series eda electronic pressure controller · 2019. 4. 18. · series eda electronic pressure...
TRANSCRIPT
![Page 1: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/1.jpg)
Series EDA Electronic Pressure ControllerSpecifications - Installation and Operating Instructions
Bulletin IN-EDAW-1
By Dwyer
MERCOID P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
A DIVISION OFDWYER INSTRUMENTS, INC. Phone: 219/879-8000
Fax: 219/872-9057dwyer-inst.come-mail: [email protected]
![Page 2: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/2.jpg)
TABLE OF CONTENTS
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2ModelChart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3InstallationInstructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5 UnpackingandMounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 ElectricalConnections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5OperatingInstructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-18 FrontPanelFunctions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 SetPoints&Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-8 Alternation(Lead/Lag)Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 ProgrammingChart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-11 MainMenuSelections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 MenusandValues . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12-18 SecurityMenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 OperationMenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 OutputMenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14-15 DisplayMenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 AdvancedMenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 TestMenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 FailsafeMenu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17DiagnosticErrorMessages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18WarrantyInformation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
![Page 3: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/3.jpg)
DIMENSIONS
3-3/32˝[78.58]
1 [25.40]1/2 FEMALE
NPT CONDUIT ENTRY
3-1/2 [88.90]
3X 1/8 [3.18]2X 5/16
[7.93]1-59/64 [50.00]
27/32 [21.43]
Ø5[127]
Ø4-15/32[115.90]
9/32 [7.14]1/4 MALE NPTWITH 3/4 [19.05]WRENCHING HEX
1-5/8 [40.88]
1
![Page 4: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/4.jpg)
SPECIFICATIONSService:Compatibleliquidsandgases.Wetted Materials:316LSS.Housing:Polycarbonate.Accuracy:±1%ofF.S.includinglinearity,hysteresis,andrepeatability(indicatorandtransmitter).Stability:<±2%ofF.S.peryear.Pressure Limits:Rangesupto6,000psi:1.5xrange;8,000psirange:10,000psi.Temperature Limits: Ambient:20to140°F(-6.6to60°C);Process:0to176°F(-18to80°C).Compensated Temperature Limits:32to122°F(0to50°C).Thermal Effect:±0.05%ofF.S./°F.Process Connection:1/4˝NPTmale,1/4˝BSPTmale,or7/16”SAE.Display:4-digitbacklitLCD(Digits:0.60˝Hx0.33”W).Display Update: 600ms(dampeningsetto1).Power Requirements:12to28VDC()/AC(~)50/60Hz.(Canworkat8VDC()for45seconds).ForT5option:14to30VDC()/AC(~)50/60Hz.Power Consumption: 2.5watts.Electrical Connections: Removableterminalblockswithtwo1/2˝femaleNPSconduitconnections.Enclosure Rating:Weatherprooftype4XIP65(IP65notevaluatedbyUL).Warm Up Time:<10seconds.Mounting Orientation:Anyposition.Weight:1.18lbs(535g).Installation Category:II(transientover-voltage).Pollution Degree: 2 .Altitude Limit: 6560ft(2000m)max.Environment:Intendedforindoorandoutdooruse.Humidity:0to95%RHupto104°F(40°C)non-condensing,10to50%at140°F(60°C)non-condensing.
SWITCH SPECIFICATIONSSwitch Type:2SPDTrelays.Electrical Rating: 5A@120/240VAC(~)50/60Hz,1A@28VDC().Repeatability:±1%ofFS(switchingonly).Set Points:Adjustable0-100%ofFS.Switch Indication:ExternalLEDforeachrelayonthefrontpanel.Switch Reset:Manualorautomatic.
TRANSMITTER SPECIFICATIONSOutput Signal:4–20mA,1-6VDC(),1-5VDC(),0-5VDC(),or0-10VDC()(directorreverseoutputselection).Minimum Excitation:14VDC().Zero and Span Adjustments:Menuscalablewithintherange.
