DVM 2010 SAMSUNG System Air Conditioner Smart Thinking, Simple Living. Samsung’s Powerful and efficient DVM Plus III outdoor units will provide the comfortable refreshment at your work place, just like it provides at your residential places. When you feel refreshed at work as much as you feel it at home, imagination Samsung Electronics Co., LTD. Head Office (Suwon Korea) 416, Maetan-3Dong, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 443-742 www.samsung.com Learn more by visiting www.dvmsystem.com Space for Partnership 2010 SAMSUNG SYSTEM AIR CONDITIONERS

Upload: dotronganhtuan

Post on 14-Apr-2015

139 views

Category:

Documents


18 download

DESCRIPTION

Samsung

TRANSCRIPT

Page 1: 2010 Samsung DVM Catalog

DVM2010

SAMSUNGSystem Air Conditioner

Smart Thinking, Simple Living.

Samsung’s Powerful and efficient DVM Plus III outdoor units will

provide the comfortable refreshmentat your work place, just like it

provides at your residential places.

When you feel refreshed at work as much as you feel it at home,

imagination

Samsung Electronics Co., LTD.Head Office (Suwon Korea) 416, Maetan-3Dong, Yeongtong-Gu, Suwon City, Gyeonggi-Do, Korea 443-742

www.samsung.com

Learn more by visiting

www.dvmsystem.com

Space for Partnership

2010 SA

MS

UN

GS

YS

TEM

AIR

CO

ND

ITION

ER

S

Page 2: 2010 Samsung DVM Catalog

Contents

INTRODUCTION 04

10

| Brand Value

| Line-up

OUTDOOR UNITS 16

26

| Outdoor Unit Feature

| Outdoor Unit Specification

INDOOR UNITS 38

56

70

74

| Indoor Unit Feature

| Indoor Unit Specification

| ERV System

| Accessories

CONTROL SYSTEMS 78

80

90

92

94

95

96

97

98

| DVM System Structure

| Integrated Management System

| Centralized Control System

| Individual Control System

| Building Management System

| Guest Management System

| Power Distribution Unit

| DVM-Pro

| Accessories

Smart Thinking,

Simple Living.

2010 SAMSUNG DVM SYSTEM AIR CONDITIONER

In N Seoul Tower, Samsung’s DVM System air conditioner is providing air

conditioning throughout the site. Now the people, who visited N Seoul Tower

will enjoy their moment at the Seoul’s most famous attraction site with the

cool and refreshing air provided by Samsung.

You want to live easier as life gets harder. Just

because life is complicated doesn’t mean you have

to live that way. Simplify your lifestyle without

dealing with complexity. Our understanding of your

needs for a better life made us put more effort in

creating the perfect solution for a carefree life.

At Samsung, while we always aim to provide the

most up-to-date innovations, we believe that

innovations in home appliance should also make life

simple, easy, and more comfortable. With Samsung

Home Appliances, experience the wonders of smart

appliances that not only take your life to another

level of effortless comfort, but also help you spend

more time on more important things in your life.

Filling your home with Samsung’s simplified but

advanced home appliances doubles your comfort

and satisfaction. Don’t sacrifice ease for the latest

technology as Samsung provides state of the art

innovative technology in simplified products. Enjoy

smart thinking for simple living with Samsung

Electronics.

PROJECTN Seoul Tower

LOCATIONSeoul, Korea

TYPETower

NUMBER OF OUTDOOR UNITS4

NUMBER OF INDOOR UNITS20

CONTROL SOLUTIONCentralized Controller, Wired Remote Controller

Page 3: 2010 Samsung DVM Catalog

01l IN

TR

OD

UC

TIO

N

01l IN

TR

OD

UC

TIO

N

2010 SAMSUNG DVM AIR CONDITIONER

0504

Samsung is Moving with

and Ahead of Our Customers

A brand value is created by its customers and that’s the novel perspective at

Samsung. With all customer attention, Samsung had another successful year.

Business Week and Interbrand ranked Samsung 19th in Global Brands.

Samsung has overtaken Sony as the world's biggest producer oftelevisions and its strong product development has resulted in global leadership in the television industry. Samsung also improvedits position from the third to the second leading player in mobilephones worldwide. The philosophy of bringing the latest technologyto people at a fair price has quickly become consumers’ favorite andSamsung’s new concept shops have been successful making thephilosophy known to more expert and demanding audiences by showing the benefits of engaging with the brand.

As a global leader, Samsung will continue to create “Future” with thecustomers.

Republic of Korea19th Consumer

Electronics $17,518m

GLOBAL BUSINESS NETWORK6 Global Operation Centers

10 Global Headquarters

Europe Stuttgart

Milano

ME Asia Africa

IndiaSW Asia SE AsiaDelhi

ChinaKorea

ShanghaiJapan Los Angeles

Mexico

USChicago

Latin America

Malaysia

Thailand

LondonCIS

7 Design Centers

4 HA R&D Centers

Page 4: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

06 07

01l IN

TR

OD

UC

TIO

N

01l IN

TR

OD

UC

TIO

N

PlanetFirstTM with

Samsung Electronics

Samsung believes in the power of innovation today for a sustainable tomorrow

Every day, all of us need to seek new ways to reduce energy consumption at home and at work. To fulfillcustomer’s greener way of life, Samsung continues to manufacture eco-friendly products. Unfortunately,many consumers are unaware of green products and feel there are not enough options. So now, Samsungcreated PlanetFirst™ which applies to all of Samsung’s eco friendly products, partnerships or internal programs.

PlanetFirst™ is the name that easily identifies eco-friendly products from Samsung. These products connect customers' desire of living green to the joy of using the latest technology. PlanetFirst™, a unique communication, makes Samsung's commitment, mind-set, and approach to greener living clear andstraightforward. As Samsung continues to work, develop, engineer and design innovative products to satisfy customers, PlanetFirst™ also means these technologies, designs and manufacturing processes aregreener. Your choice of PlanetFirst™ products help preserve nature and reduce energy use.

Samsung is always striving to find new and better ways to reduce our impact on the environment withoutsacrificing complete satisfaction in its products. Samsung started by simply reducing, reusing and recycling; then by challenging employees to seek out and adopt extraordinary breakthroughs that makeSamsung's processes and products healthier, safer and less carbon dependent. So help the cause andstart your own journey in being green with PlanetFirst™.

Samsung Electronics makes on-going efforts to developenvironment-friendly products that minimize the negativeimpacts on the environment in every aspect of its products,from raw material procurement to production, transportation,usage and final disposal. Concerns for the environment areat the core of each product development.

Samsung's environment-friendly technologies and recyclingprograms have been highly recognized via various globalapprovals and awards worldwide.

Eco-labels & Declaration

Samsung eco mark Energy mark Korea Eco Mark Korea

Ecoflower EU Energy Star Mark TCO Sweden

Blue Angel Germany EPEAT US Eco Mark Korea 2

Four Seasons of HopeSamsung's Four Seasons of Hope is all about kids. It's about using the power of our brand to givesomething back to the communities we serve.Samsung's Four Seasons of Hope supports community-based foundations and charities headed by someof the countries’ favorite sports legends. Samsung pledges to raise national awareness and funds for theseoutstanding charities and to identify how others can also make a difference in the lives of these children andfamilies.

Samsung Recycling DirectSM

All good things come to an end. Let's make sure it's a Green end.As technology continually evolves, so will your digital lifestyle. When you upgrade your consumer electronics, you will need to recycle your old products responsibly. That's why we're proud to reaffirm ourcommitment and responsibility to recycle, using DirectSM, the new Samsung Recycling program launchedon October 1st, 2008.

Page 5: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

08 09

01l IN

TR

OD

UC

TIO

N

01l IN

TR

OD

UC

TIO

N

‘Eco-friendly’ Samsung

Preserves the nature you live in.

Thinking of you and the environment, Samsung plans for the future. Realizing your hopes for a greener,healthier life for you and the generations that follow, Samsung’s environmentally friendly technologies workto make the world a more beautiful place.

Air & Water

Conservation

As a leading innovator of environment-

friendly products and technologies,

Samsung products already drastically

reduce the strains on nature's valuable

resources. Samsung uses R-600, a

natural refrigerant, and cyclopentane

insulation in its refrigerators, which do

not promote global warming or add to

the greenhouse effect. Samsung's

water-efficient washing machines also

use less detergent and water without

affecting cleanliness, helping conserve

water.

Samsung products are energy

efficient, receiving Energy Grade A+ in

the EU and ENERGY STAR in the U.S.

Samsung washers with its ceramic

heaters use less power, which save

you energy, money and time. This

energy-efficient technology protects

you and nature, giving you a greener

lifestyle.

Samsung Electronics is making significant

efforts to save the environment and

complies with the WEEE (Waste

Electrical and Electronic Equipment)

directive by joining or establishing the

recycling schemes for each country.

Use Less,

Save More

Global

Recycling

Galeria de

Innovacion

2009Samsung attended Europe’s largest air-conditioner exhibition “Climatization”in Madrid, Spain. Samsung air conditioner's beautiful design with innovative features was awarded the“Galeria de Innovacion” The idea behindthis award is to encourage innovation inthe practical application of know-howand technologies in industrial development. Once again, Samsungproves its unsurpassed standards inquality.

As one of the world's oldest & prestigious design competitions, theiF product design award can lookback on a rich and long tradition. Thisseal of fine design quality has stood forqualitatively outstanding designawards for over 50 years. Samsung'sair conditioner with design innovationshas won the iF product design awardfor the year 2009.Samsung air conditioner continues toreceive worldwide recognition andawards, proving high quality functionsand beauty to value and satisfying customers' requirements.

Organized by Fiera MilanoInternational, the Comfort & DesignAward plays the role of intermediarybetween the Jury and companiesparticipating in the 36th MostraConvegno Expocomfort / Expobagno.The MCE / EXPOBAGNO 2008 aimedto rewarding the best product thatshows a high level of environmentalquality, providing a completeoverview of the sector along the linesof "Comfort & Living Technology".And Samsung air conditioner won theprize conferring a valid and professional recognition on the bestproducts in the ceremony .

iF Product

Design Award

2009

Comfort &

Design

2008

Making continuous efforts to stay ecofriendly,Samsung uses R-410A,

all environmentally friendly refrigerant, for its air conditioners and

restrains the use of materials with high global warming potential

(GWP). Most Samsung products have received Energy Grade A+ in

the EU and ENERGY STAR in the U.S. These energy-efficient air

conditioners not only save you money, but help conserve the

environment.

Samsung Eco-Friendly Air Conditioner Received Certifications and Awards

Page 6: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

11

01l IN

TR

OD

UC

TIO

N

2010 Line-Up2010 Samsung System Air Conditioner

Once again we are introducing our line up of system air conditioners with Samsung’sinnovative Technology equipped to each and every one of the products. Take a lookat Samsung’s 2010 system air conditioners made to satisfy you.

Powerful new line up

Outdoor Units

Basic Model

High Efficiency Combination

8HP 10HP 12HP 14HP

4HP 5HP 6HP

DVM PLUS III / DVM PLUS III HR

Mini DVM

Line upRVXVHT080GERVXVRT080GE

DVM PLUS IIIDVM PLUS III HR

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

Compact Combination

8HP 10HP 12HP 14HP 16HP

Line upDVM PLUS IIIDVM PLUS III HR

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

RVXVHT160GERVXVRT160GE

Combination Table

10

High Efficiency CombinationModel 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

Compact CombinationModel 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

60 62 64

RVXVHT140GERVXVRT140GE

RVXVHT160GERVXVRT160GE

Line-Up

Page 7: 2010 Samsung DVM Catalog

01l IN

TR

OD

UC

TIO

N

01l IN

TR

OD

UC

TIO

N

Indoor Units 7K Btu/h2.2 kW

9K Btu/h2.8 kW

12K Btu/h3.6 kW

15K Btu/h4.5 kW

18K Btu/h5.6 kW

21K Btu/h6.0 kW

24K Btu/h7.1 kW

30K Btu/h9.0 kW

36K Btu/h11.2 kW

44K Btu/h12.8 kW

48K Btu/h14.0 kWType

Capacity

Wall-mountedType

Cassette Type

Duct Type

Floor &Convertible Type

MB

Vivace

Neo Forte

Slim 1Way

2Way Cassette

Mini 4WayCassette

4Way Cassette

Slim Duct

Console

Ceiling

M.S.P Duct

Line-Up

2010 SAMSUNG DVM AIR CONDITIONER

12 13

Page 8: 2010 Samsung DVM Catalog

02 Powerful and optimizedcooling and heating

Samsung provides you the perfectly optimized cooling and

heating system with its latest and most innovative

technology. World’s largest capacity will provide you the

powerful performance all year long, no matter how hot or

how cold. Furthermore, Samsung’s outdoor units barely

make any noise or vibration during operations, and they

are perfect for residential and commercial buildings.

Always stay refreshed with Samsung system air conditioner.

PROJECTTower Palace

LOCATIONSeoul, Korea

TYPEApartment Building

NUMBER OF OUTDOOR UNITS2,928

NUMBER OF INDOOR UNITS17,568

OUTDOOR UNITS 16

25

26

| DVM PLUS III

| Mini DVM

| Outdoor Unit Specification

PROJECTVolkswagen Arena

LOCATIONGermany

TYPESoccer Stadium

PROJECTSavske elektrarneLjubljana

LOCATIONSlovenia

TYPEOffice building

OUTDOOR UNITS

02l O

UT

DO

OR

UN

IT

2010 SAMSUNG DVM AIR CONDITIONER

14 15

Page 9: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

16 17

Outdoor Units FeatureDVM PLUS III

High Efficiency CombinationModel 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

RVXVHT140GERVXVRT140GE

Compact CombinationModel 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58

RVXVHT080GERVXVRT080GE

RVXVHT100GERVXVRT100GE

RVXVHT120GERVXVRT120GE

60 62 64

RVXVHT140GERVXVRT140GE

RVXVHT160GERVXVRT160GE

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

OverviewDVM Plus III System Air Conditioner has a number of key technologies that improve performance.Here are the main technologies which create the perfect cooling and heating atmosphere.

Highly efficient O8Grooved tube has beenapplied to reduce pressureloss while increasing heattransfer performance toimprove COP.

Turbo intercooler (Shell andTube Type) improves coolingand heating COP andsecures reliability on longpiping installation.

DVI (Digital Vapor Injection)compressor injects optimizedmid-range pressure refrigerantto improve cooling and heating performance and efficiency.

O8 Heat Exchanger

Turbo Intercooler

DVI Compressor

Optimized fan guarddesign enhanced air flowvolume which achieved thehigh heat transfer performance withoutincreased noise.

Fan Guard

High efficiency new G-finimproved heat transfer performance and reinforce corrosion resistance.

New G-Fin

PROJECTImperial Palace Hotel

LOCATIONCebu, Mactan Island, Philippines

TYPEHotel

Date Dec, 2008

Number of Outdoor Units141

Number of Indoor Units1176

DVM Plus III outdoor units with the most stable performance upgrades your lifestyle.With two different types of DVM PLUS III combination available, you can have the outdoor unit that is powerful as 64 horse power and consumes less energy (Up to 20 percent less) than other maker’s outdoor unit sold in the market.

Page 10: 2010 Samsung DVM Catalog

Outdoor Units FeatureDVM PLUS III

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

New G- FinHighly efficient new G-Fin increases heat transfer performance, reinforces corrosion resistance, andincreases operating duration under frosting conditions.Heat transfer performance improved by 13% compared to

the conventional fin, even with the equivalent pressure loss.

Corrosion resistence reinforced by Epoxy Acrylic Coating.

Heating operation time is 1.4 times longer under frostingconditions due to new G-Fin.

High Efficiency O8 Heat ExchangerEfficient O8 Grooved tube reduced pressure loss while increasing heat exchange rates to improve COP.

Groove shape is designed to be high and slim to increase heat transfer performance inside the tube.

