Alamance-Burlington School System Administrative Offices
1712 Vaughn Road Burlington NC 27217
Request for Proposal
Security Vestibules Upfits
April 30, 2020
IMPORTANT NOTICE TO ALL BIDDERS / PROPOSERS: Alamance‐Burlington School System reserves the right to disqualify incomplete proposals, waive minor defects, as it deems applicable, in the written proposals, to request additional information from any respondent, change or modify the scope of the project at any time, without any penalty, negotiate terms with one or more of the respondents, reject any or all proposals, without a penalty, and take any steps necessary to act in ABSS’s best interest. Bids / proposals will not be considered for award if received by Alamance‐Burlington School System after the official closing date and time.
-2-
INVITATION TO BID
Alamance‐Burlington School System Security Vestibules upfits for Three schools
The Alamance‐Burlington School System is requesting sealed bids for security vestibule upfits at three of our schools. Qualified contractors are invited to bid this project as outlined in this RFP. Sealed bids will be accepted on or before April 30, 2020 until 2:00 PM. Electronic bids will not be accepted. All terms must remain effective until end of contract.
Contractors should submit an original and two (2) additional copies of their complete proposal and (completed Bid Form) by 2:00 PM on April 30, 2020 in a sealed envelope or package clearly marked: “Highland Elementary upfit” “Hillcrest Elementary upfit” “Smith Elementary upfit” Bids should be sent to: Alamance Burlington School System, 1712 Vaughn Road, Burlington, NC 27217. (Att. Operation Dept.) Bids will be opened at 2:30 pm April 30, 2020 in the Operations Department Conference room.
All questions and concerns should be sent via email to: [email protected]. Responses and/or questions should be sent to this email with “Security Vestibule Upfit” as the subject line. All responses will be sent to all vendors that are included in the email list. If you choose to be part of the email response list please email the above email address with “Security Vestibule Upfit” in the subject line.
The winning bid will be chosen on its merit consisting of cost, bidder’s reputation, references, and the ability to meet the District’s time schedule, service after‐the‐fact and the best all‐ around interest to the Alamance‐Burlington School System.
The Alamance‐Burlington School System reserves the right to reject any or all bids and to accept the bid which appears to be in the best interest of the district, even if the bid is not the lowest. The Board reserves the right to waive any formalities in, or reject, any or all bids or any part of any bid. Any bid may be withdrawn prior to the scheduled time for the opening of bids. Any bid received after the time and date specified shall not be considered. The Board also reserves the right to negotiate with a bidder when all bids exceed the budgeted appropriation.
Outline of Project Contents: Section 1: Lunsford Act/Criminal Background Checks are strictly enforced.
Section 2: Description of Corporate Structure
-3-
Section 3: Experience, Background, and three (3) References
Section 4: Litigation and Claims History
Section 5: Based on the information provided prepare a schedule of approximate times.
Section 6: Official Statements by Contractor
Pre‐Bid site inspection: Alamance‐Burlington School System will have a representative to be present at each site to allow interested bidders to evaluate each site before bidding, this site visit is a non ‐ mandatory but is highly recommended. The date of the site visit will be April 16, 2020 starting 10:00am at Highland Elementary School located at 3720 Bonnar Bridge Parkway, Burlington NC 27215 and proceed from there to the next (2) sites Smith Elementary and Hillcrest Elementary School. The meeting will address all project specific questions, bidding procedures and bid forms.
Scope of Work: See Drawings for each school attached Beginning Date: Work shall began no sooner than 6‐15‐2020 and be substantially completed by 8‐14‐2020
-4-
Bidders must be able to meet the minimum insurance requirements listed below:
1. Worker’s Compensation Part One: Worker’s Compensation
Bodily Injury by Accident $100,000 each accident Bodily Injury by Disease $500,000 policy limit Bodily Injury by Disease $100,000 each employee
Statutory Part Two: Employers Liability
2. General Liability $1,000,000 per occurrence $2,000,000 policy aggregate
3. Auto Liability Combined Single Limit Combined Single Limit $1,000,000 per accident Uninsured Motorists $1,000,000 per accident
-5-
EXHIBIT A
Alamance Burlington School System
Bid Form
School Name: __________________________________________
Company Name:
Address:
Telephone Number:
Fax Number:
$ This amount reflects the total cost to perform the scope of work outlined in the RFP for Security Vestibule Upfit
Signature:
Printed Name:
Date:
This bid must be signed by a person authorized to legally bind the bidder.
ABBREVIATIONSSCALE: NTS
@: At (the rate of)&: And1R1S: One Rod One Shelf2R2S: Two Rods Two Shelves5S: Five Shelves
AB: Anchor BoltABV: AboveAC: Air Conditioning, Alternating Current, AcousticalACC: AccessACI: American Concrete InstituteACT: Acoustical Tile; ActualADA: Americans with Disabilities Act of 1992ADAAG: Americans with Disabilities Act Architectural GuidelinesADD: Addendum; AdditionADDL: AdditionalADJ: Adjust, Adjustable, AdjacentAFF: Above Finished FloorAGGR: AggregateAIA: American Institute of ArchitectsALUM: AluminumAMT: AmountAPPROX: ApproximateAPRVD: ApprovedARCH: Architect, ArchitecturalASB: AsbestosASSOC: Association; AssociateASTM: American Society for Testing and MaterialsAUTO: AutomaticAVG: Average
BDRM: BedroomBETW: BetweenBG: Bag (e.g., of cement)BLDG: BuildingBLKG: BlockingBLT-IN: Built-InBLW: BelowBOT: BottomBRK: BrickBTU: British Thermal UnitsBTUH: British Thermal Units per Hour
CAB: CabinetCAP: CapacityCAR: CarpetCARP: CarpenterCAT: CatalogCAV: CavityCB: Catch Basin, Concrete Block,Cast Brass, Coal BinCBL: Concrete BlockCBX: Cast Box StrikeCC: Cubic CentimeterCCT: CircuitCCW: Counter ClockwiseCCTV: Closed Circuit TVCD: Cold Drawn, CadmiumCDS: Cold Drawn SteelCEL: CellarCEM: CementCEM AB: Cement Asbestos BoardCem P: Cement Water PaintCER: CeramicCF: Cubic FeetCFL: CounterflashingCFM: Cubic Feet per MinuteCFS: Cubic Feet per SecondCFT: Cubic FootCG: Corner GuardCH: Coat HookCHB: Chalk BoardCHR: Chilled Water ReturnCHAM: ChamferCHAN: ChannelCHBD: ChalkboardCHS: Chilled Water SupplyC.I.: Cast IronCI: Cast IronCIN BL: Cinder BlockCIP: Cast Iron Pipe, Cast-in-PlaceCIR: Circle, Circular, CircuitCIRC: CircumferenceCISP: Cast Iron Soil/sewer PipeCITG: Clear Insulating Tempered GlassCJ: Control JointCJF: Cork Joint FillerCK: CaulkingCKT: CircuitCL: Centerline, Clearance, Closing, Closure, Class, ClosetCLG: CeilingCLKG: CaulkingCLH: Clothes Line HookCLL: Contract Limit LineCLO: ClosetCLP: ClampCLR: ClearCMU: Concrete Masonry UnitCMUP: Concrete Masonry Unit PaintedCNTR: Center, CounterC.O.: Cased OpeningCO: Company, Cleanout, Cased Opening, Cut OutCOL: ColumnCON: ConstructionCONC: ConcreteCONST: ConstructionCONT: Continuous, Continue, ControlCPT: CarpetCRS: CourseCT: Ceramic Tile, Cork Tile,CTR: Center, Counter
DBL: DoubleDEG: DegreeDEMO: DemolitionDH: Double HungDIAG: DiagonalDIA: DiameterDIM: DimensionDISP: DisposalDIV: DivisionDS: DownspoutDTL: DetailDWG: DrawingDS: Downspout
EA: EachEIFS: Exterior Insulation and Finish SystemEJ: Expansion JointEL: Elevation, ElevatorELEC: ElectricalELEV: Elevator, ElevationEMER: EmergencyENTR: EntranceEPDM: Ethylene Propylene Diene MonomerEQ: EqualEQUIP: EquipmentEST: EstimateEXIST: Existing
FABR: FabricateFACP: Fire Alarm Control PanelFAR: Floor Area RatioFD: Floor drainFDC: Fire Department ConnectionFE: Fire ExtinguisherFEC: Fire Extinguisher CabinetFFE: Finished Floor ElevationFF&E: Fixtures, Furnishings & EquipmentFIN: Finish, finishedFIXT: FixtureFLR: FloorFOC: Face of ConcreteFOF: Face of FinishFOS: Face of StudsFPL: FireplaceFT: Foot, Feet, Fully TemperedFTG: Footing, FittingFURN: Furnish, FurnitureFURR: Furring
GA: Gauge, GageGAL: GallonGALV: GalvanizedGB: Grab Bar, Glass Block, Gypsum BoardGC: General ContractorGCB: Gypsum Ceiling BoardGPM: Gallons Per MinuteGVL: GravelGWB: Gypsum Wall Board
HB: Hose BibHBD: HardboardHC: HandicappedHDR: HeaderHDW: HardwareHDWD: HardwoodHGT: HeightHORIZ: HorizontalHR: HourHTR: HeaterHTWR: Hot Water HeaterHVAC: Heating, Ventilating & ACHW: Hot Water
ID: Inside DiameterIN: InchINCAND: IncandescentINFO: InformationINSUL: InsulationINT: Interior, InternalINV: Invert
J-BOX: Junction BoxJAN: JanitorJST: JoistJT: Joint
KIT: KitchenKO: KnockoutKS: Kitchen Sink
L: Linen ClosetLAD: LadderLAM: Laminate, LaminatedLAV: LavatoryLB: Pound (weight)LH: Left HandLIBR: LibraryLIN: LinearLINO: LinoleumLL: Live LoadLNTL: LintelLR: Living RoomLTL: LintelLT WT: LightweightLVL: Laminated Veneer LumberLVR: Louver
MAINT: MaintenanceMAX: MaximumMECH: MechanicalMED: MediumMED CAB: Medicine CabinetMEMB: MembraneMEZZ: MezzanineMIN: MinimumMIR: MirrorMISC: MiscellaneousMTD: MountedMTL: Material, Metal
NEUT: NeutralNIC: Not In ContractNOM: NominalNTS: Not To Scale
OC: On CenterOD: Outside DiameterOH: OverheadOHD: Overhead DoorOPNG: OpeningOPP: OppositeOPP H: Opposite Hand
P. LAM: Plastic LaminatePBD: Particle BoardPLUMB: PlumbingPNEU: PneumaticPNL: PanelPRTN: PartitionPT: Pressure TreatedPTD: Painted, Paper Towel DispenserPVC: Polyvinyl Chloride
QT: Quarry Tile, QuartQTR: QuarterQTY: Quantity
RCP: Reflected Ceiling PlanRD: Roof DrainREBAR: Reinforcing BarREFL: Reflected, ReflectorREF: RefrigeratorREQD: RequiredREV: Reverse, Revise, RevisionRH: Right HandRMV: RemoveRO: Rough Opening
SAN: SanitarySCHED: ScheduleSCWD: Solid Core WoodSEAL: SealantSECT: SectionSF: Square FootSHT: SheetSIM: SimilarSPEC: Specification, SpecificationsSPECS: SpecificationsSPK: SpeakerSQ: SquareSS: Stainless SteelSTC: Sound Transmission ClassSTD: StandardSTL: SteelSTO: StorageSTRUC: StructuralSYN: Synthetic
T: ThermostatT&G: Tongue & GrooveTB: Towel BarTEL: TelephoneTEMP: TemporaryTHK: Thick, ThicknessTHRU: ThroughTR: Tread, TransomTSL: Top of SlabTST: Top of SteelTV: TelevisionTW: Top of WallTYP: Typical
UC: UndercutUL: Underwriters' LaboratoriesUNFIN: UnfinishedUNO: Unless Noted OtherwiseUT: Utility
VB: Vapor BarrierVCT: Vinyl Composition TileVENT: Ventilate, VentilatorVERT: VerticalVEST: VestibuleVIF: Verify In the FieldVIN: VinylVOL: VolumeVT: Vinyl Tile
WAINS: WainscotWD: WoodWH: Water HeaterWWF: Welded Wire Fabric
HIGHLAND ELEMENTARY3720 BONNAR BRIDGE RDBURLINGTON, NC, 27215
Architect: PLAGEMAN ARCHITECTURE408 S Spring St. - Burlington - North Carolina - 27215
phone: 336-226-3933 - Email: [email protected] - John Plageman
PERMIT SET
04/06/2020
1CS1
COVER SHEET,ABBREVIATIONS,
INDEX OF DRAWING
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2013
REVISIONS
HIG
HLA
ND
E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
372
0 B
ON
NA
R B
RID
GE
R
D, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
INDEX OF DRAWINGSSCALE: NTS
material symbols
CONCRETE MASONRY UNIT
WASHED STONE
CONCRETE
EARTH
ROUGH WOOD - BLOCKING
FINISHED WOOD
STONE
STEEL (LARGE SCALE) BATT INSULATION
RIGID FOAM INSULATION
PLYWOOD
BRICK
GLASS
GYPSUM BOARD
drawing symbolsW2ELEVATION AND DETAIL NUMBER
INTERIOR ELEVATION AND DETAIL LETTER
COLUMN LINE DESIGNATION
DENOTES MATERIAL/BUILDING FINISHES, REFER TO A8.0
DENOTES WALL TYPE DESIGNATION
DENOTES FINISHED CEILING HEIGHT AFF
DOOR NUMBER DESIGNATION
W1 WINDOW/GLASS NUMBER DESIGNATION
ABC TYPE FIRE EXTINGUISHER
A INTERIOR ELEVATION TAG
DENOTES ELEVATION HEIGHT
DENOTES FLOORING FINISH TYPE
DENOTES WALL BASE TYPEFL-1WB-1
2
SHEET NAMESUBMISSION DATE
INDEX OF DRAWING
SHEET #PERMIT SET
ARCHITECTURAL DRAWINGSCS1 COVER SHEET, ABBREVIATIONS, INDEX OF DRAWING, GENERAL NOTES
A100 GROUND FLOOR PLAN
04/06/2020
GENERAL NOTES
1. ARCHITECT IS NOT RESPONSIBLE FOR BUILDING'S EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL BERESPONSIBLE FOR FIELD VERIFICATION AND COORDINATION OF ALL INFORMATION INCLUDED WITHIN THESEDOCUMENTS.
2. ALL CONSTRUCTION AND CONSTRUCTION PRACTICES SHALL BE IN ACCORDANCE WITH THE NORTH CAROLINA STATEBUILDING CODE ALONG WITH CITY, COUNTY AND STATE REGULATIONS.
3. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY ADDITIONAL DRAWINGS NOT CONTAINED HERE-IN, FOR THEPURPOSE OF OBTAINING PERMITS.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL DRAWINGS WITH ALL SITE INFORMATION ANDAPPLICABLE CODES.
5. GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL PLUMBING, MECHANICAL, ELECTRICAL, AND FIREPROTECTION DRAWINGS. ARCHITECT IS NOT RESPONSIBLE FOR FIELD DISCREPANCIES.
6. WHERE IT IS STATED "GC TO COORDINATE WITH (INCLUDING BUT NOT LIMITED TO OWNER, ENGINEER,MANUFACTURER)", ARCHITECT IS NOT RESPONSIBLE FOR DECISIONS OR COORDINATION.
7. IF ANY FIELD CHANGES ARE MADE DURING CONSTRUCTION AND THE ARCHITECT IS NOT INCLUDED WITHIN THEDISCUSSION, ARCHITECT IS NOT RESPONSIBLE FOR RESULTS.
8. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR JOB SAFETY. THESE DRAWINGS DO NOT CONTAIN PROVISIONS FORJOB SAFETY.
9. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE ARCHITECT IMMEDIATELY OF CONSTRUCTIONDEVIATING FROM DEPICTED OR IMPLIED INFORMATION HERE-IN.
10. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COMPARING ALL DIMENSIONS IN THE CONSTRUCTIONDOCUMENTS AND EXISTING CONDITIONS IN THE FIELD.
11. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYING AND INFORMING THE ARCHITECT OF ANYDISCREPANCIES, ERRORS, CONFLICTS, OR OMISSIONS FOUND IN THE CONSTRUCTION DOCUMENTS BEFOREPROCEEDINGS OR CONTINUING WORK IN THIS AREA.
12. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL FIELD DIMENSIONS PRIOR TO STARTING WORK, ANDPRIOR TO ORDERING EQUIPMENT AND/OR CASEWORK.
13. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING ALL SHOP DRAWINGS AND VERIFYING THAT THEY ARECORRECT.
14. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING EXHAUST FOR DRYERS, BATHROOMS, AND RANGES TOEXTERIOR WITH PROPER TERMINUS (NOT TO BE LOCATED ON STREET SIDE ELEVATION) VERIFY TERMINUS TYPE ANDLOCATION WITH OWNER PRIOR TO INSTALLATION.
15. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT ALL MATERIALS, FINISHES, AND/ OR EQUIPMENTSHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND/OR RECOMMENDATIONS.
16. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION VARIATIONS FROM THE INFORMATION CONTAINEDHERE-IN UNLESS REVIEWED AND APPROVED BY ARCHITECT.
17. DO NOT SCALE DRAWINGS, BUT RATHER INQUIRE OF ARCHITECT. REPRODUCTION OF THESE DRAWINGS IS PROHIBITEDUNLESS WRITTEN PERMISSION IS OBTAINED FROM ARCHITECT.
18. ALL FINISHES ARE TO BE SELECTED BY OWNER UNLESS NOTED OTHERWISE. ALL COLORS TO BE CHOSEN FROMMANUFACTURER STANDARD COLOR SELECTION.
19. ALL MATERIALS /EQUIPMENT SPECIFIED WITHIN THESE CONSTRUCTION DOCUMENTS SHALL BE USED FORCONSTRUCTION. SUBSTITUTIONS OF SIMILAR OR EQUAL PRODUCTS MUST BE APPROVED BY THE OWNER ANDARCHITECT.
20. GENERAL CONTRACTOR SHALL PROVIDE FIRE EXTINGUISHERS DURING CONSTRUCTION PER LOCAL FIRE MARSHALREQUIREMENTS.
21. GENERAL CONTRACTOR SHALL PROVIDE ALL BASIS AND BLOCKING REQUIRED FOR ACCESSORIES, MECHANICAL,ELECTRICAL AND ALL OTHER EQUIPMENT.
1A100
1A100
X
ACM1
B
C
D
A
D1
X'-X"
CS2 APPENDIX B 04/06/202004/06/2020
BUILDING CODE SUMMARYFOR ALL COMMERCIAL PROJECTS(EXCEPT 1 & 2 FAMILY DWELLINGS AND TOWNHOUSES)
NAME OF PROJECT:
ADDRESS:
OWNER OR AUTHORIZED AGENT: PHONE:
EMAIL: FAX:
OWNED BY: PRIVATELY CITY/COUNTY STATE
CODE ENFORCEMENT JURISDICTION: CITY COUNTY STATE
NAME OF JURISDICTION:
PROJECT SUMMARY
BUILDING DESCRIPTION:
SCOPE OF WORK:
CODE COMPLIANCE SUMMARY:
ALTERNATIVE MEANS OF COMPLIANCE REQUEST:
LEAD DESIGN PROFESSIONAL/PROJECT COORDINATOR:
DESIGNER FIRM NAME LICENSE# PHONE#
ARCHITECTURAL:
CIVIL:
ELECTRICAL:
FIRE ALARM:
PLUMBING:
MECHANICAL:
SPRINKLER-STANDPIPE:
STRUCTURAL:
PRECAST:
TRUSSES:
RETAINING WALLS >5'
OTHER:
NOTE: IF APPLICABLE, SPECIAL INSPECTIONS AND INSPECTORS TO BE LISTED ON THIS SHEET
XX
OCCUPANCY INFORMATIONPRIMARY OCCUPANCIES:
ASSEMBLY: A-1 A-2 A-3 A-4 A-5 BUSINESS EDUCATIONAL
FACTORY-INDUSTRIAL: F-1 F-2
HIGH-HAZARD: H-1 H-2 H-3 H-4 H-5
INSTITUTIONAL: I-1 I-2 I-3 I-4I3 USE CONDITION: 1 2 3 4 5
MERCANTILE RESIDENTIAL: R-1 R-2 R-3 R-4
STORAGE: S-1 S-2 HIGH-PILEDS-1 REPAIR GARAGE(406.6) S-2 PARKING GARAGE OPEN(406.3) ENCLOSED(406.4)
UTILITY AND MISCELLANEOUS
OTHER USES:ACCESSORY USES (INDICATE PERCENTAGES):
INCIDENTAL USES:
SPECIAL OCCUPANCIES: 402 403 404 405 406 407 408 409 410411 412 413 414 415 416 417 418 419420 421 422 423 424 425 426 427
X
MIXED OCCUPANCY: NO YES SEPARATION:NON-SEPARATED MIXED OCCUPANCY (508.3.2)SEPARATED MIXED OCCUPANCY (508.3.3)
ACTUAL AREA OF OCCUPANCY A + ACTUAL AREA OF OCCUPANCY B < 1 ALLOWABLE AREA OF OCCUPANCY A ALLOWABLE AREA OF OCCUPANCY B
X
ALLOWABLE AREA & HEIGHT CALCULATIONS
EXTERIOR WALL ACTUAL LENGTH OPEN LENGTH WIDTH OF PUBLIC WAY OR OPEN SPACE
NORTH
SOUTH
EAST
WEST
TOTAL P F W
INCREASE FRONTAGE %INCREASE SPRINKLERS %
FRONTAGE INCREASE FORMULA ALLOWABLE AREA FORMULAI(f) = 100(F - 0.25) W
P 30
BUILDING DATACONSTRUCTION TYPE: I-A I-B II-A II-B III-A III-B IV-HT V-A V-B
MIXED CONSTRUCTION: NO YES
SPRINKLERS: NO YES NFPA 13 NFPA 13R PARTIALLY SPRINKLERED SPECIAL SUPPRESSION
STANDPIPES: NO YES CLASS: I II III WET DRY
BUILDING HEIGHT: FEET STORY
BASEMENT: NO YES MEZZANINE: NO YES
HIGH RISE: NO YES LIFE SAFETY PLAN SHEET #
GROSS BUILDING AREA:
FLOOR EXISTING (SQ FT) NEW (SQ FT) SUB-TOTAL
BASEMENTGROUND FLOORMEZZANINE2ND FLOOR3RD FLOOR4TH FLOOR
TOTAL
AREA OF PROJECT TENANT/ALTERATION/RENOVATION:AREA OF CONSTRUCTION:
X
XX
X
X X
X
BOTH BUILDING AND TENANT MUST BE INDICATED ON CHART BELOW
STORY#
OCCUPANCY (A)BLDG AREAPER STORY(ACTUAL)
(B)TABLE 503 5
AREA
(C)% OPENSPACE
INCREASE 1
(D)%
SPRINKLERINCREASE 2
(E)ALLOWABLEFLOOR AREA
ORUNLIMITED 3
RATIO OFACTUAL TOALLOWABLE
(F)MAX. BLDG
AREA 4
SEPARATIONRATING
REQUIRED
NOTES:1. OPEN SPACE AREA INCREASES FROM SECTION 506.2 ARE COMPUTED THUS:
a. PERIMETER WHICH FRONTS A PUBLIC WAY OR OPEN SPACE HAVING 20 FEET MIN. WIDTH = ______ FT(F)b. TOTAL BUILDING PERIMETER = _________ FT (P)c. RATIO (F/P) = __________ (F/P)d. W = MINIMUM WIDTH OF PUBLIC WAY = _________ FT (W)e. PERCENT OF FRONTAGE INCREASE = ___________ (FROM FORMULA ABOVE)
2. THE SPRINKLER INCREASE PER SECTION 506.3 IS AS FOLLOWS:a. MULTISTORY BUILDING IS = 200 PERCENTb. SINGLE STORY BUILDING IS = 300 PERCENT
3. UNLIMITED AREA APPLICABLE UNDER CONDITIONS OF SECTIONS GROUP B,F,M,S,A-4 (507.1, 507.2, 507.3, 507.4, 507.7); GROUP A MOTION PICTURE (507.10); MALLS (507.11); AND H-2 AIRCRAFT PAINT HANGARS (507.8).
4. MAXIMUM BUILDING AREA = TOTAL NUMBER OF STORIES IN THE BUILDING X E BUT NOT GREATER THAN 3 X E.
5. THE MAXIMUM AREA OF PARKING GARAGES MUST COMPLY WITH 406.3.5. THE MAXIMUM AREA OF AIR TRAFFIC CONTROL TOWERS MUST COMPLY WITH 412.1.2.
ALLOWABLE HEIGHTMOST RESTRICTIVE USE
(GROUP ____ )ALLOWABLE HEIGHT
(TABLE 503)INCREASE FOR
SPRINKLERSSHOWN ON
PLANSCODE REFERENCE
TYPE OF CONSTRUCTION
BUILDING HEIGHT (FT)
BUILDING HEIGHT (STORIES)
TYPE _____________ TYPE ________ TABLE 601
TABLE 503
TABLE 503
H = _______
S = _______
H + 20 FT = ______ (FT)
S + 1 = _________
H = _______ (FT)
S = ________
FIRE PROTECTION REQUIREMENTS
BUILDINGELEMENT
FIRE SEPARATIONDISTANCE
(FEET)
RATINGREQ'D PROVIDED
(W/ _____ HR*REDUCTION)
DETAIL #&
SHEET #
DESIGN #FOR RATEDASSEMBLY
DESIGN #FOR RATED
PENETRATION
DESIGN #FOR RATED
JOINTS
BEARING WALLS EXTERIORNORTHSOUTH
EASTWEST
INTERIOR BEARING WALLSNON-BEARING WALLS EXTERIOR
NORTHSOUTH
EASTWEST
INTERIOR NON-BEARING WALLS
STRUCTURAL FRAME, INCLUDINGSUPPORTING COLUMNS, GIRDERS& TRUSSES
FLOOR CONSTRUCTION,INCLUDING SUPPORTING BEAMSAND JOISTS. LIST CONSTRUCTIONTYPE.FLOOR CEILING ASSEMBLYCOLUMNS SUPPORTING FLOORS
ROOF CONSTRUCTION, INCLUDINGSUPPORTING BEAMS & JOISTS**
ROOF CEILING ASSEMBLYCOLUMNS SUPPORTING ROOFSHAFTS - EXIT ENCLOSURESSHAFTS - OTHER (DESCRIBE)SHAFTS - OTHER (DESCRIBE)CORRIDOR SEPARATIONOCCUPANCY SEPARATION
PARTY/FIRE WALL SEPARATIONINCIDENTAL USE SEPARATION
DWELLING/SLEEPING UNITSEPARATIONSMOKE BARRIER SEPARATIONTENANT SEPARATION
* INDICATE SECTION NUMBER PERMITTING REDUCTION** INDICATE IF USING TABLE 601 NOTE C EXCEPTION
PERCENTAGE OF WALL OPENING CALCULATIONSTHIS SECTION FOR ADDITIONS, NEW AND CHANGE OF USE
ALLOWABLE OPENINGS PER TABLE 705.8
WALL LEGENDS
LIFE SAFETY SYSTEM REQUIREMENTS
LIFE SAFETY PLAN SHEET # (IF REQUIRED)
EMERGENCY LIGHTING: NO YES
EXIT SIGNS: NO YES
FIRE ALARM: NO YES
SMOKE DETECTION SYSTEMS: NO YES
PANIC HARDWARE: NO YES
XXXXX
EXIT REQUIREMENTSNUMBER AND ARRANGEMENT OF EXITS
1. CORRIDOR DEAD ENDS (SECTION 1017.3)2. SINGLE EXITS (SECTION 1015.1; SECTION 1019.2)3. COMMON PATH OF EGRESS TRAVEL (SECTION 1014.3)
OCCUPANT LOAD AND EXIT WIDTH
1. SEE TABLE 1004.1.1 TO DETERMINE WHETHER NET OR GROSS AREA IS APPLICABLE.2. MINIMUM STAIRWAY WIDTH (SECTION 1009.1); MIN. CORRIDOR WIDTH (SECTION 1017.2); MIN. DOOR WIDTH
(SECTION 1008.1)3. MINIMUM WIDTH OF EXIT PASSAGEWAY (SECTION 1021.2)4. THE LOSS OF 1 MEANS OF EGRESS SHALL NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50% OF THE TOTAL
REQUIRED (SECTION 1005.1)5. ASSEMBLY OCCUPANCIES (SECTION 1025)
CITY OF BURLINGTON
EXIST. 1
XX
X
UNLIMITED
USE GROUPAND/OR SPACEDESIGNATION
(a)
AREA 1
SQ.FT.
(b)
AREA 1 PEROCCUPANT
(a/b)
NUMBER OFOCCUPANTS
REQUIRED WIDTH(a/b)xc
(TABLE 1005.1)STAIR LEVEL
EXIT WIDTH (in)2,3,4,5
ACTUAL WIDTHSHOWN ON PLANS
STAIR LEVEL
TOTAL # OF OCCUPANTS
(c)
EGRESS WIDTHPER OCCUPANT(TABLE 1005.1)STAIR LEVEL
FLOOR, ROOMAND/OR SPACEDESIGNATION
MINIMUM NUMBER OFEXITS2
REQUIRED SHOWN ONPLANS
TRAVEL DISTANCE
ALLOWABLETRAVEL DIST.
