saf-03 plant buildings

Upload: luke

Post on 06-Jul-2018

243 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/18/2019 SAF-03 Plant Buildings

    1/19

    KINGDOM OF S UDI R BI

    MINISTRY OF INTERIOR

    HIGH COMMISSION OR INDUSTRI L SECURITY

    S FETY ND FIRE PROTECTION DIRECTIVES

    OR

    INDUSTRI L F CILITIES

    SAF 03

    Plant Buildings

    Issue

    Date: 1216 1431H

    126 0512010

    RESTRI TED

    All Rights

    reserved to

    HCIS Copying

    or distribution

    prohibited

    without written

    permission from

    efS

  • 8/18/2019 SAF-03 Plant Buildings

    2/19

    Kingdom of Saudi Arabia

    Ministry ofinterior

    High Commission for Industrial Security

    Secretariat General

    SAF 03

    Plant

    Buildings

    TABLE OF

    CONTENTS

    Administration

    1 I Scope

    1.2 Application

    1 3

    Conflicts and Deviations

    Definitions

    3

    References

    4

    General Requirements

    5 Control Buildings and Buildings

    Requiring Blast Resistance

    6

    Other Requirements for Buildings

    In Plants

    Issue Date: 12 6 143lH 126105 2010

    RESTRICTED

    Page

    3

    3

    3

    3

    5

    7

    13

    16

    ~ \ . . . u \ ~ ~ \ j

    W I Cr')U .,WI

    4

    Wl

    ;;.;Lo ll

    ll

    Rights

    reserved to HCIS.

    Copying

    or distribution

    prohibited without w ritten

    permission from HCIS

    Page 2 of l9

  • 8/18/2019 SAF-03 Plant Buildings

    3/19

    Kingdom of Saudi Arabia

    Ministry

    ofInterior

    High Commission for Industrial Security

    Secretariat General

    SAF-03 Plant Buildings

    1. Administration

    I l Scope

    ~ \ . . u \ ; ; ~ i )

    u.,.)1

    J u

    l).J1 1

    Wl

    ;;';L.) 1

    This Directive provides the minimum requirements for companies and establishments

    that are subject to the supervision of the High Commission for Industrial Security

    (HCIS), Ministry of Interior, for all plant buildings, including but not limited to buildings

    that contain control rooms, process instrumentation buildings, communications buildings,

    electrical substations, operations and maintenance office buildings, maintenance shops,

    storages buildings, and mosques.

    1.2 Application

    This Directive is applicable to all facilities, including new projects, the expansion

    of

    existing facilities, and upgrades. For application to existing facilities, the Owner shall

    assess his facilities against the requirements of these Directives and coordinate with the

    General Secretariat of the HCIS to comply with the security, safety, and fire protection

    requirements according to these Directives and add to or

    modifY

    the existing facilities

    as

    required. Where the General Secretariat of the HCIS has assessed deficiencies

    in

    existing

    facilities during a survey, comparing the current state

    of

    the facilities to the requirements

    of

    these Directives, those identified deficiencies shall be corrected by the Owner.

    1.3 Conflicts and Deviations

    Where implementation

    of

    a requirement is unsuitable or impractical, where other

    equivalent company or industry Standards and Codes are followed, or where any conflict

    exists between this Directive and other company standards and Codes, the deviations

    shall be resolved by the General Secretariat of the HCIS. Deviations lower than the

    requirements of this Directive shall be listed and submitted

    in

    a report of non-compliance,

    with justification and rationale for not following the requirement, and approval shall be

    received from the General Secretariat

    of

    the HCIS prior to implementation. The

    documents shall be retained by the company

    in

    its permanent engineering files.

    2.

    Definitions

    API: American Petroleum Institute, Website: http://api-ec.apLorg/

    ASeE American Society ofCivil Engineers, Website: http://www asce org/

    Issue Date: 12I6 1431H 126 05 2010

    RESTRICTED

    AI Rights reserved to Hers. Copying or distribution prohibited without written pennission from HCIS

    Page 3 of 19

  • 8/18/2019 SAF-03 Plant Buildings

    4/19

    Kingdom of Saudi Arabia

    Ministry ofinterior

    High Commission for Industrial Security

    Secretariat General

    SAF-03 Plant Bnildings

    ~ \ 0 \ ; ~ \ j J

    u

    \ WI -\;II

    ;;....w\

    t.,, 1j

    ASHRAE: American Society of Heating, Refrigerating, and Air-Conditioning

    Engineers, Website: http://www.ashrae.org/

    Fire-Scenario Envelope: A three-dimensional space into which fire-potential equipment

    can release flammable or combustible fluids capable of burning long enough and with

    enough intensity to cause substantial property damage see API PUB 2218).

