ryp-l7/b7 pair application - daikin Θεσσαλονίκης, Μηχανήματα ... ·...

53
RYP-L7/B7 Pair Application technical data Split Sky Air air conditioning systems

Upload: others

Post on 21-Mar-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

RYP-L7/B7

Pair Application

technical data

SplitSky Air

air co

nd

ition

ing

system

s

Page 2: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

Split - Sky Air

EE

DE0

5-1

/2 •

05/2

005

Prepar

ed in

Belg

ium

by

Goeki

nt

Gra

phic

s

Zandvoordestraat 300

B - 8400 Ostend Belgium

Internet: http://www.daikineurope.com

Specifications are subject to change without prior notice.

ISO14001 assures an effective environmental management system in order to help protecthuman health and the environment from the potentialimpact of our activities, products and services and toassist in maintaining and improving the quality ofthe environment

Daikin Europe N.V. is approved by LRQA for its Quality Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.

Daikin units comply with the European regulations that guarantee the safety of the product.

Daikin Europe N.V. participates in the Eurovent Certification Programme for Air Conditioners (AC), Liquid Chilling Packages (LCP) and Fan Coil Units (FC); the certified data of certified models are listed in the Eurovent Directory.

Page 3: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

TABLE OF CONTENTSRYP-L7/B7

1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Technical specifications

Electrical specifications

3 Capacity tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

4 Dimensional drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

5 Operation range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

6 Piping diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

7 Wiring diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

8 Sound level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Sound level data

Sound pressure spectrum

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41Optional accessories

10 Center of gravity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

11 Safety device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

12 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

1• Split - Sky Air • Outdoor Units

Page 4: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

1 Features

Outdoor units for pair application

+ Daikin outdoor units are neat and sturdy and can be mountedeasily on a roof or terrace or simply placed against an outsidewall.

+ They are fitted with a scroll compressor, renowned for lownoise and high energy efficiency.

+ The piping connections can be accessed from underneath,front, side or rear.

+ The service valves are hidden inside the casing.+ A special acryl precoated fin for anti-corrosion treatment on the

heat exchanger ensures greater resistance against severeweather conditions.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

11

2 • Split - Sky Air • Outdoor Units

Page 5: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

2 Specifications

TECHNICAL SPECIFICATIONSOUTDOOR UNITS RYP71L7V1/W1 RYP100L7V1/W1 RYP125L7W1 RYP200B7W1 RYP250B7W1DIMENSIONS Unit H mm 770 1,170 1,220 1,440

W mm 900 900 1,290D mm 320 320 700

WEIGHT kg 80/79 102/101 106 196 210MATERIAL Unit Painted galvanised steel plateCOLOUR Unit Ivory whiteSOUND LEVEL Sound pressure (1)

(cooling/heating)high dB(A) 50/52 53/56 53/56 57/57 57/57

Sound power (2)(cooling)

high dB(A) 63 66 67 77/78 77/78

FAN Air flow rate(cooling/heating)

high m3/min 48/43 55/50 89/80 170/- 175/-

Speed steps 3 steps 1 stepQty x model 1xP47L11S 2xP47L11S 1xP55J11FQty x motor output W 1 x 65 1 x 90 85 + 65 1 x (320+190)

HEAT EXCHANGER Type Hi-XSS cooling tube, non sym. waffle fin J8 Hi-XA tube assymetric louvreRows x stages x fin pitch mm 2 x 34 x 2.0 2 x 52 x 2.0 2 x 52 x 2.0 2 x 40 x 2.0 2 x 50 x 2.0Face area m2 0.634 0.983 0.983 1.57 1.97

REFRIGERANT CIRCUIT Refrigerant type R-407CRefrigerant charge kg 2.8 3.7 7.5 9.2Minimum/maximum allowable distancebetween indoor and outdoor

m 5/70 - / 50 (70m equivalent)

Maximum allowable level difference m 30Additional refrigerant charge g/m Please refer to installation 100 g/m for total

piping length > 30 m140 g/m for total

piping length > 30 mRefrigerant control Expansion valve (electronic type) Expansion valve

COMPRESSOR Type Hermetically sealed scroll typeQty x model 1xJT90FA-V1N 1xJT125FA-V1NX 1xJT160FA-YE 1xJT236DA-YE@2 1xJT300DA-YE@2Motor output x no W 2,200 x 1 3,000 x 1 3,750 x 1 5,500 x 1 7,500 x 1Speed rpm - - - 2,900 2,900Oil type DAPHNE FVC68DOil charge volume ! 1,200 1,500 4 4Crankcase heater W - - - 50 72

PIPING CONNECTIONS liquid mm φ9.5 φ12.7 x 0.90 φ15.9 x 0.95gas mm φ15.9 φ19.1 28.6φ x 1.15 28.6φ x 1.15drain mm φ26 x 3 26φ x 6 26φ x 6

INSULATION MATERIAL Heat insulation Both liquid and gas pipesSafety devices High and low pressure switch, thermal protection

for indoor and outdoor fan motor, overcurrentrelay (compressor), fuse

High and low pressure switch, thermal protector for indoor and outdoor fanmotor, overcurrent relay (compressor), reverse phase protector, fuse

3TW25141-1B3TW25181-1B3TW25251-1A3TW25191-1A3TW25201-1A3TW23631-1A3TW23641-1A

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

12

3• Split - Sky Air • Outdoor Units

Page 6: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

ELECTRICAL SPECIFICATIONSOUTDOOR UNITS RYP71L7V1/W1 RYP100L7V1/W1 RYP125L7W1 RYP200B7W1 RYP250B7W1CURRENT Nominal running current cooling/heating A Please refer to electrical data 14.4 17.2

Max. running current cooling/heating A Please refer to electrical dataStarting current cooling/heating A Please refer to electrical data

POWER SUPPLY V1/W1 V1/W1 W1 W1 W1NOMINAL DISTRIBUTIONSYSTEM VOLTAGE

Phase 1∼/3N∼ 1∼/3N∼ 3N∼ 3N∼ 3N∼Frequency Hz 50 50 50 50 50Voltage V 230/400 230/400 400 400 400

NOTES1 The sound pressure level is measured in an anechoic room at 1m distance from the unit. It is a relative value, depending on the distance and

acoustic environment. For measuring conditions: please refer to item 8 of this chapter.

2 The sound power level is an absolute value indicating the ’’power’’ which a sound source generates.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

2 Specifications

12

4 • Split - Sky Air • Outdoor Units

Page 7: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

ELECTRICAL DATA

RYP71L7

Unit combination Power supply Compressor OFM IFMIndoor unit Outdoor unit Hz-Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA

FHYCP71 RYP71L7V1 50-230

Max. 50Hz-264VMin. 50Hz-198V

15.1 23.2 32 72 11.1 0.065 0.6 0.045 0.6

FUYP71 RYP71L7V1 50-230 14.7 23.2 32 72 10.8 0.065 0.6 0.045 0.6

FHYP71 RYP71L7V1 50-230 15.6 23.2 32 72 11.5 0.065 0.6 0.062 0.6

FHYKP71 RYP71L7V1 50-230 14.4 23.1 32 72 10.6 0.065 0.6 0.045 0.5

FAYP71 RYP71L7V1 50/230 14.3 22.9 32 72 10.7 0.065 0.6 0.046 0.3

FHYBP71 RYP71L7V1 50-230 14.8 23.5 32 72 10.6 0.065 0.6 0.125 0.9

FDYMP71 RYP71L7V1 50-230 14.8 23.5 32 72 10.6 0.065 0.6 0.125 0.9

FHYCP71 RYP71L7W1 50-400/230

Max. 50Hz-440/253VMin. 50Hz-360/197V

6.6 11.2 16 37 4.3 0.065 0.6 0.045 0.6

FUYP71 RYP71L7W1 50-400/230 6.5 11.2 16 37 4.2 0.065 0.6 0.045 0.6

FHYP71 RYP71L7W1 50-400/230 6.7 11.2 16 37 4.4 0.065 0.6 0.062 0.6

FHYKP71 RYP71L7W1 50-400/230 6.4 11.1 16 37 4.2 0.065 0.6 0.045 0.5

FAYP71 RYP71L7W1 50-400/230 6.2 10.9 16 37 4.2 0.065 0.6 0.046 0.3

FHYBP71 RYP71L7W1 50-400/230 6.8 11.5 16 37 4.2 0.065 0.6 0.125 0.9

FDYMP71 RYP71L7W1 50-400/230 6.8 11.5 16 37 4.2 0.065 0.6 0.125 0.9

3TW25149-2

SYMBOLSMCA : Min. Circuit AmpsTOCA : Total Over Current AmpsMFA : Max. Fuse Amps (see note 7)LRA : Locked Rotor AmpsRLA : Rated Load AmpsOFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load AmpskW : Rated motor output

NOTES1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.5°CWBOutdoor temp. : 35°CDB

2. TOCA means the total value of each OC set3. Voltage range

Units are suitable for use on electrical systems where voltagesupplied to unit terminals is not below or above listedoperation range limits

4. Maximum allowable voltage unbalance between phases is 2%.5. MCA/MFA

MCA = 1.25 x RLA + all FLA, MFA = < 2.25 x RLA + all FLA(next lower standard fuse rating Min. 16A)

6. Select wire size based on the larger value of MCA or TOCA7. Instead of fuse, use circuit breaker8. For more details concerning conditional connections, see

http://www.daikineurope.com/extranet, select ’’DaikinDocumentation’’ and select ’’conditional connection’’, ’’therequested product type’’ and ’’English’’ from the drop downlists, click the search button.Finally, click on the document title of your choice.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

2 Specifications

12

5• Split - Sky Air • Outdoor Units

Page 8: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

ELECTRICAL DATA

RYP100L7

Unit combination Power supply Compressor OFM IFMIndoor unit Outdoor unit Hz-Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA

FHYCP100 RYP100L7V1 50-230

Max. 50Hz-264VMin. 50Hz-198V

22.7 34.8 40 97 16.7 0.090 0.8 0.090 1.0

FUYP100 RYP100L7V1 50-230 22.3 34.8 40 97 16.4 0.090 0.8 0.090 1.0

FHYP100 RYP100L7V1 50-230 22.5 34.5 40 97 16.8 0.090 0.8 0.130 0.7

FAYP100 RYP100L7V1 50-230 22.1 34.2 40 97 16.7 0.090 0.8 0.049 0.4

FHYBP100 RYP100L7V1 50-230 22.3 34.8 40 97 16.4 0.090 0.8 0.135 1.0

FDYMP100 RYP100L7V1 50-230 22.4 34.8 40 97 16.5 0.090 0.8 0.135 1.0

FHYCP100 RYP100L7W1 50-400/230

Max. 50Hz-440/253VMin. 50Hz-360/197V

9.3 11.8 16 47 6.0 0.090 0.8 0.090 1.0

FUYP100 RYP100L7W1 50-400/230 9.3 11.8 16 47 6.0 0.090 0.8 0.090 1.0

FHYP100 RYP100L7W1 50-400/230 9.3 11.5 16 47 6.2 0.090 0.8 0.130 0.7

FAYP100 RYP100L7W1 50-400/230 8.8 11.2 16 47 6.1 0.090 0.8 0.049 0.4

FHYBP100 RYP100L7W1 50-400/230 9.3 11.8 16 47 6.0 0.090 0.8 0.135 1.0

FDYMP100 RYP100L7W1 50-400/230 9.4 11.8 16 47 6.1 0.090 0.8 0.135 1.0

3TW25159-2

SYMBOLSMCA : Min. Circuit AmpsTOCA : Total Over Current AmpsMFA : Max. Fuse Amps (see note 7)LRA : Locked Rotor AmpsRLA : Rated Load AmpsOFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load AmpskW : Rated motor output

NOTES1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.5°CWBOutdoor temp. : 35°CDB

2. TOCA means the total value of each OC set3. Voltage range

Units are suitable for use on electrical systems where voltagesupplied to unit terminals is not below or above listedoperation range limits

4. Maximum allowable voltage unbalance between phases is 2%.5. MCA/MFA

MCA = 1.25 x RLA + all FLA, MFA = < 2.25 x RLA + all FLA(next lower standard fuse rating Min. 16A)

6. Select wire size based on the larger value of MCA or TOCA7. Instead of fuse, use circuit breaker8. For more details concerning conditional connections, see

http://www.daikineurope.com/extranet, select ’’DaikinDocumentation’’ and select ’’conditional connection’’, ’’therequested product type’’ and ’’English’’ from the drop downlists, click the search button.Finally, click on the document title of your choice.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

2 Specifications

12

6 • Split - Sky Air • Outdoor Units

Page 9: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

ELECTRICAL DATA

RYP125L7

Unit combination Power supply Compressor OFM IFMIndoor unit Outdoor unit Hz-Volts Voltage range MCA TOCA MFA LRA RLA kW FLA kW FLA

FHYCP125 RYP125L7W1 50-400/230

Max. 50Hz-440/253VMin. 50Hz-360/197V

12.2 15.3 20 59 7.90.065

+0.085

0.6+0.7

0.09 1.0

FUYP125 RYP125L7W1 50-400/230 11.4 15.3 20 59 7.30.065

+0.085

0.6+0.7

0.09 1.0

FHYP125 RYP125L7W1 50-400/230 12.1 15.0 20 59 8.10.065

+0.085

0.6+0.7

0.13 0.7

FHYBP125 RYP125L7W1 50-400/230 12.0 15.7 20 59 7.40.065

+0.085

0.6+0.7

0.225 1.4

FDYMP125 RYP125L7W1 50-400/230 12.0 15.7 20 59 7.40.065

+0.085

0.6+0.7

0.225 1.4

FDYP125 RYP125L7W1 50-400/230 14.8 18.5 20 59 7.40.065

+0.085

0.6+0.7

0.5 4.2

3TW25209-2

SYMBOLSMCA : Min. Circuit AmpsTOCA : Total Over Current AmpsMFA : Max. Fuse Amps (see note 7)LRA : Locked Rotor AmpsRLA : Rated Load AmpsOFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load AmpskW : Rated motor output

NOTES1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.5°CWBOutdoor temp. : 35°CDB

2. TOCA means the total value of each OC set3. Voltage range

Units are suitable for use on electrical systems where voltagesupplied to unit terminals is not below or above listedoperation range limits