(TABLE 1016.1)
ACTUAL TRAVELDISTANCE SHOWN
ON PLANS
ARRANGEMENT OF MEANS OFEGRESS 1,3 (SECTION 1015.2)
REQUIRED DIST.BTWN. EXITS
(TABLE 1015.1)ACTUAL DISTANCESHOWN ON PLANS
JOHN P. PLAGEMAN
PLAGEMAN ARCHITECTURE JOHN P. PLAGEMAN 10091 919-619-5012
JOHN P. PLAGEMAN 919-619-5012
INDICATE IF THE FOLLOWING ARE PRESENT AND INDICATE BY A WALL LEGEND ON ALL PLANS:
FIRE PARTITION 709 FIRE WALLS 706 FIRE BARRIERS 707 SMOKE PARTITIONS 711
SMOKE BARRIERS 710 SHAFT ENCLOSURES 708
A001
GENERAL NOTES
1. ARCHITECT IS NOT RESPONSIBLE FOR BUILDING'S EXISTINGCONDITIONS. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORFIELD VERIFICATION AND COORDINATION OF ALL INFORMATIONINCLUDED WITHIN THESE DOCUMENTS.
2. ALL CONSTRUCTION AND CONSTRUCTION PRACTICES SHALL BE INACCORDANCE WITH THE NORTH CAROLINA STATE BUILDING CODEALONG WITH CITY, COUNTY AND STATE REGULATIONS.
3. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANYADDITIONAL DRAWINGS NOT CONTAINED HERE-IN, FOR THEPURPOSE OF OBTAINING PERMITS.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORCOORDINATING ALL DRAWINGS WITH ALL SITE INFORMATIONAND APPLICABLE CODES.
5. GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE ALLPLUMBING, MECHANICAL, ELECTRICAL, AND FIRE PROTECTIONDRAWINGS. ARCHITECT IS NOT RESPONSIBLE FOR FIELDDISCREPANCIES.
6. WHERE IT IS STATED "GC TO COORDINATE WITH (INCLUDING BUTNOT LIMITED TO OWNER, ENGINEER, MANUFACTURER)",ARCHITECT IS NOT RESPONSIBLE FOR DECISIONS ORCOORDINATION.
7. IF ANY FIELD CHANGES ARE MADE DURING CONSTRUCTION ANDTHE ARCHITECT IS NOT INCLUDED WITHIN THE DISCUSSION,ARCHITECT IS NOT RESPONSIBLE FOR RESULTS.
8. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR JOB SAFETY.THESE DRAWINGS DO NOT CONTAIN PROVISIONS FOR JOB SAFETY.
9. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYINGTHE ARCHITECT IMMEDIATELY OF CONSTRUCTION DEVIATINGFROM DEPICTED OR IMPLIED INFORMATION HERE-IN.
10. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COMPARINGALL DIMENSIONS IN THE CONSTRUCTION DOCUMENTS ANDEXISTING CONDITIONS IN THE FIELD.
11. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYINGAND INFORMING THE ARCHITECT OF ANY DISCREPANCIES,ERRORS, CONFLICTS, OR OMISSIONS FOUND IN THECONSTRUCTION DOCUMENTS BEFORE PROCEEDINGS ORCONTINUING WORK IN THIS AREA.
12. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYINGALL FIELD DIMENSIONS PRIOR TO STARTING WORK, AND PRIOR TOORDERING EQUIPMENT AND/OR CASEWORK.
13. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKINGALL SHOP DRAWINGS AND VERIFYING THAT THEY ARE CORRECT.
14. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDINGEXHAUST FOR DRYERS, BATHROOMS, AND RANGES TO EXTERIORWITH PROPER TERMINUS (NOT TO BE LOCATED ON STREET SIDEELEVATION) VERIFY TERMINUS TYPE AND LOCATION WITH OWNERPRIOR TO INSTALLATION.
15. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURINGTHAT ALL MATERIALS, FINISHES, AND/ OR EQUIPMENT SHALL BEINSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'SSPECIFICATIONS AND/OR RECOMMENDATIONS.
16. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR CONSTRUCTIONVARIATIONS FROM THE INFORMATION CONTAINED HERE-INUNLESS REVIEWED AND APPROVED BY ARCHITECT.
17. DO NOT SCALE DRAWINGS, BUT RATHER INQUIRE OF ARCHITECT.REPRODUCTION OF THESE DRAWINGS IS PROHIBITED UNLESSWRITTEN PERMISSION IS OBTAINED FROM ARCHITECT.
18. ALL FINISHES ARE TO BE SELECTED BY OWNER UNLESS NOTEDOTHERWISE. ALL COLORS TO BE CHOSEN FROM MANUFACTURERSTANDARD COLOR SELECTION.
19. ALL MATERIALS /EQUIPMENT SPECIFIED WITHIN THESECONSTRUCTION DOCUMENTS SHALL BE USED FORCONSTRUCTION. SUBSTITUTIONS OF SIMILAR OR EQUALPRODUCTS MUST BE APPROVED BY THE OWNER AND ARCHITECT.
20. GENERAL CONTRACTOR SHALL PROVIDE FIRE EXTINGUISHERSDURING CONSTRUCTION PER LOCAL FIRE MARSHALREQUIREMENTS.
21. GENERAL CONTRACTOR SHALL PROVIDE ALL BASIS AND BLOCKINGREQUIRED FOR ACCESSORIES, MECHANICAL, ELECTRICAL AND ALLOTHER EQUIPMENT.
APPENDIX B CODE SUMMARYSCALE: NTS
CS2
GENERAL NOTES,ENERGY SUMMARY,
AND APPENDIX B
3 PROJECT SUMMARYSCALE: NTS2 GENERAL NOTES
SCALE: NTS1
68,500 +/- 0 68,500 +/-
AN EXISTING SCHOOL BUILDING - IN OPERATION - TYPE 2B CONSTRUCTION
THESE DRAWINGS ARE FOR THE ALTERATION OF THE ENTRY LOBBY TO INCLUDE A SECURITY VESTIBULE
TO THE BEST OF OUR KNOWLEDGE THIS PROJECT IS DESIGNED IN COMPLIANCE WITH THE NORTHCAROLINA EXISTING BUILDING CODE.
NONE
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2013
REVISIONS
HIG
HLA
ND
E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
372
0 B
ON
NA
R B
RID
GE
R
D, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
HIGHLAND ELEMENTARY
3720 BONNAR BRIDGE RD, BURLINGTON, NC, 27215
68,500 +/- 0 68,500 +/-
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO CHANGE TO EXISTING
EXISTING BUILDING
NO CHANGE TO EXISTING
THIS PROJECT IS ADDING A SECURITY VESTIBULE INSIDE THE EXISTING ENTRYWAY. THE SCOPE OFWORK DOES NOT HINDER OR ALTER EGRESS WHICH HAS BEEN APPROVED, BUILT AND ACERTIFICATE OF OCCUPANCY GRANTED FOR THIS ELEMENTARY SCHOOL.
EXIST.
RECEPTION
CLINIC
SIMS
GUIDANCE CONFERENCE
TEST
OFFICE OFFICE
BOYS RESTROOM
ENTRY
GUIDANCE WAITING ROOM
HALLWAY
11'-0"
01
02
W1
℄
A100
2A
℄
ENTRY VESTIBULE
2B
HALLWAY
INSTALL ELECTRIFIED DOORSTRIKES TO BE CONTROLLEDAT RECEPTION DESK.
INSTALL TRANSACTIONWINDOW. SEE SPECIFICATION.
30" x 48" CLEAR FLOOR SPACEFOR PARALLEL APPROACH
01
FINISH FLOOR0'-0"
EXISTING ACT CLG10'-0"
FINISH FLOOR0'-0"
EXISTING ACT CLG10'-0"
02 TRANSACTION WINDOW AS SPECIFIED
3'-2" 3'-5 1/2" 3'-2"
10'-1 1/2"
2'-8
"
10'-0
"
1'-1
0"1'
-10"
2'-1
0"
STOREFRONT WINDOW/DOOR FRAME TYPESGENERAL WINDOW NOTE:
· ALL INTERIOR STOREFRONT WINDOW/DOORSYSTEMS TO BE "KAWNEER" INFRAMEINTERIOR FRAMING SYSTEM, FINISH:PERMAFLUOR DARK IVY.
· INSTALL ALL WINDOWS AND STOREFRONTWINDOW/DOOR SYSTEMS TO COMPLY WITHMANUFACTURER STANDARD ANDWARRANTEE INFORMATION.
· TRANSACTION WINDOW TO BE READY ACCESS,275 LOW PROFILE SINGLE PANEL SLIDER;STANDARD SIZE: 35-3/4"W x 35-3/4"H ORSIMILAR
1/4" CLEAR TEMPERED GLASS
A1004
7'-0
"
6'-0"
D1ALUMINUM STOREFRONT DOOR
6"1'
-0"
6"
6" 6"
6"
1/4" CLEARTEMPEREDGLASS
DOOR AND FRAME SCHEDULEDOOR
TAG WIDTH HEIGHT THICK TYPE MATERIAL GLAZING FIRERATING
DOORMATERIAL TYPE
FRAME HARDWARESET
NOTES
0102
6'-0"3'-0"
7'-0"7'-10"
1 3/4"1 3/4"
D1D2
ALUM YES ----
ALUM -- A ----
HARDWARE SET NOTES:A. PAIR OF EXTERIOR ALUMINUM ENTRANCE DOORS WITH PANIC HARDWARE - LOCKSET
ALUM YES ALUM -- A
7'-1
0"
3'-0"
D2ALUMINUM STOREFRONT DOOR
1'-0
"
6"
6"
1/4" CLEARTEMPEREDGLASS
4"
SOLID SURFACE COUNTERTOP,TYP. UNLESS OTHERWISENOTED. OWNER TO CHOOSETYPE AND COLOR.
1 1/
2"
4"
1 1/
2"
36" M
AX.
EXISTING MASONRY WALL
TRANSACTIONWINDOW AS SPECIFIED
INTERIOR ELEVATION A100
FLOOR PLAN
2
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2013
REVISIONS
HIG
HLA
ND
E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
372
0 B
ON
NA
R B
RID
GE
R
D, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
FLOOR PLANSCALE: 1/4" = 1'-0"1
SECTION DETAIL4
SCALE: 1/4" = 1'-0"
SCALE: 1"=1'-0"
PLAN LEGEND:
EXISTING WALL
WALL TYPE - ALL WALLS ARE TYPEW1 UNLESS OTHERWISE NOTED
PLAN NOTES:
1. ALL INTERIOR WALLS ARE WALL TYPE W1 AND ARE DRAWN AS 3-5/8"METAL STUDS UNLESS NOTED OTHERWISE.
2. DIMENSIONS ARE TO FACE OF FRAMING UNLESS NOTED OTHERWISE.3. FRAMING SUBCONTRACTOR SHALL COORDINATE FRAMING WITH
LOCATIONS OF HVAC VENTS, PLUMBING AND LIGHTING FIXTURES SOAS TO AVOID CONFLICT.