DVM PLUS III New Groove Shape (High and Slim) Item Improved Heat ExchangerO7 O819% 14.1% 10.3% 30.8% same

DiameterHeat transfer surface areaPressure loss in heatexchangerInternal heat transfer performancePressure resistance

EvaporationCondensation

O8 Heat Exchanger and New G-fin

Wide Louver FinG - Fin

Cap

acity

, Pow

er o

utpu

t (W

) 5000

4000

3000

2000

1000

00 30

Time (min.)60 90 120

EVA

. CO

ND

tem

pera

ture

(°C) 60

50

40

30

20

10

0

-10

-20

-300 30

Time (min.)60

Hydrophilic layer Acrylic resin + surfactant

Anti corrosive layer Epoxy acrylic

Raw aluminummaterial

0.3µm

2.0µm

92µm

Newly Designed Fan GuardFan Guard has been optimized to improve air volumeand reduce noise and vibration.

BLDC Motor, which is 2.7% more efficient than the competitors,has been applied.

High static pressure propeller fan and the optimum Bell Mouthform, for high external static pressure, have been applied. (External static pressure: 8mmAq)

DVM PLUS III

Conventional Model

Digital Hybrid SystemDHS (Digital Hybrid System) is a brand new concept system composed of DVI compressor, vapor injectiontechnology and turbo intercooler. These 3 factors together provide highly efficient performance.

DVI CompressorEfficient and reliable DVICompressor coupled withVapor Injection technologyhas been applied toimprove cooling and heatingperformance and energyefficiency.

Turbo IntercoolerTurbo intercooler (Shell & Tube Type) improved cooling and heating COP, to secure reliability on longpiping installation.

Vapor Injection TechnologyImproved cooling and heating performance andCOP by a new technology of two stage compression.This technology achieved the high heating performanceand COP under the lowest temperature, whichleads the industry.

Increase refrigerant flow rates with a new Vapor Injection technology.

Improved Sub-cooling necessary for long piping runswhile increasing cooling and heating performance andCOP.

Improve COP with the application of Turbo intercooler. Adequate sub-cooling to ensure reliable operation on

installations with long piping (200m).

Temperature

High

Low

Temperature

100 135 171 207 243 279 314

Sub-cooled liquid refrigerant

Low temperature gasrefrigerant

Low temperature liquid refrigerant

Saturated liquid refrigerant

2010 SAMSUNG DVM AIR CONDITIONER

18 19

Vapor InjectionTube

Vapor Injection Port

Page 11: 2010 Samsung DVM Catalog

DVM PLUS III

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

High COPHigh efficiency DVM PLUS III has improved averagecooling and heating COP compared to conventionalproducts and achieved the world’s Top Class energyefficiency

DHS(Digital Hybrid System) technology increased refrigerantflow rate and evaporation enthalpy difference.

Wide O8 Grooved pipe and G-Fin increased heat exchangeefficiency.

The best BLDC Motor in the industry and the Optimum FanGuard design increased efficiency.

The World’s Largest CapacitySamsung has achieved world’s largest capacity of 64HP by combining maximum 4 outdoor units with 5 different capacities. (8, 10, 12, 14 and 16HP) Many combinations of heat pump or heat recovery type support up to 64 indoor units to provide consumers a variety of choices for any installation condition.

Compact combinations (8~64 HP)Combination with the model requiring the smallest installation space.

High-Efficiency combinations (16~56 HP)Combination with high-efficiency model.

8HP 18HP

3.8

111

%

4.2

3

4.1

5

10%

3.7

3

4.1

0

4.0

2

ConventionalConventional

DVM PLUS IIIDVM PLUS III

Company ACompany A

Conventional Model DVM PLUS III

The Smallest Foot Print AreaThe world’s smallest foot print provides the smallestinstallation space which saves incredible amount oftime.

Approx. 32%reduction

1.35m2 0.92m2

Conventional Model

Refrigerant pump-down function

DVM PLUS III

Space SavingModel

Conventional Model

DVM PLUS III

Comparison to Conventional Model

12HP0.92m2

0.67m2

73%

16HP1.35m2

0.92m2

68%

ConventionalModel

DVM PLUSIII

8HP 10HP 12HP 14HP 16HP

27% reduction32% reduction

Digital Unit ModuleDigital Unit Module combination enables the system to alternate compressor operation to prolong each compressor’s life cycle and improvesCOP with part loads

Control the compressor capacity precisely.Ensure long life cycle by alternating operation of the DVI compressors.Improve COP using multiple heat exchangers of outdoor units at part loads.

Auto data backup in PCBIn case of problems in product, the operation information of last 30 minutes is stored before system shutdown.Therefore, DVM PLUS III can be diagnosed rapidly and serviced.

DVIScroll

FVIScroll

DVIScroll

FVIScroll

A unit B unit

2010 SAMSUNG DVM AIR CONDITIONER

20 21

Outdoor Units Feature

8~48HP

S-NET 1 PLUS

8~64HP

High pressure

Fan motor RPM

Current

Data storing

Refrigerant pump-down and pump-outDVM PLUS III provides several functions to facilitate the replacements of product, additional installation andmaintenance without much effort.

In case of moving outdoor units, maintenance of pipes betweenindoor units or between outdoor units and indoor units, it is possiblefor refrigerant to be recovered into outdoor units.

Refrigerant pump-out functionIn case of maintenance of outdoor units, it is possible for refrigerantto be recovered into indoor units or pipes units.

Breakdown

Breakdown

Page 12: 2010 Samsung DVM Catalog

Outdoor Units FeatureDVM PLUS III

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

2010 SAMSUNG DVM AIR CONDITIONER

22 23

Automatic Piping Length RecognitionAuto piping length recognition system saves time with no additional settings and performs the optimumoperation in accordance with piping length.

Optimal operation by automatic piping length recognition

Off OffOn On

L

On

Free InstallationDVM Plus III provides the degree of freedom frompriority of capacity when installing outdoor units inmodule.

No limits.

8HP (Digital Unit) 14HP (Digital Unit) 10HP (Digital Unit)

Conventional model

A digital outdoor unit with the largest capacity should come last.

8HP (Fixed Unit) 10HP (Fixed Unit) 14HP (Digital Unit)

Company A

An outdoor unit with the largest capacity should come first.

14HP 10HP 8HP

> >

DVM PLUS III

To respond to a range of various installation environments,DVM PLUS III is designed to be used up to an external static pressure of 8 mmAq.

External Static PressureThe World’s Longest Piping Length

The longest pipinglength : 220m(Equivalent Length)

Height differencesbetween indoor &

outdoor units : 50m

The first branch joint tothe farthest indoor unit :45 m(1 Size Up : 90m)

DVM PLUS III has an actual piping length up to 200m, with the maximum piping length of 45m from the firstbranch joint to the farthest indoor unit, thereby providing more convenience and flexibility for installation incommercial buildings.

Summary The longest piping length : 220m (Equivalent Length)

Total piping length: 1000m

From the first branch joint to the farthest indoor unit : 90m (with one piping Size Up)

Height difference betweenindoor units : 15m

DVM PLUS III

Page 13: 2010 Samsung DVM Catalog

PROJECTRestaurant Patron

LOCATIONNeo Psychiko Athens, Greece

TYPECafe - Restaurant

Mini DVM

High Energy EfficiencyDigital Scroll compressor offers very high cooling and heating COP.

Compact DesignMini DVM offers easy installation with its slim andcompact design saving installation space.

4

CO

P

3

2

1

04HP 5HP 6HP

3.33

4.05

3.04

3.87

3.053.73

Dimension

Capacity

Volume (m3)

Foot print (m2)

Height (mm)

Weight (kg)

4HP

0.39

0.35

1,128

124

5HP

0.39

0.35

1,128

125

6HP

0.39

0.35

1,128

125

Various Indoor UnitsMini DVM can be combined up to 11 stylish indoorunits blending with any interior design.

Easy MaintenanceMini DVM makes it possible to control compressor,PCB and EEV on front panel, allowing simple andeffortless maintenance. It is possible to react promptlyto errors because they are displayed on LED of the outdoor units by error codes.

Cooling

Heating

Wide CompatibilityMini DVM can be controlled with control systemswhich is the same as DVM PLUS III and FJM

High ReliabilityMini DVM is highly reliable with adopted DigitalScroll Compressor which can be controlled easily.Because Digital Scroll Compressor needs just onecontrol PCB, it achieves simple structure and highreliability.

Outdoor Units FeatureDVM PLUS III

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

Lead-Free and RoHs

Refrigerant Leakage PreventionTo prevent refrigerant leakage, we provide a solution to diagnose anyrefrigerant leakage during product operation. Also, changing servicevalves from flange type to brazed type further prevents refrigerant leakage.

RoHs ComplianceAlthough RoHS restriction only applies to small and large household electronics, IT equipment, lightings, power train, toys, leisure and sportsequipment and vending machines, Samsung expands the RoHS restriction into its entire range of products based on its own environmentalpolicies.

Lead-FreeDVM Plus III is an eco-friendly product that prevents pollution problemscaused by the use of lead, by applying lead-free indoor and outdoor PCBs.

2010 SAMSUNG DVM AIR CONDITIONER

24 25

Mini DVM is the perfect choice for residential and light commercial buildings. With compactand space saving size, Mini DVM will fit perfectly to the place with limited installation space.

As DVM PLUS III HR allows a simultaneous cooling and heatingoperation with one system, there are a variety of applications.

Great for places where simultaneous cooling and heating operation isrequired. (Hotels, nursing homes, conference rooms, etc.)

For seasonal air-conditioning which may need a simultaneous coolingand heating operation.

For medium and large offices, DVM PLUS III HR satisfies cooling andheating operation simultaneously for the requirements of interior andperimeter zone.

DVM PLUS III HR Versatile Application

Heating

HeatingCooling

Cooling

Heating

Cooling

MCU(Mode Change Unit)

Page 14: 2010 Samsung DVM Catalog

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

DVM PLUS III / HR

Basic ModelDVM PLUS III

DVM PLUS III HR

RVXVHT080GE

RVXVRT080GE

Notes*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping:

7.5m, Level differences: 0m*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Notes*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrigerant piping:

7.5m, Level differences: 0m*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

Horse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

822.4

76,40025.2

86,000 5.76 5.51 25

3/380~415/50HP/HR

3.89 4.57

Propeller/BLDC9.52 19.05 15.88

-200

50 (40)R410A

7.557

240242253255

880x1,703x765948x1,868x832

-5~43-20~24

RVXVHT100GE

RVXVRT100GE

1028.0

95,500 31.5

107,500 7.78 7.16 30

3/380~415/50HP/HR

3.60 4.40

Propeller/BLDC9.52

22.23 19.05

-200

50 (40)R410A

7.558

240242253255

880x1,703x765948x1,868x832

-5~43-20~24

RVXVHT120GE

RVXVRT120GE

1233.6

114,600 37.8

129,000 10.40 9.40 40

3/380~415/50HP/HR

3.23 4.02

Propeller/BLDC12.70 25.40 22.23

-200

50 (40)R410A

7.560

240242253255

880x1,703x765948x1,868x832

-5~43-20~24

RVXVHT140GE

RVXVRT140GE

1439.2

133,800 44.1

150,500 11.00 10.40

403/380~415/50

HP/HR3.56 4.24

Propeller/BLDC 12.70 25.40 22.23

-200

50 (40)R410A11.0 60

320323337340

1,200x1,703x7651,268x1,868x832

-5~43-20~24

RVXVHT160GE

RVXVRT160GE

1644.8

152,900 50.4

172,000 14.80 15.00

503/380~415/50

HP/HR3.03 3.36

Propeller/BLDC12.70 28.58 22.23

-200

50 (40)R410A11.0 60

320323337340

1,200x1,703x7651,268x1,868x832

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

16HP

Basic

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

RVXVHT080GE / RVXVRT080GERVXVHT100GE / RVXVRT100GERVXVHT120GE / RVXVRT120GERVXVHT140GE / RVXVRT140GEHorse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

2

1644.8

152,800 50.4

172,000 11.52 11.02

503/380~415/50

HP/HR3.89 4.57

Propeller/BLDC12.70 28.58 22.236.35 200

50 (40)R410A7.5x2

60 240x2242x2253x2255x2

(880x1,703x765)x2(948x1,868x832)x2

-5~43-20~24

18HP

11

1850.4

171,90056.7

193,500 13.54 12.67

503/380~415/50

HP/HR3.72 4.48

Propeller/BLDC15.88 28.58 25.406.35 200

50 (40)R410A7.5x2

60 240x2242x2253x2255x2

(880x1,703x765)x2(948x1,868x832)x2

-5~43-20~24

20HP

2

2056.0

191,000 63.0

215,000 15.56 14.32

603/380~415/50

HP/HR3.60 4.40

Propeller/BLDC15.88 28.58 25.40 6.35 200

50 (40)R410A7.5x2

61 240x2242x2253x2255x2

(880x1,703x765)x2(948x1,868x832)x2

-5~43-20~24

22HP

11

2261.6

210,100 69.3

236,500 18.18 16.56

603/380~415/50

HP/HR3.39 4.18

Propeller/BLDC15.88 28.58 25.40 6.35 200

50 (40)R410A7.5x2

62 240x2242x2253x2255x2

(880x1,703x765)x2(948x1,868x832)x2

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

24HP

Basic

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

RVXVHT080GE / RVXVRT080GERVXVHT100GE / RVXVRT100GERVXVHT120GE / RVXVRT120GERVXVHT140GE / RVXVRT140GEHorse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

3

2467.2

229,200 75.6

258,000 17.28 16.53

753/380~415/50

HP/HR3.89 4.57

Propeller/BLDC15.88 28.58 25.40 6.35 200

50 (40)R410A7.5x3

62 240x3242x3253x3255x3

(880x1,703x765)x3(948x1,868x832)x3

-5~43-20~24

26HP

21

2672.8

248,30081.9

279,500 19.30 18.18

753/380~415/50

HP/HR3.774.50

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A7.5x3

63 240x3242x3253x3255x3

(880x1,703x765)x3(948x1,868x832)x3

-5~43-20~24

28HP

12

2878.4

267,400 88.2

301,000 21.32 19.83

753/380~415/50

HP/HR3.68 4.45

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A7.5x3

63 240x3242x3253x3255x3

(880x1,703x765)x3(948x1,868x832)x3

-5~43-20~24

30HP

3

3084.0

286,500 94.5

322,500 23.34 21.48 100

3/380~415/50HP/HR

3.60 4.40

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A7.5x3

63 240x3242x3253x3255x3

(880x1,703x765)x3(948x1,868x832)x3

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

Module Type - High Efficiency

PROJECTVolkswagen Arena

LOCATIONGermany

TYPESoccer Stadium

2010 SAMSUNG DVM AIR CONDITIONER

26 27

Specification

Page 15: 2010 Samsung DVM Catalog

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

Specification

32HP

Basic

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

RVXVHT080GE / RVXVRT080GERVXVHT100GE / RVXVRT100GERVXVHT120GE / RVXVRT120GERVXVHT140GE / RVXVRT140GEHorse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

