samsung 2009 vrf dvm

60
Samsung Electronics Co., LTD. Head Office (Suwon Korea) 416, Maetan-3Dong, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 443-742 www.dvmsystem.com Version.1 When the revolutionary digital technology provides nature’s coolness Experience the revolutionary digital technology with Samsung’s DVM Plus III outdoor units Space for Partnership DVM 2009 SAMSUNG System Air Conditioner

Upload: emumcik

Post on 16-Nov-2014

4.501 views

Category:

Documents


13 download

DESCRIPTION

SAMSUNG VRF SYSTEM CATALOG

TRANSCRIPT

Page 1: Samsung 2009 Vrf Dvm

Samsung Electronics Co., LTD.Head Office (Suwon Korea) 416, Maetan-3Dong, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 443-742www.dvmsystem.com Version.1

When the revolutionary digital technology provides nature’s coolness

Experience the revolutionary digital technology with Samsung’s

DVM Plus III outdoor units

Space for Partnership

DVM2009

SAMSUNGSystem Air Conditioner

Page 2: Samsung 2009 Vrf Dvm

Most perfect system air conditionerRefreshing cooling and heating all year long with the world’s best efficiency that saves money

and energy. Satisfaction that only Samsung’s leading technologies can provide. Just the way

you want your system air conditioner to be, as it is custom made for you.

SAMSUNG ELECTRONICS HOME APPLIANCE PRODUCT AWARDSTechnology can contribute to the development of a greener, cleaner world andincrease quality of life. This is a philosophy we have held at Samsung for over 30 years.Ever since its establishment in 1973, Samsung Electronics has concentrated ondeveloping environmentally friendly products and has converged increasinglysophisticated digital technology with its appliance products to attain a strong technological advantage in improving consumers' quality of living with the ultimatein convenience and style.

Page 3: Samsung 2009 Vrf Dvm

Big Confidence Global Leading

Company >> SAMSUNGSince day one, Samsung Electronics has committed itself to becoming a leader in every facet of its market initiatives. The result is the growth of a brand that’s synonymous with impeccable standards, high quality products,and an unwavering dedication to the customer. Through continuous creativity and the development of highlyinnovative products, Samsung has captured the hearts and minds of customers worldwide, which will propel ourcompany and our brand well into the future.

SAMSUNG’S BRAND VALUEIn the Digital era, products are being distinguished by their

brand in addition to their functions or quality. In 1999 Samsung

Electronics has implemented its global brand communication

strategy. Since then, based on the research conducted by

Interbrand INC., USA, Samsung Electronics has become one of

the fastest growing brands equities from 6.4 billion USD (2001)

to over 17.7 billion USD (2008) and is now ranked 21st on

Interbrand's Top100 Global Brand List.

Samsung has increased its value by emphasizing technology as

a life innovator. Samsung will remain close to the customer

through its technologies contributing to a higher quality of life.

GLOBAL BUSINESS NETWORKSamsung's thrust on Product Innovation and R&D has given the company a competitive edge in the marketplace. With an

investment of over USD 4.59 billion, Samsung operates 16 R&D centers worldwide and employs 27,000 researchers of which

2,500 hold a Ph. D. As a result, Samsung has already applied for 1600 patents in the USA. The focus of the R&D center is to

customize electronics products to meet the Specific needs of consumers in that region. Samsung R&D Centers are helping the

company to continuously innovate and introduce products customized for today’s global market.

6 Global Operation Centers

10 Global Headquarters

EuropeStuttgart

CIS

Milano

ME Asia Africa

India

SW Asia

SE Asia

Delhi

ChinaKorea

ShanghaiJapan Los Angeles

Mexico

US Chicago

Latin America

Malaysia

Thailand

London

7 Design Centers

5 HA R&D Centers

2009 SAMSUNG DVM AIR CONDITIONER

Contents02 | INTRODUCTION

04

11

14

| Brand Value

| Line-up

| Main Technology

20 | OUTDOOR UNITS

22

46

| DVM PLUS III/HR

| Mini DVM

50 | INDOOR UNITS

52

62

76

86

94

98

| Wall-mounted Type

| Cassette Type

| Duct Type

| Floor & Convertible Type

| ERV System

| Accessories

100 | CONTROL SYSTEMS

102

110

112

114

117

118

| Integrated Management System

| Centralized Control System

| Individual Control System

| Building Management System

| DVM-Pro

| Accessories

Page 4: Samsung 2009 Vrf Dvm

Four Seasons of HopeSamsung's Four Seasons of Hope is about kids. It's about using the power of our brand to give something back to the

communities we serve.

Samsung's Four Seasons of Hope supports community-based foundations and charities headed by some of this country's

favorite sports legends. Samsung pledges to raise national awareness and funds for these outstanding charities and to

identify how others can also make a difference in the lives of these children and families.

Samsung Recycling DirectSM

All good things come to an end. Let's make sure it's a Green end.As technology continually evolves, so will your digital lifestyle. When you upgrade your consumer electronics, you will need

to recycle your old products responsibly. That's why we're proud to reaffirm our commitment and responsibility to recycle

DirectSM using the new Samsung Recycling program launched on October 1st, 2008.

Thinking of You.

Making industry-leading products is only part of the big picture. Our commitment to creating a better world for futuregenerations is equally as important. We strongly believe that if future generations aren't given the opportunity to succeed, we definitely won't. As a corporate citizen, we have dedicated ourselves to nurturing ourlocal communities through corporate social responsibility and co-prosperity initiatives. Samsung has also remainedsteadfast when it comes to supporting education initiatives, helping to preserve the "greening" of the planet whereyou live.

"A global leader is not only responsible for that which lies within its walls but alsofor that which lies beyond them."

Reported by GreenpeaceSamsung comes in second place with 5.7, scoring well on

chemicals and waste criteria. Samsung's score on e-waste is

helped by getting top marks for reporting recycling rates of

137% for TVs (based on past sales 10 years ago, the average

life span, since when Samsung's TV sales have increased

10-fold), 12% for PCs (based on 7 year lifespan) and 9%

for mobile phones (based on 2 year lifespan). It also scores well

on its use of recycled plastic, which is 16.1%, though only 0.2%

is post-consumer plastic, with a goal to increase to 25% by 2008.

Nokia:Clear leader after improving take-back inIndia.

SAMSUNG / Good scores on chemicalsand e-waste criteria.

Fujitsu Siemens:New deadline for removal ofBFRs and PVC but still poor on recycling.

Sony Ericsson:Good on toxic chemicals andenergy but very poor on recycling.

Sony:Good on toxic chemicals, room forimprovement on energy.

LG:Improved score on recycling and energy.

Toshiba:Improved climate policy, but poor on recycling.

Dell:Dropping down with poor scores on climate policy.

HP:Slightly improved score but no productsfree of most toxic chemicals.

Acer:Good on chemicals policy but poor onenergy policy.

Panasonic:Needs to improve recycling andamount of renewable energy.

Philips:Worst company on recycling with additional penalty for negative lobbying in Europe.

Apple:Progress on eliminating toxics from newproducts but needs to improve on recycling andenergy.

Lenovo:New US tack back scheme, but still noproducts free of worst toxic chemicals.

Motorola:Only phone company not to set atimeline for eliminating worst toxic chemicals.

Sharp:Most points on toxic chemicals, poor onrecycling and energy.

Microsoft:Very poor on recycling and energy.

Nintendo:Zero on most criteria except chemicalsmanagement and energy.

[Standard for the second quarter, 2008]

7

5.7

5.5

5.3

5.3

4.9

4.7

4.7

4.7

4.5

4.5

4.3

4.1

4.1

3.7

3.1

2.2

0.8

Eco-labels & DeclarationSamsung Electronics makes an effort to develop environment-

friendly products that minimize the negative impacts on the

environment in every aspect of its products, from raw material

procurement, production, transportation, usage, and final

disposal. Concerns for the environment are at the core of each

product development.

Samsung's environment-friendly technologies and recycling

programs have received global approval, receiving well-known

awards and recognitions worldwide.

Samsung eco mark Energy mark Korea Eco Mark Korea

Ecoflower EU Energy Star Mark TCO Sweden

Blue Angel Germany EPEAT US Eco Mark Korea 2

Page 5: Samsung 2009 Vrf Dvm

Air & Water ConservationAs a leading innovator of environment-friendly products and technologies, Samsung products already drastically

reduce the strains on nature's valuable resources. Samsung uses R-600, a natural refrigerant, and

cyclopentane insulation in its refrigerators, which do not promote global warming and does not add to the

greenhouse effect. Samsung's water-efficient washing machines also use less detergent and water without

effecting cleanliness, helping to conserve water.

Use Less, Save MoreSamsung products are energy efficient, receiving Energy Grade A+ in the EU and ENERGY STAR in the U.S.

Samsung washers with its ceramic heaters use less power, which saves you energy, money, and time. This

energy-efficient technology protects you and nature, giving you a greener lifestyle.

Global RecyclingSamsung Electronics is making significant efforts to save the environment and complies with the WEEE (Waste

Electrical and Electronic Equipment) directive by joining or establishing the recycling schemes for each country.

Samsung Eco-Friendly System Air ConditionerMaking continuous efforts to stay eco-friendly, Samsung's air

conditioners use R-410A, an environmentally friendly refrigerant to help

rid the air of pollutants and restrain the use of materials with high

global warming potential (GWP). Most Samsung products have

received Energy Grade A+ in the EU and ENERGY STAR in the U.S.

These energy-efficient air conditioners not only save you money, but

help conserve the environment.

'Eco-friendly'- SamsungPreserves the nature you live in.Thinking of you and the environment, Samsung plans for the future. Realizing your hopes for a greener, healthierlife for you and the generations that follow, Samsung's environmentally friendly technologies work to make theworld a more beautiful place.

Page 6: Samsung 2009 Vrf Dvm

10 112009 Samsung DVM Air Conditioners

1

1 2 1

1

1

1

1

1 2 1

1 2

1

2 3 2

1

2

1

1

1

1

2

1

1

2 3

3

1

3

1

1

1

2

1

1

2

1

3

1

3

1

3 4

2 1

1 2 1

1

3 2

1

1

2 3 2

1

2

1

1

1

1

1

2

1

2 3

3

1

2

1

1

2

2

1

1

2

2

2

1

3 4

Line- Up | Outdoor Units

Basic Model

High Efficiency Combination

Compact Combination

High Efficiency Combination

8HP 10HP 12HP 14HP

Model 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

Model 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

60 62 64

RVXVHT140GERVXVRT140GE

RVXVHT160GERVXVRT160GE

4HP 5HP 6HP

DVM PLUS III / DVM PLUS III HR

Line upRVXVHT080GERVXVRT080GE

DVM PLUS IIIDVM PLUS III HR

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

Compact Combination

8HP 10HP 12HP 14HP 16HP

Line upDVM PLUS IIIDVM PLUS III HR

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

RVXVHT160GERVXVRT160GE

Combination Table

Mini DVM

iF Product

Design Award

2009

Comfort &

Design Award

2008As one of the world's oldest & prestigious design

competitions, the iF product design award can look

back on a rich and long tradition. This seal of fine

design quality, has stood for qualitatively outstanding

design awards for over 50 years. And Samsung's air

conditioner with its design innovations has won the

iF product design award for the year 2009.

Samsung air conditioner continues to receive world-

wide recognition and awards, proving high quality of

the function and beauty to value and satisfy

customers' requirements.

Organized by Fiera Milano International, the Comfort

& Design Award plays the role of intermediary

between the Jury and companies participating in the

36th Mostra Convegno Expocomfort / Expobagno.

The MCE / EXPOBAGNO 2008 aimed to reward the

best product that shows a high level of

environmental quality, providing a complete

overview of the sector along the lines of "Comfort &

Living Technology".

And Samsung air conditioner won the prize conferring

a valid and professional recognition on the best

products in the ceremony .

Above awards were granted to Samsung’s MB air Conditioner

Page 7: Samsung 2009 Vrf Dvm

12 132009 Samsung DVM Air Conditioners

7K Btu/h2.2 kW

9K Btu/h2.8 kW

12K Btu/h3.6 kW

15K Btu/h4.5 kW

18K Btu/h5.6 kW

21K Btu/h6.0 kW

24K Btu/h7.1 kW

30K Btu/h9.0 kW

36K Btu/h11.2 kW

44K Btu/h12.8 kW

48K Btu/h14.0 kWType

Capacity

Wall-mountedType

Cassette Type

Duct Type

Floor & ConvertibleType

MB

Vivace

Neo Forte

(EEV) (EEV) (EEV)

Slim 1Way

2Way Cassette

Mini 4WayCassette

4Way Cassette

Slim Duct

M.S.P Duct

Console

Ceiling

Line- Up | Indoor Units

Page 8: Samsung 2009 Vrf Dvm

14 | MAIN TECHNOLOGY

16

17

18

| Overview

| Digital Hybrid System

| Heat Exchanger and New G-fin

14 152009 Samsung DVM Air Conditioners

Perfect technology for perfect air

Samsung’s leading technology from innovativethoughts has brought another masterpiece of systemair conditioner. World’s best efficiency with the evenmore stable performance creates the perfect air.

MAIN TECHNOLOGY

MAIN TECHNOLOGY01

Page 9: Samsung 2009 Vrf Dvm

OverviewDVM Plus III System Air Conditioner has a number of key technologies that improves performance.Here are the main technologies which create the perfect cooling and heating atmosphere.

Highly efficient O8Grooved tube has beenapplied to reduce pressureloss while increasing heattransfer performance toimprove COP.

Turbo intercooler(Shell andTube Type) improves coolingand heating COP andsecure reliability on longpiping installation.

DVI (Digital Vapor Injection)compressor injects optimizedmid-range pressure refrigerantto improve cooling and heating performance and efficiency.

O8 Heat Exchanger

Turbo Intercooler

DVI Compressor

Optimized fan guarddesign enhanced air flowvolume which achieved thehigh heat transfer performance withoutincreased noise.

Fan Guard

High efficiency new G-finimproved heat transfer performance and reinforce corrosion resistance.

New G-Fin

16 172009 Samsung DVM Air Conditioners

Main Technology

Digital Hybrid SystemDHS (Digital Hybrid System) is a brand new conceptsystem composed of DVI compressor, vapor injectiontechnology and turbo intercooler. These 3 factorstogether provide highly efficient performance.

DVI CompressorEfficient and reliable DVI Compressor coupled with VaporInjection technology has been applied to improve coolingand heating performance and energy efficiency.

Turbo IntercoolerTurbo intercooler (Shell & Tube Type) improved cooling andheating COP, to secure reliability on long piping installation.

Improve COP with the application of Turbo intercooler.

Adequate sub-cooling to ensure reliable operation on installationswith long piping (200m).

Sub-cooled liquid refrigerant

Low temperature gasrefrigerant

Vapor Injection Tube

Vapor Injection Port

Low temp. liquid refrigerant

Saturated liquid refrigerant

Vapor Injection TechnologyImproved cooling and heating performance and COP by anew technology of two stage compression. This technologyachieved the high heating performance and COP underthe lowest temperature, which leads the industry.

Increase refrigerant flow rates with a new Vapor Injection technology.

Improved Sub-cooling necessary for long piping runs whileincreasing cooling and heating performance and COP.

Temperature

High

Low

Page 10: Samsung 2009 Vrf Dvm

18 192009 Samsung DVM Air Conditioners

Newly Designed Fan GuardFan Guard has been optimized to improve air volume and reduce noise and vibration.

