saf-03 plant buildings
TRANSCRIPT
-
8/18/2019 SAF-03 Plant Buildings
1/19
KINGDOM OF S UDI R BI
MINISTRY OF INTERIOR
HIGH COMMISSION OR INDUSTRI L SECURITY
S FETY ND FIRE PROTECTION DIRECTIVES
OR
INDUSTRI L F CILITIES
SAF 03
Plant Buildings
Issue
Date: 1216 1431H
126 0512010
RESTRI TED
All Rights
reserved to
HCIS Copying
or distribution
prohibited
without written
permission from
efS
-
8/18/2019 SAF-03 Plant Buildings
2/19
Kingdom of Saudi Arabia
Ministry ofinterior
High Commission for Industrial Security
Secretariat General
SAF 03
Plant
Buildings
TABLE OF
CONTENTS
Administration
1 I Scope
1.2 Application
1 3
Conflicts and Deviations
Definitions
3
References
4
General Requirements
5 Control Buildings and Buildings
Requiring Blast Resistance
6
Other Requirements for Buildings
In Plants
Issue Date: 12 6 143lH 126105 2010
RESTRICTED
Page
3
3
3
3
5
7
13
16
~ \ . . . u \ ~ ~ \ j
W I Cr')U .,WI
4
Wl
;;.;Lo ll
ll
Rights
reserved to HCIS.
Copying
or distribution
prohibited without w ritten
permission from HCIS
Page 2 of l9
-
8/18/2019 SAF-03 Plant Buildings
3/19
Kingdom of Saudi Arabia
Ministry
ofInterior
High Commission for Industrial Security
Secretariat General
SAF-03 Plant Buildings
1. Administration
I l Scope
~ \ . . u \ ; ; ~ i )
u.,.)1
J u
l).J1 1
Wl
;;';L.) 1
This Directive provides the minimum requirements for companies and establishments
that are subject to the supervision of the High Commission for Industrial Security
(HCIS), Ministry of Interior, for all plant buildings, including but not limited to buildings
that contain control rooms, process instrumentation buildings, communications buildings,
electrical substations, operations and maintenance office buildings, maintenance shops,
storages buildings, and mosques.
1.2 Application
This Directive is applicable to all facilities, including new projects, the expansion
of
existing facilities, and upgrades. For application to existing facilities, the Owner shall
assess his facilities against the requirements of these Directives and coordinate with the
General Secretariat of the HCIS to comply with the security, safety, and fire protection
requirements according to these Directives and add to or
modifY
the existing facilities
as
required. Where the General Secretariat of the HCIS has assessed deficiencies
in
existing
facilities during a survey, comparing the current state
of
the facilities to the requirements
of
these Directives, those identified deficiencies shall be corrected by the Owner.
1.3 Conflicts and Deviations
Where implementation
of
a requirement is unsuitable or impractical, where other
equivalent company or industry Standards and Codes are followed, or where any conflict
exists between this Directive and other company standards and Codes, the deviations
shall be resolved by the General Secretariat of the HCIS. Deviations lower than the
requirements of this Directive shall be listed and submitted
in
a report of non-compliance,
with justification and rationale for not following the requirement, and approval shall be
received from the General Secretariat
of
the HCIS prior to implementation. The
documents shall be retained by the company
in
its permanent engineering files.
2.
Definitions
API: American Petroleum Institute, Website: http://api-ec.apLorg/
ASeE American Society ofCivil Engineers, Website: http://www asce org/
Issue Date: 12I6 1431H 126 05 2010
RESTRICTED
AI Rights reserved to Hers. Copying or distribution prohibited without written pennission from HCIS
Page 3 of 19
-
8/18/2019 SAF-03 Plant Buildings
4/19
Kingdom of Saudi Arabia
Ministry ofinterior
High Commission for Industrial Security
Secretariat General
SAF-03 Plant Bnildings
~ \ 0 \ ; ~ \ j J
u
\ WI -\;II
;;....w\
t.,, 1j
ASHRAE: American Society of Heating, Refrigerating, and Air-Conditioning
Engineers, Website: http://www.ashrae.org/
Fire-Scenario Envelope: A three-dimensional space into which fire-potential equipment
can release flammable or combustible fluids capable of burning long enough and with
enough intensity to cause substantial property damage see API PUB 2218).
FM FM Global Factory Mutual),
Website: http://www.fmglobal.com/
Fnnctional ly Significant Bnilding: Building that is required for the continued operation
and safe shut-down of the plant, such as control room, process interface building, and
substations.
