riovar /riovar - Компания ТЕХНО lifet-life.com.ua/img/files/ksb/riovar_riovar z.pdf ·...
TRANSCRIPT
Pump Catalogue Booklet1111.5-10 Riovar�/Riovar� Z
Circulator Pumpswith Manual Speed Variation
Fields of Application� Hot-water heating systems� Heat recovery systems
Medium HandledClean water or water treated in accordance with the relevantregulations, not containing aggressive, abrasive or solid sub-stances.Water with commercial antifreeze agents based on glycols(mixture ratio max. 1 : 1) with inhibitors (antirust).If the glycol content exceeds 20 %, the operating data have tobe checked and verified.
Operating DataScrew-ended pumps Flanged pumpsRp 1 and 1 1/4 DN 32 to 100
Q up to 6.2 m3/h, 1.7 l/s up to 80 m3/h, 22.2 l/sH up to 3.4 m up to 16 mP1 up to 170 W up to 3500 Wp 10 bar 6 bar, 10 bar on optiont +20 oC up to +130 oC
(For temperature limit values please refer to the pump variant table onpage 12)
Designation Riovar - Z 4 4 - 8 E
Type seriesTwin pumpNominal diameter in cm4-pole motorsMax. motor rating P2 in watt : 10Single-phase alternating current (D = three-phase current)
DesignRiovar: Maintenance-free wet rotor pump (glandless), flangedor screw-ended, four speed levels.Riovar Z: Riovar twin pump design for standby operation (inte-grated swing check valve) or peak-load operation on option(parallel operation).
BearingsMedium-lubricated special plain bearings.
MaterialsVolute casing Cast iron EN-GJL-250 1)Shaft Chrome steelImpeller PlasticBearings Special carbon1) to EN 1561 (previously GG-25)
Drive *)Canned motor, IP 42, thermal class F
1~230 V, 50 Hz3~400 V, 50 Hz
*) If a frequency inverter (included in the hyatronic mb standard design) is usedfor speed control (available for motor size 18 and above), make sure that themotor voltage is sinusoidal. Fit a sine filter, if required.
Special DesignSee pump variant table on page 12.
Riovar
3
Selection Chart, Twin Pumps ≈1400 1/min
The characteristic curves refer to operation of one pump.
Condensation-proofwinding, also suitable forcold-water operation
Can of antimagneticstainless steel
4 speed levelsallow exact adjustmentto the system conditions
Canned motor with highstarting torque at eachspeed level
Riovar
4
Screwed joint,above DN 32 flanges
Hydraulically optimizedimpeller of wear-resistantplastic
Carbon plain bearings,wear-resistant, safe torun dry, low-noise
Shaft of corrosion-resistant chrome steel
Riovar
7
Twin Pump Characteristic Curves ≈1400 1/minThe characteristic curves refer to operation of one pump.