BLDC Motor, which is 2.7% more efficient than the competitors, has been applied.

Applied high static pressure propeller fan and the optimum Bell Mouth form for high external static pressure. (External static pressure: 8mmAq)

New G- FinHighly efficient new G-Fin increases heat transfer performance, reinforced corrosion resistance, and increasedoperating duration in frost condition.

Heat transfer performance improved by 13% compared to the conventional fin, even with the equivalent pressure loss.

Epoxy Acrylic Coating reinforced corrosion resistance.

Heating operation time is 1.4 times longer in frost condition due to new G-Fin.

Hydrophilic layer Acrylic resin + surfactantAnti corrosive layer

Epoxy acrylic

Raw aluminummaterial

0.3µm

2.0µm

92µm

Conventional (Louver Fin)DVM PLUS III (New G-Fin)

Wide Louver FinG - Fin

Cap

acity

, Pow

er o

utpu

t (W

) 5000

4000

3000

2000

1000

00 30

Time (min.)60 90 120

EVA

. CO

ND

tem

pera

ture

(°C) 60

50

40

30

20

10

0

-10

-20

-300 30

Time (min.)60

DVM PLUS III

Conventional Model

High Efficiency O8 Heat ExchangerEfficient O8 Grooved tube reduced pressure loss while increasing heat exchange rates to improve COP.

Groove shape is designed to be high and slim to increase heat transfer performance inside the tube.

DVM PLUS IIINew Groove Shape (High and Slim)

Competitor’sProduct

Item Improved Heat ExchangerO7 O819% ↑14.1% ↓10.3% ↓30.8% ↑same

DiameterHeat transfer surface areaPressure loss in heatexchangerInternal heat transfer performancePressure resistance

EvaporationCondensation

Main Technology

O8 Heat Exchanger and New G-fin

Page 11: Samsung 2009 Vrf Dvm

20 212009 Samsung DVM Air Conditioners

Efficiently provide the perfect air

For commercial places and high buildings, no matterhow high or how large, DVM Plus III will be the perfectfit for any type of space. The world’s largest capacity,longest piping length and the highest efficiency rate,DVM Plus III will be perfect fit for any type of space.

OUTDOOR UNITS

OUTDOOR UNITS02

20 | OUTDOOR UNITS

22

46

| DVM PLUS III/HR

| Mini DVM

Page 12: Samsung 2009 Vrf Dvm

DVM PLUS III / DVM PLUS III HR DVM Plus III outdoor units have world’s largest capacity with the highest efficientcooling and heating performance. Every single DVM PLUS III HR outdoor unit canoperate simultaneously in cooling or heating mode.

22 232009 Samsung DVM Air Conditioners

OUTDOOR UNITS

Comparison to Inverter IIIDVM PLUS IIIDVM PLUS III

Company ACompany A

Up to 56HP

Only 36HP

DVM PLUS IIIDVM PLUS III

Company ACompany A

Up to 64HP

Only 54HP

HighEfficiency

Combinations

Compact Combinations

1

1 2 1

1

1

1

1

1 2 1

1 2

1

2 3 2

1

2

1

1

1

1

2

1

1

2 3

3

1

3

1

1

1

2

1

1

2

1

3

1

3

1

3 4

2 1

1 2 1

1

3 2

1

1

2 3 2

1

2

1

1

1

1

1

2

1

2 3

3

1

2

1

1

2

2

1

1

2

2

2

1

3 4

Model

High Efficiency Combination

Compact Combination

High Efficiency Combination

8HP 10HP 12HP 14HP

Model 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

Model 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

60 62 64

RVXVHT140GERVXVRT140GE

RVXVHT160GERVXVRT160GE

Line upRVXVHT080GERVXVRT080GE

DVM PLUS IIIDVM PLUS III HR

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

Compact Combination

8HP 10HP 12HP 14HP 16HP

Line upDVM PLUS IIIDVM PLUS III HR

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

RVXVHT160GERVXVRT160GE

Combination Table

Line-Up

Page 13: Samsung 2009 Vrf Dvm

The Smallest Foot Print AreaThe world’s smallest foot print provides smallest installation space which saves incredible amount of time.

High COPHigh efficiency DVM PLUS III has improved average cooling andheating COP compared to conventional products and achieved theworld’s Top Class energy efficiency

DHS(Digital Hybrid System) technology increased refrigerant flow rateand evaporation enthalpy difference.

Wide O8 Grooved pipe and G-Fin increased heat exchange efficiency.

The best BLDC Motor in the industry and Optimum Fan Guard designincreased efficiency.

ConventionalConventional

DVM PLUS IIIDVM PLUS III

Company ACompany A

Company ACompany A

3.81 11%

10%

4.23

4.15

ConventionalConventional

DVM PLUS IIIDVM PLUS III

3.73

4.10

4.02

8HP

18HP

Model 12HP 16HPConventional Model 0.92m2 1.35m2

DVM PLUS III 0.67m2 0.92m2

Comparison to Conventional Model 73% 68%

16HP

Approx. 32%reduction

1.35m2 0.92m2

Conventional Model DVM PLUS III

ConventionalModel

DVMPLUS III

8HP 10HP 12HP 14HP 16HP

27% reduction32% reduction

Space Saving

8~48HP 8~64HP

Conventional Model DVM PLUS III

The World’s Largest CapacitySamsung has achieved world’s largest capacity of 64HP by combining maximum 4 outdoor units with 5 different capacities. (8, 10, 12, 14 and 16HP) Many combinations of heat pump or heat recovery type support up to 64 indoor units to provide consumers a variety of choices for any installation condition.

Compact combinations (8~64 HP) : Combination with the model requiring the smallest installation space.

High-Efficiency combinations (16~56 HP) : Combination with high-efficiency model.

Digital Unit ModuleDigital Unit Module combination enables the system to alternatecompressor operation to prolong each compressor’s life cycleand improves COP with part loads

Control the compressor capacity precisely.

Ensure long life cycle by alternating operation of the DVI compressors.

Improve COP using multiple heat exchangers of outdoor units at partloads.

DVIScroll

FVIScroll

DVIScroll

FVIScroll

A unit B unit

The World’s Longest Piping Length

The longest pipinglength : 220m(Equivalent Length)

Height differencesbetween indoor &

outdoor units : 50m

The first branch joint to the farthest indoor unit : 45 m(1 Size Up : 90m)Height difference between indoor units : 15m

DVM PLUS III has an actual piping length up to 200m, with the maximum piping length of 45m fromthe first branch joint to farthest indoor unit, thereby providing more convenience and flexibility forinstallation in commercial buildings.

Summary The longest piping length : 220m (Equivalent Length)

Total piping length: 1000m

From the first branch joint to the farthest indoor unit : 90m (with one piping Size Up)

24 252009 Samsung DVM Air Conditioners

Feature

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Page 14: Samsung 2009 Vrf Dvm

26 272009 Samsung DVM Air Conditioners

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Free InstallationDVM Plus III/HR provides the degree of freedom from priority of capacity when installing outdoor units in module.

DVM PLUS III

No limits.

8HP(Digital Unit)

14HP(Digital Unit)

10HP(Digital Unit)

Conventional model

A digital outdoor unit with the largestcapacity should come last.

8HP(Fixed Unit)

10HP(Fixed Unit)

14HP(Digital Unit)

External Static PressureTo respond to a range of various installation environments, DVM PLUS III isdesigned to be used even in external static pressure of 8 mmAq.

Automatic Piping Length RecognitionAuto piping length recognition system saves time with no additional settings and performs the optimum operation inaccordance with piping length.

Lead-Free and RoHs

Refrigerant Leakage PreventionTo prevent refrigerant leakage, we provide a solution to diagnose any refrigerant leakage during product operation. Also, changing service valves from flange typeto brazed type further prevents refrigerant leakage.

RoHs ComplianceAlthough RoHS restriction only applies to small and large household electronics, IT equipment, lightings, power train, toys, leisure and sportsequipment, and vending machines. Samsung expands the RoHS restrictioninto its entire range of products based on its own environmental policies.

Lead-FreeDVM Plus III is an eco-friendly product that prevents pollutionproblems caused by the use of lead, by applying lead-freeindoor and outdoor PCBs.

Heating

HeatingCooling

Cooling

Heating

Cooling

MCU(Mode Change Unit)

As DVM PLUS III HR allows a simultaneouscooling and heating operation with one system,there is variety of applications.

Great for places where simultaneous cooling andheating operation is required. (Hotels, nursinghomes, conference rooms, etc.)

For seasonal air-conditioning which may need asimultaneous cooling and heating operation.

In case of medium and large office, DVM PLUS IIIHR satisfies cooling and heating operation simultaneously for the requirements of interiorand perimeter zone.

DVM PLUS III HR Versatile Application

Company A

An outdoor unit with the largest capacityshould come first.

14HP 10HP 8HP

Optimal operation by automatic piping length recognition

Off OffOn On

L

On

> >

Feature

Page 15: Samsung 2009 Vrf Dvm

28 292009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

Basic ModelModel

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

DVM PLUS III DVM PLUS III HR

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

8

22.4

76,400

25.2

86,000

5.76

5.51

25

3/380~415/50

HP/HR

3.89

4.57

Propeller/BLDC

9.52

19.05

15.88

-

200

50 (40)

R410A

7.5

57

240

242

253

255

880x1,703x765

948x1,868x832

-5~43

-20~24

10

28.0

95,500

31.5

107,500

7.78

7.16

30

3/380~415/50

HP/HR

3.60

4.40

Propeller/BLDC

9.52

22.23

19.05

-

200

50 (40)

R410A

7.5

58

240

242

253

255

880x1,703x765

948x1,868x832

-5~43

-20~24

12

33.6

114,600

37.8

129,000

10.40

9.40

40

3/380~415/50

HP/HR

3.23

4.02

Propeller/BLDC

12.70

25.40

22.23

-

200

50 (40)

R410A

7.5

60

240

242

253

255

880x1,703x765

948x1,868x832

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Model

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

DVM PLUS III DVM PLUS III HR

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

RVXVHT140GERVXVRT140GE

RVXVHT160GERVXVRT160GE

14

39.2

133,800

44.1

150,500

11.00

10.40

40

3/380~415/50

HP/HR

3.56

4.24

Propeller/BLDC

12.70

25.40

22.23

-

200

50 (40)

R410A

11.0

60

320

323

337

340

1,200x1,703x765

1,268x1,868x832

-5~43

-20~24

16

44.8

152,900

50.4

172,000

14.80

15.00

50

3/380~415/50

HP/HR

3.03

3.36

Propeller/BLDC

12.70

28.58

22.23

-

200

50 (40)

R410A

11.0

60

320

323

337

340

1,200x1,703x765

1,268x1,868x832

-5~43

-20~24

Page 16: Samsung 2009 Vrf Dvm

30 312009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

Module Type - High Efficiency

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

16HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

2

16

44.8

152,800

50.4

172,000

11.52

11.02

50

3/380~415/50

HP/HR

3.89

4.57

Propeller/BLDC

12.70

28.58

22.23

6.35

200

50 (40)

R410A

7.5x2

60

240x2

242x2

253x2

255x2

(880x1,703x765)x2

(948x1,868x832)x2

-5~43

-20~24

18HP

1

1

18

50.4

171,900

56.7

193,500

13.54

12.67

50

3/380~415/50

HP/HR

3.72

4.48

Propeller/BLDC

15.88

28.58

25.40

6.35

200

50 (40)

R410A

7.5x2

60

240x2

242x2

253x2

255x2

(880x1,703x765)x2

(948x1,868x832)x2

-5~43

-20~24

20HP

2

20

56.0

191,000

63.0

215,000

15.56

14.32

60

3/380~415/50

HP/HR

3.60

4.40

Propeller/BLDC

15.88

28.58

25.40

6.35

200

50 (40)

R410A

7.5x2

61

240x2

242x2

253x2

255x2

(880x1,703x765)x2

(948x1,868x832)x2

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

22HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

1

22

61.6

210,100

69.3

236,500

18.18

16.56

60

3/380~415/50

HP/HR

3.39

4.18

Propeller/BLDC

15.88

28.58

25.40

6.35

200

50 (40)

R410A

7.5x2

62

240x2

242x2

253x2

255x2

(880x1,703x765)x2

(948x1,868x832)x2

-5~43

-20~24

24HP

3

24

67.2

229,200

75.6

258,000

17.28

16.53

75

3/380~415/50

HP/HR

3.89

4.57

Propeller/BLDC

15.88

28.58

25.40

6.35

200

50 (40)

R410A

7.5x3

62

240x3

242x3

253x3

255x3

(880x1,703x765)x3

(948x1,868x832)x3

-5~43

-20~24

26HP

2

1

26

72.8

248,300

81.9

279,500

19.30

18.18

75

3/380~415/50

HP/HR

3.77

4.50

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

7.5x3

63

240x3

242x3

253x3

255x3

(880x1,703x765)x3

(948x1,868x832)x3

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Page 17: Samsung 2009 Vrf Dvm

32 332009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

Module Type - High Efficiency

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

28HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

2

28

78.4

267,400

88.2

301,000

21.32

19.83

75

3/380~415/50

HP/HR

3.68

4.45

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

7.5x3

63

240x3

242x3

253x3

255x3

(880x1,703x765)x3

(948x1,868x832)x3

-5~43

-20~24

30HP

3

30

84.0

286,500

94.5

322,500

23.34

21.48

100

3/380~415/50

HP/HR

3.60

4.40

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

7.5x3

63

240x3

242x3

253x3

255x3

(880x1,703x765)x3

(948x1,868x832)x3

-5~43

-20~24

32HP

2

1

32

89.6

305,600

100.8

344,000

25.96

23.72

100

3/380~415/50

HP/HR

3.45

4.25

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

7.5x3

64

240x3

242x3

253x3

255x3

(880x1,703x765)x3

(948x1,868x832)x3

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

34HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

2

1

34

95.2

324,800

107.1

365,500

26.56

24.72

100

3/380~415/50

HP/HR

3.58

4.33

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

7.5x2+11x1

64

240x2+320x1

242x2+323x1

253x2+337x1

255x2+340x1

(880x1,703x765)x2+(1,200x1,703x765)x1

(948x1,868x832)x2+(1,268x1,868x832)x1

-5~43

-20~24

36HP

1

1

1

36

100.8

343,900

113.4

387,000

29.18

26.96

100

3/380~415/50

HP/HR

3.45

4.21

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x2+11x1

64

240x2+320x1

242x2+323x1

253x2+337x1

255x2+340x1

(880x1,703x765)x2+(1,200x1,703x765)x1

(948x1,868x832)x2+(1,268x1,868x832)x1

-5~43

-20~24

38HP

1

2

38

106.4

363,100

119.7

408,500

29.78

27.96

100

103/380~415/50

HP/HR

3.57

4.28

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x1+11x2

64

240x1+320x2

242x1+323x2

253x1+337x2

255x1+340x2

(880x1,703x765)x1+(1,200x1,703x765)x2

(948x1,868x832)x1+(1,268x1,868x832)x2

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Page 18: Samsung 2009 Vrf Dvm