4. ALL GLAZING WITHIN 24" OF EITHER SIDE OF A DOOR IN A CLOSEDPOSITION, AND ON THE SAME WALL PLANE SHALL BE TEMPERED.TEMPERED GLASS SHALL BE INSTALLED BY CODE IN THE FOLLOWINGLOCATIONS:
a. DOOR GLAZINGb. GLAZING WITHIN 24" OF AN ADJACENT DOOR WITH SILL LESS THAN
60 DEGREESc. INDIVIDUAL PANES OF GLAZING GREATER THAN 9 SF AND SILL LESS
THAN 18" ABOVE FLOOR AND TOP EDGE GREATER THAN 36"5. TRANSACTION WINDOW TO BE READY ACCESS, 275 LOW PROFILE
SINGLE PANEL SLIDER; STANDARD SIZE: 35-3/4"W x 35-3/4"H ORSIMILAR
DOOR TAG01
W1
NEW WALL
WALL TYPES:
W1: 5/8" GYPSUM BOARD, 3-5/8" METALS STUDS @16" O.C., 5/8" GYPSUM BOARD
DOOR TYPES AND SCHEDULE3 SCALE: NOT TO SCALE
ABBREVIATIONSSCALE: NTS
@: At (the rate of)&: And1R1S: One Rod One Shelf2R2S: Two Rods Two Shelves5S: Five Shelves
AB: Anchor BoltABV: AboveAC: Air Conditioning, Alternating Current, AcousticalACC: AccessACI: American Concrete InstituteACT: Acoustical Tile; ActualADA: Americans with Disabilities Act of 1992ADAAG: Americans with Disabilities Act Architectural GuidelinesADD: Addendum; AdditionADDL: AdditionalADJ: Adjust, Adjustable, AdjacentAFF: Above Finished FloorAGGR: AggregateAIA: American Institute of ArchitectsALUM: AluminumAMT: AmountAPPROX: ApproximateAPRVD: ApprovedARCH: Architect, ArchitecturalASB: AsbestosASSOC: Association; AssociateASTM: American Society for Testing and MaterialsAUTO: AutomaticAVG: Average
BDRM: BedroomBETW: BetweenBG: Bag (e.g., of cement)BLDG: BuildingBLKG: BlockingBLT-IN: Built-InBLW: BelowBOT: BottomBRK: BrickBTU: British Thermal UnitsBTUH: British Thermal Units per Hour
CAB: CabinetCAP: CapacityCAR: CarpetCARP: CarpenterCAT: CatalogCAV: CavityCB: Catch Basin, Concrete Block,Cast Brass, Coal BinCBL: Concrete BlockCBX: Cast Box StrikeCC: Cubic CentimeterCCT: CircuitCCW: Counter ClockwiseCCTV: Closed Circuit TVCD: Cold Drawn, CadmiumCDS: Cold Drawn SteelCEL: CellarCEM: CementCEM AB: Cement Asbestos BoardCem P: Cement Water PaintCER: CeramicCF: Cubic FeetCFL: CounterflashingCFM: Cubic Feet per MinuteCFS: Cubic Feet per SecondCFT: Cubic FootCG: Corner GuardCH: Coat HookCHB: Chalk BoardCHR: Chilled Water ReturnCHAM: ChamferCHAN: ChannelCHBD: ChalkboardCHS: Chilled Water SupplyC.I.: Cast IronCI: Cast IronCIN BL: Cinder BlockCIP: Cast Iron Pipe, Cast-in-PlaceCIR: Circle, Circular, CircuitCIRC: CircumferenceCISP: Cast Iron Soil/sewer PipeCITG: Clear Insulating Tempered GlassCJ: Control JointCJF: Cork Joint FillerCK: CaulkingCKT: CircuitCL: Centerline, Clearance, Closing, Closure, Class, ClosetCLG: CeilingCLKG: CaulkingCLH: Clothes Line HookCLL: Contract Limit LineCLO: ClosetCLP: ClampCLR: ClearCMU: Concrete Masonry UnitCMUP: Concrete Masonry Unit PaintedCNTR: Center, CounterC.O.: Cased OpeningCO: Company, Cleanout, Cased Opening, Cut OutCOL: ColumnCON: ConstructionCONC: ConcreteCONST: ConstructionCONT: Continuous, Continue, ControlCPT: CarpetCRS: CourseCT: Ceramic Tile, Cork Tile,CTR: Center, Counter
DBL: DoubleDEG: DegreeDEMO: DemolitionDH: Double HungDIAG: DiagonalDIA: DiameterDIM: DimensionDISP: DisposalDIV: DivisionDS: DownspoutDTL: DetailDWG: DrawingDS: Downspout
EA: EachEIFS: Exterior Insulation and Finish SystemEJ: Expansion JointEL: Elevation, ElevatorELEC: ElectricalELEV: Elevator, ElevationEMER: EmergencyENTR: EntranceEPDM: Ethylene Propylene Diene MonomerEQ: EqualEQUIP: EquipmentEST: EstimateEXIST: Existing
FABR: FabricateFACP: Fire Alarm Control PanelFAR: Floor Area RatioFD: Floor drainFDC: Fire Department ConnectionFE: Fire ExtinguisherFEC: Fire Extinguisher CabinetFFE: Finished Floor ElevationFF&E: Fixtures, Furnishings & EquipmentFIN: Finish, finishedFIXT: FixtureFLR: FloorFOC: Face of ConcreteFOF: Face of FinishFOS: Face of StudsFPL: FireplaceFT: Foot, Feet, Fully TemperedFTG: Footing, FittingFURN: Furnish, FurnitureFURR: Furring
GA: Gauge, GageGAL: GallonGALV: GalvanizedGB: Grab Bar, Glass Block, Gypsum BoardGC: General ContractorGCB: Gypsum Ceiling BoardGPM: Gallons Per MinuteGVL: GravelGWB: Gypsum Wall Board
HB: Hose BibHBD: HardboardHC: HandicappedHDR: HeaderHDW: HardwareHDWD: HardwoodHGT: HeightHORIZ: HorizontalHR: HourHTR: HeaterHTWR: Hot Water HeaterHVAC: Heating, Ventilating & ACHW: Hot Water
ID: Inside DiameterIN: InchINCAND: IncandescentINFO: InformationINSUL: InsulationINT: Interior, InternalINV: Invert
J-BOX: Junction BoxJAN: JanitorJST: JoistJT: Joint
KIT: KitchenKO: KnockoutKS: Kitchen Sink
L: Linen ClosetLAD: LadderLAM: Laminate, LaminatedLAV: LavatoryLB: Pound (weight)LH: Left HandLIBR: LibraryLIN: LinearLINO: LinoleumLL: Live LoadLNTL: LintelLR: Living RoomLTL: LintelLT WT: LightweightLVL: Laminated Veneer LumberLVR: Louver
MAINT: MaintenanceMAX: MaximumMECH: MechanicalMED: MediumMED CAB: Medicine CabinetMEMB: MembraneMEZZ: MezzanineMIN: MinimumMIR: MirrorMISC: MiscellaneousMTD: MountedMTL: Material, Metal
NEUT: NeutralNIC: Not In ContractNOM: NominalNTS: Not To Scale
OC: On CenterOD: Outside DiameterOH: OverheadOHD: Overhead DoorOPNG: OpeningOPP: OppositeOPP H: Opposite Hand
P. LAM: Plastic LaminatePBD: Particle BoardPLUMB: PlumbingPNEU: PneumaticPNL: PanelPRTN: PartitionPT: Pressure TreatedPTD: Painted, Paper Towel DispenserPVC: Polyvinyl Chloride
QT: Quarry Tile, QuartQTR: QuarterQTY: Quantity
RCP: Reflected Ceiling PlanRD: Roof DrainREBAR: Reinforcing BarREFL: Reflected, ReflectorREF: RefrigeratorREQD: RequiredREV: Reverse, Revise, RevisionRH: Right HandRMV: RemoveRO: Rough Opening
SAN: SanitarySCHED: ScheduleSCWD: Solid Core WoodSEAL: SealantSECT: SectionSF: Square FootSHT: SheetSIM: SimilarSPEC: Specification, SpecificationsSPECS: SpecificationsSPK: SpeakerSQ: SquareSS: Stainless SteelSTC: Sound Transmission ClassSTD: StandardSTL: SteelSTO: StorageSTRUC: StructuralSYN: Synthetic
T: ThermostatT&G: Tongue & GrooveTB: Towel BarTEL: TelephoneTEMP: TemporaryTHK: Thick, ThicknessTHRU: ThroughTR: Tread, TransomTSL: Top of SlabTST: Top of SteelTV: TelevisionTW: Top of WallTYP: Typical
UC: UndercutUL: Underwriters' LaboratoriesUNFIN: UnfinishedUNO: Unless Noted OtherwiseUT: Utility
VB: Vapor BarrierVCT: Vinyl Composition TileVENT: Ventilate, VentilatorVERT: VerticalVEST: VestibuleVIF: Verify In the FieldVIN: VinylVOL: VolumeVT: Vinyl Tile
WAINS: WainscotWD: WoodWH: Water HeaterWWF: Welded Wire Fabric
INDEX OF DRAWINGSSCALE: NTS
HILLCREST ELEMENTARY1714 W DAVIS STREET
BURLINGTON, NC, 27215
Architect: PLAGEMAN ARCHITECTURE408 S Spring St. - Burlington - North Carolina - 27215
phone: 336-226-3933 - Email: [email protected] - John Plageman
PERMIT SET
04/06/2020
material symbols
CONCRETE MASONRY UNIT
WASHED STONE
CONCRETE
EARTH
ROUGH WOOD - BLOCKING
FINISHED WOOD
STONE
STEEL (LARGE SCALE) BATT INSULATION
RIGID FOAM INSULATION
PLYWOOD
BRICK
GLASS
GYPSUM BOARD
drawing symbolsW2ELEVATION AND DETAIL NUMBER
INTERIOR ELEVATION AND DETAIL LETTER
COLUMN LINE DESIGNATION
DENOTES MATERIAL/BUILDING FINISHES, REFER TO A8.0
DENOTES WALL TYPE DESIGNATION
DENOTES FINISHED CEILING HEIGHT AFF
DOOR NUMBER DESIGNATION
W1 WINDOW/GLASS NUMBER DESIGNATION
ABC TYPE FIRE EXTINGUISHER
A INTERIOR ELEVATION TAG
DENOTES ELEVATION HEIGHT
DENOTES FLOORING FINISH TYPE
DENOTES WALL BASE TYPEFL-1WB-1
12
SHEET NAMESUBMISSION DATE
INDEX OF DRAWING
SHEET #PERMIT SET
ARCHITECTURAL DRAWINGSCS1 COVER SHEET, ABBREVIATIONS, INDEX OF DRAWING, GENERAL NOTES
A100 GROUND FLOOR PLAN
04/06/2020
CS1
COVER SHEET,ABBREVIATIONS,
INDEX OF DRAWING
X'-X"
D1
A
D
C
B
ACM1
X
A1001
A1001
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2015
REVISIONS
HILLC
RE
ST
E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
17
14
W
D
AV
IS
S
TR
EE
T, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
GENERAL NOTES
1. ARCHITECT IS NOT RESPONSIBLE FOR BUILDING'S EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL BERESPONSIBLE FOR FIELD VERIFICATION AND COORDINATION OF ALL INFORMATION INCLUDED WITHIN THESEDOCUMENTS.
2. ALL CONSTRUCTION AND CONSTRUCTION PRACTICES SHALL BE IN ACCORDANCE WITH THE NORTH CAROLINA STATEBUILDING CODE ALONG WITH CITY, COUNTY AND STATE REGULATIONS.
3. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY ADDITIONAL DRAWINGS NOT CONTAINED HERE-IN, FOR THEPURPOSE OF OBTAINING PERMITS.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL DRAWINGS WITH ALL SITE INFORMATION ANDAPPLICABLE CODES.
5. GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL PLUMBING, MECHANICAL, ELECTRICAL, AND FIREPROTECTION DRAWINGS. ARCHITECT IS NOT RESPONSIBLE FOR FIELD DISCREPANCIES.
6. WHERE IT IS STATED "GC TO COORDINATE WITH (INCLUDING BUT NOT LIMITED TO OWNER, ENGINEER,MANUFACTURER)", ARCHITECT IS NOT RESPONSIBLE FOR DECISIONS OR COORDINATION.
7. IF ANY FIELD CHANGES ARE MADE DURING CONSTRUCTION AND THE ARCHITECT IS NOT INCLUDED WITHIN THEDISCUSSION, ARCHITECT IS NOT RESPONSIBLE FOR RESULTS.
8. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR JOB SAFETY. THESE DRAWINGS DO NOT CONTAIN PROVISIONS FORJOB SAFETY.
9. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE ARCHITECT IMMEDIATELY OF CONSTRUCTIONDEVIATING FROM DEPICTED OR IMPLIED INFORMATION HERE-IN.
10. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COMPARING ALL DIMENSIONS IN THE CONSTRUCTIONDOCUMENTS AND EXISTING CONDITIONS IN THE FIELD.
11. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYING AND INFORMING THE ARCHITECT OF ANYDISCREPANCIES, ERRORS, CONFLICTS, OR OMISSIONS FOUND IN THE CONSTRUCTION DOCUMENTS BEFOREPROCEEDINGS OR CONTINUING WORK IN THIS AREA.
12. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL FIELD DIMENSIONS PRIOR TO STARTING WORK, ANDPRIOR TO ORDERING EQUIPMENT AND/OR CASEWORK.
13. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING ALL SHOP DRAWINGS AND VERIFYING THAT THEY ARECORRECT.
14. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING EXHAUST FOR DRYERS, BATHROOMS, AND RANGES TOEXTERIOR WITH PROPER TERMINUS (NOT TO BE LOCATED ON STREET SIDE ELEVATION) VERIFY TERMINUS TYPE ANDLOCATION WITH OWNER PRIOR TO INSTALLATION.
15. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT ALL MATERIALS, FINISHES, AND/ OR EQUIPMENTSHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND/OR RECOMMENDATIONS.
16. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION VARIATIONS FROM THE INFORMATION CONTAINEDHERE-IN UNLESS REVIEWED AND APPROVED BY ARCHITECT.
17. DO NOT SCALE DRAWINGS, BUT RATHER INQUIRE OF ARCHITECT. REPRODUCTION OF THESE DRAWINGS IS PROHIBITEDUNLESS WRITTEN PERMISSION IS OBTAINED FROM ARCHITECT.
18. ALL FINISHES ARE TO BE SELECTED BY OWNER UNLESS NOTED OTHERWISE. ALL COLORS TO BE CHOSEN FROMMANUFACTURER STANDARD COLOR SELECTION.
19. ALL MATERIALS /EQUIPMENT SPECIFIED WITHIN THESE CONSTRUCTION DOCUMENTS SHALL BE USED FORCONSTRUCTION. SUBSTITUTIONS OF SIMILAR OR EQUAL PRODUCTS MUST BE APPROVED BY THE OWNER ANDARCHITECT.
20. GENERAL CONTRACTOR SHALL PROVIDE FIRE EXTINGUISHERS DURING CONSTRUCTION PER LOCAL FIRE MARSHALREQUIREMENTS.
21. GENERAL CONTRACTOR SHALL PROVIDE ALL BASIS AND BLOCKING REQUIRED FOR ACCESSORIES, MECHANICAL,ELECTRICAL AND ALL OTHER EQUIPMENT.
CS2 APPENDIX B 04/06/202004/06/2020
GENERAL NOTES
1. ARCHITECT IS NOT RESPONSIBLE FOR BUILDING'S EXISTINGCONDITIONS. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORFIELD VERIFICATION AND COORDINATION OF ALL INFORMATIONINCLUDED WITHIN THESE DOCUMENTS.
2. ALL CONSTRUCTION AND CONSTRUCTION PRACTICES SHALL BE INACCORDANCE WITH THE NORTH CAROLINA STATE BUILDING CODEALONG WITH CITY, COUNTY AND STATE REGULATIONS.
3. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANYADDITIONAL DRAWINGS NOT CONTAINED HERE-IN, FOR THEPURPOSE OF OBTAINING PERMITS.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORCOORDINATING ALL DRAWINGS WITH ALL SITE INFORMATIONAND APPLICABLE CODES.
5. GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE ALLPLUMBING, MECHANICAL, ELECTRICAL, AND FIRE PROTECTIONDRAWINGS. ARCHITECT IS NOT RESPONSIBLE FOR FIELDDISCREPANCIES.
6. WHERE IT IS STATED "GC TO COORDINATE WITH (INCLUDING BUTNOT LIMITED TO OWNER, ENGINEER, MANUFACTURER)",ARCHITECT IS NOT RESPONSIBLE FOR DECISIONS ORCOORDINATION.
7. IF ANY FIELD CHANGES ARE MADE DURING CONSTRUCTION ANDTHE ARCHITECT IS NOT INCLUDED WITHIN THE DISCUSSION,ARCHITECT IS NOT RESPONSIBLE FOR RESULTS.
8. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR JOB SAFETY.THESE DRAWINGS DO NOT CONTAIN PROVISIONS FOR JOB SAFETY.
9. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYINGTHE ARCHITECT IMMEDIATELY OF CONSTRUCTION DEVIATINGFROM DEPICTED OR IMPLIED INFORMATION HERE-IN.
10. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COMPARINGALL DIMENSIONS IN THE CONSTRUCTION DOCUMENTS ANDEXISTING CONDITIONS IN THE FIELD.
11. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYINGAND INFORMING THE ARCHITECT OF ANY DISCREPANCIES,ERRORS, CONFLICTS, OR OMISSIONS FOUND IN THECONSTRUCTION DOCUMENTS BEFORE PROCEEDINGS ORCONTINUING WORK IN THIS AREA.
12. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYINGALL FIELD DIMENSIONS PRIOR TO STARTING WORK, AND PRIOR TOORDERING EQUIPMENT AND/OR CASEWORK.
13. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKINGALL SHOP DRAWINGS AND VERIFYING THAT THEY ARE CORRECT.
14. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDINGEXHAUST FOR DRYERS, BATHROOMS, AND RANGES TO EXTERIORWITH PROPER TERMINUS (NOT TO BE LOCATED ON STREET SIDEELEVATION) VERIFY TERMINUS TYPE AND LOCATION WITH OWNERPRIOR TO INSTALLATION.
15. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURINGTHAT ALL MATERIALS, FINISHES, AND/ OR EQUIPMENT SHALL BEINSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'SSPECIFICATIONS AND/OR RECOMMENDATIONS.
16. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR CONSTRUCTIONVARIATIONS FROM THE INFORMATION CONTAINED HERE-INUNLESS REVIEWED AND APPROVED BY ARCHITECT.
