TS0070UK01 RLS/E-EV MX SERIES RLS 300/E MX 600/1250 ÷ 3550 kW RLS 400/E MX 800/1800 ÷ 4300 kW RLS 300/EV MX 600/1250 ÷ 3550 kW RLS 400/EV MX 800/1800 ÷ 4300 kW RLS/E-EV MX series burners are characterised by a modular monoblock structure that means all necessary components can be combined in a single unit thus making installation easier, faster and, above all, more flexible. The series covers a firing range from 600 to 4300 kW, and they have been designed for use in hot water boilers, overheated water boilers as well as steamboilers. Operation can be “two stage progressive” or alternative “modulating” with the installation of a PID logic regulator. The burner can, therefore, supply with precision the demanded power, guaranteeing an high efficiency system level and the stability setting, obtaining fuel consumption and operating costs reduction. The innovative combustion head, adjustment system ensures perfect movement during modulation as well as reducing noise and pollutants. LOW NOx DUAL FUEL BURNERS

Upload: lethu

Post on 15-Feb-2019

236 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

TS0070UK01

RLS/E-EV MX SERIES RLS 300/E MX 600/1250 ÷ 3550 kWRLS 400/E MX 800/1800 ÷ 4300 kWRLS 300/EV MX 600/1250 ÷ 3550 kWRLS 400/EV MX 800/1800 ÷ 4300 kW

RLS/E-EV MX series burners are characterised by a modular monoblock structure thatmeans all necessary components can be combined in a single unit thus making installationeasier, faster and, above all, more flexible.The series covers a firing range from 600 to 4300 kW, and they have been designed foruse in hot water boilers, overheated water boilers as well as steamboilers. Operation canbe “two stage progressive” or alternative “modulating” with the installation of a PID logicregulator. The burner can, therefore, supply with precision the demanded power, guaranteeingan high efficiency system level and the stability setting, obtaining fuel consumption andoperating costs reduction.The innovative combustion head, adjustment system ensures perfect movement duringmodulation as well as reducing noise and pollutants.

LOW NOx DUAL FUEL BURNERS

Page 2: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

TECHNICAL DATAA

pp

rova

lFu

el /

air

dat

aE

lect

rica

l d

ata

Em

issi

ons

600/1250÷3550 800/1800÷4300 600/1250÷3550 800/1800÷4300

516/1075÷3053 688/1548÷3698 516/1075÷3053 688/1548÷3698

50/105÷299 67/151÷362 50/105÷299 67/151÷362

60/125-355 80/180÷430 60/125-355 80/180÷430

70/145-412 93/209÷500 70/145-412 93/209÷500

included in LMV51 included in LMV51 included in LMV52 included in LMV52

6,5 9,5 6,5 9,5

4,5 7,5 4,5 7,5

9,1-15,8 17,5 - 30 9,1-15,8 17,5 - 30

51-86 113 - 195 51-86 113 - 195

83 85 83 85

CE in progress CE in progress -- --

two stages progressive/modulating

1 ÷ 4

SQM 48 (OIL and GAS)

0/60

11,86

0,82

4-6

TA4

870 (20 bar)

25

50

NO

10

0,71

8,6

0,78

--

--

--

reverse blade fan wheels

60

3/50/400 (±10%)

1/50/430 (±10%)

2

--

54

1,5

3,7

7xIn

54

54

N.A.

230 V - 2 x 5 kW

1,9 A - 35 mA

Intermittent (at least 1 stop every 24 h) or Continuous (at least 1 stop every 72 h)

N.A.

< 10

< 2

< 2

< 185

< 10

< 80

90/396 - 89/336 - 73/23 EEC

EN 267 - EN 676

Since the Company is constantly engaged in the production improvement, the aesthetic and dimensional features,the technical data, the equipment and the accessories can be changed.This document contains confidential and proprietary information of RIELLO S.p.A. Unless authorised, this informationshall not be divulged, nor duplicated in whole or in part.

Reference conditions: Temperature: 20°C - Pressure: 1000 mbar - Altitude: 100 m a.s.l. - Noise measured at a distance of 1 meter.

RLS 400/E MX RLS 300/E MX RLS 400/EV MX RLS 300/EV MX

2

type

s

kW

Mcal/h

°C min./max.

kWh/kg

kg/l

mm2/s (cSt)

kg/h

type

kg/h

bar

max. °C

kWh/Nm3

kg/Nm3

Nm3/h

kWh/Nm3

kg/Nm3

Nm3/h

kWh/Nm3

kg/Nm3

Nm3/h

type

max °C

Ph/Hz/V

Ph/Hz/V

type

kW

kW

kW

IP

kW

A

A

IP

kW

A

A

IP

type

V1 - V2

I1 - I2

dB (A)

W

mg/kWh

N° Bacharach

mg/kWh

mg/kWh

mg/kWh

mg/kWh

Model

Burner operation mode

Modulation ratio at max. output

Servomotorrun time

Heat output

Working temperature

net calorific value

Light Oildensity

viscosity at 20°C

delivery

Pumpdelivery

Atomised pressure

Fuel temperature

Fuel pre-heater

net calorific value

G20 density

gas delivery

net calorific value

G25 density

gas delivery

net calorific value

LPG density

gas delivery

Fan

Air temperature

Electrical supply

Auxiliary electrical supply

Control box

Total electrical power

Auxiliary electrical power

Heaters electrical power

Protection level

Pump motor electrical power

Rated pump motor current

Pump motor start up current

Pump motor protection level

Fan motor electrical power

Rated fan motor current

Fan motor start up current

Fan motor protection level

Ignition transformer

Working

Sound pressure

Sound power

CO emission

Light Oilgrade of smoke indicator

CxHy emission

NOx emission

G20CO emission

NOx emission

Directive

Conforming to

Certification

Page 3: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

FIRING RATES

Test conditions conforming to EN 676:

Temperature: 20°CPressure: 1000 mbarAltitude: 100 m a.s.l.