34 352009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

Module Type - High Efficiency

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

40HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

2

40

112.0

382,200

126.0

430,000

32.40

30.20

125

3/380~415/50

HP/HR

3.46

4.17

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x1+11x2

65

240x1+320x2

242x1+323x2

253x1+337x2

255x1+340x2

(880x1,703x765)x1+(1,200x1,703x765)x2

(948x1,868x832)x1+(1,268x1,868x832)x2

-5~43

-20~24

42HP

3

42

117.6

401,400

132.3

451,500

33.00

31.20

125

3/380~415/50

HP/HR

3.56

4.24

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

11x3

65

320x3

323x3

337x3

340x3

(1,200x1,703x765)x3

(1,268x1,868x832)x3

-5~43

-20~24

44HP

3

1

44

123.2

420,300

138.6

473,000

34.34

31.88

125

3/380~415/50

HP/HR

3.59

4.35

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x3+11x1

65

240x3+320x1

242x3+323x1

253x3+337x1

255x3+340x1

(880x1,703x765)x3+(1,200x1,703x765)x1

(948x1,868x832)x3+(1,268x1,868x832)x1

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

46HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

2

1

1

46

128.8

439,400

144.9

494,500

36.96

34.12

125

3/380~415/50

HP/HR

3.48

4.25

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x3+11x1

65

240x3+320x1

242x3+323x1

253x3+337x1

255x3+340x1

(880x1,703x765)x3+(1,200x1,703x765)x1

(948x1,868x832)x3+(1,268x1,868x832)x1

-5~43

-20~24

48HP

2

2

48

134.4

458,600

151.2

516,000

37.56

35.12

125

3/380~415/50

HP/HR

3.58

4.31

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x2+11x2

65

240x2+320x2

242x2+323x2

253x2+337x2

255x2+340x2

(880x1,703x765)x2+(1,200x1,703x765)x2

(948x1,868x832)x2+(1,268x1,868x832)x2

-5~43

-20~24

50HP

1

1

2

50

140.0

477,700

157.5

537,500

40.18

37.36

150

3/380~415/50

HP/HR

3.48

4.22

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x2+11x2

66

240x2+320x2

242x2+323x2

253x2+337x2

255x2+340x2

(880x1,703x765)x2+(1,200x1,703x765)x2

(948x1,868x832)x2+(1,268x1,868x832)x2

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Page 19: Samsung 2009 Vrf Dvm

36 372009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

Module Type - High Efficiency

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

18 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

1

18

50.4

171,900

56.7

193,500

13.54

12.67

50

3/380~415/50

HP/HR

3.72

4.48

Propeller/BLDC

15.88

28.58

25.40

6.35

200

50 (40)

R410A

7.5x2

60

240x2

242x2

253x2

255x2

(880x1,703x765)x2

(948x1,868x832)x2

-5~43

-20~24

20 HP

2

20

56.0

191,000

63.0

215,000

15.56

14.32

60

3/380~415/50

HP/HR

3.60

4.40

Propeller/BLDC

15.88

28.58

25.40

6.35

200

50 (40)

R410A

7.5x2

61

240x2

242x2

253x2

255x2

(880x1,703x765)x2

(948x1,868x832)x2

-5~43

-20~24

22 HP

1

1

22

61.6

210,100

69.3

236,500

18.18

16.56

60

3/380~415/50

HP/HR

3.39

4.18

Propeller/BLDC

15.88

28.58

25.40

6.35

200

50 (40)

R410A

7.5x2

62

240x2

242x2

253x2

255x2

(880x1,703x765)x2

(948x1,868x832)x2

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Module Type - CompactModel

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

52HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

2

2

52

145.6

496,800

163.8

559,000

42.80

39.60

150

3/380~415/50

HP/HR

3.40

4.14

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x2+11x2

66

240x2+320x2

242x2+323x2

253x2+337x2

255x2+340x2

(880x1,703x765)x2+(1,200x1,703x765)x2

(948x1,868x832)x2+(1,268x1,868x832)x2

-5~43

-20~24

54HP

1

3

54

151.2

516,000

170.1

580,500

43.40

40.60

150

3/380~415/50

HP/HR

3.48

4.19

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x1+11x3

66

240x1+320x3

242x1+323x3

253x1+337x3

255x1+340x3

(880x1,703x765)x1+(1,200x1,703x765)x3

(948x1,868x832)x1+(1,268x1,868x832)x3

-5~43

-20~24

56HP

4

56

156.8

535,200

176.4

602,000

44.00

41.60

150

3/380~415/50

HP/HR

3.56

4.24

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

11x4

66

320x4

323x4

337x4

340x4

(1,200x1,703x765)x4

(1,268x1,868x832)x4

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Page 20: Samsung 2009 Vrf Dvm

38 392009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Module Type - CompactModel

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

24 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

1

24

67.2

229,300

75.6

258,000

18.78

17.56

75

3/380~415/50

HP/HR

3.58

4.31

Propeller/BLDC

15.88

28.58

25.40

6.35

200

50 (40)

R410A

7.5x1+11x1

62

240x1+320x1

242x1+323x1

253x1+337x1

255x1+340x1

(880x1,703x765)x1+(1,200x1,703x765)x1

(948x1,868x832)x1+(1,268x1,868x832)x1

-5~43

-20~24

26 HP

1

1

26

72.8

248,400

81.9

279,500

21.40

19.80

75

3/380~415/50

HP/HR

3.40

4.14

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

7.5x1+11x1

62

240x1+320x1

242x1+323x1

253x1+337x1

255x1+340x1

(880x1,703x765)x1+(1,200x1,703x765)x1

(948x1,868x832)x1+(1,268x1,868x832)x1

-5~43

-20~24

28 HP

2

28

78.4

267,600

88.2

301,000

22.00

20.80

75

3/380~415/50

HP/HR

3.56

4.24

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

11x2

63

320x2

323x2

337x2

340x2

(1,200x1,703x765)x2

(1,268x1,868x832)x2

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

30 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

1

30

84.0

286,700

94.5

322,500

25.80

25.40

100

3/380~415/50

HP/HR

3.26

3.72

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

11x2

63

320x2

323x2

337x2

340x2

(1,200x1,703x765)x2

(1,268x1,868x832)x2

-5~43

-20~24

32 HP

2

32

89.6

305,800

100.8

344,000

29.60

30.00

100

3/380~415/50

HP/HR

3.03

3.36

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

11x2

63

320x2

323x2

337x2

340x2

(1,200x1,703x765)x2

(1,268x1,868x832)x2

-5~43

-20~24

34 HP

1

2

34

95.2

324,700

107.1

365,500

28.58

25.96

100

3/380~415/50

HP/HR

3.33

4.13

Propeller/BLDC

19.05

31.75

28.58

6.35

200

50 (40)

R410A

7.5x3

64

240x3

242x3

253x3

255x3

(880x1,703x765)x3

(948x1,868x832)x3

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Page 21: Samsung 2009 Vrf Dvm

40 412009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Module Type - Compact

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

36 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

3

36

100.8

343,800

113.4

387,000

31.20

28.20

100

3/380~415/50

HP/HR

3.23

4.02

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x3

64

240x3

242x3

253x3

255x3

(880x1,703x765)x3

(948x1,868x832)x3

-5~43

-20~24

38 HP

2

1

38

106.4

363,000

119.7

408,500

31.80

29.20

125

3/380~415/50

HP/HR

3.35

4.10

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x2+11x1

64

240x2+320x1

242x2+323x1

253x2+337x1

255x2+340x1

(880x1,703x765)x2+(1,200x1,703x765)x1

(948x1,868x832)x2+(1,268x1,868x832)x1

-5~43

-20~24

40 HP

2

1

40

112.0

382,100

126.0

430,000

35.60

33.80

125

3/380~415/50

HP/HR

3.15

3.73

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x2+11x1

64

240x2+320x1

242x2+323x1

253x2+337x1

255x3+340x1

(880x1,703x765)x2+(1,200x1,703x765)x1

(948x1,868x832)x2+(1,268x1,868x832)x1

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

42 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

1

1

42

117.6

401,300

132.3

451,500

36.20

34.80

125

3/380~415/50

HP/HR

3.25

3.80

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

7.5x1+11x2

64

240x1+320x2

242x1+323x2

253x1+337x2

255x1+340x2

(880x1,703x765)x1+(1,200x1703x765)x2

(948x1,868x832)x1+(1,268x1748x832)x2

-5~43

-20~24

44 HP

2

1

44

123.2

420,500

138.6

473,000

36.80

35.80

125

3/380~415/50

HP/HR

3.35

3.87

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

11x3

65

320x3

323x3

337x3

340x3

(1,200x1,703x765)x3

(1,268x1,868x832)x3

-5~43

-20~24

46 HP

1

2

46

128.8

439,600

144.9

494,500

40.60

40.40

125

3/380~415/50

HP/HR

3.17

3.59

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

11x3

65

320x3

323x3

337x3

340x3

(1,200x1,703x765)x3

(1,268x1,868x832)x3

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Page 22: Samsung 2009 Vrf Dvm

42 432009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Module Type - CompactModel

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

48 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

3

48

134.4

458,700

151.2

516,000

44.40

45.00

125

3/380~415/50

HP/HR

3.03

3.36

Propeller/BLDC

19.05

38.10

31.75

6.35

200

50 (40)

R410A

11x3

65

320x3

323x3

337x3

340x3

(1,200x1,703x765)x3

(1,268x1,868x832)x3

-5~43

-20~24

50 HP

3

1

50

140.0

477,600

157.5

537,500

42.20

38.60

150

3/380~415/50

HP/HR

3.32

4.08

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x3+11x1

66

240x3+320x1

242x3+323x1

253x3+337x1

255x3+340x1

(880x1,703x765)x3+(1,200x1,703x765)x1

(948x1,868x832)x3+(1,268x1,868x832)x1

-5~43

-20~24

52 HP

3

1

52

145.6

496,700

163.8

559,000

46.00

43.20

150

3/380~415/50

HP/HR

3.17

3.79

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x3+11x1

66

240x3+320x1

242x3+323x1

253x3+337x1

255x3+340x1

(880x1,703x765)x3+(1,200x1,703x765)x1

(948x1,868x832)x3+(1,268x1,868x832)x1

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

54 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

1

2

54

151.2

515,900

170.1

580,500

47.78

46.56

150

3/380~415/50

HP/HR

3.16

3.65

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x2+11x2

66

240x2+320x2

242x2+323x2

253x2+337x2

255x2+340x2

(880x1,703x765)x2+(1,200x1,703x765)x2

(948x1,868x832)x2+(1,268x1,868x832)x2

-5~43

-20~24

56 HP

1

1

2

56

156.8

535,100

176.4

602,000

48.38

47.56

150

3/380~415/50

HP/HR

3.24

3.71

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x1+11x3

66

240x1+320x3

242x1+323x3

253x1+337x3

255x1+340x3

(880x1,703x765)x1+(1,200x1,703x765)x3

(948x1,868x832)x1+(1,268x1,868x832)x3

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Page 23: Samsung 2009 Vrf Dvm

44 452009 Samsung DVM Air Conditioners

Specification | DVM PLUS III / DVM PLUS III HR

OUTDOOR UNITS - DVM PLUS III / DVM PLUS III HR

Module Type - CompactModel

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

62 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

3

62

173.6

592,500

195.3

666,500

55.40

55.40

175

3/380~415/50

HP/HR

3.13

3.53

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

11x4

67

320x4

323x4

337x4

340x4

(1,200x1,703x765)x4

(1,268x1,868x832)x4

-5~43

-20~24

64 HP

4

64

179.2

611,600

201.6

688,000

59.20

60.00

175

3/380~415/50

HP/HR

3.03

3.36

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

11x4

67

320x4

323x4

337x4

340x4

(1,200x1,703x765)x4

(1,268x1,868x832)x4

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Model

Basic

Performance

Power

Power Supply

Mode *3)

COP

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating

Temp. Range

58 HP

RVXVHT080GE / RVXVRT080GE

RVXVHT100GE / RVXVRT100GE

RVXVHT120GE / RVXVRT120GE

RVXVHT140GE / RVXVRT140GE

RVXVHT160GE / RVXVRT160GE

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type/Control

Liquid

Gas

Discharge Gas (DVM PLUS III HR)

Oil (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

kW

kW

A

Ø/V/Hz

-

-

-

-

Ø,mm

Ø,mm

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Max.Length

Max.Height

DVM PLUS III

DVM PLUS III HR

DVM PLUS III

DVM PLUS III HR

1

3

58

162.4

554,200

182.7

623,500

52.18

52.16

150

3/380~415/50

HP/HR

3.11

3.50

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x1+11x3

66

240x1+320x3

242x1+323x3

253x1+337x3

255x1+340x3

(880x1,703x765)x1+(1,200x1,703x765)x3

(948x1,868x832)x1+(1,268x1,868x832)x3

-5~43

-20~24

60 HP

1

3

60

168.0

573,300

189.0

645,000

54.80

54.40

175

3/380~415/50

HP/HR

3.07

3.47

Propeller/BLDC

22.23

44.50

38.10

6.35

200

50 (40)

R410A

7.5x1+11x3

67

240x1+320x3

242x1+323x3

253x1+337x3

255x1+340x3

(880x1,703x765)x1+(1,200x1,703x765)x3

(948x1,868x832)x1+(1,268x1,868x832)x3

-5~43

-20~24

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Page 24: Samsung 2009 Vrf Dvm

Mini DVMCompact size with equally high efficiency and easy maintenance, Mini DVM is perfect for lightcommercial and residential places.

46 472009 Samsung DVM Air Conditioners

OUTDOOR UNITS

Feature

High Energy EfficiencyDigital Scroll compressor offers very high cooling and heating COP.

Compact DesignMini DVM offers easy installation with its slim and compactdesign saving installation space.

4

CO

P

3

2

1

04HP 5HP 6HP

3.33

4.05

3.04

3.87

3.053.73

Dimension

Capacity

Volume (m3)

Foot print (m2)

Height (mm)

Weight (kg)

4HP

0.39

0.35

1,128

124

5HP

0.39

0.35

1,128

125

6HP

0.39

0.35

1,128

125

Various Indoor UnitsMini DVM can be combined up to 11 stylish indoor unitsblending with any interior design.

Easy MaintenanceMini DVM makes it possible to control compressor, PCB, EEVon front panel allowing simple and effortless maintenance. It is possible to react promptly to errors because they are displayed on LED of the outdoor units by error codes.

Cooling

Heating

Wide CompatibilityMini DVM can be controlled with control systems which is

the same as DVM PLUS III and FJM

High ReliabilityMini DVM is highly reliable with adopted Digital ScrollCompressor which can be controlled easily.Because Digital Scroll Compressor needs just one controlPCB, it achieves simple structure and high reliability.

• Ø1, 220~240V, 50Hz (4/5HP)• Ø3, 380~415V, 50Hz (5/6HP)

Page 25: Samsung 2009 Vrf Dvm

48 492009 Samsung DVM Air Conditioners

Specification | Mini DVM

OUTDOOR UNITS - Mini DVM

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode

COP

Compressor

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating Temp.

