service and maintenance instructionsicpindexing.toddsit.com/documents/003350/49608800100.pdfservice...

27
496 08 8001 00 2/17/2014 Specifications subject to change without notice. FEM4, FCM4, FSA4, FEA4, FSM4, FSU4, FXM4, FVM4, FMA4, WAH, WAP, WAM, WAX, REM4 SERVICE AND MAINTENANCE INSTRUCTIONS VERTICAL/HORIZONTAL/MULTI POSITION FAN COIL UNITS NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS 1 ........................ INTRODUCTION 1 .................................. FAN COIL DESCRIPTION AND TROUBLESHOOTING 1 .. FSM4P, FSU4P, FSM4X, FSU4X, FSA4X 1 ............ FEM4P, FEM4X, FXM4X, FEA4X, WAHA, WAPM, WAPT, WAPL, WAHM, WAHT, WAHL, WAXM, WAXT, WAXL, REM4P, REM4X 5 .................... FVM4X 6 ......................................... FCM4X 12 ........................................ FMA4P, FMA4X, WAMA WAXA 17 ................... ELECTRIC HEATER FUNCTION AND TROUBLESHOOTING 21 ........................ FEM4, FCM4, FSA4, FEA4, FXM4, FVM4, WAPM, WAPT, WAPL, WAHM, WHAT, WAHL, WAXM, WAXT, WAXL, REM4 21 ............................ FMA4, WAMA, WAXA 21 ............................ CARE AND MAINTENANCE 22 ....................... FEM4P, FEM4X, FCM4X, FXM4X, FVM4X, WAHA, WAPM, WAPT, WAPL, WAHM, WAHT, WAHL, WAXM, WAXT, WAXL, REM4X 22 .................... FSA4X, FEA4X, FMA4P, FMA4X, WAMA, WAXA 23 .... REFRIGERANT FLOWCONTROL DEVICE 24 .......... Thermostatic Expansion Valve (TXV) 24 ............... Piston Body Cleaning and Replacement 25 ............ COIL & CONDENSATE PAN REMOVAL and REPLACEMENT 25 .............................. R410A QUICK REFERENCE GUIDE 27 ............... SAFETY CONSIDERATIONS Improper installation, adjustment, alteration, service, maintenance, or use can cause explosion, fire, electrical shock, or other conditions which may cause death, personal injury or property damage. Consult a qualified installer, service agency, or your distributor or branch for information or assistance. The qualified installer or agency must use factoryauthorized kits or accessories when modifying this product. Refer to the individual instructions packaged with kits or accessories when installing. Follow all safety codes. Wear safety glasses, protective clothing and work gloves. Have a fire extinguisher available. Read these instructions thoroughly and follow all warnings or cautions included in literature and attached to the unit. Consult local building codes and the current editions of the National Electrical Code (NEC) NFPA 70. In Canada, refer to the current editions of the Canadian Electrical Code CSA C22.1. Recognize safety information. This is the safetyalert symbol . When you see this symbol on the unit and in instruction manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safetyalert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation. UNIT OPERATION AND SAFETY HAZARD Failure to follow this caution may result in equipment damage, improper operation or personal injury. When coils are pressurized with nitrogen, open the suction port first to release the nitrogen. Mesh screens may dislodge if the liquid line is opened first. ! CAUTION UNIT OPERATION AND SAFERTY HAZARD Failure to follow this warning could result in personal injury or death. R410A systems operate at higher pressures than R22 systems. Do not use R22 service equipment or components on R410 equipment. Ensure service equipment is rated for R410A. ! WARNING INTRODUCTION These fan coil units are designed for flexibility in a variety of applications that meet upflow, horizontal, or downflow requirements. Units are available in 11/2 through 5 ton nominal cooling capacities. Factoryauthorized, fieldinstalled electric heater packages are available in 5kW @ 240Vac through 30kW @240Vac. ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death. Before installing or servicing unit, always turn off all power to unit. There may be more than one disconnect switch. Turn off accessory heater power if applicable. Lock out and tag switch with a suitable warning label. ! WARNING

Upload: others

Post on 21-Apr-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

496 08 8001 00 2/17/2014Specifications subject to change without notice.

FEM4, FCM4, FSA4, FEA4, FSM4, FSU4, FXM4, FVM4, FMA4,WAH, WAP, WAM, WAX, REM4

SERVICE AND MAINTENANCE INSTRUCTIONSVERTICAL/HORIZONTAL/MULTI−POSITION FAN COIL UNITS

NOTE: Read the entire instruction manual before starting theinstallation.

TABLE OF CONTENTSPAGE

SAFETY CONSIDERATIONS 1. . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION 1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FAN COIL DESCRIPTION AND TROUBLESHOOTING 1. .

FSM4P, FSU4P, FSM4X, FSU4X, FSA4X 1. . . . . . . . . . . .

FEM4P, FEM4X, FXM4X, FEA4X, WAHA, WAPM,WAPT, WAPL, WAHM, WAHT, WAHL, WAXM,WAXT, WAXL, REM4P, REM4X 5. . . . . . . . . . . . . . . . . . . .

FVM4X 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FCM4X 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FMA4P, FMA4X, WAMA WAXA 17. . . . . . . . . . . . . . . . . . .

ELECTRIC HEATER FUNCTION AND TROUBLESHOOTING 21. . . . . . . . . . . . . . . . . . . . . . . .

FEM4, FCM4, FSA4, FEA4, FXM4, FVM4, WAPM,WAPT, WAPL, WAHM, WHAT, WAHL, WAXM,WAXT, WAXL, REM4 21. . . . . . . . . . . . . . . . . . . . . . . . . . . .

FMA4, WAMA, WAXA 21. . . . . . . . . . . . . . . . . . . . . . . . . . . .

CARE AND MAINTENANCE 22. . . . . . . . . . . . . . . . . . . . . . .

FEM4P, FEM4X, FCM4X, FXM4X, FVM4X, WAHA,WAPM, WAPT, WAPL, WAHM, WAHT, WAHL,WAXM, WAXT, WAXL, REM4X 22. . . . . . . . . . . . . . . . . . . .

FSA4X, FEA4X, FMA4P, FMA4X, WAMA, WAXA 23. . . .

REFRIGERANT FLOW−CONTROL DEVICE 24. . . . . . . . . .

Thermostatic Expansion Valve (TXV) 24. . . . . . . . . . . . . . .

Piston Body Cleaning and Replacement 25. . . . . . . . . . . .

COIL & CONDENSATE PAN REMOVAL and REPLACEMENT 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

R−410A QUICK REFERENCE GUIDE 27. . . . . . . . . . . . . . .

SAFETY CONSIDERATIONSImproper installation, adjustment, alteration, service,maintenance, or use can cause explosion, fire, electricalshock, or other conditions which may cause death, personalinjury or property damage. Consult a qualified installer,service agency, or your distributor or branch for information orassistance. The qualified installer or agency must usefactory−authorized kits or accessories when modifying thisproduct. Refer to the individual instructions packaged with kitsor accessories when installing.Follow all safety codes. Wear safety glasses, protectiveclothing and work gloves. Have a fire extinguisher available.Read these instructions thoroughly and follow all warnings orcautions included in literature and attached to the unit.Consult local building codes and the current editions of theNational Electrical Code (NEC) NFPA 70.In Canada, refer to the current editions of the CanadianElectrical Code CSA C22.1.

Recognize safety information. This is the safety−alert symbol

. When you see this symbol on the unit and in instructionmanuals, be alert to the potential for personal injury.Understand the signal words DANGER, WARNING, andCAUTION. These words are used with the safety−alertsymbol. DANGER identifies the most serious hazards whichwill result in severe personal injury or death. WARNINGsignifies hazards which could result in personal injury ordeath. CAUTION is used to identify unsafe practices whichmay result in minor personal injury or product and propertydamage. NOTE is used to highlight suggestions which willresult in enhanced installation, reliability, or operation.

UNIT OPERATION AND SAFETY HAZARD

Failure to follow this caution may result in equipmentdamage, improper operation or personal injury.

When coils are pressurized with nitrogen, open thesuction port first to release the nitrogen. Mesh screensmay dislodge if the liquid line is opened first.

! CAUTION

UNIT OPERATION AND SAFERTY HAZARD

Failure to follow this warning could result in personalinjury or death.

R−410A systems operate at higher pressures than R−22systems. Do not use R−22 service equipment orcomponents on R−410 equipment. Ensure serviceequipment is rated for R−410A.

! WARNING

INTRODUCTIONThese fan coil units are designed for flexibility in a variety ofapplications that meet upflow, horizontal, or downflowrequirements. Units are available in 1−1/2 through 5 tonnominal cooling capacities. Factory−authorized,field−installed electric heater packages are available in 5kW@ 240Vac through 30kW @240Vac.

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personal injuryor death.

Before installing or servicing unit, always turn off all powerto unit. There may be more than one disconnect switch.Turn off accessory heater power if applicable. Lock outand tag switch with a suitable warning label.

! WARNING

Page 2: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

2 496 08 8001 00Specifications subject to change without notice.

FAN COIL DESCRIPTION AND TROUBLESHOOTINGPSC FAN MOTOR

FSM4, FSU4, FSA4The PSC motor is two or three speed direct drive.High−speed lead is black, low−speed lead is red, andcommon lead is yellow. Be sure proper blower speed hasbeen selected..The motor is turned on through two different routes. The firstoccurs when thermostat calls for the fan in cooling, heatpump, or fan−only mode. A 24−Vac signal is sent to relay,causing relay to close its normally open contacts, turning fanon.The second occurs when there is a call for electric heat. A24−Vac signal is sent to heater sequencer/relay, causing it toclose, directing 230V through the normally closed contact offan relay, turning fan on. The fan remains on untilsequencer/relay opens.If motor does not run, test motor for an open winding or awinding shorted to motor case. If either is present, replacemotor.

ELECTRIC HEATER SERVICEService can be completed with heater in place. Shut offpower before servicing.A. Limit SwitchRefer to Electric Heater Function and Troubleshooting sectionof this manual.B. SequencerRefer to Electric Heater Function and Troubleshooting sectionof this manual.C. TransformerA 40−VA transformer supplies 24−V power for control circuit.Check for 208/230V on primary side of transformer. If present,check for 24V on secondary side.NOTE: Transformer is fused. Do not short circuit.D. Fan RelayRelay coil is 24−V. Check for proper control voltage. Replacerelay if faulty.

CLEANING OR REPLACING REFRIGERANTFLOW−CONTROL DEVICERefer to Figure 18 and instructions given in “Piston BodyCleaning or Replacement” section.

The refrigerant flow−control device is protected by a wiremesh strainer. It is located inside the 3/8−in. liquid tube atfield braze joint next to flow−control device. Access to straineris through field braze joint.

SEQUENCE OF OPERATIONA. Condensing UnitCOOLINGWhen thermostat calls for cooling, the circuit between R andG is complete and single−pole single−throw relay FR isenergized. The normally open contacts close causing blowerto operate.The circuit between R and Y is also complete. Thiscompleted circuit causes contactor in outdoor unit to closewhich starts compressor and outdoor fan.HEATINGWhen thermostat calls for heating and FAN switch is set onAUTO, the circuit between R and W is complete. The heatersequence SEQ is energized which closes contacts of relay.

There will be a time delay. This completed circuit energizes allheating elements HTR and blower motor.B. Heat PumpCOOLINGOn a call for cooling, the thermostat makes circuits R−O, R−Y,and R−G. Circuit R−O energizes reversing valve, switching itto cooling position. Circuit R−Y energizes contactor startingoutdoor fan motor and compressor. Circuit R−G energizesindoor unit blower relay starting indoor blower motor.When thermostat is satisfied, its contacts open de−energizingcontactor reversing valve and blower relay. This stopscompressor and fan motors.HEATINGOn a call for heating, the thermostat makes circuits R−Y andR−G. Circuit R−Y energizes contactor starting outdoor fanmotor and compressor. Circuit R−G energizes indoor blowerrelay starting blower motor.Should temperature continue to fall, R−W circuit is madethrough second−stage room thermostat bulb. Circuit R−Wenergizes a sequencer bringing on supplemental electricheat.When thermostat is satisfied, its contacts open de−energizingcontactor and sequencer. All heaters and motors should stop.

