Selective Coordination Study
Recommended Procedures
14
The following steps are recommended when
conducting a selective coordination study.
1. One-Line Diagram
Obtain the electrical system one-line diagram that identifies
important system components, as given below.
a. TransformersObtain the following data for protection and coordination infor-
mation of transformers:
- KVA rating
- Inrush points
- Primary and secondary connections
- Impedance
- Damage curves
- Primary and secondary voltages
- Liquid or dry type
b. Conductors - Check phase, neutral, and equipment
grounding. The one-line diagram should include infor-
mation such as:
- Conductor size
- Number of conductors per phase- Material (copper or aluminum)
- Insulation
- Conduit (magnetic or non-magnetic)
From this information, short circuit withstand curves can be
developed. This provides information on how overcurrent
devices will protect conductors from overload and short
circuit damage.
c. Motors
The system one-line diagram should include motor
information such as:
- Full load currents
- Horsepower
- Voltage
- Type of starting characteristic
(across the line, etc.)
- Type of overload relay
(Class 10, 20, 30)
Overload protection of the motor and motor circuit can be
determined from this data.
d. Fuse Characteristics
Fuse Types/Classes should be identified on the one-line
diagram.
e. Circuit Breaker Characteristics
Circuit Breaker Types should be identified on the one-line
diagram.
f. Relay Characteristics
Relay Types should be identified on the one-line diagram.
2. Short Circuit Study
Perform a short circuit analysis, calculating maximum
available short circuit currents at critical points in the
distribution system (such as transformers, main switchgear,
panelboards, motor control centers, load centers, and large
motors and generators.) (Reference: Bussmann Bulletin,Engineering Dependable Protection - EDPI.)
3. Helpful Hints
a. Determine the Ampere Scale Selection. It is most
convenient to place the time current curves in the center of
the log-log paper. This is accomplished by multiplying or
dividing the ampere scale by a factor of 10.
b. Determine the Reference (Base) Voltage. The best
reference voltage is the voltage level at which most of the
devices being studied fall. (On most low voltage industrial
and commercial studies, the reference voltage will be 208,
240, or 480 volts). Devices at other voltage levels will be
shifted by a multiplier based on the transformer turn ratio.
The best reference voltage will require the least amount ofmanipulation. Modern computer programs will automat-
ically make these adjustments when the voltage levels of
devices are identified by the input data.
c. Commencing the Analysis. The starting point can be
determined by the designer. Typically, studies begin with
the main circuit devices and work down through the
feeders and branches. (Right to left on your log-log paper.)
d. Multiple Branches. If many branches are taken off one
feeder, and the branch loads are similar, the largest rated
branch circuit should be checked for coordination with
upstream devices. If the largest branch will coordinate, and
the branch devices are similar, they generally will
coordinate as well. (The designer may wish to verify other
areas of protection on those branches, conductors, etc.)e. Don't Overcrowd the Study. Many computer generated
studies will allow a maximum of ten device characteristics
per page.
f. One-Line Diagram. A one-line diagram of the study
should be drawn for future reference.
-
8/21/2019 Selective Coordination Study
2/9
The following pages will analyze in detail the system
shown in Figure 11. It is understood that a short circuit
study has been completed, and all devices have adequate
interrupting ratings. A Selective Coordination Analysis is the
next step.
Examples of Selective Coordination Studies
15
M
JCN80EIFLA=42A
5.75% Z1000KVA
-Y480/277V
LOW-PEAK
KRP-C-1600SP
Fault X120,000A RMS Sym
Main Switchboard
1
LOW PEAK
LPS-RK-200SPLOW-PEAK
LPS-RK-400SPLOW-PEAK
LPS-RK-225SP
200A Feeder 400A Feeder 150KVA-Y
208/120V2% Z
LOW-PEAK
LPN-RK-500SPLOW-PEAK
LPS-RK-100SP
20A Branch
20A CB
20A CB
LP1
60HP 377A FLA
1600A Main Bus
PDP
13.8KV
Overcurrent Relay
#6 XLP
#3/0 THW
100A Motor Branch
#1 THW
250 kcmil2/ THW
#12 THW
This simple radial system will involve three separate
time current curve studies, applicable to the three feeder/
branches shown.
Figure 11
-
8/21/2019 Selective Coordination Study
3/9
Example
Time Current Curve #1 (TCC1)
16
Device ID Description Comments
1 1000KVA XFMR 12 x FLA
Inrush Point @ .1 Seconds
2 1000KVA XFMR 5.75%Z, liquid
Damage Curves filled
(Footnote 1)
(Footnote 2)
3 JCN 80E E-Rated Fuse
4 #6 Conductor Copper, XLP
Damage Curve Insulation
5 Medium Voltage Needed for XFMR
Relay Primary Overload
Protection
6 KRP-C-1600SP Class L Fuse
11 LPS-RK-200SP Class RK1 Fuse
12 3/0 Conductor Copper THW
Damage Curve Insulation
13 20A CB Thermal Magnetic
Circuit Breaker
14 #12 Conductor Copper THW
Damage Curve Insulation
Footnote 1: Transformer damage curves indicate when it will be damaged,thermally and/or mechanically, under overcurrent conditions.