21

3289.6

305,600 100.8

344,000 25.96 23.72 100

3/380~415/50HP/HR

3.45 4.25

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A7.5x3

64 240x3242x3253x3255x3

(880x1,703x765)x3(948x1,868x832)x3

-5~43-20~24

34HP

2

134

95.2 324,800107.1

365,500 26.56 24.72 100

3/380~415/50HP/HR

3.58 4.33

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A

7.5x2+11x164

240x2+320x1242x2+323x1253x2+337x1255x2+340x1

(880x1,703x765)x2+(1,200x1,703x765)x1(948x1,868x832)x2+(1,268x1,868x832)x1

-5~43-20~24

36HP

111

36100.8

343,900 113.4

387,000 29.18 26.96 100

3/380~415/50HP/HR

3.45 4.21

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x2+11x164

240x2+320x1242x2+323x1253x2+337x1255x2+340x1

(880x1,703x765)x2+(1,200x1,703x765)x1(948x1,868x832)x2+(1,268x1,868x832)x1

-5~43-20~24

38HP

1

238

106.4 363,100 119.7

408,500 29.78 27.96 100

3/380~415/50HP/HR

3.57 4.28

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x1+11x264

240x1+320x2242x1+323x2253x1+337x2255x1+340x2

(880x1,703x765)x1+(1,200x1,703x765)x2(948x1,868x832)x1+(1,268x1,868x832)x2

-5~43-20~24

40HP

1240

112.0 382,200 126.0

430,000 32.40 30.20 125

3/380~415/50HP/HR

3.46 4.17

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x1+11x265

240x1+320x2242x1+323x2253x1+337x2255x1+340x2

(880x1,703x765)x1+(1,200x1,703x765)x2(948x1,868x832)x1+(1,268x1,868x832)x2

-5~43-20~24

42HP

342

117.6 401,400 132.3

451,500 33.00 31.20 125

3/380~415/50HP/HR

3.56 4.24

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A11x365

320x3323x3337x3340x3

(1,200x1,703x765)x3(1,268x1,868x832)x3

-5~43-20~24

44HP

3

144

123.2 420,300 138.6

473,000 34.34 31.88 125

3/380~415/50HP/HR

3.59 4.35

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x3+11x165

240x3+320x1242x3+323x1253x3+337x1255x3+340x1

(880x1,703x765)x3+(1,200x1,703x765)x1(948x1,868x832)x3+(1,268x1,868x832)x1

-5~43-20~24

46HP

21146

128.8 439,400144.9

494,500 36.96 34.12 125

3/380~415/50HP/HR

3.48 4.25

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x3+11x165

240x3+320x1242x3+323x1253x3+337x1255x3+340x1

(880x1,703x765)x3+(1,200x1,703x765)x1(948x1,868x832)x3+(1,268x1,868x832)x1

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

48HP

Basic

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

RVXVHT080GE / RVXVRT080GERVXVHT100GE / RVXVRT100GERVXVHT120GE / RVXVRT120GERVXVHT140GE / RVXVRT140GEHorse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

2

248

134.4 458,600 151.2

516,000 37.56 35.12 125

3/380~415/50HP/HR

3.58 4.31

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x2+11x265

240x2+320x2242x2+323x2253x2+337x2255x2+340x2

(880x1,703x765)x2+(1,200x1,703x765)x2(948x1,868x832)x2+(1,268x1,868x832)x2

-5~43-20~24

50HP

112

50140.0

477,700157.5

537,500 40.18 37.36 150

3/380~415/50HP/HR

3.48 4.22

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x2+11x266

240x2+320x2242x2+323x2253x2+337x2255x2+340x2

(880x1,703x765)x2+(1,200x1,703x765)x2(948x1,868x832)x2+(1,268x1,868x832)x2

-5~43-20~24

52HP

22

52145.6

496,800163.8

559,000 42.80 39.60 150

3/380~415/50HP/HR

3.40 4.14

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x2+11x266

240x2+320x2242x2+323x2253x2+337x2255x2+340x2

(880x1,703x765)x2+(1,200x1,703x765)x2(948x1,868x832)x2+(1,268x1,868x832)x2

-5~43-20~24

54HP

1354

151.2 516,000 170.1

580,500 43.40 40.60 150

3/380~415/50HP/HR

3.48 4.19

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x1+11x366

240x1+320x3242x1+323x3253x1+337x3255x1+340x3

(880x1,703x765)x1+(1,200x1,703x765)x3(948x1,868x832)x1+(1,268x1,868x832)x3

-5~43-20~24

56HP

456

156.8 535,200 176.4

602,000 44.00 41.60 150

3/380~415/50HP/HR

3.56 4.24

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A11x466

320x4323x4337x4340x4

(1,200x1,703x765)x4(1,268x1,868x832)x4

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

Module Type - High Efficiency

DVM PLUS III

Notes

*1) Nominal cooling capacities are based on

- Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,Equivalent refrigerant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on

- Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

2010 SAMSUNG DVM AIR CONDITIONER

28 29

Page 16: 2010 Samsung DVM Catalog

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

Specification

30HP

11

3084.0

286,70094.5

322,500 25.80 25.40 100

3/380~415/50HP/HR

3.26 3.72

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A11x263

320x2323x2337x2340x2

(1,200x1,703x765)x2(1,268x1,868x832)x2

-5~43-20~24

28HP

2

2878.4

267,600 88.2

301,000 22.00 20.80

753/380~415/50

HP/HR3.56 4.24

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A11x263

320x2323x2337x2340x2

(1,200x1,703x765)x2(1,268x1,868x832)x2

-5~43-20~24

26HP

11

2672.8

248,40081.9

279,500 21.40 19.80

753/380~415/50

HP/HR3.40 4.14

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A

7.5x1+11x162

240x1+320x1242x1+323x1253x1+337x1255x1+340x1

(880x1,703x765)x1+(1,200x1,703x765)x1(948x1,868x832)x1+(1,268x1,868x832)x1

-5~43-20~24

24HP

1

1

2467.2

229,300 75.6

258,000 18.78 17.56

753/380~415/50

HP/HR3.58 4.31

Propeller/BLDC15.88 28.58 25.40 6.35 200

50 (40)R410A

7.5x1+11x162

240x1+320x1242x1+323x1253x1+337x1255x1+340x1

(880x1,703x765)x1+(1,200x1,703x765)x1(948x1,868x832)x1+(1,268x1,868x832)x1

-5~43-20~24

44HP

21

44123.2

420,500 138.6

473,000 36.80 35.80 125

3/380~415/50HP/HR

3.35 3.87

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A11x365

320x3323x3337x3340x3

(1,200x1,703x765)x3(1,268x1,868x832)x3

-5~43-20~24

42HP

11142

117.6 401,300 132.3

451,500 36.20 34.80 125

3/380~415/50HP/HR

3.25 3.80

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x1+11x264

240x1+320x2242x1+323x2253x1+337x2255x1+340x2

(880x1,703x765)x1+(1,200x1703x765)x2(948x1,868x832)x1+(1,268x1748x832)x2

-5~43-20~24

40HP

2

140

112.0 382,100 126.0

430,000 35.60 33.80 125

3/380~415/50HP/HR

3.15 3.73

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x2+11x164

240x2+320x1242x2+323x1253x2+337x1255x2+340x1

(880x1,703x765)x2+(1,200x1,703x765)x1(948x1,868x832)x2+(1,268x1,868x832)x1

-5~43-20~24

38HP

21

38106.4

363,000 119.7

408,500 31.80 29.20 125

3/380~415/50HP/HR

3.35 4.10

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A

7.5x2+11x164

240x2+320x1242x2+323x1253x2+337x1255x2+340x1

(880x1,703x765)x2+(1,200x1,703x765)x1(948x1,868x832)x2+(1,268x1,868x832)x1

-5~43-20~24

18HP

Basic

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

RVXVHT080GE / RVXVRT080GERVXVHT100GE / RVXVRT100GERVXVHT120GE / RVXVRT120GERVXVHT140GE / RVXVRT140GERVXVHT160GE / RVXVRT160GEHorse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

11

1850.4

171,900 56.7

193,500 13.54 12.67

503/380~415/50

HP/HR3.72 4.48

Propeller/BLDC15.88 28.58 25.406.35 200

50 (40)R410A7.5x2

60 240x2242x2253x2255x2

(880x1,703x765)x2(948x1,868x832)x2

-5~43-20~24

20HP

2

2056.0

191,000 63.0

215,000 15.56 14.32

603/380~415/50

HP/HR3.60 4.40

Propeller/BLDC15.88 28.58 25.406.35 200

50 (40)R410A7.5x2

61 240x2242x2253x2255x2

(880x1,703x765)x2(948x1,868x832)x2

-5~43-20~24

22HP

11

2261.6

210,100 69.3

236,500 18.18 16.56

603/380~415/50

HP/HR3.39 4.18

Propeller/BLDC15.88 28.58 25.40 6.35 200

50 (40)R410A7.5x2

62 240x2242x2253x2255x2

(880x1,703x765)x2(948x1,868x832)x2

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

32HP

Basic

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

RVXVHT080GE / RVXVRT080GERVXVHT100GE / RVXVRT100GERVXVHT120GE / RVXVRT120GERVXVHT140GE / RVXVRT140GERVXVHT160GE / RVXVRT160GEHorse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

232

89.6 305,800 100.8

344,000 29.60 30.00 100

3/380~415/50HP/HR

3.03 3.36

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A11x263

320x2323x2337x2340x2

(1,200x1,703x765)x2(1,268x1,868x832)x2

-5~43-20~24

34HP

12

3495.2

324,700 107.1

365,500 28.58 25.96 100

3/380~415/50HP/HR

3.33 4.13

Propeller/BLDC19.05 31.75 28.58 6.35 200

50 (40)R410A7.5x3

64 240x3242x3253x3255x3

(880x1,703x765)x3(948x1,868x832)x3

-5~43-20~24

36HP

3

36100.8

343,800 113.4

387,000 31.20 28.20 100

3/380~415/50HP/HR

3.23 4.02

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A7.5x3

64 240x3242x3253x3255x3

(880x1,703x765)x3(948x1,868x832)x3

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

Module Type - Compact

DVM PLUS III

2010 SAMSUNG DVM AIR CONDITIONER

30 31

Page 17: 2010 Samsung DVM Catalog

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

Specification

56HP

1

12

56156.8

535,100 176.4

602,000 48.38 47.56 150

3/380~415/50HP/HR

3.24 3.71

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x1+11x366

240x1+320x3242x1+323x3253x1+337x3255x1+340x3

(880x1,703x765)x1+(1,200x1,703x765)x3(948x1,868x832)x1+(1,268x1,868x832)x3

-5~43-20~24

54HP

11

254

151.2 515,900 170.1

580,500 47.78 46.56 150

3/380~415/50HP/HR

3.16 3.65

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x2+11x266

240x2+320x2242x2+323x2253x2+337x2255x2+340x2

(880x1,703x765)x2+(1,200x1,703x765)x2(948x1,868x832)x2+(1,268x1,868x832)x2

-5~43-20~24

52HP

3

152

145.6 496,700 163.8

559,000 46.00 43.20 150

3/380~415/50HP/HR

3.17 3.79

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x3+11x166

240x3+320x1242x3+323x1253x3+337x1255x3+340x1

(880x1,703x765)x3+(1,200x1,703x765)x1(948x1,868x832)x3+(1,268x1,868x832)x1

-5~43-20~24

64HP

464

179.2 611,600 201.6

688,000 59.20 60.00 175

3/380~415/50HP/HR

3.03 3.36

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A11x467

320x4323x4337x4340x4

(1,200x1,703x765)x4(1,268x1,868x832)x4

-5~43-20~24

Module Type - Compact

DVM PLUS III

Notes

*1) Nominal cooling capacities are based on

- Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB, Equivalent refrig-erant piping: 7.5m, Level differences: 0m

*2) Nominal heating capacities are based on

- Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB, Equivalent refrigerant piping: 7.5m, Level differences: 0m

*3) Mode - HP: Heat Pump, HR: Heat Recovery

*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.

- Specifications are subject to change without prior notice for product improvement.

46HP

Basic

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

RVXVHT080GE / RVXVRT080GERVXVHT100GE / RVXVRT100GERVXVHT120GE / RVXVRT120GERVXVHT140GE / RVXVRT140GERVXVHT160GE / RVXVRT160GEHorse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

1246

128.8439,600 144.9

494,500 40.60 40.40 125

3/380~415/50HP/HR

3.17 3.59

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A11x365

320x3323x3337x3340x3

(1,200x1,703x765)x3(1,268x1,868x832)x3

-5~43-20~24

48HP

348

134.4 458,700 151.2

516,000 44.40 45.00 125

3/380~415/50HP/HR

3.03 3.36

Propeller/BLDC19.05 38.10 31.75 6.35 200

50 (40)R410A11x365

320x3323x3337x3340x3

(1,200x1,703x765)x3(1,268x1,868x832)x3

-5~43-20~24

50HP

31

50140.0

477,600 157.5

537,500 42.20 38.60 150

3/380~415/50HP/HR

3.32 4.08

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x3+11x166

240x3+320x1242x3+323x1253x3+337x1255x3+340x1

(880x1,703x765)x3+(1,200x1,703x765)x1(948x1,868x832)x3+(1,268x1,868x832)x1

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

58HP

Basic

Performance

Power

Power SupplyMode *3)

COP

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

RVXVHT080GE / RVXVRT080GERVXVHT100GE / RVXVRT100GERVXVHT120GE / RVXVRT120GERVXVHT140GE / RVXVRT140GERVXVHT160GE / RVXVRT160GEHorse Power

Capacity

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingType/ControlLiquidGasDischarge Gas (DVM PLUS III HR)Oil (Flare)InstallationLimitationTypeFactory ChargingSound Pressure *4)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hkWkW

AØ/V/Hz

----

Ø,mmØ,mmØ,mmØ,mm

mm-

kgdB(A)

kgkgkgkg

mmmm

ºCºC

1

358

162.4 554,200 182.7

623,500 52.18 52.16 150

3/380~415/50HP/HR

3.11 3.50

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x1+11x366

240x1+320x3242x1+323x3253x1+337x3255x1+340x3

(880x1,703x765)x1+(1,200x1,703x765)x3(948x1,868x832)x1+(1,268x1,868x832)x3

-5~43-20~24

60HP

1

360

168.0 573,300 189.0

645,000 54.80 54.40 175

3/380~415/50HP/HR

3.07 3.47

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A

7.5x1+11x367

240x1+320x3242x1+323x3253x1+337x3255x1+340x3

(880x1,703x765)x1+(1,200x1,703x765)x3(948x1,868x832)x1+(1,268x1,868x832)x3

-5~43-20~24

62HP

1362

173.6 592,500 195.3

666,500 55.40 55.40 175

3/380~415/50HP/HR

3.13 3.53

Propeller/BLDC22.23 44.50 38.10 6.35 200

50 (40)R410A11x467

320x4323x4337x4340x4

(1,200x1,703x765)x4(1,268x1,868x832)x4

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeating

Max.LengthMax.Height

DVM PLUS IIIDVM PLUS III HRDVM PLUS IIIDVM PLUS III HR

2010 SAMSUNG DVM AIR CONDITIONER

32 33

Page 18: 2010 Samsung DVM Catalog

02l O

UT

DO

OR

UN

IT

02l O

UT

DO

OR

UN

IT

Specification Mini DVM

Notes*1) Nominal cooling capacities are based on - Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on - Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

RVXMHF050EA

Performance

Power

Power SupplyMode *3)

COP

Compressor

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

Horse Power

Capacity

Nominal RunningCurrent

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingTypePiston DisplacementOutput

Lubricant

TypeOutputAirflow RateLiquid (Flare)Gas (Flare)InstallationLimitationTypeFactory ChargingSound Pressure (Cooling/Heating) *3)

Net WeightShipping WeightNet Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hAA

kWkW

AØ/V/Hz

----

cc/RevkW

-cc

-W

m3/minØ,mmØ,mm

mm-

kgdB(A)

kgkg

mmmm

ºCºC

RVXMHF040EA

412.5

42,70014.5

49,40019.018.03.753.5830

1/220~240/50Heat Pump

3.333.91

Digital Scroll58.105.0

3MAF POE1,893

Propeller200x21059.5215.8810030

R410A5.5

55/56124132

932x1,128x3751,091x1,286x472

-5~43-20~24

514.0

47,80016.0

54,60022.420.14.604.1330

1/220~240/50Heat Pump

3.043.87

Digital Scroll62.985.4

3MAF POE1,893

Propeller200x21059.52

15.8810030

R410A5.5

55/57125133

932x1,128x3751,091x1,286x472

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeatingCoolingHeating

TypeCharging

Max.LengthMax.Height

RVXMHF060GA

Performance

Power

Power SupplyMode *3)

COP

Compressor

Fan

PipingConnections

Refrigerant

Sound

Set Size

OperatingTemp. Range

Model

Horse Power

Capacity

Nominal RunningCurrent

Nominal Input

Circuit Breaker (MCCB/ELB)

CoolingHeatingTypePiston DisplacementOutput

Lubricant

TypeOutputAirflow RateLiquid (Flare)Gas (Flare)InstallationLimitationTypeFactory ChargingSound Pressure (Cooling/Heating) *3)

Net WeightShipping WeightNet Dimensions (WxHxD)Shipping Dimensions (WxHxD)CoolingHeating

HPkW

Btu/hkW

Btu/hAA

kWkW

AØ/V/Hz

----

cc/RevkW

-cc

-W

m3/minØ,mmØ,mm

mm-

kgdB(A)

kgkg

mmmm

ºCºC

RVXMHF050GA

514.0

47,80016.0

54,6008.57.84.614.1320

3/380~415/50Heat Pump

3.043.87

Digital Scroll67.135.75

3MAF POE1,893

Propeller200x21059.5215.8810030

R410A5.5

55/57125133

932x1,128x3751,091x1,286x472

-5~43-20~24

616.0

54,60018.0

61,50011.09.9

5.244.8220

3/380~415/50Heat Pump

3.053.73

Digital Scroll77.206.65

3MAF POE1,774

Propeller220x21059.52

15.8810030

R410A5.5

57/60125133

932x1,128x3751,091x1,286x472

-5~43-20~24

Cooling *1)

Heating *2)

CoolingHeatingCoolingHeating

TypeCharging

Max.LengthMax.Height

• Ø1, 220~240V, 50Hz (4/5HP)• Ø3, 380~415V, 50Hz (5/6HP)

PROJECTBanca Transilvania

LOCATIONBucharest, Romania

TYPEOffice building

2010 SAMSUNG DVM AIR CONDITIONER

34 35

Page 19: 2010 Samsung DVM Catalog

03 Air that suits perfectly to your space

Samsung indoor units are not only equipped with high

performing functions, but they are also beautifully

designed to enlighten your space. Different types of

indoor units will be more than enough to satisfy

needs of your space and yourself. Only Samsung’s

functional yet beautiful indoor units will provide you

the cool air that you can enjoy.