Control Board (contact FAST for part number)This section of the service manual describes the PCB byexamining the functional operation of the PCB components.

Printed Circuit Board (PCB) ComponentLayout of the actual PCB is depicted in Figure 1.

1. The low−voltage stripped leads are used to connectthe 24−V side of transformer to indoor thermostat andoutdoor section.

2. A 5−amp fuse is used to protect the low−voltagetransformer secondary.

3. The fan relay is controlled by thermostat and turns fanon and off.

4. A plug is used as the connection for PCB power andelectric heaters. Note the pin numbers on plug.

5. A time−delay relay circuit keeps fan motor running forapproximately 90 seconds after G is de−energized.The time−delay can be defeated by cutting jumperJW1.

Unit FunctionsA. Transformer

1. Proper Wiring of Transformer Primary or High SideYellow wire from Molex plug is wired to C terminal ontransformer and black wire from PCB relay(normally−open) terminal is wired to 208−V or 230−Vterminal on transformer. Units are factory wired at230−V terminal.

2. Proper Wiring of Transformer Secondary or 24−V SideRed wire of transformer is wired to T terminal on PCBand brown wire of transformer is wired to C terminal onPCB.

NOTE: T terminal on PCB is used to protect the transformer.T terminal is connected through the fuse to R terminal onPCB.B. Indoor Fan

1. WiringIndoor fan motor yellow lead is wired to C terminal ontransformer. The red, blue, or black speed lead is wiredto SPT terminal on fan relay part of PCB. Units arefactory wired on medium speed (blue lead connected).

Page 3: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 3Specifications subject to change without notice.

NOTE: Unused fan speed leads must be capped or taped offto prevent direct short to cabinet surface.

2. Functional Controla. Thermostat and Relay Control

When thermostat calls for the fan in cooling, heatpump, heating, or fan−only mode, a 24−Vac signalis sent to relay. This causes the relay to close itsnormally−open contacts, turning on fan. Whenthermostat no longer calls for the fan, the signalsent to relay is turned off and relay opens causingfan to turn off after a 90−second fan−off delay.

b. Sequencer/Electric Heat Relay InterlockThe fan will also operate whenever there is a callfor electric heat, even if fan relay is not energized.This happens because fan is interlocked with firststage of electric heat through the normally−closedcontact of fan relay.

NOTE: The fan interlock is only connected to first stageelectric heat (W2). W3 and E do not contain an interlock withfan. See outdoor thermostat installation instructions whenelectric heat staging is desired.C. Electric HeatWhen thermostat calls for electric heat, a 24−Vac signal issent to sequencer/heat relay through W2, causing first stageto turn on. W3 and E also receive signal if wired in with W2. IfW3 and E are not wired to W2, the sequencers/heat relayscan be controlled individually to stage additional electric heat.The sequence control is described in the following section:

1. W2When thermostat sends a signal to W2, a 24−Vacsignal is applied across sequencer/relay No. 1, causingit to close. When sequencer/relay No. 1 closes, firststage of electric heat is energized. In straight electricheat, fan is also energized through the normally closedcontacts of fan relay. In cooling, heat pump, or manualfan mode, fan will already be running since fan relaywould have been energized. When thermostat stopscalling for electric heat, the 24−Vac signal tosequencer/relay No. 1 turns off and sequencer opensafter a delay of 60 to 90 seconds. Heaters equippedwith relays will be de−energized immediately. Whensequencer/relay opens, first stage of heat turns offalong with fan, providing thermostat is not calling forthe fan.

2. W3When a signal is sent to W3, a 24−Vac signal tosequencer/relay No. 2 causes it to close, with secondstage of electric heat turning on. The 24−Vac signalapplied to sequencer/relay No. 1 causes fan tooperate. Timing is such that sequencer/relay No. 1 willturn on before sequencer/relay No. 2. When signal toW3 is turned off, sequencer/relay No. 2 opens. If W2 isalso satisfied, first stage of electric heat and fan willalso turn off, providing thermostat is not calling for thefan.

3. EWhen thermostat sends a signal to E, a 24−Vac signalis sent to sequencer/relay No. 3. The 24−Vac signalapplied to sequencer/relay No. 3 turns on third stage ofelectric heat. The 24−Vac signal applied tosequencer/relay No. 1 turns on first stage of electricheat and fan. When thermostat stops calling for electricheat, the signal to sequencers/relays 1, 2, and 3 areturned off, and sequencers/relays open. This causeselectric heat to turn off with fan, providing thermostat isnot calling for the fan.

NOTE: Electric heaters are factory wired with all stages tiedtogether. If independent staging is desired, consult outdoorthermostat installation instructions, or corporate thermostatinstructions.

TROUBLESHOOTING THE PRINTED CIRCUIT BOARD

Use wiring schematics shown in Figure 1 as a guide introubleshooting PCB unless otherwise noted.A. If Fan Will Not Turn On from Thermostat:IF THERE IS NO HIGH VOLTAGE TO TRANSFORMER:

1. Check plug/receptacle connection. This supplies powerfrom heaters to PCB Fan Relay. Be sure plug isconnected properly.

2. Check sequencer/relay No. 1 and plug wiring. Yellowwire should be connected to Pin No. 9 of plug and tolimit switch. Black wire should be connected to Pin No.7 of plug and to sequencer/relay No. 1.

3. Check field power leads L1 and L2. If these are notreceiving power, system cannot function.

IF TRANSFORMER HAS HIGH VOLTAGE APPLIED TO IT:1. Check low−voltage transformer leads R (red) and C

(brown). Be sure they are wired to correct locations.2. Check output voltage of transformer secondary side R

(red) and C (brown). Be sure transformer output isbetween 18Vac and 30Vac. If transformer output isincorrect and transformer is receiving correct inputvoltage (208V or 230V), then transformer needs to bereplaced with recommended transformer. If no problemexists with transformer secondary, proceed to items 3and 4.

3. Check low−voltage fuse shown in Figure 1. If fuse isblown, replace it with an identical 5−amp fuse. Thetransformer cannot supply power to board with fuseblown or loose. If fuse blows when unit has powerapplied to it, the system most likely has one of thefollowing problems:a. Check all 24−V wiring for an electrical short.b. The maximum load on transformer is 40 VA. If load

on transformer is excessive, the low−voltage 5−ampfuse will blow to protect transformer. If load exceedsVA rating of transformer, a larger VA ratedtransformer needs to be installed. Checksequencers/relays for excessive current draw.

c. Check wiring of heaters. If a heater is miswired,fuse may blow. If a heater is miswired, correctmiswiring by comparing it to heater wiring label.

4. Check connections on primary side of transformer. Ifthey are not connected properly, the transformersecondary cannot supply the 24−V signal to energizefan relay. If transformer is receiving correct primaryvoltage but is not putting out correct secondary voltage,transformer needs to be replaced.

B. If Electric Heat Stages Will Not Turn On But Fan WillTurn On:

IF THERE IS NO HIGH VOLTAGE TO TRANSFORMER:1. Check plug connection between heaters and board.

This supplies power to transformer and fan. Be sureplug is connected properly.

2. Check sequencer/relay No. 1 and plug wiring. Yellowwire should be connected to Pin No. 9 of plug and tolimit switch. Black wire should be connected to Pin No.7 of plug and to sequencer/relay No. 1.

3. Check incoming high−voltage power leads. If these arenot receiving power, system cannot function.

Page 4: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

4 496 08 8001 00Specifications subject to change without notice.

IF TRANSFORMER HAS VOLTAGE APPLIED TO IT:1. Check low−voltage transformer leads R (red) and C

(brown). Make sure they are wired to correct location.The unit will not function without proper connections.

2. Check output voltage of transformer secondary side R(red) and C (brown). If transformer output is low (lessthan 18Vac), refer to items 3 and 4 of previous “IfTransformer Has High Voltage Applied To It” section.

IF TRACES ARE OVERHEATED ON BACK OF PCB:Usually whenever a trace is blown on PCB, it means eitherthere has been a high−voltage short or high voltage has beenapplied to low−voltage circuit. This can be prevented bymaking sure PCB is wired correctly before PCB has powerapplied to it.C. If Transformer Fuse Keeps Blowing:When low−voltage fuse blows, it means transformer wouldhave blown if fuse had not been in circuit to protect it. Thefuse usually blows when there is a high current draw ontransformer, high voltage applied to low−voltage circuit, or adirect secondary short. When there is a high current draw ontransformer, it is most likely because transformer has beenshorted or system is trying to draw more VA than transformer

rating allows. When fuse blows because of high voltage, thesystem has mixed high− and low−voltage signals.

1. Check wiring of sequencers/relays as shown inFigure 1. Be sure transformer is not shorting outbecause thermostat wires are miswired.

2. Check wiring of relays as shown in Figure 1. Be surelow−voltage and high−voltage wiring is correct.

3. Check VA draw on transformer. If VA draw is more thanVA rating of transformer, fuse will blow. If this is thecase, replace transformer with one that has a higherVA rating and meets system specifications.

D. If Fan Runs Continuously:1. If PCB has no low−voltage power, check blue and

black fan leads. These may be switched atsequencer/relay.

2. If PCB has low−voltage power, check fan relay to see ifit is opening and closing. It may be stuck in thenormally closed position due to debris in relay.

E. Transformer Failure:Check 208−V and 230−V transformer connections. They maybe miswired.

Figure 1 − Fan Coil Printed Circuit Board (contact FAST for part number)

®

®

CP

C-E

94V

-0

LR40061

HS

CI

5 A

MP

CTGR

SP

T

K1

U1

R7R9R10

C8

C7

R2R3C3R6

R11

C4

C6

C5R8

R5R4

Q1

C1C2

F1

JW1

R1Z1

D2

D1

NO

NC

FAN

RE

LAY

C

C

Representative drawing only. Please contact FAST for part number.

A03010

Figure 2 − Electric Heater Control Box

3127

53T-

O-D

60T

X11

HH

19Z

A94

5

C97

25L1

45-5

5F

3127

53T-

O-D

60T

X11

HH

19Z

A94

5

C97

25L1

45-5

5F

SPT

FANRELAY

NO

NC

5 PULL TO OPEN

WARNING

ELECTRIC SHOCKHAZARD

DISCONNECTREMOTE POWERSUPPLY BEFOREOPENING PANEL.

322861-101 REV. A

A13032

Page 5: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 5Specifications subject to change without notice.

FEM4P, FEM4X, FEA4X, FXM4, WAHA, WAPM,WAPT, WAPL, WAHM, WAHT, WAHL, WAXM,

WAXT, WAXL, REM4P, REM4XMULTI−SPEED ECM FAN MOTORThe multi−speed ECM motor used with this product containstwo parts: the control module and the motor winding section.Do not assume the motor or module is defective if it will notstart. Go through the steps described below before replacingcontrol module or entire motor. The control module isavailable as a replacement part.A. It is normal for the motor to rock back and forth on startup.

Do not replace the motor if this is the only problemidentified.

B. If the motor is not running:1. Check for proper high voltage and ground at the L,G,

and N connections at the motor. Correct any voltageissue before proceeding to the next step.

2. The motor is communicated through 24−Vac signals tothe 1,2,3,4,5 and C (common) terminals. Not all tapsare programmed, if low voltage is applied to annon−programmed terminal, the motor will not operate,which is normal. Verify the part number of the motormatches the correct replacement motor part number forthe unit model number.