2
![Page 5: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/5.jpg)
MODEL CHARTExample EDA W N1 E1 01 T0 NIST EDAW-N1E1-01T0-NISTSeries EDA ElectronicpressurecontrollerHousing W WeatherproofProcess Connection N1 1/4˝MaleNPTConduit Connection E1 Two1/2˝NPTRange 01
020304050607080910
010-30INHGVAC020-20PSIG030-60PSIG040-100PSIG050-150PSIG060-300PSIG070-600PSIG080-1000PSIG090-1500PSIG100-3000PSIG
TransmitterOutput
T0T1T2T3T4T5
None4to20mA1to5VDC0to5VDC1to6VDC0to10VDC
Options ATNISTP23444
StainlessSteelTagNISTcertificate1/2NPSMConduitPLugOxygencleaning
DisplayTheEDAhastwodisplays:alowerlargerdisplayandasmallerupperdisplay.TheHomeDisplayisthenormaldisplaywhilethecontrolisinoperationiftherearenoerrorsorfunctionsactive.TheHomedisplaywillindicatetheprocessvariableatthecurrentconditionwiththelowerdisplayandtheselectedpressureunitsfortheprocessvariablewiththeupperdisplay.Whenprogrammingtheunitbothdisplaysarealsoused.TheProgrammingChartinthisinstructionmanualindicateswhatbothdisplaysshowwhileprogrammingtheunit.Forprogrammingdescriptionsinthisinstruc-tionmanualtheformatusedis“lowerdisplay–upperdisplay”.ForexampleCtrl–1SPshowsthatCtrlwouldbeinthelowerdisplayand1SPwouldbeintheupperdisplay.
WhentheuserpressestheEkeytoeditanitem’svaluetheupperdisplaywillflash“EDIT”andthelowerdisplaywillblink.WhentheuserpressestheEkeytothensavetheedittothevaluetheupperdisplaywillflash“SAVE”andthelowerdisplaywillstopblinking.
3
![Page 6: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/6.jpg)
4
1.0 INSTALLATION
1.1 UNPACKINGRemovetheEDAfromtheshippingcartonandinspectfordamage.Ifdamageisfound,notifythecarrierimmediately.
1.2 MOUNTINGTheEDAcanbepipe,panel,orsurfacemounted.Forpipemountingthreadtheunitintoamatingfemalefittingonthepipe.Useawrenchonthe3/4˝hexatthebaseofthehousingtotightentheunittothematingfitting.Donotthreadtheunitinbyforceonthehousing.Forpanelmounting,inserttheunitintothepanelopeningandsecureinplacewiththemachinescrewsandadaptersprovidedwiththeunitasshowninFigure1below.Maximumpanelthicknessis1/8”(3.5mm)withsuppliedscrews.Forsurfacemounting,panelmounttheunitintotheA-EDA-BRKmountingbracket(SeetheDwyercatalogorwebsitefororderingdetails)alsoshowninFigure1.Theunitcanalsobedirectlysurfacemounted,asshowninFigure2,withtheproperpanelcutoutfortheconduitentrances.Supportthepressureconnectionhexwithawrenchifattachingafittingtotheunitinthecaseofpanelorflushmountingsothatthepressureconnectiondoesnottwist.Useasmallamountofplumber’stapeorothersuitablesealantstopreventleaksaroundfitting.
Figure 1: Panel Mounting and Mounting in A-EDA-BRK Bracket
Figure 2: Surface Mounting
EDAW A-EDA-BRK MOUNTING BRACKET
2X 6-20 X 2-1/4 SCREWS
3X 6-19 X 3/8 SCREWS
3X MOUNTING LUG
3X Ø5/32 [3.97]
3-3/32[78.58]
2X R 5/8[15.88]
3X 6-19 X 3/8SCREWS
1-5/8 [41.28]
3-1/2 [88.90]
![Page 7: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/7.jpg)
5
1.3 ELECTRICAL CONNECTIONS
Note: Installationmustbemadeinaccordancewithlocalcodesandregulations.