Transformer impedance, as well as primary and secondaryconnections, and type, al l wil l determine their damagecharacteristics.
Footnote 2: A -Y transformer connection requires a 15% shift, to the right,of the L-L thermal damage curve. This is due to a L-Lsecondary fault condition, which will cause 1.0 p.u. to flowthrough one primary phase, and .866 p.u. through the twofaulted secondary phases. (These currents are p.u. of 3-phasefault current.)
Notes:
1. TCC1 includes the primary fuse, secondary main fuse,
200 ampere feeder fuse, and 20 ampere branch circuit
breaker from LP1.
2. Analysis will begin at the main devices and proceed
down through the system.
3. Reference (base) voltage will be 480 volts, arbitrarily
chosen since most of the devices are at this level.
4. Selective coordination between the feeder and branch
circuit is not attainable for faults above 2500 amperes that
occur on the 20 amp branch circuit, from LP1. Notice the
overlap of the 200 ampere fuse and 20 ampere circuit
breaker.
5. The required minimum ratio of 2:1 is easily met between
the KRP-C-1600SP and the LPS-RK-200SP.
-
8/21/2019 Selective Coordination Study
4/9
Example
Time Current Curve #1 (TCC1)
17
CURRENT IN AMPERES X 10 @ 480V
TIMEIN
SECONDS
FLA
11
2
2
3
5
12
14
13
1
6
#12 DAMAGE
3/0 DAMAGE
20A MCCB
XFMRDAMAGE
4
JCN 80E
MV OLR
1000KVA5.75%Z-Y480/277V
JCN80E
13.8KV
KRP-C-1600SP
LPS-RK-200SP
200AFeeder
#6 XLP
#3/0 THW
OvercurrentRelay
20A CB
#12 THW20A CB
KRP-C-1600SP
TXINRUSH
600
400
300
200
100
80
60
40
30
20
10
8
6
4
3
2
1
.8
.6
.4
.3
.2
.1
.08
.04
.06
.03
.02
.01
800
1000
1 2 3 4 6 810
20
30
40
60
80
100
200
300
400
600
800
1000
2000
3000
4000
6000
8000
10
,000
LPS-RK-200SP
#6 DAMAGE
-
8/21/2019 Selective Coordination Study
5/9
Example
Time Current Curve #2 (TCC2)
18
Notes:
1. TCC2 includes the primary fuse, secondary main fuse,
400 ampere feeder fuse, 100 ampere motor branch fuse,
77 ampere motor and overload relaying.
2. Analysis will begin at the main devices and proceed
down through the system.
3. Reference (base) voltage will be 480 volts, arbitrarily
chosen since most of the devices are at this level.
Device ID Description Comment
1 1000KVA XFMR 12 x FLA
Inrush Point @ .1 seconds
2 1000KVA XFMR 5.75%Z, liquid
Damage Curves filled
(Footnote 1)
(Footnote 2)
3 JCN 80E E-Rated Fuse
4 #6 Conductor Copper, XLP
Damage Curve Insulation
5 Medium Voltage Needed for XFMR
Relay Primary Overload
Protection
6 KRP-C-1600SP Class L Fuse
21 LPS-RK-100SP Class RK1 Fuse
22 Motor Starting Curve Across the Line
Start
23 Motor Overload Relay Class 10
24 Motor Stall Point Part of a Motor
Damage Curve
25 #1 Conductor Copper THW
Damage Curve Insulation
Footnote 1: Transformer damage curves indicate when it will be damaged,thermally and/or mechanically, under overcurrent conditions.
Transformer impedance, as well as primary and secondaryconnections, and type, al l wil l determine their damagecharacteristics.
Footnote 2: A -Y transformer connection requires a 15% shift, to the right,of the L-L thermal damage curve. This is due to a L-Lsecondary fault condition, which will cause 1.0 p.u. to flowthrough one primary phase, and .866 p.u. through the twofaulted secondary phases. (These currents are p.u. of 3-phasefault current.)