17. DO NOT SCALE DRAWINGS, BUT RATHER INQUIRE OF ARCHITECT.REPRODUCTION OF THESE DRAWINGS IS PROHIBITED UNLESSWRITTEN PERMISSION IS OBTAINED FROM ARCHITECT.
18. ALL FINISHES ARE TO BE SELECTED BY OWNER UNLESS NOTEDOTHERWISE. ALL COLORS TO BE CHOSEN FROM MANUFACTURERSTANDARD COLOR SELECTION.
19. ALL MATERIALS /EQUIPMENT SPECIFIED WITHIN THESECONSTRUCTION DOCUMENTS SHALL BE USED FORCONSTRUCTION. SUBSTITUTIONS OF SIMILAR OR EQUALPRODUCTS MUST BE APPROVED BY THE OWNER AND ARCHITECT.
20. GENERAL CONTRACTOR SHALL PROVIDE FIRE EXTINGUISHERSDURING CONSTRUCTION PER LOCAL FIRE MARSHALREQUIREMENTS.
21. GENERAL CONTRACTOR SHALL PROVIDE ALL BASIS AND BLOCKINGREQUIRED FOR ACCESSORIES, MECHANICAL, ELECTRICAL AND ALLOTHER EQUIPMENT.
CS2
GENERAL NOTES,ENERGY SUMMARY,
AND APPENDIX B
GENERAL NOTESSCALE: NTS1
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2015
REVISIONS
HILLC
RE
ST
E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
17
14
W
D
AV
IS
S
TR
EE
T, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
HILLCREST ELEMENTARY
1714 W DAVIS STREET, BURLINGTON, NC, 27215
BUILDING CODE SUMMARYFOR ALL COMMERCIAL PROJECTS(EXCEPT 1 & 2 FAMILY DWELLINGS AND TOWNHOUSES)
NAME OF PROJECT:
ADDRESS:
OWNER OR AUTHORIZED AGENT: PHONE:
EMAIL: FAX:
OWNED BY: PRIVATELY CITY/COUNTY STATE
CODE ENFORCEMENT JURISDICTION: CITY COUNTY STATE
NAME OF JURISDICTION:
PROJECT SUMMARY
BUILDING DESCRIPTION:
SCOPE OF WORK:
CODE COMPLIANCE SUMMARY:
ALTERNATIVE MEANS OF COMPLIANCE REQUEST:
LEAD DESIGN PROFESSIONAL/PROJECT COORDINATOR:
DESIGNER FIRM NAME LICENSE# PHONE#
ARCHITECTURAL:
CIVIL:
ELECTRICAL:
FIRE ALARM:
PLUMBING:
MECHANICAL:
SPRINKLER-STANDPIPE:
STRUCTURAL:
PRECAST:
TRUSSES:
RETAINING WALLS >5'
OTHER:
NOTE: IF APPLICABLE, SPECIAL INSPECTIONS AND INSPECTORS TO BE LISTED ON THIS SHEET
XX
OCCUPANCY INFORMATIONPRIMARY OCCUPANCIES:
ASSEMBLY: A-1 A-2 A-3 A-4 A-5 BUSINESS EDUCATIONAL
FACTORY-INDUSTRIAL: F-1 F-2
HIGH-HAZARD: H-1 H-2 H-3 H-4 H-5
INSTITUTIONAL: I-1 I-2 I-3 I-4I3 USE CONDITION: 1 2 3 4 5
MERCANTILE RESIDENTIAL: R-1 R-2 R-3 R-4
STORAGE: S-1 S-2 HIGH-PILEDS-1 REPAIR GARAGE(406.6) S-2 PARKING GARAGE OPEN(406.3) ENCLOSED(406.4)
UTILITY AND MISCELLANEOUS
OTHER USES:ACCESSORY USES (INDICATE PERCENTAGES):
INCIDENTAL USES:
SPECIAL OCCUPANCIES: 402 403 404 405 406 407 408 409 410411 412 413 414 415 416 417 418 419420 421 422 423 424 425 426 427
X
MIXED OCCUPANCY: NO YES SEPARATION:NON-SEPARATED MIXED OCCUPANCY (508.3.2)SEPARATED MIXED OCCUPANCY (508.3.3)
ACTUAL AREA OF OCCUPANCY A + ACTUAL AREA OF OCCUPANCY B < 1 ALLOWABLE AREA OF OCCUPANCY A ALLOWABLE AREA OF OCCUPANCY B
X
ALLOWABLE AREA & HEIGHT CALCULATIONS
EXTERIOR WALL ACTUAL LENGTH OPEN LENGTH WIDTH OF PUBLIC WAY OR OPEN SPACE
NORTH
SOUTH
EAST
WEST
TOTAL P F W
INCREASE FRONTAGE %INCREASE SPRINKLERS %
FRONTAGE INCREASE FORMULA ALLOWABLE AREA FORMULAI(f) = 100(F - 0.25) W
P 30
BUILDING DATACONSTRUCTION TYPE: I-A I-B II-A II-B III-A III-B IV-HT V-A V-B
MIXED CONSTRUCTION: NO YES
SPRINKLERS: NO YES NFPA 13 NFPA 13R PARTIALLY SPRINKLERED SPECIAL SUPPRESSION
STANDPIPES: NO YES CLASS: I II III WET DRY
BUILDING HEIGHT: FEET STORY
BASEMENT: NO YES MEZZANINE: NO YES
HIGH RISE: NO YES LIFE SAFETY PLAN SHEET #
GROSS BUILDING AREA:
FLOOR EXISTING (SQ FT) NEW (SQ FT) SUB-TOTAL
BASEMENTGROUND FLOORMEZZANINE2ND FLOOR3RD FLOOR4TH FLOOR
TOTAL
AREA OF PROJECT TENANT/ALTERATION/RENOVATION:AREA OF CONSTRUCTION:
XX
X
XX
X
X
BOTH BUILDING AND TENANT MUST BE INDICATED ON CHART BELOW
STORY#
OCCUPANCY (A)BLDG AREAPER STORY(ACTUAL)
(B)TABLE 503 5
AREA
(C)% OPENSPACE
INCREASE 1
(D)%
SPRINKLERINCREASE 2
(E)ALLOWABLEFLOOR AREA
ORUNLIMITED 3
RATIO OFACTUAL TOALLOWABLE
(F)MAX. BLDG
AREA 4
SEPARATIONRATING
REQUIRED
NOTES:1. OPEN SPACE AREA INCREASES FROM SECTION 506.2 ARE COMPUTED THUS:
a. PERIMETER WHICH FRONTS A PUBLIC WAY OR OPEN SPACE HAVING 20 FEET MIN. WIDTH = ______ FT(F)b. TOTAL BUILDING PERIMETER = _________ FT (P)c. RATIO (F/P) = __________ (F/P)d. W = MINIMUM WIDTH OF PUBLIC WAY = _________ FT (W)e. PERCENT OF FRONTAGE INCREASE = ___________ (FROM FORMULA ABOVE)
2. THE SPRINKLER INCREASE PER SECTION 506.3 IS AS FOLLOWS:a. MULTISTORY BUILDING IS = 200 PERCENTb. SINGLE STORY BUILDING IS = 300 PERCENT
3. UNLIMITED AREA APPLICABLE UNDER CONDITIONS OF SECTIONS GROUP B,F,M,S,A-4 (507.1, 507.2, 507.3, 507.4, 507.7); GROUP A MOTION PICTURE (507.10); MALLS (507.11); AND H-2 AIRCRAFT PAINT HANGARS (507.8).
4. MAXIMUM BUILDING AREA = TOTAL NUMBER OF STORIES IN THE BUILDING X E BUT NOT GREATER THAN 3 X E.
5. THE MAXIMUM AREA OF PARKING GARAGES MUST COMPLY WITH 406.3.5. THE MAXIMUM AREA OF AIR TRAFFIC CONTROL TOWERS MUST COMPLY WITH 412.1.2.
ALLOWABLE HEIGHTMOST RESTRICTIVE USE
(GROUP ____ )ALLOWABLE HEIGHT
(TABLE 503)INCREASE FOR
SPRINKLERSSHOWN ON
PLANSCODE REFERENCE
TYPE OF CONSTRUCTION
BUILDING HEIGHT (FT)
BUILDING HEIGHT (STORIES)
TYPE _____________ TYPE ________ TABLE 601
TABLE 503
TABLE 503
H = _______
S = _______
H + 20 FT = ______ (FT)
S + 1 = _________
H = _______ (FT)
S = ________
FIRE PROTECTION REQUIREMENTS
BUILDINGELEMENT
FIRE SEPARATIONDISTANCE
(FEET)
RATINGREQ'D PROVIDED
(W/ _____ HR*REDUCTION)
DETAIL #&
SHEET #
DESIGN #FOR RATEDASSEMBLY
DESIGN #FOR RATED
PENETRATION
DESIGN #FOR RATED
JOINTS
BEARING WALLS EXTERIORNORTHSOUTH
EASTWEST
INTERIOR BEARING WALLSNON-BEARING WALLS EXTERIOR
NORTHSOUTH
EASTWEST
INTERIOR NON-BEARING WALLS
STRUCTURAL FRAME, INCLUDINGSUPPORTING COLUMNS, GIRDERS& TRUSSES
FLOOR CONSTRUCTION,INCLUDING SUPPORTING BEAMSAND JOISTS. LIST CONSTRUCTIONTYPE.FLOOR CEILING ASSEMBLYCOLUMNS SUPPORTING FLOORS
ROOF CONSTRUCTION, INCLUDINGSUPPORTING BEAMS & JOISTS**
ROOF CEILING ASSEMBLYCOLUMNS SUPPORTING ROOFSHAFTS - EXIT ENCLOSURESSHAFTS - OTHER (DESCRIBE)SHAFTS - OTHER (DESCRIBE)CORRIDOR SEPARATIONOCCUPANCY SEPARATION
PARTY/FIRE WALL SEPARATIONINCIDENTAL USE SEPARATION
DWELLING/SLEEPING UNITSEPARATIONSMOKE BARRIER SEPARATIONTENANT SEPARATION
* INDICATE SECTION NUMBER PERMITTING REDUCTION** INDICATE IF USING TABLE 601 NOTE C EXCEPTION
PERCENTAGE OF WALL OPENING CALCULATIONSTHIS SECTION FOR ADDITIONS, NEW AND CHANGE OF USE
ALLOWABLE OPENINGS PER TABLE 705.8
WALL LEGENDS
LIFE SAFETY SYSTEM REQUIREMENTS
LIFE SAFETY PLAN SHEET # (IF REQUIRED)
EMERGENCY LIGHTING: NO YES
EXIT SIGNS: NO YES
FIRE ALARM: NO YES
SMOKE DETECTION SYSTEMS: NO YES
PANIC HARDWARE: NO YES
XXX
X
EXIT REQUIREMENTSNUMBER AND ARRANGEMENT OF EXITS
1. CORRIDOR DEAD ENDS (SECTION 1017.3)2. SINGLE EXITS (SECTION 1015.1; SECTION 1019.2)3. COMMON PATH OF EGRESS TRAVEL (SECTION 1014.3)
OCCUPANT LOAD AND EXIT WIDTH
1. SEE TABLE 1004.1.1 TO DETERMINE WHETHER NET OR GROSS AREA IS APPLICABLE.2. MINIMUM STAIRWAY WIDTH (SECTION 1009.1); MIN. CORRIDOR WIDTH (SECTION 1017.2); MIN. DOOR WIDTH
(SECTION 1008.1)3. MINIMUM WIDTH OF EXIT PASSAGEWAY (SECTION 1021.2)4. THE LOSS OF 1 MEANS OF EGRESS SHALL NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50% OF THE TOTAL
REQUIRED (SECTION 1005.1)5. ASSEMBLY OCCUPANCIES (SECTION 1025)
CITY OF BURLINGTON
EXIST. 1
EXISTING
100 SF +/-100 SF +/-
UNLIMITED
USE GROUPAND/OR SPACEDESIGNATION
(a)
AREA 1
SQ.FT.
(b)
AREA 1 PEROCCUPANT
(a/b)
NUMBER OFOCCUPANTS
REQUIRED WIDTH(a/b)xc
(TABLE 1005.1)STAIR LEVEL
EXIT WIDTH (in)2,3,4,5
ACTUAL WIDTHSHOWN ON PLANS
STAIR LEVEL
TOTAL # OF OCCUPANTS
(c)
EGRESS WIDTHPER OCCUPANT(TABLE 1005.1)STAIR LEVEL
FLOOR, ROOMAND/OR SPACEDESIGNATION
MINIMUM NUMBER OFEXITS2
REQUIRED SHOWN ONPLANS
TRAVEL DISTANCE
ALLOWABLETRAVEL DIST.
(TABLE 1016.1)
ACTUAL TRAVELDISTANCE SHOWN
ON PLANS
ARRANGEMENT OF MEANS OFEGRESS 1,3 (SECTION 1015.2)
REQUIRED DIST.BTWN. EXITS
(TABLE 1015.1)ACTUAL DISTANCESHOWN ON PLANS
JOHN P. PLAGEMAN
PLAGEMAN ARCHITECTURE JOHN P. PLAGEMAN 10091 919-619-5012
JOHN P. PLAGEMAN 919-619-5012
INDICATE IF THE FOLLOWING ARE PRESENT AND INDICATE BY A WALL LEGEND ON ALL PLANS:
FIRE PARTITION 709 FIRE WALLS 706 FIRE BARRIERS 707 SMOKE PARTITIONS 711
SMOKE BARRIERS 710 SHAFT ENCLOSURES 708
APPENDIX B CODE SUMMARYSCALE: NTS3 PROJECT SUMMARY
SCALE: NTS2
87,640 +/- 0 87,640 +/-
AN EXISTING SCHOOL BUILDING - IN OPERATION - TYPE 2B CONSTRUCTION
THESE DRAWINGS ARE FOR THE ALTERATION OF THE ENTRY LOBBY TO INCLUDE A SECURITY VESTIBULE
TO THE BEST OF OUR KNOWLEDGE THIS PROJECT IS DESIGNED IN COMPLIANCE WITH THE EXISTINGBUILDING CODE OF NORTH CAROLINA
NONE
HILLCREST ELEMENTARY IS BROKEN UP INTO 4 BUILDINGS CONNECTED BY SMALL HALLWAYCONNECTORS.
THIS PROJECT IS THE ADDITION OF A SECURITY VESTIBULE WITHIN THE MAIN BUILDINGENTRYWAY.
THE MAIN BUILDING IS APPROXIMATELY 31,960 SQ.FT.
87,640 +/- 0 87,640 +/-
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO CHANGE TO EXISTING
EXISTING BUILDING
NO CHANGE TO EXISTING
PRINCIPAL CONFERENCE
ENTRY
LIBRARY OFFICE
HEALTH OFFICE
HALLWAY
WORKROOM
PROFESSIONAL LIBRARY
RECEPTION
23'-0
"
W1
01 02
A100
2B
1
1
2A
TRANSACTION WINDOW AS SPECIFIED
INSTALL ELECTRIFIED DOOR STRIKE TOBE CONTROLLED AT RECEPTION DESK.