Electricalconnectionsaremadetotheremovableterminalblocksinsidetheenclosure.Removethetopbackcover,donotremovebottomcover.FeedstrippedandtinnedleadsthroughtheconduitopeningandconnectthemasshowninFigure3.TheEDAprovidestwo1/2˝NPTfemaleportsforconduitconnection.Theconduitconnectionsmustbemadesuchthatcondensationisnotallowedtoenterthesensorhousing.Ifnecessaryinstallaconduitbreatherdraininaseparateconduitbodytopreventbuildupofmoisture.Itisrecommendedthatshieldedtwistedpairwirebeusedforthetransmitteroutputoptionifthepotentialexistsforinterferencefromexternalnoisesources.Whenreplacingtopbackcovertightenscrewsto2±.25in.lbs.
LoadscanbeconnectedtoconnectorsCONN7andCONN8terminalblocksbasedontheControlsettings: •Forsinglesetpointmode(CtrL-1SP),connecttheLoadtoSP1relay(CONN7). •Fortwosetpointsmode(CtrL-2SP),connecttheLoad1toSP1relay(CONN7)and Load2toSP2relay(CONN8). •Forsinglesetpointandalarmmode(CtrL-SPAL),connecttheLoad1toSP1relay (CONN7)andLoad2toALARMrelay(CONN8).WiringAnexternalswitchorcircuitbreakershouldbeaddedtoduringtheinstallationasadisconnectingdevice.TheswitchorcircuitbreakermustmeettherequirementsofIEC60947-1andIEC60947-3,shalldisconnectallcurrentcarryingconductors,andshallnotinterrupttheprotectiveearthground.Thedisconnectingswitchorcircuitbreakermustbemarkedorlabeledwiththesymbols“I”foronand“O”foroff,perIEC60417-5007&IEC60417-5008andshallbemarkedas“DisconnectingDevice”.DonotpositionthePLSinaspacewhereitisdifficulttooperatethedisconnectingdevicethatprovidespower.300V@90°C18AWG/0.75mm2wiringwithPVCorequivalentinsulationwith94-V0orFV-0flammabilityratingisrecommendedfortheswitchoutputsandpower.Terminalblocksratedfor16-22solidorstrandedcopperconductor.6lbinissuggestedtighteningtorque.
Figure 3: Wiring Anexternalpowersupplyof12-28VDC/AC with minimum current capabilityof 200 mA must be used to power theunit. The power supply connection isnotpolaritysensitiveso thepositiveandnegative connections may be made toeitherterminalofCONN9terminalblock.For voltage output option, connect thevoltage receiver (-) to terminal 1 andvoltage receiver (+) to terminal 2 of theCONN10 terminal block. For currentoutputoption,connectthecurrentreceiver(-) to terminal 3 and current receiver(+) to terminal 4 of CONN10 terminalblock. DO NOT APPLY EXTERNALPOWER TO CONN10 TERMINALS -PERMANENTDAMAGENOTCOVEREDBYWARRANTYWILLRESULT.
Asapermanentlyinstalledpieceofequipment,apowerdisconnectswitch,circuitbreaker,orotherapproveddisconnectdevicemustbeinstalledincloseproximitytotheinstalledboardandwithin
easyreachoftheoperator.Thisdisconnectdevicemustincludealabelindicatingitsfunctionasamainsdisconnect.Acircuitbreakerorfusedeviceisrecommended(seeFigure3).
SP1RELAY
5A 250 VAC FOR LOADS USING 120/240 VAC POWER1A 32 VDC FOR LOADS USING 30 VDC POWER
375 mA 250 VAC
LINEINPUT
12 TO 30 VDC/ACPOWER
SP2 OR ALARMRELAY
Explanation of Symbols:
Symbol Publication DescriptionIEC50417-5031 DirectcurrentIEC50417-5032 AlternatingcurrentIEC50417-5019 ProtectiveconductorterminalIEC50417-5007 On(supply)IEC50417-5008 Off(supply)
~
ELECTRIC SHOCK HAZARD. DISCONNECT POWER BEFORE MAKING ELECTRICALCONNECTIONS.Failuretodosowillresultininjuryordeath.