3. Initiate a demand from the thermostat and check thevoltage between C (common) and terminal 1− 5. Ifvoltage is present and the motor isn’t operating, thenthe motor/control module is failed.

C. Prior to installing the replacement control module, themotor section condition needs to be verified.1. Check to see if the blower wheel spins freely.2. To check for short to ground, use an ohmmeter to

measure the resistance from any one of the motorconnector pins to the aluminum end plate of the motor.This resistance should be greater than 100,000 ohms.

3. Check the motor phase−to−phase resistance betweeneach of the leads in the three−pin motor connector. Thelead−to−lead resistance across any two leads shouldbe less than 20 ohms. Each lead−to−lead resistanceshould be the same within −/+ 10 percent.

4. If any motor fails any of the three tests, do not install anew control module. The new control can fail if placedon a defective motor.

The prior fan coil models with multi−speed ECM blowermotors used a printed circuit board, similar to the PSCmodels. The current fan coils do not use the printed circuitboard and rely on the motor control programming to providethe off−delay timing.Another design aspect of the control board was to provide aresistor in the “G” circuit in case a power stealing thermostatwas used. This resistor is no part of the wiring harness, asshown on wiring diagram. The resistor is a 2−watt, 1500−ohmresistor.If the resistor has failed open, a likely cause is due to thepower stealing thermostat. Connecting C (common) mayresolve the issue. Having an open resistor should not affectthe operation of the motor.Fan Speed SelectionThe fan speed selection is done at the motor connector.Units with or without electric heaters require a minimum CFM.Refer to the unit wiring label to ensure that the fan speedselected is not lower than the minimum fan speed indicated.

To change motor speeds disconnect the BLUE fan lead frommotor connector terminal No. 2 (factory default position) andmove to desired speed-tap; 1, 2, 3, or 5.Speed-taps 1, 2, and 3 have a 90−second blower off timedelay pre-programmed into the motor. Speed-tap 4 is usedfor electric heat only (with 0 second blower time delay) andthe WHITE wire should remain on tap 4. Speed-tap 5 is usedfor high static applications, but has a 0−second blower timedelay pre-programmed into the motor. See AirflowPerformance tables for actual CFM. Also, see Figure 3 formotor speed selection location.NOTE: In low static applications, lower motor speed tapshould be used to reduce possibility of water being blown offcoil.

Tap 1 Low 90 sec off delay

Tap 2 Medium 90 sec off delay

Tap 3 High 90 sec off delay

Tap 4 Electric heat † 0 sec off delay

Tap 5 Max ‡ 0 sec off delay† electric heat airflow is same CFM as Tap 3, except 0 sec off delay‡ high static applications, see airflow tables for max airflow

Figure 3 − Motor Speed Selection

1 2 3 4 5

Speed Taps may be located on motor,or on plug close to motor.

CL

GN

1 2 3 4 5

TWO MOTOR STYLES

A11048

Page 6: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

6 496 08 8001 00Specifications subject to change without notice.

Figure 4 − FVM4 motor/ECM 5.0 Motor

NAMEPLATENAMEPLATELABELLABEL

A13028

FVM4Constant Air FlowUnlike fan coils using induction motors where static pressureaffects airflow, these fan coils are constant airflow units. Theblower delivers requested airflow regardless of staticpressure. Consult fan coil Specification Sheet for staticpressure limits. The ECM 5.0 is pre−programmed andcontains airflow tables for all modes of operation. Blowercharacteristics (requested airflow, torque, and speed) areknown from laboratory testing If any two characteristics areknown, the third is defined.Requested airflow is known from Easy Select Boardconfiguration and thermostat signals. Torque is knownbecause it is directly related to stator current, which ismeasured by motor control. Speed is measured by countingback EMF pulses from stator windings. This information isentered into an expression that calculates torque from speedand airflow numbers. If calculation does not match storedblower characteristics, torque is adjusted until agreement isreached. This calculation and adjustment is performed every0.8 seconds while motor is in operation. There is no directmeasure of static pressure, but unit does react to a change instatic to maintain constant airflow. A change in pressure willresult in a change in stator speed and torque. The motor willbegin to adjust on the next sampling, calculate new desiredspeed and torque, and adjust as necessary.

INTEGRATED CONTROLS AND MOTOR ECM 5.0An ECM 5.0 is fed high voltage AC power through the 5−pinconnector. (See Figure 4.) The AC power is then internallyrectified to DC by a diode module. After rectification, DCsignal is electronically communicated and fed in sequentialorder to three stator windings. The frequency of thesecommutation pulses determines motor speed. The rotor ispermanently magnetized.An ECM 5.0 is powered with high voltage at all times. Themotor will not run with high voltage alone. Low voltage mustbe applied to control plug to run motor.ECM 5.0 Control PowerThe ECM 5.0 control power is supplied from R circuit throughprinted circuit runs to motor control Connector−Pin 8, throughmotor control harness to motor. The C side of low−voltage

control power circuit is connected by printed circuit runs tomotor Connector −Pins 9, 10, and 11 then through motorcontrol harness to motor.Low−Voltage Circuit Fusing and ReferenceThe low−voltage circuit is fused by a board−mounted 5−ampautomotive−type fuse placed in series with transformer SEC2and R circuit. The C circuit of transformer is referenced tochassis ground through a printed circuit run at SEC1connected to metal standoff marked.NOTE: The PCB must be mounted with two screws andmotor ground lead secured to blower housing or erratic motoroperation can result.Transformer, Motor, and Electric Heater PowerConnectionTransformer high voltage supplied from electric heaterpackage or high voltage leads through 12−pin heaterconnector plug2/recp2. The ECM 5.0 power connections aremade at the transformer primary terminals. The transformersecondary connections are made at SEC1 and SEC2connectors.

PCB LAYOUT AND DESCRIPTIONNOTE: Layout of actual PCB is depicted in Figure 5.The Easy Select Board is the interface between the ECMmotor and other system components. The board offerschoices of electric heater size, outdoor unit size and type,comfort or efficiency settings, on and off delay profiles, andcontinuous fan speed. The installer should select the correctsize of components that are being installed in eachinstallation. If no selections are made, the factory defaultsettings are for the largest heater, largest outdoor unit, ACsystem type, nominal airflow adjust, and 0/90 time delay.NOTE: Outdoor unit model should have an AHRI rating withthe variable speed fan coil. Some outdoor unit models will notwork properly with this fan coil.Power for system is supplied from a 230−Vac, 60−Hz line.Class 2 voltage (24 Vac nom.), used for thermostatconnections, is derived from transformer located in closeproximity to PCB. The 24−Vac secondary circuit includes5−amp automotive−type fuse in SEC2 circuit.Connection to heater panel is made through 12−pinconnector PL−1. Connections to thermostat are made at

Page 7: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 7Specifications subject to change without notice.

screw terminals. Twenty−one pin terminals comprise fieldselect taps for motor.Fuse Data: 5−amp automotive−type ATC/ATO (tan) at 32Vac,200 percent current opening time of five seconds maximum.Electrical ConnectionsTwenty−one 0.110−in pin terminals are used to provideprogramming selections for operating modes of ECM 5.0. The6 selection modes are listed below. For additional information,refer to Easy Select Configuration Taps section.AUX Heat Range—(Violet Wire)AC/HP Size—(Blue Wire) Type—(Orange Wire)AC/HP CFM Adjust—(Black Wire)AC/HP Time Delay—(Grey Wire)Continuous Fan—(Yellow Wire)SEQUENCE OF OPERATIONA. Continuous Fan ModeThe thermostat closes circuit R to G. The unit delivers theairflow selected for fan only operation.B. Cooling Mode—Single Speed or Two−Speed High

Thermostat closes circuits R to G, R to Y/Y2 and R to O (heatpump only). A circuit R to Y1 is required for two−speed highoperation. Airflow delivered the airflow selected by AC/HPSIZE selection and CFM ADJUST selection.C. Cooling Mode—Two−Speed LowThermostat closes R to G and R to Y1 and R to O (heat pumponly). Unit delivers two−speed low airflow for AC/HP SIZEand CFM ADJUST selected.D. Cooling + Dehumidify ModeJ1 jumper must be pulled from Easy Select Board. Controlcloses R to G, R to Y/Y2, and R to O (heat pump only) andopen R to DH. Dehumidification is active when 24Vac isremoved from DH terminal. Unit delivers 20 percent lessairflow.E. Super Dehumidify ModeThis mode is only activated when the control closes R toY/Y2, R to O (heat pump only) and opens R to DH and R toG. This signals the fan coil to run at minimum airflow formaximum humidity removal. The control will cycle theequipment 10 minutes on and 10 minutes off until satisfied.

Table 1 – Motor and Modules

Model Size Motor Type Current Blower MotorP/N

Required Control ModuleReplacement Kit Number

FVM4X2400 (Series B) ECM 5.0 1185246 1185326FVM4X3600 (Series B) ECM 5.0 1185247 1185327FVM4X4800 (Series B) ECM 5.0 1185248 1185328FVM4X6000 (Series B) ECM 5.0 1185249 1185329

Figure 5 − Easy Select Board 1185358

YY

WW

X

AU

X/H

EA

T K

W/C

FM

AC

/HP

SIZ

E

AC

/HP

CF

M A

DJU

ST

ON

/OF

F D

ELA

Y

CO

NT

INU

OU

S F

AN

HE

AT

ER

/MO

TO

R

AU

X1

HU

M1

AU

X224V

AC H

UM

2

LOM

ED

HI

YE

L

SY

ST

EM

TY

PE

SE

C1

®

®

EA

SY

SE

LEC

T

SE

C2

J1

5 AM

P.

MA

X.

F1

D4D5D2

D3

D1

R1

R2

HK61EA006

5

STI

J2

YE

LPL1

GR

Y

WH

T

BLK

OR

N

BLU

VIO

0-301075

0-20875

0-10725

0-5625

036030

024018

AC

HP

-CO

MF

OR

TH

P-E

FF

NO

MLO

HI

0903090

00E

NH

DHRW1

W2

Y1

Y/Y

2

GOC

1

Page 8: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

8 496 08 8001 00Specifications subject to change without notice.

Figure 6 − Easy Select Board Schematic

AUX1

SYSTEM DIAGRAM

HEATER/MOTOR

121110987654321

SEC1 SEC2

5 AMP J1

DH

R

W1

W2

Y1

Y/Y2

G

O

C

J2

HUM1

AUX2

HUM2

DIODELOGIC

AUX HEATKW/CFM

AC/HPSIZE

SYSTEMTYPE

AC/HP CFMADJUST

ON/OFFDELAY

CONTINUOUSFAN

GRY

1/4"

1/4"

1/4"

1/4"

1/4"

1/4"

1/4"

A96431

Table 2 – FVM4X Connections and ConnectorsType Connection Type Connector Pin No. Description

Heater Connection 12-Pin

Pin 1 Common to screw terminal GPin 2 Common to screw terminal Y/Y2 through diode D3Pin 3 Common through Y1 through diode D2Pin 4 Common to W2 screw terminalPin 5 Common to W2 screw terminalPin 6 Common to W1 screw terminalPin 7 Common to W1 screw terminalPin 8 R 24VacPin 9 Common to transformer CPin 10 Common to transformer CPin 11 Common to transformer CPin 12 Common to DH screw terminal

Table 3 – Typical Operating ModesOperating Mode Terminals Energized

Heat Pump Only Heating R, Y/Y2, G, DHHeat Pump Only Heating + Super Comfort Heat Mode R, Y/Y2, DH

Heat Pump Heating + Auxiliary Heat (non-staged) R, Y/Y2, G, DH, W2Cooling R, Y/Y2, G, DH, O

Cooling + Dehumidification R, Y/Y2, G, OCooling + Superdehumidification R, Y/Y2, O

F. Heat Pump Heating Mode — Single Speed orTwo−Speed High

Thermostat closes R to Y/Y2 and R to G. A circuit R to Y1 isrequired for two−speed high operation. The unit deliversairflow selected by AC/HP SIZE selection and CFM ADJUSTselection. Selected delay profile is active in this mode.G. Heat Pump Heating Mode — 2−Speed LowThermostat closes R to G and R to Y1. Unit deliverstwo−speed low airflow for AC/HP SIZE and CFM ADJUSTselected. Selected delay profile is active in this mode.H. Non−Staged Auxiliary with Heat Pump Heating ModeThermostat should already have closed R to G, R to Y2 forheat pump heating operation. With J2 jumper in place,energizing either W1 or W2 will produce the W2 airflow. Thisis the greater of heat pump heating and auxiliary heat airflowplus an additional 15 percent. The elected delay profile is notactive in this mode.