Range

RVXMHF040EA

Horse Power

Capacity

Nominal Running

Current

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type

Piston Displacement

Output

Lubricant

Type

Output

Airflow Rate

Liquid (Flare)

Gas (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure(Cooling/Heating) *3)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

A

A

kW

kW

A

Ø/V/Hz

-

-

-

-

cc/Rev

kW

-

cc

-

W

m3/min

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Cooling

Heating

Type

Charging

Max. Length

Max. Height

4

12.5

42,600

14.5

49,400

19.0

18.0

3.75

3.58

30

1/220~240/50

Heat Pump

3.33

4.05

Digital Scroll

58.10

-

3MAF POE

1,893

Propeller

200x2

105

9.52

15.88

100

30

R410A

5.5

55/56

124

132

932x1,128x375

1,091x1,286x472

-5~43

-20~24

RVXMHF050EA

5

14.0

47,700

16.0

54,500

22.4

20.1

4.60

4.13

30

1/220~240/50

Heat Pump

3.04

3.87

Digital Scroll

62.98

-

3MAF POE

1,893

Propeller

200x2

105

9.52

15.88

100

30

R410A

5.5

55/57

125

133

932x1,128x375

1,091x1,286x472

-5~43

-20~24

RVXMHF050GA

5

14.0

47,700

16.0

45,500

8.5

7.8

4.61

4.13

20

3/380~415/50

Heat Pump

3.04

3.87

Digital Scroll

67.13

-

3MAF POE

1,893

Propeller

200x2

105

9.52

15.88

100

30

R410A

5.5

55/57

125

133

932x1,128x375

1,091x1,286x472

-5~43

-20~24

RVXMHF060GA

6

16.0

54,500

18.0

61,400

11.0

9.9

5.24

4.82

20

3/380~415/50

Heat Pump

3.05

3.73

Digital Scroll

77.20

-

3MAF POE

1,774

Propeller

220x2

105

9.52

15.88

100

30

R410A

5.5

57/60

125

133

932x1,128x375

1,091x1,286x472

-5~43

-15~24

Model

Notes

*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode

COP

Compressor

Fan

Piping

Connections

Refrigerant

Sound

Set Size

Operating Temp.

Range

Horse Power

Capacity

Nominal Running

Current

Nominal Input

Circuit Breaker (MCCB/ELB)

Cooling

Heating

Type

Piston Displacement

Output

Lubricant

Type

Output

Airflow Rate

Liquid (Flare)

Gas (Flare)

Installation

Limitation

Type

Factory Charging

Sound Pressure(Cooling/Heating) *3)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Cooling

Heating

HP

kW

Btu/h

kW

Btu/h

A

A

kW

kW

A

Ø/V/Hz

-

-

-

-

cc/Rev

kW

-

cc

-

W

m3/min

Ø,mm

Ø,mm

m

m

-

kg

dB(A)

kg

kg

mm

mm

ºC

ºC

Cooling *1)

Heating *2)

Cooling

Heating

Cooling

Heating

Type

Charging

Max. Length

Max. Height

Model RVMMH120EZ

4

12.0

40,900

14.0

47,700

18.0

18.0

3.56

3.58

-

1/220~240/50

Heat Pump

3.37

3.91

Digital Scroll

-

-

SONTEX 200LT

-

Propeller

-

95

9.52

19.05

70

30

R22

6.5

55/56

124

132

932x1,128x375

1,091x1,286x472

-5~43

-15~24

RVMMH120GZ

4

12.0

40,900

14.0

47,700

6.5

6.4

3.80

3.58

-

3/380~415/50

Heat Pump

3.16

3.91

Digital Scroll

82.59

-

SONTEX 200LT

1,890

Propeller

-

95

9.52

19.05

70

30

R22

6.5

55/56

124

132

932x1,128x375

1,091x1,286x472

-5~43

-15~24

RVMMH140EZ

5

14.0

47,700

16.0

54,500

22.5

21.5

4.65

4.50

-

1/220~240/50

Heat Pump

3.01

3.56

Digital Scroll

93.03

-

SONTEX 200LT

1,890

Propeller

-

95

9.52

19.05

70

30

R22

6.5

55/57

125

133

932x1,128x375

1,091x1,286x472

-5~43

-15~24

RVMMH140GZ

5

14.0

47,700

16.0

54,550

8.5

8.0

4.90

4.30

-

3/380~415/50

Heat Pump

2.86

3.72

Digital Scroll

98.06

4.2

SONTEX 200LT

1,890

Propeller

-

95

9.52

19.05

70

30

R22

6.5

55/57

125

133

932x1,128x375

1,091x1,286x472

-5~43

-15~24

RVMMH160GZ

6

16.0

54,500

18.0

61,400

10.2

9.9

5.55

5.20

-

3/380~415/50

Heat Pump

2.89

3.46

Digital Scroll

107.80

-

SONTEX 200LT

1,890

Propeller

-

95

9.52

19.05

70

30

R22

6.5

57/60

125

133

932x1,128x375

1,091x1,286x472

-5~43

-15~24

Page 26: Samsung 2009 Vrf Dvm

50 512009 Samsung DVM Air Conditioners

Spread the perfect air to every corner

Each of Samsung’s indoor units has their own individual unique feature to provide the perfect airthroughout the entire space. Indoor units designed tofit all the different type of space. It will be like havingcustomized air conditioner designed just for you.

INDOOR UNITS

INDOOR UNITS03

50 | INDOOR UNITS

52

62

76

86

94

98

| Wall-mounted Type

| Cassette Type

| Duct Type

| Floor & Convertible Type

| ERV System

| Accessories

Page 27: Samsung 2009 Vrf Dvm

Wall-mounted type Air conditionersSamsung’s wall-mounted type air conditioners not only have stylish and sophisticated designs, but it

also concerns about high performance and health. Samsung’s wall-mounted type air conditioners

represent cool, clean and healthy freshness in everyday living.

52 532009 Samsung DVM Air Conditioners

MB Vivace Neo-Forte

Wall-mounted Type Line-Up

INDOOR UNITS

MPI Zone (MB/Vivace)

Creation of an Intensely Purified Zone Protection against disease Safe from allergy-causing agents Controls active oxygen which can cause disease,cancer, and accelerated aging

Do you know that harmful substances andviruses breed in the space you live in?

How Micro Plasma Ion Systemtechnology Works

Health Care System 5-Step Air Purifying System

Micro Plasma Ion improves your IndoorAir Quality and eliminates all your worries.

Active hydrogen /Oxygen ions

Active hydrogen and oxygen ionsare generated

Harmful substancesCombines with

Harmful substancesOH radical, Harmfulviruses and bacteria.

Harmlesswater

Turns into harmless water

Health Care System (MB)

Good’sleep II (MB/Neo Forte)

Best Temperature for deep sleepAccording to the stage of sleep, temperatures are adjusted so you fall into deep sleep faster and get up morerefreshed in the morning for a great start of your day.

1. Falling asleep stage: Eases you into sleep by dropping the temperature.2. Sound sleep stage: Relaxes your body and raises your temperature slightly.3. Wake up stage: Allows you to wake up from comfortable intermittent air and it makes you feel refresh.

MPI Zone (Optional)Stage 1

Stage 1 Auto Roof Shutter(MB)

Stage 3

Stage 2

Step 5

Deodorizing filterStep 4

DNA or Catechin FilterStep 3

Silver Coated Evaporator(Optional)

Step 2

Silver Coated FilterStep 1

The Samsung air conditioner is all what you needto keep your air consistently clean and fresh.

The Auto Roof Shutter keeps dirt from gettinginside.

Stage 2 MPI (Micro Plasma Ion)Biological contaminants and various pathogenssuch as bacteria, viruses, and molds are removed.

Stage 3 DNA filter & 5 step filterExogenous endocrine-disrupting chemicals, hazardous materials, and other harmful chemicals are removed.

Page 28: Samsung 2009 Vrf Dvm

Auto Roof Shutter (2.8/3.6kW)This unique air conditioner automatically seals off to preventdirt infiltration when not in operation.

DNA FilterIt is a new technology that screens selectively for only toxicagents. This enables a smarter and effective air managementcompared to other filters.

MPI (Micro Plasma Ion)The world's first technology that generates active hydrogenatoms together with oxygen ions to improve your Indoor AirQuality. It protects you from harmful particles and virusesexisting in the air.

Good’sleep IIInnovative technology developed to control the air temperatureduring your sleep and maintain optimum skin temperature toenjoy a comfortable sleep and also a refreshed wake up.

Deodorizing filterIncorporated with activated carbon, the Deodorizing Filterefficiently adsorbs cigarette smoke, pet odors and otherunpleasant odors.

Silver Coated EvaporatorThe fins of the evaporator are triple coated with environmentallyfriendly materials (2 layers of chrome-free silica, 1 layer of Silvercoating) to ensure efficient removal of condensation and toguarantee the production of clean and fresh air.

54 552009 Samsung DVM Air Conditioners

MBThe polished design, luxurious pearl color and misty blue light add sophistication and style to your space.

INDOOR UNITS - WALL-MOUNTED TYPE

Auto Roof Shutter(2.8/3.6kW) Specification | MB

MPI (Micro Plasma Ion) DNA Filter Good’sleep II

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

*5) Optional Accessory

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

AVXWBH028EE AVXWBH036EE AVXWBH056EE AVXWBH071EE

3.6

12,200

4.0

13,600

30

0.19

1/220~240/50

HP/HR

35 / 21

Cross Flow Fan

10.0

10.0

R410A

EEV

6.35

12.70

ID 18 hose

10.2

11.5

900x304x185

963x349x247

Filter (Washable)

ARH-1364

5.6

19,100

6.3

21,400

50

0.3

1/220~240/50

HP/HR

40 / 30

Cross Flow Fan

12.0

12.0

R410A

EEV

6.35

12.70

ID 18 hose

13.0

16.0

1,100x307x225

1,157x381x292

Filter (Washable)

ARH-1364

6.8

23,200

7.0

23,800

50

0.3

1/220~240/50

HP/HR

41 / 30

Cross Flow Fan

13.0

13.0

R410A

EEV

9.52

15.88

ID 18 hose

13.0

16.0

1,100x307x225

1,157x381x292

Filter (Washable)

ARH-1364

2.8

9,500

3.2

10,900

30

0.18

1/220~240/50

HP/HR

31 / 20

Cross Flow Fan

9.0

9.0

R410A

EEV

6.35

12.70

ID 18 hose

10.2

11.5

900x304x185

963x349x247

Filter (Washable)

ARH-1364

Cooling *1)

Heating *2)

Optional Accessories

MWR-WS0MWR-WE00 MWR-TH01

9.K Btu/h2.8 kW

12K Btu/h3.6 kW

18K Btu/h5.6 kW

MWR-SH00

Individual Controllers

Wireless Remote Controller

Line-Up

Standard Accessories

24K Btu/h7.1 kW

Page 29: Samsung 2009 Vrf Dvm

MPI (Micro Plasma Ion)The world's first technology that generates active hydrogenatoms together with oxygen ions to improve your Indoor AirQuality. It protects you from harmful particles and virusesexisting in the air.

Good’sleep IIInnovative technology developed to control the air temperatureduring your sleep and maintain optimum skin temperature toenjoy a comfortable sleep and also a refreshed wake up.

Deodorizing filterIncorporated with activated carbon, the Deodorizing Filterefficiently adsorbs cigarette smoke, pet odors and otherunpleasant odors.

Silver Coated EvaporatorThe fins of the evaporator are triple coated with environmentallyfriendly materials (2 years of chrome-free silica, 1 layer of Silvercoating) to ensure efficient removal of condensation and toguarantee the production of clean and fresh air.

56 572009 Samsung DVM Air Conditioners

Vivace (Shadow Mirror)The Samsung Vivace air conditioner brings a taste of the future into your home. With advanced technology and a flatsmoked mirror panel, this air conditioner is a modern elegance.

INDOOR UNITS - WALL-MOUNTED TYPE

MPI (Micro Plasma Ion) Good’sleep II

Shadow Mirror Hidden Display Trim-less Design

Catechin filterCatechin, extracted from green tea, is contained in the filterand deactivates captured bacteria and unpleasant odors.

Optional Accessories

7K Btu/h2.2 kW

9K Btu/h2.8 kW

Line-Up

Standard Accessories

Specification | Vivace (Shadow Mirror)

12K Btu/h3.6 kW

18K Btu/h5.6 kW

24K Btu/h7.1 kW

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

*5) Optional Accessory

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

AVXWVH022EE

2.2

7,500

2.5

8,500

30

0.13

1/220~240/50

HP/HR

31 / 21

Cross Flow Fan

7.0

7.3

R410A

EEV *5)

6.35

12.70

ID 18 hose

8.5

11.5

825x285x189

900x349x252

Filter (Washable)

ARH-1364

AVXWVH028EE

2.8

9,500

3.2

10,900

30

0.18

1/220~240/50

HP/HR

31 / 21

Cross Flow Fan

7.0

7.3

R410A

EEV *5)

6.35

12.70

ID 18 hose

8.5

11.5

825x285x189

900x349x252

Filter (Washable)

ARH-1364

AVXWVH036EE

3.6

12,200

4.0

13,600

35

0.19

1/220~240/50

HP/HR

35 / 21

Cross Flow Fan

8.2

8.8

R410A

EEV *5)

6.35

12.70

ID 18 hose

8.5

11.5

825x285x189

900x349x252

Filter (Washable)

ARH-1364

AVXWVH056EE

5.6

19,100

6.3

21,400

50

0.30

1/220~240/50

HP/HR

40 / 30

Cross Flow Fan

13.3

14.0

R410A

EEV *5)

6.35

12.70

ID 18 hose

12.0

15.0

1,065x298x218

1,137x377x299

Filter (Washable)

ARH-1364

AVXWVH071EE

6.8

23,200

7.0

23,800

50

0.30

1/220~240/50

HP/HR

41 / 30

Cross Flow Fan

13.3

14.0

R410A

EEV *5)

9.52

15.88

ID 18 hose

12.0

15.0

1,065x298x218

1,137x377x299

Filter (Washable)

ARH-1364

Individual Controllers

Wireless Remote Controller

MWR-WS0MWR-WE00 MWR-TH01 MWR-SH00

Page 30: Samsung 2009 Vrf Dvm

Specification | Neo Forte (EEV)

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

*5) Optional Accessory

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

AVXWWH022EE AVXWWH028EE AVXWWH036EE

2.2

7,500

2.5

8,500

-

-

1/220-240/50

HP / HR

34/25

Cross Flow Fan

-

-

R410A

Internal EEV

6.35

12.70

ID 18 hose

-

-

825x285x189

900x349x252

Filter (Washable)

ARH-465

2.8

9,500

3.2

10,900

-

-

1/220-240/50

HP / HR

34/25

Cross Flow Fan

-

-

R410A

Internal EEV

6.35

12.70

ID 18 hose

-

-

825x285x189

900x349x252

Filter (Washable)

ARH-465

3.4

11,600

-

-

-

-

1/220-240/50

HP / HR

38/25

Cross Flow Fan

-

-

R410A

Internal EEV

6.35

12.70

ID 18 hose

-

-

825x285x189

900x349x252

Filter (Washable)

ARH-465

Good’sleep IIInnovative technology developed to control the air temperatureduring your sleep and maintain optimum skin temperature toenjoy a comfortable sleep and also a refreshed wake up.

Deodorizing filterIncorporated with activated carbon, the Deodorizing Filterefficiently adsorbs cigarette smoke, pet odors and otherunpleasant odors.

Silver Coated EvaporatorThe fins of the evaporator are triple coated with environmentallyfriendly materials (2 years of chrome-free silica, 1 layer of Silvercoating) to ensure efficient removal of condensation and toguarantee the production of clean and fresh air.

