rpm1800 60hzperfectotal.com/uploadfile/27eptv_60.pdf · powered by lovol diesel generator set...

4
POWERED BY LOVOL DIESEL GENERATOR SET Model:27EPTV 190V-440V3P4W RPM1800 60Hz Rating Range Emergency: kW 30 Kva 38 prime: kW 27 Kva 34 STANDARD FEATURES AND CHARACTERISTICS QUALITY STANDARDS ASSEMBLY CONTROL SYSTEM AND PROTECTIO WARRANTY Prime power(P) These ratings are applicable for supplying continuous electrical power(at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% over-load power for 1 hour in 12 hours. Emergency power(E) There ratings are applicable for supplying continuous electrical power in the event of a utility power failure, up to a maximum of 200 hours per year. No overload is permitted on these ratings. Exceeding 200 hours operation per year may result in a reduced product life. www.perfectotal.com

Upload: others

Post on 07-Oct-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RPM1800 60Hzperfectotal.com/uploadfile/27EPTV_60.pdf · POWERED BY LOVOL DIESEL GENERATOR SET Model:27EPTV 190V-440V3P4W RPM1800 60Hz Rating Range Emergency: kW 30 Kva 38 prime: kW

POWERED BY LOVOL DIESEL GENERATOR SET

Model:27EPTV

190V-440V3P4W

RPM1800 60Hz Rating Range

Emergency: kW 30Kva 38

prime: kW 27Kva 34

STANDARD FEATURES AND CHARACTERISTICSQUALITY STANDARDS

ASSEMBLY

CONTROL SYSTEM AND PROTECTIO

WARRANTY

Prime power(P)These ratings are applicable for supplying continuous electrical power(at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% over-load power for 1 hour in12 hours.Emergency power(E)There ratings are applicable for supplying continuous electrical power in the event of a utility power failure, up to a maximum of 200 hours per year. No overload is permitted on these ratings. Exceeding 200 hours operation per year may result in areduced product life.

www.perfectotal.com

Page 2: RPM1800 60Hzperfectotal.com/uploadfile/27EPTV_60.pdf · POWERED BY LOVOL DIESEL GENERATOR SET Model:27EPTV 190V-440V3P4W RPM1800 60Hz Rating Range Emergency: kW 30 Kva 38 prime: kW

Hangzhou Perfect Total Machinery Co.,Ltd

POWERED BY LOVOL DIESEL GENERATOR SET

DIESEL ENGINEEngine Model 1003GBASIC TECHNICAL DATA FUEL CONSUMPTIONManufacturer Number LOVOL Power rating

of cylinders Cylinder 3 Standby power(L/h) 8.2

arrangement Vertical in-line 3 100% prime power(L/h) 7.4

Cycle 4 stroke 75% prime power(L/h) 5.3

Induction system aspirated 50% prime power(L/h) 3.9

Compressionratio 16.5:1Bore(mm) 100 EXHAUST SYSTEMStroke(mm) 127 Maximum back pressure(kPa) 5

Cubic capacity(L) 2.99 Exhaust outlet size-horizontal/vertical(mm) 34/40

Estimated total weight(dry)(kg) 410COOLING SYSTEM

GENERAL INSTALLATION RadiatorEngine rated speed(rpm) 1800 Face area 17.7Gross engine power-prime(kW) 33 Rows and materials(m2) 2 rows, AluminiumGross engine power-Standby(kW) 36 Matrix density and material 14.5 FPI AluminiumBrake mean effective pressure(kPa) Pressure cap setting(kPa) 75

Mean piston speed(m/s) 6.35 FanEngine coolant flow(L/min) Diameter(mm) Combustion air flow(m3/min) 1850 Drive ratio 508Exhaust gas flow (max)(m3/min) 5.6 Number of blades 10Exhaust gas temperature outlet (max)(℃) 600 Material Plastic

Type Pusher

LUBRICATION SYSTEM CoolantLubricating oil capacity Total system capacity(with radiator)(L) 17 Maximum sump capacity(L) 9.5 Maximum top tank temperature(℃) 100 Total system(L) 8.1 Max static pressure head on pump(kPa) 35

Minimum(L) 6.9 Thermostat operation range(℃) 82-88Maximum engine operating angles-front up/front down/right side or left side 25º ELECTRICAL SYSTEMLubricating oil pressure 310-390 Alternator 12/24vMinimum oil pressure(kPa) Starter motor 12/24v