I. Staged Auxiliary Heat with Heat Pump Heating ModeThe auxiliary heat can be staged by removing the J2 jumperthat ties W1 and W2 terminals together. Staging can be doneby using outdoor thermostats or by using the heat stagingoption where the indoor control can be configured forthree−stage electric heat. The unit will automatically adjustairflow when the different stages of heat are energized. Theairflow delivered will depend on the heat pump size selectedand electric heat size selected. The greater of the twoairflows will be delivered. The selected delay profile is notactive in this mode.J. Electric Heat without Heat PumpThermostat closes R to W and thermostat should be set up toenergize G with W. This is due to the Super Comfort Heatprogramming in the motor. Energizing W without G will resultin 25% lower airflow delivery. The selected delay profile is notactive in this mode.

Page 9: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 9Specifications subject to change without notice.

EASY SELECT CONFIGURATION TAPSThe Easy Select taps are used by installer to configuresystem. The ECM 5.0 uses selected taps to modify itsoperation to a pre−programmed table of airflows. Airflows arebased on system size and mode of operation and thoseairflows are modified in response to other inputs such as theneed for de−humidification. (See Figure 5.)The FVM4 Fan Coils must be configured to operate properlywith system components with which it is installed. Tosuccessfully configure a basic system (see informationprinted on circuit board located next to select pins), move thesix select wires to pins which match components used, alongwith homeowner preferences.A. Auxiliary Heat RangeThe installer must select the auxiliary heat airflow approvedfor application with kW size heater installed. Each select pinis marked with a range of heaters for which airflow (alsomarked) is approved. For increased comfort select thenarrowest kW range matching the heater size, for example,0−10 for a 10−kW heater. This airflow must be greater thanthe minimum CFM for electric heater application with the sizesystem installed for safe and continuous operation. Note thatairflow marked is the airflow which will be supplied inemergency heat mode and heating mode on air conditionerswhen electric heat is primary heating source. To ensure safeheater operation in heat−pump heating mode, when electricheaters are energized, the ECM 5.0 will run the higher of heatpump airflow and electric heater airflow. The factory defaultselection is largest heater range approved. (See Figure 5.)B. AC/HP SizeThe factory default setting for air conditioner or heat pumpsize is largest unit meant for application with model of fan coilpurchased. The installer needs to select air conditioner orheat pump size to ensure that airflow delivered falls withinproper range for size of unit installed in all operational modes.(See Figure 5.)Unpack unit and move to final location. Remove carton takingcare not to damage unit. Inspect equipment for damage priorto installation. File claim with shipping company if shipment isdamaged or incomplete.Locate unit rating plate which contains proper installationinformation. Check rating plate to be sure unit matches jobspecifications.C. System TypeThe type of system must be selected.

1. AC—air conditioner (approx. 350 CFM/ton)2. HP−COMFORT—provides lower airflow than air

conditioner selection (approximately 315 CFM/ton) inheating mode. In cooling mode supplies 350 CFM/ton.

3. HP−EFF—provides same airflow for heat pump heatingand cooling modes (approximately 350 CFM/ton).

The factory setting is AC. (See Figure 5.)D. AC/HP CFM AdjustSelect low, nominal, or high airflow. The factory selection isNOM. The adjust selections HI/LO will regulate airflowsupplied for cooling and heat pump heating modes only, +15percent and −10 percent respectively. The adjust selectionoptions are provided to adjust airflow supplied to meetindividual installation needs for such things as noise, comfort,and humidity removal. (See Figure 5.)

E. ON/OFF DelayNOTE: ON/OFF Delay is active only in cooling and heatpump only heating modes. In auxiliary heat mode oremergency heat mode, the ON delay is 0 seconds and theOFF delay is fixed and cannot be overridden.

Select desired time delay profile. Four motor−operation delayprofiles are provided to customize and enhance systemoperation. (See Figure 5.) The selection options are:

1. The standard 90−seconds off delay (factory setting0/90).

2. No delay option used for servicing unit or when athermostat is utilized to perform delay functions (0/0).

3. A 30−seconds on/90−seconds off delay profile usedwhen it is desirable to allow system coils time to heatup/cool down prior to airflow. This profile will minimizecold blow in heat pump operation and could enhancesystem efficiency (30/90).

4. ENH, enhanced selection provides a 30−secondson/150−seconds at 70 percent airflow and no off delay.

F. Continuous FanSelect desired continuous−fan profile LO, MED, or HI. Airfloware provided to customize and enhance the continuous fanfunctions. (See Figure 5.) The possible selections are:

1. LO—provides 50 percent of Y/Y2 Cool airflow.2. MED—provides 65 percent of Y/Y2 Cool airflow (71

percent on 5 ton model).3. HI—provides 100 percent of Y/Y2 Cool airflow.

The factory setting is LO.NOTE: If applied to two−speed unit, do not select continuousfan as HI since low speed cooling will also run at HIGH airflowand insufficient dehumidification may result.

G. Easy Select Board JumpersJ1 − This jumper must be pulled to activate dehumidificationmode. The jumper connects R to DH. With the jumper in, theDH terminal is always energized. With the jumper pulled, theDH terminal is de−energized. A thermostat capable of aDEHUM feature must be used to supply the 24−V signalwhen there is no call for dehumidification, and turn off the24−V when there is a call for dehumidfication.J2 − This jumper activates heat staging. The jumper connectsthe W1 and W2 terminals together. If either is energized, W2airflow is delivered. With the jumper pulled, there areseparate airflows for W1 and W2.H. Airflow DeliveryThese units deliver airflow depending on the system sizeselections and operating mode. The thermostat energizes acombination of terminals on the Easy Select Board which tellsthe motor what CFM to deliver. The following are typicaloperating modes and the terminals that should be energizedon the Easy Select Board.NOTE: The DH terminal on the Easy Select Board is fordehumidification. It is de−energized on a call fordehumidification.I. Variable Speed Motor Logic Sequence:The ECM motors in these fan coils are programmed to delivera variety of airflows. The motor goes through:COOLINGThe nominal cooling airflow for these fan coils is 350 CFM perton. Selecting the HI adjust tap increases the airflow to 400CFM per ton. The LO tap decreases airflow to 315 CFM perton. The low adjustment is only active during normal coolingmode. Removing the signal from the DH terminal reduces theairflow to 80 percent of cooling airflow. Removing the G signal

Page 10: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

10 496 08 8001 00Specifications subject to change without notice.

which initiates Superdehumidification and reduces the airflowto 50 percent of cooling.HEATINGThe base heat pump only heating airflow is determined by theSYSTEM TYPE selection on the Easy Select Board. IfHP−EFFICIENCY is selected, the airflow is the same asCooling. IF HP−COMFORT is selected, the airflow is 315CFM per ton. The airflow will adjust up if necessary whenauxiliary heating is required. When both the Y/Y2 and W1 orW2 terminals are energized, the motor will run the higher ofthe heat pump or electric heat airflows. Super Comfort Heatmode is initiated when the indoor control removes the Gsignal from the board. This slows the motor to 75 percent ofheat pump airflow. If the CFM adjust is set to LO, it will deliver67.5 percent of heat pump airflow during Super Comfort Heatmode.

TROUBLESHOOTINGA. Troubleshooting Easy Select Board (FVM4)If Traces Are Overheated on Back of PCB:Usually whenever there is a trace broken on PCB, it meanseither there has been a high−voltage short or high voltagehas been applied to low−voltage circuit. This can beprevented by making sure PCB is wired correctly before fancoil has power applied to it.If PCB Fuse Keeps Blowing:When low−voltage fuse blows, it means transformer wouldhave blown if fuse had not been in circuit to protect it. Thefuse usually blows when there is a high current drawn ontransformer, high voltage applied to low−voltage circuit, or adirect secondary short. When there is a high current drawn ontransformer, it is most likely because transformer has beenshorted or system is trying to draw more Vac than transformerrating allows. When fuse blows because of high voltage, thesystem has mixed high and low−voltage signals.

1. Check transformer and thermostat wiring. (SeeFigure 5.) Be sure transformer is not shorting outbecause thermostat wires are miswired.

2. Check wiring of relays. (See Figure 5.) Be surelow−voltage and high−voltage wiring are connected toproper sequencers.

3. Check VA draw on transformer. If VA draw is more thanVA rating of transformer, fuse will blow. If this is thecase, replace transformer with one that has a higherVA rating.

B. Troubleshooting Common ProblemsAirflow Too Low:Y1 instead of Y/Y2 on single−speed air conditioner or heatpump application. Y1 input is only for two−speed applications.Using this terminal will deliver about 60 percent of full coolingairflow.Wrong Easy Select Board selection. Selecting an outdoor unitor electric heater smaller than actually installed will result inlow airflow for the application.G not energized with call for cooling or heating. This triggersSuper Comfort Heat or SuperDehumidify mode which delivers50 percent of cooling airflow.J1 jumper pulled with no dehumidistat installed. The J1jumper ties the DH terminal to R and is installed at the factory.When pulled, a dehumidistat supplies a 24−V signal to DHwhen there is no call for dehumidification (reverse logic).When there is no signal on DH, the motor reduces airflow to80 percent for better dehumidification.

Airflow Too High:Wrong Easy Select Board selection. Fan coil is factory set forthe largest outdoor unit and largest electric heater. Selectsizes that are actually installed.Continuous fan set too high for two−speed applications. Setto MED or LO.Motor Will Not Stop:The off delay on any W call is one minute and cannot beoverridden.Some power−stealing thermostats could bleed enoughvoltage to cause motor to run slowly when there is no heatingor cooling call. Disconnect thermostat wires and wait twominutes to see if motor stops. If it stops, replace thermostat,or install resistor per thermostat installation instructions.Motor Will Not Start:See following section, “Troubleshooting ECM 5.0 Motor andControlsC. Troubleshooting ECM 5.0 Motor and Controls

ELECTRICAL OPERATIONS HAZARD

Failure to follow this caution may result in equipmentdamage or improper operation.

High voltage is always present at motor. Disconnectpower to unit before removing or replacing connectorsor servicing motor. Wait at least five minutes afterdisconnecting power before opening motor.

CAUTION!

The ECM/ICM motor used with this product contains twoparts: the control module and the motor winding section. Donot assume the motor or module is defective if it will not start.Go through the steps described below before replacingcontrol module, Easy Select Board or entire motor. Thecontrol module is available as a replacement part.D. If Motor Turns Slowly:

1. It is normal operation to run noticeably slower if Gterminal is not energized in cooling or heat pumpheating modes.

2. Attach blower access panel. Motor may appear to runslowly if access panel is removed.

E. If Motor Does Not Run:Turn power off, wait five minutes and check the following:

1. With power turned off, check 5−amp fuse on EasySelect Board.

2. Check all plugs and receptacles for any deformation orcorrosion that could cause bad connections. Be sureplugs are fully seated.

ELECTRICAL OPERATION HAZARD

Failure to follow this caution may result in equipmentdamage or improper operation.