Hazardons Classified) Area: Locations as defined by API RP 500, API 505, NFPA 70,
NFPA 497, or NFPA 499 which have the potential of ignitable mixtures with respect to
electrical equipment installations.
HCIS: High Commission for Industrial Security, Ministry ofInterior.
High-Population Building: Any building, such as offices, mosque, cafeteria, training
building, medical clinic, or other occupancy that can contain 25 or more people at any
time.
HVAC: Heating, Ventilation, and Air Conditioning.
ICC: International Code Council ICC) Website: http://www.iccsafe.org/
Listed: A device that is tested and certified by an independent testing lab to be suitable
for its purpose.
Manned Building: Buildings such as control rooms, operations and maintenance office
buildings, and maintenance shops where people are expected to be present to do their
jobs on a regular basis.
Noncombustible: Material that will not burn or support burning such as concrete,
masonry or steel.
Owner: Person, partnership, or company that has possession of a facility or
establishment.
Plant: Facilities used to manufacture, process, store, transport, or transfer a material or
substance.
Issue Date:
I2I611431H
26 05 2010
RESTRICTED
All Rights reserved to HCIS. Copying or distribution prohibited without written permission
from HCIS
Page 4 of 19
-
8/18/2019 SAF-03 Plant Buildings
5/19
Kingdom
of
Saudi Arabia
Ministry ofInterior
High Commission for Industrial Security
Secretariat General
~ I . . U \ ; ~ r J
,, -a ll V')U
\ WI
~ W \ ~ t . . . 1 \
SAF 03
Plant Buildings
Plant Buildings: All buildings that are within the plant property boundary.
NFPA:
National Fire Protection Association Website: http://www.nfpa.orgl
Shall: Indicates a mandatory requirement.
Should: Indicates a recommendation or that which is advised but not required.
UL Underwriters Laboratories Inc. Website: http://www.ul.com/
Unmanned Building:
Buildings which are unattended by people under normal
circumstances such as substations and process interface buildings.
3 References
This directive adopts the latest edition
of
the references listed.
PI RP 500
PI RP 505
PI RP 752
PI RP 753
SCEReport
ASHRAE 15
SHR E 52.1
ASHRAE52.2
SHRAE 55
SHR E
62 1
Issue Date:
121611431H
12610512010
Classification
of
Locations for Electrical Installations at Petroleum
Facilities Classified as Class L Division 1 and Division 2
Classification ofLocations for Electrical Installations at Petroleum
Facilities Classified as Class L Zone
0
Zone
1 and
Zone 2
Management of
Hazards Associated with Location
of
Process Plant
Buildings
Management ofHazards Associated with Location ofProcess Plant
Portable Buildings
Design ofBlast Resistant Buildings in Petrochemical Facilities
Safety Standardfor Refrigeration Systems
Gravimetric and Dust Spot Procedures for Testing Air Cleaning
Devices Used in General Ventilation for Removing Particulate
Matter
Method
of
Testing General Ventilation Air Cleaning Devicesfor
Removal Efficiency by Particle Size
Thermal Environmental Conditions for Human Occupancy
Ventilation for Acceptable Indoor ir Quality
RESTRICTED
All Rights reserved
to
HCIS
Copying or distribution prohibited
without
written
pennission
from HCIS
Page 5 of 9
-
8/18/2019 SAF-03 Plant Buildings
6/19
Kingdom of Saudi Arabia
Ministry ofInterior
High Commission for Industrial Security
Secretariat General
WI Cr SU 1.).11
1
a...W\
4;1.,. 11
SAF 03 Plant Buildings
SH
RAE
62 2
SHR E III
FM
ICCEC
ICCIBC
ICCIEBC
ICCIECC
ICCIFC
ICCIMC
ICCIPC
ICC IPSDC
ICCIRC
NFPA 10
NFPA 13
NFPA 45
NFPA
70
NFPA 72
NFPA
75
NFPA
76
NFPA 80
NFPA 90A
NFPA 221
NFPA 251
Issue Date 12161l431H /26/05/2010
Ventilation and Acceptable Indoor ir Quality in Low-Rise
Residential Buildings
Practices for Measurement Testing Adjusting and Balancing
of
Building Heating Ventilation Air-Conditioning and Refrigeration
Systems
FM
Global Property Loss Prevention Data Sheets
International Electrical Code
International Building Code
International Existing Building Code
International Energy Conservation Code
International Fire Code
International Mechanical Code
International Plumbing Code
International Private Sewage Disposal Code