    FM FM Global Factory Mutual),

    Website: http://www.fmglobal.com/

    Fnnctional ly Significant Bnilding: Building that is required for the continued operation

    and safe shut-down of the plant, such as control room, process interface building, and

    substations.

    Hazardons Classified) Area: Locations as defined by API RP 500, API 505, NFPA 70,

    NFPA 497, or NFPA 499 which have the potential of ignitable mixtures with respect to

    electrical equipment installations.

    HCIS: High Commission for Industrial Security, Ministry ofInterior.

    High-Population Building: Any building, such as offices, mosque, cafeteria, training

    building, medical clinic, or other occupancy that can contain 25 or more people at any

    time.

    HVAC: Heating, Ventilation, and Air Conditioning.

    ICC: International Code Council ICC) Website: http://www.iccsafe.org/

    Listed: A device that is tested and certified by an independent testing lab to be suitable

    for its purpose.

    Manned Building: Buildings such as control rooms, operations and maintenance office

    buildings, and maintenance shops where people are expected to be present to do their

    jobs on a regular basis.

    Noncombustible: Material that will not burn or support burning such as concrete,

    masonry or steel.

    Owner: Person, partnership, or company that has possession of a facility or

    establishment.

    Plant: Facilities used to manufacture, process, store, transport, or transfer a material or

    substance.

    Issue Date:

    I2I611431H

    26 05 2010

    RESTRICTED

    All Rights reserved to HCIS. Copying or distribution prohibited without written permission

    from HCIS

    Page 4 of 19

  • 8/18/2019 SAF-03 Plant Buildings

    5/19

    Kingdom

    of

    Saudi Arabia

    Ministry ofInterior

    High Commission for Industrial Security

    Secretariat General

    ~ I . . U \ ; ~ r J

    ,, -a ll V')U

    \ WI

    ~ W \ ~ t . . . 1 \

    SAF 03

    Plant Buildings

    Plant Buildings: All buildings that are within the plant property boundary.

    NFPA:

    National Fire Protection Association Website: http://www.nfpa.orgl

    Shall: Indicates a mandatory requirement.

    Should: Indicates a recommendation or that which is advised but not required.

    UL Underwriters Laboratories Inc. Website: http://www.ul.com/

    Unmanned Building:

    Buildings which are unattended by people under normal

    circumstances such as substations and process interface buildings.

    3 References

    This directive adopts the latest edition

    of

    the references listed.

    PI RP 500

    PI RP 505

    PI RP 752

    PI RP 753

    SCEReport

    ASHRAE 15

    SHR E 52.1

    ASHRAE52.2

    SHRAE 55

    SHR E

    62 1

    Issue Date:

    121611431H

    12610512010

    Classification

    of

    Locations for Electrical Installations at Petroleum

    Facilities Classified as Class L Division 1 and Division 2

    Classification ofLocations for Electrical Installations at Petroleum

    Facilities Classified as Class L Zone

    0

    Zone

    1 and

    Zone 2

    Management of

    Hazards Associated with Location

    of

    Process Plant

    Buildings

    Management ofHazards Associated with Location ofProcess Plant

    Portable Buildings

    Design ofBlast Resistant Buildings in Petrochemical Facilities

    Safety Standardfor Refrigeration Systems

    Gravimetric and Dust Spot Procedures for Testing Air Cleaning

    Devices Used in General Ventilation for Removing Particulate

    Matter

    Method

    of

    Testing General Ventilation Air Cleaning Devicesfor

    Removal Efficiency by Particle Size

    Thermal Environmental Conditions for Human Occupancy

    Ventilation for Acceptable Indoor ir Quality

    RESTRICTED

    All Rights reserved

    to

    HCIS

    Copying or distribution prohibited

    without

    written

    pennission

    from HCIS

    Page 5 of 9

  • 8/18/2019 SAF-03 Plant Buildings

    6/19

    Kingdom of Saudi Arabia

    Ministry ofInterior

    High Commission for Industrial Security

    Secretariat General

    WI Cr SU 1.).11

    1

    a...W\

    4;1.,. 11

    SAF 03 Plant Buildings

    SH

    RAE

    62 2

    SHR E III

    FM

    ICCEC

    ICCIBC

    ICCIEBC

    ICCIECC

    ICCIFC

    ICCIMC

    ICCIPC

    ICC IPSDC

    ICCIRC

    NFPA 10

    NFPA 13

    NFPA 45

    NFPA

    70

    NFPA 72

    NFPA

    75

    NFPA

    76

    NFPA 80

    NFPA 90A

    NFPA 221

    NFPA 251

    Issue Date 12161l431H /26/05/2010

    Ventilation and Acceptable Indoor ir Quality in Low-Rise

    Residential Buildings

    Practices for Measurement Testing Adjusting and Balancing

    of

    Building Heating Ventilation Air-Conditioning and Refrigeration

    Systems

    FM

    Global Property Loss Prevention Data Sheets

    International Electrical Code

    International Building Code

    International Existing Building Code

    International Energy Conservation Code

    International Fire Code

    International Mechanical Code

    International Plumbing Code

    International Private Sewage Disposal Code

    International Residential Code

    Portable Fire Extinguishers

    Installation

    of

    Sprinkler Systems

    Fire Protection for Laboratories Using Chemicals

    National Electrical Code

    National Fire Alarm Code

    Protection ofInformation Technology Equipment

    Telecommunications Facilities

    Fire Doors and Other Opening Protectives

    Installation ofAir-Conditioning and Ventilating Systems

    High Challenge Fire Walls Fire Walls and Fire Barrier Walls

    Fire Tests ofBuilding Construction and Materials

    RESTRICTED

    ll Rights reserved to

    HeIS

    Copying or distribution prohibited without written permission from HerS

    Page 6 of 19

  • 8/18/2019 SAF-03 Plant Buildings

    7/19

    Kingdom of Saudi Arabia

    Ministry of Interior

    High Commission for Industrial Security

    Secretariat General

    SAF-03

    Plant Buildings

    ~ \ J J \ ; ; ~ \ J

    W I

  • 8/18/2019 SAF-03 Plant Buildings

    8/19

    Kingdom of Saudi Arabia

    Ministry of Interior

    High Commission for Industrial

    Security

    Secretariat General

    SAF 03

    Plant Buildings

    ~ \ . . U \ ¢ j

    ,WI

    Cr )\J

    \ WI ; }I

    4 oW\

    :\ ;\..0\1\

    4.2.2 Rooms

    in

    functionally significant buildings that serve an important function for plant

    operation, such as computer rooms, data transmission rooms, processing rooms, store

    rooms, control rooms, communication rooms, battery rooms, and mechanical rooms, shall

    be subdivided by two-hour fire rated walls from rooms that serve different functions,

    such

    as

    offices. All interior finishing materials and furniture shall be made

    of

    noncombustible material; however, if noncombustible finishing materials are not

    available, then the alternative materials used shall be

    of

    a limited fire-spread index rating

    of 25 or less according to NFP A 255.

    4.2.3 Doors and windows that penetrate fire walls or on the exterior

    of

    a building shall

    be

    fire

    rated and shall be labeled with its rating of fire resistance. The doors and windows shall

    identify the agency that certified the design. Fire rated doors and windows shall meet

    NFPA80.

    a)

    Fire protection rating of a fire door presumes that the door is installed with the

    appropriate frame, hardware, and other accessories required by NFPA 80.

    b) Fire rated doors shall be self-closing or automatic closing, i.e. an electro-magnetic

    device may be used to hold interior fire doors open provided that they are installed

    on a self-closing door and allow the door to close

    in

    case

    of

    fire alarm activation.

    c)

    Fire rated windows shall either be

    of

    a fixed type or be automatic closing.

    d)

    Doors designated

    as

    security doors to buildings housing sensitive or vital equipment

    or to perimeter fences or other control

    of

    access areas shall be constructed to meet

    the appropriate security directive. However, all doors shall also meet the following

    safety requirements:

    1)

    The number of doors shall meet the safety requirements of the IBC.