DANGER
TomaintainType4Xratingof theenclosure,1/2NPTconduitfittingsmusthaveaULType4Xoutdoorrating.
NOTICE
EQUIPMENT DAMAGE.DonotallowwiretotouchorpressonPCBAcomponentswhenfishingwirethroughtheconduitconnection.Failuretodosomayresultindamagetothecircuitry.
CAUTION
EQUIPMENT DAMAGE.Donotexceedthespecifiedsupplyvoltagerating.Failuretodosomayresultinpermanentequipmentdamage.
CAUTION
NOTICE
![Page 8: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/8.jpg)
6
Key FunctionsHome Position Function Main Menu Function Item Function
SP/AL
SequencesthedisplaythroughSETPOINTand
ALARMsettingsReturntohomeposition Returntohomeposition
MENUAllowsaccesstomenus Returntohomeposition Returntopreviousmenu
UP ARROW
Sequencesthroughmenus Incrementsavalue
DOWN ARROW
Sequencesthroughmenus Incrementsavalue
ENTERDisplaysfullscalerange
ofunit Enterintoitems
Changesavalueorsetting.PressEnteranddisplaywillblink.AdjustwithUPorDOWNarrows.PressENTERtostore.Display
willstopblinking.
RESET
ClearsorresetsanAlarm(alarmsetformanual
reset)
Peak/Valleyresetsdisplaytopresentvalue.
2. OPERATING INSTRUCTIONS
2.1 FRONT PANEL & KEY FUNCTIONS
Figure 4: Front Panel Functions
![Page 9: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/9.jpg)
7
2.2 SET POINTS & ALARMS
Setting Set Points and Alarms
Set Point Adjustment Adjustingthesetpointsisquickandsimple.Insteadofsettingasetpointanddeadband,simplyadjustSP1H,SetPoint1High,andSP2H,SetPoint2High,forthedesiredrelayturnonpoint,andthenadjustSP1L,SetPoint1Low,andSP2L,SetPoint2Low,forthedesiredrelayturnoffpoint.
Intheabovegraph,aninstrumentwitha100psirangewouldhavetheSP1relayturnONat80psiandOFFat40psi.SP1HsetstherelayturnONpoint,andSP1LsetstherelayturnOFFpoint.
The hot key provides direct access to the Set Point and Alarm settings. The Set Point and Alarm settings that are displayed are based upon the Control (CtrL) menu item.
![Page 10: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/10.jpg)
8
Relay Action
Therelaysoutputsnormallyfunctioninthedirectactingmode,whichmeanstherelaysturnONwithanincreaseinpressure.SP1andSP2maybeconfiguredtoactasreverseactingrelays(refertotheCtrLmenuitem).Whensetforreverseacting,SP1HandSP2HsettherelayturnOFFpoint,andSP1LandSP2LsettherelayturnONpoint.Theabovegraphdemonstratesdirectandreverseactiononprocess(pressure)change.
Alternating (Lead/Lag) OperationTheEDAisdesignedtoeasilyoperateapairofpumpsinanalternatingoperationtominimizepumpwear.Theunithasprogrammableonandoffsetpointsforpumponeandtwo.Ifthelead/lagfeatureisturnedoffthentherelaysremainattachedtotheircorrespondingsetpoints,SP1HandSP1Lcontrolrelay1(pump1)andSP2HandSP2Lcontrolrelay2(pump2).Thereisnoalternatingfunction. Iflead/lagfeatureisturnedonthentherelayswillalternatewithsetpointsSP1HandSP1LtoSP2HandSP2Lwitheverycycleofsetpoints.TheLastrelayturnedoffwillbelastrelayturnedonwiththenextcycle.Onthefirstcycleonincreaseofpressure,assumingdirectacting,theSP1relay(pump1)willcomeonandthenonfurtherincreaseofpressuretheSP2relay(pump2)willcomeon.OnthesubsequentdecreaseofpressuretheSP2relay(pump2)willcomeoffandthentheSP1relay(pump1)willcomeoff.WhenpressureincreasesonthenextcycletherelayusedonthelastcycleforSP2willnowbeusedforSP1,sothatSP1nowcontrolspump2andSP2nowcontrolspump1.EvenifSP2isnotusedonthepressurecycletherelaysstillalternateonnextcycle.