-
8/21/2019 Selective Coordination Study
6/9
Example
Time Current Curve #2 (TCC2)
19
KRP-C-1600SP
LPS-RK-400SP
LPS-RK-100SP
60HP
400A Feeder
CURRENT IN AMPERES X 10 @ 480V
TIMEIN
SECOND
S
MV OLR
2
2
3
5
1
6
4
21
2225
23
24
FLA
MS
JCN80EMTR START
LPS-RK-100SP
MTR OLRXFMR DAMAGE
M
#1 THW
TXINRUSH
#6 XLP
13.8KV
OvercurrentRelay
JCN 80E
1000KVA5.75%Z-Y480/277V
600
400
300
200
100
80
60
40
30
20
10
8
6
4
3
2
1
.8
.6
.4
.3
.2
.1
.08
.04
.06
.03
.02
.01
800
1000
1 2 3 4 6 810
20
30
40
60
80
100
200
300
400
600
800
1000
2000
3000
4000
6000
8000
10
,000
KRP-C-1600SP
#1 DAMAGE
#6 DAMAGE
-
8/21/2019 Selective Coordination Study
7/9
Example
Time Current Curve #3 (TCC3)
20
Notes:
1. TCC3 includes the primary fuse, secondary main fuse,
225 ampere feeder/transformer primary and secondary
fuses.
2. Analysis will begin at the main devices and proceed
down through the system.3. Reference (base) voltage will be 480 volts, arbitrarily
chosen since most of the devices are at this level.
4. Relative to the 225 ampere feeder, coordination between
primary and secondary fuses is not attainable, noted by
overlap of curves.
5. Overload and short circuit protection for the 150 KVA
transformer is afforded by the LPS-RK-225SP fuse.
Device ID Description Comment
1 1000KVA XFMR 12 x FLA
Inrush Point @ .1 seconds
2 1000KVA XFMR 5.75%Z, liquid
Damage Curves filled
(Footnote 1)
(Footnote 2)
3 JCN 80E E-Rated Fuse
4 #6 Conductor Copper, XLP
Damage Curve Insulation
5 Medium Voltage Needed for XFMR
Relay Primary Overload
Protection
6 KRP-C-1600SP Class L Fuse
31 LPS-RK-225SP Class RK1 Fuse
32 150 KVA XFMR 12 x FLA
Inrush Point @.1 Seconds
33 150 KVA XFMR 2.00% Dry Type
Damage Curves (Footnote 3)
34 LPN-RK-500SP Class RK1 Fuse
35 2-250kcmil Conductors Copper THW
Damage Curve Insulation
Footnote 1: Transformer damage curves indicate when it will be damaged,thermally and/or mechanically, under overcurrent conditions.
Transformer impedance, as well as primary and secondaryconnections, and type, al l wil l determine their damagecharacteristics.
Footnote 2: A -Y transformer connection requires a 15% shift, to the right,of the L-L thermal damage curve. This is due to a L-Lsecondary fault condition, which will cause 1.0 p.u. to flowthrough one primary phase, and .866 p.u. through the twofaulted secondary phases. (These currents are p.u. of 3-phasefault current.)
Footnote 3: Damage curves for a small KVA (
-
8/21/2019 Selective Coordination Study
8/9
Example
Time Current Curve #3 (TCC3)
21
CURRENT IN AMPERES X 10 @ 480V
600
400
300
200
100
80
60
40
30
20
10
8
6
4
3
2
1
.8
.6
.4
.3
.2
.1
.08
.04
.06
.03
.02
.01
TIMEIN
SECOND
S
800
1000
4
5
2
FLA FLA
MV OLR
XFMR DAMAGE
JCN80E
XFMR DAMAGE 33
35
LPS-RK-225SP
LPN-RK-500SP
KRP-C-1600SP
TXINRUSH
TXINRUSH
132
6
#6 XLP
JCN 80E
13.8KV
OvercurrentRelay
250 kcmil2/ THW
31
34
KRP-C1600SP
23
1000KVA5.75%Z-Y480/277V
150KVA2.0%Z-Y208/120V
1 2 3 4 6 810
20
30
40
60
80
100
200
300
400
600
800
1000
2000
3000
4000
6000
8000
10
,000
LPS-RK-225SP
LPN-RK-500SP
2-250 DAMAGE
#6 DAMAGE
-
8/21/2019 Selective Coordination Study
9/9
Unnecessary power OUTAGES, such as the
BLACKOUTS we so often experience, can be stopped by
isolating a faulted circuit from the remainder of the system
through the proper selection of MODERN CURRENT-
LIMITING FUSES.
Time-Delay type current-limiting fuses can be sizedclose to the load current and still hold motor-starting
currents or other harmless transients, thereby
ELIMINATING nuisance OUTAGES.
The SELECTIVITY GUIDE on page 10 may be used for
an easy check on fuse selectivity regardless of the short-
circuit current levels involved. Where medium and high
voltage primary fuses are involved, the time-current
characteristic curves of the fuses in question should be
plotted on standard NEMA log-log graph paper for proper
study.
The time saved by using the SELECTIVITY GUIDE will
allow the electrical systems designer to pursue other areas
for improved systems design.
Conclusions