    2) Doors designated

    as

    emergency exits shall meet the specifications

    of

    the IBC

    for safe egress. Security measures shall not prevent safe egress from occupied

    buildings.

    4.2.4 A

    N

    AC duct penetrating a two-hour fire resistant wall required

    in

    4.2.3 shall be

    provided with a fire rated automatic smoke and fire damper to stop smoke and fire from

    spreading throughout the building. The rating

    of

    the automatic damper for the air duct

    shall be consistent with the fire rating

    ofth

    wall, floor, or ceiling that

    is

    penetrated.

    4.2.5 Roofing systems shall be fire-resistive, meeting at least Underwriters Laboratories UL)

    Class A or B or Factory Mutual FM) Class 1 or 2 rating.

    Issue

    Date:

    12 61l43lH 126 05 2010

    RESTRICTED

    All Rights

    reserved

    to HeIS Copying or distribution prohibited

    without

    written

    pennission

    from HerS

    Page 8 of

    19

  • 8/18/2019 SAF-03 Plant Buildings

    9/19

    Kingdom

    of

    Saudi Arabia

    Ministry ofInterior

    High

    Commission for Industrial Security

    Secretariat General

    SAF 03

    Plant Buildings

    ~ J J \ ' ; Z i J

    U \ WI

    >4>1

    a w \ : t ; v ~ \

    4.2.6 Where instrument or electrical cables penetrate fire walls and partitions, the wall

    openings shall be sealed with system that

    is

    designed to prevent passage

    of

    water, fire and

    smoke.

    All

    through-penetration protection systems shall be tested and rated

    as

    specified

    in NFPA 221.

    4.2.7 Management

    of

    hazards to reduce risk

    of

    plant portable buildings due to explosion, fire,

    and toxic release hazards shall meet API

    RP

    753. Specific portable building siting

    guidelines and procedures for managing change shall

    be

    developed for use and location

    of

    portable bUildings.

    4 3 Access and Egress

    4.3.1 Building design shall comply with the requirements

    of

    the IBe Chapter

    10

    including

    minimum size and number

    of fire exits, emergency lights, and exit signs.

    4.3.2 Exits shall be clearly marked

    so

    that they are identifiable as exits. Access to exits shall be

    marked by readily visible signs where the exit or a pathway to reach the exit is not readily

    apparent to the occupants.

    4.3.3 There shall

    be

    at least two 2) means of egress from any building, room, or space except

    as specifically allowed

    in

    the IBC. Travel distance to any means

    of

    egress shall not

    exceed the specified distance for each type

    of

    occupancy.

    4.3.4 I1lumination

    of

    the means

    of

    egress floors and stairs) shall be not less than

    108

    lux 10

    foot candles), measured at the walking surfaces.

    4.3.5 During a power outage, emergency egress illumination shall be provided for at least I

    Y

    hours where illumination shall be on average no less than 10.8 lux 1.0 foot-candle),

    permitted to decline to not less than

    6 5

    lux 0.06 foot-candles). Emergency lighting

    systems shall be supplied from storage batteries or an on-site generator set and the system

    shall be installed in accordance with the requirements ofNFPA 70.

    Exception: Normal and emergency egress illumination

    is not required where the purpose

    of

    the industrial occupancy does not require routine human habitation or where the

    structure

    is

    occupied only during daylight hours and skylights or windows provide the

    required level

    of

    illumination.

    4.3.6 Building exits shall face away from equipment handling hazardous material, if possible.

    4.3.7 Emergency egress doors shall be provided with door opening hardware that is designed

    for both fire and panic protection the door shall be opened by pushing on a panic bar to

    Issue

    Date: 12 6 1431H

    126105 2010

    RESTRICTED

    All

    Rights

    reserved to HCIS Copying or distribution prohibited without written permission

    from

    HCIS

    Page 9

    ofI9

  • 8/18/2019 SAF-03 Plant Buildings

    10/19

    Kingdom of Saudi Arabia

    Ministry

    ofinterior

    High

    Commission for

    Industrial

    Security

    Secretariat General

    SAF-03

    lant

    Bnildings

    ~ \ J . l \ / ) )

    ifU

    Cr )IJ \ WI

    .. .'

    w\

    ;V\..1.j1

    exit or

    is

    designed so that the door or window readily opens outward when pushed). The

    doors shall be operable from the inside without the use

    of

    a key or tool.