Riovar
8
Technical DataRiovar 1) Speed
l lP1 Motor
t tiSwitch
l 3)Max. permissible operating pressure
ISO 7/I *)p
level protection2
plug 3) 6 bar 10 barRp or DN 1/min W A 2) kg kg
24-2 D 1 4321
1300125011501050
112866446
0.350.230.170.13
- C - - 00 126 839 5.4
24-8 D 1 4321
1350130012001150
15012010080
0.530.380.280.22
V C - - 00 126 841 7.3
34-2 D 1 1/4 4321
1300125011501050
112866446
0.350.230.170.13
- C - - 00 126 843 5.8
34-8 D 1 1/4 4321
1350130012001150
15012010080
0.530.380.280.22
V C - - 00 126 845 7.8
44-8 E 40 4321
1250120011001000
200190175155
1.11.050.950.85
V E 00 126 836 10.3 00 126 846 11.8
44-8 D 40 4321
1250115011001000
17014011085
0.530.380.280.22
V C 00 126 837 10.3 00 126 847 11.8
44-18 D 40 4321
130011501050850
365320260185
0.90.750.60.45
V C 29 120 663 19.4 29 120 664 20.9
54-18 D 50 4321
1350130012001100
290260220165
0.90.750.60.45
V C 29 120 665 14.0 29 120 666 16.2
54-30 D 50 4321
1350125011501050
635585490395
1.61.31.10.8
V C 29 120 667 25.0 29 120 668 27.6
54-100 D 50 4321
1400135013001200
1650150013301100
4.03.63.12.7
V C - - 29 120 669 67.0
64-30 D 65 4321
1400130012001100
580530450370
1.61.31.10.8
V C 29 120 670 27.0 29 120 671 29.8
64-48 D 65 4321
130012001050950
970880715560
2.21.91.51.2
V C 29 120 672 28.0 29 120 673 31.0
64-160 D 65 4321
1400130012001100
2500220018001350
6.15.34.63.7
V C - - 29 120 674 79.0
84-48 D 80 4321
1350130011501050
745685585490
2.21.91.51.2
V C 29 120 675 32.5 29 120 676 35.3
84-75 D 80 4321
1400135012501100
133012601140920
3.22.82.52.2
V C 29 120 677 38.5 29 120 678 40.4
84-250 D 80 4321
1400130012001100
3500310027002300
8.68.07.36.7
V C - - 29 120 679 97.0
104-110 D 100 4321
1400130012001100
1650150013001000
4.13.63.12.6
V C 29 120 680 43.5 29 120 681 46.8
104-250 D 100 4321
1400130012001100
3400320027002300
8.68.07.36.7
V C - - 29 120 682 109.5
Riovar
9
Technical Data
Riovar Z 1) Speedl l
P1 Motort ti
Switchl 3)
Max. permissible operating pressureplevel protection
2)plug 3) 6 bar 10 bar
DN 1/min W A2)
kg kg
Z 44-8 E 40 4321
1250120011001000
200190175155
1.11.050.950.85
V E 00 126 870 20.0 00 126 872 22.0
Z 44-8 D 40 4321
1250115011001000
17014011085
0.530.380.280.22
V C 00 126 871 20.0 00 126 873 21.0
Z 44-18 D 40 4321
130011501050850
365320260185
0.90.750.60.45
V C 48 837 867 42.0 48 837 873 44.0
Z 54-18 D 50 4321
1350130012001100
290260220165
0.90.750.60.45
V C 29 120 687 27.0 29 120 688 29.0
Z 54-30 D 50 4321
1350125011501050
635585490395
1.61.31.10.8
V C 48 837 868 54.5 48 837 874 57.0
Z 64-30 D 65 4321
1400130012001100
580530450370
1.61.31.10.8
V C 29 120 689 58.0 29 120 690 59.0
Z 64-48 D 65 4321
130012001050950
970880715560
2.21.91.51.2
V C 48 837 869 57.0 48 837 875 61.0
Z 84-48 D 80 4321
1350130011501050
745685585490
2.21.91.51.2
V C 29 120 691 62.0 29 120 692 64.0
Z 84-75 D 80 4321
1400135012501100
133012601140920
3.22.82.52.2
V C 48 837 870 72.0 48 837 876 73.0
Z 104-110 D 100 4321
1400130012001100
1650150013001000
4.13.63.12.6
V C 29 120 693 90.5 29 120 694 91.5
*) Gaskets are included in the scope of supply. For union ends and union nuts, see Pump Accessories.1) E = 1~230 V, D = 3~400 V2) - = No motor protection required, anti-jam motors.
V = Full protection of motor by way of integrated temperature switches in connection with Riovar switchgears DV or, for three-phase current pumps, DUV 2-G or DDV 4.3) Switch plug variants, if a Riovar switchgear is used.