Normal oil temperature( ℃) 105oil flow at rated speed(L/min) 330

NOTE:All dat a is based on: 1.Engineoperatingwithfuelsystem,waterpump,lubricatingoilpump,aircleanerandexhaustsilencer;notincludedarebatterychargingalternator,fan,andoptionaldrivencomponents.2.EngineoperatingwithfuelcorrespondingtogradeNo.2-DperASTMD975.3.ISO3046,Part1,StandardReferenceConditionsof:BarometricPressure:100kPa(29.53inHg)AirTemperature:25(77℉)Altitude:110m(361 ft)RelativeHumidity:30%AirIntakeRestriction:254mmHO(10 in H2O)ExhaustRestriction:51mmHg(2 in Hg)N/A: Not AvailableTBD: To Be Determined CP: Continuous power FSP: Fuel stop power

FUEL SYSTEMType of injection Indirect injection

Fuel injection pump CASSETTE pump Nozzle opening pressure(MPa) 70

Maximum particle size 25 microns

FUEL LIFT PUMPType MerchanicalFlow/hour(L/h) 55Pressure(kPa) 9Maximum suction head(m) 0.8Maximum static pressure head(m) 3

Governor type Merchanica

www.perfectotal.com

Page 3: RPM1800 60Hzperfectotal.com/uploadfile/27EPTV_60.pdf · POWERED BY LOVOL DIESEL GENERATOR SET Model:27EPTV 190V-440V3P4W RPM1800 60Hz Rating Range Emergency: kW 30 Kva 38 prime: kW

Hangzhou Perfect Total Machinery Co.,Ltd

POWERED BY LOVOL DIESEL GENERATOR SET

ALTERNATOR

LEROY SOMER STAMFORD

Alternator Model LSA42.2M7 PI144G

FrequencyandSpeed 60Hz/1800rpm 60Hz/1800rpm

Voltage(V) 220/127 220/127

Primecapacity(kVA) 34 35.3

Primepower(kW) 27 28.2

Powerefficiency(%) 89.7 86.6

Inputpower(kW) 30.1 32.65

Voltageregulation 0.5% 1.0%

Ratedpowerfactor 0.8 0.8

Statorwinding 2/3 2/3

Maximumoverspeed 2250min-1 2250min-1

Sustainedshortcircuit 300%(3IN):10S 188Amps

CoolingAir(m3/sec) 0.18 0.108

Dimensions and WeightsOpen Style Soundproof StyleOverallSize , L W H mm 1750 780 950 OverallSize , L W H mm 2200 950 1380Weight(radiatormodel),net,kg 500kg Weight(radiatormodel),net,kg 1150kg

www.perfectotal.com

Page 4: RPM1800 60Hzperfectotal.com/uploadfile/27EPTV_60.pdf · POWERED BY LOVOL DIESEL GENERATOR SET Model:27EPTV 190V-440V3P4W RPM1800 60Hz Rating Range Emergency: kW 30 Kva 38 prime: kW

Hangzhou Perfect Total Machinery Co.,Ltd

POWERED BY PERKINS DIESEL GENERATOR SET

DEEPSEA CONTROL SYSTEMControlled by Model DSE7220

Description For Module DSE7220

Standardfunctions Shutdown WarningEngineControl LossofSpeedSignal AlternatorUnder/OverVoltage

GeneratorMonitoring AlternatorUnder/OverVoltage AlternatorUnder/OverFrequency

GeneratorProtection AlternatorUnder/OverFrequency MainsUnder/OverVoltage

EngineMonitoring MainsUnder/OverVoltage MainsUnder/OverFrequency

ClearTextDisplay MainsUnder/OverFrequency Under/OverSpeed

Under/OverSpeed LowOilPressurePre-Alarm

LowOilPressure HighEngineTemperaturePre-Alarm

High Engine Temperature High/LowBatteryVoltage

PhaseSequenceElectrical(Option) Over-current

EarthFault(Option) Periodicmaintenance

The Gen-set Controller DSE7220 is a microprocessor based control unit containing all necessary functions forprotection and control of a diesel engine. Further more,it contains a three-phase AC voltage measuring circuit. The unit is equipped with an LCD display presenting all values and alarms. DSE7220 is a compact all-in-one unitdesigned for the following applications:1. Automatic engine start/stop2. Engine protection3. Breaker control4. Generator protection

Hangzhou Perfect Total Machinery Co.,Ltd

www.perfectotal.com