DO NOT remove or apply 5−pin plug on motor withpower on. Arcing could occur, which can damagecontrol module

CAUTION!

Turn power back on and check the following:3. Check for 24Vac on SEC1 and SEC2. If no voltage is

present, check transformer.4. Verify that approximately 230Vac is present at motor.5. Verify low voltage control signals to motor according to

procedure below.

Page 11: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 11Specifications subject to change without notice.

Use following procedure to check low voltage signals:The ECM motor in these fan coils receive low voltage signalsfrom the Easy Select Board through the wiring harnessassembly. The combination of pins energized at the motordetermines the speed the motor will run. The procedurebelow isolates the fan coil from all external devices such as athermostat, condensing unit, humidifier or electronic aircleaner. There is also a specific troubleshooting example todemonstrate the process. Table 7 provides informationneeded to verify that the correct voltages are present at themotor and the Easy Select Board.THERMOSTAT:

1. Remove all thermostat and accessory wires from EasySelect Board.

2. On Easy Select Board, jumper screw terminals (1 at atime): R−G, R−Y/Y2, R−Y1, R−W1, R−W2. If motorruns in all cases, check thermostat outputs. Thermostatwires may be broken, or thermostat may be miswired,configured incorrectly, or defective. If the motor doesnot run, or runs in some cases, but not others, continuethis procedure to check wiring harness and circuitboard.

WIRING HARNESS:1. Remove 16−pin plug from motor.2. Check for appropriate voltages on 16−pin connector

with screw terminals jumpered. (See Table 2.)3. If signals check correctly, and motor does not run,

inspect wiring harness for loose pins or damagedplastic that could cause poor connections.

4. If connections are good, either control module or motoris defective.

5. If proper signals are not present, check circuit boardusing procedure below:

12−PIN PLUG (PL−1) ON Easy Select Board:1. Completely disconnect wire harness from Easy Select

Board.2. Jumper the screw terminals one at a time; R−G,

R−Y/Y2, R−Y1, R−W1, R−W2 and check forappropriate voltages on the Easy Select Board pins. Ifproper signals are not present, replace Easy SelectBoard. If proper signals are present at the pins and notat 16−pin connector to the motor, the wiring harness isdefective.

TROUBLESHOOTING EXAMPLE:Motor is not running on a call for heat pump heating afterjumpering the Easy Select Board screw terminals asdescribed in Thermostat section above.With all thermostat wires removed from Easy Select Board,place a jumper wire between R and Y/Y2 low−voltage screwterminals on the Easy Select Board.

1. Check Table 4 for pin number on 16−pin connectorassociated with the Y/Y2 signal. The correct pin is No.14. The far right column of Table 4 shows that (−)12Vdc should be present between Pin No. 14 and PinNo. 1 (common) on the 16−pin connector.

2. Set meter to read DC voltage. Place meter leadsbetween Pins No. 1 (common) and No. 14 and checkfor (−) 12Vdc. If signal is present, the problem is in themodule or motor. If signal is not present, the problem iseither in wiring harness or Easy Select Board.

These steps can be repeated for other modes of operation.To check Easy Select Board:

1. Leave jumper wire in place between R and Y/Y2.2. Check Table 4 under Volt Meter on Easy Select Board

Plug column and row for Pin No. 14 on motor plug tosee pin number on Easy Select Board that should havevoltage. The correct pin is No. 2. The column on farright will show voltage that should be present betweenPin No. 2 and Pin No. 9 (common).

3. Place meter leads between Pins No. 2 and No. 9 onEasy Select Board and check for (−) 12Vdc.

4. If voltage is present, the wiring harness is bad. If not,the Easy Select Board is bad.

Verify Motor Winding Section:Before proceeding with module replacement, check thefollowing to ensure motor winding section is functional. Withcontrol module removed and unplugged from winding section:

1. The resistance between any two motor leads should besimilar.

2. The resistance between any motor lead and theunpainted motor end plate should be greater than100,000 ohms.

If motor winding fails one of these tests, it is defective andmust be replaced.F. Dehumidify ModeNOTE: Humidistat must open on humidity rise.

Latent capacities for systems using the FVM4 fan coils arebetter than average systems. If increased latent capacity isan application requirement, the field wiring terminal blockprovides connection terminals for use of a standardhumidistat. The FVM4 fan coils will detect the humidistatcontacts opening on increasing humidity and reduce itsairflow to approximately 80 percent of nominal cooling modeairflow. This reduction will increase the system latent capacityuntil the humidity falls to a level which causes the humidistatto close its contacts. When the contacts close, airflow willreturn to 100 percent of the selected cooling airflow. Toactivate this mode, remove jumper J1 and wire in a standardhumidistat. Carefully consult product airflow data for coolingand dehumidification modes.

Table 4 – FVM4 Motor Control Test Values (With 16−pin connector at motor unplugged)Terminals Jumpered

Volt Meter on 16-pin HarnessPlug

Volt Meter on 12-pinEasy Select Board Plug Voltage

+ - + -R to W1 Pin 2 Pin 1 Pin 7 Pin 9 24VacR to W2 Pin 13 Pin 1 Pin 4 Pin 9 24VacR to Y1 Pin 6 Pin 1 Pin 3 Pin 9 (-)12Vdc

R to Y/Y2 Pin 14 Pin 1 Pin 2 Pin 9 (-)12VdcR to G (LO) Pin 15 Pin 1 Pin 3 Pin 9 0Vac

R to G (MED) Pin 6 Pin 1 Pin 3 Pin 9 (-)12VdcR to G (HI) Pin 14 Pin 1 Pin 2 Pin 9 (-)12Vdc

Page 12: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

12 496 08 8001 00Specifications subject to change without notice.

Figure 7 − Humidistat Wiring for De−Humidify Mode

EASY SELECTBOARD TERMINAL

BLOCK

DHJ1

R

HUMIDISTAT

REMOVEJUMPER

A95316

FCM4Model FCM4 fan coil is designed to be installed with theObserver� communicating wall control. The FCM4 fan coilwill provide airflow at a rate commanded by the Observer wallcontrol. The nominal airflow/ton rate is 350 CFM/ton. TheObserver wall control will modify the commanded airflowunder certain operating modes. Refer to the Observer wallcontrol literature for further system control details. This fancoil will not respond to commands from a common thermostatexcept under certain emergency situations explained in thisdocument.

ELECTRONICALLY COMPUTED MOTOR ECM 3.0An ECM 3.0 is fed high voltage AC power through the 5−pinconnector. The AC power is then internally rectified to DC bya diode module. After rectification, DC signal is electronicallycommunicated and fed in sequential order to 3 statorwindings. The frequency of these communication pulsesdetermines motor speed. The rotor is permanentlymagnetized.ECM 3.0 CONTROL POWERThe ECM 3.0 control power is supplied from R circuit throughprinted circuit runs to motor control connector Plug 1, Pin 1,through motor control harness to motor. The C side oflow−voltage control power circuit is connected by printedcircuit runs to motor connector Plug 1, Pin 2 then throughmotor control harness to motor. A digital signal is sent fromPlug 1, Pins 3 and 4 to communicate with the motor includingall airflow requirements.LOW−VOLTAGE CIRCUIT FUSING AND REFERENCEThe low−voltage circuit is fused by a board−mounted 5−ampautomotive type fuse placed in series with transformer SEC2and R circuit. The C circuit of transformer is referenced tochassis ground through a printed circuit run at SEC1connected to metal standoff.NOTE: The PCB must be mounted with two screws andmotor ground lead secured to blower housing or erratic motoroperation can result.TRANSFORMER, MOTOR, AND ELECTRIC HEATERPOWER CONNECTIONTransformer high voltage supplied from electric heaterpackage or high voltage leads through 12−pin heaterconnector plug/recp2. The ECM 3.0 power connections aremade at the transformer primary terminals. The transformersecondary connections are made at SEC1 and SEC2connectors.

TROUBLESHOOTINGNOTE: Always check high and low voltage supply to the fancoil components. Check the integrity of the plug receptacleconnections and fan coil wiring harness prior to assuming acomponent failure.

A. LED Description:LEDs built into fan coil control provide installer or serviceperson information concerning operation and/or faultcondition of the fan coil control and ECM motor. Thisinformation is also available at the Observer wall control intext with basic troubleshooting instructions. Careful use ofinformation displayed will reduce the need for extensivemanual troubleshooting.The amber LED located at bottom center of control adjacentto motor harness plug is Motor Status LED, and it is labeledMOTOR. A second amber LED, located in upper right centerof control adjacent to System Communications connector(DX+, DX−, C, R), is the System Status LED, and it is labeledSTATUS. The green LED labeled COMM is also locatedadjacent to System Communications connector, belowSTATUS LED, and is used as an indicator of systemcommunications status. Status Codes will be displayed onthe STATUS LED using the following protocol:

1. The number of short flashes indicates first digit of code.2. The number of long flashes indicates second digit of

code.3. A short flash is 0.25 seconds on. A long flash is one

second on.4. The time between flashes is 0.25 seconds.5. The time between last short flash and first long flash is

1 second.6. The LED will be off for 2.5 seconds before repeating

code.B. Fan Coil Control Start−Up and System

Communications Troubleshooting:On power up, green COMM LED will be turned off untilsuccessful system communications are established (thisshould happen within 10 seconds). Once communicationswith Observer wall control are successful, COMM LED will belit and held on. At the same time, amber STATUS LED will belit and held continuously on until a request for operating modeis received. The STATUS LED will be on any time fan coil is inidle mode.If, at any time, communications are not successful for aperiod exceeding two minutes, fan coil control will only allowemergency heating or cooling operation using a commonthermostat, a non−communicating outdoor unit and the R, C,Y, O, W outdoor unit terminal strip connections and willdisplay Status Code 16, System Communication Fault, onamber STATUS LED. No further fan coil troubleshootinginformation will be available at Observer wall control untilcommunications are re−established.If COMM LED does not light within proper time period andstatus code is not displayed:

1. Check system transformer high and low voltage to besure the system is powered.

2. Check fuse on fan coil control to be sure it is not blown.If fuse is open, check system wiring before replacing itto be sure a short does not cause a failure ofreplacement fuse.

If COMM LED does not light within proper time period andstatus code is displayed:

Page 13: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 13Specifications subject to change without notice.

Check system wiring to be sure Observer wall control ispowered and connections are made DX+ to DX+, DX− toDX−, etc. and wiring is not shorted. Mis−wiring or shorting ofthe DX+, DX−, C, R communications wiring will not allowsuccessful communications.NOTE: Shorting or mis−wiring low voltage system wiring willnot cause damage to fan coil control or Observer wall controlbut may cause low voltage fuse to open.

C. ECM Motor TroubleshootingThe ECM motor used in this product consists of two parts: thecontrol module and the motor winding section. Do notassume motor or module is defective if it will not start. Use thedesigned−in LED information aids and follow troubleshootingsteps described below before replacing motor control moduleor entire motor. Motor control module is available as areplacement part.

Figure 8 − FCM4 ECM 3.0 Motor

A12231

VERIFY MOTOR WINDING SECTION:

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury or death or possible equipment damage.

After disconnecting power from the ECM motor, wait atleast five minutes before removing the control section.Internal capacitors require time to discharge. Minorinjury from electrical shock may result from early contactwith live metal parts.

! WARNING

Before proceeding to replace a motor control module:1. Check motor winding section to be sure it is functional.2. Remove motor control module section and unplug

winding plug. Motor shaft should turn freely, resistancebetween any two motor leads should be similar andresistance between any motor lead and unpaintedmotor end should exceed 100,000 ohms.

3. Failing any of these tests, entire ECM motor must bereplaced.

4. Passing all of the tests, motor control module alonecan be replaced.

MOTOR TURNS SLOWLY:1. Low static pressure loading of blower while access

panel is removed will cause blower to run slowly.Particularly at low airflow requests. This is normal, donot assume a fault exists.