4. Maximum allowable voltage unbalance between phases is 2%.5. MCA/MFA

MCA = 1.25 x RLA + all FLA, MFA = < 2.25 x RLA + all FLA(next lower standard fuse rating Min. 16A)

6. Select wire size based on the larger value of MCA or TOCA7. Instead of fuse, use circuit breaker8. For more details concerning conditional connections, see

http://www.daikineurope.com/extranet, select ’’DaikinDocumentation’’ and select ’’conditional connection’’, ’’therequested product type’’ and ’’English’’ from the drop downlists, click the search button.Finally, click on the document title of your choice.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

2 Specifications

12

7• Split - Sky Air • Outdoor Units

Page 10: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

RYP200-250B7

Unit combination Power supply Compressor OFM IFMIndoor unit Outdoor unit Hz-Volts Voltage range MCA MFA LRA RLA kW FLA kW FLA

FDYP200B7V1 RYP200B7W1 50-400 Min. 360VMax. 440V 19.0 25 (Outdoor) + 16 (Indoor) 98 12.9

0.19+

0.23

1.28+

1.43650 6.8

FDYP250B7V1 RYP250B7W1 50-400 Min. 360VMax. 440V 22.9 32 (Outdoor) + 16 (Indoor) 108 16.0

0.19+

0.23

1.28+

1.431,000 7.6

3TW23611-2

ELECTRICAL DATA

SYMBOLSMCA : Min. Circuit AmpsMFA : Max. Fuse AmpsLRA : Locked Rotor AmpsRLA : Rated Load Amps (A)OFM : Outdoor Fan MotorIFM : Indoor Fan MotorFLA : Full Load AmpsKW : Rated motor output (W)

NOTES1. RLA is based on the following conditions:

Indoor temp.: 27°CDB/19.0°CWBOutdoor temp. : 35°CDB

2. Voltage rangeUnits are suitable for use on electrical systems where voltage suppliedto unit terminals is not below or above listed operation range limits

3. Maximum allowable voltage unbalance between phases is 2%.4. MCA/MFA

MCA = 1.25 x RLA + ea FLAMFA = <2.25 x RLA + ea FLA(next lower standard fuse rating min 16A)

5. Select wire size based on the larger value of MCA or TOCA6. Instead of fuse, use circuit breaker7. For more details concerning conditional connections, see

http://www.daikineurope.com/extranet, select ’’Daikin Documentation’’and select ’’conditional connection’’, ’’the requested product type’’ and’’English’’ from the drop down lists, click the search button.Finally, click on the document title of your choice.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

2 Specifications

12

8 • Split - Sky Air • Outdoor Units

Page 11: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

3 Capacity tables

FHYKP71BV1 + RYP71L7V1RYP71L7W1

Cooling capacity V1/T1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

71

12.0 18.00 6.2 4.9 1.77 6.1 4.8 2.02 5.7 4.7 2.19 5.5 4.6 2.36 5.3 4.5 2.61 4.9 4.2 2.8714.0 20.00 6.6 4.9 1.86 6.5 4.8 2.11 6.0 4.7 2.28 5.9 4.6 2.36 5.5 4.5 2.61 5.3 4.2 2.8716.0 22.00 7.2 5.0 1.86 7.0 4.9 2.11 6.5 4.8 2.28 6.3 4.7 2.45 6.0 4.6 2.70 5.5 4.3 2.9518.0 25.00 7.7 5.2 1.94 7.5 5.0 2.11 7.2 4.9 2.36 6.8 4.8 2.53 6.4 4.6 2.70 6.0 4.5 3.0419.0 27.00 8.0 5.3 1.94 7.7 5.2 2.11 7.3 5.0 2.36 7.1 4.8 2.53 6.6 4.7 2.78 6.2 4.6 3.0419.5 27.00 8.0 5.3 1.94 7.9 5.2 2.11 7.4 5.0 2.36 7.2 4.8 2.53 6.7 4.7 2.78 6.3 4.6 3.0422.0 30.00 8.7 5.4 2.02 8.5 5.3 2.19 8.0 5.2 2.45 7.9 4.9 2.61 7.4 4.8 2.78 6.8 4.6 3.1224.0 32.00 9.4 5.4 2.02 9.1 5.3 2.19 8.6 5.2 2.53 8.4 5.0 2.61 8.0 4.8 2.87 7.4 4.6 3.20

3TW25142-7A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FHYKP

71 AFR 17BF 0.07

7. Add the following corrections to power input of each model.

Model Supply FHYKP

71 V1 0.13W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

13

9• Split - Sky Air • Outdoor Units

Page 12: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FHYKP71BV1 + RYP71L7V1RYP71L7W1

Heating capacity V1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

71

16.0 6.3 2.17 6.7 2.25 7.4 2.25 8.1 2.33 8.6 2.33 - -18.0 6.3 2.17 6.7 2.25 7.4 2.33 8.0 2.41 8.6 2.41 - -20.0 6.3 2.33 6.7 2.33 7.3 2.41 8.0 2.49 8.6 2.57 9.3 2.6522.0 6.3 2.33 6.7 2.41 7.3 2.49 8.0 2.57 8.6 2.57 9.1 2.6524.0 6.3 2.41 6.7 2.49 7.3 2.57 7.9 2.65 8.6 2.65 9.1 2.73

3TW25142-13A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FHYKP

71 AFR 17BF 0.07

6. Add the following corrections to power input of each model.

Model Supply FHYKP

71 V1 0.14W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

10 • Split - Sky Air • Outdoor Units

Page 13: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FAYP71-100BV1 + RYP71-100L7V1RYP71-100L7W1

Cooling capacity V1/T1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

71

12.0 18.0 6.2 4.9 1.77 6.1 4.8 2.02 5.7 4.7 2.19 5.5 4.6 2.36 5.3 4.5 2.61 4.9 4.2 2.8714.0 20.0 6.6 4.9 1.86 6.5 4.8 2.11 6.0 4.7 2.28 5.9 4.6 2.36 5.5 4.5 2.61 5.3 4.2 2.8716.0 22.0 7.2 5.0 1.86 7.0 4.9 2.11 6.5 4.8 2.28 6.3 4.7 2.45 6.0 4.6 2.70 5.5 4.3 2.9518.0 25.0 7.7 5.2 1.94 7.5 5.0 2.11 7.2 4.9 2.36 6.8 4.8 2.53 6.4 4.6 2.70 6.0 4.5 3.0419.0 27.0 8.0 5.3 1.94 7.7 5.2 2.11 7.3 5.0 2.36 7.1 4.8 2.53 6.6 4.7 2.78 6.2 4.6 3.0419.5 27.0 8.0 5.3 1.94 7.9 5.2 2.11 7.4 5.0 2.36 7.2 4.8 2.53 6.7 4.7 2.78 6.3 4.6 3.0422.0 30.0 8.7 5.4 2.02 8.5 5.3 2.19 8.0 5.2 2.45 7.9 4.9 2.61 7.4 4.8 2.78 6.8 4.6 3.1224.0 32.0 9.4 5.4 2.02 9.1 5.3 2.19 8.6 5.2 2.53 8.4 5.0 2.61 8.0 4.8 2.87 7.4 4.6 3.20

100

12.0 18.0 8.4 7.2 2.57 8.3 7.1 2.76 8.1 6.9 3.14 7.8 6.8 3.33 7.5 6.4 3.71 6.9 6.2 4.0914.0 20.0 8.9 7.2 2.66 8.8 7.1 2.76 8.7 6.9 3.14 8.4 6.8 3.33 7.8 6.4 3.71 7.5 6.2 4.0916.0 22.0 10.1 7.3 2.66 9.8 7.2 2.85 9.1 7.0 3.23 8.9 6.9 3.42 8.5 6.5 3.81 7.8 6.3 4.1918.0 25.0 10.8 7.6 2.66 10.5 7.5 2.85 9.8 7.1 3.23 9.6 7.0 3.42 9.0 6.8 3.81 8.4 6.4 4.2819.0 27.0 11.1 7.7 2.66 10.8 7.6 2.95 10.1 7.2 3.33 10.0 7.1 3.52 9.4 6.9 3.90 8.7 6.5 4.3819.5 27.0 11.2 7.7 2.66 11.0 7.6 2.95 10.3 7.2 3.33 10.1 7.1 3.52 9.5 6.9 3.90 8.8 6.5 4.3822.0 30.0 12.2 7.8 2.76 11.8 7.7 2.95 11.2 7.3 3.42 11.0 7.2 3.62 10.4 7.1 4.00 9.6 6.8 4.3824.0 32.0 13.0 7.9 2.85 12.7 7.8 3.04 11.9 7.5 3.52 11.6 7.3 3.71 11.1 7.2 4.09 10.3 6.9 4.47

3TW25142-6A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FAYP

71 AFR 19BF 0.1

100 AFR 23BF 0.1

7. Add the following corrections to power input of each model.

Model Supply FAYP

71 V1 0.12W1 0

100 V1 0.04W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

11• Split - Sky Air • Outdoor Units

Page 14: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FAYP71-100BV1 + RYP71-100L7V1RYP71-100L7W1

Heating capacity V1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CWB)EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

71

16.0 6.3 2.04 6.7 2.11 7.4 2.11 8.1 2.19 8.6 2.19 - -18.0 6.3 2.04 6.7 2.11 7.4 2.19 8.0 2.26 8.6 2.26 - -20.0 6.3 2.19 6.7 2.19 7.3 2.26 8.0 2.34 8.6 2.42 9.3 2.4922.0 6.3 2.19 6.7 2.26 7.3 2.34 8.0 2.42 8.6 2.42 9.1 2.4924.0 6.3 2.26 6.7 2.34 7.3 2.42 7.9 2.49 8.6 2.49 9.1 2.57

100

16.0 8.4 3.08 9.1 3.18 10.0 3.27 11.0 3.37 11.6 3.47 - -18.0 8.3 3.18 9.0 3.27 10.0 3.37 10.9 3.47 11.6 3.56 - -20.0 8.3 3.37 8.9 3.47 9.8 3.56 10.8 3.66 11.5 3.76 12.5 3.8522.0 8.3 3.47 8.9 3.56 9.8 3.66 10.8 3.76 11.5 3.85 12.4 3.9524.0 8.2 3.56 8.9 3.66 9.6 3.76 10.6 3.85 11.3 3.95 12.4 4.05

3TW25142-12A

SYMBOLS

AFR: Air flow rate (m3/min)EDB: Entering dry bulb temp. (°CDB)WB: Wet bulb temperature (°CWB)TC: Total cooling capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FAYP

71 AFR 19BF 0.1

100 AFR 23BF 0.1

6. Add the following corrections to power input of each model.

Model Supply FAYP

71 V1 0.14W1 0

100 V1 0.03W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

12 • Split - Sky Air • Outdoor Units

Page 15: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FHYCP71-125B7V1 + RYP71-100L7V1RYP71-125L7W1

Cooling capacity V1/T1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

71

12.0 18.00 6.2 4.8 1.86 6.1 4.7 2.13 5.7 4.6 2.31 5.5 4.5 2.48 5.3 4.4 2.75 4.9 4.1 3.0114.0 20.00 6.6 4.8 1.95 6.5 4.7 2.22 6.0 4.6 2.39 5.9 4.5 2.48 5.5 4.4 2.75 5.3 4.1 3.0116.0 22.00 7.2 4.9 1.95 7.0 4.8 2.22 6.5 4.7 2.39 6.3 4.6 2.57 6.0 4.5 2.84 5.5 4.2 3.1018.0 25.00 7.7 5.1 2.04 7.5 4.9 2.22 7.2 4.8 2.48 6.8 4.7 2.66 6.4 4.5 2.84 6.0 4.4 3.1919.0 27.00 8.0 5.2 2.04 7.7 5.1 2.22 7.3 4.9 2.48 7.1 4.7 2.66 6.6 4.6 2.93 6.2 4.5 3.1919.5 27.00 8.0 5.2 2.04 7.9 5.1 2.22 7.4 4.9 2.48 7.2 4.7 2.66 6.7 4.6 2.93 6.3 4.5 3.1922.0 30.00 8.7 5.3 2.13 8.5 5.2 2.31 8.0 5.1 2.57 7.9 4.8 2.75 7.4 4.7 2.93 6.8 4.5 3.2824.0 32.00 9.4 5.3 2.13 9.1 5.2 2.31 8.6 5.1 2.66 8.4 4.9 2.75 8.0 4.7 3.01 7.4 4.5 3.37

100

12.0 18.00 8.4 7.0 2.60 8.3 6.9 2.79 8.1 6.7 3.18 7.8 6.6 3.37 7.5 6.2 3.75 6.9 6.0 4.1414.0 20.00 8.9 7.0 2.69 8.8 6.9 2.79 8.7 6.7 3.18 8.4 6.6 3.37 7.8 6.2 3.75 7.5 6.0 4.1416.0 22.00 10.1 7.1 2.69 9.8 7.0 2.89 9.1 6.8 3.27 8.9 6.7 3.46 8.5 6.3 3.85 7.8 6.1 4.2318.0 25.00 10.8 7.4 2.69 10.5 7.3 2.89 9.8 6.9 3.27 9.6 6.8 3.46 9.0 6.6 3.85 8.4 6.2 4.3319.0 27.00 11.1 7.5 2.69 10.8 7.4 2.98 10.1 7.0 3.37 10.0 6.9 3.56 9.4 6.7 3.94 8.7 6.3 4.4319.5 27.00 11.2 7.5 2.69 11.0 7.4 2.98 10.3 7.0 3.37 10.1 6.9 3.56 9.5 6.7 3.94 8.8 6.3 4.4322.0 30.00 12.2 7.6 2.79 11.8 7.5 2.98 11.2 7.1 3.46 11.0 7.0 3.66 10.4 6.9 4.04 9.6 6.6 4.4324.0 32.00 13.0 7.7 2.89 12.7 7.6 3.08 11.9 7.3 3.56 11.6 7.1 3.75 11.1 7.0 4.14 10.3 6.7 4.52