0

4

8

12

10

6

2

14

18

16

00

40

80

120

100

60

20

140

180

160

RLS 300/E-EV MX RLS 400/E-EV MX

hP

a (m

bar

)

mm

H2O

3

Mcal/h15001000500 2000 2500 3000 3500 4000 4500

kW500 10000 1500 2000 2500 3000 3500 4000 4500 5000

19190

Useful working field for choosing the burner

Modulation range

Page 4: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

The burners are fitted with a butterfly valve to regulate the fuel, controlled by the main managementmodule of burner through a high precisionservomotor.Fuel can be supplied either from the right orleft sides, on the basis of the applicationrequirements.A maximum gas pressure switch stops theburner in case of excess pressure in the fuelline.The gas train can be selected to best fit systemrequirements depending on the fuel output andpressure in the supply line.The gas trains are “Multibloc” and “Composed”type (assembly of the single components)without seal control. This function is includedin the burner management module.

GAS TRAIN

FUEL SUPPLY

Gas input pipework

Manual valve

Anti-vibration joint

Pressure gauge with pushbutton cock

Filter

Pressure regulator (vertical)

Minimum gas pressure switch

VS safety solenoid (vertical)

VR regulation solenoid (vertical)Two settings: - firing output (rapid opening)

- maximum output (slow opening)

Gasket and flange supplied with the burner

Gas adjustment butterfly valve

Burner

Gas train-burner adapter

Maximum gas pressure switch

Combustion head pressure

Pressure downstream from the regulator

Pressure upstream from the filter

Gas train supplied separately, with the code given in the table

Installer’s responsibility

1

2

3

4

5

6

7

8

9

10

11

12

14

15

P1

P2

P3

L

L1

MULTIBLOC gas train type MBC 1200

COMPOSED gas train type MBC 1900-3100-5000

L L1

Example of the RLS/E MX gas adjustment butterfly valve.

12

12

4

P1

15 1110

14 6

L L1

9 8

7

5

4

P3P2

3 2 1

P1

1511

10

14 9 6 8

7

5

4

P3P2

3 2 1

Page 5: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

COMPOSEDGAS TRAINS

MULTIBLOCGAS TRAINS

Y

ZX

Øo

Y

Z X

Øi

Øo

Name

MBC 1200 SE 50

MBC 1900 SE 65 FC

MBC 3100 SE 80 FC

MBC 5000 SE 100 FC

Code

3970221

3970222

3970223

3970224

Ø i

2”

DN 65

DN 80

DN 100

X mm

573

583

633

733

Y mm

161

237

240

350

Z mm

425

430

500

576

Ø o

2”

DN 65

DN 80

DN 100

Example of gas train“COMPOSED” typewithout seal control

Example of gas train“MULTIBLOC” typewithout seal control

Øi

Gas trains are approved by standard EN 676 together with the burner.

The overall dimensions of the gas train depends on how they are constructed. The following tableshows the maximum dimensions of the gas trains that can be fitted to RLS 300-400/E-EV MX burners,intake and outlet diameters.The maximum gas pressure of gas train “Multibloc” type is 360 mbar, and that one of gas train“Composed” type is 500 mbar.MULTIBLOC guarantees a range of pressure towards the burner from 3 to 60 mbar. For version DN65 and DN 80 is from 20 to 40 mbar. The range of pressure in the MULTIBLOC with flange can bemodified choosing the stabiliser spring (see gas train accessory).

5

Page 6: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

PRESSURE DROP DIAGRAM

RLS 300/E-EV MX

RLS 400/E-EV MX

The diagrams indicate the minimum pressure drop of the burners with the various gas trains thatcan be matched with them; at the value of these pressure drop add the combustion chamber pressure.The value thus calculated represents the minimum required input pressure to the gas train.

NATURAL GAS

note Please contact the Riello Burner Technical Office for different pressure levels from those aboveindicated and refer to the technical manual for the correct choice of the spring.

MBC 1200 gas train: the minimum operating pressure (*) is higher or equal to 10 mbar.The gas train has to be installed next to the burner (if needed, only with the adapters listed inthe catalogue) and it has to operate in its own working field.

MBC 1900-3100-5000 gas train: the minimum operating pressure (*) is higher or equal to15 mbar. The gas train has to be installed next to the burner (if needed, with the adapters listedin the catalogue) and it has to operate in its own working field.

(*) it is the upstream gas train pressure in full load operation conditions.

Gas train

MBC 1200 SE 50

MBC 1900 SE 65 FC

MBC 3100 SE 80 FC

MBC 5000 SE 100 FC

Code

3970221

3970222

3970223

3970224

Adapter

3000826 ( I )

3010221 ( I )

3010222 ( I )

3970223 ( I )

Seal Control

(*)

(*)

(*)

(*)

Gas train

MBC 1200 SE 50

MBC 1900 SE 65 FC

MBC 3100 SE 80 FC

MBC 5000 SE 100 FC

Code

3970221

3970222

3970223

3970224

Adapter

3000826 ( I )

3010221 ( I )

3010222 ( I )

3970223 ( I )

Seal Control

(*)

(*)

(*)

(*)

(*) The seal control is managed by the control box LMV51/LMV52.