International Residential Code
Portable Fire Extinguishers
Installation
of
Sprinkler Systems
Fire Protection for Laboratories Using Chemicals
National Electrical Code
National Fire Alarm Code
Protection ofInformation Technology Equipment
Telecommunications Facilities
Fire Doors and Other Opening Protectives
Installation ofAir-Conditioning and Ventilating Systems
High Challenge Fire Walls Fire Walls and Fire Barrier Walls
Fire Tests ofBuilding Construction and Materials
RESTRICTED
ll Rights reserved to
HeIS
Copying or distribution prohibited without written permission from HerS
Page 6 of 19
-
8/18/2019 SAF-03 Plant Buildings
7/19
Kingdom of Saudi Arabia
Ministry of Interior
High Commission for Industrial Security
Secretariat General
SAF-03
Plant Buildings
~ \ J J \ ; ; ~ \ J
W I
-
8/18/2019 SAF-03 Plant Buildings
8/19
Kingdom of Saudi Arabia
Ministry of Interior
High Commission for Industrial
Security
Secretariat General
SAF 03
Plant Buildings
~ \ . . U \ ¢ j
,WI
Cr )\J
\ WI ; }I
4 oW\
:\ ;\..0\1\
4.2.2 Rooms
in
functionally significant buildings that serve an important function for plant
operation, such as computer rooms, data transmission rooms, processing rooms, store
rooms, control rooms, communication rooms, battery rooms, and mechanical rooms, shall
be subdivided by two-hour fire rated walls from rooms that serve different functions,
such
as
offices. All interior finishing materials and furniture shall be made
of
noncombustible material; however, if noncombustible finishing materials are not
available, then the alternative materials used shall be
of
a limited fire-spread index rating
of 25 or less according to NFP A 255.
4.2.3 Doors and windows that penetrate fire walls or on the exterior
of
a building shall
be
fire
rated and shall be labeled with its rating of fire resistance. The doors and windows shall
identify the agency that certified the design. Fire rated doors and windows shall meet
NFPA80.
a)
Fire protection rating of a fire door presumes that the door is installed with the
appropriate frame, hardware, and other accessories required by NFPA 80.
b) Fire rated doors shall be self-closing or automatic closing, i.e. an electro-magnetic
device may be used to hold interior fire doors open provided that they are installed
on a self-closing door and allow the door to close
in
case
of
fire alarm activation.
c)
Fire rated windows shall either be
of
a fixed type or be automatic closing.
d)
Doors designated
as
security doors to buildings housing sensitive or vital equipment
or to perimeter fences or other control
of
access areas shall be constructed to meet
the appropriate security directive. However, all doors shall also meet the following
safety requirements:
1)
The number of doors shall meet the safety requirements of the IBC.
2) Doors designated
as
emergency exits shall meet the specifications
of
the IBC
for safe egress. Security measures shall not prevent safe egress from occupied
buildings.
4.2.4 A
N
AC duct penetrating a two-hour fire resistant wall required
in
4.2.3 shall be
provided with a fire rated automatic smoke and fire damper to stop smoke and fire from
spreading throughout the building. The rating
of
the automatic damper for the air duct
shall be consistent with the fire rating
ofth
wall, floor, or ceiling that
is
penetrated.
4.2.5 Roofing systems shall be fire-resistive, meeting at least Underwriters Laboratories UL)
Class A or B or Factory Mutual FM) Class 1 or 2 rating.
Issue
Date:
12 61l43lH 126 05 2010
RESTRICTED
All Rights
reserved
to HeIS Copying or distribution prohibited
without
written
pennission
from HerS
Page 8 of
19
-
8/18/2019 SAF-03 Plant Buildings
9/19
Kingdom
of
Saudi Arabia
Ministry ofInterior
High
Commission for Industrial Security
Secretariat General
SAF 03
Plant Buildings
~ J J \ ' ; Z i J
U \ WI
>4>1
a w \ : t ; v ~ \
4.2.6 Where instrument or electrical cables penetrate fire walls and partitions, the wall
openings shall be sealed with system that
is
designed to prevent passage
of
water, fire and
smoke.
All
through-penetration protection systems shall be tested and rated
as
specified
in NFPA 221.