![Page 11: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/11.jpg)
9
2.3 PROGRAMMING CHART
MENU MAP
HOME MAIN MENUS ITEMS SETTINGS
![Page 12: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/12.jpg)
10
HOME MAIN MENUS ITEMS SETTINGS
CONTROL MODESELECTION
ITEMS PRESENTWHEN “CtrL” SETTO “1SP”, “2SP”OR “SPAL”
ITEMS PRESENT WHEN “CtrL” SETTO “2SP”
ITEMS PRESENTWHEN “CtrL” SETTO “SPAL”
![Page 13: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/13.jpg)
11
HOME
SEE PAGE 17.
MAIN MENUS ITEMS SETTINGS
![Page 14: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/14.jpg)
12
2.4 MAIN MENU SELECTIONS
Menu Selections PresstheMENUbuttontostartthemenusothattheupperrightdisplaysreadsMENU.Pressthe▼keytoadvancetothenextmenuitem.Youcanpressthe▲keytogobacktothepreviousmenu.PresstheEkeytoenteramenu.
SECr SecurityMenu Lockoutaccesstosetpointandalarmsettings,orlockoutaccesstoallsettings.
OPEr OperationMenu Selectpressureunits,zerothedisplay,andturnthebacklightonoroff.
Out OutputMenu Selectrelaymodeofoperation,alternatingfunction,timedelay,andlampindication.
diS DisplayMenu Monitorandadjustdisplayrelatedsettings:Peak,ValleyandDampening.
AdU AdvancedFunctionsMenu Modifyadvancedfunctionparameters:transmitteroutputscaling,directorreverseoutputsetting, calibration,orrestoringfactorydefaultcalibration.
tESt TestMenu Simulateinputovertherangewithoutpressuretotestswitchandtransmitteroutputfunction.
FAIL FailsafeMenu Settherelayandtransmitteroutputstocertainpresetvalueswhenfailsafeconditionsoccur.Errorcodes willshowonthedisplayindicatingtheproblem.Userchoosesifrelayisde-energized,energized,orno actiontaken.Withtransmitteroption,userchoosesanoutputof3.6mA,22mA,ornoactiontaken.
Menus and Values
SECr SecurityMenu
SECr Whenthesecurityitemisselected,thepresentsecuritylevelisdisplayedintheupperright hand display.Tochangethesecuritylevel,adjustthenumberdisplayedtothepasswordvalueinthe PasswordTable,shownbelow,bypressingthe▲or▼keyandthenpressingtheEkeyatthedesired securitylevel.
Thepasswordvaluesshowninthetablecannotbealtered,soretainacopyofthesepagesforfuturereference.
Security LevelDisplayed Access
PasswordValue to Enter
12
3
4
AllmenusaccessMenuAccessSP/ALLockedSP/ALAccessMenusLockedAllsettingslocked
1070
90
111
![Page 15: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/15.jpg)
13
OPEr OperationMenu
Unit PressureUnits WiththedisplayreadingUnit-PSI,presstheEkey.Theupperdisplaywillblink.Pressthe▼keyto changeunitthenpressEkeytosavethenewunit.
PSI Poundspersquareinch FS %offullscale OZIN Ouncespersquareinch CMWC Centimetersofwatercolumn MPA Megapascals BAR Bar MBAR Millibar KPA Kilopascals FTWC Feetofwatercolumn KGCM Kilogramspersquarecentimeter MMHG Millimetersofmercury INWC Inchesofwatercolumn INHG Inchesofmercury
Pressure Range vs. Available Units
ZERO AutoZero Note:DONOTapplyanypressurewhenperformingthisfunction.Withthedisplayreadingxx - ZERO, presstheEkey.Theupperdisplaywillblink.PressEagaintozerothedisplay.Thedisplaywillread0.0 ifthezerooffsetislessthan±5%offullscale.
bCLt Backlight ON Backlightalwayson. OFF Backlightalwaysoff. 30 Backlightstaysonfor30minutes. 10 Backlightstaysonfor10minutes. 5 Backlightstaysonfor5minutes. 2 Backlightstaysonfor2minutes.