(*) The seal control is managed by the control box LMV51/LMV52.

mba

r

ΔP

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

pm

bar

ΔP

Com

busti

on h

ead

and

gas

train

Com

busti

on h

ead

Pres

sure

dro

p

Mcal/h

10

20

0

G25G20

0

30

40

50

60

70

80

90

20

40

60

80

100

120

140

160

180

200

220

240

260

280

MBC

SE

1900

MBC

SE 31

00

MBC

SE

1200

3000 35001500 25002000500 1000

kW2500 350030002000 4000500 1000 15000

0

100

G25G20

6

MBC

SE 5

000

Mcal/h

kW2500 350030002000 4000 4500

3000 400035001500 25002000

500 1000 1500

500 1000

20

40

0 0

60

80

100

120

140

20

40

60

80

100

120

140

160

180

200

MBC SE 1

900

MBC SE 3100

MBC

SE

1200

MBC SE 5000

Page 7: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8 1 2 3 4 5 106 20

50 60 10080 200 400 800 1000600

3

69

12152230

45 61 76 95 122 152 V1 2 3 4 5 6 7 8 10 20 30 40

1,4

1/2

3/4

1"

1" 1/2

6"

1" 1/4

4"

3"2" 1/22"

PRESSURE DROP (mbar)

PIPE DIAMETER

PIPE LENGTH (m)

= Gas output Nmc/h

1 - G20= 0,62 - G25

1,18 - G31{f

V

15,34

7

Figure A

The following diagram enables pressure drop in a pre-existing gas line to be calculated and to select thecorrect gas train.The diagram can also be used to select a new gas line when fuel output and pipe length are known. Thepipe diameter is selected on the basis of the desired pressure drop. The diagram uses methane gas asreference; if another gas is used, conversion coefficient and a simple formula (on the diagram) transformthe gas output to a methane equivalent (refer to figure A). Please note that the gas train dimensions musttake into account the back pressure of the combustion chamber during operations.

Control of the pressure drop in an existing gas line or selecting a new gas supply line.The methane output equivalent is determined by the formula fig. A on the diagram and the conversioncoefficient.

Once the equivalent output has been determined on the delivery scale ( ), shown at the top of thediagram, move vertically downwards until you cross the line that represents the pipe diameter; at thispoint, move horizontally to the left until you meet the line that represents the pipe length.Once this point is established you can verify, by moving vertically downwards, the pipe pressure dropof on the botton scale below (mbar).By subtracting this value from the pressure measured on the gas meter, the correct pressure value willbe found for the choice of gas train.

Example: - gas used G25- gas output 9.51 mc/h- pressure at the gas meter 20 mbar- gas line length 15 m- conversion coefficient 0.62 (see figure A)

- equivalent methane output = 9.51 = 15.34 mc/h0.62

- once the value of 15.34 has been identified on the output scale ( ), moving vertically downwards youcross the line that represents 1" 1/4 (the chosen diameter for the piping);

- from this point, move horizontally to the left until you meet the line that represents the length of 15 mof the piping;

- move vertically downwards to determine a value of 1.4 mbar in the pressure drop botton scale;- subtract the determined pressure drop from the meter pressure, the correct pressure level will be found

for the choice of gas train;

- correct pressure = ( 20-1.4 ) = 18.6 mbar

V

V

V

SELECTING THE FUEL SUPPLY LINES

Page 8: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

HYDRAULIC CIRCUIT

EN 267 > 100 Kg/h (TRD 604, NBN)

The hydraulic circuit of the RLS/E-EV MX series of burnersis characterised by a fuel pump with an independentmotor.The burners are fitted with two valves (a safety valveand an operation valve) and an oil filter along the oilline from the pump to the nozzle.A pressure regulator on the return circuit from the nozzleenables the quantity of fuel burnt to be varied.Two safety valves on the return circuit avoid oil leakagefrom the nozzle when the burner is in stand-by andprepurge phase.The models are fitted with a maximum pressure switchon the oil return circuit, and a minimum oil pressureswitch on the oil line from the pump to the nozzle.The burner is suitable for continuous operation.

Example of the RLS/E-EV MX burner hydraulic circuit

P

PO min

VF

VS

MM

NL

U

AT

MR

SM

RO

PO max

VR

VR1

Pump with filter and pressure regulator

Min. oil pressure switch on the delivery circuit

Operating valve

Safety valve on the delivery circuit

Pressure gauge on the delivery circuit

Nozzle pipe

Nozzle

Actuator for opening and closing the nozzle needle

Pressure gauge on the return circuit

Servomotor

Pressure regulator on the return circuit

Max. oil pressure switch on the return circuit

Safety valve on the return circuit

Safety valve on the return circuit

P

VS

POmax RO

SM

VR

MRPOmin

U

NL

VF

VR1

M

MM

8

Page 9: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

The fuel feed must be completed with the safety devices required by the local norms.

The table shows the choice of piping diameter, depending on the difference in height between theburner and the tank and their distance.

