sat procedure rev0

Upload: lrpatra

Post on 06-Jul-2018

265 views

Category:

Documents


1 download

TRANSCRIPT

  • 8/17/2019 SAT Procedure Rev0

    1/27

    gGE T&D  

    Document Number : P3405_SAT_Procedure_Rev0.doc

    Version : 1

    Revision : 0

    Date : 14 May 2008

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - SiteAcceptance Test Procedure

  • 8/17/2019 SAT Procedure Rev0

    2/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    ii  

     NOTICE OF COPYRIGHT & PROPRIETARY RIGHTS 

    © 2008, General Electric All rights reserved.

    The contents of this presentation are the property of General Electric No part of this work may

    be reproduced or transmitted in any form or by any means, except as permitted in written

    license agreement with General Electric 

    The information contained in this document is subject to change without notice.

    TRADEMARK NOTICES

    WESDAC  is a registered trademark of General Electric Company, General Electric and/or GE

     Harris Energy Control Systems Canada, Inc. All other brand and product names mentioned in

    this document are trademarks or registered trademarks of their respective companies.

  • 8/17/2019 SAT Procedure Rev0

    3/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    iii  

    Table of Contents

    About This Document.............................................................................................................. vi Purpose of this Document ....................................................................................................... vi 

    Definition of Terms.................................................................................................................vii 

    Chapter 1  SAT Requirements................................................................................................. 1-1 

    1.1  Scope of Tests .............................................................................................................1-1 

    1.2  Hardware Environment ............................................................................................ 1-1 

    1.3  Software Environment............................................................................................... 1-1 

    1.4  System Availability Tests ..........................................................................................1-2 

    1.5  Test Equipment ..........................................................................................................1-2 

    1.6  Test Witness................................................................................................................ 1-2 

    Chapter 2  Communications Equipment and Time Synchronization Equipment Tests .... 2-3 

    2.1  LAN Communications Functional Check................................................................ 2-3 

    2.2  Network Management Software (NMS) Check ......................................................2-4 

    2.3  IEC 60870-5-101 Serial Communication Check .....................................................2-4 

    2.3.1 Gateway Communications to PLCC Modem ..........................................................2-4

    2.3.2 IEC 60870-5-101 Serial Communications Verification ..........................................2-4

    2.4  Time Synchronization Tests......................................................................................2-5 

    2.4.1 Time Synchronization Equipment Functional Check.............................................. 2-5

    2.4.2 System Time Synchronization Check...................................................................... 2-6

    Chapter 3  SAS Operational Tests........................................................................................... 3-1 

    3.1  System Data Retrieval ...............................................................................................3-1 

    3.1.1 Digital Inputs Retrieval............................................................................................3-1

    3.1.2 Digital Outputs......................................................................................................... 3-2

    3.1.3 Analog Inputs........................................................................................................... 3-2

    3.2  Software Interlock Logic ........................................................................................... 3-3 

    3.3  Synchronizing Tests ................................................................................................... 3-3 

    3.3.1 Check Synchronization............................................................................................ 3-33.4  220kV Auto-Sequencing ............................................................................................ 3-4 

  • 8/17/2019 SAT Procedure Rev0

    4/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    iv  

    3.4.1 220kV Auto-Sequencing..........................................................................................3-4

    Chapter 4  HMI/Server Tests ................................................................................................... 4-1 

    4.1  HMI Functions Test................................................................................................... 4-1 

    4.1.1 Shutdown and Startup of Servers.............................................................................4-1

    4.1.2 HMI Security and Access Test ................................................................................4-14.1.3 HMI SLDs and Bay Details Screens........................................................................4-2

    4.1.4 HMI Alarms and Events Processing........................................................................ 4-2

    4.1.5 HMI Trending Display.............................................................................................4-3

    4.1.6 HMI Reports Function ............................................................................................. 4-3

    4.2  HMI Server Function Tests....................................................................................... 4-3 

    4.2.1 HMI Workstation Memory and Disk Utilization.....................................................4-3

    4.2.2 HMI Server Redundancy Checks.............................................................................4-4

    Chapter 5  Substation Controller/Gateway Function Tests.................................................. 5-5 