125

12.0 18.00 11.1 9.1 3.37 10.8 8.8 3.67 10.0 8.3 3.97 9.7 8.2 4.26 9.2 8.0 4.66 8.6 7.6 5.3514.0 20.00 11.8 9.1 3.47 11.4 8.8 3.67 10.7 8.3 4.06 10.4 8.2 4.36 9.8 8.0 4.76 9.2 7.6 5.3516.0 22.00 12.7 9.2 3.47 12.1 8.9 3.77 11.4 8.4 4.06 11.1 8.3 4.46 10.4 8.1 4.86 9.7 7.7 5.4518.0 25.00 13.3 9.5 3.57 13.0 9.1 3.77 12.1 8.7 4.16 11.8 8.6 4.56 11.2 8.3 4.96 10.4 8.0 5.4519.0 27.00 13.6 9.6 3.67 13.3 9.1 3.87 12.7 8.8 4.26 12.2 8.6 4.56 11.5 8.4 5.06 10.8 8.1 5.5519.5 27.00 13.8 9.6 3.67 13.5 9.1 3.87 12.8 8.8 4.26 12.4 8.7 4.56 11.7 8.4 5.06 11.0 8.1 5.5522.0 30.00 15.1 9.7 3.77 14.6 9.4 3.87 13.7 9.0 4.36 13.4 8.9 4.66 12.9 8.7 5.15 12.0 8.3 5.7524.0 32.00 15.9 9.8 3.77 15.5 9.5 3.97 14.6 9.1 4.46 14.3 9.0 4.76 13.6 8.8 5.25 12.9 8.6 5.85

3TW25142-1A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FHYCP

71 AFR 19BF 0.1

100 AFR 28BF 0.16

125 AFR 33BF 0.07

7. Add the following corrections to power input of each model.

Model Supply FHYCP

71 V1 0.06W1 0

100 V1 0.27W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

13• Split - Sky Air • Outdoor Units

Page 16: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FHYCP71-125B7V1 + RYP71-100L7V1RYP71-125L7W1

Heating capacity V1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CWB)EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

71

16.0 6.3 2.44 6.7 2.53 7.4 2.53 8.1 2.62 8.6 2.62 - -18.0 6.3 2.44 6.7 2.53 7.4 2.62 8.0 2.71 8.6 2.71 - -20.0 6.3 2.62 6.7 2.62 7.3 2.71 8.0 2.80 8.6 2.89 9.3 2.9822.0 6.3 2.62 6.7 2.71 7.3 2.80 8.0 2.89 8.6 2.89 9.1 2.9824.0 6.3 2.71 6.7 2.80 7.3 2.89 7.9 2.98 8.6 2.98 9.1 3.07

100

16.0 8.7 3.08 9.5 3.18 10.3 3.27 11.4 3.37 12.1 3.47 - -18.0 8.6 3.18 9.4 3.27 10.3 3.37 11.3 3.47 12.1 3.56 - -20.0 8.6 3.37 9.3 3.47 10.1 3.56 11.2 3.66 11.9 3.76 12.9 3.8522.0 8.6 3.47 9.3 3.56 10.1 3.66 11.2 3.76 11.9 3.85 12.8 3.9524.0 8.5 3.56 9.3 3.66 9.9 3.76 11.0 3.85 11.7 3.95 12.8 4.05

125

16.0 11.5 4.22 12.5 4.43 13.4 4.53 14.7 4.64 15.7 4.85 - -18.0 11.5 4.32 12.5 4.53 13.4 4.64 14.6 4.85 15.6 4.95 - -20.0 11.5 4.53 12.3 4.74 13.4 4.95 14.6 5.06 15.5 5.17 16.7 5.3822.0 11.5 4.64 12.3 4.85 13.4 4.95 14.6 5.17 15.5 5.27 16.7 5.4824.0 11.3 4.74 12.3 4.95 13.3 5.17 14.5 5.27 15.5 5.48 16.4 5.69

3TW25142-9A

SYMBOLS

AFR: Air flow rate (m3/min)EDB: Entering dry bulb temp. (°CDB)WB: Wet bulb temperature (°CWB)TC: Total cooling capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FHYCP

71 AFR 19BF 0.10

100 AFR 28BF 0.16

125 AFR 33BF 0.07

6. Add the following corrections to power input of each model.

Model Supply FHYCP

71 V1 0.05W1 0

100 V1 0.09W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

14 • Split - Sky Air • Outdoor Units

Page 17: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FHYBP71-125B7V1 + RYP71-100L7V1RYP71-125L7W1

Cooling capacity V1/T1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

71

12.0 18.00 6.2 4.8 1.81 6.1 4.7 2.07 5.7 4.6 2.24 5.5 4.5 2.42 5.3 4.4 2.68 4.9 4.1 2.9414.0 20.00 6.6 4.8 1.90 6.5 4.7 2.16 6.0 4.6 2.33 5.9 4.5 2.42 5.5 4.4 2.68 5.3 4.1 2.9416.0 22.00 7.2 4.9 1.90 7.0 4.8 2.16 6.5 4.7 2.33 6.3 4.6 2.50 6.0 4.5 2.76 5.5 4.2 3.0218.0 25.00 7.7 5.1 1.99 7.5 4.9 2.16 7.2 4.8 2.42 6.8 4.7 2.59 6.4 4.5 2.76 6.0 4.4 3.1119.0 27.00 8.0 5.2 1.99 7.7 5.1 2.16 7.3 4.9 2.42 7.1 4.7 2.59 6.6 4.6 2.85 6.2 4.5 3.1119.5 27.00 8.0 5.2 1.99 7.9 5.1 2.16 7.4 4.9 2.42 7.2 4.7 2.59 6.7 4.6 2.85 6.3 4.5 3.1122.0 30.00 8.7 5.3 2.07 8.5 5.2 2.24 8.0 5.1 2.50 7.9 4.8 2.68 7.4 4.7 2.85 6.8 4.5 3.1924.0 32.00 9.4 5.3 2.07 9.1 5.2 2.24 8.6 5.1 2.59 8.4 4.9 2.68 8.0 4.7 2.94 7.4 4.5 3.28

100

12.0 18.00 8.4 7.0 2.60 8.3 6.9 2.79 8.1 6.7 3.18 7.8 6.6 3.37 7.5 6.2 3.75 6.9 6.0 4.1414.0 20.00 8.9 7.0 2.69 8.8 6.9 2.79 8.7 6.7 3.18 8.4 6.6 3.37 7.8 6.2 3.75 7.5 6.0 4.1416.0 22.00 10.1 7.1 2.69 9.8 7.0 2.89 9.1 6.8 3.27 8.9 6.7 3.46 8.5 6.3 3.85 7.8 6.1 4.2318.0 25.00 10.8 7.4 2.69 10.5 7.3 2.89 9.8 6.9 3.27 9.6 6.8 3.46 9.0 6.6 3.85 8.4 6.2 4.3319.0 27.00 11.1 7.5 2.69 10.8 7.4 2.98 10.1 7.0 3.37 10.0 6.9 3.56 9.4 6.7 3.94 8.7 6.3 4.4319.5 27.00 11.2 7.5 2.69 11.0 7.4 2.98 10.3 7.0 3.37 10.1 6.9 3.56 9.5 6.7 3.94 8.8 6.3 4.4322.0 30.00 12.2 7.6 2.79 11.8 7.5 2.98 11.2 7.1 3.46 11.0 7.0 3.66 10.4 6.9 4.04 9.6 6.6 4.4324.0 32.00 13.0 7.7 2.89 12.7 7.6 3.08 11.9 7.3 3.56 11.6 7.1 3.75 11.1 7.0 4.14 10.3 6.7 4.52

125

12.0 18.00 11.1 9.1 3.36 10.8 8.8 3.66 10.0 8.3 3.96 9.7 8.2 4.25 9.2 8.0 4.65 8.6 7.6 5.3414.0 20.00 11.8 9.1 3.46 11.4 8.8 3.66 10.7 8.3 4.06 10.4 8.2 4.35 9.8 8.0 4.75 9.2 7.6 5.3416.0 22.00 12.7 9.2 3.46 12.1 8.9 3.76 11.4 8.4 4.06 11.1 8.3 4.45 10.4 8.1 4.85 9.7 7.7 5.4418.0 25.00 13.3 9.5 3.56 13.0 9.1 3.76 12.1 8.7 4.15 11.8 8.6 4.55 11.2 8.3 4.95 10.4 8.0 5.4419.0 27.00 13.6 9.6 3.66 13.3 9.1 3.86 12.7 8.8 4.25 12.2 8.6 4.55 11.5 8.4 5.04 10.8 8.1 5.5419.5 27.00 13.8 9.6 3.66 13.5 9.1 3.86 12.8 8.8 4.25 12.4 8.7 4.55 11.7 8.4 5.04 11.0 8.1 5.5422.0 30.00 15.1 9.7 3.76 14.6 9.4 3.86 13.7 9.0 4.35 13.4 8.9 4.65 12.9 8.7 5.14 12.0 8.3 5.7424.0 32.00 15.9 9.8 3.76 15.5 9.5 3.96 14.6 9.1 4.45 14.3 9.0 4.75 13.6 8.8 5.24 12.9 8.6 5.84

3TW25142-2A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FHYBP

71 AFR 19BF 0.11

100 AFR 27BF 0.2

125 AFR 35BF 0.14

7. Add the following corrections to power input of each model.

Model Supply FHYBP

71 V1 0.06W1 0

100 V1 0.22W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

15• Split - Sky Air • Outdoor Units

Page 18: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FHYBP71-125B7V1 + RYP71-100L7V1RYP71-125L7W1

Heating capacity V1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CWB)EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

71

16.0 6.3 2.17 6.7 2.25 7.4 2.25 8.1 2.33 8.6 2.33 - -18.0 6.3 2.17 6.7 2.25 7.4 2.33 8.0 2.41 8.6 2.41 - -20.0 6.3 2.33 6.7 2.33 7.3 2.41 8.0 2.49 8.6 2.57 9.3 2.6522.0 6.3 2.33 6.7 2.41 7.3 2.49 8.0 2.57 8.6 2.57 9.1 2.6524.0 6.3 2.41 6.7 2.49 7.3 2.57 7.9 2.65 8.6 2.65 9.1 2.73

100

16.0 8.7 3.26 9.5 3.36 10.3 3.46 11.4 3.56 12.1 3.67 - -18.0 8.6 3.36 9.4 3.46 10.3 3.56 11.3 3.67 12.1 3.77 - -20.0 8.6 3.56 9.3 3.67 10.1 3.77 11.2 3.87 11.9 3.97 12.9 4.0722.0 8.6 3.67 9.3 3.77 10.1 3.87 11.2 3.97 11.9 4.07 12.8 4.1824.0 8.5 3.77 9.3 3.87 9.9 3.97 11.0 4.07 11.7 4.18 12.8 4.28

125

16.0 11.4 3.77 12.4 3.96 13.4 4.05 14.6 4.14 15.5 4.33 - -18.0 11.4 3.86 12.4 4.05 13.4 4.14 14.5 4.33 15.5 4.43 - -20.0 11.4 4.05 12.2 4.24 13.3 4.43 14.5 4.52 15.4 4.61 16.6 4.8022.0 11.4 4.14 12.2 4.33 13.3 4.43 14.5 4.61 15.4 4.71 16.6 4.9024.0 11.3 4.24 12.2 4.43 13.2 4.61 14.4 4.71 15.4 4.90 16.3 5.09

3TW25142-10A

SYMBOLS

AFR: Air flow rate (m3/min)EDB: Entering dry bulb temp. (°CDB)WB: Wet bulb temperature (°CWB)TC: Total cooling capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FHYBP

71 AFR 19BF 0.11

100 AFR 27BF 0.2

125 AFR 35BF 0.14

6. Add the following corrections to power input of each model.

Model Supply FHYBP

71 V1 0W1 0

100 V1 0.04W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

16 • Split - Sky Air • Outdoor Units

Page 19: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FHYP71-125BV1 + RYP71-100L7V1RYP71-125L7W1

Cooling capacity V1/T1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

71

12.0 18.00 6.2 4.8 1.86 6.1 4.7 2.12 5.7 4.6 2.30 5.5 4.5 2.47 5.3 4.4 2.74 4.9 4.1 3.0014.0 20.00 6.6 4.8 1.94 6.5 4.7 2.21 6.0 4.6 2.39 5.9 4.5 2.47 5.5 4.4 2.74 5.3 4.1 3.0016.0 22.00 7.2 4.9 1.94 7.0 4.8 2.21 6.5 4.7 2.39 6.3 4.6 2.56 6.0 4.5 2.83 5.5 4.2 3.0918.0 25.00 7.7 5.1 2.03 7.5 4.9 2.21 7.2 4.8 2.47 6.8 4.7 2.65 6.4 4.5 2.83 6.0 4.4 3.1819.0 27.00 8.0 5.2 2.03 7.7 5.1 2.21 7.3 4.9 2.47 7.1 4.7 2.65 6.6 4.6 2.92 6.2 4.5 3.1819.5 27.00 8.0 5.2 2.03 7.9 5.1 2.21 7.4 4.9 2.47 7.2 4.7 2.65 6.7 4.6 2.92 6.3 4.5 3.1822.0 30.00 8.7 5.3 2.12 8.5 5.2 2.30 8.0 5.1 2.56 7.9 4.8 2.74 7.4 4.7 2.92 6.8 4.5 3.2724.0 32.00 9.4 5.3 2.12 9.1 5.2 2.30 8.6 5.1 2.65 8.4 4.9 2.74 8.0 4.7 3.00 7.4 4.5 3.36

100

12.0 18.00 8.4 7.0 2.66 8.3 6.9 2.86 8.1 6.7 3.26 7.8 6.6 3.45 7.5 6.2 3.85 6.9 6.0 4.2414.0 20.00 8.9 7.0 2.76 8.8 6.9 2.86 8.7 6.7 3.26 8.4 6.6 3.45 7.8 6.2 3.85 7.5 6.0 4.2416.0 22.00 10.1 7.1 2.76 9.8 7.0 2.96 9.1 6.8 3.35 8.9 6.7 3.55 8.5 6.3 3.95 7.8 6.1 4.3418.0 25.00 10.8 7.4 2.76 10.5 7.3 2.96 9.8 6.9 3.35 9.6 6.8 3.55 9.0 6.6 3.95 8.4 6.2 4.4419.0 27.00 11.1 7.5 2.76 10.8 7.4 3.06 10.1 7.0 3.45 10.0 6.9 3.65 9.4 6.7 4.04 8.7 6.3 4.5419.5 27.00 11.2 7.5 2.76 11.0 7.4 3.06 10.3 7.0 3.45 10.1 6.9 3.65 9.5 6.7 4.04 8.8 6.3 4.5422.0 30.00 12.2 7.6 2.86 11.8 7.5 3.06 11.2 7.1 3.55 11.0 7.0 3.75 10.4 6.9 4.14 9.6 6.6 4.5424.0 32.00 13.0 7.7 2.96 12.7 7.6 3.16 11.9 7.3 3.65 11.6 7.1 3.85 11.1 7.0 4.24 10.3 6.7 4.64