PSI KG/CM2 BAR INHg FTWC KPA MPA INWC MBAR CMWC MMHg OZ/IN2 % FS-14.7020.0060.0100.0150.0300.060010001500300060008000
-1.0331.4064 .227.0310.5521.0942 .270.3105.5210.9422562
-1.0131 .3794 .146 .8910.3420.6841 .468 .9103.4206.8414551
-29 .9340.7122 .2203.6305.4611122220363054
-33 .9446 .1138 .4230.7346.0692138423073460
-101.4137 .941468910342068
-0.1010.13790.4140.6891.0342.0684 .146 .8910.3420.6841 .455 .1
-407.355416632771
-10131379
-10341406
-76110353105
-235 .2320.096016002400
100100100100100100100100100100100100
![Page 16: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/16.jpg)
14
OUtOutputMenu
CtrL ControlMode 1SP Singlesetpoint. 2SP Twofullyindependentsetpoints. SPAL Singlesetpointandalarm.
1SP SP1,SetPoint1,ReverseorDirectActing DIR Direct.Relayturnsonwithincreasingpressure. REV Reverse.Relayturnsonwithdecreasingpressure.
DEL1 SP1,SetPoint1,TimeDelay Setstheamountoftimeasetpointconditionmustbecontinuouslymetbeforethesetpointcondition isrecognized.TheDEL1delayisadjustablefrom0-60seconds.
LEd1 SP1,SetPoint1,Lamp OFF The SP1LEDonthefrontpanelturnsOFFwhentheSP1relayturnsOFF. The SP1LEDonthefrontpanelturnsONwhentheSP1relayturnsON. ON The SP1LEDonthefrontpanelturnsONwhentheSP1relayturnsOFF. The SP1LEDonthefrontpanelturnsOFFwhentheSP1relayturnsON.
ThefollowingSP2functionvaluesareonlyactivatedwhenCtrLissetto2SP:
2SP SP2,SetPoint2,ReverseorDirectActing DIR Direct.Relayturnsonwithincreasingpressure. REV Reverse.Relayturnsonwithdecreasingpressure.
DEL2 SP2,SetPoint2,timedelay Setstheamountoftimeasetpointconditionmustbecontinuouslymetbeforethesetpointconditionis recognized.TheDEL2delayisadjustablefrom0-60seconds.
LEd2 SP2,SetPoint2,Lamp OFF The SP2LEDonthefrontpanelturnsOFFwhentheSP2relayturnsOFF. The SP2LEDonthefrontpanelturnsONwhentheSP2relayturnsON. ON The SP2LEDonthefrontpanelturnsONwhentheSP2relayturnsOFF. The SP2LEDonthefrontpanelturnsOFFwhentheSP2relayturnsON.
LdL9 RelayAlternation(Seepage8) OFF Thereisnoalternatingfunction. ON RelayswillalternatewithsetpointsSP1H/LandSP2H/Lwitheverycycleofsetpoints.2SP controlmodeonly.
![Page 17: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/17.jpg)
15
ThefollowingalarmfunctionmenuitemsareactivatedwhenCtrLissettoSPAL:
DELA AlarmDelay Setstheamountoftimeanalarmconditionmustbecontinuouslymetbeforethealarmconditionis recognized.Thealarmdelayisadjustablefrom0-60seconds.
LEdA AlarmLamps OFF The ALLOLEDorALHILEDonthefrontpanelturnsOFFwhenthealarmrelayturnsOFF. The ALLOLEDorALHILEDonthefrontpanelturnsONwhenthealarmrelayturnsON. ON The ALLOLEDorALHILEDonthefrontpanelturnsONwhenthealarmrelayturnsOFF.The ALLOLEDorALHILEDonthefrontpanelturnsOFFwhenthealarmrelayturnsON.