INSTALL ELECTRIFIED DOOR STRIKE TOBE CONTROLLED AT RECEPTION DESK.
30" x 48" CLEAR FLOOR SPACEFOR PARALLEL APPROACH
ENTRY VESTIBULE
7'-0
"
6'-0"
D1ALUMINUM STOREFRONT DOOR
6"1'
-0"
6"
6" 6"
6"
1/4" CLEARTEMPEREDGLASS
DOOR AND FRAME SCHEDULEDOOR
TAG WIDTH HEIGHT THICK TYPE MATERIAL GLAZING FIRERATING
DOORMATERIAL TYPE
FRAME HARDWARESET
NOTES
0102
6'-0"6'-0"
7'-0"7'-0"
1 3/4"1 3/4"
D1D1
ALUM YES ----
ALUM -- A ----
HARDWARE SET NOTES:A. PAIR OF EXTERIOR ALUMINUM ENTRANCE DOORS WITH PANIC HARDWARE - LOCKSET
ALUM YES ALUM -- A
FINISH FLOOR0'-0"
TOP OF WALL11'-0"
0201
CAP WALL AND LEAVECEILING ABOVE EXPOSED
EXPOSED CEILINGEXPOSED CEILING
2BINTERIOR ELEVATION
TRANSACTIONWINDOW AS SPECIFIED
2'-1
0"
FINISH FLOOR0'-0"
TOP OF WALL11'-0"
2AINTERIOR ELEVATION
A1005
STOREFRONT WINDOW/DOOR FRAME TYPES
GENERAL WINDOW NOTE:
· ALL INTERIOR STOREFRONT WINDOW/DOOR SYSTEMS TO BE "KAWNEER" INFRAME INTERIOR FRAMING SYSTEM, FINISH: PERMAFLUOR DARK IVY.· INSTALL ALL WINDOWS AND STOREFRONT WINDOW/DOOR SYSTEMS TO COMPLY WITH MANUFACTURER STANDARD AND WARRANTEE INFORMATION.· TRANSACTION WINDOW TO BE READY ACCESS, 275 LOW PROFILE SINGLE PANEL SLIDER; STANDARD SIZE: 35-3/4"W x 35-3/4"H OR SIMILAR
7'-0
"
1/4" CLEARTEMPEREDGLASS
DOOR, SEE DOORTYPE AND SCHEDULE
DOOR, SEE DOORTYPE AND SCHEDULE
1'-4"
15'-2"
6'-0" 6'-0" 1'-4"
2'-1
0"
TYPE 1
4"
SOLID SURFACE COUNTERTOP,TYP. UNLESS OTHERWISENOTED. OWNER TO CHOOSETYPE AND COLOR.
1 1/
2"
4"
1 1/
2"
36" M
AX.
EXISTING MASONRY WALL
TRANSACTIONWINDOW AS SPECIFIED
EXISTING MASONRY WALL
INTERIOR ELEVATIONSCALE: 1/4" = 1'-0"
A100
FLOOR PLAN
2
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2015
REVISIONS
HILLC
RE
ST
E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
17
14
W
D
AV
IS
S
TR
EE
T, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
FLOOR PLANSCALE: 1/4" = 1'-0"1
PLAN LEGEND:
EXISTING WALL
WALL TYPE - ALL WALLS ARE TYPEW1 UNLESS OTHERWISE NOTED
PLAN NOTES:
1. ALL INTERIOR WALLS ARE WALL TYPE W1 AND ARE DRAWN AS3-5/8" METAL STUDS UNLESS NOTED OTHERWISE.
2. DIMENSIONS ARE TO FACE OF FRAMING UNLESS NOTEDOTHERWISE.
3. FRAMING SUBCONTRACTOR SHALL COORDINATE FRAMING WITHLOCATIONS OF HVAC VENTS, PLUMBING AND LIGHTING FIXTURESSO AS TO AVOID CONFLICT.
4. ALL GLAZING WITHIN 24" OF EITHER SIDE OF A DOOR IN A CLOSEDPOSITION, AND ON THE SAME WALL PLANE SHALL BE TEMPERED.TEMPERED GLASS SHALL BE INSTALLED BY CODE IN THEFOLLOWING LOCATIONS:
a. DOOR GLAZINGb. GLAZING WITHIN 24" OF AN ADJACENT DOOR WITH SILL LESS
THAN 60 DEGREESc. INDIVIDUAL PANES OF GLAZING GREATER THAN 9 SF AND SILL
LESS THAN 18" ABOVE FLOOR AND TOP EDGE GREATER THAN 36"5. TRANSACTION WINDOW TO BE READY ACCESS, 275 LOW PROFILE
SINGLE PANEL SLIDER; STANDARD SIZE: 35-3/4"W x 35-3/4"H ORSIMILAR
DOOR TAG01
W1
NEW WALL
WALL TYPES:
W1: 5/8" GYPSUM BOARD, 3-5/8" METAL STUDS @16" O.C., 5/8" GYPSUM BOARD
DOOR SCHEDULE AND TYPESCALE: NOT TO SCALE3
SECTION DETAILSCALE: 1" = 1'-0"5 WINDOW TYPES
SCALE: NOT TO SCALE4
ABBREVIATIONSSCALE: NTS
@: At (the rate of)&: And1R1S: One Rod One Shelf2R2S: Two Rods Two Shelves5S: Five Shelves
AB: Anchor BoltABV: AboveAC: Air Conditioning, Alternating Current, AcousticalACC: AccessACI: American Concrete InstituteACT: Acoustical Tile; ActualADA: Americans with Disabilities Act of 1992ADAAG: Americans with Disabilities Act Architectural GuidelinesADD: Addendum; AdditionADDL: AdditionalADJ: Adjust, Adjustable, AdjacentAFF: Above Finished FloorAGGR: AggregateAIA: American Institute of ArchitectsALUM: AluminumAMT: AmountAPPROX: ApproximateAPRVD: ApprovedARCH: Architect, ArchitecturalASB: AsbestosASSOC: Association; AssociateASTM: American Society for Testing and MaterialsAUTO: AutomaticAVG: Average
BDRM: BedroomBETW: BetweenBG: Bag (e.g., of cement)BLDG: BuildingBLKG: BlockingBLT-IN: Built-InBLW: BelowBOT: BottomBRK: BrickBTU: British Thermal UnitsBTUH: British Thermal Units per Hour
CAB: CabinetCAP: CapacityCAR: CarpetCARP: CarpenterCAT: CatalogCAV: CavityCB: Catch Basin, Concrete Block,Cast Brass, Coal BinCBL: Concrete BlockCBX: Cast Box StrikeCC: Cubic CentimeterCCT: CircuitCCW: Counter ClockwiseCCTV: Closed Circuit TVCD: Cold Drawn, CadmiumCDS: Cold Drawn SteelCEL: CellarCEM: CementCEM AB: Cement Asbestos BoardCem P: Cement Water PaintCER: CeramicCF: Cubic FeetCFL: CounterflashingCFM: Cubic Feet per MinuteCFS: Cubic Feet per SecondCFT: Cubic FootCG: Corner GuardCH: Coat HookCHB: Chalk BoardCHR: Chilled Water ReturnCHAM: ChamferCHAN: ChannelCHBD: ChalkboardCHS: Chilled Water SupplyC.I.: Cast IronCI: Cast IronCIN BL: Cinder BlockCIP: Cast Iron Pipe, Cast-in-PlaceCIR: Circle, Circular, CircuitCIRC: CircumferenceCISP: Cast Iron Soil/sewer PipeCITG: Clear Insulating Tempered GlassCJ: Control JointCJF: Cork Joint FillerCK: CaulkingCKT: CircuitCL: Centerline, Clearance, Closing, Closure, Class, ClosetCLG: CeilingCLKG: CaulkingCLH: Clothes Line HookCLL: Contract Limit LineCLO: ClosetCLP: ClampCLR: ClearCMU: Concrete Masonry UnitCMUP: Concrete Masonry Unit PaintedCNTR: Center, CounterC.O.: Cased OpeningCO: Company, Cleanout, Cased Opening, Cut OutCOL: ColumnCON: ConstructionCONC: ConcreteCONST: ConstructionCONT: Continuous, Continue, ControlCPT: CarpetCRS: CourseCT: Ceramic Tile, Cork Tile,CTR: Center, Counter
DBL: DoubleDEG: DegreeDEMO: DemolitionDH: Double HungDIAG: DiagonalDIA: DiameterDIM: DimensionDISP: DisposalDIV: DivisionDS: DownspoutDTL: DetailDWG: DrawingDS: Downspout
EA: EachEIFS: Exterior Insulation and Finish SystemEJ: Expansion JointEL: Elevation, ElevatorELEC: ElectricalELEV: Elevator, ElevationEMER: EmergencyENTR: EntranceEPDM: Ethylene Propylene Diene MonomerEQ: EqualEQUIP: EquipmentEST: EstimateEXIST: Existing
FABR: FabricateFACP: Fire Alarm Control PanelFAR: Floor Area RatioFD: Floor drainFDC: Fire Department ConnectionFE: Fire ExtinguisherFEC: Fire Extinguisher CabinetFFE: Finished Floor ElevationFF&E: Fixtures, Furnishings & EquipmentFIN: Finish, finishedFIXT: FixtureFLR: FloorFOC: Face of ConcreteFOF: Face of FinishFOS: Face of StudsFPL: FireplaceFT: Foot, Feet, Fully TemperedFTG: Footing, FittingFURN: Furnish, FurnitureFURR: Furring
GA: Gauge, GageGAL: GallonGALV: GalvanizedGB: Grab Bar, Glass Block, Gypsum BoardGC: General ContractorGCB: Gypsum Ceiling BoardGPM: Gallons Per MinuteGVL: GravelGWB: Gypsum Wall Board
HB: Hose BibHBD: HardboardHC: HandicappedHDR: HeaderHDW: HardwareHDWD: HardwoodHGT: HeightHORIZ: HorizontalHR: HourHTR: HeaterHTWR: Hot Water HeaterHVAC: Heating, Ventilating & ACHW: Hot Water
ID: Inside DiameterIN: InchINCAND: IncandescentINFO: InformationINSUL: InsulationINT: Interior, InternalINV: Invert
J-BOX: Junction BoxJAN: JanitorJST: JoistJT: Joint
KIT: KitchenKO: KnockoutKS: Kitchen Sink
L: Linen ClosetLAD: LadderLAM: Laminate, LaminatedLAV: LavatoryLB: Pound (weight)LH: Left HandLIBR: LibraryLIN: LinearLINO: LinoleumLL: Live LoadLNTL: LintelLR: Living RoomLTL: LintelLT WT: LightweightLVL: Laminated Veneer LumberLVR: Louver
MAINT: MaintenanceMAX: MaximumMECH: MechanicalMED: MediumMED CAB: Medicine CabinetMEMB: MembraneMEZZ: MezzanineMIN: MinimumMIR: MirrorMISC: MiscellaneousMTD: MountedMTL: Material, Metal
NEUT: NeutralNIC: Not In ContractNOM: NominalNTS: Not To Scale
OC: On CenterOD: Outside DiameterOH: OverheadOHD: Overhead DoorOPNG: OpeningOPP: OppositeOPP H: Opposite Hand
P. LAM: Plastic LaminatePBD: Particle BoardPLUMB: PlumbingPNEU: PneumaticPNL: PanelPRTN: PartitionPT: Pressure TreatedPTD: Painted, Paper Towel DispenserPVC: Polyvinyl Chloride
QT: Quarry Tile, QuartQTR: QuarterQTY: Quantity
RCP: Reflected Ceiling PlanRD: Roof DrainREBAR: Reinforcing BarREFL: Reflected, ReflectorREF: RefrigeratorREQD: RequiredREV: Reverse, Revise, RevisionRH: Right HandRMV: RemoveRO: Rough Opening
SAN: SanitarySCHED: ScheduleSCWD: Solid Core WoodSEAL: SealantSECT: SectionSF: Square FootSHT: SheetSIM: SimilarSPEC: Specification, SpecificationsSPECS: SpecificationsSPK: SpeakerSQ: SquareSS: Stainless SteelSTC: Sound Transmission ClassSTD: StandardSTL: SteelSTO: StorageSTRUC: StructuralSYN: Synthetic
T: ThermostatT&G: Tongue & GrooveTB: Towel BarTEL: TelephoneTEMP: TemporaryTHK: Thick, ThicknessTHRU: ThroughTR: Tread, TransomTSL: Top of SlabTST: Top of SteelTV: TelevisionTW: Top of WallTYP: Typical
UC: UndercutUL: Underwriters' LaboratoriesUNFIN: UnfinishedUNO: Unless Noted OtherwiseUT: Utility
VB: Vapor BarrierVCT: Vinyl Composition TileVENT: Ventilate, VentilatorVERT: VerticalVEST: VestibuleVIF: Verify In the FieldVIN: VinylVOL: VolumeVT: Vinyl Tile
WAINS: WainscotWD: WoodWH: Water HeaterWWF: Welded Wire Fabric
INDEX OF DRAWINGSSCALE: NTS
SMITH ELEMENTARY2235 DELANEY DRIVE
BURLINGTON, NC, 27215
Architect: PLAGEMAN ARCHITECTURE408 S Spring St. - Burlington - North Carolina - 27215
phone: 336-226-3933 - Email: [email protected] - John Plageman
PERMIT SET
03/30/2020
material symbols
CONCRETE MASONRY UNIT
WASHED STONE
CONCRETE
EARTH
ROUGH WOOD - BLOCKING
FINISHED WOOD
STONE
STEEL (LARGE SCALE) BATT INSULATION
RIGID FOAM INSULATION
PLYWOOD
BRICK
GLASS
GYPSUM BOARD
drawing symbolsW2ELEVATION AND DETAIL NUMBER
INTERIOR ELEVATION AND DETAIL LETTER
COLUMN LINE DESIGNATION
DENOTES MATERIAL/BUILDING FINISHES, REFER TO A8.0
DENOTES WALL TYPE DESIGNATION
DENOTES FINISHED CEILING HEIGHT AFF
DOOR NUMBER DESIGNATION
W1 WINDOW/GLASS NUMBER DESIGNATION
ABC TYPE FIRE EXTINGUISHER
A INTERIOR ELEVATION TAG
DENOTES ELEVATION HEIGHT
DENOTES FLOORING FINISH TYPE
DENOTES WALL BASE TYPEFL-1WB-1
12
SHEET NAMESUBMISSION DATE
INDEX OF DRAWING
SHEET #CD 100%
ARCHITECTURAL DRAWINGSCS1 COVER SHEET, ABBREVIATIONS, INDEX OF DRAWING, GENERAL NOTES
A100 GROUND FLOOR PLAN
04/06/2020
CS1
COVER SHEET,ABBREVIATIONS,
INDEX OF DRAWING
X'-X"
D1
A
D
C
B
ACM1
X
A1001
A1001
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2014
REVISIONS
SM
IT
H E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
22
35
D
EL
AN
EY
D
RIV
E, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
GENERAL NOTES
1. ARCHITECT IS NOT RESPONSIBLE FOR BUILDING'S EXISTING CONDITIONS. GENERAL CONTRACTOR SHALL BERESPONSIBLE FOR FIELD VERIFICATION AND COORDINATION OF ALL INFORMATION INCLUDED WITHIN THESEDOCUMENTS.
