sentinel outlets - iosh...2017/09/03 · • sentinel outlets not identified • not measuring hot...
TRANSCRIPT
Sentinel Outlets
the nearest and furthest/last outlets from
hot and cold water cylinders and tanks.
Dead end and dead legs need to be removed
• A dead end- a redundant length of pipe, closed at one end,
through which no water is flowing
• A dead leg - is a pipe leading to an outlet which water flows
but the outlet is un-used or infrequently used.
All need to be removed by cutting them back to the main pipe run
Thermostat mixing valves
• Picture TMVs
these blend hot and cold water to reduce
the temperature where a scald risk is present
Expansion vessels in hot or cold
water systems (not central heating)
• Preferably be flow through
design
• Have a drain valve
– flush through and purge to drain
(HSG274 Pt2 Table 2.1)
• Minimise volume stored
• Should be sited
– in cool areas
– vertically on pipework not
horizontally
Specialised Assisted Baths
• Separate cleaning shower
head system
• Hydro-massage function
• Flexible hoses
• Expansion vessels
• Filters
Other issues to address:
• TMVs should be fitted as close as possible to the point of
use (typically one per outlet);
• Infrequently used outlets should be flushed weekly (includes
short usage and no hot water flowing);
• Shower heads and hoses should be dismantled, cleaned and
descaled or replaced at least quarterly.
• Redundant supply pipework should be cut back as far as
possible to a common supply;
• Replace EPDM (ethylene propylene diene monomer). rubber
hoses with eg. PE (polyethylene), PEX (cross-linked
polyethylene
• Keep water system clean
Monitoring water temperatures for
legionella control
Thermometers needed
Surface temperature probeImmersion temperature probe
Measure the temperature at the hot water tanks
monthly
• hold the surface probe against the pipe
work at the hot water tank outlet
• check the temperature tallies with any
fixed thermometer, if installed.
Measure the temperatures at the sentinel cold water and
hot water outlets monthly
Use the immersion probe to measure the temperature of the
water flowing from the outlet (NB – on hot outlet where TMV is
fitted, this needs to be done on TMV inlet pipe)
•Hot water should measure at least
500C within 1 minute of running
water
• Cold water should measure
less than 200C within 2 minutes
Measure sentinel hot water temperature at inlet to
TMV monthly
Measure at least 500C within 1 minute of running water
Measure the temperatures at the cold water tanks 6
monthly
Incoming water Water in tank
Measure less than 200C
Common failings 1
• No Legionella risk assessment and occupiers are ignorant of the control and monitoring requirements (lack of competence)
• Assessment findings not being implemented
• No schematics or not comprehensive
• Sentinel outlets not identified
• Not measuring hot water temperatures at inlet to TMVs where fitted
• Homes only measure and record hot water temps after tmv’s for scald risk
• Tmv’s fitted too far from outlet
• Not measuring hot water storage temperatures
• Hot water storage thermostats set below 50 degrees C
Common failings 2
• No temperature gauges fitted to hot water outlets and returns (and no one measuring with surface probe)
• Hot water vent pipe overflowing to cold water tank
• Cold water stored above 200C (eg un-insulated cold water tanks located on roofs)
• Cold water tank lids not tight fitting or broken
• Insects screens not fitted to cold water over flows and vents
• Dead legs / ends present
• Infrequently used outlets not flushed weekly
• No cleaning of shower heads
• Evidence that some Water treatment company reports do not reflect the inadequate management, treatment and control of legionella at the homes
When is legionella sampling required?
• Where storage and distribution temperatures are
reduced from those required
• Where an outbreak is suspected or identified
• Where assessment identifies it is necessary to
help monitor effectiveness of controls
Where to sample?
• cold water samples -taken from the cold water tank/s and
furthest outlets
• hot water samples
- the nearest tap to the hot water tank outlet plus the return
to the hot water tank (if re-circulating)
- base of hot water tank and furthest outlet from the tank
When is disinfection needed?
• If required temperatures not being achieved
• System has been substantially altered; or
• During or following an outbreak
Other issues to consider
What is an infrequently used outlet?
What is the impact of green technologies or energy conservation on Legionella control?
How many people are contracting Legionnaires disease from care homes?
RIDDOR does not require non-worker reports of disease to HSE –but requirement to report to HPA
Frequency of Monitoring
Temperatures
Monthly Measure the temperature at the hot and
cold water sentinel outlets and the hot
water tank
Six monthly
Check the temperature at the cold water
storage tank/s (at least once in winter
and once in summer during a hot
period);
Annually Check a representative number of cold
water outlets on a rotational basis
Frequency of water temperature checks
The Frequency of Other Checks
At least weekly Flush infrequently used hot and cold
water outlets
At least 3 monthly Clean and de-scale or replace shower
heads and hoses
At least annually
Visually inspect the cold water storage
tank/s and clean and disinfect as
required
Check the schematic diagram/s of the
H &CW system to ensure they are correct
and up to date (eg addition or removal of
water tanks and outlets)
Note: All checks should be carried out using safe systems and some checks or corrective
actions may need to be done by an external competent person
Frequency of other checks
Further information
HSE H&SC Legionella webpage:
http://www.hse.gov.uk/healthservices/legionella.htm
HSE Legionella H&CWS webpage:
http://www.hse.gov.uk/legionnaires/hot-and-cold.htm
HSE SIM – Control of Legionella in H&CWS http://www.hse.gov.uk/foi/internalops/sims/pub_serv/07-12-07/index.htm
HSE ACOP L8: http://books.hse.gov.uk/hse/public/saleproduct.jsf?catalogueCode=9780717617722
HSE ACOP HSG274 Part 2
http://www.hse.gov.uk/pubns/priced/hsg274part2.pdf
HSE Safety Notice: http://www.hse.gov.uk/safetybulletins/legionella2.htm