125

12.0 18.00 11.1 9.1 3.30 10.8 8.8 3.59 10.0 8.3 3.88 9.7 8.2 4.17 9.2 8.0 4.56 8.6 7.6 5.2414.0 20.00 11.8 9.1 3.39 11.4 8.8 3.59 10.7 8.3 3.98 10.4 8.2 4.27 9.8 8.0 4.65 9.2 7.6 5.2416.0 22.00 12.7 9.2 3.39 12.1 8.9 3.68 11.4 8.4 3.98 11.1 8.3 4.36 10.4 8.1 4.75 9.7 7.7 5.3318.0 25.00 13.3 9.5 3.49 13.0 9.1 3.68 12.1 8.7 4.07 11.8 8.6 4.46 11.2 8.3 4.85 10.4 8.0 5.3319.0 27.00 13.6 9.6 3.59 13.3 9.1 3.78 12.7 8.8 4.17 12.2 8.6 4.46 11.5 8.4 4.94 10.8 8.1 5.4319.5 27.00 13.8 9.6 3.59 13.5 9.1 3.78 12.8 8.8 4.17 12.4 8.7 4.46 11.7 8.4 4.94 11.0 8.1 5.4322.0 30.00 15.1 9.7 3.68 14.6 9.4 3.78 13.7 9.0 4.27 13.4 8.9 4.56 12.9 8.7 5.04 12.0 8.3 5.6224.0 32.00 15.9 9.8 3.68 15.5 9.5 3.88 14.6 9.1 4.36 14.3 9.0 4.65 13.6 8.8 5.14 12.9 8.6 5.72

3TW25142-4A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FHYP

71 AFR 17BF 0.1

100 AFR 24BF 0.14

125 AFR 30BF 0.13

7. Add the following corrections to power input of each model.

Model PI FHYP

71 V1 0.05W1 0

100 V1 0.03W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

17• Split - Sky Air • Outdoor Units

Page 20: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FHYP71-125BV1 + RYP71-100L7V1RYP71-125L7W1

Heating capacity V1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CWB)EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

71

16.0 6.3 2.44 6.7 2.53 7.4 2.53 8.1 2.62 8.6 2.62 - -18.0 6.3 2.44 6.7 2.53 7.4 2.62 8.0 2.71 8.6 2.71 - -20.0 6.3 2.62 6.7 2.62 7.3 2.71 8.0 2.80 8.6 2.89 9.3 2.9822.0 6.3 2.62 6.7 2.71 7.3 2.80 8.0 2.89 8.6 2.89 9.1 2.9824.0 6.3 2.71 6.7 2.80 7.3 2.89 7.9 2.98 8.6 2.98 9.1 3.07

100

16.0 8.5 3.24 9.3 3.34 10.1 3.44 11.2 3.55 11.9 3.65 - -18.0 8.4 3.34 9.2 3.44 10.1 3.55 11.1 3.65 11.9 3.75 - -20.0 8.4 3.55 9.1 3.65 10.0 3.75 11.0 3.85 11.7 3.95 12.7 4.0522.0 8.4 3.65 9.1 3.75 10.0 3.85 11.0 3.95 11.7 4.05 12.6 4.1524.0 8.3 3.75 9.1 3.85 9.8 3.95 10.8 4.05 11.5 4.15 12.6 4.26

125

16.0 11.1 4.16 12.0 4.37 12.9 4.47 14.1 4.57 15.0 4.78 - -18.0 11.1 4.26 12.0 4.47 12.9 4.57 14.0 4.78 14.9 4.89 - -20.0 11.1 4.47 11.8 4.68 12.8 4.89 14.0 4.99 14.8 5.09 16.0 5.3022.0 11.1 4.57 11.8 4.78 12.8 4.89 14.0 5.09 14.8 5.20 16.0 5.4124.0 10.9 4.68 11.8 4.89 12.7 5.09 13.9 5.20 14.8 5.41 15.8 5.61

3TW25142-8A

SYMBOLS

AFR: Air flow rate (m3/min)EDB: Entering dry bulb temp. (°CDB)WB: Wet bulb temperature (°CWB)TC: Total cooling capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FHYP

71 AFR 17BF 0.10

100 AFR 24BF 0.14

125 AFR 30BF 0.13

6. Add the following corrections to power input of each model.

Model Supply FHYP

71 V1 0.05W1 0

100 V1 0.05W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

18 • Split - Sky Air • Outdoor Units

Page 21: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FUYP71-125BV1 + RYP71-100L7V1RYP71-125L7W1

Cooling capacity V1/T1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

71

12.0 18.00 6.2 4.9 1.86 6.1 4.8 2.12 5.7 4.7 2.30 5.5 4.6 2.47 5.3 4.5 2.74 4.9 4.2 3.0014.0 20.00 6.6 4.9 1.94 6.5 4.8 2.21 6.0 4.7 2.39 5.9 4.6 2.47 5.5 4.5 2.74 5.3 4.2 3.0016.0 22.00 7.2 5.0 1.94 7.0 4.9 2.21 6.5 4.8 2.39 6.3 4.7 2.56 6.0 4.6 2.83 5.5 4.3 3.0918.0 25.00 7.7 5.2 2.03 7.5 5.0 2.21 7.2 4.9 2.47 6.8 4.8 2.65 6.4 4.6 2.83 6.0 4.5 3.1819.0 27.00 8.0 5.3 2.03 7.7 5.2 2.21 7.3 5.0 2.47 7.1 4.8 2.65 6.6 4.7 2.92 6.2 4.6 3.1819.5 27.00 8.0 5.3 2.03 7.9 5.2 2.21 7.4 5.0 2.47 7.2 4.8 2.65 6.7 4.7 2.92 6.3 4.6 3.1822.0 30.00 8.7 5.4 2.12 8.5 5.3 2.30 8.0 5.2 2.56 7.9 4.9 2.74 7.4 4.8 2.92 6.8 4.6 3.2724.0 32.00 9.4 5.4 2.12 9.1 5.3 2.30 8.6 5.2 2.65 8.4 5.0 2.74 8.0 4.8 3.00 7.4 4.6 3.36

100

12.0 18.00 8.4 7.2 2.76 8.3 7.1 2.96 8.1 6.9 3.37 7.8 6.8 3.58 7.5 6.4 3.98 6.9 6.2 4.3914.0 20.00 8.9 7.2 2.86 8.8 7.1 2.96 8.7 6.9 3.37 8.4 6.8 3.58 7.8 6.4 3.98 7.5 6.2 4.3916.0 22.00 10.1 7.3 2.86 9.8 7.2 3.06 9.1 7.0 3.47 8.9 6.9 3.68 8.5 6.5 4.09 7.8 6.3 4.5018.0 25.00 10.8 7.6 2.86 10.5 7.5 3.06 9.8 7.1 3.47 9.6 7.0 3.68 9.0 6.8 4.09 8.4 6.4 4.6019.0 27.00 11.1 7.7 2.86 10.8 7.6 3.17 10.1 7.2 3.58 10.0 7.1 3.78 9.4 6.9 4.19 8.7 6.5 4.7019.5 27.00 11.2 7.7 2.86 11.0 7.6 3.17 10.3 7.2 3.58 10.1 7.1 3.78 9.5 6.9 4.19 8.8 6.5 4.7022.0 30.00 12.2 7.8 2.96 11.8 7.7 3.17 11.2 7.3 3.68 11.0 7.2 3.88 10.4 7.1 4.29 9.6 6.8 4.7024.0 32.00 13.0 7.9 3.06 12.7 7.8 3.27 11.9 7.5 3.78 11.6 7.3 3.98 11.1 7.2 4.39 10.3 6.9 4.80

125

12.0 18.00 11.1 9.5 3.34 10.8 9.2 3.64 10.0 8.7 3.93 9.7 8.6 4.23 9.2 8.4 4.62 8.6 8.0 5.3114.0 20.00 11.8 9.5 3.44 11.4 9.2 3.64 10.7 8.7 4.03 10.4 8.6 4.32 9.8 8.4 4.72 9.2 8.0 5.3116.0 22.00 12.7 9.6 3.44 12.1 9.3 3.73 11.4 8.8 4.03 11.1 8.7 4.42 10.4 8.5 4.81 9.7 8.1 5.4018.0 25.00 13.3 9.9 3.54 13.0 9.5 3.73 12.1 9.1 4.13 11.8 9.0 4.52 11.2 8.7 4.91 10.4 8.4 5.4019.0 27.00 13.6 10.0 3.64 13.3 9.5 3.83 12.7 9.2 4.23 12.2 9.0 4.52 11.5 8.8 5.01 10.8 8.5 5.5019.5 27.00 13.8 10.0 3.64 13.5 9.5 3.83 12.8 9.2 4.23 12.4 9.1 4.52 11.7 8.8 5.01 11.0 8.5 5.5022.0 30.00 15.1 10.1 3.73 14.6 9.8 3.83 13.7 9.4 4.32 13.4 9.3 4.62 12.9 9.1 5.11 12.0 8.7 5.7024.0 32.00 15.9 10.2 3.73 15.5 9.9 3.93 14.6 9.5 4.42 14.3 9.4 4.72 13.6 9.2 5.21 12.9 9.0 5.80

3TW25142-5A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FUYP

71 AFR 19BF 0.07

100 AFR 29BF 0.07

125 AFR 32BF 0.07

7. Add the following corrections to power input of each model.

Model Supply FUYP

71 V1 0.05W1 0

100 V1 0.05W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

19• Split - Sky Air • Outdoor Units

Page 22: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FUYP71-125BV1 + RYP71-100L7V1RYP71-125L7W1

Heating capacity V1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CWB)EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

71

16.0 6.3 2.04 6.7 2.11 7.4 2.11 8.1 2.19 8.6 2.19 - -18.0 6.3 2.04 6.7 2.11 7.4 2.19 8.0 2.26 8.6 2.26 - -20.0 6.3 2.19 6.7 2.19 7.3 2.26 8.0 2.34 8.6 2.42 9.3 2.4922.0 6.3 2.19 6.7 2.26 7.3 2.34 8.0 2.42 8.6 2.42 9.1 2.4924.0 6.3 2.26 6.7 2.34 7.3 2.42 7.9 2.49 8.6 2.49 9.1 2.57

100

16.0 8.5 2.93 9.3 3.02 10.1 3.11 11.2 3.21 11.9 3.30 - -18.0 8.4 3.02 9.2 3.11 10.1 3.21 11.1 3.30 11.9 3.39 - -20.0 8.4 3.21 9.1 3.30 10.0 3.39 11.0 3.48 11.7 3.57 12.7 3.6622.0 8.4 3.30 9.1 3.39 10.0 3.48 11.0 3.57 11.7 3.66 12.6 3.7524.0 8.3 3.39 9.1 3.48 9.8 3.57 10.8 3.66 11.5 3.75 12.6 3.85

125

16.0 11.1 3.63 12.0 3.81 12.9 3.90 14.1 3.99 15.0 4.17 - -18.0 11.1 3.72 12.0 3.90 12.9 3.99 14.0 4.17 14.9 4.26 - -20.0 11.1 3.90 11.8 4.08 12.8 4.26 14.0 4.35 14.8 4.44 16.0 4.6222.0 11.1 3.99 11.8 4.17 12.8 4.26 14.0 4.44 14.8 4.53 16.0 4.7124.0 10.9 4.08 11.8 4.26 12.7 4.44 13.9 4.53 14.8 4.71 15.8 4.89

3TW25142-11A

SYMBOLS

AFR: Air flow rate (m3/min)EDB: Entering dry bulb temp. (°CDB)WB: Wet bulb temperature (°CWB)TC: Total cooling capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FUYP

71 AFR 19BF 0.07

100 AFR 29BF 0.07

AFR AFR 32BF 0.07

6. Add the following corrections to power input of each model.

Model Supply FUYP

71 V1 0.14W1 0

100 V1 0.03W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

20 • Split - Sky Air • Outdoor Units

Page 23: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FDYMP71-125L7V1 + RYP71-100L7V1RYP71-125L7W1

Cooling capacity V1/T1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

71

12.0 18.00 6.2 4.8 1.82 6.1 4.7 2.08 5.7 4.6 2.25 5.5 4.5 2.43 5.3 4.4 2.69 4.9 4.1 2.9514.0 20.00 6.6 4.8 1.91 6.5 4.7 2.17 6.0 4.6 2.34 5.9 4.5 2.43 5.5 4.4 2.69 5.3 4.1 2.9516.0 22.00 7.2 4.9 1.91 7.0 4.8 2.17 6.5 4.7 2.34 6.3 4.6 2.51 6.0 4.5 2.77 5.5 4.2 3.0318.0 25.00 7.7 5.1 1.99 7.5 4.9 2.17 7.2 4.8 2.43 6.8 4.7 2.60 6.4 4.5 2.77 6.0 4.4 3.1219.0 27.00 8.0 5.2 1.99 7.7 5.1 2.17 7.3 4.9 2.43 7.1 4.7 2.60 6.6 4.6 2.86 6.2 4.5 3.1219.5 27.00 8.0 5.2 1.99 7.9 5.1 2.17 7.4 4.9 2.43 7.2 4.7 2.60 6.7 4.6 2.86 6.3 4.5 3.1222.0 30.00 8.7 5.3 2.08 8.5 5.2 2.25 8.0 5.1 2.51 7.9 4.8 2.69 7.4 4.7 2.86 6.8 4.5 3.2124.0 32.00 9.4 5.3 2.08 9.1 5.2 2.25 8.6 5.1 2.60 8.4 4.9 2.69 8.0 4.7 2.95 7.4 4.5 3.29