With ring distribution oil systems, the feasible drawings and dimensioning are the responsibilityof specialised engineering studios, who must check compatibility with the requirements andfeatures of each single installation.

note

Model

Diameter piping

+H, -H (m)

+2,0

+1,5

+1,0

+0,5

0

-0,5

-1,0

-1,5

-2,0

-3,0

Ø1/2”

L max (m)

25

23

20

18

15

12

10

8

5

3

Ø 3/4”

L max (m)

85

80

70

65

60

50

45

35

30

15

H

Ø

P

V

1

2

3

4

5

6

7

8

9

10

7

10

9 5 V

P

+H

-H

8

1

4

10 cm2

57 3

9

6

6

MAXIMUM EQUIVALENT LENGTH FOR THE PIPING L[m]

Difference in height pump-foot valve

Internal pipe diameter

Max. height 10 m

Height 4 m

Burner

Burner pump

Filter

Manual shut off valve

Suction pipework

Bottom valve

Remote controlled rapid manualshut off valve(compulsory in Italy)

Type approved shut off solenoid valve(compulsory in Italy)

Return pipework

Check valve

RLS/E-EV MX

9

SELECTING THE FUEL SUPPLY LINES

Page 10: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

The ventilation unit comes witha sound proofing radialregulating system.All the burners in the RLS/E-EVMX series are fitted with fans

with reverse curve blades, which give excellent performanceand are fitted in line with the combustion head. The air flowand sound-deadening materials used in the construction aredesigned to reduce sound emissions to the minimum andguarantee high levels of performance in terms of output andair pressure.A high precision servomotor through the main managementmodule installed on each burner of RLS/E-EV MX series,controls the air dampers position constantly, guaranteeingan optimal fuel-air mix.

COMBUSTION HEAD

VENTILATION

The innovative combustionhead adjustment systemensures perfect movementduring modulation as well as

reducing noise and pollutants.Simple adjustment of the combustion head allows to adaptinternal geometry of the head to the output of the burner.The same adjustment servomotor for the air damper alsovaries, depending on the required output, the setting ofthe combustion head, through a simple lever.This system guarantees excellent mix on all firing ratesrange.

Flame dimensions

Example:Burner thermal output = 3500 kW;L flame (m) = 3,5 m (medium value);D flame (m) = 1,5 m (medium value).

D

L

Burner output (MW)0 2

3

5

1

1 3

2

4

6

7

4 5 6 7 8 9 10

Flam

e le

ng

th (

m)

Flam

e d

iam

eter

(m

)

0

4

0

0,5

1

1,5

2

2,5

3

3,5

L max

L min

D max

D min

10

Example of a RLS/E MX burner combustion head

Example of a sound proofing radial regulating system

Page 11: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

Each RLS/E-EV MX series burner is equipped with an electronicmicroprocessor management panel, which controls the air damperservomotor as well the fuel servomotors.

Hysteresis is prevented by the precise control of the two servomotorsand the software link by can - bus.The high precision regulation is due to the absence of mechanicalclearance normally found in mechanical regulation cams on traditionalmodulating burners. For the burner commissioning it is necessaryto use the AZL unit display. It must be ordered separately for /Emodels, while for /EV models it is included.In the RLS/E series burner the standard working is two stageprogressive and the PID regulator, to control the boiler temperatureor pressure, is available as accessories.

In the RLS/EV series burner the PID regulator to control the boilertemperature or pressure is included in LMV52. The burner can workfor a long time on intermediate output settings (see picture A).In the RLS/EV series variable

speed drive control (VDS) and Oxygen control are obtained byinstallation of a special kit. The display operating unit (AZL) isalready on board.The display and operating unit (AZL) shows all operationalparameters in real time, so as to keep a constant check on theburner:- servomotor angle- required set-point and actual set-point- fuel consumption (RLS/EV)- smoke and environmental temperature (RLS/EV)- O2 value (RLS/EV)- error checking, self diagnostic fault analysis.

ADJUSTMENT

BURNER OPERATION MODE

Control box management table

Function

Intermittent operationContinuos operationIntermittent operation flame detector

Continuos operation flame detector

Numbers of regulating stepper actuatorsVariable Speed Drive (VSD)Input O2 probeBuilt in O2 regulatorSingle fuel operationDouble fuel operation (different timing for oil and gas)Gas valve proving systemBuilt in temperature pressure PID regulatorExternal analog modulationAnalog 4÷20 mA output load signalEfficency IndicationExternal e-Bus Interface (AZL)Commissioning PC Interface (AZL)Commissioning Interface Display (AZL)

LMV 51 LMV 52

Control box management version table

LMV 51

LMV 52

RLS/Eversion

RLS/EVversion

11

Main management module forRLS/E-EV MX series

Ou

tpu

t

Picture A

Ch

ecke

d V

aria

ble bar

°C

MAX

MIN

time

time

“Modulating” operation

Included in supply

As accessory

Ionisation Probe

Ionisation Probe /Infrared Detector

Ionisation Probe

4 5

------

on demand

--

Ionisation Probe /Infrared Detector

Page 12: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

Example of burner management system in dual fuel burner configuration

Burner management system

The new electronic cam is a microprocessor based burner management system with matching systemcomponents for the control and supervision of forced draft burners.The system components are interconnected via a bus system.Communication between the individual bus users takes place via a reliable system-based data bus.All safety-related digital outputs of the system are permanently monitored via e contact feedbacknetwork.

12

Fan speed control (on demand)

The inverter device fitted to the RLS/EV series burner acts on the electrical supply frequency of thefan motor to adjust the air flow through the motor speed variation.

The main advantages of speed control:- lower sound emissions- electric power saving.

The fan motor supplies just the necessary airflow, thus reducing sound emissions andavoiding energy loss due to the air damperregulation mechanism. The inverter technologycan save up to 35% of the energy costs.A safety device to verify the correct speed ofthe motor is mounted on the air suction circuitof the burner.