    4.3.8 Exterior doors and all interior doors penetrating fire walls fire door) shall

    be

    equipped

    with automatic, quick-acting, adjustable door closers. The doors shall be kept closed and

    sign-posted to inform all workers to keep the doors closed.

    4.3.9 Fire exit doors shall not be locked

    in

    a way that would prevent immediate exit if any

    persons are inside the room or building.

    4.4 Fire Detection and Protection

    4.4.1 The fire detection, alarm and fire protection systems shall be fully commissioned and

    tested before a building is occupied.

    4.4.2 All functionally significant plant buildings such as control rooms, process interface

    buildings, substations or any other buildings which are critical to the continued operation

    of the plant shall be provided with a fire alarm system designed according to NFPA

    72.

    Fire detection and alarm systems fire panels, initiating and end devices, and associated

    equipment) shall be of the addressable type, i.e. each component can be individually

    identifiable at the fire panel.

    a)

    Fire alarms systems shall be provided with at least two independent and reliable

    power supplies, one primary and one standby.

    b) The primary power supply shall have a high degree of reliability. The secondary

    power supply e.g. emergency generation

    ndlor

    battery) shall be of sufficient

    capacity to operate the system for 24 hours to meet NFP A 72. The installation

    of

    all

    power supplies to the system shall meet NFPA 70 and NFPA 72.

    4.4.3 Detectors shall be installed above suspended ceilings and below raised floors

    of

    control

    buildings, computer centers, data processing centers, and telecommunications facilities

    where required to meet NFPA

    75

    or NFPA 76.

    4.4.4 Activation

    of

    the building fire detection and alarm system for buildings shall produce

    audible and visible alarms that can be observed from inside the building, outside the

    building, and at a permanently manned location, such as control room or fire station.

    4.4.5 Buildings shall be provided with the numbers

    and

    types

    of

    fire extinguishers suitable for

    the hazards to meet the requirements ofNFPA

    10.

    a) Fire extinguishers shall be located where readily accessible

    in

    the event

    of

    a fire.

    Issue Date 12 611431H 126 0512010

    RESTRICTED

    An Rights reserved to HCIS. Copying or distribution prohibited without written permission from HC1S

    Page

    10 of 19

  • 8/18/2019 SAF-03 Plant Buildings

    11/19

    Kingdom

    of

    Saudi Arabia

    Ministry ofInterior

    High

    Commission

    for Industrial Security

    Secretariat General

    SAF 03 Plant Bnildings

    4>1

    ;; WI < u \ ' ~ \

    b) They shall be located along a normal path of travel and at exits from areas.

    c) Portable fire extinguishers shall

    be

    installed on a hanger or bracket supplied or placed

    in

    cabinets or wall recesses that are clearly identified to contain a fire extinguisher.

    d) Portable extinguishers shall be maintained

    in

    a fully charged and operable condition.

    They shall be kept

    in

    their designated places at all times when they are not being

    used.

    e) Type and size

    of

    portable fire extinguishers shall be based on the types

    of

    hazards

    presented by the use of the building.

    f) Distribution

    of

    fire extinguishers

    in

    buildings shall depend

    on

    the type

    of

    hazard and

    coverage requirement in NFP A 10 Travel distance to a fire extinguisher shall be

    consistent with the type of hazard, e.g.

    no

    more than 23 meters for a Class A hazard

    or 15 meters for a Class B hazard. Refer to NFP A

    10

    for more details.

    4.4.6 The need for a sprinkler system or other automatic fire extinguishing system shall be

    determined by the Owner based on best international fire protection practices to protect

    life and property

    as

    specified below:

    a) At a minimum, fire detection and protection systems shall be installed where required

    by the BC and the IFC.

    b) The design of fire protection systems shall comply with the appropriate NFPA

    Standard, such as NFP A

    13

    for sprinkler systems and NFP A 2001 for clean agent Fire

    extinguishing systems.