    5.1  Gateway IEC 60870-5-101 Data Retrieval...............................................................5-5 

    5.1.1 Master Station Digital data Retrieval.......................................................................5-5

    5.1.2 Master Analog data Retrieval ..................................................................................5-5

    Chapter 6  Engineering Workstation (EWS) Tests............................................................... 6-1 

    6.1  Setting and Configuration of BCUs..........................................................................6-1 

    6.2  Setting of Protection Relays ......................................................................................6-1 

    6.2.1 Setting of UR Relays ............................................................................................... 6-1

    6.2.2 Setting of Siemens 7SA522 Relays ......................................................................... 6-1

    Chapter 7  Remote Workstation (RWS) Tests ....................................................................... 7-1 7.1  HMI 7-1 

  • 8/17/2019 SAT Procedure Rev0

    5/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    v  

    MODIFICATION RECORD

    VERSION REV. DATE INITIALS COMMENT

    1 0 16-May-2008 MaheshSathe

    Created.

  • 8/17/2019 SAT Procedure Rev0

    6/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    vi  

    About This Document

    Purpose of this DocumentThis document defines the scope and procedure for the Site Acceptance Tests (SAT).

    All the tests shall be carried out based on this document. The test results shall be recorded on

    SAT Check List. (Refer P3405_SAT Checklist_Rev0)

  • 8/17/2019 SAT Procedure Rev0

    7/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    vii  

    Definition of TermsAI  Analog Input

    ASE  Applied Systems Engineering Test Kit Manufacturer

    BCU  Bay Controller Unit

    BPU  Bay Protection Unit

    DBX  Data Base Terminal

    DI  Digital Input

    DO  Digital Output

    COS  Change Of State

    EWS  Engineering Work Station

    FOC  Fiber Optic Cable

    GDP  Graphic Display PanelHMI  Human-Machine Interface

    IEC  International Electrotechnical Commission

    IED  Intelligent Electronic Device

    IRCON  short name for IRCON International Limited, Ministry of Railways

    LAN  Local Area Network

    NMS  Network Management System

    OWS  Operator Work Station

    Powergrid short name for Power Grid Corporation of India Limited

    p.u.  Power UnitsSAS  Substation Automation System

    SAT  Site Acceptance Test

    SIT Site Inspection and Test

    SNMP  Simple Network Management Protocol

    SNTP  Simple Network Time Protocol

    SOE  Sequence Of Events

  • 8/17/2019 SAT Procedure Rev0

    8/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    viii  

    This page intentionally left blank. 

  • 8/17/2019 SAT Procedure Rev0

    9/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    1-1 

    Chapter 1 SAT Requirements

    1.1 Scope of TestsThe Site Acceptance Tests (SAT) will verify that the Substation Automation System (SAS)

    functions are per the approved design.It is not the scope of this SAT document to test the Protection portion of the substation.

    The SAT tests have been divided into relevant sections in order to perform the tests

    systematically. Upon successful verification of the tests in each section, pertinent forms and

    test results shall be completed and signed for acceptance by the customer or its

    representative.

    After the SAT has been successfully verified, the System Acceptance document will be

    signed by representatives from Powergrid, IRCON and GE.

    1.2 Hardware EnvironmentThe SAS hardware equipment consist of:

    Bay Control Units in respective Bay Panels in the Kiosks.

    Protection Relays in the Protection Panels.

    HMI/Operator Workstation system consisting of Redundant Servers.

    Engineering Workstation.

    Time Synchronization Equipment consisting of a GPS Receiver Unit, Time Display

    Unit and IRIG-B/PPS Distribution Unit.

    Substation Controller/Gateway Subsystem.

    LAN Switch Equipment distributed in the Bay Panels/Kiosk.

    1.3 Software EnvironmentThe following Firmware and Software applications are used in the system:

    F650 Firmware Version 3.70 with IEC 61850 (Server) capability.

    F600 Substation Controller, with IEC 61850 (Client) capability.

    D200 Gateway Firmware with support for IEC 60870-5-101.

    UR Protection Relays Firmware Version 5.2, with IEC 61850 (Server) capability.

    Siemens 7SA522 Firmware Version 4.6, with IEC 61850 (Server) capability.

    Siemens DIGSI 4.7TM

     shall be used in the configuration of Siemens IED.