10 20 30 40 50 60 70 80 90 100Heat output (%)

Ele

ctri

cal p

ow

er c

ons

ump

tio

n kW

Electrical power consumption of the fan motor with Inverter

Electrical power consumption of the fan motor with air damper adjusting

35% energysaving

Page 13: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

CAN-Bus

LMV51-52

Stepper actuators 3 / 20 / 35 NmAZL display and

operating unit Interfacewith BMS & PC-Tool

QGO2Sensor

CAN-BusVariable Speed

Drive VSD

IONISATION / QRIContinuos Operation

Electronic Cam Platform

QRBIntermittentOperation

Features:

Multifuel BurnersBurner Control

Valves Seal ControlElectronic CamO2 Regulation

Speed RegulationOptional Regulator

5 IP54 servomotorsFuel meter

Output/Efficiency digital signal

RLS 300-400/E-EV MX

time (s)

1 - Closing thermostat2 - Closing thermostat3 - Fan motor working4 - Ignition transformer5 - Valves open6 - Actuators7 - Flame max. - min.

0

1

2

3

4

5

6

7

13

START UP CYCLE

Page 14: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

OUTPUT INPUT CONNECTIONS

WIRING DIAGRAMS

Electrical connections must bemade by qualified and skilledpersonnel, according to thelocal norms.

Example of the terminal boardfor electrical connections

THREE PHASE SUPPLY TO THE POWER CIRCUIT AND GAS TRAINS CONNECTIONS

RLS 300-400/E-EV MX

X1RS(1)(2)

- Main supply terminal strip- Remote lock-out reset button- Available for oil circuit external interlock- Available for gas circuit external interlock

L1 L2 L3 N PE

-X1

L

F

L1 L2 L3 N PE

3N ~ 400/230V 50Hz

-Y

-X1

N P1 P2(2) (3) PE

VS VR

-PGMin -PGVP

N V1 V2 P P

V1N V2 PE P1 P2 PVP

PVP

PVP

PVP

1 2

3

1 2

3P P

Triggering / Safety devices

-X1

-TS -TL

TS1 TS2 TL1 TL2 XG1 XG2 X01 X02

P ϑ P ϑ

(1) (2)

14

Fuel remote selector

OIL

GAS

FUEL EXTERNAL SELECTORNO NO

NO NO

OIL

COM

GAS

Indicators / Ancillaries

RS2RS1 32 41

Oil o

pera

tion

76 85

Gas o

pera

tion

Burn

er lo

ck ou

t

Flame

aligh

t - G

AS

-RS

9 10

Flame

aligh

t - O

IL

Rese

t

-X1

Gas valve + PVP leak detection

-X1

Page 15: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

INPUT CONNECTIONS

FOR RLS 300-400/E MX

FOR RLS 300-400/EV MX

Two stage progressive position

-X1

-TR

I Stage II Stage

T6 T7 T8

P ϑNC NO

C

-X1 -X1

-BP1BN GN WH

0 / 10V

QBE620-P……

X61.

1

X61.

2

X61.

4

X61.

FE

PE

PE1 2

4…20mA

X61.

1

X61.

2

X61.

FE

Pt 100

X60.

1

X60.

2

X60.

4

X60.

FE

WH WH RD RD

15

Power regulation with 3-position contact

-X1

X60.

1

X60.

2

X60.

3

X60.

4

X60.

FE

-BT3+BC

-BT5+BC

-BA+BC

-BV+BC

X61.

1

X61.

2

X61.

3

X61.

4

X61.

FE

Possibility of probe input

ϑ

Pt 100

ϑ

Pt /LG Ni 1000TEMPERATURE /PRESSURE INPUT

TEMPERATURE /PRESSURE INPUT

POWERSUPPLY

OUTPUT REFERANCEGROUND

POWERSUPPLY

OUTPUT

4...20 mA

REFERANCEGROUND

0

0

Possibility of Riello probe input

INPUT WITH QBE620-P………

-BP+BC

-BT4+BC

ϑ

Page 16: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

OUTPUT CONNECTIONS

FOR RLS 300-400/EV MX

FOR RLS 300-400/EV MX

16

-BV1+BC

-BA1+BC

-X1

X62.

1

X62.

2

X62.

3

X62.

4

X62.

FE

Possibility of setpoint input and setpoint shift

0...10VSET POINT

OUTPUT REFERANCEGROUND

4...20 mASET POINT

OUTPUT REFERANCEGROUND

Possibility of external modulation

-X1

-BV2+BC

-BA3+BC

2...10VEXTERNAL MODULATION

OUTPUT REFERANCEGROUND

4...20 mAEXTERNAL MODULATION

OUTPUT REFERANCEGROUND

X62.

1

X62.

2

X62.

3

X62.

3

X63.

FEOutput for load indicator

-BA2+BC

-X1

X63.

1

X63.

2

X63.

FE

4...20 mALOAD INDICATOR

INPUT REFERANCEGROUND

Page 17: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

OPTIONAL CONNECTION

Note: for others probe input ask Riello techical dept

RWF40 power controller

FOR RLS 300-400/E MX WITH RWF40 POWER CONTROL KIT

Possibility of setpoint input and setpoint shift

RWF 40 (High version)

-X1

-+

17

-X2

-B1+MB

TE L1 NQ1

3Q1

4 Q Y1 Y2 I1 M1 G1+ U1 X1+ X1-

M6 XB6

XU6 G+ G- CA CB CG D1 D2 GND B9 M9

PE L NQ1

3Q1

4 Q Y1 Y2 I1 M1 G1+ U1 X1+ X1-

M6 XB6

XU6 G+ G- CA CB CG D1 D2 GND B9 M9

RWF40.......