4.2.7 Management
of
hazards to reduce risk
of
plant portable buildings due to explosion, fire,
and toxic release hazards shall meet API
RP
753. Specific portable building siting
guidelines and procedures for managing change shall
be
developed for use and location
of
portable bUildings.
4 3 Access and Egress
4.3.1 Building design shall comply with the requirements
of
the IBe Chapter
10
including
minimum size and number
of fire exits, emergency lights, and exit signs.
4.3.2 Exits shall be clearly marked
so
that they are identifiable as exits. Access to exits shall be
marked by readily visible signs where the exit or a pathway to reach the exit is not readily
apparent to the occupants.
4.3.3 There shall
be
at least two 2) means of egress from any building, room, or space except
as specifically allowed
in
the IBC. Travel distance to any means
of
egress shall not
exceed the specified distance for each type
of
occupancy.
4.3.4 I1lumination
of
the means
of
egress floors and stairs) shall be not less than
108
lux 10
foot candles), measured at the walking surfaces.
4.3.5 During a power outage, emergency egress illumination shall be provided for at least I
Y
hours where illumination shall be on average no less than 10.8 lux 1.0 foot-candle),
permitted to decline to not less than
6 5
lux 0.06 foot-candles). Emergency lighting
systems shall be supplied from storage batteries or an on-site generator set and the system
shall be installed in accordance with the requirements ofNFPA 70.
Exception: Normal and emergency egress illumination
is not required where the purpose
of
the industrial occupancy does not require routine human habitation or where the
structure
is
occupied only during daylight hours and skylights or windows provide the
required level
of
illumination.
4.3.6 Building exits shall face away from equipment handling hazardous material, if possible.
4.3.7 Emergency egress doors shall be provided with door opening hardware that is designed
for both fire and panic protection the door shall be opened by pushing on a panic bar to
Issue
Date: 12 6 1431H
126105 2010
RESTRICTED
All
Rights
reserved to HCIS Copying or distribution prohibited without written permission
from
HCIS
Page 9
ofI9
-
8/18/2019 SAF-03 Plant Buildings
10/19
Kingdom of Saudi Arabia
Ministry
ofinterior
High
Commission for
Industrial
Security
Secretariat General
SAF-03
lant
Bnildings
~ \ J . l \ / ) )
ifU
Cr )IJ \ WI
.. .'
w\
;V\..1.j1
exit or
is
designed so that the door or window readily opens outward when pushed). The
doors shall be operable from the inside without the use
of
a key or tool.
4.3.8 Exterior doors and all interior doors penetrating fire walls fire door) shall
be
equipped
with automatic, quick-acting, adjustable door closers. The doors shall be kept closed and
sign-posted to inform all workers to keep the doors closed.
4.3.9 Fire exit doors shall not be locked
in
a way that would prevent immediate exit if any
persons are inside the room or building.
4.4 Fire Detection and Protection
4.4.1 The fire detection, alarm and fire protection systems shall be fully commissioned and
tested before a building is occupied.
4.4.2 All functionally significant plant buildings such as control rooms, process interface
buildings, substations or any other buildings which are critical to the continued operation
of the plant shall be provided with a fire alarm system designed according to NFPA
72.
Fire detection and alarm systems fire panels, initiating and end devices, and associated
equipment) shall be of the addressable type, i.e. each component can be individually
identifiable at the fire panel.
a)
Fire alarms systems shall be provided with at least two independent and reliable
power supplies, one primary and one standby.
b) The primary power supply shall have a high degree of reliability. The secondary
power supply e.g. emergency generation
ndlor
battery) shall be of sufficient
capacity to operate the system for 24 hours to meet NFP A 72. The installation
of
all
power supplies to the system shall meet NFPA 70 and NFPA 72.
4.4.3 Detectors shall be installed above suspended ceilings and below raised floors
of
control
buildings, computer centers, data processing centers, and telecommunications facilities
where required to meet NFPA
75
or NFPA 76.
4.4.4 Activation
of
the building fire detection and alarm system for buildings shall produce
audible and visible alarms that can be observed from inside the building, outside the
building, and at a permanently manned location, such as control room or fire station.
4.4.5 Buildings shall be provided with the numbers
and
types
of
fire extinguishers suitable for
the hazards to meet the requirements ofNFPA
10.
a) Fire extinguishers shall be located where readily accessible
in
the event
of
a fire.