AL AlarmType(seeAlarmAdjustmentbelow) HIGH Highalarmonly. LOW Lowalarmonly. HILO Forahighandlowguardbandtypealarm.Sharethesamerelayoutput.
Alarm AdjustmentAlarmsettingsaredependentupontheselectedalarmtype.TheEDApressurecontrolleralarmmaybeconfiguredasaHighAlarm,LowAlarm,orHigh/LowAlarm.Alarmsettingsmaybesettoanywherewithintherangeoftheinstru-ment.Thedeadbandsofthealarmsarefixedat1%offullscale.
ALrE AlarmReset AUTO Automaticreset. HOLD Manualreset.AnalarmisresetbypressingtheRSTkeyonthefrontpanel.
ALiHLowAlarmInhibit OFF Alarminhibitisoff. ON Alarminhibitison.Note: IfALiH isselectedON,a lowalarmcondition issuspendeduponpowerupuntil theprocessvaluepassesthroughthealarmsetpointonce.
![Page 18: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/18.jpg)
16
diS Display Menu
PEAK Peak ThePeakfeaturestoresthehighestpressurereadingtheinstrumenthasmeasuredsincethelastresetor powerup.AtpowerupPEAKisresettothepresentpressurereading.TomanuallyresetthePEAKvalue, presstheRST(RESET)keywhileinPEAK .
VALY Valley TheValleyfeaturestoresthelowestpressurereadingtheinstrumenthasmeasuredsincethelastreset orpowerup.AtpowerupVALYisresettothepresentpressurereading.TomanuallyresettheVALY value,presstheRST(RESET)keywhileinVALY .
DAMP Dampening Adjustfrom1-15.Dampeningstabilizesthedisplayfrominstabilitiesduetothingssuchasvibration andexcessivepressurefluctuations.Thedampeningsettingadjuststheamount ofreadingsthatare averagedforeachdisplayupdate.Adjustthedampeningvalueuntilthedisplayreadsastablevaluefor theapplication.
AdUAdvancedMenu
POL,ProcessOutputLow,andPOH,ProcessOutputHighareusedtoscalethetransmitteroutputforaunitwiththeoutputoptionof4to20mA,0-5VDC,0-10VDC,1-5VDC,or1-6VDC.Belowshowswith4to20mAoutputoption.
POL ProcessOutputLow Settothedesireddisplayreadingforthe4mAoutput.Maybesetfrom2%belowminimumscaleupto POH.
POH ProcessOutputHigh Settothedesireddisplayreadingforthe20mAoutput.MaybesetfromPOLto2%abovemaximum scale.
CAL – ZERO ZeroCalibration DONOTapplyanypressurewhenperformingthisfunction.Withthedisplayreading CAL - ZERO,presstheEkey.Theupperdisplaywillblink.PresstheEkeyagaintocomplete thezeroingoftheinstrumentorpresstheMENUkeytocancel.
CAL – FS Full-scaleCalibration WiththedisplayreadingCAL - FS,applyfull-scalepressuretotheunit,presstheEkey. Theupperdisplaywillblink.PresstheEkeyagaintocompletethecalibrationorpressthe MENUkeytocancel.
trAnsetsthetransmitteroutputoptionfunctionforaunitwiththeoutputoptionof4to20mA,0-5VDC,0-10VDC,1-5VDC,or1-6VDC.Belowshowswith4to20mAoutputoption.
trAn DIR DirectOutput.4mAoutputatzero,20mAoutputatfullscalepressure. REV ReverseOutput.20mAoutputatzero,4mAoutputatfullscalepressure.
CAL - DFLT FactoryDefaultCalibration WiththedisplayreadingCAL - DFLT,presstheEkey.Theupperdisplaywillblink.PressE againtorestoretheoriginalfactorycalibrationvaluesorpresstheMENUkeytocancel.