Possibility of probe input

0 - 20mA 4 - 20mA DC

I1 M1

Current probe output0 - 1V 0 - 10V DC

Voltage probe output

-BA BV

-BT1

Thermocouple

I1 M1 U1 M1

Possibility of Riello probe input only andwith kit RWF40

ϑ

PE

Pt 100

-BT4+BC

RDWH

-X1

RDWH

M1G1+ M1I1 G- G+ I1

-BP+BC

2 PE1

4...20mA

-BR

-BA1 -BV10 - 20mA 4 - 20mA DC

M6 XB6

0 - 1V 0 - 10V DCResistance Potentiometer

XB6 M6

Current input Voltage input

XU6

M6

-X2

-BTEXT

Climatic compensation

M9 B9

ϑ

Outside Temperature

-X1

-BT2 -BT3ϑ ϑ

G1+ M1 G1+ M1I1

Resistance Thermometer in2-wire circuit

Resistance Thermometer in3-wire circuit

-X1

-BP1

U1G+G-M1

WH BN GN

QBE620-P……

0/10V

-X2 CA CB CG

Optional

RxDT

xD +

RxDT

xD -

GND

Serial Interface RS485

Page 18: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

VARIABLE SPEED DRIVE CONNECTIONS

FOR RLS 300-400/EV MX

OXYGEN CONTROL KIT CONNECTIONS

FOR RLS 300-400/EV MX

BA - DC input 0...20 mA, 4...20 mABA1 - DC input 0...20 mA, 4...20 mA for modifying the

remote setpointBA2 - Load indicatorBA3 - DC dispositive for the external modulation output 4...20 mAB1 - RWF 40 power controllerBP - Pressure probeBP1 - Pressure probeBR - Potentiometer for modifying the set pointBT1 - Thermocouple probeBT2 - Probe PT 100 with 2 wiresBT3 - Probe Pt100 with 3 wiresBT4 - Probe Pt100 with 3 wiresBT5 - PT/LG-Ni1000 probeBTEXT - External probe for the climatic compensation of

the remote setpointBV - DC voltage input 0...1 V, 0...10 VBV1 - DC voltage input 0...1 V, 0...10 V for modifying

the remote setpoint

BV2 - DC voltage input 2...10VGF - Variable speed driveG10 - O2 sensor, OGO20.. typeG20 - Flue gases air temperature control probeG30 - Air temperature control probeMV - Fan motorPGMin - Minimum gas pressure switchPGVP - Gas pressure switch for leak detection control deviceRS - Remote lock-out reset buttonTL - Load limit remote control systemTR - High-low mode load remote control systemTS - Safety control device systemX1 - Main sypply terminal stripX2 - RWF 40 power controller terminal stripY - Gas adjustment valve + gas safety valve

The following table shows the supply lead sections and the type of fuse to be used.

Table A

RLS 300/E MX

16 aM4

25 aM6

Model

A

mm2

FL

RLS 400/E MX RLS 300/EV MX

16 gG4

25 gG6

RLS 400/EV MX

18

-XO2

QGO20...

Q4 Q5 PE B1 M B2 M G2 U3 -G10+BC

-G20+BC

-G30+BC

L N PE B1 M B2 M G2 U3 sch

TGAS

1

TGAS

2 sch

TAIR

1

TAIR

2 sch

ϑ

Pt/LG-Ni 1000

ϑ

Pt/LG-Ni 1000

-GFPE W V U L1 L2 L3 PE

INVERTER SIEMENS TYPE SED2

-MV

PEWVU sch GNYE

BU BN BK

4x6mm2+sch

BK BN BU

4x6mm2

GNYE

U1 V1 W1 PE6x0.5mm2+sch

sch 5GY

4YE

3GN

2BN

1WH

BN BU

3x1mm2

FEX7

3.5

X73.

4X7

3.3

X73.

2X7

3.1 24 25

FE 2- 3+ 21NO

5 9 22 25 24IN OUT COM COM NO

+24Setpoint0/4…20mA

X1

Page 19: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

EMISSIONS

The emission data has beenmeasured in the various models atmaximum output, according to EN676 and EN 267 standard.

The RLS/E-EV MX series combustion head reduce polluting emissions thanks to their special designwhich optimises the air fuel mix.

In the RLS/E-EV MX series part ofthe gas is distributed throughoutlets which the remaining gas isinjected directly into the centre ofthe flame.This prevents no homogeneousconcentrations in the flame withareas of high oxidation,producing very stable flame withg r a d u a l a n d p r o g r e s s i v ecombustion as the flame develops,thus giving polluting emissionvalues below even the mostrestrictive norm values.

Combustion head operating diagram of RLS/E-EV MX series

19

NOISE EMISSIONS

dB

(A)

0

20

40

60

80

100

RLS 300/E-EV MX RLS 400/E-EV MX

NOx EMISSIONS

mg

/kW

h

0

50

100

150

200

250

RLS 300/E-EV MX RLS 400/E-EV MX

Page 20: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

X

Z

Y

OVERALL DIMENSIONS (mm)

PACKAGING

BURNER - BOILER MOUNTING FLANGE

RLS 300-400/E-EV MX

BURNER

ØD2350350

M18M18

452452

D1

Ø

D2

45°

45°

D1

Model X19601960

Y970970

kg240250

Z940940

Model

RLS 300/E-EV MX

RLS 400/E-EV MX

RLS 300/E-EV MX

RLS 400/E-EV MX

Model

RLS 300/E-EV MX

RLS 400/E-EV MX

F QA D E H I N OM SP

M

S

O

M

O

S

Q

Q

A

D

E

I

F

H

N

P

20

720775

373373

320320

890890

13251325

313313

605605

164164

10551055

DN80DN80

11751175

342342

Page 21: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

HYDRAULIC AND ELECTRICALCONNECTIONS AND START UP

Install the nozzle, choosing this on the basis of themaximum boiler output and following the diagramsincluded in the burner instruction handbook.