    HMI using Factory Link 7.5 Platform with IEC 61850 (Client) capability.

    The Configuration files and applications are archived in the Engineering Workstation.

  • 8/17/2019 SAT Procedure Rev0

    10/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    1-2  

    1.4 System Availability TestsThe 1000 hours system availability test will be covered in another document.

    1.5 Test EquipmentTo conduct the test procedures outlined in this document, the following equipments are

    required to be arranged by M/S IRCON and supplied at site.

    - Digital Multimeter.

    - 3 Phase Current and Voltage Injection kit - if the bays are not commissioned.

    - Protocol Analyzer. (Optional item)

    1.6 Test WitnessIRCON/Powergrid shall provide a Representative to witness and sign-off this SAT.

  • 8/17/2019 SAT Procedure Rev0

    11/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    2-3  

    Chapter 2 Communications Equipmentand Time Synchronization Equipment

    Tests

    2.1 LAN Communications Functional CheckPurpose

    1. To verify that LAN Switch Backbone redundancy is functional and running.

    2. To verify that Ethernet LAN communications in the Substation Automation System

    are functional and running.

    Set up/Program

    1. In the HMI, navigate to “Communication Network Architecture”.

    2. Setup multiple Ping screens in the EWS to different devices in the system.

    Procedure

    LAN SWITCH BACKBONE - REDUNDANCY CHECK.

    [ ] 1 Select LAN Switch SW-4A. On this LAN Switch, disconnect the LAN cable

    connected to SW-01A. (i.e. Port 14 on SW-1A)

    [ ] 2 Verify in the Ping screens and the HMI Communications Summary Screen

    that there is no communication failure of the devices in the system.

    [ ] 3 On LAN Switch SW-1A, disconnect the LAN cable connected to SW-02A(i.e. Port 17 on SW-1A).

    [ ] 4 Repeat step 2.

    [ ] 5 Restore LAN cables on SW-1A.

    [ ] 6 Select other Backbone switches and the network should remain undisturbed

    for any 2 failures in the communication network.

    [ ] 7 These link failures should be indicated in the Alarm List. Verify the same at

    every step of the test.

  • 8/17/2019 SAT Procedure Rev0

    12/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    2-4  

    2.2 Network Management Software (NMS) CheckPurpose

    1. To verify that NMS software is functional and running

    Set up/Program2. OWS-1, OWS-2 are running under normal conditions.

    Procedure

    NMS SOFTWARE.

    [ ] 1 Start the NMS Viewer (iSNMP DataViewer)

    [ ] 2 Verify that the LAN Port status and the Network Analyst Data is valid.

    [ ] 3 This data is represented in the graphical form in the HMI.

    2.3 IEC 60870-5-101 Serial Communication Check

    2.3.1 Gateway Communications to PLCC Modem

    Purpose

    To verify Gateway communications to PLCC Modem.

    Setup

    1. Using the EWS, connect to D200 Gateway.

    2. Ensure the communications cable to gateway to NSK5 modem is connected to

    the correct ports of the NSK5 modem.

    Procedure

    [ ] 1 On the Gateway Wesmaint screen, go to 68k Monitor.

    [ ] 2 In 68k Monitor, bring up the serial analyzer function by typing at the prompt

    “sa com 1”.

    [ ] 3 Observe that IEC 101 transmit packets are captured in the screen.

    [ ] 4 This will test communications up to the output of the NSK5 modem.

    2.3.2 IEC 60870-5-101 Serial Communications Verification

    Purpose

    To verify that the Gateway IEC 60870-5-101 communications to PLCC modem are

    functional.

    Notes:

    a) PLCC communication equipment is supplied by others. IEC 60870-5-101

    communications shall be tested up to modem serial port.

    b) To test IEC 60870-5-101 communications to RSCC, coordination is required.

  • 8/17/2019 SAT Procedure Rev0

    13/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    2-5  

    Set up/Program

    1. If the LDC communication is up and running, the data can be verified with the

    LDC. In absence of this connection, use an ASE Test Set to simulate IEC 60870-

    5-101 Master Station polling at the cable connection to PLCC modem.

    Procedure[ ] 1 Verify that communication is established with the ASE test set.