100

12.0 18.00 8.4 7.0 2.66 8.3 6.9 2.86 8.1 6.7 3.26 7.8 6.6 3.45 7.5 6.2 3.85 6.9 6.0 4.2414.0 20.00 8.9 7.0 2.76 8.8 6.9 2.86 8.7 6.7 3.26 8.4 6.6 3.45 7.8 6.2 3.85 7.5 6.0 4.2416.0 22.00 10.1 7.1 2.76 9.8 7.0 2.96 9.1 6.8 3.35 8.9 6.7 3.55 8.5 6.3 3.95 7.8 6.1 4.3418.0 25.00 10.8 7.4 2.76 10.5 7.3 2.96 9.8 6.9 3.35 9.6 6.8 3.55 9.0 6.6 3.95 8.4 6.2 4.4419.0 27.00 11.1 7.5 2.76 10.8 7.4 3.06 10.1 7.0 3.45 10.0 6.9 3.65 9.4 6.7 4.04 8.7 6.3 4.5419.5 27.00 11.2 7.5 2.76 11.0 7.4 3.06 10.3 7.0 3.45 10.1 6.9 3.65 9.5 6.7 4.04 8.8 6.3 4.5422.0 30.00 12.2 7.6 2.86 11.8 7.5 3.06 11.2 7.1 3.55 11.0 7.0 3.75 10.4 6.9 4.14 9.6 6.6 4.5424.0 32.00 13.0 7.7 2.96 12.7 7.6 3.16 11.9 7.3 3.65 11.6 7.1 3.85 11.1 7.0 4.24 10.3 6.7 4.64

125

12.0 18.00 11.1 9.1 3.36 10.8 8.8 3.66 10.0 8.3 3.96 9.7 8.2 4.25 9.2 8.0 4.65 8.6 7.6 5.3414.0 20.00 11.8 9.1 3.46 11.4 8.8 3.66 10.7 8.3 4.06 10.4 8.2 4.35 9.8 8.0 4.75 9.2 7.6 5.3416.0 22.00 12.7 9.2 3.46 12.1 8.9 3.76 11.4 8.4 4.06 11.1 8.3 4.45 10.4 8.1 4.85 9.7 7.7 5.4418.0 25.00 13.3 9.5 3.56 13.0 9.1 3.76 12.1 8.7 4.15 11.8 8.6 4.55 11.2 8.3 4.95 10.4 8.0 5.4419.0 27.00 13.6 9.6 3.66 13.3 9.1 3.86 12.7 8.8 4.25 12.2 8.6 4.55 11.5 8.4 5.04 10.8 8.1 5.5419.5 27.00 13.8 9.6 3.66 13.5 9.1 3.86 12.8 8.8 4.25 12.4 8.7 4.55 11.7 8.4 5.04 11.0 8.1 5.5422.0 30.00 15.1 9.7 3.76 14.6 9.4 3.86 13.7 9.0 4.35 13.4 8.9 4.65 12.9 8.7 5.14 12.0 8.3 5.7424.0 32.00 15.9 9.8 3.76 15.5 9.5 3.96 14.6 9.1 4.45 14.3 9.0 4.75 13.6 8.8 5.24 12.9 8.6 5.84

3TW25142-3A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR (m3/min) x (1-BF) x (DB*-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FDYMP

71 AFR 19BF 0.11

100 AFR 27BF 0.2

125 AFR 35BF 0.14

7. Add the following corrections to power input of each model.

Model Supply FDYMP

71 V1 0.08W1 0

100 V1 0.1W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

21• Split - Sky Air • Outdoor Units

Page 24: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FDYP125B7V1 + RYP125L7W1

Cooling capacity V1/T1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

125

12.0 18.0 11.1 10.4 3.46 10.8 10.1 3.76 10.0 9.6 4.07 9.7 9.5 4.37 9.2 9.3 4.78 8.6 8.9 5.4914.0 20.0 11.8 10.4 3.56 11.4 10.1 3.76 10.7 9.6 4.17 10.4 9.5 4.48 9.8 9.3 4.88 9.2 8.9 5.4916.0 22.0 12.7 10.5 3.56 12.1 10.2 3.87 11.4 9.7 4.17 11.1 9.6 4.58 10.4 9.4 4.99 9.7 9.0 5.6018.0 25.0 13.3 10.8 3.66 13.0 10.4 3.87 12.1 10.0 4.27 11.8 9.9 4.68 11.2 9.6 5.09 10.4 9.3 5.6019.0 27.0 13.6 10.9 3.76 13.3 10.4 3.97 12.7 10.1 4.37 12.2 9.9 4.68 11.5 9.7 5.19 10.8 9.4 5.7019.5 27.0 13.8 10.9 3.76 13.5 10.4 3.97 12.8 10.1 4.37 12.4 10.0 4.68 11.7 9.7 5.19 11.0 9.4 5.7022.0 30.0 15.1 11.0 3.87 14.6 10.7 3.97 13.7 10.3 4.48 13.4 10.2 4.78 12.9 10.0 5.29 12.0 9.6 5.9024.0 32.0 15.9 11.1 3.87 15.5 10.8 4.07 14.6 10.4 4.58 14.3 10.3 4.88 13.6 10.1 5.39 12.9 9.9 6.00

3TW25202-6A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB) (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR(m3/min) x (1-BF) x (DB°-EDB)/860Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FDYP

125 AFR 45BF 0.25

FDYP125B7V1 + RYP125L7W1

Heating capacity V1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

125

16.0 11.5 3.76 12.5 3.95 13.4 4.04 14.7 4.13 15.7 4.32 - -18.0 11.5 3.85 12.5 4.04 13.4 4.13 14.6 4.32 15.6 4.42 - -20.0 11.5 3.95 12.3 4.13 13.4 4.23 14.6 4.42 15.6 4.60 17.0 4.7021.0 11.5 4.04 12.3 4.23 13.4 4.42 14.6 4.51 15.5 4.60 16.7 4.7922.0 11.5 4.13 12.3 4.32 13.4 4.42 14.6 4.60 15.5 4.70 16.7 4.8924.0 11.3 4.23 12.3 4.42 13.3 4.60 14.5 4.70 15.5 4.89 16.4 5.07

3TW25202-12

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB) (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FDYP

125 AFR 45BF 0.25

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

22 • Split - Sky Air • Outdoor Units

Page 25: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FDYP200∼250B7V1 + RYP200∼250B7W1

Cooling capacity V1: 1∼230V [50Hz]W1: 3∼400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

20 25 32 35 40 46TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI

RYP200

12.0 18.0 17.5 14.8 6.49 16.8 14.3 6.98 15.8 13.7 7.83 15.4 13.4 8.23 14.8 13.0 9.02 14.1 12.6 10.0814.0 20.0 18.7 14.9 6.59 17.9 14.4 7.08 16.9 13.8 7.94 16.5 13.6 8.36 15.9 13.2 9.15 15.1 12.7 10.2216.0 22.0 20.0 15.0 6.68 19.2 14.5 7.19 18.1 13.9 8.06 17.7 13.7 8.49 17.0 13.3 9.29 16.2 12.8 10.3718.0 25.0 21.3 15.9 6.79 20.4 15.4 7.31 19.3 14.8 8.19 18.9 14.6 8.62 18.2 14.2 9.43 17.4 13.7 10.5419.0 27.0 21.9 16.8 6.84 21.1 16.3 7.37 20.0 15.7 8.26 19.5 15.5 8.69 18.8 15.1 9.51 17.9 14.6 10.6222.0 30.0 24.1 16.8 7.02 23.2 16.3 7.56 22.0 15.8 8.47 21.5 15.5 8.92 20.7 15.1 9.75 19.8 14.7 10.8924.0 32.0 25.6 16.8 7.15 24.6 16.4 7.70 23.4 15.8 8.63 22.9 15.5 9.09 22.1 15.1 9.93 21.1 14.6 11.07

RYP250

12.0 18.0 22.4 19.1 7.62 21.5 18.5 8.20 20.2 17.7 9.19 19.7 17.3 9.67 18.9 16.8 10.58 18.0 16.2 11.8314.0 20.0 24.0 19.2 7.73 23.0 18.6 8.31 21.7 17.8 9.32 21.2 17.5 9.82 20.3 17.0 10.73 19.4 16.4 12.0016.0 22.0 25.6 19.3 7.84 24.6 18.7 8.45 23.2 17.9 9.46 22.7 17.6 9.97 21.8 17.1 10.90 20.8 16.5 12.1718.0 25.0 27.2 20.5 7.97 26.2 19.9 8.58 24.8 19.2 9.61 24.2 18.8 10.12 23.3 18.3 11.06 22.3 17.7 12.3719.0 27.0 28.1 21.7 8.03 27.0 21.1 8.65 25.6 20.3 9.69 25.0 20.0 10.20 24.1 19.5 11.16 23.0 18.9 12.4622.0 30.0 30.9 21.6 8.24 29.7 21.1 8.87 28.2 20.3 9.94 27.6 20.0 10.47 26.5 19.5 11.45 25.4 18.9 12.7824.0 32.0 32.8 21.7 8.39 31.6 21.1 9.03 30.0 20.4 10.13 29.4 20.0 10.67 28.3 19.5 11.65 27.1 18.9 13.00

3TW23632-1A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB) (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC and SHC are shown by kW

NOTES1. Ratings shown are net capacities which include a deduction for indoor fan

motor heat2. Shows nominal capacities3. SHC is based on each EWB and EDB

SHC* = SHC correction for other dry bulb= 0.29 x 60 x AFR(m3/min) x (1-BF) x (DB°-EDB)Add SHC* to SHC if SHC > TC, then TC equal SHC

4. Direct interpolation is permissible. Do not extrapolate.5. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

6. Air flow rate and BF are tabulated below.

Model FDYP200 FDYP250AFR 69 89BF 0.25 0.25

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

23• Split - Sky Air • Outdoor Units

Page 26: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FDYP200∼250B7V1 + RYP200∼250B7W1

Heating capacity V1: 1∼230V [50Hz]W1: 3∼400V [50Hz]

OutdoorIndoor Outdoor temperature (°CDB)

EWB(°C)

EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

RYP200

9.0 16.0 15.1 6.42 16.7 6.47 19.6 6.76 23.4 7.16 26.3 7.50 30.3 7.9911.0 18.0 14.8 6.58 16.6 6.65 19.5 6.95 23.2 7.37 26.1 7.72 30.1 8.2312.0 20.0 14.6 6.76 16.3 6.84 19.3 7.15 23.1 7.59 26.0 7.95 30.0 8.4913.0 21.0 14.5 6.86 16.2 6.92 19.3 7.25 23.0 7.70 26.0 8.08 29.9 8.6214.0 22.0 14.4 6.96 16.0 7.02 19.3 7.36 23.0 7.82 25.9 8.21 29.8 8.7615.0 24.0 14.2 7.16 15.7 7.23 19.2 7.59 22.9 8.08 25.8 8.46 29.7 9.05

RYP250

9.0 16.0 17.6 7.41 19.5 7.47 22.9 7.81 27.3 8.27 30.8 8.66 35.4 9.2211.0 18.0 17.3 7.60 19.4 7.68 22.7 8.02 27.1 8.51 30.6 8.91 35.2 9.5012.0 20.0 17.1 7.81 19.1 7.89 22.6 8.26 27.0 8.76 30.4 9.18 35.0 9.8013.0 21.0 16.9 7.92 18.9 7.99 22.6 8.37 26.9 8.89 30.3 9.32 34.9 9.9514.0 22.0 16.8 8.03 18.7 8.10 22.5 8.49 26.9 9.03 30.3 9.47 34.9 10.1115.0 24.0 16.6 8.27 18.4 8.34 22.5 8.76 26.8 9.32 30.2 9.77 34.8 10.44

3TW23632-2A

SYMBOLS

AFR: Air flow rate (m3/min)BF: Bypass factorEWB: Entering wet bulb temp. (°CWB)EDB: Entering dry bulb temp. (°CDB)DB*: Dry bulb temp. (°CDB) (°CDB)TC: Total cooling capacity (kW)SHC: Sensible heating capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities which include a deduction for indoor fan

motor heat2. Shows nominal capacities3. Capacities are based on following conditions:

Corresponding refrigerant piping length: 7.5 mLevel difference: 0 mOutdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FDYP200 FDYP250AFR 69 89BF 0.25 0.25

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

24 • Split - Sky Air • Outdoor Units

Page 27: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

FDYMP71-125L7V1 + RYP71-100L7V1RYP71-125L7W1

Heating capacity V1: 230V [50Hz]W1: 400V [50Hz]

OutdoorIndoor Outdoor temperature (°CWB)EDB(°C)

-10 -5 0 6 10 15TC PI TC PI TC PI TC PI TC PI TC PI

71

16.0 6.3 2.17 6.7 2.25 7.4 2.25 8.1 2.33 8.6 2.33 - -18.0 6.3 2.17 6.7 2.25 7.4 2.33 8.0 2.41 8.6 2.41 - -20.0 6.3 2.33 6.7 2.33 7.3 2.41 8.0 2.49 8.6 2.57 9.3 2.6522.0 6.3 2.33 6.7 2.41 7.3 2.49 8.0 2.57 8.6 2.57 9.1 2.6524.0 6.3 2.41 6.7 2.49 7.3 2.57 7.9 2.65 8.6 2.65 9.1 2.73

100

16.0 8.5 3.22 9.3 3.32 10.1 3.42 11.2 3.52 11.9 3.62 - -18.0 8.4 3.32 9.2 3.42 10.1 3.52 11.1 3.62 11.9 3.72 - -20.0 8.4 3.52 9.1 3.62 10.0 3.72 11.0 3.82 11.7 3.92 12.7 4.0222.0 8.4 3.62 9.1 3.72 10.0 3.82 11.0 3.92 11.7 4.02 12.6 4.1224.0 8.3 3.72 9.1 3.82 9.8 3.92 10.8 4.02 11.5 4.12 12.6 4.22

125

16.0 11.4 3.76 12.4 3.95 13.4 4.04 14.6 4.13 15.5 4.32 - -18.0 11.4 3.85 12.4 4.04 13.4 4.13 14.5 4.32 15.5 4.42 - -20.0 11.4 4.04 12.2 4.23 13.3 4.42 14.5 4.51 15.4 4.60 16.6 4.7922.0 11.4 4.13 12.2 4.32 13.3 4.42 14.5 4.60 15.4 4.70 16.6 4.8924.0 11.3 4.23 12.2 4.42 13.2 4.60 14.4 4.70 15.4 4.89 16.3 5.07

3TW25142-14A

SYMBOLS

AFR: Air flow rate (m3/min)EDB: Entering dry bulb temp. (°CDB)WB: Wet bulb temperature (°CWB)TC: Total cooling capacity (kW)PI: Power input (kW)

(comp.+indoor+outdoor fan motor)

Caution:TC is shown by kW

NOTES1. Ratings shown are net capacities.