2. Recheck airflow using Observer wall control servicescreens with access panel in place.

NOTE: Blower motor faults will not cause a lockout of bloweroperation. Fan coil control will attempt to run the blower motoras long as the Observer wall control maintains a demand forairflow. Fan coil control will not operate electric heaters whilea fault condition exists. The fan coil control communicateswith the motor at least once every five seconds, even whenthe motor is idle. If, during operation, the fan coil control doesnot communicate with the motor for more than 25 seconds,the motor will shut itself down and wait for communications tobe reestablished.

D. Using Motor LED in TroubleshootingThe MOTOR LED is connected to the blower motorcommunication line and works with the fan coil controlmicroprocessor and the STATUS LED to provide fan coiloperation and troubleshooting information. When the motor iscommanded to operate, the MOTOR LED will be turned onand will flash each time instructions are sent to the motor.When the motor is commanded to stop, the MOTOR LED willbe turned off.If the MOTOR LED is lit, flashing and the motor is running or ifthe MOTOR LED is off and the motor is stopped, operation isnormal and no motor fault exists.If the MOTOR LED is lit, flashing and the motor does not run,or if the MOTOR LED is off and the motor is running, checkthe STATUS LED for the Status Code. Refer to thetroubleshooting instructions for the indicated Status Code inSection E, Fan Coil Troubleshooting.

Page 14: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

14 496 08 8001 00Specifications subject to change without notice.

E. Fan Coil TroubleshootingFan coil faults indicated by flashing codes on the ambersystem STATUS LED can be resolved using troubleshootinginformation provided below. Codes are listed in order of theirpriority, highest to lowest. Though multiple faults can exist atany time, only the highest priority code will be displayed onSTATUS LED. Clearing the indicated fault when multiplefaults exist will cause the next highest priority Status Code tobe flashed. All existing faults, as well as a fault history, can beviewed at Observer wall control.STATUS CODE 45, CONTROL BOARD TEST FAULT:Fan coil control has failed internal start−up tests and must bereplaced. No other service procedure will correct.STATUS CODE 37, HEATER OUTPUT SENSED ONWHEN NOT ENERGIZED:Fan coil control is provided with circuitry to detect presence ofa 24−Vac signal on Electric Heater stage 1 and stage 2outputs.If fan coil control detects a 24−Vac signal on either heaterstage output and it is not supplying signal, Status Code 37will be displayed on STATUS LED. Fan coil control will turn offoutput and command blower motor to supply an airflowdetermined to be safe for current operation mode with electricheaters energized.To find the fault:

1. Stop all system operations at Observer wall control andcheck heater stage 24−Vac outputs.

2. Disconnect electric heater at plug/receptacle 2 andcheck heater wiring for faults. See Status Code 36 formore information.

STATUS CODE 44, MOTOR COMMUNICATION FAULT:The MOTOR LED is connected to the blower motorcommunication line and works with the fan coil controlmicroprocessor and STATUS LED to provide fan coiloperation and troubleshooting information.When motor is commanded to operate, the MOTOR LED willbe turned on and will flash each time instructions are sent tothe motor.When the motor is commanded to stop, the MOTOR LED willbe turned off. The MOTOR LED will not flash to indicatecommunications when it is turned off.Fan coil control is constantly communicating with the motor,even when the motor and MOTOR LED are off. If motor doesnot acknowledge receipt of communications, the control willdisplay Status Code 44 on STATUS LED and continue to tryto communicate with the motor. If motor acknowledgescommunication, status code will be cleared.If MOTOR LED is lit and flashing and motor does not run:

1. Check the STATUS LED. If STATUS LED is indicating aStatus 44 code, check the motor wiring harness forproper connection to control and motor receptacles.

2. Check motor wiring harness to be sure all wiringcomplies with wiring diagram description, makes acomplete circuit from connector to connector and is notshorted.

3. Check 12−Vdc low−voltage supply to motor at Pins 1(+) and 2 (−) of motor header connection to fan coilcontrol.

If all checks are normal, fan coil control is good and controlmodule on motor may need replacement. Check motor andMotor Control Module following the instructions in Section C.ECM Motor Troubleshooting.

Shorted or mis−wiring of the low voltage motor harness wiringwill not cause damage to fan coil control or to motor controlmodule.If the MOTOR LED is off, STATUS LED is indicating a StatusCode 44 and motor is running:Disconnect the motor harness at the fan coil control. If motorcontinues to run, fan coil control is good and control moduleon motor may need replacementSTATUS CODE 25, INVALID MOTOR / MODELSELECTION:On initial start−up, fan coil control shall poll motor for its sizedata and check fan coil size data stored in fan coil controlmemory.

1. If motor size is incorrect for fan coil size or fan coil sizedata is invalid, Status Code 25 will be displayed onSTATUS LED.

2. If model size data is missing (as is the case when areplacement fan coil control is installed), Observer wallcontrol will prompt installer to enter correct model sizefrom a list of valid sizes.

3. If motor size is incorrect for model size, motor must bereplaced with proper size motor. Fan coil control willnot respond to operation requests until this faultcondition is resolved.

STATUS CODE 27, INVALID OUTDOOR UNIT SIZE:On initial power−up, fan coil control will write into memoryoutdoor unit size as provided by Observer wall control in afully communicating system.

1. If outdoor unit size is invalid, Status Code 27 will bedisplayed on STATUS LED.

2. If model size data is missing (as is the case when areplacement outdoor control is installed), Observer wallcontrol will prompt the installer to choose size from alist of valid sizes for application with fan coil.

3. Check communications wiring to be sure Observer wallcontrol has established communications with outdoorunit or select proper size from valid size list provided atObserver wall control.

4. Check motor and motor control module following theinstructions in Section C. ECM Motor Troubleshooting.

STATUS CODE 26, INVALID HEATER SIZE:On initial power−up, fan coil control will write into memoryelectric heater size as read from heater if heater is providedwith Identifier Resistor (IDR). Heater size must be valid forcombination of indoor and outdoor components installed. Fancoil control will read IDR value connected to Pins 5 and 8 ofheater harness connector. If no resistor is found, Observerwall control will prompt installer to select heater size installedfrom a list of valid heater sizes for fan coil and outdoor unitsize installed.If heater ID resistor value read is invalid, Status Code 26 willbe displayed on STATUS LED.If heater installed is equipped with a resistor connected toPins 5 and 8 of heater harness connector and Status Code26 is displayed on STATUS LED:

1. Check wiring harness connections to be sureconnections are secure.

2. If symptoms persist, disconnect wiring harness at fancoil control heater header and check for a resistancevalue greater than 5000 ohms.

3. Check for proper wiring of resistor assembly.4. Make sure heater size installed is an approved size for

outdoor unit and fan coil sizes installed.

Page 15: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 15Specifications subject to change without notice.

NOTE: Fan coil control will not operate electric heater untilthis Status Code is resolved. If the heater size is set throughthe Observer wall control, the heater will be operated as asingle stage heater. If staging is desired, the IDR value mustbe read in by the fan coil control.

Table 5 – FCM4 self−identifying resistor valuesHeater Size

kWResistor Ohms

NominalNo heater Open

9 11k15 18k20 24k24 33k30 39k

STATUS CODE 36, HEATER OUTPUT NOT SENSEDWHEN ENERGIZED:Fan coil control is provided with circuitry to detect presence ofa 24−Vac signal on Electric Heater stage 1 and stage 2outputs.If fan coil control energizes either heater stage and does notdetect the 24−Vac signal on output, Status Code 36 will bedisplayed on the STATUS LED Fan coil control will continueto energize heater output(s) and adjust blower operation to asafe airflow level for energized electric heat stage(s).To find the fault, check for 24Vac on heater stage outputs.Fan coil control or sensing circuit may be bad.NOTE: It may be useful as an electric heater troubleshootingprocedure to disconnect the system communications to forceStatus Code 16 enabling of emergency heat mode. It isdifficult to know which heater output is energized or notenergized in normal operation. When fan coil is operated inemergency heat mode using electric heaters, both outputsare energized and de−energized together. Terminal stripinputs to control can then be connected R to W to turn onboth electric heat outputs. Heater output sensing circuits canthen be checked to resolve Status Code 36 or 37 problems.

STATUS CODE 41, BLOWER MOTOR FAULT:If MOTOR LED is lit and flashing and motor does not run:

1. Check STATUS LED. If STATUS LED is indicatingStatus Code 41, motor control has detected that themotor will not come up to speed within 30 seconds ofbeing commanded to run or that the motor has beenslowed to below 250 rpm for more than 10 secondsafter coming up to speed. Motor wiring harness and fancoil control are operating properly, do not replace.

2. Check to be sure that the blower wheel is not rubbingthe housing.

3. Check motor to be sure that the motor shaft is notseized (motor control module must be removed andelectronics disconnected from windings to perform thischeck properly).

4. Check motor windings section following instructions inSection C. ECM Motor Troubleshooting.

If all these checks are normal, the motor control module mayneed replacement.STATUS CODE 16, SYSTEM COMMUNICATION FAULT:If, at any time, system communications are not successful fora period exceeding two minutes, the fan coil control will onlyallow emergency heating or cooling operation using acommon thermostat, a non−communicating outdoor unit, andthe R, C, Y, O, W outdoor unit terminal strip connections andwill display Status Code 16 on the amber STATUS LED (see

section E, Emergency Heating and Cooling Modes). Nofurther fan coil troubleshooting information will be available atthe Observer wall control until communications arereestablished.Check system wiring to be sure the Observer wall control ispowered and connections are made DX+ to DX+, DX− toDX− etc. and wiring is not shorted. Mis−wiring or shorting ofthe DX+, DX−, C, R communications wiring will not allowsuccessful communications. Correcting wiring faults will clearthe code and reestablish communications.Shorting or mis−wiring the low voltage system wiring will notcause damage to fan coil control or to Observer wall controlbut may cause the low voltage fuse to open.STATUS CODE 46, BROWNOUT CONDITION:If the secondary voltage of the transformer falls below 15Vacfor a period exceeding four seconds, Status Code 46 will bedisplayed on STATUS LED.If system includes a non−communicating outdoor airconditioner or heat pump, the Observer wall control willcommand the fan coil to turn off Y output controllingcompressor.When secondary voltage rises above 17Vac for more thanfour seconds, the brownout condition is cleared and normalsystem operation will resume subject to any minimumcompressor off delay function which may be in effect.Brownout does not affect blower or electric heater operation.STATUS CODE 53, OUTDOOR AIR TEMPERATURESENSOR FAULT:If an OAT sensor is found at power−up, input is constantlychecked to be within a valid temperature range. If sensor isfound to be open or shorted at any time after initial validation,Status Code 53 will be displayed at amber STATUS LED.Check for faults in wiring connecting sensor to OAT terminals.Using an Ohmmeter, check resistance of thermistor for ashort or open condition.If thermistor is shorted or open, replace it to return the systemto normal operation. If fault is in the wiring connections,correcting the fault will clear the code and return the systemto normal operation.NOTE: If fault condition is an open thermistor or a wiringproblem that appears to be an open thermistor and the powerto the fan coil control is cycled off, the fault code will becleared on the next power−up but the fault will remain andsystem operation will not be as expected. This is because onpower−up, the fan coil control cannot discern the differencebetween an open sensor or if a sensor is not installed.F. Emergency Heating and Cooling ModesFan coil control can provide emergency heating or coolingusing a common heat/cool thermostat in the event that thereare no system communications, fault is in Observer wallcontrol and no replacement is immediately available.To activate these modes, the thermostat and outdoor unitmust be wired as a common heating/cooling system to fancoil control RYWC terminals. Fan coil control must bepowered and displaying Status Code 16, SystemCommunication Fault.NOTE: These emergency modes do not provide the level ofcomfort and efficiency expected by the consumer and shouldonly be activated when Observer wall control cannot bereplaced immediately.