Check the position of the electrodes

Adjust the combustion head

Install the gas train to the burner flange choosingthe right adapter code if the gas train and burnerhinge are situated to the same size.

Connect the ends of the flexible pipes to the sunctionand return pipework using the supplied nipples.

Make the electrical connections to the burnerfollowing the wiring diagrams included in theinstruction handbook.

Prime the pump by turning the motor.

Proceed with the start up regulating before the gasside, so the oil side.

On start up, check:- Gas pressure at the combustion head (to the max.

and min. output)- Pressure pump (to the max. and min.)- Combustion quality, in terms of unburned

substances and excess air.

INSTALLATION DESCRIPTION

Installation, start up and maintenance must be carriedout by qualified and skilled personnel. All operationmust be performed in accordance with the technicalhandbook supplied with the burner.

After drilling the boilerplate, using the supplied gasketas template, prepare a suitable lifting system and,after hooking onto the rings, fix burner to boiler.

BURNER SETTING

21

Page 22: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

BURNER ACCESSORIES

22

Accessories for modulating operation

To obtain modulating operation, the RLS/E MX series of burners requires a regulator with three pointoutlet controls. The following table lists the accessories for modulating operation with their applicationrange. In RLS/EV models PID regulator is integrated inside LMV 52 control box.

The relative temperature or pressure probes fitted to the regulator must be chosen on the basis ofthe application.

RLS 300-400/E MX

RLS 300-400/E MX

RWF 40

Regulator code

3010356

3010357

Burner Regulator type

RWF 40

Basic version with 3 position output

High version with additional modulatingoutput and RS 485 Interface

Probe type

Temperature PT 100Pressure 4 ÷ 20 mAPressure 4 ÷ 20 mA

RLS 300-400/E-EV MXRLS 300-400/E-EV MXRLS 300-400/E-EV MX

Burner Range (°C) (bar)

-100 ÷ 500°C0 ÷ 2,5 bar0 ÷ 16 bar

Probe code

3010110

3010213

3010214

Variable Speed Drive (VSD) for RLS/EV series only

The motor speed variation for the RLS/EV MX burners series is obtained thanks to a frequencyconverter: variable speed drive (VSD). It always must be ordered with RLS/EV series.

Variable Speed Drive (VSD)

RLS 300-400/EV MX

Code

3010379

Burner

Nozzles

The nozzles must be ordered separately. The following table shows thefeatures and codes on the basis of the maximum required fuel output.

Nozzles type B5 SA 60°

RLS 300-400/E MX

RLS 300-400/E MX

RLS 300-400/E MX

RLS 300-400/E MX

RLS 300-400/E MX

RLS 300-400/E MX

RLS 400/E MX

RLS 400/E MX

RLS 400/E MX

RLS 400/E MX

RLS 400/E MX

Nozzle code

3009363

3009364

3009365

3009366

3009367

3009368

3009369

3009370

3009371

3009372

3009373

Burner

150

200

225

250

275

300

325

350

375

400

425

Rated delivery (kg/h)

Page 23: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

23

Kit efficiency with oxygen control kit (for RLS/EV only)

The kit includes two temperature sensors: one for air and one for exhaust gas detection. They mustbe wired to oxygen control kit interface to allow the LMV 52 efficiency calculation. The value is showedon AZL display.

Kit efficiency

RLS 300-400/EV MX

Code

3010377

Burner

Oxygen Control kit (QGO2)

The QGO2 is an oxygen analizer with relevant probe which controls and supervises the residualoxygen content in exhaust gases.

Oxygen Control kit (QGO2)

RLS 300-400/EV MX

Code

3010378

Burner

PC Interface Software (ACS 450)

PC tool for convenient programming and burner settings, process visualization, data recording,selection of AZL language, software update AZL.

PC Interface Software (ACS 450)

RLS 300-400/E-EV MX

Code

3010388

Burner

Display and Operating Unit (AZL)

This tool is needed for combustion system commissioning and monitoring.The AZL is included in RLS/EV models.

Display and Operating Unit (AZL)

RLS 300-400/E MX

Code

3010355

Burner

Sound proofing box

If noise emission needs reducing even further, sound-proofing boxes are available, as given in thefollowing table:

(*) according to EN 15036-1 standard

RLS 300-400/E-EV MXBurner Box code

3010376C7Box type

Sound proofing box

10Average noise reduction [dB(A)](*)

Page 24: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

MBC 1900 SE 65 FCMBC 3100 SE 80 FCMBC 5000 SE 100 FC

Stabiliser spring

Stabiliser spring

To vary the pressure range of the gas train stabilisers, accessory springs are available. The followingtable shows these accessories with their application range:

Gas train Spring codeSpring

3010381

3010382

3010383

3010384

White from 4 to 20 mbarRed from 20 to 40 mbar

Black from 40 to 80 mbarGreen from 80 to 150 mbar

Please refer to the technical manual for the correct choice of spring.

RLS 300-400/E-EV MX

Adapters

Adaptercode

2” DN 80

DN 65 DN 80

DN 80 DN 80

DN 80DN 100

DN 65 DN 80

DN 80DN 100

Adapters

Below are given the adapters than can be fitted on the various burners:

Burner

MBC 1200 SE 50

MBC 1900 SE 65 FC

MBC 3100 SE 80 FC

MBC 5000 SE 100 FC

MBC 1900 SE 65 FC

MBC 5000 SE 100 FC

Gastrain

3000826

3010221

3010222

3010223

3010369

3010370

DimensionsØ - DN

24

LPG kit

For burning LPG gas, a special kit is available to be fitted to the combustion head of the burner.