PROJECTRestaurant Patron

LOCATIONNeo Psychiko Athens,Greece

TYPECafe - Restaurant

NUMBER OF OUTDOOR UNITS1 DVM + 1 CAC

NUMBER OF INDOOR UNITS13

PROJECTOffice Building

LOCATIONWaiblingen,Germany

TYPEOffice building

PROJECTRestaurant Kioupia

LOCATIONKolonaki Athens,Greece

TYPECafe-Restaurant

INDOOR UNITS

03l IN

DO

OR

UN

IT

INDOOR UNITS 38

42

48

52

56

70

74

| Wall-mounted Type

| Cassette Type

| Duct Type

| Floor & Convertible Type

| Indoor Unit Specification

| ERV System

| Accessories

2010 SAMSUNG DVM AIR CONDITIONER

36 37

Page 20: 2010 Samsung DVM Catalog

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Wall-mounted Type Main Feature

Sensational design and compact size wall-mounted

indoor units can be installed practically anywhere

without restriction. Design was improved one step

further with simple and modern style to enlighten

your interior space.

MB MB II Vivace Neo-Forte

Creation of an Intensely Purified ZoneProtection against diseaseSafe from allergy-causing agentsControls active oxygen which can cause disease,

cancer and accelerated aging

Do you know that harmful substances and virusesbreed in the space you live in?

How Works

Health Care System 5-Step Air Purifying System

improves your Indoor AirQuality and eliminates all your worries.

Active hydrogen /Oxygen ions

Active hydrogen and oxygen ionsare generated

Harmful substancesCombines with

Harmful substancesOH radical, Harmfulviruses and bacteria.

Harmlesswater

Turns into harmless water

Health Care System

(Micro Plasma Ionizer)

Good’sleep II

Best Temperature for deep sleepAccording to the stage of sleep, temperatures are adjusted so you fall into deep sleep faster and get up more refreshedin the morning for a great start of your day.

1. Falling asleep stage: Eases you into sleep by dropping the temperature.2. Sound sleep stage: Relaxes your body and raises your temperature slightly.3. Wake up stage: Allows you to wake up from comfortable intermittent air and it makes you feel refreshed.

Stage 1

Stage 1 Auto Roof Shutter(MB)

Stage 3

Stage 2

Step 5

Step 4

Step 3

Step 2

Step 1

The Samsung air conditioner is all you need tokeep your air consistently clean and fresh.

The Auto Roof Shutter keeps dirt from gettinginside.

Stage 2Biological contaminants and various pathogenssuch as bacteria, viruses and molds are removed.

Stage 3 DNA filter & 5 step filterExogenous endocrine-disrupting chemicals, hazardous materials and other harmful chemicals are removed.

2010 SAMSUNG DVM AIR CONDITIONER

38 39

Indoor Units Feature

Deodorizing filter

DNA or Catechin Filter

Silver Coated Evaporator(Optional)

Silver Coated Filter

Page 21: 2010 Samsung DVM Catalog

MB / MB II | Luxurious Refreshness

| Shadow Mirror

| Fresh and Pleasant Cooling

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Units Feature

Auto Roof Shutter (2.8/3.6kW)This unique air conditioner automatically seals off toprevent dirt infiltration when not in operation.

DNA FilterIt is a new technology that screens selectively for onlytoxic agents. This enables a smarter and effective airmanagement compared to other filters.

Deodorizing filterIncorporated with activated carbon, the DeodorizingFilter efficiently adsorbs cigarette smoke, pet odors andother unpleasant odors.

Silver Coated EvaporatorThe fins of the evaporator are triple-coated with environmentallyfriendly materials (2 layers of chrome-free silica, 1 layer ofSilver coating) to ensure efficient removal of condensationand to guarantee the production of clean and fresh air.

Neo Forte

Vivace

Deodorizing filterIncorporated with activated carbon, the DeodorizingFilter efficiently adsorbs cigarette smoke, pet odors andother unpleasant odors.

Silver Coated EvaporatorThe fins of the evaporator are triple-coated with environ-mentally friendly materials (2 years of chrome-free silica,1 layer of Silver coating) to ensure efficient removal ofcondensation and to guarantee the production of cleanand fresh air.Shadow Mirror Hidden Display Trim-less Design

Anti allergy filterMakes your skin feel fresh and clean. It removes invisibledust and bacteria, resulting in helping you avert allergy problems associated with such allergens.

Deodorizing filterIncorporated with activated carbon, the DeodorizingFilter efficiently adsorbs cigarette smoke, pet odorsand other unpleasant odors.

Silver Coated EvaporatorThe fins of the evaporator are triple-coated withenvironmentally friendly materials (2 years ofchrome-free silica, 1 layer of Silver coating) toensure efficient removal of condensation and toguarantee the production of clean and fresh air.

Catechin filterCatechin, extracted from green tea, is contained inthe filter and deactivates any captured bacteria andunpleasant odors.

Clean-Cut Front Panel Silver Accent LineBottom OpeningFront Panel

2010 SAMSUNG DVM AIR CONDITIONER

40 41

Good’sleep II

Auto Roof Shutter

Good’sleep II

DNA Filter

Deodorizing Filter Silver Coated Evaporator

Good’sleep II

Deodorizing Filter Silver Coated Evaporator

Deodorizing Filter Silver Coated Evaporator

Page 22: 2010 Samsung DVM Catalog

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Main Feature

Slim 1Way Cassette 2Way Cassette Mini 4Way Cassette 4Way Cassette

The new cassette type air conditioner isequipped with uniquely designed blades thatare wider to provide even cooling and heatingpower throughout the room.

Wide Blade

Airflow is directed towards theceiling which cause ceilingsoiling.

Airflow is directed downwardswithout having contact with theceiling.

Ceiling Soiling PreventionNewly designed panel will control the air direction to avoid having contact with the ceiling. This new design will prevent the ceiling soiling and keep your interior cleanerthan ever even, after a long period of operation.

Conventional Blade

Ceiling Ceiling

New Blade

High Lift-up Drain PumpThe lift-up drain pump lifts condensed waterup to 750mm, compared to the competitor’s700mm, allowing for flexible and convenientinstallation.

Fresh Air IntakeWith optional installation of an air intakemotor, fresh air can enter through the cassette unit so you have fresher air in the room.

Samsung's unique drain pipe prevents leaksand is easier to install with no need to usetape or adhesives.

Quick Connection of Drain Pipe

Company ASamsung

WIDEWIDEWIDEWIDEHIGHHIGHHIGHHIGH

QUICKQUICKQUICKQUICK

FRESHFRESHFRESHFRESH

2010 SAMSUNG DVM AIR CONDITIONER

42 43

Cassette TypeCassette type air conditioners have different numbers

and directions of outlets to provide the cool air evenly

in any type of space. Compact size of indoor units can

be installed even in low ceilings and the easy installation

method will save time that you once conventionally

needed to spend on installation.

Sub DuctThe Sub Duct lets you use the same air conditioner unit to cool additional smallerspace nearby. (The cassette unit is fitted witha knock-out component to accommodate this.)

SUB DUCTSUB DUCTSUB DUCTSUB DUCT

Indoor Units Feature

600(mm) 650

Lift-up RangeLift-up Range

700 750

750mm

700mm

46mm64mm

WIDER

Fresh air

Motor

Page 23: 2010 Samsung DVM Catalog

Slim 1Way Cassette 2Way Cassette

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

WIDE BLADE

QUICK CONNECTION OF DRAIN PIPE

CEILING SOILINGPREVENTION

HIGH LIFT-UP DRAIN PUMP

Slim and Compact DesignWant a cassette type air conditioner, but have limited space? Samsung's new Slim 1Way cassettetype air conditioner is the answer.

10.5kg

17kg

38% Down

4kW R410A model Weight

Only 135mm thickSamsung introduces the world's slimmest indoor air conditionerunit. Only 135mm thick, the slim 1Way Cassette air conditionercan be installed practically anywhere.

Lighter indoor unitThe first to apply ABS cabinets into its indoor units,Samsung has achieved the lightest units on the market. Itsslim lightweight design makes installation and maintenancea breeze.

Quiet OperationSamsung's new blade design drastically reducesnoise levels, so you can relax in peace and quiet.

25dB

35dB

30dB

43dB

Low

High

Fan speed Noise level

Faulty drainage installation or power failures cancause condensed water to flow back into the unit,causing leakage and odors. Samsung's air conditioners are equipped with a check valve builtdirectly into the drain pump to prevent water fromflowing backward.

Check Valve Inside Drain Pump

Check Valve

135m

m

155m

m

Drain pan is included within panel

QUICK CONNECTION OF DRAIN PIPE

HIGH LIFT-UP DRAIN PUMP

Small Size Big PerformanceThe 2Way cassette air conditioner is now 45%smaller than competitor’s models, so it's even easier to incorporate into building design.

Twin Cross Flow FanThe 2Way cassette type unit is perfect fit for long andnarrow rectangular type of space. Twin Cross FlowFan inside of the 2Way cassette will spread cool orwarm air even further and wider with less noise.

Standard Formula for Easy InstallationThe dimension of the 2Way cassette air conditionerallows for easy installation into standard ceiling grids(600Wx600D), so everything just falls into place.

230mm

890mm575mm

45%Decreased

305mm

1,180mm600mm

600mm

600mm

Cross flow fans

PROJECTEspaço Quinta

LOCATIONPortugal

TYPELeisure

Indoor Units Feature

2010 SAMSUNG DVM AIR CONDITIONER

44 45

HIGHHIGHHIGHHIGH QUICKQUICKQUICKQUICKWIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH

QUICKQUICKQUICKQUICK

| Slim and Quiet | Compact but Powerful

Ensure that there is sufficient installation space. Allow at least170mm for the installation.

NOTE

Min. 170mm

Page 24: 2010 Samsung DVM Catalog

Mini 4Way Cassette

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Units Feature

Ideal Compact SizeThe Mini 4Way cassette air conditioner can be installedon one standard ceiling tile (600Wx600D), which cansave installation time.

Unit : mm

Fan Speed AdjustmentFan speed can be adjusted according to ceilingheight by adjusting dip switch of indoor unit’s PCB.

3~3.5m 2.7m

High Ceiling

On : Increased fan speed Off : Standard fan speed

Standard Ceiling

QUICK CONNECTION OF DRAIN PIPE

HIGH LIFT-UP DRAIN PUMP

FRESH AIR INTAKE

Conventional 4Way

New 4Way

Detachable corners make installationand height adjustments much easier.

Air distribution

Detaching the whole panel tookmore time.

218mm

Air distribution

4Way Cassette

WIDE BLADE

FRESH AIR INTAKE

SUB DUCTQUICK CONNECTION OF DRAIN PIPE

CEILING SOILINGPREVENTION

HIGH LIFT-UP DRAIN PUMP

New Turbo Fan

Quiet OperationImagine a room of cool calmness. The aerodynamicallydesigned ‘Turbo Fan' minimizes noise from the turbulence of blade movement. Therefore noise isless than conventional models.

Uniform DistributionThe new 'Turbo Fan' with wide blades providesextreme cooling and heating power from 4 separateoutlets so the entire room gets cool or warm faster.Now, every nook and cranny is comfortable.

Outlet1

Outlet2

Outlet3

Outlet4

‘A’ View

‘B’ View

‘C’ View

Easy LevelingEach corner portion of the panel is detachable, whichgives easier access to adjust the height, therefore leveling and installation is much easier and quicker thanbefore.

Compact SizeThe 4Way cassette type unit has gotten even slimmer.Now only 218mm thick (4.5/5.6/7.1/9.0kW), 24%slimmer compare to competitor’s 288mm (9.0kW).It's still the industry leader in compactness and iseven easier to install in tight spaces.

2010 SAMSUNG DVM AIR CONDITIONER

46 47

WIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH

SUB DUCTSUB DUCTSUB DUCTSUB DUCT

HIGHHIGHHIGHHIGH

QUICKQUICKQUICKQUICKQUICKQUICKQUICKQUICKFRESHFRESHFRESHFRESH

FRESHFRESHFRESHFRESH

Efficient Cooling3-dimensional shaped blade, which has the worldwide patent, is able to spread cool or warm air further and evenly to all corners of the space.

Stylish Panel DesignThe stylish panel is well harmonized with any interiordesign.

| Evenly Distribute the Cool Air

| IdeallyEfficient

New 4Way Conventional 4Way

Page 25: 2010 Samsung DVM Catalog

Duct TypeOne duct type indoor unit can provide cool air

to multiple places in a building with flexible

installation options.

It doesn’t matter how complicated the floor

plan is because the duct type indoor unit

offers different solutions for any shape of the

interior. With the indoor unit hiding in the ceiling,

you can create clean interior looks.

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Main Feature

Slim Duct MSP Duct

Clean Filter SystemThe anti-bacteria filter and the filter cleaning indicator provide you with cleaner, healthier air. You deserve to breathe fresh air everyday.

Anti-bacteria FilterThe anti-bacteria filter not only traps dust particles, but suppresses proliferation ofmolds and bacteria.

BACTERIABACTERIABACTERIABACTERIA

Easy Filter CleaningAfter 1,000 hours of operation the filterclean indicator will inform you that the filtershould be cleaned. The filter can be easilyremoved from the bottom, left, or right ofthe unit. (1,000 hours is the default set time,which can be adjusted to 2,000 hours onthe internal PCB.)

High Lift-up Drain Pump (optional)The lift-up drain pump lifts condensed waterup to 750mm, compared to the competitor’s700mm, allowing for flexible and convenientinstallation.

HIGHHIGHHIGHHIGH

Smart Pressure ControlThe Smart Pressure Control System adjustsfan speed according to E.S.P(External StaticPressure), so the air conditioner always givesyou consistent cooling and heating powerregardless of the surrounding environment.

E.S.P Control

Air v

olum

e

Static pressure (mmAq)Minimum Maximum

H

H

M

M

L

L

2010 SAMSUNG DVM AIR CONDITIONER

48 49

Indoor Units Feature

Page 26: 2010 Samsung DVM Catalog

Slim Duct MSP Duct

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Units Feature

Slim DesignOnly 199mm thick, this slim design makes installation, maintenance and repair easy.

