robust project planning & documentation · 16.10.2014 · robust project planning &...

14
Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality - None (C1) Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

Upload: others

Post on 18-Oct-2019

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Robust Project Planning & Documentationin

Large-scale deployment of IEC 61850

IEC 61850 Europe 2014

Prague 2014-10-16Confidentiality - None (C1)

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

Page 2: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Content

• Background

• Driving forces for standardization

• IEC 61850 process based on a pilot concept

• Robust project planning and documentation with third party tool

• Large scale deployment of IEC 61850

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

Page 3: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Background

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

• Rapidly aging substation automation systems

(SAS)

• Limited life time of modern DSAS devices

• Unique solutions because of functional purchase

• Need a new standardized concept to efficiently

replace SAS

• Strategic direction within Vattenfall Distribution to

standardize DSAS by implementing IEC 61850

Page 4: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Driving forces for standardization

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

Future-proofinvestments

Sustainable asset management

Uniform structure

Page 5: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Pilot SS Upplands Väsby

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

Vattenfall IEC 61850 Process supported by Specification and Lifecycle Management Tool

FunctionLibrary

Formal System

Specification

GeneralSpecifications

SignalList

GeneralSpecification

IEC61850

SSD

System

Design IEC61850

SCDSignal

List

Design Review

(FAT)

Re-import Delivery to

Specification ToolValidation against

Specification

Delivery

Review(SAT)

IEC61850

SCD

Signal

List

Maintenance

Cycles

Commissioning

As Build

Doc

Specification

Design

As Build

Vendor independent Specification Tool

(HELINKS STS)

Specification& Integration Tool

Vendor SpecificTools (IED & System

Integration

Colors indicate

tool usage

Data Flow & Workflow

Iterations and Feedback Flow

Export from

Specification ToolImport to Integration Tool

Commis-

sioning

• Develop work processes for IEC 61850- Test a new model for project execution (based on SCL files) for

IEC 61850 SAS that covers the whole life cycle of the substation

- Specification with top-down architecture by using 3rd party

software

• New technology and new concept- Test new equipment for process bus IEC 61850-9-2 to collect sampled

values

- Developing and testing Vattenfall standard Service PC solution, including a Remote Access solution

- Critical substation functions as blockings, interlockings, bfp, collection

and triggering of disturbance files and information from/to IEDs to

gateway is done via the station bus

Page 6: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Vattenfall Distribution Project Model

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

• Vattenfall is an organization which purchasenew substations based on functionalrequirements, ie we do not decide the construction

• All design and construction is done by external contractors

• The Vattenfall IEC 61850 process developedis therefore focused on the activities:

- Specification

- Acceptance of delivery

- Final documentation for O&M activities

Page 7: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

IEC 61850 Process supported by tools

Page 8: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

3

IED configurationtools

IID

SCD

6SCD

with Substation Structure

& SignalNames

SS/VL/Bay/OC_4PTOC.Str.general

DOI Description: Imax/Start

Scada Signal List

SSD

Only Substation Structure

SCL: SS/VL/Bay

Functions&SignalNames

SS/VL/Bay/PTOC.Str.general

+ Imax/Start

2

8

Project

Documentation

System Integration

tool

IEDs

Logical Nodes

DataObjects

Map with

Function &

Signalname

Substation Structure

4

Co

mm

unic

ation

En

gin

ee

ring5

Initial Vattenfall Engineering Workflow

VF Third-party tool

IEDs

Logical Nodes

DataObjects

104 Addresses

Scada Attributes

De

sig

n

Va

lida

tion

7

Substation Structure

Functions

Logical Nodes

DataObjects

1VF Library

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

Page 9: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Use of three different signal naming principles in third-party tool

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

• Apart from the IEC 61850 product and functional names VF also uses a third

naming based on classical company names for functions and signals. This to

minimize the knowledge gap

Page 10: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Function Library

• Reflecting Vattenfall standards

• Combines IEC 61850 elements with no IEC 61850 elements

• Creation of substation specific signal list from the library

• Library exchange as ZIP-file between users

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

Page 11: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Design review

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

• Comparision of specified signals with the implemented signals

• IED by IED review to get an overview of the quality of delivery

• Following statuses are added for every signal:

Specified, Implemented as specified, Implemented differently and Implemented

Page 12: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Visualization of GOOSE exchange at the functional level

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

• The aim is to vizualize GOOSE functions in the third-party tool from a functional perspective instead of a communiation view

Desired visualization Status today

Page 13: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Advantages for Vattenfall with the new IEC 61850 process

• Minimize errors caused by humans

• Standardized and scalable solutions

• Increased efficiency

• Clear and coherent utility/contractor relationship

• Larger volumes of standardized solutions

• Increased future possibilities

• Uniform structure

• Sustainable substation management

• Future proof investments

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16

Page 14: Robust Project Planning & Documentation · 16.10.2014 · Robust Project Planning & Documentation in Large-scale deployment of IEC 61850 IEC 61850 Europe 2014 Prague 2014-10-16 Confidentiality

Future proof our assets

-MISSION

Master

IEC 61850

OTHER OBJECTIVES

New business

opportunities

Modern way of work

Game Plan – IEC61850 deployment at Vattenfall

CRITICAL SUCCESS

FACTORS

Implementnew process IT infra-

structure in place

Fast experiencefeed back

Developinhouse

knowledge

Management

commitment

& support

Strong connection to

ordinarybusiness

RESOURCES

• Prtoection &

Automation

Engineers

• Project

managers

• Communication Specialists

• Process

development

team

• Management

• IT-department

• Change

Management

• Purchase

department

• Maintenancedepartment

Prepare large-scale deploym.

• Impl new process

• Update the governing doc

• Coord technical guidelines & tool library

• Education & training

• Inform Entrepreneurs

• Plan for multiple substations

• Pre-studies for software and file management

• Communicate

Impl large-scale

deployment

• BAU in process-organisationen

• IEC61850-knowledge relevant at recruitment

• Measure & Followup

• Incentive for increaseddevelopment ofDSAS

• Develop SW and file mgmt solutions

• Communicateinternally & externally

• Pilot substation

• Develop concept

• Develop process

• Test tools (Third-party tool & ServicePC)

• Evaluate overall

• Risk Analysis

Develop

conceptRefine the

concept

• Complete and

refine process

• Improve tools

• Acceptance Test

• Business Case

• Clarify decision making and strate-

gic direction

• DEMT decision

• Software and file management solutions in place

• Valid for all substation projects

• New procurement strategy

• New maintenance strategy

Robust Project Planning & Documentation in Large scale deployment of IEC 61850 | Berkan Kapkac | 2014-10-16