    [ ] 2 Verify that the ASE test set is sending request on the primary channel and that

    the SAS Gateway is responding on both the primary and the secondary

    channels.

    [ ] 3 Disconnect the ASE test set from the primary channel and connect it to the

    secondary channel; verify that the SAS Gateway will respond on both

    channels to requests received on the Secondary channel

    2.4 Time Synchronization Tests

    2.4.1 Time Synchronization Equipment Functional Check

    Purpose

    To verify that the following components of the Time Synchronization Equipment are

    functional and receiving satellite time updates:

    1. GPS Receiver

    2. External Time Display Unit

    Procedure[ ] 1 Disconnect the GPS Receiver Antenna. Set the GPS Receiver to send LocalTime. Change the value of this local time to 00:00:00.

    [ ] 2 Verify that the External Time Display Unit displays this local time. This

    confirms that the IRIG-B signal from the GPS unit to the Time Display Unit is

    functional.

    [ ] 3 Verify that the IEDs, Operator Workstations and Substation Gateway times

    match this local time. This confirms that the SNTP packets are broadcasted by

    the GPS receiver and received by the end devices.

    [ ] 4 Verify that GPS Receiver Out-of-Lock Alarm is received in the OWS.

    [ ] 5 Restore the GPS Receiver Antenna connection. Verify that the GPS Receiveris locked up to at least 3 satellites. Verify that the GPS is updated to satellite

    time.

    [ ] 6 Verify that the IEDs, Operator Workstations and Substation Gateway times

    match this satellite time update. This confirms that the time updates are

    broadcasted by the GPS receiver and received by the end devices.

    [ ] 7 Confirm that the External Time Display Unit is also updated to the new time.

  • 8/17/2019 SAT Procedure Rev0

    14/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    2-6  

    2.4.2 System Time Synchronization Check

    Purpose

    To verify that the GPS System time is received by all SAS devices and working

    according to the time synchronization requirements of IEC 61850.

    Procedure

    SAS IED TIME SYNCHRONIZATION

    [ ] 1 Change the time on one Bay control unit (BCU) by a few minutes.

    [ ] 2 The device will get synchronized over SNTP and the time will automatically

    adjust to the correct time

    [ ] 3 Repeat Step 3 for a few sample BCU’s.

    HMI EQUIPMENT

    [ ] 4 Set the Primary or the secondary server to an incorrect time.

    [ ] 5 The machine will automatically synchronize over SNTP with the GPS clock.

    [ ] 6 Repeat the procedure on the Engineering workstation.

  • 8/17/2019 SAT Procedure Rev0

    15/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    3-1 

    Chapter 3 SAS Operational Tests

    3.1 System Data Retrieval

    3.1.1 Digital Inputs Retrieval

    Purpose

    To verify that:

    1. The change of state and SOEs of Digital Input points are updated in the BCU GDP

    and the Substation HMI Operator Workstations.

    2. That selected SOEs according to the IEC 60870-5-101 mapping table are updated in

    the Master Station.

    Setup

    1. On the GDP of the BCU under test, go to the ‘Digital Inputs’ display screen.

    2. On the Operator Workstation 1 (OWS-1), go to the Point Detail Screen

    3. On the Operator Workstation 2 (OWS-2), go to the Alarm Screen.

    Procedure

    [ ] 1 Select a BCU to test.

    [ ] 2 From the field, simulate the Digital Input points on the BCU under test by

    changing their states from ‘OFF” to “ON” (single points) or from “OPEN” to

    “CLOSED” (double points).[ ] 3 Verify that the change of state in the BCU GDP.

    [ ] 4 Verify the same in both the servers.

    [ ] 5 For points configured with alarm, verify that alarms are displayed in the

    Alarm Screen with correct time stamps.

    [ ] 6 Repeat steps 1 to 5 for sample Digital Input points on the BCU.

  • 8/17/2019 SAT Procedure Rev0

    16/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    3-2  

    3.1.2 Digital Outputs

    Purpose

    To verify that digital output operations are successfully executed.

    Setup1. On the GDP of the BCU under test, go to the single line display.