Easy to MaintainParts are easily accessible by simply opening thebottom panel, which reduces time and maintenance costs.

199mm

199mm

220mm

225mm

160 180 200 220210 230

ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA

EASY FILTER CLEANING

HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH

SMART PRESSURECONTROL

Flexible InstallationThe air inlet can be set up on either the bottom or rearof the unit, so there is more flexibility in installation.

Rear side air inlet

Bottom side air inlet

Suction Duct

Suction Duct

Tex

TexDiffuser

Diffuser

Flexible InstallationSamsung's MSP Duct air conditioners offer differentsolutions for any shape room allowing for specificairflow requirements.

L-shaped area Y-shaped areaAreas far apart

Narrow Width (5.6/7.1kW)

Middle Static Pressure

Slim DuctmmAq

MSP Duct

24

6

8

10

12

14

0~14mmAq

0~6mmAq

ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA

EASY FILTER CLEANING

HIGH LIFT-UP DRAIN PUMPHIGHHIGHHIGHHIGH

SMART PRESSURECONTROL

WIRED REMOTE CONTROLLERWiredWiredWiredWired

Easy to MaintainReduce time and maintenance costs bykeeping parts easily accessible.

900mmWidth measured without control box.

Silent Operation with the static-pressure controlThe external static pressure control makes it easy todesign duct work to ensure efficiency and silentoperation.

2010 SAMSUNG DVM AIR CONDITIONER

50 51

| Slim and Flexible | Silent with Pressure Control

Page 27: 2010 Samsung DVM Catalog

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Floor & ConvertibleTypeInstallation options can’t be more diverse than

Samsung’s floor and convertible type air conditioners.

With a variety of installation options and the elegant

design, wherever you install these indoor units, they

will become picture perfect.

Main Feature

2010 SAMSUNG DVM AIR CONDITIONER

52 53

Console Ceiling

Interior DesignNow with more flexibility in placement,the air conditioner can add a stylish element to your room.

INTERIORINTERIORDESIGNDESIGN

INTERIORINTERIORDESIGNDESIGN

Silent ModeIndoor units operate quietly with theleast possible noise.

Anti-bacteria FilterThe anti-bacteria filter not only trapsdust particles, but suppresses proliferationof molds and bacteria.

BACTERIABACTERIABACTERIABACTERIA

Virus Doctor improves your indoor AirQuality(IAQ) by eliminating the biologicalcontaminants that threaten your healthsuch as viruses, bacteria and allergycausing agents. Virus Doctor, anadvanced air purifying technology,offers you fresh, clean air you can enjoy.

Light Weight UnitThis extremely lightweight designmakes maintenance and installationeasy.

LIGHTLIGHTLIGHTLIGHT

Flexible Pipe InstallationThe drain pipe can be installed in 6different places, so you have moreoptions in where to place your airconditioner.

Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

Indoor Units Feature

Page 28: 2010 Samsung DVM Catalog

Console Ceiling

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Units Feature

2010 SAMSUNG DVM AIR CONDITIONER

54 55

Clean PanelStay clean with the smartly designed Clean Panel. Thisunique panel keeps dust from being accumulated so theunit and the room stays cleaner.

Slim DesignIt can't get any slimmer. This newly introduced consoletype air conditioner is only 199mm thick, the slimmeston the market. Its slim design easily integrates the unitinto your decor.

Silent Operation (23dB)

The silent, yet powerful and efficient cooling and heating system keeps things more comfortable. Silentmode is available in 4 different operating modes: High /Medium / Low / Silence.

2Way air outletsThere are two separate air outlets for cooling and heating. Having warmer air coming out from the bottompart of the air outlet will spread the warm air evenly throughout the room. Stay cooler and warmer in everycorner of your room.

199mm

INTERIORDESIGN

INTERIORINTERIORDESIGNDESIGN

INTERIORINTERIORDESIGNDESIGN

ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA

LIGHT WEIGHT UNIT

LIGHTLIGHTLIGHTLIGHT

SILENT MODEFLEXIBLE PIPEINSTALLATION

Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

WIRELESS REMOTECONTROLWirelessWirelessWirelessWireless

Elegant Design

Slim & Smart DesignThis extremely slim design with Clean Panel adds aesthetic value to any interior.

INTERIORDESIGN

INTERIORINTERIORDESIGNDESIGN

INTERIORINTERIORDESIGNDESIGN

ANTI-BACTERIA FILTERBACTERIABACTERIABACTERIABACTERIA

LIGHT WEIGHT UNIT

LIGHTLIGHTLIGHTLIGHT FLEXIBLE PIPEINSTALLATION

Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

Compact but PowerfulSamsung’s ceiling type air conditioner boasts a slim,compact design, half the size of its competitors’,with cooling power comparable to competitor’s larg-er products.

2way InstallationDepending on the space availability and the purposeof the air conditioner, the indoor unit can be installedunder the ceiling or on the floor.

Under Ceiling

Floor Standing

200%

100%

136%

118% 123%

100%

Size

7.1kW Model

Weight

Smaller Lighter

Black DisplayFunctional art, the touch screen display is elegant whileit maximizes the convenience of control.

| Slim and Elegant | Powerful Air from Ceiling or Floor

PROJECTUniversita Roma

LOCATIONRoma

TYPEUniversita

Page 29: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

56 57

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Unit Specification

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Optional Accessory- Specifications are subject to change without prior notice for product improvement.

MB/MBII Vivace (Shadow Mirror)

Feature

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

Model AVXWBH028EE

2.8

9,500

3.2

10,900

30

0.18

1/220~240/50

HP/HR

31 / 20

Cross Flow Fan

9.0

9.0

R410A

EEV

6.35

12.70

ID 18 hose

10.2

11.5

900x304x185

963x349x247

Filter (Washable)

ARH-1364

AVXWBH036EE

3.6

12,200

4.0

13,600

35

0.19

1/220~240/50

HP/HR

35 / 21

Cross Flow Fan

10.0

10.0

R410A

EEV

6.35

12.70

ID 18 hose

10.2

11.5

900x304x185

963x349x247

Filter (Washable)

ARH-1364

AVXWBH056EE

5.6

19,100

6.3

21,400

50

0.3

1/220~240/50

HP/HR

40 / 30

Cross Flow Fan

12.0

12.0

R410A

EEV

6.35

12.70

ID 18 hose

13.0

16.0

1,100x307x225

1,157x381x292

Filter (Washable)

ARH-1364

AVXWBH071EE

6.8

23,200

7.0

23,800

50

0.3

1/220~240/50

HP/HR

41 / 30

Cross Flow Fan

13.0

13.0

R410A

EEV

9.52

15.88

ID 18 hose

13.0

16.0

1,100x307x225

1,157x381x292

Filter (Washable)

ARH-1364

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

Model AVXWVH022EE

2.2

7,500

2.5

8,500

30

0.13

1/220~240/50

HP/HR

31 / 21

Cross Flow Fan

7.0

7.3

R410A

EEV *5)

6.35

12.70

ID 18 hose

8.5

11.5

825x285x189

900x349x252

Filter (Washable)

ARH-1364

AVXWVH028EE

2.8

9,500

3.2

10,900

30

0.18

1/220~240/50

HP/HR

31 / 21

Cross Flow Fan

7.0

7.3

R410A

EEV *5)

6.35

12.70

ID 18 hose

8.5

11.5

825x285x189

900x349x252

Filter (Washable)

ARH-1364

AVXWVH036EE

3.6

12,200

4.0

13,600

35

0.19

1/220~240/50

HP/HR

35 / 21

Cross Flow Fan

8.2

8.8

R410A

EEV *5)

6.35

12.70

ID 18 hose

8.5

11.5

825x285x189

900x349x252

Filter (Washable)

ARH-1364

AVXWVH056EE

5.6

19,100

6.3

21,400

50

0.30

1/220~240/50

HP/HR

40 / 30

Cross Flow Fan

13.3

14.0

R410A

EEV *5)

6.35

12.70

ID 18 hose

12.0

15.0

1,065x298x218

1,137x377x299

Filter (Washable)

ARH-1364

AVXWVH071EE

6.8

23,200

7.0

23,800

50

0.30

1/220~240/50

HP/HR

41 / 30

Cross Flow Fan

13.3

14.0

R410A

EEV *5)

9.52

15.88

ID 18 hose

12.0

15.0

1,065x298x218

1,137x377x299

Filter (Washable)

ARH-1364

Optional Accessories Standard Accessories

MWR-WE00 MWR-WH00 MWR-SH00

Individual Controllers

Wireless Remote Controller

Optional Accessories Standard Accessories

MWR-WE00 MWR-WH00 MWR-SH00

Individual Controllers

Wireless Remote Controller

Good’sleep II

Auto Roof Shutter DNA Filter

Deodorizing Filter

Silver Coated Evaporator

Good’sleep II

Deodorizing Filter Silver Coated Evaporator Anti allergy filter

Page 30: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

58 59

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Unit Specification

Neo Forte

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

Panel Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Model AVXCSH022EE

2.2

7,500

2.5

8,500

40

0.20

1/220~240/50

HP/HR

30/25

Cross Flow Fan

6.0

7.0

R410A

EEV

6.35

12.70

VP20(OD 25,ID 20)

10.5

13.5

970x135x410

1,164x212x478

PSSMA

3.1

4.5

1,180x25x460

1,259x144x539

Filter (Washable)

24/750

AVXCSH028EE

2.8

9,500

3.2

10,900

45

0.23

1/220~240/50

HP/HR

30/25

Cross Flow fan

7.0

8.0

R410A

EEV

6.35

12.70

VP20(OD 25,ID 20)

10.5

13.5

970x135x410

1,164x212x478

PSSMA

3.1

4.5

1,180x25x460

1,259x144x539

Filter (Washable)

24/750

AVXCSH036EE

3.6

12,200

4.0

13,600

50

0.25

1/220~240/50

HP/HR

32/27

Cross Flow fan

8.0

9.0

R410A

EEV

6.35

12.70

VP20(OD 25,ID 20)

10.5

13.5

970x135x410

1,164x212x478

PSSMA

3.1

4.5

1,180x25x460

1,259x144x539

Filter (Washable)

24/750

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Slim 1Way Cassette • Slim and Compact Design

• Quiet Operation

• Check Valve Inside Drain Pump

Optional Accessories

PSSMAMWR-SH00

Individual Controllers

Panel

MR-CH01MWR-WE00

WIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH QUICKQUICKQUICKQUICK

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Optional Accessory- Specifications are subject to change without prior notice for product improvement.

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

Model AVXWNH022EE

2.2

7,500

2.5

8,500

25

0.18

1/220~240/50

HP/HR

32/23

Cross Flow Fan

7.8

8.2

R410A

External EEV *5)

6.35

12.70

ID 18 hose

7.8

9.4

825x285x189

900x349x252

Filter (Washable)

ARH-465

AVXWNH028EE

2.8

9,500

3.2

10,900

25

0.18

1/220~240/50

HP/HR

32/23

Cross Flow Fan

7.8

8.2

R410A

External EEV *5)

6.35

12.70

ID 18 hose

7.8

9.4

825x285x189

900x349x252

Filter (Washable)

ARH-465

AVXWNH036EE

3.6

12,200

4.0

13,600

30

0.18

1/220~240/50

HP/HR

36/23

Cross Flow Fan

9.3

9.5

R410A

External EEV *5)

6.35

12.70

ID 18 hose

7.8

9.4

825x285x189

900x349x252

Filter (Washable)

ARH-465

AVXWNH056EE

5.6

19,100

6.3

21,400

45

0.27

1/220~240/50

HP/HR

40/30

Cross Flow Fan

12.0

13.0

R410A

External EEV *5)

6.35

12.70

ID 18 hose

13.0

16.0

1,065x298x218

1,137x377x299

Filter (Washable)

ARH-465

AVXWNH071EE

6.8

23,200

7.0

23,800

50

0.30

1/220~240/50

HP/HR

41/30

Cross Flow Fan

14.0

15.0

R410A

External EEV *5)

9.52

15.88

ID 18 hose

13.0

16.0

1,065x298x218

1,137x377x299

Filter (Washable)

ARH-465

MWR-WH00

Optional Accessories Standard Accessories

MWR-WE00 MWR-WH00 MWR-SH00

Individual Controllers

Wireless Remote Controller

Good’sleep II

Deodorizing Filter Silver Coated Evaporator Catechin filter

Page 31: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

60 61

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Unit Specification

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Mini 4Way Cassette • Slim and Compact Design • Quiet Operation

• Check Valve Inside Drain Pump

Optional Accessories

Individual Controllers

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

Panel Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Model AVXC2H056EE

5.6

19,100

6.3

21,400

70

0.38

1/220~240/50

HP/HR

36 / 28

Cross Flow Fan

14.0

16.0

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

21.0

25.0

890x230x575

1,077x299x642

P2SMA

4.0

8.0

1,030x25x650

1,103x151x727

Filter (Washable)

24/750

AVXC2H071EE

7.1

24,200

8.0

27,200

75

0.40

1/220~240/50

HP/HR

38 / 28

Cross Flow Fan

14.0

16.0

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

21.0

25.0

890x230x575

1,077x299x642

P2SMA

4.0

8.0

1,030x25x650

1,103x151x727

Filter (Washable)

24/750

2Way Cassette • Slim and Compact Design • Quiet Operation

• Check Valve Inside Drain Pump

Optional Accessories

Individual Controllers

P2SMA

Panel Panel

PMSMA

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

Panel Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Model AVXCMH028EE

2.8

9,500

3.2

10,900

90

0.50

1/220~240/50

HP/HR

30 / 25

Turbo Fan

10.1

11.9

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

17.0

20.0

575x260x575

660x310x635

PMSMA

3.0

5.0

670x35x670

717x93x717

Filter / Safety Grille

24/750

AVXCMH036EE

3.6

12,200

4.0

13,600

90

0.50

1/220~240/50

HP/HR

34 / 27

Turbo Fan

10.1

11.9

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

17.0

20.0

575x260x575

660x310x635

PMSMA

3.0

5.0

670x35x670

717x93x717

Filter / Safety Grille

24/750

AVXCMH056EE

5.6

19,100

6.3

21,400

95

0.52

1/220~240/50

HP/HR

41 / 33

Turbo Fan

10.6

12.6

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

17.0

20.0

575x260x575

660x310x635

PMSMA

3.0

5.0

670x35x670

717x93x717

Filter / Safety Grille

24/750

AVXCMH060EE

6.0

20,400

6.8

23,200

100

0.55

1/220~240/50

HP/HR

41 / 33

Turbo Fan

12.2

14.5

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

17.0

20.0

575x260x575

660x310x635

PMSMA

3.0

5.0

670x35x670

717x93x717

Filter / Safety Grille

24/750

HIGHHIGHHIGHHIGH FRESHFRESHFRESHFRESH QUICKQUICKQUICKQUICKHIGHHIGHHIGHHIGH QUICKQUICKQUICKQUICK

MWR-SH00MR-CH01MWR-WE00 MWR-WH00 MWR-SH00MR-CH01MWR-WE00 MWR-WH00

Page 32: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

62 63

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Unit Specification

Optional Accessories

Individual Controllers

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

4Way Cassette • New Turbo Fan • Easy Leveling

• Compact Size • Efficient Cooling

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

Panel Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Model

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Drain Pump (Pumping speed / lift)

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

kg

kg

mm

mm

-

l/h /mm

Cooling *1)

Heating *2)

Model AVXC4H045EE

4.5

15,300

5.0

17,000

40

0.19

1/220~240/50

HP/HR

34/29

Turbo Fan

14.5

16.5

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

25.0

31.0

840x218x840

926x280x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H056EE

5.6

19,100

6.3

21,400

40

0.19

1/220~240/50

HP/HR

34/29

Turbo Fan

14.5

16.5

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

25.0

31.0

840x218x840

926x280x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H071EE

7.1

24,200

8.0

27,200

45

0.21

1/220~240/50

HP/HR

36/30

Turbo Fan

17.0

18.5

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

25.0

31.0

840x218x840

926x280x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H090EE

9.0

30,700

10.0

34,100

50

0.23

1/220~240/50

HP/HR

39/32

Turbo Fan

19.5

21.5

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

25.0

31.0

840x218x840

926x280x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H112EE

11.2

38,200

12.5

42,600

50

0.23

1/220~240/50

HP/HR

40 / 33

Turbo Fan

23.0

26.5

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

29.0

35.0

840x288x840

926x360x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H128EE

12.8

43,600

13.8

47,000

65

0.30

1/220~240/50

HP/HR

41 / 35

Turbo Fan

25.0

29.5

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

29.0

35.0

840x288x840

926x360x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

AVXC4H140EE

14.0

47,700

16.0

54,500

80

0.36

1/220~240/50

HP/HR

45 / 38

Turbo Fan

26.5

32.0

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

29.0

35.0

840x288x840

926x360x926

P4SMA

7.0

10.3

950x35x950

1,042x103x1,042

Filter / Safety Grille

24/750

Panel

P4SMA

WIDEWIDEWIDEWIDE HIGHHIGHHIGHHIGH FRESHFRESHFRESHFRESH SUB DUCTSUB DUCTSUB DUCTSUB DUCT QUICKQUICKQUICKQUICK

MWR-SH00MR-CH01MWR-WE00 MWR-WH00

Note

Numbers within parenthesis are the values for large capacity units*.At least 245mm (315mm for large capacity units*) of space is need

for installation. * Large capacity units : 11.2/12.8/14.0kW

Page 33: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

64 65

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Unit Specification

Optional Accessories

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Slim Duct • Flexible Installation • Slim Design

• Easy to Maintain

Drain Pump

MDP-E075SEE / MDP-E075SEE1

Individual Controllers

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

Standard Accessories

OptionalAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

External Static Pressure

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Duct Receiver Kits

Drain Pump

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

mmAq

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

-

-

Cooling *1)

Heating *2)

Standard(Min.~Max.)