Influence of fan motor heat is included.2. Shows nominal capacities3. Capacities are based on following conditions:

Outdoor air : 85 % RH. however, the condition on nominal capacity is7° CDB/6° CWB (heating)Corresponding refrigerant piping length: 7.5 mLevel difference: 0 m

4. Direct interpolation is permissible. Do not extrapolate.5. Air flow rate and BF are tabulated below.

Model FDYMP

71 AFR 19BF 0.11

100 AFR 27BF 0.2

125 AFR 35BF 0.14

6. Add the following corrections to power input of each model.

Model Supply FDYMP

71 V1 0W1 0

100 V1 0.09W1 0

125 W1 0

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

3 Capacity tables

13

25• Split - Sky Air • Outdoor Units

Page 28: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

3 Capacity tables3-1 Cooling capacity in low latent heat application

Method and illustration

The capacity will be increased when the dip switch DS2-4, mounted on the outdoor PCB, is set to ON.

Detail dip switch setting

OFF (factory setting)

ON

OFF

ON

OFF

ON

Capacity result at low temperatureThe capacity increases when outdoor temperature drops below 21°C as indicated on table below

Dip switch OFF(factory setting) Dip switch ON

Capacity low temperature 100%* 150 ∼ 200%

*This is a relative comparisson to indicate an increase of 50 to 100% capacity with the dipswitch ON.

Caution+ Finally the capacity result will depend on the total condition of the installation site.

This is the responsibility of the customer.+ There is additional limitation for the relative humidity when operating this switch.

Finally, it will depend on the total condition of the installation site and is responsibility of the customer.+ Evaluation is necessary for each installation site by a professional responsible installer.+ Only use the switch for capacity increase in the area indicated on the graph of page 4.+ Do not set the switch in combination with the option EKRPER, this is only for use of Daikin indoor units.

Reason for limitationWhen operating with switch ON, there will be a change of freeze protection control see table on next page. By this there will be some risk of+ Ice building up at indoor heat exchanger.+ Water blown off from the unit into the room.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

13

3-1

26 • Split - Sky Air • Outdoor Units

Page 29: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

3 Capacity tables3-2 Details about software change

B-typeL-type

Dip switch OFF (factory setting) Dip switch ON

Function: capacity increase at low temperature Not present Not activated Activated

Freeze protection (partly)IN condition

+ Intelligent control+ Indoor decision+ 25min integrated coil temp ≤-1°C+ coil temp ≤’’A’’°C continuous 1min+ 20min continuous comp operation time+ coil temp ≤-1°C continuous 1min

’’A’’: depend on each indoor typeEx.: FHY...-3°C

FHYC...-5°C

+ Indoor decision+ 25min integrated coil temp ≤-1°C+ coil temp ≤’’A’’°C continuous 1min+ 20min continuous comp operation time+ coil temp ≤-1°C continuous 1min

’’A’’: depend on each indoor typeEx.:FHY...-3°C

FHYC...-5°C

+ 25min integrated coil temp ≤-1°C+ coil temp ≤’’A’’°C continuous 1min+ 20min continuous comp operation time+ coil temp ≤-1°C continuous 1min

’’A’’: depend on each indoor typeEx.:FHY...-3°C

FHYC...-5°C

OUT condition Coil temp >10°C continuous ≥ 10min X Coil temp >7°C continuous ≥ 3min

Discharge temp (TK) control limitation

TK acceptable areaAir

TK acceptable areaAir >12°C:NormalAir≤ 12°C:

TK acceptable area

Only use the switch for capacity increase in thisarea.

Humidity limitation

HOR

H&HOR

& H H HOR

&

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

•PairApplication

•R-407C•RYP71-125L7V1/W

1∼RYP200-250B7W1

3Capacity

tables3-2

Detailsaboutsoftwarechange133-2

27

• Split - Sky Air • Outdoor Units

•Split-

SkyA

ir•

OutdoorU

nits

Page 30: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

4 Dimensional drawings

unit (mm)

1 Gas pipe connection J15.9 flare2 Liquid pipe connection - J9.5 flare3 Service port (in the unit)4 Grounding terminal M5 (in switch box)5 Refrigerant piping intake6 Power supply wiring intake (knock hole J34)7 Control wiring intake (knock hole J27)8 Drain outlet

RYP71L7Hole for anchor bolt4-M12

3TW25144-1

unit (mm)

1 Gas pipe connection J19.1 flare2 Liquid pipe connection - J9.5 flare3 Service port (in the unit)4 Grounding terminal M5 (in switch box)5 Refrigerant piping intake6 Power supply wiring intake (knock hole J34)7 Control wiring intake (knock hole J27)8 Drain outlet

RYP100L7Hole for anchor bolt4-M12

3TW25154-1

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

14

28 • Split - Sky Air • Outdoor Units

Page 31: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

unit (mm)

1 Gas pipe connection J19.1 flare2 Liquid pipe connection - J9.5 flare3 Service port (in the unit)4 Grounding terminal M5 (in switch box)5 Refrigerant piping intake6 Power supply wiring intake (knock hole J34)7 Control wiring intake (knock hole J27)8 Drain outlet

RYP125L7

Hole for anchor bolt4-M12

3TW25204-1

unit (mm)

1 Liquid piping connection opening2 Gas piping connection opening3 Ground terminal4 Power supply wiring outlet

RYP200B7

Knock hole for lower piping

3TW21484-1C

(Distance between anchor bolt holes)

Pipes connected to theside

Foundation hole

(pipes connected tothe front)

NOTE: The dimensions marked withz refer todistances after fixing the accessory pipes.

(Dist

ance

betw

een

anch

orbo

ltho

les)

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

4 Dimensional drawings

14

29• Split - Sky Air • Outdoor Units

Page 32: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

unit (mm)

1 Liquid piping connection opening2 Gas piping connection opening3 Ground terminal4 Power supply wiring outlet

RYP250B7

Knock hole for lower piping

3TW21494-1C

(Distance between anchor bolt holes)

Pipes connected to theside

Foundation hole

(pipes connected tothe front)

NOTE: The dimensions marked withz refer todistances after fixing the accessory pipes.

(Dist

ance

betw

een

anch

orbo

ltho

les)

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

4 Dimensional drawings

14

30 • Split - Sky Air • Outdoor Units

Page 33: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

5 Operation range

RYP71-125L7

3TW25143-1A

Heating

Cooling

Indoor temp. (°CWB)

Out

door

tem

p.(°

CDB)

Allo

wab

lera

nge

ofop

erat

ion

(pul

l-dow

n)

Indoor temperature (°CDB)

Out

door

tem

p.(°

CWB)

Allo

wab

lera

nge

ofop

erat

ion

(war

min

g-up

)

Model name

RYP71L7V1 RYP100L7V1 RYP125L7W1

RYP71L7W1 RYP100L7W1

Notes:- Depending on operation and installation conditions, the indoor unit can change over to

freeze-up operation (indoor de-icing).- To reduce the freeze-up operation (indoor de-icing) frequency, it is recommended to install

the outdoor unit in a location not exposed to wind.

Ope

ratio

nra

nge

Ope

ratio

nra

nge

RYP200-250B7

3TW23633-1

Heating

Cooling

Indoor temp. (°CWB)

Out

door

tem

p.(°

CDB)

Allo

wab

lera

nge

ofop

erat

ion

(pul

l-dow

n)

Indoor temperature (°CDB)

Out

door

tem

p.(°

CWB)

War

min

gup

perio

d

Notes:The graph is based on the following conditions:1. Equivalent piping length 70 m2. Level difference 30 m3. Indoor air flow rate 72m3/min (200 class)

90m3/min (250 class)

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

15

31• Split - Sky Air • Outdoor Units

Page 34: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

6 Piping diagrams

RYP71L7

3TW25145-1

Indoor unit

Field pipingJ15.9 C122OT-O

Field pipingJ9.5 C122OT-O

Low pressureswitch

Heat exchanger

Filter

Stop valve(with service port 1/4 ’ flare)

Solenoid valve

Filter

Electronic expansionvalve

Filter

4-way valve

Compressor

Receiver

Service port1/4’’

Heat exchanger

Muffler

One way valve

One way valve

High pressureswitch

One way valve

Filter

Outdoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

HeatingCooling

One way valve

One way valve

StrainerService port

1/4’’

RYP100-125L7

3TW25155-1

Indoor unit

Field pipingJ15.9 C122OT-O

Field pipingJ9.5 C122OT-O

Low pressureswitch

Heat exchanger

Filter

Stop valve(with service port 1/4 ’ flare)

Solenoid valve

Filter

Electronic expansionvalve

Filter

4-way valve

Compressor

Receiver

High pressureswitch

Service port1/4’’

Heat exchanger

Muffler

One way valve

One way valve

One way valve

One way valve

Filter

Outdoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

HeatingCooling

One way valve

Strainer

Service port1/4’’

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

16

32 • Split - Sky Air • Outdoor Units

Page 35: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

RYP200-250B7

3TW23635-1

Indoor unit

Field piping •B

Field piping •ALow pressure

switch

Indoor heat exchanger

Stop valve(with service port 1/4 ’ flare)

Solenoid valve

Electronic expansionvalve Filter

4-way valve

Compressor

Receiver

High pressureswitch

Service port1/4’’

Outdoor heat exchanger

Muffler

One way valve

One way valve

One way valve

One way valve

Filter

Outdoor unit

O Check valve L Flare connection M Screw connection N Flange connection Z Pinched pipe P Spinned pipe

Filter

Propeller fan

Fan

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

6 Piping diagrams

16

33• Split - Sky Air • Outdoor Units

Page 36: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

7 Wiring diagrams

2TW25146-1

RYP71-100L7V1

A1P Printed circuit boardBS1 Push button (forced defrost-pump down)C1R Capacitor (M1F)C3R Capacitor (M1C)C4 Starting capacitor (M1C)DS1, DS2 Selector switchF1U, F2U Fuse (250V, 10A,jB )F3U Field fuseHAP Light emitting diode (service monitor green)

K1M Magnetic contactor (M1C)K1R Magnetic relay (K1M)K3R Magnetic relay (Y1S)K4R Magnetic relay (Y2S)K8R,K9R,K10R Magnetic relay (M1F)K11R Starting relayM1C Motor compressorM1F Motor fan 1

Q1M Thermo switch (M1F)Q3E Earth leak detectorR1T Thermistor (air)R2T Thermistor (coil)R3T Thermistor (discharge pipe)R4C ResistorRC Signal receiver circuitS1PH Pressure switch (high)

S1LP Pressure switch (low)SD Safety devices inputT1A Current transformerT1R Transformer (220-240V/24.9V)TC Signal transmission circuitX1M,X2M Terminal stripY1E Expansion valve (electronic type)Y1S 4-way valveY2S Solenoid valve

Indoor

NOTES:

1. Confirm the method of setting the selectorswitches by service. When the unit is shipped byfactory all switches are set to be off.

2. Do not operate the unit by short-circuiting S1LPIt will cause compressor failure.

g Field wiringD : TerminalF : Connector„ : Wire clampb : Protective earth (screw)L : LiveN : Neutral

ColoursBLK: Black/ BLU: Blue/ WHT: White/RED: Red/ ORG: Orange/ YLW:Yellow

Switch box(Outdoor)

Outdoor

ON

OFF

ON

OFF

Position ofcompressorterminal

Wire entrance

NOTE 1

2TW25186-1

RYP71-100L7W1

A1P Printed circuit boardBS1 Push button (forced defrost-pump down)C1R Capacitor (M1F)DS1, DS2 Selector switchF1U, F2U Fuse (250V, 10A,jB )F3U Field fuseHAP Light emitting diode (service monitor green)K1M Magnetic contactor (M1C)

K1R Magnetic relay (K1M)K3R Magnetic relay (Y1S)K4R Magnetic relay (Y2S)K8R,K9R,K10R Magnetic relay (M1F)M1C Motor compressorM1F Motor fan 1PRC Phase reverse circuitQ1M Thermo switch (M1F)

Q3E Earth leak detectorR1T Thermistor (air)R2T Thermistor (coil)R3T Thermistor (discharge pipe)RC Signal receiver circuitS1PH Pressure switch (high)S1LP Pressure switch (low)SD Safety devices inputT1A Current transformer

T1R Transformer (220-240V/24.9V)TC Signal transmission circuitX1M,X2MX3M

Terminal strip

Y1E Expansion valve (electronic type)Y1S 4-way valveY2S Solenoid valve

Indoor

NOTES:

1. Do not operate the unit by short-circuiting S1LPIt will cause compressor failure.

2. Confirm the method of setting the selector switches byservice. When the unit is shipped by factory all switchesare set to be off.

g Field wiringD : TerminalF : Connector„ : Wire clampb : Protective earth (screw)L : LiveN : Neutral

ColoursBLK: Black/ BLU: Blue/ WHT: White/RED: Red/ ORG: Orange/ YLW:Yellow

Switch box(Outdoor)

Outdoor

ON

OFF

ON

OFF

Position ofcompressorterminal

Wire entrance

NOTE 1

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

17

34 • Split - Sky Air • Outdoor Units

Page 37: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

2TW25196-1

RYP125L7W1

A1P Printed circuit boardBS1 Push button (forced defrost-pump down)C1R Capacitor (M1F)C2R Capacitor (M2F)DS1, DS2 Selector switchF1U, F2U Fuse (250V, 10A,jB )F3U Field fuseHAP Light emitting diode (service monitor green)K1M Magnetic contactor (M1C)

K1R Magnetic relay (K1M)K3R Magnetic relay (Y1S)K4R Magnetic relay (Y2S)K5R,K6R,K7R Magnetic relay (M2F)K8R,K9R,K10R Magnetic relay (M1F)M1C Motor compressorM1F Motor fan 1M2F Motor fan 2PRC Phase reverse circuit