Issue Date 12 611431H 126 0512010
RESTRICTED
An Rights reserved to HCIS. Copying or distribution prohibited without written permission from HC1S
Page
10 of 19
-
8/18/2019 SAF-03 Plant Buildings
11/19
Kingdom
of
Saudi Arabia
Ministry ofInterior
High
Commission
for Industrial Security
Secretariat General
SAF 03 Plant Bnildings
4>1
;; WI < u \ ' ~ \
b) They shall be located along a normal path of travel and at exits from areas.
c) Portable fire extinguishers shall
be
installed on a hanger or bracket supplied or placed
in
cabinets or wall recesses that are clearly identified to contain a fire extinguisher.
d) Portable extinguishers shall be maintained
in
a fully charged and operable condition.
They shall be kept
in
their designated places at all times when they are not being
used.
e) Type and size
of
portable fire extinguishers shall be based on the types
of
hazards
presented by the use of the building.
f) Distribution
of
fire extinguishers
in
buildings shall depend
on
the type
of
hazard and
coverage requirement in NFP A 10 Travel distance to a fire extinguisher shall be
consistent with the type of hazard, e.g.
no
more than 23 meters for a Class A hazard
or 15 meters for a Class B hazard. Refer to NFP A
10
for more details.
4.4.6 The need for a sprinkler system or other automatic fire extinguishing system shall be
determined by the Owner based on best international fire protection practices to protect
life and property
as
specified below:
a) At a minimum, fire detection and protection systems shall be installed where required
by the BC and the IFC.
b) The design of fire protection systems shall comply with the appropriate NFPA
Standard, such as NFP A
13
for sprinkler systems and NFP A 2001 for clean agent Fire
extinguishing systems.
4.4.7 Fixed carbon dioxide (C02) fire protection systems shall not be used for manned
bUildings.
4.4.8 Fire protection shall be provided according to the SAF-4.
4.4.9 Fire protection for storage buildings shall comply with NFPA
13
4.4.1 0 Fire detection, protection, and fire prevention procedures for laboratories shall comply
with NFPA 45.
4.4.11 Fire protection
of
computer roqms, communication equipment rooms, and plant control
rooms shall comply with NFPA 75 and NFPA 76 where loss
of
function
of
computer and
telecommunications equipment and data will impact life safety, process plant safety, or
where third parties are critically affected.
Issu. Date: I2IG/1431H /26/05/2010
RESTRICTED
All Rights reserved
to
HCIS Copying
or distribution prohibited
without
written pennission from
HCIS
Page 11 ofl
-
8/18/2019 SAF-03 Plant Buildings
12/19
Kingdom
of
Saudi Arabia
Ministry
ofInterior
High Commission for Industrial
Security
Secretariat General
SAF-03
lant
Buildings
~ I . . U \ / ) )
-
8/18/2019 SAF-03 Plant Buildings
13/19
Kingdom
of
Saudi Arabia
Ministry ofInterior
High Commission for Industrial Security
Secretariat General
SAF-03
Plant Buildiugs
~ \ . . u \ ; ~ \ j
WI 0 )U \,WI < >1
t.oWI
A ; t ~ \
5.
Control Buildings
and Other
Buildings Requiring Blast Resistance
5.1 Control buildings, multiple-occupancy buildings that contain control rooms, and other
functionally significant buildings that are identified by the Owner to require equivalent
protection
in
refineries, petrochemical plants, and other types
of
facilities that produce,
process, or store flammable, toxic, or explosive substances,
shaH
be located to minimize
exposure to fire, explosion or release of hazardous materials (see Section 4.1, above).
When necessary, they shaH be made blast resistant to the extent needed to prevent
coHapse due to overpressure from a vapor cloud explosion if one were to occur from a
plant-related incident.
5.2 While the spacing and design of the control building should be guided by the principles
of API 752, the minimum spacing between a control building (or building that contains a
control room) and vessels, tanks, or other process equipment handling combustible,
flammable, toxic, or explosive materials
shaH
be 30 meters.
5.3 The control building shall be designed to prevent the entry of combustible, flammable, or
toxic liquids, gases or vapors.
5.4 Control buildings located inside
of
a plant
shaH be
single-story and without windows.
Exceptions: In plants where there
is
no explosion hazard, 5.4 does not apply or where the
Owner s engineer otherwise approves multi-story construction. Where the windows are
speciaHy designed to withstand the overpressure should an explosion occur, windows are
aHowed.