Min. PressureMin. pressure p min at the pump suction nozzle to avoid cavita-tion noise at an ambient temperature of +40 °C and a pumped-water temperature of �max.:
The values are applicable up to 300 m above sea level. Forinstallation heights >300 m, +0.01 bar/100 m have to be added.
t 50 oC 95 oC 110 oC 130 oC
pminRiovar bar bar bar bar
24-2/34-224-8/34-8
0.050.05
0.20.2
0.80.8
2.12.1
44-844-18
0.050.05
0.20.5
0.81.1
2.12.4
54-1854-3054-100
0.050.050.3
0.30.51.0
0.91.11.6
2.22.42.9
64-3064-4864-160
0.050.050.3
0.30.51.0
0.91.11.6
2.22.42.9
84-4884-7584-250
0.050.050.3
0.30.51.0
0.91.11.6
2.22.42.9
104-110104-250
0.050.3
0.51.0
1.11.6
2.42.9
Fig
.
Outline Drawings Riovar
Riovar
10
Fig. 1 Fig. 2Flange dimensions PN 6, DIN 2531
PN 16, DIN 2533
Dimension Table
ISO 7/I ISO 228
D g k i zRiovar Rp/DN G a b1 b2 c h PN 6 PN 16 PN 6 PN 16 PN 6 PN 16 PN 6 PN 16 PN 6 PN 16
24-224-8
11
11
11/211/2
169181
5875
98106
204216
180180
Screw-ended pumps
34-234-8
11
1 1/41 1/4
22
169181
5875
98106
204216
180180
44-844-18
22
4040
--
173226
65106
106110
226296
250320
130130
150150
8080
8888
100100
110110
1414
1818
44
44
54-1854-3054-100
222
505050
---
210258286
88115165
110127146
272327391
280340440
140140-
165165165
9090
-
102102102
110110-
125125125
1414-
181818
44-
444
64-3064-4864-160
222
656565
---
265265353
128128175
127127148
342342462
340340475
160160-
185185185
110110
-
122122122
130130-
145145145
1414-
181818
44-
444
84-4884-7584-250
222
808080
---
269288394
134134185
127140166
357376521
360360500
190190-
200200200
128128
-
138138138
150150-
160160160
1818-
181818
44-
888
104-110104-250
22
100100
--
288426
143194
140166
391566
395550
210-
220220
148-
158158
170-
180180
18-
1818
4-
88
Riovar
11
Outline Drawing Riovar Z
Flange dimensions PN 6, DIN 2531PN 16, DIN 2533
Dimension Table
ISO 7/ID g k i z
Riovar Rp/DN a b1 b2 c h PN 6 PN 16 PN 6 PN 16 PN 6 PN 16 PN 6 PN 16 PN 6 PN 16
Z 44-8Z 44-18
4040
176226
146217
152210
244306
250320
130130
150150
8080
8888
100100
110110
1414
1818
44
44
Z 54-18Z 54-30
5050
209258
157217
168226
279343
280340
140140
165165
9090
102102
110110
125125
1414
1818
44
44
Z 64-30Z 64-48
6565
265265
222222
239239
370370
340340
160160
185185
110110
122122
130130
145145
1414
1818
44
44
Z 84-48Z 84-75
8080
269269
232232
252252
384384
360360
190190
200200
128128
138138
150150
160160
1818
1818
44
88
Z 104-110 100 280 250 274 395 395 210 220 148 158 170 180 18 18 4 8
Outline Drawing Riovar with Y-pipe Dimension Table
Flange dimensions of Y-pipes PN 16, DIN 2533
1) On these Riovar sizes, the casing diameter is so large that the motorcannot be arranged towards the front. Therefore the pumps have tobe moved 90o to the outside so that the motors point to the left andthe right. Dimension ”F” includes this arrangement.