Q1M Thermo switch (M1F)Q2M Thermo switch (M2F)Q3E Earth leak detectorR1T Thermistor (air)R2T Thermistor (coil)R3T Thermistor (discharge pipe)RC Signal receiver circuitS1PH Pressure switch (high)S1LP Pressure switch (low)

SD Safety devices inputT1A Current transformerT1R Transformer (220-240V/24.9V)TC Signal transmission circuitX1M,X2MX3M

Terminal strip

Y1E Expansion valve (electronic type)Y1S 4-way valveY2S Solenoid valve

Indoor

NOTES:

1. Do not operate the unit by short-circuiting S1LPIt will cause compressor failure.

2. Confirm the method of setting the selector switches byservice. When the unit is shipped by factory all switchesare set to be off.

g Field wiringD : TerminalF : Connector„ : Wire clampb : Protective earth (screw)L : LiveN : Neutral

ColoursBLK: Black/ BLU: Blue/ WHT: White/RED: Red/ ORG: Orange/ YLW:Yellow

Switch box(Outdoor)

Outdoor

ON

OFF

ON

OFF

Position ofcompressorterminal

Wireentrance

NOTE 1

2TW23636-1B

RYP200-250B7W1

A1P,A2P,A3P Printed circuit boardBS1 Push button (forced defrost-pump down)C1R,C2R Capacitor (M1F-M2F)DS1 Selector switch (defrost)DS2 Selector switch (various see PCB)DS3 Selector switch (emergency)F1C Overcurrent relayF1U,F2U Fuse (250V, 10A)F3U Field fuse

HAP Light emitting diode (service monitor green)H1P,H2P Light emitting diode (service monitor red)J1HC Crankcase heaterK1M Magnetic contactor (M1C)M1C Motor (compressor)M1F,M2F Motor (fan)PRC Phase reverse circuitQ1L,Q2L Thermo switch (M1F)Q3E Earth leak detector

R1T Thermistor (air)R2T Thermistor (coil)R3T Thermistor (discharge pipe)RC Signal receiver circuitRyC Magnetic relay (K1M)RyCH Magnetic relay (J1HC)RyF1-2 Magnetic relay (M1F-M2F)RyR Magnetic relay (Y1S)RyS Magnetic relay (Y1R)

S1LP Pressure switch (low)S1PH Pressure switch (high)SD Safety devices inputT1R Transformer (230V/20.1V)TC Signal transmission circuitX1M Terminal stripY1E Expansion valveY1R 4-way valveY1S Solenoid valve

IndoorNote:

Do not operate the unit by short-circuiting S1LP

g Field wiringD TerminalF : Connector„ : Wire clampb : Protective earth (screw)L : LiveN : Neutral

ColoursBLK: Black/ BLU: Blue/ WHT: White/RED: Red/ ORG: Orange/ YLW:Yellow

Switch box

Outdoor

L1-RED L2-WHT L3-BLK N-BLU

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

7 Wiring diagrams

17

35• Split - Sky Air • Outdoor Units

Page 38: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

4TW25149-6

RYP71-125L7

Field wire

Symbol explication

I = PairII = TwinIII = TripleM = MasterS = Slave1 = Earth leak detector2 = Fuse3 = Remote control

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

7 Wiring diagrams

17

36 • Split - Sky Air • Outdoor Units

Page 39: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

8 Sound level8-1 Sound level data

Soun

dpr

essu

rele

vel(

dB)

Soun

dpr

essu

rele

vel(

dB)

Model

Sound pressure levelSound power level (H)

(cooling)230V, 50Hz

Measuring locationH (cooling) H (heating)

RYP71L7 50 52 63

RYP100L7 53 56 66

RYP125L7 53 56 67

RYP200B7 57 57 77

RYP250B7 57 57 77

Octave band center frequency (Hz) Octave band center frequency (Hz)

RYP71L7 RYP71L7

3TW25147-2A3TW25147-1A

8-2 Sound pressure spectrum

NOTES

1 Data is valid at free field condition2 Data is valid at nominal conditions.3 dB(A) = A-weighted sound pressure level (A-scale according

to IEC)4 Reference acoustic pressure 0dB = 20µPa5 Curve for RYP71-125L7V1/W1 in cooling mode

Cooling Heating

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

18

8-1

37• Split - Sky Air • Outdoor Units

Page 40: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

Soun

dpr

essu

rele

vel[

dB(A

)]

Soun

dpr

essu

rele

vel[

dB(A

)]

Octave band center frequency (Hz) Octave band center frequency (Hz)

RYP100L7 RYP100L7

RYP125L7 RYP125L7

Soun

dpr

essu

rele

vel[

dB(A

)]

Soun

dpr

essu

rele

vel[

dB(A

)]

Octave band center frequency (Hz) Octave band center frequency (Hz)

3TW25157-1A 3TW25157-2A

3TW25207-1A 3TW25207-2A

Cooling Heating

Cooling Heating

NOTES

1 Data is valid at free field condition2 Data is valid at nominal conditions.3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)4 Reference acoustic pressure 0dB = 20µPa5 Curve for RYP71-125L7V1/W1 in cooling mode

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

8 Sound level8-2 Sound pressure spectrum

18

8-2

38 • Split - Sky Air • Outdoor Units

Page 41: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

Soun

dpr

essu

rele

vel[

dB(A

)]

Soun

dpr

essu

rele

vel[

dB(A

)]Octave band center frequency (Hz) Octave band center frequency (Hz)

RYP200B7 RYP200B7

RYP250B7W1 RYP250B7W1

Soun

dpr

essu

rele

vel[

dB(A

)]

Soun

dpr

essu

rele

vel[

dB(A

)]

Octave band center frequency (Hz) Octave band center frequency (Hz)

3TW23637-1 3TW23637-1

3TW23647-1 3TW23647-1

Cooling Heating

Cooling Heating

NOTES

1 Data is valid at free field condition2 dB(A) = A-weighted sound pressure level (A-scale according to

IEC)3 Reference acoustic pressure 0dB = 20Pa

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

8 Sound level8-2 Sound pressure spectrum

18

8-2

39• Split - Sky Air • Outdoor Units

Page 42: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

Soun

dpr

essu

rele

vel[

dB(A

)]

Soun

dpr

essu

rele

vel[

dB(A

)]

Octave band center frequency (Hz) Octave band center frequency (Hz)

RYP71L7 RYP100L7

RYP125L7

Soun

dpr

essu

rele

vel[

dB(A

)]

Octave band center frequency (Hz)

3TW25147-3 3TW25157-3

3TW25207-3

Cooling Cooling

Cooling

NOTES

1 Data is valid at free field condition2 Data is valid at nominal conditions.3 dB(A) = A-weighted sound pressure level (A-scale according to IEC)4 Reference acoustic pressure 0dB = 20µPa5 Curve for RYP71-125L7V1/W1 in cooling mode

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

8 Sound level8-2 Sound pressure spectrum

18

8-2

40 • Split - Sky Air • Outdoor Units

Page 43: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

9 Accessories9-1 Standard accessories

RYP200-250B7

Available options for RYP71-125L7V1,W1

Name of option RYP71L RYP100L RYP125L

Central drain plug KKPJ5F180

Refrigerant branch pipingTwin KHRQ22M20TA7

Triple ∼ KHRP127HB7

Connection to Air handling unit EKRPER

3TW25149-1A3TW23189-1AAvailable options for RYP200-250B7W1

Option RYP200B7 RYP250B7

Fan motor size up NFM22C5

Refnet KHRQ22M20TA7*

Refnet KHRQ22M64T7*

Refnet KHRP127HB7*

3TW23619-2A

* Table with possible indoor combinations = combination matrix 3TW23619-1A See chapter RYP-L7/B7, twin/triple/double twin application

Gas pipes

9-2 Optional accessories

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

19

9-1

41• Split - Sky Air • Outdoor Units

Page 44: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

9 Accessories9-2 Optional accessories

Refnet kits overview

Liquid side joint Suction gas side joint

Suction gas side headerLiquid side header

Reducers - Expanders

I.D. J12.70I.D. J9.52 I.D. J15.90 I.D. J12.70

I.D. J19.10I.D. J22.20 I.D. J25.40 I.D. J25.40

I.D. J26.60

I.D. J9.52

I.D. J15.90

I.D. J12.70

I.D. J9.52 (3x)

I.D. J6.35 (3x)

I.D. J12.70 (2x)

I.D. J15.90 (2x)

I.D. J19.10 (2x)

I.D. J29.60

I.D. J19.10

I.D. J25.40

I.D. J12.70

I.D. J15.90

I.D. J12.70I.D. J9.52

I.D. J9.52 I.D. J6.35

I.D. J6.35I.D. J9.52

I.D. J19.10 I.D. J22.20

I.D. J15.90

I.D. J15.90I.D. J12.70

I.D. J15.90

I.D. J19.10

I.D. J12.70 I.D. J15.90

I.D. J12.70 I.D. J9.52

I.D. J6.35

I.D. J 15.90

I.D. J6.35I.D. J12.70

I.D. J31.60 I.D. J29.60

I.D. J25.40I.D. J15.90I.D. J19.10

I.D. J12.70

I.D. J15.90I.D. J19.10

I.D. J25.40

KHRQ

22M

20TA

7KH

RQ22

M64

T7KH

RR12

7HB7

1TW25799-1

1TW25799-1D

O.D. J9.52 I.D. J6.35j5

j5 2 x

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

19

9-2

42 • Split - Sky Air • Outdoor Units

Page 45: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

10 Center of gravity

11 Safety device settings

RYP71-125L7

ModelSafety device RYP71L7 RYP100L7 RYP125L7

Fan motor thermal protector Off 135 ±5°COn 95 ±15°C

HPS Off 3.30 ± 0.1 MpaOn 2.55 ± 0.15 Mpa

LPS Off -0.03 ± 0.02 MpaOn 0.05 ± 0.02 Mpa

Max discharge temperature By thermistor and software control

Overcurrent relay By TC on PCB and software control

4TW25141-2

RYP71L7V1/W1

Model A

RYP71L7 335

3TW25149-5

RYP100L7V1/W1

Model A

RYP100-125L7 455 3TW25159-5

RYP125L7W1

RYP200-250

Model A

RYP200B7W1 380

RYP250B7W1 510

4TW23619-1

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

110

43• Split - Sky Air • Outdoor Units

Page 46: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

12 Installation

+ Where there are noobstacles above the unit.

1 Installation of single unit+ In case obstacles exist only in

front of outlet side.

2 Installation of multiple units inlateral connection (2 units ormore).

+ Where there areobstacles above theunit.

1 Installation of single unit+ In case obstacles exist

only in front of outletside.

2 Installation of multiple unitsin lateral connection (2units or more).

+ In case obstacles existonly in front of outletside.

(C) In case obstacles exist infront of both the air inlet andoutlet sides.

+ Where there are no obstaclesabove the unit.

RYP71-125L7/B7The numerical figures used here represent the dimensions for the models RP71to 125. The figures inside ( ) indicate the dimensions for the models RP100 and125. (Unit:mm)The figures inside < > indicate the dimension of discharge grille when it isinstalled facing downwardWhen installing multiple units in lateral connection, discharge grille cannot be setto discharge air in Left/Right direction

(A) In case obstacles exist in front of the air inlet

+ In case obstacles exist in front of theair inlet and on both sides of theunit.

+ In case obstacles exist in frontof the air inlet and on bothsides of the unit.

1 Installation of singleunit.

2 Installation ofmultiple units inlateral connection(2 units or more).

+ Where there are no obstacles abovethe unit

Where obstacle infront of the air outletis higher than theunit.

2 Installation of multiple units in lateralconnection (2 units or more).

Pattern 1

2 Installation of multiple units in lateralconnection (2 units or more).

+ In case obstacles exist in frontof the air inlet and on bothsides of the unit.

+ Where there are obstacles above theunit.

1 Installation of single unit+ In case obstacles exist only in

front of the air inlet.

1 Installation of single unit+ In case obstacles exist only in front of the

air inlet.+ In case obstacles exist in front of the air

inlet and on both sides of the unit.

(B) In case obstacles exist only in front of outlet side

50 or more (100)

100 or more

100 or more

100 or more

20 mm or more

20 mm or more

1000 mm or more

20 mm or more

500 or less

100 or more

500 or less

150 or more

150 or more

150 or more

500 or less

20 mm or more

1000 mm or more

20 mm or more

200 mm or more200 or more (300)

150 or more

20 mm or more

20 mm or more

1000 mm ormore

500 or less

500 mm or more

500 or less

1000 mm or more

20 mm or more

20 mm or more

50 or more (100)

500 or more (1000)

20 mm or more

20 mm or more

200 or more (300)

1000 or more(1500)

100orm

ore

1000m

morm

ore

1000m

morm

ore

1000m

morm

ore

1000m

morm

ore

200 or more (300)

DU427-826

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

112

44 • Split - Sky Air • Outdoor Units

Page 47: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

1 In case of installingone unit per row.

2 In case of installingmultiple units (2 unitsor more) in lateralconnection per row.

2 Installation of multiple units inlateral connection (2units or less).

Relation of dimensions of H, A, and Lare shown in the table below.

L A

L ≤ H0 < L ≤ 1/2 H 150 (250)

1/2 H < L 200 (300)H < L Set the frame to be L<=H

(D) In case of stacked installation1 In case obstacles exist in front of the

outlet side.Do not stack more than one unit..About 100mm is required as thedimension for laying the upper outdoorunit’s drain pipe..Get the portion A sealed so that air fromthe outlet does not bypass..

Relation of dimensions of H, A, and L are shownin the table below.

L A

L ≤ H0 < L ≤ 1/2 H 150 (250)

1/2 H < L 200 (300)H < L Installation impossible

2 In case obstacles exist in front of theair inlet.

Do not stack more than one unit..

About 100mm is required as thedimension for laying the upper outdoorunit’s drain pipe..

Get the portion A sealed so that air fromthe outlet does not bypass..

(E) In case of multiple-low installation(for roof top use, etc.).

RYP71-125L7/B7+ Where there are obstacles

above the unit.

+ Where there are no obstacles abovethe unit.