58 592009 Samsung DVM Air Conditioners

Neo ForteDesign incorporates a clean and fashionable front panel with a unique silver accent line that adds a strongimpression and a stylish touch to the whole design.

INDOOR UNITS - WALL-MOUNTED TYPE

Good’sleep II

Catechin filterCatechin, extracted from green tea, is contained in the filterand deactivates captured bacteria and unpleasant odors.

Clean-Cut Front Panel Silver Accent LineBottom OpeningFront Panel

Optional Accessories

Line-Up

Standard Accessories

7K Btu/h2.2 kW

9K Btu/h2.8 kW

12K Btu/h3.6 kW

18K Btu/h5.6 kW

24 Btu/h7.1 kW

Individual Controllers

Wireless Remote Controller

MWR-WS0MWR-WE00 MWR-TH01 MWR-SH00

Page 31: Samsung 2009 Vrf Dvm

Specification | Neo Forte

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

*5) Optional Accessory

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

AVXWNH056EE AVXWNH071EE

5.6

19,100

6.3

21,400

45

0.27

1/220~240/50

HP/HR

40/30

Cross Flow Fan

12.0

13.0

R410A

External EEV *5)

6.35

12.70

ID 18 hose

13.0

16.0

1,065x298x218

1,137x377x299

Filter (Washable)

ARH-465

6.8

23,200

7.0

23,800

50

0.30

1/220~240/50

HP/HR

41/30

Cross Flow Fan

14.0

15.0

R410A

External EEV *5)

9.52

15.88

ID 18 hose

13.0

16.0

1,065x298x218

1,137x377x299

Filter (Washable)

ARH-465

Specification | Neo Forte

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

*5) Optional Accessory

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

AVXWNH022EE

2.2

7,500

2.5

8,500

25

0.18

1/220~240/50

HP/HR

32/23

Cross Flow Fan

7.8

8.2

R410A

External EEV *5)

6.35

12.70

ID 18 hose

7.8

9.4

825x285x189

900x349x252

Filter (Washable)

ARH-463

AVXWNH028EE

2.8

9,500

3.2

10,900

25

0.18

1/220~240/50

HP/HR

32/23

Cross Flow Fan

7.8

8.2

R410A

External EEV *5)

6.35

12.70

ID 18 hose

7.8

9.4

825x285x189

900x349x252

Filter (Washable)

ARH-465

AVXWNH036EE

3.6

12,200

4.0

13,600

30

0.18

1/220~240/50

HP/HR

36/23

Cross Flow Fan

9.3

9.5

R410A

External EEV *5)

6.35

12.70

ID 18 hose

7.8

9.4

825x285x189

900x349x252

Filter (Washable)

ARH-465

60 612009 Samsung DVM Air ConditionersINDOOR UNITS - WALL-MOUNTED TYPE

Page 32: Samsung 2009 Vrf Dvm

Cassette type Air conditionersModern style design, functionality for efficiency and four different types of model fits in any interior space.Cooling and heating begins from Samsung’s Cassette type indoor units while it gives finishing touch toyour interior design.

62 632009 Samsung DVM Air Conditioners

Slim 1Way Cassette Type 2Way Cassette Type Mini 4Way Cassette Type 4Way Cassette Type

Cassette Type Line-Up

Wide BladeThe new cassette type air conditioner is equipped with uniquely designed blades that are wider to provide evencooling and heating power throughout the room.

WIDEWIDEWIDEWIDE

64mm

46mm

WIDER

Airflow is directed towards theceiling which cause ceilingsoiling.

Airflow is directed downwardswithout having contact with theceiling.

Ceiling Soiling PreventionNewly designed panel will control the air direction to avoidhaving contact with the ceiling. This new design will preventthe ceiling soiling and keep your interior cleaner than evereven, after long period of operation.

Conventional Blade

Ceiling Ceiling

New Blade

600(mm) 650

Lift-up Range

700 750

750mm

700mm

High Lift-up Drain PumpThe lift-up drain pump lifts condensed water up to 750mm,compared to the competitor’s 700mm, allowing for flexibleand convenient installation.

Fresh Air IntakeWith optional installation of an air intake motor, fresh aircan enter through the cassette unit so you have fresherair in the room.

Sub DuctThe Sub Duct lets you use the same air conditioner unit tocool another smaller space nearby. (The cassette unit is fitted with a knock-out component to accommodate this.)

Quick Connection of Drain PipeSamsung's unique drain pipe prevents leaks and is easierto install with no need to use tape or adhesives.

FRESHFRESHFRESHFRESH

SUB DUCTSUB DUCTSUB DUCTSUB DUCT QUICKQUICKQUICKQUICK

HIGHHIGHHIGHHIGH

Company A

Fresh air

Motor

Samsung

INDOOR UNITS

Page 33: Samsung 2009 Vrf Dvm

64 652009 Samsung DVM Air Conditioners

Slim 1Way CassetteSuper slim design helps easier installation and the quiet operation still provides the strongest air.

Optional Accessories

PSSMAMWR-WS0 MWR-TH01

7K Btu/h2.2 kW

9K Btu/h2.8 kW

12K Btu/h3.6 kW

MWR-SH00

Individual Controllers

Panel

Line-Up

INDOOR UNITS - CASSETTE TYPE

Slim and Compact Design

Slim 1Way CassetteWant a cassette type air conditioner, but have limited space? Samsung's new Slim 1Way cassette type air conditioner is the answer.

10.5kg

17kg

38% Down

4kW R410A model Weight

Only 135mm thickSamsung introduces the world's slimmest indoorair conditioner unit. Only 135mm thick, the slim 1Way Cassette air conditioner can be installedpractically anywhere.

Lighter indoor unitThe first to apply ABS cabinets into its indoorunits, Samsung has achieved the lightest unitson the market. Its slim lightweight design makesinstallation and maintenance a breeze.

135mm

Ensure that there is sufficient installation space. Allow at least170mm for the installation.

NOTE

Min. 170mm

Quiet OperationSamsung's new blade design drastically reduces noise levels, so you can relax in peace and quiet.

25dB

35dB

30dB

43dB

Low

High

Fan speed Noise level

Check Valve Inside Drain PumpFaulty drainage installation or power failures can cause condensed water to flow back into the unit,causing leakage and odors. Samsung's air conditioners are equipped with a check valve built directlyinto the drain pump to prevent water from flowing backward.

Check Valve

WIDE BLADEQUICK CONNECTION OF DRAIN PIPE

CEILING SOILINGPREVENTION

HIGH LIFT-UP DRAIN PUMPWIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH QUICKQUICKQUICKQUICK

MR-CH01MWR-WE00

Page 34: Samsung 2009 Vrf Dvm

66 672009 Samsung DVM Air Conditioners

INDOOR UNITS - CASSETTE TYPE

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Panel Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

AVXCSH022EEModel

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

2.2

7,500

2.5

8,500

40

0.20

1/220~240/50

HP/HR

30/25

Cross Flow Fan

6.0

7.0

R410A

EEV

6.35

12.70

VP20(OD 25,ID 20)

10.5

13.5

970x135x410

1,164x212x478

PSSMA

3.0

5.0

1,180x25x460

1,259x144x539

Filter (Washable)

24/750

Cooling *1)

Heating *2)

Specification | Slim 1Way Cassette

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Panel Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

AVXCSH028EE

2.8

9,500

3.2

10,900

45

0.23

1/220~240/50

HP/HR

30 / 25

Cross Flow fan

7.0

8.0

R410A

EEV

6.35

12.70

VP20(OD 25,ID 20)

10.5

13.5

970x135x410

1,164x212x478

PSSMA

3.0

5.0

1,180x25x460

1,259x144x539

Filter (Washable)

24/750

AVXCSH036EE

3.6

12,200

4.0

13,600

50

0.25

1/220~240/50

HP/HR

32 / 27

Cross Flow fan

8.0

9.0

R410A

EEV

6.35

12.70

VP20(OD 25,ID 20)

10.5

13.5

970x135x410

1,164x212x478

PSSMA

3.0

5.0

1,180x25x460

1,259x144x539

Filter (Washable)

24/750

Page 35: Samsung 2009 Vrf Dvm

68 692009 Samsung DVM Air Conditioners

2Way CassetteAir coming out from two sides with and the compact size can be perfect fit for long and narrow place withlimited installation space.

Optional Accessories

P2SMA

18K Btu/h5.6 kW

24K Btu/h7.1 kW

Panel

Line-Up

INDOOR UNITS - CASSETTE TYPE

QUICK CONNECTION OF DRAIN PIPE

HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH QUICKQUICKQUICKQUICK

Small Size Big PerformanceThe 2Way cassette air conditioner is now 45% smaller thancompetitor’s models, so it's even easier to incorporate intobuilding design.

Twin Cross Flow FanThe 2Way cassette type unit is perfect fit for long and narrowrectangular type of space. Twin Cross Flow Fan inside of the2Way cassette will spread cool or warm air even further andwider with less noise.

Standard Formula for Easy InstallationThe dimensions of the 2Way cassette air conditioner allows for easyinstallation into standard ceiling grids (600Wx600H), so everythingjust falls into place.

230mm

890mm575mm

45%Decreased

305mm

1,180mm600mm

600mm

600mm

Cross flow fans

Specification | 2Way Cassette

Individual Controllers

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Panel Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

AVXC2H056EE

5.6

19,100

6.3

21,400

70

0.38

1/220~240/50

HP/HR

36 / 28

Cross Flow Fan

14.0

16.0

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

21.0

25.0

890x230x575

1,077x299x642

P2SMA

4.0

8.0

1,030x25x650

1,103x151x727

Filter (Washable)

24/750

AVXC2H071EE

7.1

24,200

8.0

27,200

75

0.40

1/220~240/50

HP/HR

38 / 28

Cross Flow Fan

14.0

16.0

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

21.0

25.0

890x230x575

1,077x299x642

P2SMA

4.0

8.0

1,030x25x650

1,103x151x727

Filter (Washable)

24/750

MWR-WS0 MWR-TH01 MWR-SH00 MR-CH01MWR-WE00

Page 36: Samsung 2009 Vrf Dvm

70 712009 Samsung DVM Air Conditioners

Mini 4Way CassetteFour way airflow for large coverage with more compact size, it is best for the place with smaller ceiling structure.

INDOOR UNITS - CASSETTE TYPE

QUICK CONNECTION OF DRAIN PIPE

HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH QUICKQUICKQUICKQUICK

FRESH AIR INTAKEFRESHFRESHFRESHFRESH

Ideal Compact SizeThe Mini 4Way cassette air conditioner can be installed in one standardceiling tile (600Wx600H), which can save installation time.

Unit : mm

Fan Speed AdjustmentFan speed can be adjusted according to ceiling height byadjusting dip switch of indoor unit’s PCB.

3~3.5m 2.7m

High Ceiling

On : Increased fan speed Off : Standard fan speed

Standard Ceiling

Optional Accessories

Panel

Line-Up

PMSMA

9K Btu/h2.8 kW

12K Btu/h3.6 kW

18K Btu/h5.6 kW

21K Btu/h6.0 kW

Specification | Mini 4Way Cassette

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Panel Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

AVXCMH028EE

2.8

9,500

3.2

10,900

90

0.50

1/220~240/50

HP/HR

30 / 25

Turbo Fan

10.1

11.9

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

17.0

20.0

575x260x575

660x310x635

PMSMA

3.5

6.2

670x35x670

717x93x717

Filter / Safety Grille

24/750

AVXCMH036EE

3.6

12,200

4.0

13,600

90

0.50

1/220~240/50

HP/HR

34 / 27

Turbo Fan

10.1

11.9

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

17.0

20.0

575x260x575

660x310x635

PMSMA

3.5

6.2

670x35x670

717x93x717

Filter / Safety Grille

24/750

AVXCMH056EE

5.6

19,100

6.3

21,400

95

0.52

1/220~240/50

HP/HR

41 / 33

Turbo Fan

10.6

12.6

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

17.0

20.0

575x260x575

660x310x635

PMSMA

3.5

6.2

670x35x670

717x93x717

Filter / Safety Grille

24/750

AVXCMH060EE

6.0

20,400

6.8

23,200

100

0.55

1/220~240/50

HP/HR

41 / 33

Turbo Fan

12.2

14.5

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

17.0

20.0

575x260x575

660x310x635

PMSMA

3.5

6.2

670x35x670

717x93x717

Filter / Safety Grille

24/750

Individual Controllers

MWR-WS0 MWR-TH01 MWR-SH00 MR-CH01MWR-WE00

Page 37: Samsung 2009 Vrf Dvm

72 732009 Samsung DVM Air Conditioners

4Way CassetteThe air coming out from four different places, 4Way Cassette type indoor units provide the air into every corner of the space.

Optional Accessories

15K Btu/h4.5 kW

Panel

Line-Up

INDOOR UNITS - CASSETTE TYPE

Stylish Panel DesignThe stylish panel is well harmonized with any interior design.

WIDE BLADEFRESH AIR INTAKE

SUB DUCTQUICK CONNECTION OF DRAIN PIPE

CEILING SOILINGPREVENTION

HIGH LIFT-UP DRAIN PUMPWIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH FRESHFRESHFRESHFRESH SUB DUCTSUB DUCTSUB DUCTSUB DUCT QUICKQUICKQUICKQUICK

18K Btu/h5.6 kW

24K Btu/h7.1 kW

30K Btu/h9.0 kW

36K Btu/h11.2 kW

44K Btu/h12.8 kW

48K Btu/h14.0 kW

New Turbo Fan

Quiet OperationImagine a room of cool calmness. Theaerodynamically designed ‘Turbo Fan'minimizes noise from the turbulenceof blade movement. Therefore noiseis less than conventional models.

Uniform DistributionThe new 'Turbo Fan' with wide bladesprovides extreme cooling and heatingpower from 4 separate outlets so theentire room gets cool or warm faster.Now, every nook and cranny is comfortable.

Easy LevelingEach corner portion of the panel is detachable,which gives easier access to adjust the height,therefore leveling and installation is much easierand quicker than before.

Compact SizeThe 4Way cassette type unit has gotten evenslimmer. Now only 218mm thick(4.5/5.6/7.1/9.0kW), 24% slimmer compare to competitor’s 288mm (9.0kW). It's still theindustry leader in compactness and is eveneasier to install in tight spaces.

Efficient Cooling3-dimensional shaped blade, which has the world wide patent, is able to spread cool or warm air further andevenly to all corners of the space.

Conventional 4Way

Conventional 4Way

New 4Way

New 4Way

Detachable corners make installationand height adjustments much easier.

Air distribution

Detaching the whole panel tookmore time.