![Page 19: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/19.jpg)
17
tEStTestMenu
tESt Whenselectedtheunitsimulatesapressureinputovertherangetotesttheprogrammingandoutput function.TostartanautomaticsimulatedcyclingthroughthepressurerangepresstheEkey.Thistest willruncontinuallyuntiltheEkeyispressedagain.Tomanuallyadjustthesimulatedpressure pressthe▲or▼keytoadjustthepressurevalue.ToexittEStpresstheMENUkey.
FAILFailsafeMenu
TheFailsafemenuisusedtosettherelayandtransmitteroutputstocertainpresetvalueswhenfailsafeconditionsoccur.Errorcodeswillshowonthedisplayindicatingtheproblem.SeeDiagnosticErrorMessagesonthenextpage.
rEL RelayOutputFailsafeCondition OPEN Therelayisde-energizeduponfailsafecondition.TheNOcontactswillbeopened,andthe NCcontactswillbeclosed. CLSE Therelayisenergizeduponfailsafecondition.TheNOcontactswillbeclosed,andtheNC contactswillbeopened. NORM Nochangeappliedtotherelayuponfailsafecondition.
OUtPsetsthetransmitteroutputoptionfailsafeconditionforaunitwiththeoutputoptionof4to20mA,0-5VDC,0-10VDC,1-5VDC,or1-6VDC.Seebelowchartoftransmitteroutputactionaccordingtooutputsignaltype.
OUtP TransmitterOutputFailsafeCondition LOW Transmitteroutputgoestolowfailsafecondition. HIGH Transmitteroutputgoestohighfailsafecondition. NORM Nochangeappliedtotransmitteroutputuponfailsafecondition.
FrEs Failsafereset AUTO Automaticreset-Failsafeisresetautomaticallywhenthefailsafeerrorconditionisremoved. HOLD Manualreset-FailsafeisresetwhentheMENUkeyispressed.
Output Signal 4-20 mA 0-5 VDC 0-10 VDC 1–6 VDC 1-5 VDC LOWHIGH
3.6mA22mA
-0.125VDC5.625VDC
-0.250VDC11.250VDC
0.875VDC6.625VDC
0.9VDC5.5VDC
![Page 20: Series EDA Electronic Pressure Controller · 2019. 4. 18. · Series EDA Electronic Pressure Controller Specifications - Installation and Operating Instructions Bulletin IN-EDAW-1](https://reader035.vdocument.in/reader035/viewer/2022071005/5fc242a1f53aa5023f4a8dd5/html5/thumbnails/20.jpg)
©Copyright2019DwyerInstruments,Inc. PrintedinU.S.A.4/19 FR#443725-50Rev.2
18
4. DIAGNOSTIC ERROR MESSAGES
5. MAINTENANCE/REPAIRUponfinalinstallationoftheSeriesEDA,inspectandcleanwithwaterordampclothatregularintervals.TheSeriesEDAisnotfieldserviceableandshouldbereturnedifrepairisneeded(fieldrepairshouldnotbeattemptedandmayvoidwarranty.
Thissymbolindicateswasteelectricalproductsshouldnotbedisposedofwithhouseholdwaste.Pleaserecyclewherefacilitiesexist.CheckwithyourLocalAuthorityorretailerforrecyclingadvice.
6. WARRANTY/RETURNReferto“TermsandConditionsofSales”inourcatalogandonourwebsite.ContactcustomerservicetoreceiveaReturnGoodsAuthorizationnumberbeforeshippingtheproductbackforrepair.Besuretoincludeabriefdescriptionoftheproblemplusanyadditionalapplicationnotes.
Display MeaningErr1
Err2
Err3
Err4
Err5
LowtemperaturelimitAtemperaturebelow0°FhasbeenappliedtothesensorHightemperaturelimitAtemperatureabove180°FhasbeenappliedtothesensorSensorfailureThemicro-controllerisreceivinginvalidsignalfromthesensorOverpressurelimitProofpressurehavebeenexceededKeypadshort
MERCOID P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.
A DIVISION OFDWYER INSTRUMENTS, INC. Phone: 219/879-8000
Fax: 219/872-9057dwyer-inst.come-mail: [email protected]