Receiver

Receiver Wire

Model AVXDSH022EE

2.2

7,500

2.5

8,500

80

0.40

1/220~240/50

HP/HR

31 / 26

Sirocco Fan

8.0

9.0

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

26.0

31.0

900x199x600

1,133x333x730

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH028EE

2.8

9,500

3.2

10,900

80

0.40

1/220~240/50

HP/HR

32 / 27

Sirocco Fan

9.0

10.0

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

26.0

31.0

900x199x600

1,133x333x730

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH036EE

3.6

12,200

4.0

13,600

80

0.40

1/220~240/50

HP/HR

32 / 27

Sirocco Fan

10.0

12.0

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

26.0

31.0

900x199x600

1,133x333x730

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH045EE

4.5

15,300

5.0

17,000

90

0.60

1/220~240/50

HP/HR

33 / 30

Sirocco Fan

14.5

16.5

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

31.0

39.0

1,100x199x600

1,330x330x730

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH056EE

5.6

19,100

6.3

21,400

100

0.60

1/220~240/50

HP/HR

33 / 30

Sirocco Fan

15.5

18.0

2 (0~4)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

31.0

39.0

1,100x199x600

1,330x330x730

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH071EE

7.1

24,200

8.0

27,200

120

0.60

1/220~240/50

HP/HR

36 / 32

Sirocco Fan

16.5

20.0

2 (0~4)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

31.0

39.0

1,100x199x600

1,330x330x730

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE

AVXDSH090EE

9.0

30,700

10.0

34,100

170

0.96

1/220~240/50

HP/HR

40 / 36

Sirocco Fan

29.0

34.0

3 (0-6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

43.0

51.5

1,300x295x690

1,600x444x831

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE1

AVXDSH112EE

11.2

38,200

12.5

42,600

170

0.96

1/220~240/50

HP/HR

40 / 36

Sirocco Fan

31.2

34.0

3 (0~6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

43.0

51.5

1,300x295x690

1,600x444x831

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE1

AVXDSH128EE

12.8

43,600

13.8

47,000

200

1.13

1/220~240/50

HP/HR

41 / 38

Sirocco Fan

34.0

36.0

3 (0~6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

46.0

54.5

1,300x295x690

1,600x444x831

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE1

AVXDSH140EE

14.0

47,700

16.0

54,500

220

1.24

1/220~240/50

HP/HR

41 / 38

Sirocco Fan

36.0

38.0

3 (0~6)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

46.0

54.5

1,300x295x690

1,600x444x831

Filter (Washable)

MRK-A00

MRW-10A

MDP-E075SEE1

BACTERIABACTERIABACTERIABACTERIAHIGHHIGHHIGHHIGH

MWR-SH00MR-CH01MWR-WE00 MWR-WH00

Page 34: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

66 67

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Unit Specification

Optional Accessories

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

MSP Duct • Silent Operation with the Static Pressure Control

• Narrow Width • Middle Static Pressure

• Easy to Maintain • Flexible InstallationIndividual Controllers

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

Standard Accessories

OptionalAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

External Static Pressure

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Duct Receiver Kits

Drain Pump

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

mmAq

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

-

-

Cooling *1)

Heating *2)

Standard(Min.~Max.)

Receiver

Receiver Wire

Model AVXDUH056EE

5.6

19,100

6.3

21,400

130

1.10

1/220~240/50

HP/HR

37 / 33

Sirocco Fan

14.5

15.5

4 (0~8)

R410A

EEV

6.35

12.70

VP25 (OD 32,ID 25)

31.0

36.0

900x260x480

1,146x345x584

Filter (Washable)

MRK-A00

MRW-10A

MDP-M075SGU3

AVXDUH071EE

7.1

24,200

8.0

27,200

190

1.25

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

18.5

20.0

4 (0~8)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

31.0

36.0

900x260x480

1,146x345x584

Filter (Washable)

MRK-A00

MRW-10A

MDP-M075SGU3

Drain Pump

MDP-M075SGU1 / MDP-M075SGU2 /MDP-M075SGU3

BACTERIABACTERIABACTERIABACTERIAHIGHHIGHHIGHHIGH WiredWiredWiredWired

AVXDUH090EE

9.0

30,700

10.0

34,100

240

1.30

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

19.5

21.5

6 (4~8)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

35.0

41.0

1,150x260x480

1,390x345x584

Filter(Washable)

MRK-A00

MRW-10A

MDP-M075SGU1

AVXDUH112EE

11.2

38,200

12.5

42,600

260

1.17

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

27.0

27.0

8 (6~12)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

39.0

46.0

1,150x320x480

1,390x420x584

Filter (Washable)

MRK-A00

MRW-10A

MDP-M075SGU1

AVXDUH128EE

12.8

43,600

13.8

47,000

370

1.67

1/220~240/50

HP/HR

39 / 35

Sirocco Fan

32.0

31.0

8 (6~14)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

52.0

60.0

1,200x360x650

1,447x425x769

Filter (Washable)

MRK-A00

MRW-10A

MDP-M075SGU2

AVXDUH140EE

14.0

47,700

16.0

54,500

410

1.86

1/220~240/50

HP/HR

43 / 38

Sirocco Fan

37.0

36.0

8 (6~14)

R410A

EEV

9.52

15.88

VP25 (OD 32,ID 25)

52.0

60.0

1,200x360x650

1,447x425x769

Filter (Washable)

MRK-A00

MRW-10A

MDP-M075SGU2

MWR-SH00MR-CH01MWR-WE00 MWR-WH00

Page 35: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

68 69

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Indoor Unit Specification

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.*5) Optional Accessory- Specifications are subject to change without prior notice for product improvement.

Ceiling• 2Way Installation

• Compact but Powerful

Notes*1) Nominal cooling capacities are based on: Indoor temperature: 27°C DB, 19°C WB, Outdoor temperature: 35°C DB, 24°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*2) Nominal heating capacities are based on: Indoor temperature: 20°C DB, 15°C WB, Outdoor temperature: 7°C DB, 6°C WB,

Equivalent refrigerant piping: 7.5m, Level differences: 0m*3) Mode - HP: Heat Pump, HR: Heat Recovery*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.- Specifications are subject to change without prior notice for product improvement.

Console• Slim & Smart Design • 2Way Air Outlets

• Silent Operation (23dB)

Optional Accessories Standard Accessories

Individual Controllers

Wireless RemoteControllers

Optional Accessories

Individual Controllers

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

Model AVXTJH028EE

2.8

9,500

3.2

10,900

30

0.25

1/220~240/50

HP/HR

38 / 23

Turbo Fan

7.0

7.2

R410A

EEV

6.35

12.70

ID 18 hose

15.2

20.3

720x620x199

810x710x295

Filter (Washable)

ARH-1378

AVXTJH036EE

3.6

12,200

4.0

13,600

35

0.29

1/220~240/50

HP/HR

39 / 24

Turbo Fan

8.5

9.0

R410A

EEV

6.35

12.70

ID 18 hose

15.2

20.3

720x620x199

810x710x295

Filter (Washable)

ARH-1378

AVXTJH056E*

5.6

19,100

6.3

21,400

62

0.49

1/220-240/50

HP / HR

44/25

Turbo Fan

13.0

13.5

R410A

EEV

6.35

12.70

ID 18 hose

15.2

20.3

720x620x199

810x710x295

Filter (Washable)

ARH-2208

Performance Capacity

Power

Power Supply

Mode *3)

Sound

Fan

Airflow Rate

Refrigerant

PipingConnections

Weight

Set Size

StandardAccessories

Input

Running Current

Sound Pressure (High/Low) *4)

Type

Cooling (High)

Heating (High)

Type

Control Method

Liquid (Flare)

Gas (Flare)

Drain (Quick Lock)

Net Weight

Shipping Weight

Net Dimensions (WxHxD)

Shipping Dimensions (WxHxD)

Filter / Safety Grille

Wireless Remote Controller

kW

Btu/h

kW

Btu/h

W

A

Ø/V/Hz

-

dB(A)

-

m3/min

m3/min

-

-

Ø,mm

Ø,mm

Ø,mm

kg

kg

mm

mm

-

-

Cooling *1)

Heating *2)

Model AVXTFH056EE

5.6

19,100

6.3

21,400

72

0.33

1/220~240/50

HP/HR

38 / 32

Sirocco Fan

14.0

14.5

R410A

EEV *5)

6.35

12.70

ID 18 hose

22.0

26.0

1,000x650x200

1,074x726x294

Filter (Washable)

-

AVXTFH071EE

7.1

24,200

8.0

27,200

80

0.35

1/220~240/50

HP/HR

41 / 36

Sirocco Fan

18.0

18.5

R410A

EEV *5)

9.52

15.88

ID 18 hose

22.0

26.0

1,000x650x200

1,074x726x294

Filter (Washable)

-

INTERIORINTERIORDESIGNDESIGN

INTERIORINTERIORDESIGNDESIGN BACTERIABACTERIABACTERIABACTERIA

LIGHTLIGHTLIGHTLIGHT

Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

INTERIORINTERIORDESIGNDESIGN

INTERIORINTERIORDESIGNDESIGN BACTERIABACTERIABACTERIABACTERIA

LIGHTLIGHTLIGHTLIGHT

Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation

WirelessWirelessWirelessWireless

MWR-SH00MWR-WE00 MWR-WH00 MWR-SH00MWR-WE00 MWR-WH00

Page 36: 2010 Samsung DVM Catalog

03l IN

DO

OR

UN

IT

What is proper ventilation?Misunderstandings about proper ventilation ofindoor spaces

Samsung has found the solution:Energy Recovery Ventilation Unit

2010 SAMSUNG DVM AIR CONDITIONER

70 71

ERV System

Harmful substances existing in the indoor air and the sicknesses they cause:

Indoor air contaminants

Cancer, Mucous membrane irritation,Heart disease and stroke

Cigarette Smoke

Asbestosis, CancerAsbestos

Irritations, Allergic reactions, CancerFormaldehyde (HCHO)

Damage central nervous system, CancerVolatile Organic Compound

Laryngitis, Decrease heart and lungfunction

Carbon Monoxide (CO)

Decrease lung functionNitrogen Dioxide

Cancer, Respiratory ailmentsParticle Contaminants

Ototoxic, HepatotoxicityInsecticide

CancerRadon

Main features of ERV

Wide compatibility with home networking and other air conditioning systems, intelligentcontrolling, with the energy efficiency, it provides optimized indoor air quality.

Powerful control

CO2 sensor provides fresh filtered air with an appropriate level of moisture, while saving energy to reduce the cost of ventilation.

Smart air refresh system - CO2 sensor

Samsung’s ERV has achieved effective heat exchange rate over 50% for cooling and 70% for heating. Test done by Samsung

World’s best heat exchange rate

Outside noise is absorbed by the ERV, which ensures quiet and sweet operation.Silent operation

Slim design flexible installation option helps use the space efficiently allowing installation even in low ceilings.

Easy installation

High efficiency filter keeps the high quality indoor air by eliminating microscopic particles.High efficiency filtering

ERV System(Energy Recovery Ventilator)

Always stay with clean and healthy air. ERV

system circulates the air to prevent indoor air

pollution and minimizes the energy loss with

energy recovery technology.

Page 37: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

72 73

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

ERV SystemFeature

Line-up

Specification

How it Works

Key Technology

New Diamond TypeOptimized Airflow Design High Efficiency ElementCompact size

Automatic Refresh System (CO2 Sensor) :OptionalERV is automatically operated to give fresh air into

room by sensing CO2 Level.

High Efficiency Motor (BLDC)Constant air volume by BLDC motor.

Intelligent Operating System (-15˚C) Without Heater

WinterIt reduces the costs of heating ventilated air by transferring heat from the warm inside air beingexhausted to the fresh (but cold) supply air.

SummerThe inside air cools the warmer supply air to reduceventilation cooling costs.

Heat

Heat

HeatHeat

Heat

Heat

Cool

Cool Cool

Cool Cool

CoolCool

IndoorOutdoor

Element

Rectangular Type

Diamond Type

Hexagonal Type

Compact Size & Flexible InstallationCompact and Slim in Size by High Efficiency Diamond

Element.

Ex.) Model No. RHF-035~050

Energy Saving Operation (Auto Mode)

Extreme Climates (Winter & Summer)When temperature and humidity level differencebetween indoor and outdoor is big, it operates as ERV.

Mild Climates (Spring & Fall)When temperature and humidity level differencebetween indoor and outdoor is small, it operates asconventional ventilation fan.

It automatically changes operation mode depending ontemperature difference between indoor and outdoor tosave energy.