218mm

Air distribution

Outlet1

Outlet2

Outlet3

Outlet4

‘A’ View

‘B’ View

‘C’ View

P4SMA

Individual Controllers

MWR-WS0 MWR-TH01 MWR-SH00 MR-CH01MWR-WE00

Page 38: Samsung 2009 Vrf Dvm

74 752009 Samsung DVM Air Conditioners

INDOOR UNITS - CASSETTE TYPE

Specification | 4Way Cassette

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Panel Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

AVXC4H140EE

14.0

47,700

16.0

54,500

80

0.36

1/220~240/50

HP/HR

45 / 38

Turbo Fan

26.5

32.0

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

29.0

35.0

840x298x840

926x360x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H128EE

12.8

43,600

13.8

47,000

65

0.30

1/220~240/50

HP/HR

41 / 35

Turbo Fan

25.0

29.5

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

29.0

35.0

840x298x840

926x360x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H112EE

11.2

38,200

12.5

42,600

50

0.23

1/220~240/50

HP/HR

40 / 33

Turbo Fan

23.0

26.5

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

29.0

35.0

840x298x840

926x360x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Panel Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

AVXC4H045EE

4.5

15,300

5.0

17,000

40

0.19

1/220~240/50

HP/HR

34/29

Turbo Fan

14.5

16.5

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

25.0

31.0

840x218x840

926x280x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H056EE

5.6

19,100

6.3

21,400

40

0.19

1/220~240/50

HP/HR

34/29

Turbo Fan

14.5

16.5

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

25.0

31.0

840x218x840

926x280x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H071EE

7.1

24,200

8.0

27,200

45

0.21

1/220~240/50

HP/HR

36/30

Turbo Fan

17.0

18.5

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

25.0

31.0

840x218x840

926x280x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H090EE

9.0

30,700

10.0

34,100

50

0.23

1/220~240/50

HP/HR

39/32

Turbo Fan

19.5

21.5

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

25.0

31.0

840x218x840

926x280x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

Page 39: Samsung 2009 Vrf Dvm

Duct type Air conditionersSamsung’s duct type air conditioners have wide range of line up, with slim size that offers flexibleinstallation option and the smart pressure control system which gives silent operation.

76 772009 Samsung DVM Air Conditioners

Slim Duct MSP Duct

Duct Type Line-Up

INDOOR UNITS

Clean Filter SystemThe anti-bacteria filter and the filter cleaning indicator provide you with cleaner, healthier air. You deserve to breathe fresh air everyday.

Anti-bacteria FilterThe anti-bacteria filter not only traps dust particles,but suppresses proliferation of molds and bacteria.

BACTERIABACTERIABACTERIABACTERIA Easy Filter CleaningAfter 1,000 hours of operation the filter cleanindicator will inform you that the filter should becleaned. The filter can be easily removed fromthe bottom, left, or right of the unit. (1,000 hoursis the default set time, which can be adjusted to2,000 hours on the internal PCB.)

High Lift-up Drain Pump (optional)The lift-up drain pump lifts condensed water up to 750mm, compared to the competitor’s 700mm, allowing for flexible and convenient installation.

HIGHHIGHHIGHHIGH

Smart Pressure ControlThe Smart Pressure Control System adjusts fan speed according toE.S.P(External Static Pressure), so the air conditioner always givesyou consistent cooling and heating power regardless of the surrounding environment.

E.S.P Control

Air v

olum

e

Static pressure (mmAq)Minimum Maximum

H

H

M

M

L

L

Page 40: Samsung 2009 Vrf Dvm

Slim DesignOnly 199mm thick, this slim design makes installation, maintenanceand repair easy.

Easy to MaintainParts are easily accessible bysimply opening the bottompanel, which reduces timeand maintenance costs.

199mm

199mm

220mm

225mm

160 180 200 220210 230

78 792009 Samsung DVM Air Conditioners

Slim DuctSlim duct type indoor units with the most compact size that leads industry gives flexible installationand easier maintenance option.

Optional Accessories

7K Btu/h2.2 kW

Line-Up

INDOOR UNITS - DUCT TYPE

Specification | Slim Duct

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA

EASY FILTER CLEANING

HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH

SMART PRESSURECONTROL

Flexible InstallationThe air inlet can be set up on either the bottomor rear of the unit, so there is more flexibility ininstallation.

Rear side air inlet Bottom side air inlet

Suction Duct Suction Duct

TexTex

Diffuser Diffuser

9K Btu/h2.8 kW

12K Btu/h3.6 kW

15K Btu/h4.5 kW

18K Btu/h5.6 kW

24K Btu/h7.1 kW

30K Btu/h9.0 kW

36K Btu/h11.2 kW

44K Btu/h12.8 kW

48K Btu/h14.0 kW

Drain Pump

MDP-E075SEE / MDP-E075SEE1

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Optional

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

External Static Pressure

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter /

Safety Grille

Duct Receiver Kits

Drain Pump

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

mmAq

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

-

-

Cooling *1)

Heating *2)

Standard(Min.~Max.)

Receiver

Receiver Wire

AVXDSH022EE

2.2

7,500

2.5

8,500

80

0.40

1/220~240/50

HP/HR

31 / 26

Sirocco Fan

8.0

9.0

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

26.0

31.0

900x199x600

1,133x333x722

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH028EE

2.8

9,500

3.2

10,900

80

0.40

1/220~240/50

HP/HR

32 / 27

Sirocco Fan

9.0

10.0

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

26.0

31.0

900x199x600

1,133x333x722

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH036EE

3.6

12,200

4.0

13,600

80

0.40

1/220~240/50

HP/HR

32 / 27

Sirocco Fan

10.0

12.0

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

26.0

31.0

900x199x600

1,133x333x722

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE

Model

Individual Controllers

MWR-WS0 MWR-TH01 MWR-SH00 MR-CH01MWR-WE00

Page 41: Samsung 2009 Vrf Dvm

80 812009 Samsung DVM Air Conditioners

INDOOR UNITS - DUCT TYPE

Specification | Slim Duct

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Optional

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

External Static Pressure

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter /

Safety Grille

Duct Receiver Kits

Drain Pump

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

mmAq

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

-

-

Cooling *1)

Heating *2)

Standard(Min.~Max.)

Receiver

Receiver Wire

Model AVXDSH090EE

9.0

30,700

10.0

34,100

170

0.96

1/220~240/50

HP/HR

40 / 36

Sirocco Fan

29.0

34.0

3 (0-6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

43.0

51.5

1,300x295x690

1,600x444x831

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE1

AVXDSH112EE

11.2

38,200

12.5

42,600

170

0.96

1/220~240/50

HP/HR

40 / 36

Sirocco Fan

31.2

34.0

3 (0~6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

43.0

51.5

1,300x295x690

1,600x444x831

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE1

AVXDSH128EE

12.8

43,600

13.8

47,000

200

1.13

1/220~240/50

HP/HR

41 / 38

Sirocco Fan

34.0

36.0

3 (0~6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

46.0

54.5

1,300x295x690

1,600x444x831

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE1

AVXDSH140EE

14.0

47,700

16.0

54,500

220

1.24

1/220~240/50

HP/HR

41 / 38

Sirocco Fan

36.0

38.0

3 (0~6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

46.0

54.5

1,300x295x690

1,600x444x831

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE1

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Optional

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

External Static Pressure

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter /

Safety Grille

Duct Receiver Kits

Drain Pump

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

mmAq

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

-

-

Cooling *1)

Heating *2)

Standard(Min.~Max.)

Receiver

Receiver Wire

Model AVXDSH045EE

4.5

15,300

5.0

17,000

90

0.60

1/220~240/50

HP/HR

33 / 30

Sirocco Fan

14.5

16.5

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

31.0

39.0

1,100x199x600

1,330x330x730

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH056EE

5.6

19,100

6.3

21,400

100

0.60

1/220~240/50

HP/HR

33 / 30

Sirocco Fan

15.5

18.0

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

31.0

39.0

1,100x199x600

1,330x330x730

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH071EE

7.1

24,200

8.0

27,200

120

0.60

1/220~240/50

HP/HR

36 / 32

Sirocco Fan

16.5

20.0

2 (0~4)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

31.0

39.0

1,100x199x600

1,330x330x730

Filter

(Washable)

MRK-A00

MRW-10A

MDP-E075SEE

Page 42: Samsung 2009 Vrf Dvm

82 832009 Samsung DVM Air Conditioners

MSP DuctFlexible installation options offer a variety of solutions for different shapes of room, and the smart pressurecontrol system provide silent operation.

INDOOR UNITS - DUCT TYPE

Drain Pump

MDP-M075SGU1 / MDP-M075SGU2 /MDP-M075SGU3

Flexible InstallationSamsung's MSP Duct air conditioners offer different solutionsfor any shape room allowing for specific airflow requirements.

L-shaped area Y-shaped areaAreas far apart

Silent Operation with the static pressure controlThe external static pressure control makes it easy to design duct work to ensure efficiency and silent operation.

Narrow Width (5.6/7.1kW) Middle Static Pressure

Slim DuctmmAq

2

4

6

8

10

MSP Duct

0~10mmAq

0~6mmAq

ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA

EASY FILTER CLEANING

HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH

SMART PRESSURECONTROL

WIRED REMOTE CONTROLLERWiredWiredWiredWired

Easy to MaintainReduce time and maintenance costsby keeping parts easily accessible.

900mm Width measured without control box.

Optional Accessories

Line-Up18K Btu/h

5.6 kW24K Btu/h

7.1 kW30K Btu/h

9.0 kW36K Btu/h11.2 kW

44K Btu/h12.8 kW

48K Btu/h14.0 kW

Specification | MSP Duct

Individual Controllers

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Optional

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

External Static Pressure

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter /

Safety Grille

Duct Receiver Kits

Drain Pump

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

mmAq

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

-

-

Cooling *1)

Heating *2)

Standard(Min.~Max.)

Receiver

Receiver Wire

Model AVXDUH056EE

5.6

19,100

6.3

21,400

130

1.10

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

14.5

15.5

4 (0~6)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

31.0

36.0

900x260x480

1,146x345x584

Filter

(Washable)

MRK-A00

MRW-10A

MDP-M075SGU3

AVXDUH071EE

7.1

24,200

8.0

27,200

190

1.25

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

18.5

20.0

4 (0~6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

31.0

36.0

900x260x480

1,146x345x584

Filter

(Washable)

MRK-A00

MRW-10A

MDP-M075SGU3

MWR-WS0 MWR-TH01 MWR-SH00 MR-CH01MWR-WE00

Page 43: Samsung 2009 Vrf Dvm

84 852009 Samsung DVM Air Conditioners

INDOOR UNITS - DUCT TYPE

Specification | MSP Duct

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Optional

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

External Static Pressure

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter /

Safety Grille

Duct Receiver Kits

Drain Pump

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

mmAq

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

-

-

Cooling *1)

Heating *2)

Standard(Min.~Max.)

Receiver

Receiver Wire

Model AVXDUH128EE

12.8

43,600

13.8

47,000

370

1.67

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

32.0

31.0

8 (6~10)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

52.0

60.0

1,200x360x650

1,447x425x769

Filter

(Washable)

MRK-A00

MRW-10A

MDP-M075SGU2

AVXDUH140EE

14.0

47,700

16.0

54,500

410

1.86

1/220~240/50

HP/HR

43 / 38

Sirocco Fan

37.0

36.0

8 (6~10)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

52.0

60.0

1,200x360x650

1,447x425x769

Filter

(Washable)

MRK-A00

MRW-10A

MDP-M075SGU2

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Optional

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

External Static Pressure

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter /

Safety Grille

Duct Receiver Kits

Drain Pump

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

mmAq

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

-

-

Cooling *1)

Heating *2)

Standard(Min.~Max.)

Receiver

Receiver Wire

Model AVXDUH090EE

9.0

30,700

10.0

34,100

240

1.30

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

19.5

21.5

6 (4~8)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

35.0

41.0

1,150x260x480

1,390x345x584

Filter

(Washable)

MRK-A00

MRW-10A

MDP-M075SGU1

AVXDUH112EE

11.2

38,200

12.5

42,600

260

1.17

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

27.0

27.0

8 (6~10)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

39.0

46.0

1,150x320x480

1,390x420x584

Filter

(Washable)

MRK-A00

MRW-10A

MDP-M075SGU1

Page 44: Samsung 2009 Vrf Dvm

Floor & Convertible type Air conditionersUnique features and uniquely designed indoor units allow more installation optionsfor efficient operation and convenient installation.

86 872009 Samsung DVM Air Conditioners

Console Ceiling

Floor & Convertible Type Line-Up

INDOOR UNITS

I Interior DesignNow with more flexibility in placement, the air conditionercan add a stylish element to your room.

INTERIORINTERIORDESIGNDESIGN

INTERIORINTERIORDESIGNDESIGN

Silent ModeIndoor units operate quietly with the leastpossible noise.

Anti-bacteria FilterThe anti-bacteria filter not only traps dust particles, butsuppresses proliferation of molds and bacteria.

BACTERIABACTERIABACTERIABACTERIA

Light Weight UnitThis extremely lightweight design makes maintenanceand installation easy.

LIGHTLIGHTLIGHTLIGHT

Flexible Pipe InstallationThe drain pipe can be installed in 6 different places, so youhave more options in where to place your air conditioner.

Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

Page 45: Samsung 2009 Vrf Dvm

88 892009 Samsung DVM Air Conditioners

ConsoleUnique design with the two air outlets on top and bottom side of the indoor unit provide moreefficient cooling and heating.

Optional Accessories Standard Accessories

9K Btu/h2.8 kW

Individual Controllers

Wireless RemoteControllers

Line-Up

INDOOR UNITS - FLOOR & CONVERTIBLE TYPE

INTERIORDESIGNINTERIORINTERIOR

DESIGNDESIGNINTERIORINTERIORDESIGNDESIGN

ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA

LIGHT WEIGHT UNIT

LIGHTLIGHTLIGHTLIGHT

SILENT MODEFLEXIBLE PIPEINSTALLATIONFlexible PipeFlexible Pipe

InstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

WIRELESS REMOTECONTROLWirelessWirelessWirelessWireless

(2.8/3.6kW)

12K Btu/h3.6 kW

18K Btu/h5.6 kW

Elegant Design

Clean PanelStay clean with the smartly designed CleanPanel. This unique panel keeps dust frombeing accumulated so the unit and the roomstays cleaner.

Slim DesignIt can't get any slimmer. This newly introducedconsole type air conditioner is only 199mmthick, the slimmest on the market. Its slimdesign easily integrates the unit into yourdecor.

Silent Operation (23dB)The silent, yet powerful and efficient cooling and heating systemkeeps things more comfortable. Silent mode is available in 4 different operating modes: High / Medium / Low / Silence.

2Way air outletsThere are two separate air outlets for cooling and heating. Havingwarmer air coming out from the bottom part of the air outlet willspread the warm air evenly throughout the room. Stay cooler andwarmer in every corner of your room.

Slim & Smart DesignThis extremely slim design with Clean Panel adds aesthetic value to any interior.

Black DisplayFunctional art, the touch screen display iselegant while it maximizes the convenienceof control.

(5.6kW)

199mm

MWR-WS0 MWR-TH01 MWR-SH00MWR-WE00

Page 46: Samsung 2009 Vrf Dvm

90 912009 Samsung DVM Air Conditioners

INDOOR UNITS - FLOOR & CONVERTIBLE TYPE

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

Specification | Console

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

AVXTJH028EE

2.8

9,500

3.2

10,900

30

0.25

1/220~240/50

HP/HR

38 / 23

Turbo Fan

7.0

7.2

R410A

EEV

6.35

12.70

ID 18 hose

15.2

20.3

720x620x199

810x710x295

Filter (Washable)

ARH-1378

AVXTJH036EE

3.6

12,200

4.0

13,600

35

0.29

1/220~240/50

HP/HR

39 / 24

Turbo Fan

8.5

9.0

R410A

EEV

6.35

12.70

ID 18 hose

15.2

20.3

720x620x199

810x710x295

Filter (Washable)

ARH-1378

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

AVXTJH056E*

5.6

19,100

6.3

21,400

62

0.49

1/220-240/50

HP / HR

44/25

Turbo Fan

13.0

13.5

R410A

EEV

6.35

12.70

ID 18 hose

15.2

20.3

720x620x199

810x710x295

Filter (Washable)

ARH-2202

Page 47: Samsung 2009 Vrf Dvm

92 932009 Samsung DVM Air Conditioners

CeilingTwo way installation options allow the air coming out from the ceiling or floor.