5.5 Control buildings shall be blast resistant to the extent needed to prevent collapse from a
plant-related incident. Design of blast resistant buildings shall be accomplished by a
registered or chartered professional engineer that is experienced
in
blast resistant
structural design. Simulation
of
the resultant overpressure and suction overpressure from
a potential plant related explosion shall be done using a registered or chartered
professional engineer from an engineering firm that specializes in such simulation. The
results shaH be used for the basis of structural design by a professional engineering firm.
5.5.1 The simulation shall be used to select blast overpressure and duration (impulse) for the
structural design basis.
5.5.2 The simulation shall take into account existing process equipment and future plant
expansion equipment that is likely to be installed.
Issue Date 1216 1431H 126 05 2010
RESTRICTED
AI
Rights reserved to HCIS. Copying or distribution prohibited without written pennission
from
HOS
Page \3 of
19
-
8/18/2019 SAF-03 Plant Buildings
14/19
Kingdom
o
Saudi Arabia
Ministry
ofInterior
High Commission for Industrial Security
Secretariat General
SAF-03
Plant Buildings
5.5.3 Wind and seismic loads shall not be combined with blast loading.
~ \ . . u \ ; j
,W I 0 )0 l W1
4
-
8/18/2019 SAF-03 Plant Buildings
15/19
Kingdom of Saudi Arabia
Ministry ofinterior
High
Commission for Industrial Security
Secretariat General
SAF 03 Plant Buildings
~ ~ ~ l j
W I .y u l W1 >4>1
;uWI
a ;\ ..
1\
5.6.8 Design for compression elements, such
as
load-bearing walls and exterior columns,
should consider secondary bending effects.
5.7 No combustible, flammable, or toxic material piping shall be piped into or through the
control building.
5.8 No process or material handling equipment, pressure vessels, storage tanks, or piping
containing combustible, flammable, or toxic materials shall be located above or under a
control room or bUilding
5.9 Offices, dining areas,
and
other types
of
rooms in the control building shall be limited to
what
is
needed for the plant to function properly. Non-essential offices, dining and
recreational rooms shall be separate from the control building and located
in
a safe
location see 4.1.3).
5.10 Exterior doors shall face away from process areas whenever possible.
5 10 1 All exterior doors, inclnding equipment access double doors, shall meet the blast
resistance requirements of the structural walls
ofth
building. Manufacturers shall certifY
that blast resistant doors are designed to withstand the intended blast loading. The doors
shall be marked with the manufacturers name and rating information.
5.10.2 External frames for blast resistant doors shall be set in grooves or anchored on all sides to
prevent doors and frames from being blown into the building
in
the event of an explosion.
Exterior doors shall open outwards and be equipped with automatic door closers. The
doors shall be kept closed and sign-posted to inform workers to keep the doors closed at
all times.
5 11
The parts
of
the ventilation and air conditioning equipment that are necessarily external
to the building shall be shielded or otherwise designed to survive any anticipated blast
effects.
5.11.1 The
fan inlet ducting shall be elevated, be free of leaks, and be protected from
mechanical damage and corrosion to prevent ingress of flammable or toxic vapors or
gases.
5.11.2 Inlet duct openings shall be minimized, arranged to be shielded from direct blast, and
prevent pressure on the top surfaces
of
suspended ceilings.
5.11.3 External louvers, their frames, and associated components shall be capable of
withstanding design blast over-pressures.
Issue
Date:
IU6 1431H
126 05 2010
RESTRICTED
AU Rights reserved
to
HCIS Copying
or
distribution
prohibited
without written
pennission
from HCIS
Page 15
of 19
-
8/18/2019 SAF-03 Plant Buildings
16/19
Kingdom o Saudi Arabia
Ministry oflnterior
High
Commission for Industrial Security
Secretariat General
SAF 03 Plant Bnildings
~ \ . . u l o J \ j
-
8/18/2019 SAF-03 Plant Buildings
17/19
Kingdom of Saudi Arabia
Ministry
ofInterior
High Commission for
Industrial Security
Secretariat General
SAF-03
Plant uildings
~ U J \ o ~ \ j
,W I ,)\J \ WI
;. »1
w
;VL,, t\
6.3.6 Building pressurization shall be monitored by a differential pressure gauge and switch
connected between the inside and outside of the building. Loss of building pressurization
shall alarm at the nearest control room.
6.3.7 The ventilation and air conditioning equipment system shall be designed to prevent the
entry
of
flammable vapors or gases in accordance with the applicable NFPA 496.