    2. On the Operator Workstation 1 (OWS-1), go to the bay detail under test.

    3. On the Operator Workstation 2 (OWS-2), go to the Alarm/Event Screen.

    Procedure

    [ ] 1 From the Operator Work Station, initiate digital output requests to the BCU

    under test.

    [ ] 2 Verify that the corresponding outputs are activated.

    3.1.3 Analog Inputs

    Purpose

    To verify that the Analog Input points are updated in the BCU GDP, the Operator

    Workstations.

    Setup

    1. Select Bay under normal operations

    2. Go to the BCU GDP Display screen.

    3. Go to the bay detail screen on the Operator Workstations.

    Procedure

    AC ANALOG INPUTS

    [ ] 1 Verify that the correct readings are presented in the BCU GDP display screens

    and the HMI Point Detail Screens for the injected voltage and current values.

    [ ] 2 Confirm that the corresponding readings are updated.

    3.DC ANALOG INPUTS

    Note that only the Transformer and Reactor Bays have BCUs to monitor DC

    Analogs.

    [ ] 1 Verify that the correct readings and accuracy are presented in the BCU GDPs

    and the HMI Point Detail Screens for the s4-20mA transducer outputs.

  • 8/17/2019 SAT Procedure Rev0

    17/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    3-3  

    3.2 Software Interlock LogicPurpose

    To verify that software interlock logic for CBs and Isolators are operational based on

    actual field conditions.

    If all interlock conditions cannot be set during SAT, the interlock inputs (auxiliary

    contacts) shall be simulated in the field.

    Procedure

    [ ] 1 Select a bay to test.

    [ ] 2 Refer to protection schematic drawings. For each interlock condition, attempt

    to operate controls related to the interlock logic being tested. Verify that the

    interlock is successful.

    3.3 Synchronizing Tests

    3.3.1 Check Synchronization

    Purpose

    1. To verify that Incoming and Running (Reference) voltages are within the

    synchronizing range before the circuit breaker can close. The circuit breaker will not

    close if any of the limiting parameters is not within the check synchronizing range.

    2. To verify that the running voltage reference is properly selected (voltage selection)

    depending on isolator switch conditions.

    Procedure

    [ ] 1 Select a BCU and corresponding Circuit Breaker to test.

    [ ] 2 Verify the voltage selection based on the isolator status.

    [ ] 3 Verify the voltage reading in the Enervista F650 setup software for the

    synchrocheck function.

    [ ] 4 Initiate a Close request on this Circuit Breaker.

    [ ] 5 Verify that the Circuit Breaker closes only when configured settings are met.

  • 8/17/2019 SAT Procedure Rev0

    18/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    3-4  

    3.4 220kV Auto-Sequencing

    3.4.1 220kV Auto-Sequencing

    Purpose

    To verify that the 220kV Auto-Sequencing logic functions correctly.

    Setup

    Ensure that the HMI Servers are running.

    Procedure

    [ ] 1 Select a Feeder to test.

    [ ] 2 Turn ON the Auto-sequencing controls.

    [ ] 3 Click “Transfer to TBC” or the “Transfer Bus” sequence.

    [ ] 4 Verify the “Transfer Logic Status” as well as the actual isolators beingcontrolled.

    [ ] 5 The sequence can be aborted at any given time by using the abort – “Set”

    button.

    [ ] 6 Repeat above tests with negative conditions – e.g. another Feeder is already on

    Transfer Bus. Verify that the appropriate alarms are indicated and operation is

    not permitted.

  • 8/17/2019 SAT Procedure Rev0

    19/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    4-1 

    Chapter 4 HMI/Server Tests

    4.1 HMI Functions Test

    4.1.1 Shutdown and Startup of Servers

    Purpose

    To verify that the HMI Redundancy is operational during shutdown of the active server.

    Setup

    1. Ensure that the HMI Servers are running.

    Procedure

    [ ] 1 With both Servers running, and the HMI client is running under normal mode.

    [ ] 2 Shutdown the Active Server. (say OWS-1)

    [ ] 3 Observe that the Standby server takes over and becomes the “Stand-alone”

    HMI server.

    [ ] 4 Restore the machines (Startup OWS-1). Observe that there is no interruption

    to the Bay level devices.

    [ ] 5 Observe that Viewer clients attach to OWS-1 and remote devices are still

    normal and communicating with OWS-2.