Optional Accessories

Individual Controllers

Line-Up

INDOOR UNITS - FLOOR & CONVERTIBLE TYPE

INTERIORDESIGNINTERIORINTERIOR

DESIGNDESIGNINTERIORINTERIORDESIGNDESIGN

ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA

LIGHT WEIGHT UNIT

LIGHTLIGHTLIGHTLIGHT FLEXIBLE PIPEINSTALLATIONFlexible PipeFlexible Pipe

InstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

Compact but PowerfulSamsung’s ceiling type air conditioner boasts a slim, compactdesign, half the size of its competitors, with cooling powercomparable to competitor’s larger products.

2way InstallationDepending on the space availability and the purposeof the air conditioner, the indoor unit can be installedunder the ceiling or on the floor.

Under Ceiling Floor Standing

200%

100%

136%

118% 123%

100%

Size

7.1kW Model

Weight

Smaller Lighter

18K Btu/h5.6 kW

24K Btu/h7.1 kW

Specification | Ceiling

Performance

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

Piping

Connections

Weight

Set Size

Standard

Accessories

Capacity

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

Model

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

Notes

*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

*5) Optional Accessory

- Specifications are subject to change without prior notice for product improvement.

AVXTFH056EE

5.6

19,100

6.3

21,400

72

0.33

1/220~240/50

HP/HR

38 / 32

Sirocco Fan

14.0

14.5

R410a

EEV *5)

6.35

12.70

ID 18 hose

22.0

26.0

1,000x650x200

1,074x726x294

Filter (Washable)

-

AVXTFH071EE

7.1

24,200

8.0

27,200

80

0.35

1/220~240/50

HP/HR

41 / 36

Sirocco Fan

18.0

18.5

R410a

EEV *5)

9.52

15.88

ID 18 hose

22.0

26.0

1,000x650x200

1,074x726x294

Filter (Washable)

-

MWR-WS0 MWR-TH01 MWR-SH00 MR-CH01MWR-WE00

Page 48: Samsung 2009 Vrf Dvm

ERV(Energy Recovery Ventilator) SystemPerfect ventilation system with charming technology, provides fresh air while savingenergy all year long.

94 952009 Samsung DVM Air Conditioners

ERV(Energy Recovery Ventilator) SYSTEM

How it Works

Key Technology

New Diamond Type Optimized Airflow Design

High Efficiency Element

Compact size

Automatic Refresh System (CO2 Sensor) : Optional ERV is automatically operated to give fresh air into room by sensing CO2 Level.

High Efficiency Motor (BLDC) Constant air volume by BLDC motor.

Intelligent Operating System (-15˚C) Without Heater

WinterIt reduces the costs of heating ventilated air by transferring heatfrom the warm inside air being exhausted to the fresh (but cold)supply air.

SummerThe inside air cools the warmer supply air to reduce ventilationcooling costs.

Heat

Heat

HeatHeat

Heat

Heat

Cool

Cool Cool

Cool Cool

CoolCool

IndoorOutdoor

Element

Rectangular Type

Diamond Type

Hexagonal Type

Page 49: Samsung 2009 Vrf Dvm

Energy Saving Operation (Auto Mode)

Extreme Climates (Winter & Summer)When temperature and humidity level difference between indoor andoutdoor is big, it operates as ERV.

Mild Climates (Spring & Fall)When temperature and humidity level difference between indoor andoutdoor is small, it operates as conventional ventilation fan.

It automatically changes operation mode depending on temperature difference between indoorand outdoor to save energy.

Element

EA

OA

EA

OA

RA

SA

RA

SA

Element

Damper

Damper

Compact Size & Flexible Installation Compact and Slim in Size by High Efficiency Diamond Element.

Ex.) Model No. RHF-035~050

96 972009 Samsung DVM Air Conditioners

ERV(Energy Recovery Ventilator) SYSTEM

RHF025EE250

RHF035EE350

RHF050EE500

RHF080EE800

RHF100EE1,000

Voltage

Frequency

Withstand Voltage

Insulation Resistance

Air Volume

External Static Pressure

Leakage Rate

Power Input

Current

Temperature Exchange

Efficiency

Effective Enthalpy

Exchange Efficiency

Sound Level (Turbo/Low)

Dust Collection Method

Net Dimensions(WxHxD)

Gross Dimensions (WxHxD)

Weight (Net/Gross)

Duct Diameter

Cooling

Heating

Cooling

Heating

Model

V

Hz

-

-

m3/hr

Pa

%

W

A

%

%

%

%

dB(A)

-

mm

mm

kg

Ø,mm

RHF025EE

220~240

50/60

AC1500V, 1min

30MG

250

110

10

115

0.7

70

70

50

70

27/22

High efficiency filter(PP)

600X350X660

760X400X807

25.5/30

150

RHF035EE

220~240

50/60

AC1500V, 1min

30MG

350

155

10

115

0.7

70

70

50

70

31/24

High efficiency filter(PP)

1,012X270X1,000

1,299X337X1,183

42.5/53.5

200

RHF050EE

220~240

50/60

AC1500V, 1min

30MG

500

165

10

175

1.1

70

70

50

70

32/25

High efficiency filter(PP)

1,012X270X1,000

1,299X337X1,183

42.5/53.5

200

RHF080EE

220~240

50/60

AC1500V, 1min

30MG

800

155

10

330

2.1

70

70

50

70

33/29

High efficiency filter(PP)

1,220X340X1,135

1,475X 440 X1,330

67/75.5

250

RHF100EE

220~240

50/60

AC1500V, 1min

30MG

1,000

155

10

450

2.9

70

70

50

70

37/32

High efficiency filter(PP)

1,220X340X1,135

1,475X440X1,330

67/75.5

250

Specification | ERV System

Line-up

Page 50: Samsung 2009 Vrf Dvm

98 992009 Samsung DVM Air Conditioners

INDOOR UNITS - ACCESSORIES

Accessories

MXJ-YA1509K

MXJ-YA2512K

MXJ-YA2812K

MXJ-YA2815K

MXJ-YA3119K

MXJ-YA3819K

MXJ-YA4422K

MXJ-HA2512K

MXJ-HA3115K

MXJ-HA3819K

MXJ-YA1500K

MXJ-YA2500K

MXJ-YA3100K

MXJ-YA3800K

MXJ-T3819K

MXJ-T4422K

MXJ-T3100K

MXJ-T3800K

MCU-4EAE1

MCU-4EAEV1

MCU-6EAE1

15.0kW and below

Over 15.0 ~ 40.6kW and below

Over 40.6 ~ 46.4kW and below

Over 46.4 ~ 69.6kW and below

Over 69.6 ~ 98.6kW and below

Over 98.6 ~ 139.2kW and below

Over 139.2kW

Below 46.4kW

46.5 ~ 69.6kW

Over 69.7kW

23.2kW and below

Over 23.2 ~ 63.9kW and below

Over 69.6 ~ 139.2kW and below

Over 139.3kW

Below 48HP

Over 50HP

Below 48HP

Over 50HP

Below 4 indoor units

Below 4 indoor units *1)

Below 6 indoor units

Requisite

Option

Requisite

Requisite

Requisite

Requisite(HR only)

DVM PLUS II,

DVM PLUS II HR

DVM PLUS III,

DVM PLUS III HR

DVM PLUS II,

DVM PLUS II HR

DVM PLUS III,

DVM PLUS III HR

DVM PLUS II, DVM PLUS

II HR, DVM PLUS III, DVM

PLUS III HR (Module)

DVM PLUS III HR

DVM PLUS III HR

(Module)

DVM PLUS II HR,

DVM PLUS III HR

Y-Joint

Header Joint

Y-Joint(Only for DVM PLUS IIIHR in high pressure gasconnection)

Outdoor Joint for DVM PLUS III / HR (Outdoor Connection)

Outdoor Joint only for DVM PLUS III HR Module(High Pressure GasConnection)

MCU Kits

ModelFeatureClassification Description Relevant Unit Remark

Notes

*1) MCU-4EAEV1 is the product that includes built in EEV to connect the indoor unit (wall-mounted type and ceiling type) that does notinclude EEV.

MXD-A13K116A

MXD-A13K200A

MXD-A16K200A

MXD-A22K200A

MXD-A13K216A

MXD-A13K300A

MXD-A16K213A

MXD-A16K300A

MEV-A13SA

MEV-A16SA

MDP-E075SEE

MDP-E075SEE1

MDP-M075SGU1

MDP-M075SGU2

MDP-M075SGU3

PSSMA

P2SMA

PMSMA

P4SMA

Below 3.6kW (1 Room) +

5.6 kW~9.0kW (1Room)

Below 3.6kW (2 Rooms)

5.6 kW~9.0kW (2Rooms)

5.6 kW~7.1kW (2Rooms)

Below 3.6kW (2 Rooms) +

5.6 kW~9.0kW (1Room)

Below 3.6kW (3 Rooms)

Below 3.6kW (1 Room) +

5.6 kW~9.0kW (2Rooms)

5.6 kW~9.0kW (3Rooms)

Below 3.6kW (1 Room)

5.6 kW~9.0kW (1Room)

Slim Duct (2.2~7.1) kW

Slim Duct (9.0~14.0) kW

M.S.P Duct (9.0, 11.2) kW

M.S.P Duct (12.8, 14.0) kW

M.S.P Duct (5.6, 7.1) kW

Slim 1Way Cassette

2Way Cassette

Mini 4Way Cassette

4Way Cassette

Option

Option

Option

Option

Requisite

EEV Kits

Drain PumpDrain Pump

Front Panel

ModelFeatureClassification Description Relevant Unit Remark

Wall-mounted &

Ceiling indoor unit

(For 2 indoor units)

Wall-mounted &

Ceiling indoor unit

(For 3 indoor units)

Wall-mounted &

Ceiling indoor unit

(For single unit)

-

-

Page 51: Samsung 2009 Vrf Dvm

100 1012009 Samsung DVM Air Conditioners

Manage the distribution of perfect air

Samsung’s convenient control systems have beenimproved one step forward for better usability andmanagement. Practically you can control your air conditioner anywhere and anytime.

CONTROL SYSTEMS

CONTROL SYSTEMS04

100 | Control Systems

102

110

112

114

117

118

| Integrated Management System

| Centralized Control System

| Individual Control System

| Building Management System

| DVM-Pro

| Accessories

Page 52: Samsung 2009 Vrf Dvm

Integrated Management SystemIntegrated Management System is convenient for managing system air conditioners installed in smalland middle-sized buildings. It can be managed through the Internet so you can control the air conditioners from anywhere.

102 1032009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Integrated Management System

Web-based Data Management Server allows you to control indoor and outdoor units and manage otherfunctions through the Internet as well.

MIM-D00• Built-in web server for PC-independent management and remote access control

• Multiple upper-layer control access (S-NET 3, S-NET Mini, Web-client)

• Individual/Group control of up to 256 indoor units and heat exchange units

• Error history management

• Weekly/Daily schedule control

• Power distribution function

• 2 digital inputs, 2 digital outputs

• Current time management even during power failure (for 24 hours)

• Data storage in non-volatile memory

• Emergency stop function with simple contact interface

• Operation mode lock

• Temperature limit setting

Data Management Server

DMS

S-NET 3

S-NET mini

Page 53: Samsung 2009 Vrf Dvm

104 1052009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Integrated Management System

CentralizedController

DMS

Interface Module

Interface Module

Interface Module

CentralizedController

SIM Watt HourMeter

Web Server Function• Built-in web server.

• Multiple upper-layer control access with prioritized management.

• Remote access control with the static IP address.Internet

Anytime, Anywhere Control

Enhanced central management• Operation mode lock

• Temperature limit setting

• Wireless / wired remote control restriction

DMS System

Main Features

Easy Control & Monitoring• Individual/Group control and monitoring of up to 256 indoor units.

• Operation mode, temperature setting, airflow direction and

fan speed.

• Easy multiple/full indoor unit selection.

• Full room temperature display.

• Error history query based on date.

360kWh

460kWh

140kWh

Indoor unit operation state

1. Operation data accumulation andpower distribution

2.Data extract - Excel format

610kWh

180kWh

Cooling Schedule Setup

Power Distribution System• Power distribution to up to 256 indoor units.

• Data query for watt-hour, use time and use ratio.

• File save in Microsoft Excel format.

• 93 days worth of power distribution data storage.

08:00 AM On 10:00 PM Off

External Contact Interface• Full indoor unit control with simple contact

input. (Emergency/Lock)

• State output (Operation/Error) for synchronous

control.

Schedule Control Function• Up to 256 schedule settings.

• Weekly, Daily or 1-Day schedule control.

• Exception date setting.

History Management• Easy service and management with error history.

• Occurrence date, error details, current state.

Building Control System

Rapid Service Response

Error History Monitoring

Fire Control System Error Status Indicator

Operation Restriction

Service

5th Floor

4th Floor

3rd Floor

2nd Floor

1st Floor

Page 54: Samsung 2009 Vrf Dvm

106 1072009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Integrated Management System

Smart Net Control System

S-NET 3 System

S-NET 3

Supports 16 DMSs

Max. 16 units

You can manage a group of buildings with S-NET3 through Data Management Servers that manage eachof the buildings. S-NET3 provides flexible and complete control for a great variety of applications.

Control and Monitoring• Control & monitoring of up to 4,096 indoor units

• Heat exchange unit management

• Wireless/wired remote control restriction

• Temperature limit setting

• Multiple/full indoor unit selection

• Icon-based indoor unit display mode

Schedule Control• Graphical schedule settings

• Weekly, Daily schedule control

• Exception date setting

Zone Management• Management structure customization regardless of installation structure• Control zone creation/edition/deletion• Tree structure zone management control

Power Distribution Management• Data query for power distribution and operation time

• Power distribution report generation and print

• Time section setting for different electricity rates

• Group setting for power distribution summation

History Management• Error/Event history management

• Indoor unit operation history management

• Report generation and print

Cycle monitoring• Monitoring outdoor / indoor unit cycle data

(Supported for specific outdoor unit models)

Main Features

• Fully integrated PC management software.

• Up to 16 DMSs connection through the Ethernet.

• Central management of up to 4,096 indoor/heatexchange units.

• Schedule/Zone control.

• Error/Operation history management.

• Power distribution management and analysis.

• Automatic update through the Internet.