    4.4.7 Fixed carbon dioxide (C02) fire protection systems shall not be used for manned

    bUildings.

    4.4.8 Fire protection shall be provided according to the SAF-4.

    4.4.9 Fire protection for storage buildings shall comply with NFPA

    13

    4.4.1 0 Fire detection, protection, and fire prevention procedures for laboratories shall comply

    with NFPA 45.

    4.4.11 Fire protection

    of

    computer roqms, communication equipment rooms, and plant control

    rooms shall comply with NFPA 75 and NFPA 76 where loss

    of

    function

    of

    computer and

    telecommunications equipment and data will impact life safety, process plant safety, or

    where third parties are critically affected.

    Issu. Date: I2IG/1431H /26/05/2010

    RESTRICTED

    All Rights reserved

    to

    HCIS Copying

    or distribution prohibited

    without

    written pennission from

    HCIS

    Page 11 ofl

  • 8/18/2019 SAF-03 Plant Buildings

    12/19

    Kingdom

    of

    Saudi Arabia

    Ministry

    ofInterior

    High Commission for Industrial

    Security

    Secretariat General

    SAF-03

    lant

    Buildings

    ~ I . . U \ / ) )

  • 8/18/2019 SAF-03 Plant Buildings

    13/19

    Kingdom

    of

    Saudi Arabia

    Ministry ofInterior

    High Commission for Industrial Security

    Secretariat General

    SAF-03

    Plant Buildiugs

    ~ \ . . u \ ; ~ \ j

    WI 0 )U \,WI < >1

    t.oWI

    A ; t ~ \

    5.

    Control Buildings

    and Other

    Buildings Requiring Blast Resistance

    5.1 Control buildings, multiple-occupancy buildings that contain control rooms, and other

    functionally significant buildings that are identified by the Owner to require equivalent

    protection

    in

    refineries, petrochemical plants, and other types

    of

    facilities that produce,

    process, or store flammable, toxic, or explosive substances,

    shaH

    be located to minimize

    exposure to fire, explosion or release of hazardous materials (see Section 4.1, above).

    When necessary, they shaH be made blast resistant to the extent needed to prevent

    coHapse due to overpressure from a vapor cloud explosion if one were to occur from a

    plant-related incident.

    5.2 While the spacing and design of the control building should be guided by the principles

    of API 752, the minimum spacing between a control building (or building that contains a

    control room) and vessels, tanks, or other process equipment handling combustible,

    flammable, toxic, or explosive materials

    shaH

    be 30 meters.

    5.3 The control building shall be designed to prevent the entry of combustible, flammable, or

    toxic liquids, gases or vapors.

    5.4 Control buildings located inside

    of

    a plant

    shaH be

    single-story and without windows.

    Exceptions: In plants where there

    is

    no explosion hazard, 5.4 does not apply or where the

    Owner s engineer otherwise approves multi-story construction. Where the windows are

    speciaHy designed to withstand the overpressure should an explosion occur, windows are

    aHowed.

    5.5 Control buildings shall be blast resistant to the extent needed to prevent collapse from a

    plant-related incident. Design of blast resistant buildings shall be accomplished by a

    registered or chartered professional engineer that is experienced

    in

    blast resistant

    structural design. Simulation

    of

    the resultant overpressure and suction overpressure from

    a potential plant related explosion shall be done using a registered or chartered

    professional engineer from an engineering firm that specializes in such simulation. The

    results shaH be used for the basis of structural design by a professional engineering firm.

    5.5.1 The simulation shall be used to select blast overpressure and duration (impulse) for the

    structural design basis.

    5.5.2 The simulation shall take into account existing process equipment and future plant

    expansion equipment that is likely to be installed.