Riovar withY-pipe
DN A B F L
44-844-18
4040
275275
190190
446485
630700
54-1854-3054-100 1)
505050
300300300
210210210
498542872
700760860
64-3064-4864-160 1)
656565
325325325
230230230
580580
1031
800800935
84-4884-7584-250 1)
808080
350350350
260260260
611624
1138
880880
1020
104-110104-250 1)
100100
325325
295295
6081177
9851140
44-8
E
24/3
4-2
D
24/3
4-8
D
44-8
D
44-1
8 D
54-1
8 D
54-3
0 D
54-1
00 D
64-3
0 D
64-4
8 D
64-1
60 D
84-4
8 D
84-7
5 D
84-2
50 D
104-
110
D
Z 4
4-8
E
Z 4
4-18
D
Z 5
4-18
D
Z 5
4-30
D
Z 6
4-30
D
Z 6
4-48
D
Z 8
4-48
D
Z 8
4-75
D
Z 1
04-1
10 D
104-
250
D
Z 4
4-8
D
Zubehör siehe Seite 79
Riovar
12
Riovar (Z) Pump Variants n = 1400 1/min
Single Pumps Twin Pumps
X standard programme 3)
S special design
Pipe connectionswith set of screw unions Rp 1 or Rp 1 1/4 X X
Flange PN 6 /DIN 2531 Press. gauge connect. Rp 1/8 X X X X X X X X X X X X X X X X X X X X
Flange PN 16 /DIN 2533 Press. gauge connect. Rp 1/8 X X X X X X X X X X X X X X X X X X X X X X X X
Max. permissible operating pressure p6 bar X X X X X X X X X X X X X X X X X X X X
10 bar X X X X X X X X X X X X X X X X X X X X X X X X X X
16 bar (casing GG-20) S S S S S S S
Pump casing materialsCast iron GG-20/25 X X X X X X X X X X X X X X X X X X X X X X X X X X
Nodular cast iron GGG-40.3 (flanges PN 16; p = 16 bar) S S S S S S S S S S S S S S S S S
Perm. temp. ranges of medium handled (water)+20 oC to +130 oC X X X X X X X X X X X X X X X X X X X X X X X X X X
Connection to following types of power supply1~230 V, 50 Hz (special a. c. current motor) X X
3~400 V, 50 Hz X X X X X X X X X X X X X X X X X X X X X X X X
3~230 V, 3~415 V, 3~500 V, 50 Hz S S S S S S S S S S S S S S S S S S S S S S S S S
3~220 V, 3~380 V, 3~440 V, 60 Hz S S S S S S S S S S S S S S S S S S S S S S S S S
Motor protectionNot required X
Integrated full motor protection 4) X X X X X X X X X X X X X X X X X X X X X X X X X
Speed variationManual 4-level control X X X X X X X X X X X X X X X X X X X X X X X X X X
Automatic 1)time-dependent on/off X
time-dependent 2-level control X X X X X X X X X X X X X X X X
load-dependent 2-level control X X X X X X X X X X X X X X X X
load-dependent 4-level control X X X X X X X X X X X X X X X X X X X X X X X X
load-dependent infinitely variable speed adjustment X X X X X X X X X X X X S X S X X X X X X X X X X
time-dependent alternate operation control 2) X X X X X X X X X X
load-dependent alternate operation control 2) X X X X X X X X X X
Switch plug C C E C C C C C C C C C C C C C E C C C C C C C C C
1) See table of switchgears, pages 13 and 14.2) Speed change-over nmax/nmin can be set, if one pump was pre-set
to nmax and the other to nmin by hand.3) Gaskets are included in the scope of supply. For union ends and
union nuts, see Pump Accessories.4) Integrated circuit breakers in connection with Riovar switchgears
(see Accessories).