2. ALL CONSTRUCTION AND CONSTRUCTION PRACTICES SHALL BE IN ACCORDANCE WITH THE NORTH CAROLINA STATEBUILDING CODE ALONG WITH CITY, COUNTY AND STATE REGULATIONS.
3. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANY ADDITIONAL DRAWINGS NOT CONTAINED HERE-IN, FOR THEPURPOSE OF OBTAINING PERMITS.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ALL DRAWINGS WITH ALL SITE INFORMATION ANDAPPLICABLE CODES.
5. GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL PLUMBING, MECHANICAL, ELECTRICAL, AND FIREPROTECTION DRAWINGS. ARCHITECT IS NOT RESPONSIBLE FOR FIELD DISCREPANCIES.
6. WHERE IT IS STATED "GC TO COORDINATE WITH (INCLUDING BUT NOT LIMITED TO OWNER, ENGINEER,MANUFACTURER)", ARCHITECT IS NOT RESPONSIBLE FOR DECISIONS OR COORDINATION.
7. IF ANY FIELD CHANGES ARE MADE DURING CONSTRUCTION AND THE ARCHITECT IS NOT INCLUDED WITHIN THEDISCUSSION, ARCHITECT IS NOT RESPONSIBLE FOR RESULTS.
8. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR JOB SAFETY. THESE DRAWINGS DO NOT CONTAIN PROVISIONS FORJOB SAFETY.
9. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYING THE ARCHITECT IMMEDIATELY OF CONSTRUCTIONDEVIATING FROM DEPICTED OR IMPLIED INFORMATION HERE-IN.
10. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COMPARING ALL DIMENSIONS IN THE CONSTRUCTIONDOCUMENTS AND EXISTING CONDITIONS IN THE FIELD.
11. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYING AND INFORMING THE ARCHITECT OF ANYDISCREPANCIES, ERRORS, CONFLICTS, OR OMISSIONS FOUND IN THE CONSTRUCTION DOCUMENTS BEFOREPROCEEDINGS OR CONTINUING WORK IN THIS AREA.
12. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL FIELD DIMENSIONS PRIOR TO STARTING WORK, ANDPRIOR TO ORDERING EQUIPMENT AND/OR CASEWORK.
13. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKING ALL SHOP DRAWINGS AND VERIFYING THAT THEY ARECORRECT.
14. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING EXHAUST FOR DRYERS, BATHROOMS, AND RANGES TOEXTERIOR WITH PROPER TERMINUS (NOT TO BE LOCATED ON STREET SIDE ELEVATION) VERIFY TERMINUS TYPE ANDLOCATION WITH OWNER PRIOR TO INSTALLATION.
15. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING THAT ALL MATERIALS, FINISHES, AND/ OR EQUIPMENTSHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS AND/OR RECOMMENDATIONS.
16. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR CONSTRUCTION VARIATIONS FROM THE INFORMATION CONTAINEDHERE-IN UNLESS REVIEWED AND APPROVED BY ARCHITECT.
17. DO NOT SCALE DRAWINGS, BUT RATHER INQUIRE OF ARCHITECT. REPRODUCTION OF THESE DRAWINGS IS PROHIBITEDUNLESS WRITTEN PERMISSION IS OBTAINED FROM ARCHITECT.
18. ALL FINISHES ARE TO BE SELECTED BY OWNER UNLESS NOTED OTHERWISE. ALL COLORS TO BE CHOSEN FROMMANUFACTURER STANDARD COLOR SELECTION.
19. ALL MATERIALS /EQUIPMENT SPECIFIED WITHIN THESE CONSTRUCTION DOCUMENTS SHALL BE USED FORCONSTRUCTION. SUBSTITUTIONS OF SIMILAR OR EQUAL PRODUCTS MUST BE APPROVED BY THE OWNER ANDARCHITECT.
20. GENERAL CONTRACTOR SHALL PROVIDE FIRE EXTINGUISHERS DURING CONSTRUCTION PER LOCAL FIRE MARSHALREQUIREMENTS.
21. GENERAL CONTRACTOR SHALL PROVIDE ALL BASIS AND BLOCKING REQUIRED FOR ACCESSORIES, MECHANICAL,ELECTRICAL AND ALL OTHER EQUIPMENT.
CS2 APPENDIX B 04/06/202004/06/2020
BUILDING CODE SUMMARYFOR ALL COMMERCIAL PROJECTS(EXCEPT 1 & 2 FAMILY DWELLINGS AND TOWNHOUSES)
NAME OF PROJECT:
ADDRESS:
OWNER OR AUTHORIZED AGENT: PHONE:
EMAIL: FAX:
OWNED BY: PRIVATELY CITY/COUNTY STATE
CODE ENFORCEMENT JURISDICTION: CITY COUNTY STATE
NAME OF JURISDICTION:
PROJECT SUMMARY
BUILDING DESCRIPTION:
SCOPE OF WORK:
CODE COMPLIANCE SUMMARY:
ALTERNATIVE MEANS OF COMPLIANCE REQUEST:
LEAD DESIGN PROFESSIONAL/PROJECT COORDINATOR:
DESIGNER FIRM NAME LICENSE# PHONE#
ARCHITECTURAL:
CIVIL:
ELECTRICAL:
FIRE ALARM:
PLUMBING:
MECHANICAL:
SPRINKLER-STANDPIPE:
STRUCTURAL:
PRECAST:
TRUSSES:
RETAINING WALLS >5'
OTHER:
NOTE: IF APPLICABLE, SPECIAL INSPECTIONS AND INSPECTORS TO BE LISTED ON THIS SHEET
XX
OCCUPANCY INFORMATIONPRIMARY OCCUPANCIES:
ASSEMBLY: A-1 A-2 A-3 A-4 A-5 BUSINESS EDUCATIONAL
FACTORY-INDUSTRIAL: F-1 F-2
HIGH-HAZARD: H-1 H-2 H-3 H-4 H-5
INSTITUTIONAL: I-1 I-2 I-3 I-4I3 USE CONDITION: 1 2 3 4 5
MERCANTILE RESIDENTIAL: R-1 R-2 R-3 R-4
STORAGE: S-1 S-2 HIGH-PILEDS-1 REPAIR GARAGE(406.6) S-2 PARKING GARAGE OPEN(406.3) ENCLOSED(406.4)
UTILITY AND MISCELLANEOUS
OTHER USES:ACCESSORY USES (INDICATE PERCENTAGES):
INCIDENTAL USES:
SPECIAL OCCUPANCIES: 402 403 404 405 406 407 408 409 410411 412 413 414 415 416 417 418 419420 421 422 423 424 425 426 427
X
MIXED OCCUPANCY: NO YES SEPARATION:NON-SEPARATED MIXED OCCUPANCY (508.3.2)SEPARATED MIXED OCCUPANCY (508.3.3)
ACTUAL AREA OF OCCUPANCY A + ACTUAL AREA OF OCCUPANCY B < 1 ALLOWABLE AREA OF OCCUPANCY A ALLOWABLE AREA OF OCCUPANCY B
X
ALLOWABLE AREA & HEIGHT CALCULATIONS
EXTERIOR WALL ACTUAL LENGTH OPEN LENGTH WIDTH OF PUBLIC WAY OR OPEN SPACE
NORTH
SOUTH
EAST
WEST
TOTAL P F W
INCREASE FRONTAGE %INCREASE SPRINKLERS %
FRONTAGE INCREASE FORMULA ALLOWABLE AREA FORMULAI(f) = 100(F - 0.25) W
P 30
BUILDING DATACONSTRUCTION TYPE: I-A I-B II-A II-B III-A III-B IV-HT V-A V-B
MIXED CONSTRUCTION: NO YES
SPRINKLERS: NO YES NFPA 13 NFPA 13R PARTIALLY SPRINKLERED SPECIAL SUPPRESSION
STANDPIPES: NO YES CLASS: I II III WET DRY
BUILDING HEIGHT: FEET STORY
BASEMENT: NO YES MEZZANINE: NO YES
HIGH RISE: NO YES LIFE SAFETY PLAN SHEET #
GROSS BUILDING AREA:
FLOOR EXISTING (SQ FT) NEW (SQ FT) SUB-TOTAL
BASEMENTGROUND FLOORMEZZANINE2ND FLOOR3RD FLOOR4TH FLOOR
TOTAL
AREA OF PROJECT TENANT/ALTERATION/RENOVATION:AREA OF CONSTRUCTION:
XX
X
XX
X
X
BOTH BUILDING AND TENANT MUST BE INDICATED ON CHART BELOW
STORY#
OCCUPANCY (A)BLDG AREAPER STORY(ACTUAL)
(B)TABLE 503 5
AREA
(C)% OPENSPACE
INCREASE 1
(D)%
SPRINKLERINCREASE 2
(E)ALLOWABLEFLOOR AREA
ORUNLIMITED 3
RATIO OFACTUAL TOALLOWABLE
(F)MAX. BLDG
AREA 4
SEPARATIONRATING
REQUIRED
NOTES:1. OPEN SPACE AREA INCREASES FROM SECTION 506.2 ARE COMPUTED THUS:
a. PERIMETER WHICH FRONTS A PUBLIC WAY OR OPEN SPACE HAVING 20 FEET MIN. WIDTH = ______ FT(F)b. TOTAL BUILDING PERIMETER = _________ FT (P)c. RATIO (F/P) = __________ (F/P)d. W = MINIMUM WIDTH OF PUBLIC WAY = _________ FT (W)e. PERCENT OF FRONTAGE INCREASE = ___________ (FROM FORMULA ABOVE)
2. THE SPRINKLER INCREASE PER SECTION 506.3 IS AS FOLLOWS:a. MULTISTORY BUILDING IS = 200 PERCENTb. SINGLE STORY BUILDING IS = 300 PERCENT
3. UNLIMITED AREA APPLICABLE UNDER CONDITIONS OF SECTIONS GROUP B,F,M,S,A-4 (507.1, 507.2, 507.3, 507.4, 507.7); GROUP A MOTION PICTURE (507.10); MALLS (507.11); AND H-2 AIRCRAFT PAINT HANGARS (507.8).
4. MAXIMUM BUILDING AREA = TOTAL NUMBER OF STORIES IN THE BUILDING X E BUT NOT GREATER THAN 3 X E.
5. THE MAXIMUM AREA OF PARKING GARAGES MUST COMPLY WITH 406.3.5. THE MAXIMUM AREA OF AIR TRAFFIC CONTROL TOWERS MUST COMPLY WITH 412.1.2.
ALLOWABLE HEIGHTMOST RESTRICTIVE USE
(GROUP ____ )ALLOWABLE HEIGHT
(TABLE 503)INCREASE FOR
SPRINKLERSSHOWN ON
PLANSCODE REFERENCE
TYPE OF CONSTRUCTION
BUILDING HEIGHT (FT)
BUILDING HEIGHT (STORIES)
TYPE _____________ TYPE ________ TABLE 601
TABLE 503
TABLE 503
H = _______
S = _______
H + 20 FT = ______ (FT)
S + 1 = _________
H = _______ (FT)
S = ________
FIRE PROTECTION REQUIREMENTS
BUILDINGELEMENT
FIRE SEPARATIONDISTANCE
(FEET)
RATINGREQ'D PROVIDED
(W/ _____ HR*REDUCTION)
DETAIL #&
SHEET #
DESIGN #FOR RATEDASSEMBLY
DESIGN #FOR RATED
PENETRATION
DESIGN #FOR RATED
JOINTS
BEARING WALLS EXTERIORNORTHSOUTH
EASTWEST
INTERIOR BEARING WALLSNON-BEARING WALLS EXTERIOR
NORTHSOUTH
EASTWEST
INTERIOR NON-BEARING WALLS
STRUCTURAL FRAME, INCLUDINGSUPPORTING COLUMNS, GIRDERS& TRUSSES
FLOOR CONSTRUCTION,INCLUDING SUPPORTING BEAMSAND JOISTS. LIST CONSTRUCTIONTYPE.FLOOR CEILING ASSEMBLYCOLUMNS SUPPORTING FLOORS
ROOF CONSTRUCTION, INCLUDINGSUPPORTING BEAMS & JOISTS**
ROOF CEILING ASSEMBLYCOLUMNS SUPPORTING ROOFSHAFTS - EXIT ENCLOSURESSHAFTS - OTHER (DESCRIBE)SHAFTS - OTHER (DESCRIBE)CORRIDOR SEPARATIONOCCUPANCY SEPARATION
PARTY/FIRE WALL SEPARATIONINCIDENTAL USE SEPARATION
DWELLING/SLEEPING UNITSEPARATIONSMOKE BARRIER SEPARATIONTENANT SEPARATION
* INDICATE SECTION NUMBER PERMITTING REDUCTION** INDICATE IF USING TABLE 601 NOTE C EXCEPTION
PERCENTAGE OF WALL OPENING CALCULATIONSTHIS SECTION FOR ADDITIONS, NEW AND CHANGE OF USE
ALLOWABLE OPENINGS PER TABLE 705.8
WALL LEGENDS
LIFE SAFETY SYSTEM REQUIREMENTS
LIFE SAFETY PLAN SHEET # (IF REQUIRED)
EMERGENCY LIGHTING: NO YES
EXIT SIGNS: NO YES
FIRE ALARM: NO YES
SMOKE DETECTION SYSTEMS: NO YES
PANIC HARDWARE: NO YES
XXX
X
EXIT REQUIREMENTSNUMBER AND ARRANGEMENT OF EXITS
1. CORRIDOR DEAD ENDS (SECTION 1017.3)2. SINGLE EXITS (SECTION 1015.1; SECTION 1019.2)3. COMMON PATH OF EGRESS TRAVEL (SECTION 1014.3)
OCCUPANT LOAD AND EXIT WIDTH
1. SEE TABLE 1004.1.1 TO DETERMINE WHETHER NET OR GROSS AREA IS APPLICABLE.2. MINIMUM STAIRWAY WIDTH (SECTION 1009.1); MIN. CORRIDOR WIDTH (SECTION 1017.2); MIN. DOOR WIDTH
(SECTION 1008.1)3. MINIMUM WIDTH OF EXIT PASSAGEWAY (SECTION 1021.2)4. THE LOSS OF 1 MEANS OF EGRESS SHALL NOT REDUCE THE AVAILABLE CAPACITY TO LESS THAN 50% OF THE TOTAL
REQUIRED (SECTION 1005.1)5. ASSEMBLY OCCUPANCIES (SECTION 1025)
CITY OF BURLINGTON
EXIST. 1
EXISTING
100 SF +/-100 SF +/-
UNLIMITED
USE GROUPAND/OR SPACEDESIGNATION
(a)
AREA 1
SQ.FT.