S-NET 3

Page 55: Samsung 2009 Vrf Dvm

108 1092009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Integrated Management System

• Dynamic compatibility options (DMS, centralized controller, interface module)• Control and monitoring of up to 256 indoor units• Detailed cycling information monitoring• Schedule function (Weekly, Daily)• USB keyboard support • Error display • 7-inch wide LCD display • Temperature limit setting • Touch screen• Zone control• Child-lock setting• Operation mode lock• External contact control

S-NET mini

Main Features

Dynamic Compatibility Option

Supports 16

InterfaceModules

Supports 4 DMSs

Supports 16

CentralizedControllers

Control and monitoring• Control & Monitoring of up to 256 indoor units/heat exchange units• Operation control and monitoring• Detailed operation cycling information monitoring• Wireless/wired remote control restriction setting

Schedule Control• Maximum 256 Weekly, Daily schedule control

• Schedule repetition, exception date setting

• Schedule edit (add, edit, delete)

• Detailed operation schedule setting

• Remote control restriction option setting

Zone Management• Management structure customization regardless of installation structure • Control zone creation/edition/deletion

Temperature Limit Setting• Upper/Lower temperature limit setting

Cycle Monitoring• Outdoor/Indoor unit cycling information monitoring

(supported for specific outdoor unit models)

Error Management• Error history management• Error management information query• Detailed error information query

Smart Net Control System

Page 56: Samsung 2009 Vrf Dvm

Centralized Control SystemSamsung's centralized control system can control and monitor up to 4,096 individual indoor unitsand 256 groups of indoor units simultaneously with great convenience and efficiency.

110 1112009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Centralized Control System

Function Icon

ON/OFF, OPERATION MODE, FAN SPEED,AIRFLOW, TEMPERATURE SETTING

OperationOperationOperationOperation INDIVIDUAL AND GROUP CONTROL (MAXIMUM 16 INDOOR UNITS)

GroupGroupGroupGroup

ERROR DISPLAYErrorErrorErrorError

FILTER REPLACEMENT ALARM RESETFilterFilterFilterFilter

MCM-A202A• Maximum 16 group controls

(Maximum 256 Indoor units)

• Unified/Individual indoor unitcontrol (On/Off)

• Wireless/wired remote controlrestriction

• Cooling/Heating mode control

• Indoor unit error display

Centralized Controller

MCM-A100

Function Controller

• Operation mode selection (Cooling, Heating or Auto)

• Mixed operation mode protection

Operation Mode Selection SwitchMCM-C200

OperationOperationOperationOperation ErrorErrorErrorError FilterFilterFilterFilter

S-NET II Plus• Indoor unit control of up to 256 groups• Extensive individual control of up to 4,096 indoor units• Weekly and Daily schedule function• Zone setting and control• Dynamic exchange to Permitted and Prohibited wireless/wired remote control• Full/Group/Individual indoor unit display

256 group 4,096 indoor units controls Zone controlSchedule controlIndividual control

Max. 16 units

RS232-RS485Converter

S-NET II Plus

• Control and monitoring ofup to 16 indoor unit groups

To use Function Controller, itrequires to be connected toMCM-A202A

• Communicator betweenindoor/outdoor units and the centralized controller

Interface ModuleMIM-B13A

MIM-B04A

Page 57: Samsung 2009 Vrf Dvm

Individual Control SystemErgonomic and innovative remote controllers feature better design, easy grip, large and softbuttons with easy-to-view displays.

112 1132009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Individual Control System

Function Icon

ON/OFF, OPERATION MODE, FAN SPEED,AIRFLOW, TEMPERATURE SETTING

OperationOperationOperationOperation INDIVIDUAL AND GROUP CONTROL (MAXIMUM 16 INDOOR UNITS)

GroupGroupGroupGroup

ERROR DISPLAYErrorErrorErrorError

FILTER REPLACEMENT ALARM RESETFilterFilterFilterFilter

• Compact size• Simple schedule control• Soft touch button

MR-CH01 MR-AH01

• Simple schedule control• Wide display• Soft touch button

Wireless Remote Controller

OperationOperationOperationOperation FilterFilterFilterFilter OperationOperationOperationOperation FilterFilterFilterFilter

MWR-WS0 (Premium)• Weekly schedule setting

(Maximum 70 schedules)• Exception date setting• Built-in room temperature

sensor• Clear and bright screen

with LCD backlight• Temperature limit setting• Wireless remote control

restriction• Automatic Stop mode • Sleep and Silent mode• Child lock

• Mode selection protection

MWR-TH01

Wired Remote Controller

MWR-SH00

Simplified wired remote controller

• Individual and group control(Maximum 16 ERVs)

• On/Off control• Operation mode (By-Pass, Heat

Exchange), fan speed• Simple schedule control• Error display• Synchronous operation with

indoor units

MWR-VH01ERV Wired remote controller

• Simple schedule control

• Wireless remote controlrestriction

OperationOperationOperationOperation GroupGroupGroupGroup

ErrorErrorErrorError FilterFilterFilterFilter

MWR-WE00 (Multi function)• Unified controller

(A/C, ERV, A/C+ERV)• Different button permission

levels• Weekly schedule setting

(A/C, ERV, A/C+ERV)• Exception date setting• Built-in room temperature

sensor• Clear and bright screen

with LCD backlight• Wireless remote control

restriction• Automatic Stop mode • Sleep and Silent mode• Child lock

OperationOperationOperationOperation GroupGroupGroupGroup

ErrorErrorErrorError FilterFilterFilterFilter

OperationOperationOperationOperation GroupGroupGroupGroup

ErrorErrorErrorError FilterFilterFilterFilter

OperationOperationOperationOperation GroupGroupGroupGroup

ErrorErrorErrorError FilterFilterFilterFilter

• ON/OFF control• Operation indication• Error Indication• Filter replacement sign• Use with receiver wire, MRW-10A

MRK-A00

Wireless Signal Receiver (for Duct-type indoor unit)

• Up to 100 weekly and dailyschedule settings

• Schedule setting based on 1-minute time units

• Digital clock display• Permanent schedule setting

storage

MWR-BS00

7-day Scheduler

• Current time protection from blackout (maximum 3 days)

• Use with wired remote controller, or centralized controller. (MWR-TH01, MCM-A202A)

Page 58: Samsung 2009 Vrf Dvm

Building Management SystemBMS (Building Management System) makes it possible to control and monitor the air conditioning network usingthe remote control and monitoring function. Optimum control with BMS-related interface modules keeps the airconditioning system efficient, saves energy, reduces maintenance costs and extends the life cycle of the units.

114 1152009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Building Management System

MIM-B07• Interface for Lon-Connection to Lonworks management system• Quick and easy installation• Up to 12 indoor units can be controlled• Communication : RS485 to Lonworks• Upper physical layer : FTT-10A

BMS Control Function

• On/Off control• Temperature setting• Operation mode• Fan speed

Monitoring Function

• On/Off• Operation mode• Room temperature• Error information

Guest Room Management System

Lonworks

External Contact Interface Module

Key Tag Interface Module

The Guest Room Management System is asmart way to save energy and money.When the Key Tag is in place, the air conditioneris activated. When the Key Tag is removed,the air conditioner switches off. Now youcan avoid cooling an unoccupied room andsave energy.

MIM-B14• Direct indoor unit control by external contact signal• Window-synchronized indoor unit control • Emergency control with simple contact input • Indoor unit operation/error state output through relay contacts

MIM-B02• Indoor unit control by external contact signals• Individual/Group control of up to 16 indoor units• Combinational use with sensor/timer/emergency inputs

Room 501

Key-Holder

Key-Tag

On/Off

Window OpenSensor

MalfunctionAlarm

External deviceControl

Room 502

Key-Holder

Room 503

Key-Holder

Room 504

Key-Holder

On/Off On/OffError

(Wall mounted type indoor unit : Only EEV including model supports state output function)

Example

Example

Page 59: Samsung 2009 Vrf Dvm

116 1172009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Building Management System

Room01(60kWh)

Room04(210kWh) 600kWh

Room03(210kWh)

Room02(120kWh)

RS 485

RS 485

Power Supply

Power Distribution UnitMCM-B102• Real-time power distribution for one indoor/outdoor system.

• Power distribution to maximum 48 indoor units.

• Communication error display.

• Total system power consumption display.

• Power consumption display of individual indoor units.

• Data storage even during a power failure.

• Consult with Samsung Electronics for watt-hour meter interface

= x

Room01

Room02

Room03

Room04

40%

30%

20%

10%

0%Room01 Room02 Room03 Room04

20% 19.4%

35.0%35.3% 35.0%35.1%

Actual Usage Rate

Displayed Rate

10.2% 10.2%

Room 01 electric powerconsumption

Total powerconsumption

Demand capacityof Room 01

Total demand capacityof indoor units

• Exclusive use for DMS power distribution.• Connection with up to 8 watt-hour meters.• RS485 interface with watt-hour meters.• Power consumption display for each watt-hour meter.• Automatic detection of specified watt-hour meters.

MIM-B12

Watt-hour meter Interface Module

DVM - Pro (DVM, FJM, CAC Equipment Selection Software)

DVM-Pro consists of two kinds of software called DVM-Pro Sales and CAD mode.

DVM-Pro Sales mode• Workspace: Creation ’Project’ & ‚’Workspace (DVM, FJM, CAC)’

• Indoor Unit: Indoor unit and accessory selection

• Outdoor Unit: Automatic selection and capacity simulation

• Piping: Basic, standard or manual selection with system check

• Wiring: Automatic diagram with communication wiring of indoor/outdoor/control units and electric power meters

• Control system: Automatic control unit selection

• Report: Specifications, diagrams and quotation

Download!www.dvmsystem.com Download Center DVM-Pro

DVM-Pro CAD mode• Quick, easy, precise design

• Compatibility with AutoCAD

• Automatic calculation: Refrigerant & drain pipe size

• Automatic selection: Refnet joint, header & distributor kit

• System check: Installation regulation & refrigerant addition

• Simulation: System capacities

• Easy control system selection

• Automatic report: Piping installation diagram, equipment list & quotation

Contact to Samsung HQ or Distributors for DVM-Pro CAD!

Page 60: Samsung 2009 Vrf Dvm

118 1192009 Samsung DVM Air Conditioners

CONTROL SYSTEMS - Accessories

Accessories Icon IndexClassification Product Model Image Application Model

IntegratedManagementSystem

Controller

InterfaceModule

DMS MIM-D00 DVM Series, FJM, CAC, ERV

DVM Series, FJM, CAC, ERV

DVM Series, FJM, CAC

S-NET 3 MST-P3P

S-NET mini MST-S3W

DVM Series, FJMSiM MIM-B12

CentralizedControlSystem

InterfaceModule

S-NET II Plus MSP-S1P DVM, DVM HR, DVM PLUS II, DVM PLUS II HR, CAC

DVM Series, FJM, CAC, ERV

DVM Series, FJM, CAC

Mini DVM(R410A), DVM PLUS II, DVM PLUSII HR, DVM PLUS III, DVM PLUS III HR, FJM,ERV

MCM-A202A

Controller

Centralized Controller

MCM-A100Function Controller

MIM-B13ACentralized Control Interface Module

DVM, DVM PLUS, DVM HR, CACMIM-B04A

DVM SeriesMCM-C200Operation Mode Selection Switch

DVM Series, FJMPower Distribution Unit

DVM Series : Mini DVM, DVM, DVM PLUS, DVM HR, DVM PLUS II, DVM PLUS IIHR, DVM PLUS III, DVM PLUS IIIHR

MCM-B102

Mini DVM(R410A), DVM PLUS II, DVM PLUS II HR, DVM PLUS III, DVM PLUS III HR, FJM(Non MH FKEA)

External Contact Interface Module MIM-B14

Building ManagementSystem

Lonworks Interface Module MIM-B07 DVM Series, FJM

Power Distribution

DVM Series, FJM Key-tag Interface Module MIM-B02Guest RoomManagementSystem

IndividualControlSystem

Controller Wireless Remote Controller MR-AH01MR-CH01

Cassette, Ceiling, Duct (Receiverneeded), Console (Included)

Cassette, Wall Mounted, Ceiling, Duct, Console

Cassette, Wall Mounted, Ceiling, Duct, Console

Duct (For Wireless Remote Controller)

Duct (For Wireless Remote Controller)

Cassette, Wall Mounted, Ceiling, Duct

Wired Remote Controller (Premium) MWR-WS0

Wired Remote Controller MWR-TH01

Cassette, Wall Mounted, Ceiling, Duct, Console

Simplified Wired Remote Controller MWR-SH00

ERVERV Wired Remote Controller MWR-VH01

Wireless SignalReceiver Kit

MRK-A00Wireless Signal Receiver

Receiver Wire MRW-10A

7-day Scheduler MWR-BS00

Cassette, Wall Mounted, Ceiling, Duct, Console

Wired Remote Controller (Multi Function) MWR-WE00

Wall-mounted Type Icon

Auto Roof ShutterAir conditioner automatically sealsoff to prevent dirt infiltration.

MPI (Micro Plasma Ion)MPI generates Hydrogen atoms andOxygen ions to create healthier air.

DNA FilterThe DNA structure possesses qualities inabsorbing and eliminating microscopiccarcinogenic agents.

Good’sleep IIControl the air temperature during yoursleep to enjoy a comfortable sleep andrefreshed wake up.

Cassette Type Icon

WIDE BLADEWider blades provide moreeven cooling power. WIDEWIDEWIDEWIDE

CEILING SOILINGPREVENTIONNewly designed panel preventsceiling contamination.

HIGH LIFT-UP DRAIN PUMPLift-up condensed water upto 750mm higher than anyother competitor.

FRESH AIR INTAKE

Optional air intake motorbrings in fresh air from outside.

HIGHHIGHHIGHHIGH

FRESHFRESHFRESHFRESH

QUICK CONNECTIONOF DRAIN PIPEUnique drain pipe connectionis easy to install.

QUICKQUICKQUICKQUICK

SUB DUCT

The Sub Duct makes it easyto provide air conditioning toa nearby smaller space.

SUB DUCTSUB DUCTSUB DUCTSUB DUCT

Duct Type Icon

ANTI-BACTERIA FILTERAnti-bacteria Filter traps dust particles and suppresses proliferationof molds and bacteria.

EASY FILTER CLEANINGFilter cleaning indicator willlet you know when the filterneeds to be cleaned.

HIGH LIFT-UP DRAIN PUMPLift-up condensed water upto 750mm higher than anyother competitor.

SMART PRESSURE CONTROLAdjusts fan speed to provideconstant cooling and heatingperformance.

BACTERIABACTERIABACTERIABACTERIAHIGHHIGHHIGHHIGH

WIRED REMOTE CONTROLLERDefault wired remote controlleris provided.

WiredWiredWiredWired

Control Systems Icon

Floor & Convertible Type Icon

INTERIOR DESIGNThe clean, modern designcomplements any decor.

LIGHT WEIGHT UNITExtremely lightweight, so maintenance and installation is easy.

ANTI-BACTERIA FILTERAnti-bacteria Filter traps dustparticles and suppresses proliferation of molds and bacteria.

INTERIORINTERIORDESIGNDESIGN

INTERIORINTERIORDESIGNDESIGN BACTERIABACTERIABACTERIABACTERIA

AUTO CHANGEOVERAutomatically changes operationmode according to temperaturesetting.

AUTOAUTOAUTOAUTO

LIGHTLIGHTLIGHTLIGHT

FLEXIBLE PIPEINSTALLATIONThe pipe can be installedin 6 different places formore placement options.

SILENT MODEIndoor and outdoor unitoperates silently.

Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

WIRELESS REMOTECONTOLLERDefault wireless remote controlleris provided.

WirelessWirelessWirelessWireless

ON/OFF, OPERATION MODE,FAN SPEED, AIR FLOW, TEMPERATURE SETTING

OperationOperationOperationOperation INDIVIDUAL AND GROUPCONTROL (MAXIMUM 16INDOOR UNITS)

GroupGroupGroupGroup

ERROR DISPLAYErrorErrorErrorError FILTER REPLACEMENT

ALARM RESET