Switch plug variantsE C
Riovar
13
Riovar Switchgears
Switchgears for Riovar single pumps Riovar Z twin pumps
Switchgears DV DVP MDV EUV 2-G DUV 2-G DDV 4 DTV 4 DUV 2-ZG DDV 4-Z DTV 4-Z
RiovarSwitchplug E C C C C C
24/34-2 D C X X X
24/34-8 D C X X X X X X
44-8 E E X X X
44-8 D C X X X X X X
44-18 D C X X X X X X
54-18 D C X X X X X X
54-30 D C X X X X X X
54-100 D C X X X X X X
64-30 D C X X X X X X
64-48 D C X X X X X X
64-160 D C X X X X X
84-48 D C X X X X X X
84-75 D C X X X X X X
84-250 D C X X X X X
104-110 D C X X X X X X
104-250 D C X X X X X
Z 44-8 E E X X X
Z 44-8 D C X X X X X
Z 44-18 D C X X X X X
Z 54-18 D C X X X X X
Z 54-30 D C X X X X X
Z 64-30 D C X X X X X
Z 64-48 D C X X X X X
Z 84-48 D C X X X X X
Z 84-75 D C X X X X X
Z 104-110 D C X X X X X
Technical Data of Riovar Switchgears
Riovar
15
Accessories for Twin Pumps
UnionPipe end Pump end Ident. No. ~kg
Y-pipes for twin pumps *) suction sidePN 10 / 16 discharge side
suction sidedischarge sidesuction sidedischarge sidesuction sidedischarge sidesuction sidedischarge side
DN 40DN 40DN 50DN 50DN 65DN 65DN 80DN 80
DN 100DN 100
DN 40DN 40DN 50DN 50DN 65DN 65DN 80DN 80
DN 100DN 100
40 000 688 L40 000 679 L40 000 689 L40 000 680 L40 000 690 L40 000 681 L48 936 065 L48 936 202 L40 000 692 L40 000 440 L
12.013.015.017.019.020.025.028.033.035.0
Wafer-type non-return valvePN 6 - 16
DN 40DN 50DN 65DN 80
DN 100
DN 40DN 50DN 65DN 80
DN 100
48 860 616 L48 860 617 L48 860 618 L48 860 619 L48 860 620 L
0.61.01.32.02.8
*) Scope of supply: bolts, nuts, gaskets and integrated changeover flap (on discharge side only)
Screw Union Sets and Union Ends
UnionPipe end Pump end Ident. No. ~kg
Screw union sets **)with internal thread malleable cast ironwith internal thread malleable cast iron
Rp 1Rp 1 1/4
G 1 1/2G 2
40 980 836 L40 980 837 L
0.20.2
**) Scope of supply: two union nuts, union ends and gaskets each
L = available ex stock
1
1
Riovar
16
Electrical Accessories
RiovarLength x height x depth
mm 1~ 3~ ~kg
Riovar switchgear DV 84 x 130 x 66for full motor protection release and manual start-up/shut-down.
Required for motor sizes ..-8 E/D and above,unless switchgears type EUV 2-G or DUV 2-(Z)G or DDV 4-(Z) or DTV 4-(Z) are used.
X X 00 521 822 0.35
Riovar switchgear DVP 84 x 130 x 66Switchgear as above, but with volt-free contacts for operation and fault message.
X X 01 018 335 0.35
Riovar swichgear MDVfor full motor protection release
Plug-in module, suitable for Riovar with three-phase current motor with thermal contact terminal,for motor sizes 8 D to 130 D.
X 01 018 336
Temperature sensor ET 2, 45 x 100 x 58signal transmitter for temperature-dependent change-over with switchgears EUV 2-G, DUV 2-G, DUV 2-ZG or MS.
X X 00 521 825 0.4
Riovar switchgear EUV 2-G 206 x 146 x 74with integrated full motor protection release, for automatic change-over between maximum and minimum speedby a timer with daily program.By day speed changing may, in addition, also be effectedload-dependent by means of an external transmitter: dependingon the feed temperature with temperature sensor ET 2.With 3 m pump connection cable with special plug variant E.
X 01 018 337 1.5
Riovar switchgear DUV 2-G 225 x 260 x 70with integrated full motor protection release, for automaticchange-over between maximum and minimum speed by timerwith daily program, e. g. for reduction to lower speed at night.With 3 m pump connection cable with special plug variant C.By day speed changing may, in addition, also be effectedload-dependent by means of external transmitters:- depending on feed temperature by means of temperature
sensor ET 2 - depending on differential pressure by means of differential
pressure contact gauge DK.