    Observe that the system is back to normal.

    4.1.2 HMI Security and Access Test

    Purpose

    To verify that the OWS/HMI system has Security Classes; that these are enabled and

    configured properly.

    Setup

    1. Ensure that the HMI Servers are running.

    Procedure

    [ ] 1 At Primary Server, Login as the “observer” user.[ ] 2 Verify that this user class has proper access level as per HMI Security

  • 8/17/2019 SAT Procedure Rev0

    20/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    4-2  

    Classification.

    [ ] 3 Go to any bay detail screen. Verify if access to tool bar and object controls are

    according to the allowed in the access level logged in.

    [ ] 4 Repeat steps 1 to 4 for the other HMI Usernames (Operator and

    Administrator).

    [ ] 5 Repeat steps 1 to 4 on Secondary Server.

    4.1.3 HMI SLDs and Bay Details Screens

    Purpose

    To verify that the Single Line Diagram and Bay Detail Screens in the OWS/HMI system

    are configured properly and are in correct operating condition.

    Setup

    1. Ensure that the HMI Servers are running.

    2. Log in as an “Operator”.

    Procedure

    [ ] 1 Verify the layout of each One-Line screen.

    [ ] 2 Verify the device number and device description for each device.

    [ ] 3 Verify all displayed analog and digital values in One-Line screens.

    [ ] 4 Click on each device object and confirm that the correct pop up screen or

    bay/device detail screen is displayed.

    [ ] 5 Repeat steps 1 to 4 for each One-Line screen’s.[ ] 6 Repeat steps 1 to 5 for each Workstation.

    4.1.4 HMI Alarms and Events Processing

    Purpose

    To verify that the Alarm and Event Points are configured properly and are in correct

    operating condition.

    Setup

    1. Ensure that the HMI Servers are running.

    2. Display the Alarm Logger Screen.

    Procedure

    [ ] 1 Select a Digital Input point from one of the BCU’s configured as an Alarm.

    [ ] 2 Change the state of the selected point.

    [ ] 3 Confirm that an Alarm is displayed in the Active Alarm Logger screen with

    proper description and Time Stamp.

    [ ] 4 Acknowledge this alarm.

    [ ] 5 Locate the Event History screen and verify that this alarm is displayed and thatit is acknowledged.

  • 8/17/2019 SAT Procedure Rev0

    21/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    4-3  

    [ ] 6 Repeat steps 1 to 5 for several Digital Input points that are configured as

    Alarms (Events).

    4.1.5 HMI Trending Display

    Purpose

    To verify that the trending in the OWS/HMI system are configured properly and are in

    correct operating condition.

    Setup

    1. Ensure that the HMI Servers are running.

    2. Go to the trending screen.

    Procedure

    [ ] 1 Select Pen Editor Form.

    [ ] 2 Verify that a Pen Select screen pops up.[ ] 3 Assign a point to the selected pen.

    [ ] 4 Repeat step 3 for other pens.

    4.1.6 HMI Reports Function

    Purpose

    To verify that the Reports Function in the OWS/HMI system are configured properly and

    are in correct operating condition.

    Setup

    Ensure that the HMI Servers are running.

    Procedure

    HISTORICAL REPORTS

    [ ] 5 Go to the Statistical Report Screen.

    [ ] 6 Select an analog value to print. Select the range of date by selecting the start

    and stop dates.

    [ ] 7 Save the report as a CSV file.

    [ ] 8 Print CSV file. Confirm that the file is printed.

    DAILYREPORTS

    [ ] 9 Verify that the daily reports are prepared in the “Reports” folder.

    [ ] 10 Verify the validity of the data in the report.

    4.2 HMI Server Function Tests

    4.2.1 HMI Workstation Memory and Disk Utilization

    Purpose

  • 8/17/2019 SAT Procedure Rev0

    22/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    4-4  

    To verify that the Operator Workstation/HMI Computers have Memory and Disk usage and

    allocation that are within specification requirements.

    Setup

    1. Ensure that the HMI Servers are running.

    Procedure

    [ ] 1 On the Primary HMI (OWS-1), open the WindowsTM

    Operating System Task

    Manager. Note that the OWS Computers have server grade operating system.