Get the lower part of the frame sealed so thatair from the outlet does not bypassDo not install more than 2 units

1 Installation of single unit.

2 Installation of multiple units in lateralconnection (2 units or more).

Relation of dimensions of H, A, and L areshown in the table below.

L A

L ≤ H0 < L ≤ 1/2 H 750<1250>

1/2 H < L 1000<1500>H < L Set the frame to be L<=H

Relation of dimensions of H, A, and L areshown in the table below.

L A

L ≤ H0 < L ≤ 1/2 H 1000<1500>

1/2 H < L 1250<1750>H < L Set the frame to be L<=H

Pattern 2Where obstacle in front of the air outlet islower than the unit.

1 Installation of single unit.

2 Installation of multiple units in lateralconnection (2 units or more).

Relation of dimensions of H, A, and L areshown in the table below.

L A0 < L ≤ 1/2 H 150 (250)

1/2 H < L 200 (300)

+ Where there are obstacles above theunit.

1 Installation of single unit.

Relation of dimensions of H, A, and L areshown in the table below.

L A

L ≤ H0 < L ≤ 1/2 H 50 (100)

1/2 H < L 100 (200)H < L Set the frame to be L<=H

Get the lower part of the frame sealed so thatair from the outlet does not bypass

Get the lower part of the frame sealed sothat air from the outlet does not bypass

Get the lower part of the frame sealed so thatair from the outlet does not bypass

Do not install more than 2 units

500 or less

150 or more (250)

500 or less

20 mm ormore

200 or more (300)

50 or more (100)

500 or more (1000)

20 mm or more

20 mm or more

1000 or more (1500)

500 or less

500 or more (1000)

500 or less

20 mm ormore

1000 or more (1500)

20 mm or more

1000 mm or more

20 mm or more

200 or more (300)

50 or more (100)

1000 or more (2000)

100 or more (200)

500 or more (1000)

20 mm or more

20 mm or more

2000 or more (3000)

400 or more (600)

1000 or more (1500)

1000m

morm

ore

1000m

morm

ore100

ormore

1000m

morm

ore

DU427-826

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

12 Installation

112

45• Split - Sky Air • Outdoor Units

Page 48: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

Single installation Installation in a row Conentrated installation

Case 1 Case 1 Case 1

Case 2 Case 2

Case 3 Case 3

Case 2

1 Case 1and case 2+ Front wall height is 1500mm+ Suction wall height is 500mm+ Side wall height has no limit+ Case 3 wall height has no limit

2 If the wall is higher than mentioned in note 1: ADO h2/2 (front side) and ANO h1/2(suction side) to the mentioned values for installation. (h1 and h2: see figure to the left)

3 Before installing, please check the passage of humans and air at the side, and select aplace which is suitable for the case. (If there are a lot of units to be installed, take carethat there is no shortcircuit of air)

4 Please install considering piping installation at the front side.

suct

ion

side

front

side

RYP200-250B7

3TW23619-4

RYP200-250B7

12 Installation

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

•PairApplication

•R-407C•RYP71-125L7V1/W

1∼RYP200-250B7W1

12Installation

11246

• Split - Sky Air • Outdoor Units

•Split-

SkyA

ir•

OutdoorU

nits

Page 49: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

3TW25149-4A

Do not stack more than one unit.About 100mm is required as the dimension for laying the upper outdoorunit’s drain pipe.Get the portion A sealed so that air from the outlet does not bypass.

Legend= mmSSO Suction side obstacleDSO Discharge side obstacleLSO Left side obstacleRSO Right side obstacleTSO Top side obstacle

B. Stacked installation

1. Obstacles exist in front of the outlet side

C. Stacked installation

1. Installation of one unit per row

2. Obstacles exist in front of the air inlet

R(Y)(E)P-L

A. Non stacked installation

2. Installing multiple units (2 units or more) in lateralconnection per row

Relation of dimensions of H, A, and L are shown in the table below.L A

L ≤ H0 < L ≤ 0.5 H 150 (250)

0.5 H < L 200 (300)H < L Installation impossible

✓ Obstacle is presentIn these cases, close the bottom of the installation frame to prevent discharged air frombeing bypassed.In these cases, only 2 units can be installed.

x This situation is not allowed.( ) Figures between ( ) indicate the dimensions only for the 100-125 class models.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

12 Installation

112

47• Split - Sky Air • Outdoor Units

Page 50: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

RYP71-125L7

Refrigerant pipe size

Pair system

Model Piping length

Class Gas pipe Liquid pipe

71 J15.9xt1.0J9.5xt0.8

100, 125 J19.1xt1.0

The pipes between the outdoor unit and the branch (L1) should have thesame size as the outdoor connections. The pipes between the branch andthe indoor units (L2-L4) should have the same size as the indoorconnections.

Allowable pipe length and height difference

See the table below concerning lengths and heights. Refer to thefigures. Assume that the longest line in the figure corresponds with theactual longest pipe, and the highest unit in the figure corresponds with theactual highest unit.

Allowable pipe length

Maximum allowable pipe length(figures between parenthesisrepresent equivalent length)

Pair L1 70 m(90 m)Twin/Triple L1+L2

Maximum total one-way pipelength

Twin L1+L2+L380 m

Triple L1+L2+L3+L4

Maximum branch pipe length Twin/Triple L2 20 m

Maximum difference betweenbranch lengths

Twin L2-L310 m

Triple L2-L4

Maximum height between indoorand outdoor All H1 30 m

Maximum height between indoors Twin/Triple H2 0.5 m

Chargeless length All L1+L2+L3+L4 ≤30 m

The minimal piping length should be 5 m. If installation is performed withless field piping, the system will be overcharged (abnormal HP, etc.). If thedistance between indoor and outdoor unit is less than 5 m, please makesure that the piping length is ≥5 m by additional bending of the pipes.

Charging refrigerantThis unit requires additional charging of refrigerant according to the lengthof pipe connected at the site. Charge the refrigerant to the liquid pipe in itsliquid state. Since R-407C is a mixed refrigerant, its composition changes ifcharged in a state of gas and normal system operation would no longerbe assured.

On this model it is not necessary to charge additionaly if the piping length≤30 m.

On twin/triple application, piping length means sum of main pipe andbranch pipe.

Piping length is the 1 way length, gas or liquid.

Over 30 m or for complete recharging, please charge based as shown inthe figures, where the pipe length is respectively L1+L2+L3 andL1+L2+L3+L4.

Additional charging of refrigerant

Over 30 m please, add refrigerant quantity according to following table.

For future servicing, mark with a circle the selected amount on the tablesbelow.

Pair system

Table 1: Additional charging amount <unit: kg>

Model Piping length

Class 30∼40m 40∼50m 50∼60m 60∼70m

H/P71 +0.50 +1.00 +1.50 +2.00

100-125 +0.75 +1.50 +2.25 +3.00

C/O 71-100-125 +0.25 0.50 +1.75 +1.00

For twin/triple system

Please charge additionaly according to the following calculation. (Additionalamount is R1+ R2)1. G1: total length of J9.5 mm liquid piping

G2: total length of J6.4 mm liquid piping2. a G1 > 30 m

calculate length over 30 m (+ G1 - 30 m)Based on this length decide R1, R2 in the table

b G ≤ 30 m and G1 + G2 > 30 mcalculate total length over 30 m (= G1 + G2 - 30 m)Total additional charge amount

3. Total additional charge amountR = R1 + R2 (kg)

Table 2: Additional charging amount <unit: kg>

Model Length exceeding 30 m

Class Piping J 0-10 10-20 20-30 30-40 40-50

H/P

71Main

9.5 0.50 1.00 1.50 2.00 2.50R1

100-125 9.5 0.75 1.50 2.25 3.00 3.75

71

Branch

9.5 0.30 1.00 1.50 2.00 2.50R1

100-125 9.5 0.75 1.50 2.25 3.00 3.75

71-100-125 6.4 0.30 0.60 0.90 1.20 1.50 R2

C/O 71-100-125

Main 9.5 0.25 0.50 0.75 1.00 1.25R1

Branch9.5 0.25 0.50 0.75 1.00 1.25

6.4 0.15 0.30 0.45 0.60 0.75 R2

Twin

Pair

Triple

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

12 Installation

112

48 • Split - Sky Air • Outdoor Units

Page 51: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

Example 1

100 type

outdoor heat pump

L1 = 35 (J9.5)

L2 = 7 (J9.5)

L3 = 5 (J6.4)

71 type

Indoor

35 type

1. G1 = L1 + L2 = 35 + 7 = 42 m G2 = L3 = 52. Over 30 m

a G1 - 30 = 12 m → J9.5 R1 = 1.50 kgb G2 = 5 m → J6.4 R2 = 0.30 kg

3. Refrigerant charge amount= R = R1 + R2 = 1.50 + 0.30 = 1.80 kg

Example 2

125 type

outdoor heat pump

L1 = 5 (J9.5)

L2 = 17 (J6.4)

L3 = 17 (J6.4)

L4 = 20 (J6.4)

45 type

Indoor

45 type

Indoor

45 type

1. G1 = L1 = 5 m G2 = L2 + L3 + L4 = 17 + 17 + 20 = 542. Over 30 m

a G1 = 5 m → R1 = 0.0 kgb (G1 + G2) - 30 = (5 + 54) - 30 = 29 → J6.4 R2 = 0.90 kg

3. Refrigerant charge amount= R = R1 + R2 = 0.0 + 0.9 = 0.9 kg

In case of complete recharge of the refrigerant, please first executevacuuming. Execute this vacuuming from the service port. Do not use theport of the stop valve for vacuuming. Vacuuming can not be executedcompletely using such port.

Position of service port:Heat pump: On the piping between the heat exchanger and the 4-way valve.Cooling only: On the discharge pipe.

Complete charging of the refrigerant (after a leak, etc.)

When the entire refrigerant pipe length is within 30 meters, charge therefrigerant in accordance with the amount mentioned in the nameplate,and when the pipe length exceeds 30 meters, the charging amountmentioned in the nameplate and that required for additional charging areto be totalled as the net charging amount.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

12 Installation

112

49• Split - Sky Air • Outdoor Units

Page 52: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

RYP200-250B7

Refrigerant pipe size

1. Pair system (fig. 1)

Outdoor unitRefrigerant pipe size

Gas pipe Liquid pipe

RYP200 J 28.8 J 12.7

RYP250 J 28.8 J 15.9

2. Simultaneous operation systemTwin and triple operation system (fig. 2 / fig. 3)The pipes between the outdoor unit and the branch (L1) should have the same sizeas the outdoor connections.The pipes between the branch and the indoor units (L2-L4) should have the samesize as the indoor connections.Branch: see marking ’Q’ on the figures. Double twin operation system (fig. 4)The pipes between the outdoor unit and the branch (L1) should have the same sizeas the outdoor connections.The pipes between the branch and the indoor units (L2-L4) should have the samesize as the indoor connections.Branch: see marking ’Q’ on the figures.

Outdoor unitRefrigerant pipe size

Gas pipe Liquid pipe

RYP200,250 J 19.1 J 9.5

Additional chargeThe units require additional charging of refrigerant, according to the length of pipeconnected at the size.The correct amount of refrigerant to charge ’G’ (kg) can be lound by using thefollowing formulas (If G<O: no addition is required).

1. Pair systemL1 (m) One way length of liquid pipe

RP200 G = (L1-30) * 0.06

RP250 G = (L1-30) * 0.09

RYP200 G = (L1-30) * 0.10

RYP250 G = (L1-30) * 0.14

2. Simultaneous operation systemL1 (m) One way length of main liquid pipeL2-L7 (m) One way length of branched liquid pipes

RP200 G = (L1-30) * 0.06+L2*A+L3*A+L4*A+L5*A+L6*A+L7*A

RP250 G = (L1-30) * 0.09+L2*A+L3*A+L4*A+L5*A+L6*A+L7*A

RYP200 G = (L1-30) * 0.10+L2*A+L3*A+L4*A+L5*A+L6*A+L7*A

RYP250 G = (L1-30) * 0.14+L2*A+L3*A+L4*A+L5*A+L6*A+L7*A

Outdoor unit Branched pipe A

RP200,250 J 9.5 0.03 kg/m

RYP200,250J 6.4 0.03 kg/m

J 9.5 0.05 kg/mAllowable pipe length

See the table below concerning lengths and heights. Refer to the figures. Assume that the longest line in the figure corresponds with the actual longest pipe, and the highest unit inthe figure corresponds with the actual highest unit.

Maximum allowable pipe length (figures between parenthesis represent equivalent length)

Pair L1

50m (70m)Twin/triple L1+L2

Double twin L1+L2+L4

Maximum total one-way pipe length

Twin L1+L2+L3

60mTriple L1+L2+L3+L4

Double twin L1+L2+L3+L4+L5+L6+L7

Maximum branch pipe lengthTwin/triple L2

20mDouble twin L2+L4

Maximum difference between branch lengths

Twin L2-L3

10mTriple L2-L4

Double twin (L2+L4)-(L3+L7)

Maximum difference between each 1st branch Double twin L2-L3 10m

Maximum difference between each 2nd branch Double twin L4-L5, L6-L7 10m

Maximum height between indoor and outdoor All H1 30m

Maximum height between indoors Twin / triple / double twin H2 0.5m

fig. 1: Pair3TW23619-3

fig. 4: Double twin

fig. 2: Twin

fig. 3: Triple

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

12 Installation

112

50 • Split - Sky Air • Outdoor Units

Page 53: RYP-L7/B7 Pair Application - DAIKIN Θεσσαλονίκης, Μηχανήματα ... · 2017-05-05 · Daikin Europe N.V. is approved by LRQA for its Quality ... OUTDOOR UNITS RYP71L7V1/W1

RYP71-125L7

4TW25149-8

Oil trapIndoor unit

Oil trap

Gas piping

Liquid piping

Outdoor unit

Inst

allt

rap

atea

chdi

ffere

nce

inei

ghto

f15m

NOTE:

Since there is fear of the oil held inside the riser piping flowing back into the compressor when stopped and causing liquidcompression phenomenon, or cases of deterioration of oil return, it well be necessary to provide a trap at an appropriateplace in

A trap is not necessary when the outdoor unit is installed in a higher position than the indoor unit.

• Pair Application • R-407C • RYP71-125L7V1/W1∼RYP200-250B7W1

12 Installation

112

51• Split - Sky Air • Outdoor Units