(b)
AREA 1 PEROCCUPANT
(a/b)
NUMBER OFOCCUPANTS
REQUIRED WIDTH(a/b)xc
(TABLE 1005.1)STAIR LEVEL
EXIT WIDTH (in)2,3,4,5
ACTUAL WIDTHSHOWN ON PLANS
STAIR LEVEL
TOTAL # OF OCCUPANTS
(c)
EGRESS WIDTHPER OCCUPANT(TABLE 1005.1)STAIR LEVEL
FLOOR, ROOMAND/OR SPACEDESIGNATION
MINIMUM NUMBER OFEXITS2
REQUIRED SHOWN ONPLANS
TRAVEL DISTANCE
ALLOWABLETRAVEL DIST.
(TABLE 1016.1)
ACTUAL TRAVELDISTANCE SHOWN
ON PLANS
ARRANGEMENT OF MEANS OFEGRESS 1,3 (SECTION 1015.2)
REQUIRED DIST.BTWN. EXITS
(TABLE 1015.1)ACTUAL DISTANCESHOWN ON PLANS
JOHN P. PLAGEMAN
PLAGEMAN ARCHITECTURE JOHN P. PLAGEMAN 10091 919-619-5012
JOHN P. PLAGEMAN 919-619-5012
INDICATE IF THE FOLLOWING ARE PRESENT AND INDICATE BY A WALL LEGEND ON ALL PLANS:
FIRE PARTITION 709 FIRE WALLS 706 FIRE BARRIERS 707 SMOKE PARTITIONS 711
SMOKE BARRIERS 710 SHAFT ENCLOSURES 708
GENERAL NOTES
1. ARCHITECT IS NOT RESPONSIBLE FOR BUILDING'S EXISTINGCONDITIONS. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORFIELD VERIFICATION AND COORDINATION OF ALL INFORMATIONINCLUDED WITHIN THESE DOCUMENTS.
2. ALL CONSTRUCTION AND CONSTRUCTION PRACTICES SHALL BE INACCORDANCE WITH THE NORTH CAROLINA STATE BUILDING CODEALONG WITH CITY, COUNTY AND STATE REGULATIONS.
3. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ANYADDITIONAL DRAWINGS NOT CONTAINED HERE-IN, FOR THEPURPOSE OF OBTAINING PERMITS.
4. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FORCOORDINATING ALL DRAWINGS WITH ALL SITE INFORMATIONAND APPLICABLE CODES.
5. GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE ALLPLUMBING, MECHANICAL, ELECTRICAL, AND FIRE PROTECTIONDRAWINGS. ARCHITECT IS NOT RESPONSIBLE FOR FIELDDISCREPANCIES.
6. WHERE IT IS STATED "GC TO COORDINATE WITH (INCLUDING BUTNOT LIMITED TO OWNER, ENGINEER, MANUFACTURER)",ARCHITECT IS NOT RESPONSIBLE FOR DECISIONS ORCOORDINATION.
7. IF ANY FIELD CHANGES ARE MADE DURING CONSTRUCTION ANDTHE ARCHITECT IS NOT INCLUDED WITHIN THE DISCUSSION,ARCHITECT IS NOT RESPONSIBLE FOR RESULTS.
8. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR JOB SAFETY.THESE DRAWINGS DO NOT CONTAIN PROVISIONS FOR JOB SAFETY.
9. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR NOTIFYINGTHE ARCHITECT IMMEDIATELY OF CONSTRUCTION DEVIATINGFROM DEPICTED OR IMPLIED INFORMATION HERE-IN.
10. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR COMPARINGALL DIMENSIONS IN THE CONSTRUCTION DOCUMENTS ANDEXISTING CONDITIONS IN THE FIELD.
11. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR IDENTIFYINGAND INFORMING THE ARCHITECT OF ANY DISCREPANCIES,ERRORS, CONFLICTS, OR OMISSIONS FOUND IN THECONSTRUCTION DOCUMENTS BEFORE PROCEEDINGS ORCONTINUING WORK IN THIS AREA.
12. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYINGALL FIELD DIMENSIONS PRIOR TO STARTING WORK, AND PRIOR TOORDERING EQUIPMENT AND/OR CASEWORK.
13. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CHECKINGALL SHOP DRAWINGS AND VERIFYING THAT THEY ARE CORRECT.
14. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDINGEXHAUST FOR DRYERS, BATHROOMS, AND RANGES TO EXTERIORWITH PROPER TERMINUS (NOT TO BE LOCATED ON STREET SIDEELEVATION) VERIFY TERMINUS TYPE AND LOCATION WITH OWNERPRIOR TO INSTALLATION.
15. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURINGTHAT ALL MATERIALS, FINISHES, AND/ OR EQUIPMENT SHALL BEINSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'SSPECIFICATIONS AND/OR RECOMMENDATIONS.
16. THE ARCHITECT SHALL NOT BE RESPONSIBLE FOR CONSTRUCTIONVARIATIONS FROM THE INFORMATION CONTAINED HERE-INUNLESS REVIEWED AND APPROVED BY ARCHITECT.
17. DO NOT SCALE DRAWINGS, BUT RATHER INQUIRE OF ARCHITECT.REPRODUCTION OF THESE DRAWINGS IS PROHIBITED UNLESSWRITTEN PERMISSION IS OBTAINED FROM ARCHITECT.
18. ALL FINISHES ARE TO BE SELECTED BY OWNER UNLESS NOTEDOTHERWISE. ALL COLORS TO BE CHOSEN FROM MANUFACTURERSTANDARD COLOR SELECTION.
19. ALL MATERIALS /EQUIPMENT SPECIFIED WITHIN THESECONSTRUCTION DOCUMENTS SHALL BE USED FORCONSTRUCTION. SUBSTITUTIONS OF SIMILAR OR EQUALPRODUCTS MUST BE APPROVED BY THE OWNER AND ARCHITECT.
20. GENERAL CONTRACTOR SHALL PROVIDE FIRE EXTINGUISHERSDURING CONSTRUCTION PER LOCAL FIRE MARSHALREQUIREMENTS.
21. GENERAL CONTRACTOR SHALL PROVIDE ALL BASIS AND BLOCKINGREQUIRED FOR ACCESSORIES, MECHANICAL, ELECTRICAL AND ALLOTHER EQUIPMENT.
APPENDIX B CODE SUMMARYSCALE: NTS
CS2
GENERAL NOTES,ENERGY SUMMARY,
AND APPENDIX B
3 PROJECT SUMMARYSCALE: NTS2 GENERAL NOTES
SCALE: NTS1
87,640 +/- 0 87,640 +/-
AN EXISTING SCHOOL BUILDING - IN OPERATION - TYPE 2B CONSTRUCTION
THESE DRAWINGS ARE FOR THE ALTERATION OF THE ENTRY LOBBY TO INCLUDE A SECURITY VESTIBULE
TO THE BEST OF OUR KNOWLEDGE THIS PROJECT IS DESIGNED IN COMPLIANCE WITH THE EXISTINGBUILDING CODE OF NORTH CAROLINA
NONE
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2014
REVISIONS
SM
IT
H E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
22
35
D
EL
AN
EY
D
RIV
E, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
SMITH ELEMENTARY
2235 DELANEY DRIVE, BURLINGTON, NC, 27215
SMITH ELEMENTARY IS BROKEN UP INTO 4 BUILDINGS CONNECTED BY SMALL HALLWAYCONNECTORS.
THIS PROJECT IS THE ADDITION OF A SECURITY VESTIBULE WITHIN THE MAIN BUILDINGENTRYWAY.
THE MAIN BUILDING IS APPROXIMATELY 31,960 SQ.FT.
87,640 +/- 0 87,640 +/-
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO SCOPE OF WORK
EXISTING BUILDING
NO CHANGE TO EXISTING
EXISTING BUILDING
NO CHANGE TO EXISTING
PRINCIPAL
RECEPTION
CONFERENCE
ENTRY
LIBRARY OFFICE
HEALTH OFFICE
HALLWAY
WORKROOM
PROFESSIONAL LIBRARY
23'-0
"
W1
01 02
A100
2B
ENTRY VESTIBULE
1
1
2A
TRANSACTION WINDOW AS SPECIFIED
INSTALL ELECTRIFIED DOOR STRIKE TOBE CONTROLLED AT RECEPTION DESK.
30" x 48" CLEAR FLOOR SPACEFOR PARALLEL APPROACH
INSTALL ELECTRIFIED DOOR STRIKE TOBE CONTROLLED AT RECEPTION DESK.
FINISH FLOOR0'-0"
TOP OF WALL11'-0"
0201
CAP WALL AND LEAVECEILING ABOVE EXPOSED
EXPOSED CEILINGEXPOSED CEILING
2BINTERIOR ELEVATION
7'-0
"
6'-0"
D1ALUMINUM STOREFRONT DOOR
6"1'
-0"
6"
6" 6"
6"
1/4" CLEARTEMPEREDGLASS
DOOR AND FRAME SCHEDULEDOOR
TAG WIDTH HEIGHT THICK TYPE MATERIAL GLAZING FIRERATING
DOORMATERIAL TYPE
FRAME HARDWARESET
NOTES
0102
6'-0"6'-0"
7'-0"7'-0"
1 3/4"1 3/4"
D1D1
ALUM YES ----
ALUM -- A ----
HARDWARE SET NOTES:A. PAIR OF EXTERIOR ALUMINUM ENTRANCE DOORS WITH PANIC HARDWARE - LOCKSET
ALUM YES ALUM -- A
STOREFRONT WINDOW/DOOR FRAME TYPES
GENERAL WINDOW NOTE:
· ALL INTERIOR STOREFRONT WINDOW/DOOR SYSTEMS TO BE "KAWNEER" INFRAME INTERIOR FRAMING SYSTEM, FINISH: PERMAFLUOR DARK IVY.· INSTALL ALL WINDOWS AND STOREFRONT WINDOW/DOOR SYSTEMS TO COMPLY WITH MANUFACTURER STANDARD AND WARRANTEE INFORMATION.· TRANSACTION WINDOW TO BE READY ACCESS, 275 LOW PROFILE SINGLE PANEL SLIDER; STANDARD SIZE: 35-3/4"W x 35-3/4"H OR SIMILAR
7'-0
"
1/4" CLEARTEMPEREDGLASS
DOOR, SEE DOORTYPE AND SCHEDULE
DOOR, SEE DOORTYPE AND SCHEDULE
1'-4"
15'-2"
6'-0" 6'-0" 1'-4"
2'-1
0"
TYPE 1
TRANSACTIONWINDOW AS SPECIFIED
2'-1
0"
FINISH FLOOR0'-0"
TOP OF WALL11'-0"
2AINTERIOR ELEVATION
A1005
4"
SOLID SURFACE COUNTERTOP,TYP. UNLESS OTHERWISENOTED. OWNER TO CHOOSETYPE AND COLOR.
1 1/
2"
4"
1 1/
2"
36" M
AX.
EXISTING MASONRY WALL
TRANSACTIONWINDOW AS SPECIFIED
EXISTING MASONRY WALL
INTERIOR ELEVATIONSCALE: 1/4" = 1'-0"
A100
FLOOR PLAN
2
CO
NS
TR
UC
TIO
N D
RA
WIN
GS
F
OR
:
JOB NUMBER
PA2014
REVISIONS
SM
IT
H E
LE
ME
NT
AR
Y
Plageman Architecture
Burlington, NC 27215
408 S. Spring St.
336-226-3933
SHEET NAME
IS
SU
ED
F
OR
C
ON
ST
RU
CT
IO
N
plagemanarchitecture.com
CO
PY
RIG
HT
2
01
8 - P
LA
GE
MA
N A
RC
HIT
EC
TU
RE
- T
HE
SE
D
RA
WIN
GS
A
RE
IN
ST
RU
ME
NT
S O
F S
ER
VIC
E IN
TE
ND
ED
F
OR
T
HE
U
SE
O
F T
HIS
P
RO
JE
CT
O
NL
Y - A
NY
R
EU
SE
O
R R
EP
RO
DU
CT
IO
N F
OR
A
NO
TH
ER
P
RO
JE
CT
IS
S
TR
IC
TL
Y P
RO
HIB
IT
ED
.
04/06/2020
INITIAL
PERMIT
SUBMITTAL
22
35
D
EL
AN
EY
D
RIV
E, B
UR
LIN
GT
ON, N
C, 2
72
15
SHEET NUMBER
DRAWN BY: (JC)
04/06/2020
FLOOR PLANSCALE: 1/4" = 1'-0"1
PLAN LEGEND:
EXISTING WALL
WALL TYPE - ALL WALLS ARE TYPEW1 UNLESS OTHERWISE NOTED
PLAN NOTES:
1. ALL INTERIOR WALLS ARE WALL TYPE W1 AND ARE DRAWN AS3-5/8" METAL STUDS UNLESS NOTED OTHERWISE.
2. DIMENSIONS ARE TO FACE OF FRAMING UNLESS NOTEDOTHERWISE.
3. FRAMING SUBCONTRACTOR SHALL COORDINATE FRAMING WITHLOCATIONS OF HVAC VENTS, PLUMBING AND LIGHTING FIXTURESSO AS TO AVOID CONFLICT.
4. ALL GLAZING WITHIN 24" OF EITHER SIDE OF A DOOR IN A CLOSEDPOSITION, AND ON THE SAME WALL PLANE SHALL BE TEMPERED.TEMPERED GLASS SHALL BE INSTALLED BY CODE IN THEFOLLOWING LOCATIONS:
a. DOOR GLAZINGb. GLAZING WITHIN 24" OF AN ADJACENT DOOR WITH SILL LESS
THAN 60 DEGREESc. INDIVIDUAL PANES OF GLAZING GREATER THAN 9 SF AND SILL
LESS THAN 18" ABOVE FLOOR AND TOP EDGE GREATER THAN 36"5. TRANSACTION WINDOW TO BE READY ACCESS, 275 LOW PROFILE
SINGLE PANEL SLIDER; STANDARD SIZE: 35-3/4"W x 35-3/4"H ORSIMILAR
DOOR TAG01
W1
NEW WALL
WALL TYPES:
W1: 5/8" GYPSUM BOARD, 3-5/8" METAL STUDS @16" O.C., 5/8" GYPSUM BOARD
DOOR SCHEDULE AND TYPESCALE: NOT TO SCALE3
SECTION DETAILSCALE: 1" = 1'-0"5 WINDOW TYPES
SCALE: NOT TO SCALE4