SEQUENCE OF OPERATIONThe FCM4 fan coil is designed for installation with Observercommunicating wall control. This fan coil will not respond tocommands provided by a common thermostat except under

Page 16: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

16 496 08 8001 00Specifications subject to change without notice.

certain emergency situations described in the Start Up andTroubleshooting sub−section.The Observer wall control uses temperature; humidity andother data supplied from indoor and outdoor systemcomponents to control heating or cooling system for optimumcomfort.

ADVANCED TROUBLESHOOTING:Troubleshooting the FCM4 Fan Coil Circuit Board:The circuit board Fan Coil part number 1184554Primary test that should be performed:Motor Line Voltage Check

1. Turn off power (240V).2. Remove Plug 3 from ECM motor3. Turn on power.4. Check Plug 3, terminals 4 and 5, to ensure there are

240V.5. Turn off power.6. Reconnect Plug 3 to motor.

The following troubleshooting techniques will assist indetermining the correct component to replace when the FanCoil Board presents a Fault Code 44 or 41:

1. Disconnect power from the unit (240V).2. Disconnect the DX+, DX−, C, R connector from the

board.3. Disconnect Plug 1 from the board. (See Figure 10.)4. Turn on power (240 volts).5. After reestablishing power, you should receive Fault

Code 44, and the motor LED should be off.6. Place a jumper across the R and G terminals on the

low voltage terminal block7. Fault Code 44 should still be flashing.8. The Motor LED should be flashing, indicating the board

is able to transmit a signal to the motor.9. If Motor LED is not flashing, check to ensure that 24V

is present across R and C on the low voltage terminalblock and that there is a good connection with the Rand G jumper.

10. If 24V is present and the jumper/connections aregood,

11. Replace the board.Check Board

12. If Fault Code 44 and the Motor LED are both flashing,place a DC voltmeter across terminals PL1-1 Red (+)to PL1-2 Green (-). (See Figure 10.)

13. Across terminal PL1−1 and PL1−2, a 12−Vdc shouldbe present. If 12Vdc is not present, replace circuitboard.

14. If Fault Code 44 is flashing and the Motor LED isflashing, place a DC voltmeter across terminal PL1−3(+) and PL1−2 (−).

15. Across terminal PL1−3 (+) and PL1−2 (−), the DC voltmeter should display 5Vdc. The voltage should be verystable and should not fluctuate more than .02Vdc. If thevoltage fluctuates, get a different voltmeter beforeproceeding to the following steps.

16. Reconnect Plug 1 to circuit board and connect DCvoltmeter across terminals PL1−3 Yellow (+) andPL1−2 Green (−). Does the voltage appear to fluctuatemore than in step 15? Typical voltmeters will show afluctuation of .2Vdc to 1Vdc. The amount of fluctuation

is not important. You could see even more fluctuationdepending on the voltmeter used.

Figure 9 − FCM4 Circuit Board LED Locations

SEC 1SEC 2 FUS

E

3AM

P

HE

ATER

STA

TU

S C

OM

M

MOTOR

HP

TOPN

COM

CLS

GW

RC

HU

MY

OD

X+

DX

C

R

A13031

Figure 10 − ECM/Plug Wiring Diagram

17. Check the blower motor serial output signal. Theblinking LED on the control board represents the serialoutput signal. You can measure the signal with a DCvoltmeter by removing Plug 1 from the circuit board andconnecting the DC voltmeter across PL1−4 (+) andPL1−2 (−). The voltage should be near 0Vdc but it willfluctuate briefly several times per second. If you havean analog voltmeter, the needle briefly will go highseveral times per second. If you have a digitalvoltmeter with a bar graph, it will show a large changein magnitude on the bar graph several times persecond. If you have a plain, digital voltmeter, it willshow a brief fluctuation in voltage, and the magnitudemay vary depending on the voltmeter used.

Page 17: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 17Specifications subject to change without notice.

FMA4P, WAMA, FMA4X, WAXA

ELECTRICAL OPERATION HAZARD

Failure to follow this warning could result in personalinjury or death.

Before installation or servicing system, always turn offmain power to system. There may be more than onedisconnect switch. Turn off accessory heater power ifapplicable. Lock out and tag switch with a suitablewarning label.

! WARNING

FAN MOTOR

FMA4P, WAMAThe FMA4P and WAMA motor is three−speed ECM directdrive. High−speed lead is black, medium−speed lead is red,low−speed lead is blue, and common lead is purple. Be sureproper blower speed has been selected.The motor is turned on through two different routes. The firstoccurs when thermostat calls for the fan in cooling, heatpump, or fan−only mode. A 24−Vac signal is sent to relay,causing relay to close its normally open contacts, turning fanon.The second occurs when there is a call for electric heat. A24−Vac signal is sent to heater sequencer/relay, causing it toclose, directing 230V through the normally closed contact offan relay, turning fan on. The fan remains on untilsequencer/relay opens.If motor does not run, test motor for an open winding or awinding shorted to motor case. If either is present, replacemotor.

FMA4X, WAXAThe FMA4X and WAXA motor is five−speed direct drive. Thecooling speed tap is selected by connecting the green wire tothe desired motor tap number indicated on the motor plug.For the electric heat fan speed selection connect the whitewire to the desired motor tap number indicated on the motorplug.The blower motor in this unit has blower−on and blower−offdelays. The blower−on delay is 0−30 seconds and will keepthe motor running after a heating or cooling call ends.If motor does not run, test motor for an open winding or awinding shorted to motor case. If either is present, replacemotor.

ELECTRIC HEATER SERVICEService can be completed with heater in place. Shut offpower before servicing.A. Limit SwitchRefer to Electric Heater Kit Function and Troubleshootingsection of this manual.B. SequencerRefer to Electric Heater Kit Function and Troubleshootingsection of this manual.C. TransformerA 40−VA transformer supplies 24−V power for control circuit.Check for 208/230V on primary side of transformer. If present,check for 24V on secondary side.NOTE: Transformer is fused. Do not short circuit.

D. Fan RelayRelay coil is 24−V. Check for proper control voltage. Replacerelay if faulty.

CLEANING OR REPLACING REFRIGERANTFLOW−CONTROL DEVICE

FMA4P, WAMAThe FMA4P and WAMA piston can be removed and cleanedif believed to be plugged. This unit’s piston is unique andreplacements are available from FAST.The filter drier should be located on the liquid line at theindoor unit to prevent particulate from plugging the piston.

FMA4X, WAXAThe FMA4X and WAXA fan coils use an R−410A TXV. TheTXV’s are preset at the factory and do not need adjustmentfor reliable operation. Reference the outdoor unit instructionsto properly charge the unit to the correct subcooling. Foroptimal performance, adjust the TXV so that 6º F ofsuperheat is measured at the outdoor unit’s vapor servicevalve when the indoor return air is 80º F DB/67º F WB andoutdoor ambient is 82º F DB. To increase superheat turn theTXV adjustment stem clockwise no more than one rotation ata time. After an adjustment is made, wait until the superheattemperature has been stable for 15 minutes before makingfurther adjustments.

SEQUENCE OF OPERATIONA. Condensing UnitCOOLINGWhen thermostat calls for cooling, the circuit between R andG is complete and single−pole single−throw relay FR isenergized. The normally open contacts close causing blowerto operate.The circuit between R and Y is also complete. Thiscompleted circuit causes contactor in outdoor unit to closewhich starts compressor and outdoor fan.HEATINGWhen thermostat calls for heating and FAN switch is set onAUTO, the circuit between R and W is complete. The heatersequence SEQ is energized which closes contacts of relay.There will be a time delay. This completed circuit energizes allheating elements HTR and blower motor.B. Heat PumpCOOLINGOn a call for cooling, the thermostat makes circuits R−O, R−Y,and R−G. Circuit R−O energizes reversing valve, switching itto cooling position. Circuit R−Y energizes contactor startingoutdoor fan motor and compressor. Circuit R−G energizesindoor unit blower relay starting indoor blower motor.When thermostat is satisfied, its contacts open de−energizingcontactor reversing valve and blower relay. This stopscompressor and fan motors.HEATINGOn a call for heating, the thermostat makes circuits R−Y andR−G. Circuit R−Y energizes contactor starting outdoor fanmotor and compressor. Circuit R−G energizes indoor blowerrelay starting blower motor.Should temperature continue to fall, R−W circuit is madethrough second−stage room thermostat bulb. Circuit R−Wenergizes a sequencer bringing on supplemental electricheat.When thermostat is satisfied, its contacts open de−energizingcontactor and sequencer. All heaters and motors should stop.

Page 18: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

18 496 08 8001 00Specifications subject to change without notice.

Figure 11 − FMA4, WAMA, WAXA (sizes 18 & 24) Expanded View− Case

18K & 24K Case

A13135B

Figure 12 − FMA4, WAMA, WAXA (sizes 18 & 24) Expanded View− Duct Components, Blower & Electrical Parts

A13136

Page 19: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 19Specifications subject to change without notice.

Figure 13 − FMA4, WAMA, WAXA (sizes 18 & 24) Expanded View− Evaporator Parts & Drain Pan

(FMA4X & WAXA use TXV, not shown)

A13137B

Figure 14 − FMA4, WAMA, WAXA (sizes 30 & 36) Expanded View− Case

A13138B

Page 20: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

20 496 08 8001 00Specifications subject to change without notice.

Figure 15 − FMA4, WAMA, WAXA (sizes 30 & 36) Expanded View− Duct Components, Blower & Electrical Parts

A13139

Figure 16 − FMA4, WAMA, WAXA (sizes 30 & 36) Expanded View− Evaporator Parts & Drain Pan

A13140

Page 21: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 21Specifications subject to change without notice.

ELECTRIC HEATER FUNCTION ANDTROUBLESHOOTING

FEM4, FCM4, FSA4, FEA4, FXM4, FVM4,WAPM, WAPT, WAPL, WAHM, WAHT, WAHL,

WAXM, WAXT, WAXL, REM4This section describes EHK and EHC series electric heatersby examining the functional operation of these heaters.

DESCRIPTION OF ELECTRIC HEATER COMPONENTSA. Limit SwitchThe limit switch is a temperature sensitive control whosefunction is to prevent system from overheating in abnormalconditions. The temperature settings often vary from heater toheater due to variations in airflow patterns and elementradiant heat conditions.The devices are sized to remain on−line under heat pumpconditions (115� air off coil) and minimum CFM, but trip toprevent outlet air conditions above 200� F or excessivecomponent or duct temperatures.The device itself consists of a bimetallic disc, which whenoverheated ”snaps through” to open a normally closedhigh−voltage, high−current switch. When systemtemperatures cool sufficiently, the switch will automaticallyreset to its closed position. Normal failure mode for this switchis open.If a limit switch has been determined to be defective, NEVERBYPASS THE LIMIT SWITCH. When replacing limit switch,ensure that it is replaced with a limit switch of identicalopening temperature and closing differential. Limit switchesare typically color coded to identify their range.B. EHK and EHC Electric Heat RelayEHK and EHC electric heater packages have relayscontrolling the heater elements instead of sequencers. Asmall rectifier PCB is mounted to each relay which convertsthe incoming 24−Vac control signal to DC.In addition to the rectifier circuit, the second and third stagerelays contain a time−on delay circuit of five seconds forsecond stage, and eight seconds for third stage. When thecontrol signal is removed from the relays, all relays will openwith no time−off delay.

