road lighting pelindo iii gresik section row 30m
DESCRIPTION
WTRANSCRIPT
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30MDate: 05-02-2012
Designer: Syaiful Fikri
CalcuLuX Road 7.6.1.0
The nominal values shown in this report are the result of precision calculations, based upon precisely positioned luminaires in a fixedrelationship to each other and to the area under examination. In practice the values may vary due to tolerances on luminaires, luminairepositioning, reflection properties and electrical supply.
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
1. Project Description
1.1 3-D Project Overview
B BRP372 LED126NW 138W 22
B
B
B
BBBBBB
B
B
B
BBBBBB
X
YZ
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 2/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
1.2 Top Project Overview
B BRP372 LED126NW 138W 22
-22 -17 -12 -7 -2 3 8 13 18
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 3/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
2. Summary
2.1 Main Road
Luminaire Type : BRP372 LED126NW 138W 220-240V DM2ELamp Type : 1 * Luxeon R x64LEDs Ra75.1Lamp Flux : 12623 lumenTilt90 (T) : 5.0 degGrid Method : CEN LuminanceProject Maintenance Factor : 0.90
T
O
H
WW C
S
Carriageway : Dual CarriagewayCentral Reserve (C) : 3.00 mRoad Width (W) : 7.00 mNumber of Lanes : 3Reflection Table : CIE C1Q0 of Table : 0.100Maintenance Factor : 0.90Installation : Twin CentralHeight (H) : 13.00 mSpacing (S) : 40.00 mOverhang (O) : 1.50 m
Overall quality figures for the above road scheme.
LuminanceAverage = 1.70 cd/m2Minimum = 1.18 cd/m2Maximum = 2.58 cd/m2Minimum/Maximum = 0.45Minimum/Average = 0.69Ul = 0.60
GlareTI = 5.5 %
Horizontal IlluminanceAverage = 16.8 luxMinimum = 10.5 luxMaximum = 29.3 luxMinimum/Maximum = 0.36
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 4/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3. Calculation Results
3.1 Main L (O1): Graphical Table
TI ( 1.17,-31.63, 1.50) = 5.5%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (1.17,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.70 0.69 0.45 0.90
B BRP372 LED126NW 138W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
B
B
B
B
1.8
1.7
1.5
1.4
1.3
1.2
1.2
1.2
1.2
1.4
1.5
1.6
1.7
1.8
1.9
1.7
1.6
1.4
1.4
1.2
1.2
1.2
1.3
1.4
1.5
1.7
1.8
1.9
2.0
1.8
1.6
1.5
1.4
1.3
1.2
1.3
1.3
1.5
1.5
1.7
1.9
2.0
2.1
1.9
1.7
1.5
1.4
1.3
1.3
1.3
1.4
1.5
1.6
1.8
2.0
2.1
2.2
2.0
1.7
1.5
1.5
1.4
1.3
1.4
1.4
1.6
1.7
1.9
2.1
2.2
2.3
2.1
1.8
1.6
1.5
1.4
1.4
1.4
1.5
1.6
1.7
1.9
2.2
2.3
2.3
2.1
1.9
1.7
1.5
1.4
1.4
1.5
1.5
1.7
1.8
2.0
2.2
2.4
2.4
2.2
1.9
1.7
1.6
1.5
1.5
1.5
1.6
1.7
1.9
2.1
2.3
2.5
2.6
2.4
2.1
1.9
1.7
1.6
1.5
1.6
1.6
1.8
2.0
2.2
2.5
2.6
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 5/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.2 Main L (O1): Iso Contour
TI ( 1.17,-31.63, 1.50) = 5.5%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (1.17,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.70 0.69 0.45 0.90
B BRP372 LED126NW 138W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
) 1.2
51.
5
1.5
1.75
1.75
2
22.
252.252.
5
2.5
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 6/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.3 Main L (O1): Filled Iso Contour
TI ( 1.17,-31.63, 1.50) = 5.5%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O1) (1.17,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.70 0.69 0.45 0.90
B BRP372 LED126NW 138W 22
2.5
2.25
2
1.75
1.5
1.25
-12 -7 -2 3 8 13 18
X(m)
-41
611
1621
2631
3641
Y(m
)
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 7/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.4 Main L (O2): Graphical Table
TI ( 3.50,-31.63, 1.50) = 5.3%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (3.50,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.73 0.70 0.46 0.90
B BRP372 LED126NW 138W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
B
B
B
B
1.8
1.7
1.5
1.4
1.4
1.2
1.2
1.2
1.3
1.4
1.5
1.6
1.7
1.8
1.9
1.8
1.6
1.4
1.4
1.3
1.2
1.2
1.3
1.5
1.5
1.7
1.8
1.9
2.0
1.8
1.7
1.5
1.4
1.3
1.3
1.3
1.3
1.5
1.6
1.8
1.9
2.1
2.1
1.9
1.7
1.5
1.5
1.3
1.3
1.3
1.4
1.5
1.6
1.8
2.0
2.2
2.2
2.0
1.8
1.6
1.5
1.4
1.4
1.4
1.4
1.6
1.7
1.9
2.1
2.2
2.3
2.1
1.8
1.6
1.5
1.4
1.4
1.4
1.5
1.6
1.7
2.0
2.2
2.3
2.3
2.1
1.9
1.7
1.6
1.5
1.4
1.5
1.5
1.7
1.8
2.0
2.3
2.4
2.4
2.2
1.9
1.7
1.6
1.5
1.5
1.5
1.6
1.7
1.9
2.1
2.3
2.4
2.6
2.3
2.1
1.8
1.7
1.6
1.5
1.6
1.6
1.8
2.0
2.2
2.5
2.6
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 8/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.5 Main L (O2): Iso Contour
TI ( 3.50,-31.63, 1.50) = 5.3%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (3.50,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.73 0.70 0.46 0.90
B BRP372 LED126NW 138W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
) 1.25
1.5
1.5
1.75
1.75
2
2
2
2.252.252.