LPG kit

RLS 300-400/E-EV MX

Code

in progress

Burner

Adaptertype

I

I

I

I

I

I

Lmm

300

400

400

400

10

50

GAS TRAIN ACCESSORIES

Page 25: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

SPECIFICATION

A specific index guides your choice of burner from the variousmodels available in the RLS/E-EV MX series. Below is a clearand detailed specification description of the product.

DESIGNATION OF SERIES

Size

Fuel : S Natural GasL Light oilLS Light oil/Natural GasN Heavy oil

Series : R

RBASIC DESIGNATION

LS 300 /E TC FS1 3/400/50 230/50-60

EXTENDED DESIGNATION

Emission : ... Class 1 EN267 - EN676MZ Class 2 EN267 - EN676BLU Class 3 EN267 - EN676

MXClass 2 EN267Class 3 EN676

Head : TC Standard headTL Extended head

MX

Auxiliary voltage :230/50-60 230V/50-60Hz110/50-60 110V/50-60Hz

Electrical supply to the system :

Flame control system : FS1 Standard (1 stop every 24 h)FS2 Continuous working (1 stop every 72 h)

AVAILABLE BURNER MODELS

RLS/EV models and other versions are available on specific request.

Setting : /1 Single stage /P Proportioning air/gas valve/B Two stage /EV Electronic cam predisposed for/M Modulating - Mechanical cam variable speed (with inverter)/E Electronic cam

1/230/50 1/230V/50Hz3/230/50 3/230V/50Hz3/400/50 3N/400V/50Hz3/230-400/50 3/230V/50Hz - 3N/400V/50Hz3/220/60 3/220V/60Hz3/380/60 3N/380V/60Hz3/220-380/60 3/220/60Hz - 3N/380V/60Hz

25

RLS 300/E MX TC FS1/FS2 3/400/50 230/50-60

RLS 400/E MX TC FS1/FS2 3/400/50 230/50-60

Page 26: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

BurnerMonoblock forced draught gas burner with modulating operation, fully automatic, made up of:- Fan with reverse curve blades high performance with low sound emissions- Air suction circuit lined with sound-proofing material- Air damper for air setting controlled by a high precision servomotor- Air pressure switch- Fan starting motor at 2800 rpm, three-phase 230/400 - 400/690 V with neutral, 50Hz- Separate light oil pump- Low emission combustion head, that can be set on the basis of required output, fitted with:

- stainless steel end cone, resistant to corrosion and high temperatures- ignition electrodes- flame stability disk

- Maximum gas pressure switch, with pressure test point, for halting the burner in the case of overpressure on the fuel supply line

- Module for air/fuel setting and output modulation with separated PID control of temperature orpressure, available as accessory for RLS/E MX model

- Electronic cam for controlling the system safety- Infrared flame detector- Star/triangle starter for the fan motor (burners with motor electrical power ≥ 7,5 kW - RLS/E versions)- Main electrical supply terminal board- Burner on/off switch- Auxiliary voltage led signal- Burner working led signal- Contacts motor and thermal relay with release button- Motor internal thermal protection- Motor failure led signal- Burner failure led signal and lighted release button- Emergency button- Coded connection plugs-sockets- Burner opening hinge- Lifting rings- IP 54 electric protection level- Gears pump for high pressure fuel supply- Pump starting motor- Oil safety valves- Valve unit with double oil safety valve on the output circuit and double safety valve on the return

circuit- Oil/Gas selector- Flame inspection window.

Gas train:Fuel supply line in the Multibloc configuration (for a diameter of 2") or Composed configuration(from a diameter of DN 65 to a diameter of DN 100) fitted with:- Filter- Stabilizer- Minimum gas pressure switch- Safety valve- One stage working valve with ignition gas output regulatorNote: valve seal control already present inside burner control box.

Conforming to:- 89/336/EEC directive (electromagnetic compatibility)- 73/23/EEC directive (low voltage)- 90/396/EEC directive (gas)- EN 676 (gas burners).

26

PRODUCT SPECIFICATION

Page 27: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

Standard equipment:- 1 flange gasket- 4 screws for fixing the flange- 1 thermal screen- 4 screws for fixing the burner flange to the boiler- 2 flexible pipes for connection to the oil supply network- 2 nipples for connection to the pump with gaskets- Seal control- Seal control pressure switch (for installation on gas train)- Instruction handbook for installation, use and maintenance- Spare parts catalogue.

Available accessories to be ordered separately:- Pressure probe 0 ÷ 2.5 bar- Pressure probe 0 ÷ 16 bar- Temperature probe -100 ÷ 500°C- RWF 40 for RLS/E MX- Display and operating unit (AZL)(included in /EV models)- Sound proofing box- LPG kit- Nozzle- Variable speed drive (VSD) for /EV models- Oxygen control kit- Kit efficiency for /EV models- PC interface software (ACS 450).

27

Page 28: RLS/E-EV MX SERIES RLS 300/E MX RLS 400/E MX RLS … EV MX... · rls 400/e-ev mx The diagrams indicate the minimum pressure drop of the burners with the various gas trains that can

ISO 9001 Cert. n. 0061

Since the Company is constantly engaged in the production improvement, the aesthetic anddimensional features, the technical data, the equipment and the accessories can be changed.

This document contains confidential and proprietary information of RIELLO S.p.A.Unless authorised, this information shall not be divulged, nor duplicated in whole or in part.

RIELLO S.p.A. - Via Ing. Pilade Riello, 5 - 37045 Legnago (VR) ItalyTel. ++39.0442630111 - Fax ++39.044221980

Internet: http://www.rielloburners.com - E-mail: [email protected]