Element

EA

OA

EA

OA

RA

SA

RA

SA

Element

Damper

Damper

RHF025EE250

RHF035EE350

RHF050EE500

RHF080EE800

RHF100EE1,000

Voltage

Frequency

Air Volume

External Static Pressure

Leakage Rate

Power Input

Current

Temperature Exchange

Efficiency

Effective Enthalpy

Exchange Efficiency

Sound Level (Turbo/Low)

Dust Collection Method

Net Dimensions(WxHxD)

Gross Dimensions (WxHxD)

Weight (Net/Gross)

Duct Diameter

Cooling

Heating

Cooling

Heating

Model

V

Hz

m3/hr

Pa

%

W

A

%

%

%

%

dB(A)

-

mm

mm

kg

Ø,mm

RHF025EE

220~240

50/60

250

110

10

115

0.7

70

70

50

70

27/22

High efficiency filter(PP)

600X350X660

760X400X807

25.5/30

150

RHF035EE

220~240

50/60

350

155

10

115

0.7

70

70

50

70

31/24

High efficiency filter(PP)

1,012X270X1,000

1,299X337X1,183

42.5/53.5

200

RHF050EE

220~240

50/60

500

165

10

175

1.1

70

70

50

70

32/25

High efficiency filter(PP)

1,012X270X1,000

1,299X337X1,183

42.5/53.5

200

RHF080EE

220~240

50/60

800

155

10

330

2.1

70

70

50

70

33/29

High efficiency filter(PP)

1,220X340X1,135

1,475X 440 X1,330

67/75.5

250

RHF100EE

220~240

50/60

1,000

155

10

450

2.9

70

70

50

70

37/32

High efficiency filter(PP)

1,220X340X1,135

1,475X440X1,330

67/75.5

250

Page 38: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

74 75

03l IN

DO

OR

UN

IT

03l IN

DO

OR

UN

IT

Accessories

MXJ-YA1509K

MXJ-YA2512K

MXJ-YA2812K

MXJ-YA2815K

MXJ-YA3119K

MXJ-YA3819K

MXJ-YA4422K

MXJ-HA2512K

MXJ-HA3115K

MXJ-HA3819K

MXJ-YA1500K

MXJ-YA2500K

MXJ-YA3100K

MXJ-YA3800K

MXJ-T3819K

MXJ-T4422K

MXJ-T3100K

MXJ-T3800K

MCU-4EAE2

MCU-4EAEV2 *1)

MCU-4EAEV3 *1)

MCU-6EAE2

15.0kW and below

Over 15.0 ~ 40.6kW and below

Over 40.6 ~ 46.4kW and below

Over 46.4 ~ 69.6kW and below

Over 69.6 ~ 98.6kW and below

Over 98.6 ~ 139.2kW and below

Over 139.2kW

Below 46.4kW

46.5 ~ 69.6kW

Over 69.7kW

23.2kW and below

Over 23.2 ~ 63.9kW and below

Over 69.6 ~ 139.2kW and below

Over 139.3kW

Below 48HP

Over 50HP

Below 48HP

Over 50HP

Below 4 indoor units

Over 5.6kW

Below 4.5kW

Below 6 indoor units

Requisite

Option

Requisite

Requisite

Requisite

Requisite(HR only)

DVM PLUS II,

DVM PLUS II HR

DVM PLUS III,

DVM PLUS III HR

DVM PLUS II,

DVM PLUS II HR

DVM PLUS III,

DVM PLUS III HR

DVM PLUS II, DVM PLUS

II HR, DVM PLUS III, DVM

PLUS III HR (Module)

DVM PLUS III HR

DVM PLUS III HR

(Module)

DVM PLUS II HR,

DVM PLUS III HR

Y-Joint

Header Joint

Y-Joint(Only for DVM PLUS IIIHR in high pressure gasconnection)

Outdoor Joint for DVM PLUS III / HR (Outdoor Connection)

Outdoor Joint only for DVM PLUS III HR Module(High Pressure GasConnection)

MCU Kits

ModelFeatureClassification Description Relevant Unit Remark

Notes

*1) MCU-4EAEV2/3 is the product that includes built in EEV to connect the indoor unit (wall-mounted type and ceiling type) that does notinclude EEV.

MXD-A13K116A

MXD-A13K200A

MXD-A16K200A

MXD-A22K200A

MXD-A13K216A

MXD-A13K300A

MXD-A16K213A

MXD-A16K300A

MEV-A13SA

MEV-A16SA

MDP-E075SEE

MDP-E075SEE1

MDP-M075SGU1

MDP-M075SGU2

MDP-M075SGU3

PSSMA

P2SMA

PMSMA

P4SMA

Below 3.6kW (1 Room) +

5.6 kW~9.0kW (1Room)

Below 3.6kW (2 Rooms)

5.6 kW~9.0kW (2Rooms)

Over 9.0kW (2Rooms)

Below 3.6kW (2 Rooms) +

5.6 kW~9.0kW (1Room)

Below 3.6kW (3 Rooms)

Below 3.6kW (1 Room) +

5.6 kW~9.0kW (2Rooms)

5.6 kW~9.0kW (3Rooms)

Below 3.6kW (1 Room)

5.6 kW~9.0kW (1Room)

Slim Duct (2.2~7.1) kW

Slim Duct (9.0~14.0) kW

M.S.P Duct (9.0, 11.2) kW

M.S.P Duct (12.8, 14.0) kW

M.S.P Duct (5.6, 7.1) kW

Slim 1Way Cassette

2Way Cassette

Mini 4Way Cassette

4Way Cassette

Option

Option

Option

Option

Requisite

EEV Kits

Drain Pump

Front Panel

ModelFeatureClassification Description Relevant Unit Remark

Wall-mounted &

Ceiling indoor unit

(For 2 indoor units)

Wall-mounted &

Ceiling indoor unit

(For 3 indoor units)

Wall-mounted &

Ceiling indoor unit

(For single unit)

-

-

Page 39: 2010 Samsung DVM Catalog

04Samsung’s control system is the most convenient

system in the industry. A variety of controllers

have been improved to control the system air

conditioner more simply and easily. With

Samsung’s innovative control system, your life

will become easier.

PROJECTPudong International Airport (Terminal 2)

LOCATIONShanghai, China

TYPEAirport

TOTAL CAPACITY OF OUTDOOR UNITS616 HP

NUMBER OF INDOOR UNITS162 Units

PROJECTPallas Informatik

LOCATIONAller, Denmark

TYPEBusiness Building

CONTROL SYSTEMS

04l C

ON

TR

OL S

YS

TE

MS

CONTROL SYSTEMS

78

80

90

92

94

95

96

97

98

| DVM System Structure

| Integrated Management System

| Centralized Control System

| Individual Control System

| Building Management System

| Guest Room Management System

| Power Distribution Unit

| DVM-Pro

| Accessories

PROJECTVMD Building 2008

LOCATIONZagreb, Republic of Croatia

TYPEBusiness &Apartments

Intelligent control and management

2010 SAMSUNG DVM AIR CONDITIONER

76 77

Page 40: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

04l C

ON

TR

OL S

YS

TE

MS

2010 SAMSUNG DVM AIR CONDITIONER

78 79

Outdoor Unit

Outdoor Unit

Indoor Unit

Indoor Unit

Indoor Unit

Indoor Unit

Indoor Unit

Indoor Unit

Interface Module

Interface Module

SiM (WHM SiM (WHM interface interface module)module)

Centralized

Centralized Controller

Controller

S-NET mini

S-NET mini

S-NET3S-NET3

DMS2DMS2

DMS2DMS2

DMS2DMS2

Network Hub

Network Hub

Web ClientWeb Client

Indoor Unit

Indoor Unit

Wired Remote

Wired Remote

Controller

Controller

Wired Remote

Wired Remote ControllerController

InternetInternet

Wired Remote

Wired Remote

Controller

Controller

Key Tag Key Tag Interface Module

Interface ModuleKey Tag Key Tag Interface Module

Interface ModuleWireless Remote

Wireless Remote

Controller

Controller

Building Management System

Outdoor Unit

Lonworks interface module

ControlCenter

Watt-hour

Watt-hour metermeter

DMS2

DMS2 is an internet-based management device whichstores and manages all the data relevant to system airconditioner. It controls up to 256 indoor units includingERV and AHU units and its built-in web server allowsaccess from multiple upper-level controllers. (S-NET3, S-NET mini, Web Client)

S-NET3

Integrated software which connects to the internet tomanage system air conditioners through DMS. S-NET3supports up to 16 different DMSs installed in differentbuildings which means you can control system air conditioners in 16 different places from a single computer connected to internet.

S-NET mini

Upper level controller, similar to S-NET3, but this touchscreen controller can be connected directly with the system air conditioners through centralized controllers orinterface modules allowing up to 256 indoor units. S-NETmini also supports up to 4 DMSs to provide the sameremote control function as S-NET3.

Centralized controller

Centralized controller is a device that controls up to 16groups (256 indoor units) of system air conditioners. Itcan control the system air conditioners individually or ingrounds and supports many other functions.

Interface modules

Interface module is a device, which transmits databetween the outdoor units and the upper level controllers.

Wired remote controller/ Wireless remote controller

Individual controller, which controls a single indoor unit.

DVM System Structure

Outdoor Unit

Indoor Unit

Indoor Unit

Indoor Unit

Interface Module

SiM (WHM interface module)

Centralized Controller

S-NET mini

S-NET3

DMS2

DMS2DMS2

DMS2DMS2

Network Hub

Web Client

Indoor Unit

Wired Remote

Controller

Wired Remote Controller

Internet

Wired Remote

Controller

Key Tag Interface ModuleKey Tag Interface ModuleWireless Remote

Controller

Watt-hour meter

Page 41: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

DMS2 (Data Management Server 2)The newly improved Data Management Server has gotten smarter. It can manage a variety of different airconditioning units and the newly upgrade functions will automatically manage your air conditioning system.

Built-in web server for PC-independent management and remote access control

Multiple upper-level control access (S-NET3, S-NET mini, Web-client)

Individual/Group control of up to 256 indoor unitsincluding ERV, AHU

User editable control logic

Accessible level management.

Dynamic security management

Operation & error history management

Weekly/Daily schedule control

Power distribution function

Current time management even during power failure (for 24 hours)

Data storage in non-volatile memory & SD memory

Emergency stop function with simple contact interface

DMS2 is available from May, 2010. This schedule is subjected to change

2010 SAMSUNG DVM AIR CONDITIONER

80 81

04l C

ON

TR

OL S

YS

TE

MS

IntegratedManagement

SystemFor a relatively larger place with lots ofindoor and outdoor units to manage, youneed a control solution, which is convenientto manage. Samsung’s Integrated managesystem is the perfect choice for managinglarge and middle-sized buildings.

Integrated Management System

MIM-D00A

DMS2

Interface Module

SIM Watt HourMeter

DMS2 System

CentralizedController

DMS2

Interface Module

SIM Watt HourMeter

Page 42: 2010 Samsung DVM Catalog

• Cooling only / No remote controller / Minimum setting temperature in cooling is 20oC

A zone

B zone

A zone

• Cooling only / Remote controller useB zone

04l C

ON

TR

OL S

YS

TE

MS

04l C

ON

TR

OL S

YS

TE

MS

Integrated Management System

2010 SAMSUNG DVM AIR CONDITIONER

82 83

DMS2 (Data Management Server 2)

Easy control & Monitoring• Control and monitoring of up to 256 indoor units via

internet network

• Operation on/off

• Operation mode, fan speed, temperature setting

• ERV, AHU support

Smart central management• Control & monitoring zone edition

• Wireless/wired remote control restriction

• Temperature limit setting

• Operation mode restriction

Flexible connectivity• Indoor unit control via Centralized controllers or

interface modules directly

• Select connection point according to site

Accessible level management• It is possible to specify the scope of control and monitoring unit by each user.

Enhanced graphical displayUser friendly icon-basedunit control

Color indication and iconmakes it easy to recognizeindoor unit state

Zoom in & Zoom out icondisplay

Convenient & stylish controller

Anytime, Anywhere DMS2 Control

Small & Medium size Connect interface module directly

Under 16 outdoor units

Over 16 outdoor units

Large sizeConnect centralized controllers

CentralizedController

Interface Module

Interface Module

CentralizedController

Interface Module

Interface Module

SIM Watt HourMeter

DMS2

Interface Module

Interface Module

SIM Watt HourMeter

Indoor unitERV

AHU

User1

User2

User4

User3

All installed units

Each user can controland monitor theallowed unit only

User1 Screen

DMS2

Page 43: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

04l C

ON

TR

OL S

YS

TE

MS

Integrated Management System

2010 SAMSUNG DVM AIR CONDITIONER

84 85

DMS2 (Data Management Server 2)

User editable control logic• User can edit control logic with arithmetic/conditional operators and parameters.

• Efficient energy saving can be realized for various operation conditions.

Ex) Energy saving function, Operation adjustment depending on outdoor temperature

Power distribution system• Power distribution to up to 256 indoor units

• Data query for watt-hour, use time and use ratio

• File save in Microsoft Excel format

• 1-year worth of power distribution data storage

Useful history management• DMS2 records indoor unit operation and error

occurrence history.

• It makes convenient to analyze air-conditioner operation and maintain units

1. Operation On/Off execution time2. Daily accumulated operation On time3. Schedule operation execution time

Emergency contact control• Interlock with emergency alarm system

• Indoor unit operation with simple contact input.

• Full unit control On/Off and restrict remote controller.

• State output (Operation/Error) for synchronous control

• Extended contact control with 10 channels of inputand output

Speed-up hardware improvementImproved hardware makes you access your air-conditioner faster than ever before.

• CPU upgrade (800MHz)

• Ethernet 100base-T (100Mhz)

• RS485 communication channel increase (1 channel --> 5 channels)

Dynamic user security management• By ID and password, general user, manager and

administrator can be registered separately.Administrators (Utility managers) have an authorityto put accessible levels of DMS2 functions onusers.

Powerful data backup• Important data is stored on SD memory card safely.1. Indoor/outdoor unit name2. Power distribution data3. Operation history (On/Off by DMS)4. DMS power On/Off history5. System configuration 6. Others

Rapid & easy service response• Real time malfunction state monitoring

• E-mail dispatches when malfunctions occur

• Remote monitoring of all units detail state(Outdoor unit / indoor unit cycle data).

Functions

Control / Monitoring

Zone management

Schedule

Power distribution

System configuration

Admin

Access all

O

O

O

O

O

Manager

O

O

O

O

X

User

O

X

O

X

X

Changeable

Malfunction e-mail

Automatic storing

Automatic system recovery after service

Operation history

1. Error occurred unit name2. Error details3. Error occurrence/clear time4. Error state (solved / unsolved )

Error history

4 times faster

RoomOutdoor

Air conditioner /ERV / AHU And / OrCycle data

Arithmetic equationFunction

360kWh

460kWh

140kWh

Indoor unit operation state

1. Operation data accumulation andpower distribution

2.Data extract - Excel format

610kWh

180kWh

5th Floor

4th Floor

3rd Floor

2nd Floor

1st Floor

Building Control System

Fire Control System Error Status Indicator

Operation Restriction

Remote Service

Logic

Control

Out temp < Room temp

Turn ON ERV (Cool air intake Up)

Room temp < Out temp

Turn ON air conditioner

Page 44: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

04l C

ON

TR

OL S

YS

TE

MS

Integrated Management System

2010 SAMSUNG DVM AIR CONDITIONER

86 87

S-NET3 Feature

Fully integrated PC management software.

• Up to 16 DMSs connection through the Ethernet.

• Central management of up to 4,096 indoor/heat

exchange units.

• Schedule/Zone control.

• Error/Operation history management.

• Power distribution management and analysis.

S-NET3

S-NET3 System

Supports 16 DMSs

S-NET3

Control and Monitoring• Control & monitoring of up to 4,096 indoor units

• ERV unit management

• Wireless/wired remote control restriction

• Temperature limit setting

• Operation mode lock

• Multiple/full indoor unit selection

• Icon-based indoor unit display mode

Schedule Control• Graphical schedule settings

• Weekly, Daily schedule control

• Exception date setting

Zone Management• Management structure customization regardless

of installation structure

• Control zone creation/edition/deletion

• Tree structure zone management control

Power Distribution Management• Data query for power distribution and

operation time

• Power distribution report generation and print

• Time section setting for different electricity rates

• Group setting for power distribution summation

History Management• Error/Event history management

• Indoor unit operation history management

• Report generation and print

Cycle monitoring• Monitoring outdoor / indoor unit cycle data

(Supported for specific outdoor unit models)

You can manage a group of buildings with S-NET3 through Data Management Servers that manage each ofthe buildings. S-NET3 provides flexible and complete control for a great variety of applications.

Page 45: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

04l C

ON

TR

OL S

YS

TE

MS

Integrated Management System

2010 SAMSUNG DVM AIR CONDITIONER

88 89

S-NET mini FeatureS-NET mini supports up to 4DMSs to provide the same remote control functions as S-NET3 and this touchscreen controller can be connected directly with system air conditioner through centralized controller or interfacemodules allowing up to 256 indoor units.