5
2.5
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 9/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.6 Main L (O2): Filled Iso Contour
TI ( 3.50,-31.63, 1.50) = 5.3%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O2) (3.50,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.73 0.70 0.46 0.90
B BRP372 LED126NW 138W 22
2.5
2.25
2
1.75
1.5
1.25
-12 -7 -2 3 8 13 18
X(m)
-41
611
1621
2631
3641
Y(m
)
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 10/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.7 Main L (O3): Graphical Table
TI ( 5.83,-31.63, 1.50) = 5.0%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (5.83,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.74 0.71 0.48 0.90
B BRP372 LED126NW 138W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
B
B
B
B
1.8
1.7
1.6
1.4
1.4
1.3
1.2
1.3
1.3
1.5
1.5
1.7
1.8
1.9
1.9
1.8
1.6
1.5
1.4
1.3
1.3
1.3
1.3
1.5
1.6
1.7
1.9
2.0
2.1
1.9
1.7
1.5
1.5
1.3
1.3
1.3
1.4
1.5
1.6
1.8
2.0
2.1
2.2
2.0
1.7
1.6
1.5
1.4
1.3
1.4
1.4
1.6
1.7
1.9
2.1
2.2
2.2
2.0
1.8
1.6
1.5
1.4
1.4
1.4
1.5
1.6
1.7
1.9
2.2
2.3
2.3
2.1
1.8
1.6
1.5
1.4
1.4
1.4
1.5
1.7
1.8
2.0
2.2
2.3
2.3
2.1
1.8
1.7
1.6
1.5
1.4
1.5
1.5
1.7
1.8
2.0
2.2
2.3
2.4
2.2
1.9
1.7
1.6
1.5
1.5
1.5
1.6
1.7
1.9
2.1
2.3
2.4
2.5
2.3
2.0
1.8
1.7
1.6
1.5
1.6
1.6
1.8
2.0
2.2
2.4
2.6
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 11/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.8 Main L (O3): Iso Contour
TI ( 5.83,-31.63, 1.50) = 5.0%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (5.83,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.74 0.71 0.48 0.90
B BRP372 LED126NW 138W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-41
611
1621
2631
3641
Y(m
)
1.25
1.5
1.5
1.75
1.75
2
2
22.2
5
2.25
2.5
2.5
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 12/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.9 Main L (O3): Filled Iso Contour
TI ( 5.83,-31.63, 1.50) = 5.0%Grid : Main at Z = -0.00 mCalculation : Luminance towards CEN Observer (O3) (5.83,
-60.00, 1.50) (cd/m2)Road Surface : CIE C1 with Q0 = 0.100
Average Min/Ave Min/Max Project maintenance factor 1.74 0.71 0.48 0.90
B BRP372 LED126NW 138W 22
2.5
2.25
2
1.75
1.5
1.25
-12 -7 -2 3 8 13 18
X(m)
-41
611
1621
2631
3641
Y(m
)
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 13/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.10 Main Eh: Graphical Table
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 16.8 0.63 0.36 0.90
B BRP372 LED126NW 138W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
B
B
B
B
21
19
17
15
13
11
11
11
11
13
15
17
19
21
22
20
17
15
13
11
11
11
11
13
15
17
20
22
23
21
18
15
13
11
11
11
11
13
15
18
21
23
24
21
18
15
13
11
11
11
11
13
15
18
21
24
24
22
18
15
13
11
11
11
11
13
15
18
22
24
25
22
19
15
14
12
11
11
12
14
15
19
22
25
26
23
19
16
14
12
11
11
12
14
16
19
23
26
27
24
20
17
14
12
12
12
12
14
17
20
24
27
29
26
22
18
15
13
12
12
13
15
18
22
26
29
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 14/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.11 Main Eh: Iso Contour
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 16.8 0.63 0.36 0.90
B BRP372 LED126NW 138W 22
-18 -13 -8 -3 2 7 12 17 22
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
15
15
20
20
25
25
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 15/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
3.12 Main Eh: Filled Iso Contour
Grid : Main at Z = -0.00 mCalculation : Horizontal Illuminance (lux)
Average Min/Ave Min/Max Project maintenance factor 16.8 0.63 0.36 0.90
B BRP372 LED126NW 138W 22
25
20
15
-12 -7 -2 3 8 13 18
X(m)
-6-1
49
1419
2429
3439
44Y
(m)
B
B
B
B
Scale1:250
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 16/17
-
ROAD LIGHTING PELINDO III (GRESIK)SECTION TYPICAL ROW 30M Date: 05-02-2012
4. Luminaire Details
4.1 Project Luminaires
Xceed Medium FOT Sample(64LED700)BRP372 LED126NW 138W 220-240V 1xLuxeon R x64LEDs Ra75.1/3934
Light output ratios DLOR : 1.00 ULOR : 0.00 TLOR : 1.00Ballast : 700mA Global DriverLamp flux : 12623 lmLuminaire wattage : 138.0 WMeasurement code : LVC1121498
Note: Luminaire data not from database.
750
750
0o 30o30o
60o 60o
90o 90o
120o 120o150o 150o180o
C = 180o C = 0o C = 270o C = 90o C = 195o Imax C = 15o
Luminous Intensity Diagram (candela/1000 lumen)
Philips Lighting B.V. - CalcuLuX Road 7.6.1.0 Page: 17/17