X 00 103 994 1.5
Riovar switchgear DDV 4 225 x 260 x 70with integrated full motor protection release.Change-over between 4 speeds depending on differentialpressure. Exact energy-saving adjustment to varyingrequirements. Overruling timer effects reduction to speed atnight.With 3 m pump connection cable with special plug variant C.Always required:differential pressure contact gauge DK.
X 00 103 995 3.2
Riovar switchgear DTV 4 225 x 260 x 70with integrated full motor protection release.Change-over between 4 speeds depending on temperature or differential temperature. Exact energy-savingadjustment to varying requirements. Overruling timer effects reduction to speed at night.With 3 m pump connection cable with special plug variant C, with 2 clip-on sensors as signal transmitters(temperature-dependent control requires only 1 transmitter), with 5 m cable each,with 2 strap retainers for fixing to pipes up to DN 100.
X 01 018 338 3.2
4
1 4
1
4
1 4
1
Riovar
17
Electrical Accessories
RiovarLength x height x depth
mm 1~ 3~ ~kg
Riovar switchgear DUV 2-ZG 225 x 260 x 70with integrated full motor protection release.For time-dependent change-over from pump I to pump II or from pump I to pumps I + II (parallel operation). Manual preselection of different speeds for pump I(min./reduction at night) and pump II (max./operation by day)allows low speed by night and high speed by day. In addition, change-over from pump I to pump II or from pump I to pump I + II by day can also be effected load-dependent by means of external transmitters:- depending on feed temperature by means of temperature
sensor ET 2 - depending on differential pressure by means of differential
pressure contact gauge DK.The possibility of operating pump I and II in parallel in the case ofpeak heat consumption allows selection of a low-cost twin pumpfor medium heat consumption.
X X 00 103 996 2.2
Riovar switchgear DDV 4-Z 2 times 225 x 260 x 70Time-dependent change-over from pump I to pump II andchange-over between 4 speeds of on-duty pump depending ondifferential pressure. Alternatively pump I and II can be operated in parallel, with one pump working at speed level ,while the other one is started up from speed levels throughdepending on the differential pressure (parallel operation).Integrated full motor protection release.Exact energy-saving adjustment to varying requirements.Overruling timer effects reduction to speed at night.With 2 x 3 m pump connection cable with special plug variant C. Always required:differential pressure contact gauge DK.
X 00 103 997 6.2
Riovar switchgear DTV 4-Z 2 times 225 x 260 x 70Time-dependent change-over from pump I to pump II andchange-over between 4 speeds of on-duty pump depending ontemperature or differential temperature.Alternatively pump I and II can be operated in parallel, withone pump working at speed level , while the other one isstarted up from speed levels through depending on thetemperature or differential temperature (parallel operation).Integrated full motor protection release.Exact energy-saving adjustment to varying requirements.Overruling timer effects reduction to speed at night.With 2 x 3 m pump connection cable with special plug variant C,with 2 clip-on sensors as signal transmitters with 5 m cable each(temperature-dependent control requires only 1 transmitter),with 2 strap retainers for fixing to pipes up to DN 100.
X 01 018 339 6.2
Riovar
18
Electrical Accessories
Riovarmm 1~ 3~ ~kg
Differential pressure contact gauge DK ø132 x 101 X Xfor change-over between 2 or 4 speeds (as required by Riovar switchgear) depending on thedifferential pressure.5 m connection cable
Effective range 0 to 0.6 bar DK 6
Effective range 0 to 1.0 bar DK 10
Effective range 0 to 1.6 bar DK 16
24-2/-834-2/-844-854-1864-3084-48
44-1854-3064-4884-75104-110
54-10064-16084-250104-250
00 521 838
00 521 839
00 521 840
1.8
1.8
1.8