Dynamic compatibility options (DMS, centralized controller, interface module)

• Control and monitoring of up to 256 indoor units

• Detailed cycling information monitoring

• Schedule function (Weekly, Daily)

• USB keyboard support

• Error display

• 7-inch wide LCD display

• Temperature limit setting

• Touch screen

• Zone control

• Child-lock setting

• Operation mode lock

• External contact control

S-NET mini

Dynamic Compatibility Option

Control and monitoring• Control & Monitoring of up to 256 indoor

units/ERVs• Operation control and monitoring

• Detailed operation cycling information monitoring

• Wireless/wired remote control restriction setting

Schedule Control• Maximum 256 Weekly, Daily schedule control

• Schedule repetition, exception date setting

• Schedule edit (add, edit, delete)

• Detailed operation schedule setting

• Remote control restriction option setting

Zone Management• Management structure customization regardless

of installation structure

• Control zone creation/edition/deletion

Central Restriction Function• Upper/Lower temperature limit setting

• Operation mode lock

Cycle Monitoring• Outdoor/Indoor unit cycling information

monitoring (supported for specific outdoor unit models)

Error Management• Error history management

• Error management information query

• Detailed error information query

Supports 16

InterfaceModules

Supports 4 DMSs

Supports 16

CentralizedControllers

S-NET mini

Page 46: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

Centralized Controller

Maximum 16 group controls (Maximum 256 Indoor units)

Unified/Individual indoor unit control (On/Off)

Wireless/wired remote control restriction

Cooling/Heating mode control

Indoor unit error display

2010 SAMSUNG DVM AIR CONDITIONER

90 91

04l C

ON

TR

OL S

YS

TE

MS

Centralized Control

SystemCentralized control system is morethan enough to control multiplegroups and individual indoor units.With samsung’s centralized controller,conveniently and efficiently control themultiple or individual indoor units.

Control Systems Function Icon

Centralized Control System

MCM-A202B

Function Controller

Control and monitoring of up to 16 indoor unit groups

MCM-A100

To use Function Controller, it requires to be connected toMCM-A202A

MCM-A202B has compatibility with MCM-A202A

MIM-B13B has compatibility with MIM-B13A

Operation Mode Selection Switch

Operation mode selection (Cooling, Heating or Auto)

Mixed operation mode protection

Communicator between indoor/outdoor units and the centralized controller

Communicator between indoor/outdoor units and the centralized controller

MCM-C200

Interface Module

MIM-B13B

MIM-B04A

ON/OFF, OPERATION MODE, FAN SPEED, AIRFLOW, TEMPERATURE SETTING

OperationOperationOperationOperationINDIVIDUAL AND GROUPCONTROL (MAXIMUM 16INDOOR UNITS)

GroupGroupGroupGroup

ErrorErrorErrorErrorERROR DISPLAY

FILTER REPLACEMENTALARM RESET

FilterFilterFilterFilter

OperationOperationOperationOperation ErrorErrorErrorError FilterFilterFilterFilter

Page 47: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

2010 SAMSUNG DVM AIR CONDITIONER

92 93

04l C

ON

TR

OL S

YS

TE

MS

Individual Control

SystemThere are a variety of wired and wirelesscontrollers for convenient use of your airconditioners. With different controloptions, you can choose one that suitsfor your air conditioning environment.

Individual Control System

Control Systems Function IconON/OFF, OPERATION MODE, FAN SPEED, AIRFLOW, TEMPERATURE SETTING

OperationOperationOperationOperation

SLEEP & SILENT MODESilentSilentSilentSilent

BUILT-IN ROOM TEMPERATURE SENSOR

CHILD LOCKLockLockLockLock

AUTOMATIC STOP MODEAuto StopAuto StopAuto StopAuto Stop

WIRELESS REMOTECONTROL RESTRICTIONWirelessWirelessWirelessWireless

CLEAR & BRIGHT SCREENWITH LCD BACKLIGHT

BrightBrightINDIVIDUAL AND GROUPCONTROL (MAXIMUM 16INDOOR UNITS)

GroupGroupGroupGroup

ErrorErrorErrorErrorERROR DISPLAY

FILTER REPLACEMENTALARM RESET

FilterFilterFilterFilter

OperationOperationOperationOperation SilentSilentSilentSilent

LockLockLockLock Auto StopAuto StopAuto StopAuto Stop

WirelessWirelessWirelessWireless

BrightBright

GroupGroupGroupGroup ErrorErrorErrorError FilterFilterFilterFilter

OperationOperationOperationOperation GroupGroupGroupGroup ErrorErrorErrorError FilterFilterFilterFilter

Wired Remote Controller

Unified controller (A/C, ERV,A/C+ERV)

• Different permission levels

• Weekly schedule setting(A/C, ERV, A/C+ERV)

• Exception date setting

MWR-WE00 (Multi function)

Simplified Wired Remote Controller

Mode selection protection

MWR-SH00

ERV Wired Remote Controller

Individual and group control(Maximum 16 ERVs)

On/Off control

Operation mode (By-Pass, HeatExchange), fan speed

Simple schedule control

Error display

Synchronous operation withindoor units

MWR-VH02

OperationOperationOperationOperation SilentSilentSilentSilentLockLockLockLock Auto StopAuto StopAuto StopAuto Stop

Simple schedule control

Different permission levels

MWR-WH00

Wireless Remote Controller

Simple schedule control

Wide display

Soft touch button

MR-CH01OperationOperationOperationOperation FilterFilterFilterFilter

Wireless Signal Receiver (for Duct-type indoor unit)

ON/OFF control

Operation indication

Error Indication

Filter replacement sign

Use with receiver wire, MRW-10A

MRK-A00

External Room Sensor

External sensor to senseexact user environment temperature

MRW-TA

7-day Scheduler

Up to 100 weekly and daily schedule settings

• Schedule setting based on 1-minute time units

• Digital clock display

• Permanent schedule setting storage

• Current time protection from blackout(maximum 3 days)

• Use with wired remote controller, orcentralized controller. (MWR-TH01,MCM-A202B)

MWR-BS00

Page 48: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

2010 SAMSUNG DVM AIR CONDITIONER

94 95

04l C

ON

TR

OL S

YS

TE

MS

Building Management

SystemBMS (Building Management System)makes it possible to control and monitor the air conditioning networkusing the remote control and monitoringfunction. Optimum control with BMS-related interface modules keeps the airconditioning system efficient, savesenergy, reduces maintenance costsand extends the life cycle of the units.

Guest Room Management System

Lonworks

Interface for Lon-Connection to Lonworks management system

Quick and easy installation

Up to 12 indoor units can be controlled

Communication : RS485 to Lonworks

Upper physical layer : FTT-10A

MIM-B07

BMS Control Function

• On/Off control• Temperature setting• Operation mode• Fan speed

• On/Off• Operation mode• Room temperature• Error information

Monitoring Function

The Guest Room Management System is a smartway to save energy and money.When the Key Tag is in place, the air conditioner is activated. When the Key Tag is removed, the air conditioner switches off. Now you can avoidcooling an unoccupied room and save energy.

Key Tag Interface Module

Indoor unit control by external contact signals

Individual/Group control of up to 16 indoor units

Combinational use with sensor/timer/emergencyinputs

MIM-B02

Room 501

Key-Holder

Room 502

Key-Holder

Room 503

Key-Holder

Room 504

Key-Holder

External Contact Interface Module

Direct indoor unit control by external contact signal

Window-synchronized indoor unit control

Emergency control with simple contact input

Indoor unit operation/error state output throughrelay contacts

MIM-B14

Example

Key-Tag

On/Off

Window OpenSensor

MalfunctionAlarm

External deviceControl

On/Off On/OffError

(Wall mounted type indoor unit : Only the model including EEV supports state output function)

Example

Page 49: 2010 Samsung DVM Catalog

04l C

ON

TR

OL S

YS

TE

MS

04l C

ON

TR

OL S

YS

TE

MS

Power Distribution Unit

2010 SAMSUNG DVM AIR CONDITIONER

96 97

Real-time power distribution for one indoor/outdoorsystem.

Power distribution to maximum 48 indoor units.

Communication error display.

Total system power consumption display.

Power consumption display of individual indoor units.

Data storage even during a power failure.

MCM-B102

Exclusive use for DMS power distribution.

Connection with up to 8 watt-hour meters.

RS485 interface with watt-hour meters.

Power consumption display for each watt-hour meter.

Automatic detection of specified watt-hour meters.

MIM-B12

DVM - Pro (DVM, FJM, CAC Equipment Selection Software)

Room01(60kWh)

Room04(210kWh) 600kWh

Room03(210kWh)

Room02(120kWh)

RS 485

RS 485

Power Supply

• Consult with Samsung Electronics for watt-hour meter interface

= x

Room01

Room02

Room03

Room04

40%

30%

20%

10%

0%Room01 Room02 Room03 Room04

20% 19.4%

35.0%35.3% 35.0%35.1%

Actual Usage Rate

Displayed Rate

10.2% 10.2%

Room 01 electric powerconsumption

Total powerconsumption

Demand capacityof Room 01

Total demand capacityof indoor units

Watt-hour meter Interface Module

DVM-Pro Sales mode• Workspace: Creation ‘Project’ & ‘Workspace (DVM, FJM, CAC)’

• Indoor Unit: Indoor unit and accessory selection

• Outdoor Unit: Automatic selection and capacity simulation

• Piping: Basic, standard or manual selection with system check

• Wiring: Automatic diagram with communication wiring of indoor/outdoor/control units and electric power meters

• Control system: Automatic control unit selection

• Report: Specifications, diagrams and quotation

Download!www.dvmsystem.com Download Center DVM-Pro

DVM-Pro CAD mode• Quick, easy, precise design

• Compatibility with AutoCAD

• Automatic calculation: Refrigerant & drain pipe size

• Automatic selection: Refnet joint, header & distributor kit

• System check: Installation regulation & refrigerant addition

• Simulation: System capacities

• Easy control system selection

• Automatic report: Piping installation diagram, equipment list & quotation

Contact to Samsung HQ or Distributors for DVM-Pro CAD!

Page 50: 2010 Samsung DVM Catalog

2010 SAMSUNG DVM AIR CONDITIONER

98 99

AccessoriesClassification Product Model Image Application Model

IntegratedManagementSystem

Controller

InterfaceModule

DMS2 MIM-D00A DVM Series, FJM, CAC, ERV

DVM Series, FJM, CAC, ERV

DVM Series, FJM, CAC, ERV

S-NET3 MST-P3P

S-NET mini MST-S3W

DVM Series, FJMSiM MIM-B12

CentralizedControlSystem

InterfaceModule

DVM Series, FJM, CAC, ERV

DVM Series, FJM, CAC

Mini DVM(R410A), DVM PLUS II, DVM PLUSII HR, DVM PLUS III, DVM PLUS III HR, FJM,ERV

MCM-A202BController Centralized Controller

MCM-A100Function Controller

MIM-B13BCentralized Control Interface Module

DVM, DVM PLUS, DVM HR, CACMIM-B04A

DVM Series (Except HR models)MCM-C200Operation Mode Selection Switch

DVM Series, FJMPower Distribution Unit

DVM Series : Mini DVM, DVM, DVM PLUS, DVM HR, DVM PLUS II, DVM PLUS IIHR, DVM PLUS III, DVM PLUS IIIHR

MCM-B102

CAC, Mini DVM(R410A), DVM PLUS II, DVM PLUS II HR, DVM PLUS III, DVM PLUS III HR, FJM(Non MHFKEA)

External Contact Interface Module MIM-B14

Building ManagementSystem

Lonworks Interface Module MIM-B07 DVM Series, FJM

Power Distribution

DVM Series, FJM (Non MHFXEAB)Key-tag Interface Module MIM-B02Guest RoomManagementSystem

IndividualControlSystem

Controller Wireless Remote Controller MR-CH01 Cassette, Ceiling, Duct (Receiverneeded), Console (Included)

Cassette, Wall Mounted, Ceiling, Duct, Console

Duct (For Wireless Remote Controller)

Duct (For Wireless Remote Controller)

Centralized Controller

Cassette, Wall Mounted, Ceiling, Duct, Console

Wired Remote Controller MWR-WH00

Cassette, Wall Mounted, Ceiling, Duct, Console

Simplified Wired Remote Controller MWR-SH00

ERVERV Wired Remote Controller

ERV CO2 Sensor

MWR-VH02

Wireless SignalReceiver Kit

MRK-A00Wireless Signal Receiver

Receiver Wire MRW-10A

7-day Scheduler

External Room Sensor

MWR-BS00

MRW-TA

Cassette, Wall Mounted, Ceiling, Duct, Console, ERV

Wired Remote Controller (Multi Function) MWR-WE00

ERVMOS-C1

Icon IndexWall-mounted Type Icon

Auto Roof ShutterAir conditioner automatically sealsoff to prevent dirt infiltration.

Virus Doctor generates Hydrogenatoms and Oxygen ions to createhealthier air.

DNA FilterThe DNA structure possesses qualities inabsorbing and eliminating microscopiccarcinogenic agents.

Good’sleep IIControl the air temperature during yoursleep to enjoy a comfortable sleep andrefreshed wake up.

Cassette Type Icon

WIDE BLADEWider blades provide moreeven cooling power.

CEILING SOILINGPREVENTIONNewly designed panel preventsceiling contamination.

HIGH LIFT-UP DRAIN PUMPLift-up condensed water upto 750mm higher than anyother competitor.

FRESH AIR INTAKEOptional air intake motorbrings in fresh air from outside.

QUICK CONNECTIONOF DRAIN PIPEUnique drain pipe connectionis easy to install.

SUB DUCTThe Sub Duct makes it easyto provide air conditioning toa nearby smaller space.

WIDEWIDEWIDEWIDE

HIGHHIGHHIGHHIGH SUB DUCTSUB DUCTSUB DUCTSUB DUCTQUICKQUICKQUICKQUICK

FRESHFRESHFRESHFRESH

Duct Type Icon

Floor & Convertible Type Icon

Control System Icon

ANTI-BACTERIA FILTERAnti-bacteria Filter traps dust particles and suppresses proliferationof molds and bacteria.

EASY FILTER CLEANINGFilter cleaning indicator willlet you know when the filterneeds to be cleaned.

HIGH LIFT-UP DRAIN PUMPLift-up condensed water upto 750mm higher than anyother competitor.

SMART PRESSURE CONTROLAdjusts fan speed to provideconstant cooling and heatingperformance.

WIRED REMOTE CONTROLLERDefault wired remote controlleris provided.

BACTERIABACTERIABACTERIABACTERIAHIGHHIGHHIGHHIGH

WiredWiredWiredWired

INTERIOR DESIGNThe clean, modern designcomplements any decor.

LIGHT WEIGHT UNITExtremely lightweight, so maintenance and installation is easy.

ANTI-BACTERIA FILTERAnti-bacteria Filter traps dustparticles and suppresses proliferation of molds and bacteria.

AUTO CHANGEOVERAutomatically changes operationmode according to temperaturesetting.

FLEXIBLE PIPEINSTALLATIONThe pipe can be installedin 6 different places formore placement options.

SILENT MODEIndoor and outdoor unitoperates silently.

WIRELESS REMOTECONTOLLERDefault wireless remotecontroller is provided.

INTERIORINTERIORDESIGNDESIGN

INTERIORINTERIORDESIGNDESIGN BACTERIABACTERIABACTERIABACTERIA

LIGHTLIGHTLIGHTLIGHT

AUTOAUTOAUTOAUTO

Flexible PipeFlexible PipeInstallationInstallationFlexible PipeFlexible PipeInstallationInstallation WirelessWirelessWirelessWireless

ON/OFF, OPERATION MODE, FAN SPEED, AIRFLOW, TEMPERATURE SETTING

OperationOperationOperationOperation SLEEP & SILENT MODESilentSilentSilentSilent

BUILT-IN ROOM TEMPERATURE SENSOR

CHILD LOCKLockLockLockLock

AUTOMATIC STOP MODEAuto StopAuto StopAuto StopAuto Stop

WIRELESS REMOTECONTROL RESTRICTIONWirelessWirelessWirelessWireless

CLEAR & BRIGHT SCREENWITH LCD BACKLIGHT

BrightBrightINDIVIDUAL AND GROUPCONTROL (MAXIMUM 16INDOOR UNITS)

GroupGroupGroupGroup

ErrorErrorErrorErrorERROR DISPLAYFILTER REPLACEMENT

ALARM RESETFilterFilterFilterFilter

Virus Doctor generates Hydrogenatoms and Oxygen ions to createhealthier air.