    Issue Date 1216 1431H 126 05 2010

    RESTRICTED

    AI

    Rights reserved to HCIS. Copying or distribution prohibited without written pennission

    from

    HOS

    Page \3 of

    19

  • 8/18/2019 SAF-03 Plant Buildings

    14/19

    Kingdom

    o

    Saudi Arabia

    Ministry

    ofInterior

    High Commission for Industrial Security

    Secretariat General

    SAF-03

    Plant Buildings

    5.5.3 Wind and seismic loads shall not be combined with blast loading.

    ~ \ . . u \ ; j

    ,W I 0 )0 l W1

    4

  • 8/18/2019 SAF-03 Plant Buildings

    15/19

    Kingdom of Saudi Arabia

    Ministry ofinterior

    High

    Commission for Industrial Security

    Secretariat General

    SAF 03 Plant Buildings

    ~ ~ ~ l j

    W I .y u l W1 >4>1

    ;uWI

    a ;\ ..

    1\

    5.6.8 Design for compression elements, such

    as

    load-bearing walls and exterior columns,

    should consider secondary bending effects.

    5.7 No combustible, flammable, or toxic material piping shall be piped into or through the

    control building.

    5.8 No process or material handling equipment, pressure vessels, storage tanks, or piping

    containing combustible, flammable, or toxic materials shall be located above or under a

    control room or bUilding

    5.9 Offices, dining areas,

    and

    other types

    of

    rooms in the control building shall be limited to

    what

    is

    needed for the plant to function properly. Non-essential offices, dining and

    recreational rooms shall be separate from the control building and located

    in

    a safe

    location see 4.1.3).

    5.10 Exterior doors shall face away from process areas whenever possible.

    5 10 1 All exterior doors, inclnding equipment access double doors, shall meet the blast

    resistance requirements of the structural walls

    ofth

    building. Manufacturers shall certifY

    that blast resistant doors are designed to withstand the intended blast loading. The doors

    shall be marked with the manufacturers name and rating information.

    5.10.2 External frames for blast resistant doors shall be set in grooves or anchored on all sides to

    prevent doors and frames from being blown into the building

    in

    the event of an explosion.

    Exterior doors shall open outwards and be equipped with automatic door closers. The

    doors shall be kept closed and sign-posted to inform workers to keep the doors closed at

    all times.

    5 11

    The parts

    of

    the ventilation and air conditioning equipment that are necessarily external

    to the building shall be shielded or otherwise designed to survive any anticipated blast

    effects.

    5.11.1 The

    fan inlet ducting shall be elevated, be free of leaks, and be protected from

    mechanical damage and corrosion to prevent ingress of flammable or toxic vapors or

    gases.

    5.11.2 Inlet duct openings shall be minimized, arranged to be shielded from direct blast, and

    prevent pressure on the top surfaces

    of

    suspended ceilings.

    5.11.3 External louvers, their frames, and associated components shall be capable of

    withstanding design blast over-pressures.

    Issue

    Date:

    IU6 1431H

    126 05 2010

    RESTRICTED

    AU Rights reserved

    to

    HCIS Copying

    or

    distribution

    prohibited

    without written

    pennission

    from HCIS

    Page 15

    of 19

  • 8/18/2019 SAF-03 Plant Buildings

    16/19

    Kingdom o Saudi Arabia

    Ministry oflnterior

    High

    Commission for Industrial Security

    Secretariat General

    SAF 03 Plant Bnildings

    ~ \ . . u l o J \ j

  • 8/18/2019 SAF-03 Plant Buildings

    17/19

    Kingdom of Saudi Arabia

    Ministry

    ofInterior

    High Commission for

    Industrial Security

    Secretariat General

    SAF-03

    Plant uildings

    ~ U J \ o ~ \ j

    ,W I ,)\J \ WI

    ;. »1

    w

    ;VL,, t\

    6.3.6 Building pressurization shall be monitored by a differential pressure gauge and switch

    connected between the inside and outside of the building. Loss of building pressurization

    shall alarm at the nearest control room.

    6.3.7 The ventilation and air conditioning equipment system shall be designed to prevent the

    entry

    of

    flammable vapors or gases in accordance with the applicable NFPA 496.

    6.3.8 Any room/building requiring pressurization shall be designed to withstand

    an

    internal

    pressure

    of

    no less than 6.5 millimeter water gauge 0.25 inch water gauge).