    [ ] 2 Select the ‘Performance’ tab, take note of the ‘Total” and ‘Available’

    “Physical Memory information.

    [ ] 3 Calculate the percentage of available memory. Close the Task Manager.

    [ ] 4 Open Windows Explorer. Check the properties of the Hard Drive volume.

    [ ] 5 Calculate the current usage.

    [ ] 6 Record the information.

    [ ] 7 Repeat for the rest of the workstations.

    4.2.2 HMI Server Redundancy Checks

    Purpose

    To verify that the HMI Redundancy is operational during simulated loss of Level 2

    communications.

    To verify that the HMI Workstations support redundant LAN communications.

    Setup1. Ensure that the HMI Servers are running.

    2. The OWS-1 (Primary Server) is the active server.

    3. The OWS-2 (Secondary Server) is in Standby Mode.

    Procedure

    [ ] 1 Verify that the devices are online with the HMI.

    [ ] 2 On OWS-1 (Primary Server), disconnect LAN-A cable. Observe that Viewer

    clients and remote devices are still normal and communicating with OWS-1.

    [ ] 3 On OWS-1, now disconnect LAN-B cable. Observe that all the devices go

    Offline.

    [ ] 4 Initiate a switchover to make OWS-2 (Secondary Server) the active HMI

    Server.

    [ ] 5 Restore the LAN connections and system is back to normal operation.

    [ ] 6

  • 8/17/2019 SAT Procedure Rev0

    23/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    5-5  

    Chapter 5 Substation

    Controller/Gateway Function Tests

    5.1 Gateway IEC 60870-5-101 Data Retrieval Note: This section of tests will need coordination with the Master Station

    5.1.1 Master Station Digital data Retrieval

    Purpose

    To verify that the Substation Gateway correctly responds to polls for Digital Input andSOE data by the Master Station.

    Procedure

    [ ] 1 Select a Bay to test.

    [ ] 2 Verify the Switchgear Status with the Master Station.

    [ ] 3 Verify that SOE and COS data are received and updated in the Master Station.

    5.1.2 Master Analog data Retrieval

    PurposeTo verify that the Substation Gateway correctly responds to polls for Analog data

    from the Master Station.

    Procedure

    [ ] 1 Select a Bay to test.

    [ ] 2 Verify the analog values with the Master Station.

  • 8/17/2019 SAT Procedure Rev0

    24/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    5-6  

    This page intentionally left blank. 

  • 8/17/2019 SAT Procedure Rev0

    25/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    6-1 

    Chapter 6 Engineering Workstation(EWS) Tests

    6.1 Setting and Configuration of BCUsPurpose

    To verify that the BCUs can be configured online or offline using Enervista Software.

    Setup

    Ensure that the EWS is running.

    Procedure

    [ ] 3 Run the Enervista F650 Setup application in the EWS.

    [ ] 4 Change some parameters on this BCU. Store the configuration. Observe that

    the parameter changed is now active.

    [ ] 5 Download the original configuration file for this BCU. Observe that the

    parameters changed in the previous step are now changed to the original

    values.

    6.2 Setting of Protection Relays

    6.2.1 Setting of UR Relays

    Verify the software functionality in the EWS

    6.2.2 Setting of Siemens 7SA522 Relays

    Verify the software functionality in the EWS.

  • 8/17/2019 SAT Procedure Rev0

    26/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    P3405_SAT_Procedure_Rev0.doc

    6-2  

    This page intentionally left blank. 

  • 8/17/2019 SAT Procedure Rev0

    27/27

    400/220kV Ludhiana/Gwalior SubstationSubstation Automation System - Site Acceptance Test Procedure  

    GE T&D

    Chapter 7 Remote Workstation (RWS)Tests

    7.1 HMIPurpose

    To verify that the Remote HMI function.

    Setup

    The Remote HMI computer is on the Local Area Network in the control Room.

    Procedure

    [ ] 1 Run the HMI Client.

    [ ] 2 Log-in the HMI using different user name like “Operator”, “Admin” to verify

    the access rights

    [ ] 3 Navigate through the various screens in the HMI along with the

    Alarms/Events screen.

    [ ] 4 Initiate control commands to verify the functionality.