6.3.8 Any room/building requiring pressurization shall be designed to withstand
an
internal
pressure
of
no less than 6.5 millimeter water gauge 0.25 inch water gauge).
6.3.9 The ventilation and air conditioning system for buildings requiring pressurization shall
maintain an internal building positive pressure
of
at least 2.5 millimeter water gauge
0.1
inch water gauge) with all doors and other openings closed.
a) The system shall be capable of providing a minimum outward velocity of 0.30
m/sec 60 ftlmin) through all openings. All doors capable of being opened, except
equipment doors that are used infrequently, shall be considered open. An allowance
for other openings shall be included. An alarm shall activate at the control room
upon loss of pressurization below this
2.5
millimeter water gauge.
b) Outside air flow rate available for building pressurization equal to not less than two
2) air changes per hour
of
the total pressurized space with doors closed. The design
pressure shall be 6.5 millimeter water gauge 0.25 inch water).
6.3.10 Interior dry bulb design temperature shall be 22 degrees C 75 degrees F),
50
percent
relative humidity with the outside conditions based on recognized local design
conditions.
a) The thermal environmental conditions shall meet ASHRAE 55. HVAC systems
shall be capable of maintaining dry bulb temperature and relative humidity (if
applicable) within the performance range given in Table 1, ASHRAE 55, unless
stricter indoor design conditions are required.
b) The number of doors and other penetrations shall be minimized so that positive
pressure can be maintained, while at the same time, the number
of
doors shall be
adequate for safe exit per the IBC. The system shall be tested and balanced to meet
ASHRAE STD Il l .
c) Devices to read and indicate temperature, relative humidity, and the indoor/outdoor
differential pressure shall be installed in the control room.
Issue Date:
I2IGI 43 H 126 05 2010
RESTRICTED
All
Rights reserved to HClS Copying or distribution prohibited without written permission from eIS
Page
17 of 19
-
8/18/2019 SAF-03 Plant Buildings
18/19
Kingdom of Saudi Arabia
Ministry ofinterior
High Commission for Industrial Security
Secretariat General
SAF 03 Plant Buildings
WI u-- >U \ WI
4...>WI:t;t... 11
d) Air lock type entries are required to entrances normally used by personnel. Air
locks are not required for large doors used infrequently to bring in large equipment.
6.3.11 Ventilation and air conditioning equipment located in hazardous classified) areas shall
meet the requirements ofNFPA 70
6.3.12 Air-conditioning and refrigeration installations shall meet the safety requirements of
ASHRAE Standard IS.
6.4 Maximum allowable noise levels inside the an occupied room in a plant building, such as
a control room, shall
be 55
decibels
to
be achieved without hearing protection for the
occupants.
6 5 A fire detection and alarm system shall
be
installed that will monitor for fire and/ or
smoke in all rooms adjacent to the control room.
6 6 Two-hour fire-resistant separation shall separate control rooms from other areas such
as
communications rooms, rack rooms, process interface equipment rooms, computer
rooms, store rooms, kitchens, toilets, mechanical rooms, electrical switchgear rooms,
laboratories, workshops, and offices. The two-hour fire-resistant separation shall be of
materials or assemblies that have withstood a fire test exposure per NFPA 251.
6 7 Fixed fire protection shall meet the requirements
of
NFPA
75
for control rooms and
multiple occupancy buildings that contain control rooms.
6 8
f
a raised access, modular type computer floor
is
used, the floor components shall meet
the fire-resistant requirements of the IBe.
a) Smoke detectors shall be provided at internals under the floor that meet NFPA 72
b) Ventilation under the floor shall be adequate
to
meet the requirements of the wiring
and other components.
6.9 Electrical power feed and communications cables to control buildings shall be
underground to the extent possible to protect them from mechanical damage during a fire
or explosion.
a) All cables or conduits entering the building shall be from underground.
b) Underground cable and conduit systems shall be designed for underground service.
Issue
Date:
12161143lH
1261 512 1
RESTRICTED
AI
Rights
reserved to
HeIS Copying or distribution prohibited without written permission
from HCIS
Page 18 of 19
-
8/18/2019 SAF-03 Plant Buildings
19/19
Kingdom o Saudi Arabia
Ministry ofInterior
High
Commission
for
Industrial Security
Secretariat
General
SAF 03 Plant Buildings
~ \ . . 0 \ ; ; ~ \ j