    6.3.9 The ventilation and air conditioning system for buildings requiring pressurization shall

    maintain an internal building positive pressure

    of

    at least 2.5 millimeter water gauge

    0.1

    inch water gauge) with all doors and other openings closed.

    a) The system shall be capable of providing a minimum outward velocity of 0.30

    m/sec 60 ftlmin) through all openings. All doors capable of being opened, except

    equipment doors that are used infrequently, shall be considered open. An allowance

    for other openings shall be included. An alarm shall activate at the control room

    upon loss of pressurization below this

    2.5

    millimeter water gauge.

    b) Outside air flow rate available for building pressurization equal to not less than two

    2) air changes per hour

    of

    the total pressurized space with doors closed. The design

    pressure shall be 6.5 millimeter water gauge 0.25 inch water).

    6.3.10 Interior dry bulb design temperature shall be 22 degrees C 75 degrees F),

    50

    percent

    relative humidity with the outside conditions based on recognized local design

    conditions.

    a) The thermal environmental conditions shall meet ASHRAE 55. HVAC systems

    shall be capable of maintaining dry bulb temperature and relative humidity (if

    applicable) within the performance range given in Table 1, ASHRAE 55, unless

    stricter indoor design conditions are required.

    b) The number of doors and other penetrations shall be minimized so that positive

    pressure can be maintained, while at the same time, the number

    of

    doors shall be

    adequate for safe exit per the IBC. The system shall be tested and balanced to meet

    ASHRAE STD Il l .

    c) Devices to read and indicate temperature, relative humidity, and the indoor/outdoor

    differential pressure shall be installed in the control room.

    Issue Date:

    I2IGI 43 H 126 05 2010

    RESTRICTED

    All

    Rights reserved to HClS Copying or distribution prohibited without written permission from eIS

    Page

    17 of 19

  • 8/18/2019 SAF-03 Plant Buildings

    18/19

    Kingdom of Saudi Arabia

    Ministry ofinterior

    High Commission for Industrial Security

    Secretariat General

    SAF 03 Plant Buildings

    WI u-- >U \ WI

    4...>WI:t;t... 11

    d) Air lock type entries are required to entrances normally used by personnel. Air

    locks are not required for large doors used infrequently to bring in large equipment.

    6.3.11 Ventilation and air conditioning equipment located in hazardous classified) areas shall

    meet the requirements ofNFPA 70

    6.3.12 Air-conditioning and refrigeration installations shall meet the safety requirements of

    ASHRAE Standard IS.

    6.4 Maximum allowable noise levels inside the an occupied room in a plant building, such as

    a control room, shall

    be 55

    decibels

    to

    be achieved without hearing protection for the

    occupants.

    6 5 A fire detection and alarm system shall

    be

    installed that will monitor for fire and/ or

    smoke in all rooms adjacent to the control room.

    6 6 Two-hour fire-resistant separation shall separate control rooms from other areas such

    as

    communications rooms, rack rooms, process interface equipment rooms, computer

    rooms, store rooms, kitchens, toilets, mechanical rooms, electrical switchgear rooms,

    laboratories, workshops, and offices. The two-hour fire-resistant separation shall be of

    materials or assemblies that have withstood a fire test exposure per NFPA 251.

    6 7 Fixed fire protection shall meet the requirements

    of

    NFPA

    75

    for control rooms and

    multiple occupancy buildings that contain control rooms.

    6 8

    f

    a raised access, modular type computer floor

    is

    used, the floor components shall meet

    the fire-resistant requirements of the IBe.

    a) Smoke detectors shall be provided at internals under the floor that meet NFPA 72

    b) Ventilation under the floor shall be adequate

    to

    meet the requirements of the wiring

    and other components.

    6.9 Electrical power feed and communications cables to control buildings shall be

    underground to the extent possible to protect them from mechanical damage during a fire

    or explosion.

    a) All cables or conduits entering the building shall be from underground.

    b) Underground cable and conduit systems shall be designed for underground service.

    Issue

    Date:

    12161143lH

    1261 512 1

    RESTRICTED

    AI

    Rights

    reserved to

    HeIS Copying or distribution prohibited without written permission

    from HCIS

    Page 18 of 19

  • 8/18/2019 SAF-03 Plant Buildings

    19/19

    Kingdom o Saudi Arabia

    Ministry ofInterior

    High

    Commission

    for

    Industrial Security

    Secretariat

    General

    SAF 03 Plant Buildings

    ~ \ . . 0 \ ; ; ~ \ j