NEW RETAINING WALL
CONSTRUCTION JOINT,
SEE DETAIL 4/S1
1'-6
"3
'-6
"
2'-0
" +
/-, V
AR
IE
S
TOP OF FOOTING
EL. -3'-6"
TOP OF PAVEMENT
EL. 0'-0"
1'-2"
2" CLR.,
TYP.
DRAIN BY
OTHERS
#6 @ 6" O.C.
#4 @ 12" O.C.
1'-6" 1'-6"
4'-2"
(5) #4 EACH
FACE
(5) #4 EACH
FACE
TOP OF WALL
EL. VARIES
1'-2"
CONSTRUCTION
JOINT
ARCHITECTURAL
REVEAL
3
4
" MAX -
EXPOSED SIDE ONLY
WATERSTOP
Consultants
1
A
1
2
2
3
3
4
4
5
5
6
6
7
7
B
C
D
E
A
B
C
D
E
Project
Client
DescriptionMark Date
Project No.
Date
Drawn
Checked
Scale
Sheet Title
Sheet No.
Headquarters & Laboratories : Northbrook, IllinoisAtlanta | Austin | Boston | Chicago | Cleveland | Dallas | Denver | DetroitHonolulu | Houston | Los Angeles | Minneapolis | New Haven | New York
Philadelphia | Princeton | San Francisco | Seattle | South Florida | Washington, D.C.
©C
opyr
ight
201
9. A
ll rig
hts r
eser
ved.
No
part
of th
is d
ocum
ent m
ay b
e re
prod
uced
in a
ny fo
rm o
r by
any
mea
ns w
ithou
tpe
rmis
sion
from
Wis
s, Ja
nney
, Els
tner
Ass
ocia
tes,
Inc.
(WJE
). W
JE d
iscl
aim
s any
resp
onsi
bilit
y fo
r its
una
utho
rized
use
.
Plot
ted:
10/
22/2
019
2:57
PM
by
Doa
ne, A
ndre
w H
. F
ile N
ame:
P:\2
018\
2018
.5xx
x\20
18.5
014.
0 - g
rf -
fy19
reta
iner
(jfd
)\06
draw
ings
\tv tr
uck
dock
reta
inin
g w
all
draw
ings
\She
ets\
S1 N
ew R
etai
ning
Wal
l Pla
n, D
etai
ls, a
nd N
otes
.dw
g
THIS SHEET PLOTS FULL SIZE
AT 22x34 (INCHES)
0 1/2" 1" 2"
Wiss, Janney, Elstner Associates, Inc.
330 Pfingsten Road
Northbrook, Illinois 60062
847.272.7400 tel | 847.291.9599 fax
www.wje.com
ENGINEERSARCHITECTSMATERIALS SCIENTISTS
TV Truck Dock Improvements
at Guaranteed Rate Field
Chicago, Illinois 60616
Illinois Sports
Facilities Authority
333 West 35th Street
Chicago, Illinois 60616
2018.5014
10-22-19
AHD
JFD
As Noted
New Retaining Wall
Plan, Details, and Notes
S1
1SCALE: 1" = 20'-0"
Plan of New Retaining Wall
N
NOTE: PLAN BACKGROUND REPRODUCED FROM GEWALT
HAMILTON ASSOCIATES, INC. DRAWING C2, DATED 10-14-19
2NOT TO SCALE
Soil Profile at New Retaining Wall
3SCALE: 3/4" = 1'-0"
Section at New Retaining Wall
4SCALE: 3/4" = 1'-0"
Plan of New Retaining Wall at Construction Joint
S1
3
TYP.
STRUCTURAL NOTES
GENERAL
1. ALL STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH THE DEMOLITION, CIVIL, AND SHOP DRAWINGS AND THE PROJECT SPECIFICATIONS.
2. CONSTRUCTION SHALL MEET THE REQUIREMENTS OF THE CURRENT CHICAGO BUILDING CODE (CBC). THE CBC SHALL GOVERN EXCEPT WHERE OTHER
APPLICABLE CODES OR THESE DOCUMENTS ARE MORE RESTRICTIVE.
