note: Due to the constant progress in standards and equipment, the characteristics shown in the texts and images in this document are only binding once expressly confi rmed by ourselves
AMTED399086EN 10-2011
As standards, specifi cations and designs change from time to time, please ask for confi rmation of the information given in this publication.
Design: Schneider Electric Industries SASPhotos: Schneider Electric Industries SASPrinted: Altavia Connexion - Made in France