3. THE CONTRACTOR ALONE IS RESPONSIBLE FOR THE JOB SITE SAFETY. SITE REVIEW OF THE CONSTRUCTION BY THE ENGINEER IS TO DETERMINE
CONFORMANCE WITH THE PLANS AND SPECIFICATIONS. IT DOES NOT ENCOMPASS SAFETY PROCEDURES OR OPERATIONS.
4. WRITTEN DIMENSIONS SHALL BE USED FOR CONSTRUCTION. DO NOT SCALE DRAWINGS.
SOIL PARAMETERS
1. SOIL PARAMETERS ARE BASED ON A SOIL BORING FROM STS/AECOM FROM THE SW CORNER OF 39TH AND STATE STREET, CHICAGO, IL DATED JUNE 27, 2008.
2. ASSUMED ALLOWABLE SOIL BEARING CAPACITY: 3000 PSF
3. ASSUMED UNIT WEIGHT OF SOIL:125 PCF
4. CONTRACTOR SHALL INDEPENDENTLY VERIFY SOIL PROFILE, ALLOWABLE BEARING CAPACITY, AND UNIT WEIGHT. NOTE: CURRENT DEPTH OF URBAN FILL
ASSUMED TO BE 3'-6".
CONCRETE
1. REINFORCED CONCRETE SHALL CONFORM TO ACI 350
2. PORTLAND CEMENT SHALL CONFORM TO ASTM C150 TYPE II. ONE BRAND OF CEMENT SHALL BE USED THROUGHOUT THE WORK.
3. ALL AGGREGATES SHALL CONFORM TO ASTM C33. THE MAXIMUM SIZE AGGREGATE SHALL BE 3/4 INCH.
4. MIN 28 DAY CONCRETE COMPRESSIVE STRENGTH SHALL BE 4000 PSI.
5. ALL CONCRETE SHALL HAVE AIR ENTRAINMENT OF 3.5 TO 5.0 PERCENT.
6. CONSTRUCTION JOINTS SHALL NOT BE PLACED AT LOCATIONS OTHER THAN THOSE SHOWN ON THE DRAWINGS WITHOUT THE PRIOR APPROVAL OF THE
ENGINEER.
7. ALL EXPOSED CORNERS OF CONCRETE SHALL HAVE 3/4” MINIMUM CHAMFER, UNLESS NOTED OTHERWISE.
CONCRETE REINFORCING
1. REINFORCING STEEL SHALL CONFORM TO THE LATEST EDITION OF ASTM SPECIFICATION A615, GRADE 60 OR A706.
2. REINFORCING STEEL FABRICATION SHALL BE IN ACCORDANCE WITH THE LATEST EDITION OF CRSI MANUAL OF STANDARD PRACTICE.
3. REINFORCING SHALL HAVE 2 IN. CLEAR CONCRETE COVER, UNLESS OTHERWISE NOTED ON THE DRAWINGS.
4. SPLICED BARS SHALL HAVE A MINIMUM CLASS B LAP AS SPECIFIED IN THE LATEST EDITION OF ACI 315 DETAILING MANUAL UNLESS OTHERWISE NOTED ON THE
DRAWINGS.
5. AT FOOTING CORNERS AND INTERSECTIONS, EXTEND BARS AROUND CORNERS AND LAP A MINIMUM OF 40 BAR DIAMETERS.
CONCRETE JOINTS
1. ALL LAP SPLICES SHALL BE CLASS B TENSION LAP.
2. SEALANT SHALL BE PROVIDED IN JOINTS WHERE SHOWN ON THE DRAWINGS.
3. WATERSTOPS SHALL BE PROVIDED IN JOINTS WHERE SHOWN ON THE DRAWINGS
4. WATERSTOP SHALL BE PLACED AT CENTER OF WALL.
FOR BID