TROUBLESHOOTING EHK and EHCSERIES ELECTRIC HEATERS

A. Discolored Wire Insulation at TerminalCheck quick−connect terminal at discoloration. Connectionmay be loose, creating a high resistance through connectionpoint.B. Fuse Failure

1. Check for shorted wire. Replace wire. Never try to fixwire using electrical tape.

2. Check shorted element. If element is shorted, replaceheater.

C. No Heat1. Check fuse for failure. If fuse has failed, refer to Fuse

Failure section.2. Check for faulty transformer. Check output voltage of

transformer secondary side R (red) and C (brown).Make sure output is between 18Vac and 30Vac. Ifoutput voltage is low and input voltage tests normal,replace transformer.

3. Check for miswired heater plug harness.4. Check limit switch or sequencer failure. These switches

should have failed in open position. If output voltage iszero volts, replace switch.

5. Check heater relay and PCB (EHK and EHC heatersonly). Control voltage input to PCB should be 24Vac.Output to relay should be 18−Vdc minimum. If input ispresent but no output, replace PCB. If output ispresent, replace relay.

D. Heater Will Not Turn Off1. Check low−voltage wiring for miswire.2. Check for shorted elements to ground.3. Replace sequencer/relays. They may be stuck closed.

E. Nuisance Trips1. Check for low airflow due to dirty filters, blocked

registers, or undersized duct.2. Check blower motor and wheel for proper operation.

Excessive current draw of motor will cause internaloverload to trip.

3. The fan speed may be low.

FMA4, WAMA, WAXAThis section describes EHK2 series electric heaters byexamining functional operation of this heater.Service can be completed with heater in place. Shut offpower before servicing.

DESCRIPTION OF ELECTRIC HEATER COMPONENTS

A. Limit SwitchThe limit switch is a temperature sensitive control that’sfunction is to prevent system from overheating in abnormalconditions. The temperature settings often vary from heater toheater due to variations in airflow patterns and elementradiant heat conditions.The devices are sized to remain on-line under heat pumpconditions (115� F air off coil) and minimum CFM, but trip toprevent outlet air conditions above 200� F or excessivecomponent or duct temperatures. The device itself consistsof a bimetallic disc, which when overheated “snaps through”to open a normally closed high-voltage, high-current switch.When system temperatures cool sufficiently, the switch willautomatically reset to its closed position. Normal failure modefor this switch is open.If a limit switch has been determined to be defective, NEVERBYPASS THE LIMIT SWITCH. When replacing limit switch,ensure that it is replaced with a limit switch of identicalopening temperature and closing differential. Contact FASTfor replacement part. Limits switches are typicallycolor−coded to identify their range.B. SequencerThe sequencer is essentially a thermally−activated time-delayrelay normally activated by low-voltage control signals fromthermostat. The typical sequencer is a 1- or 2−pole normallyopen device which energizes within 30 to 70 seconds afterapplication of control signal and de−energizes 60 to 90seconds after control signal is removed.In simplistic terms, the sequencers which we use are nothingmore than normally open limit switches which sit on top of asmall resistive heater. When voltage is applied to this heater,a positive temperature coefficient resistor (PTC), heat issupplied to a bimetallic disc which “snaps through” andcloses switch.The time required for PTC to heat to a sufficient point controlsON timing of device. The time required for disc to cool downwhen power is removed controls OFF time of device. ThePTC can be varied to provide varied timing. Typically a shortON equates to a long OFF.Because this is a thermally−activated device, ambientconditions affect the ON/OFF cycle. Higher ambienttemperature means shorter ON times and longer OFF times.

Page 22: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

22 496 08 8001 00Specifications subject to change without notice.

Application of these devices is such that the first switch ONnot only turns on first heater element, but also ensures thatindoor fan is energized, because first ON is last OFF. Thisensures fan remains ON until the last heater de-energizes.

CARE AND MAINTENANCEFEM4, FCM4, FXM4, FVM4, WAP, WAH,

WAX, REM4To continue high performance, and minimize possibleequipment failure, it is essential periodic maintenance beperformed on this equipment.The ability to properly perform maintenance on thisequipment requires certain mechanical skills and tools. Theonly consumer service recommended or required is filtermaintenance. (See Filter Assembly.)

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury or death.

Disconnect all power to the unit before servicing the fieldwires or removing the control package. The disconnect(when used) on the access panel does not disconnectpower to the line side of the disconnect, but does allowsafe service to all other parts of the unit.

! WARNING

The minimum maintenance requirements for this equipmentare as follows:

1. Inspect and clean or replace air filter each month or asrequired.

2. Inspect cooling coil, drain pan, and condensate draineach cooling season for cleanliness. Clean asnecessary.

3. Inspect blower motor and wheel for cleanliness eachheating and cooling season. Clean as necessary.

4. Inspect electrical connections for tightness andcontrols for proper operation each heating and coolingseason. Service as necessary.

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Usecare and wear appropriate protective clothing and gloveswhen handling parts.

CAUTION!

FILTER ASSEMBLYTo clean or replace air filter, push plastic connectors towardcenter of unit and remove filter access panel outward. Pushfilter up and back into unit. Then slide filter out.Clean filter by using cold water and mild detergent. Rinse andallow filter to dry. No oiling or coating of filter is required.New filters are available from your local distributor. Place filterin slot with cross−mesh binding up or facing cooling coil andreplace filter access panel.

COOLING COIL, DRAIN PAN, AND CONDENSATE DRAINThe cooling coil is easily cleaned when it is dry. Inspect thecoil and clean (if necessary) before each cooling season. Tocheck or clean cooling coil, remove coil access panel. If coil

is coated with dirt or lint, vacuum it with a soft brushattachment.Be careful not to bend coil fins. If coil is coated with oil orgrease, clean it with a mild detergent and water solution.Rinse coil thoroughly with clear water. Be careful not tosplash water on insulation.Inspect drain pan and condensate drain at the same timecooling coil is checked. Clean drain pan and condensatedrain by removing any foreign matter from pan. Flush panand drain tube with clear water.If drain tube is restricted, it can generally be cleared byhigh−pressure water. Cut plastic line and work outsidecondensate pan and away from coil to clean drain tube.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipmentdamage.

Do not use caustic household drain cleaners in thecondensate pan or near the coil. Drain cleaners canquickly destroy a coil.

CAUTION!

BLOWER MOTOR AND WHEEL

Clean blower motor and wheel when cooling coil is cleaned.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personalinjury or death.

Disconnect electrical power before removing anyaccess panels. Lock out and tag switch with a suitablewarning label.

! WARNING

To clean blower motor or blower wheel:1. Remove blower access panel.2. Remove motor leads from fan coil control. Note lead

location for ease of reassembly.3. Remove the two outside screws holding blower/motor

assembly against blower deck flange and slideassembly out of cabinet.

4. (If applicable) Remove screw in strap holding motorcapacitor to blower housing and slide capacitor outfrom under strap. Remove screw with green wire fromblower housing. Mark blower wheel, motor, and motorsupport in relation to blower housing beforedisassembly to ensure proper reassembly. Noteposition of blades on wheel.

5. Loosen setscrew holding blower wheel onto motorshaft.

6. Remove the three bolts holding motor mount to blowerhousing and slide motor and mount out of housing.Further disassembly should not be necessary asadequate clearance is available.

7. Remove blower wheel from housing by removing cutoffplate from blower housing outlet. Note wheelorientation and cutoff location for reassembly. Theblower motor and wheel may be cleaned by using avacuum with a soft brush attachment.

8. Remove grease with a mild solvent such as hot waterand detergent. Be careful not to disturb balance

Page 23: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 23Specifications subject to change without notice.

weights (clips) on blower−wheel vanes. Also, do notdrop or bend wheel, as balance will be affected.

To reassemble blower:1. Place blower wheel back into housing. Be sure to

position correctly for proper location.2. Reassemble cutoff plate to housing using identified

holes from disassembly procedure.3. Position motor and mount in same position as when

blower housing was in unit. Secure motor mount onhousing, using removed bolts. Make sure mount ormotor is grounded to blower housing.

4. Locate blower wheel setscrew over flat on motor shaft.Rotate wheel in housing. It should not rub housing andshould be centered in inlet opening. If not, loosensetscrew and align as necessary.

5. Attach green wire to blower housing with screw.6. (If applicable). Secure motor capacitor under strap and

tighten strap screw.7. Slide blower assembly to blower deck. Be sure (once

blower is within the unit casing) to force blowerassembly toward control box while sliding assemblyinto unit to ensure that blower assembly engages deckproperly.

8. Fasten blower assembly to deck with screwspreviously removed.

9. Reconnect electrical leads to fan coil control.10. Reconnect electrical power to unit and test fan for

proper rotation.

FSA4, FEA4, FMA4, WAMA, WAXAThe minimum maintenance requirements for this equipmentare as follows:

1. Inspect and clean or replace air filter each month or asrequired.

2. Inspect cooling coil, drain pan, and condensate draineach cooling season for cleanliness. Clean asnecessary.

3. Inspect blower motor and wheel for cleanliness eachheating and cooling season. Clean as necessary.

4. Inspect electrical connections for tightness andcontrols for proper operation each heating and coolingseason. Service as necessary.

CUT HAZARD

Failure to follow this caution may result in personal injury.

Sheet metal parts may have sharp edges or burrs. Usecare and wear appropriate protective clothing and gloveswhen handling parts.

CAUTION!

A. Air FilterThe air filter should be replaced as needed.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipmentdamage.

Never operate unit without a filter.

CAUTION!

B. Cooling Coil, Drain Pan, and Condensate DrainThe cooling coil is easily cleaned when it is dry. Inspect coiland clean (if necessary) before each cooling season. Tocheck or clean cooling coil, remove blower/heater accesspanel to gain full access to cooling coil. If coil is coated withdirt or lint, vacuum with a soft brush attachment.Be careful not to bend coil fins. If coil is coated with oil orgrease, clean it with a mild detergent and water solution.Rinse coil with clear water.Be careful not to splash water onto insulation.Inspect drain pan and condensate drain at same time coolingcoil is checked. Clean drain pan and condensate drain byremoving any foreign matter from pan. Flush pan and draintube with clear water.If drain tube is restricted, it can generally be cleared byhigh−pressure water. Cut plastic line and work outsidecondensate pan and away from coil to clear drain tube.NOTE: There MUST be a trap in condensate line. Trap mustbe at least 3−in. deep, not higher than the bottom of unitcondensate drain opening, and pitched downward to an opendrain or sump.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipmentdamage.

Do not use caustic household drain cleaners in thecondensate pan or near the coil. Drain cleaners canquickly destroy a coil.

CAUTION!

C. Blower Motor and WheelClean blower motor and wheel when cooling coil is cleaned.To clean or service wheel or motor, proceed as follows:

1. Pull unit disconnect (when used) and remove bloweraccess panel.

2. Disconnect motor electrical leads from control box andcapacitor. Mark location of wires for reassembly.

3. Remove the three bolts holding motor mount to blowerhousing while supporting motor shell with hand.

4. Pull motor inlet ring and blower wheel assembly out ofblower housing.

5. With blower wheel, inlet ring, and motor mount stillattached to motor, place motor on flat, horizontalsurface, shaft up. Mark position of wheel on motor shaftfor reassembly.

6. Loosen blower wheel setscrew and remove blowerwheel from motor shaft.

NOTE: Further disassembly of motor and mount is notnecessary as adequate clearance is available to clean motor.

7. Clean blower motor and wheel using a vacuum with asoft brush attachment. Remove grease with a mildsolvent such as hot water and detergent. Be careful notto disturb balance weights (clips) on blower wheelvanes. Do not drop or bend wheel as balance will beaffected.

To reassemble unit, proceed as follows:1. Place motor with mount attached on flat, horizontal

surface with shaft up.2. Set inlet ring on top of motor mount grommets. Center

inlet ring flush on all three grommets.3. Slide blower wheel onto motor shaft with setscrew

upward and aligned with shaft flat portion. Vertically

Page 24: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

24 496 08 8001 00Specifications subject to change without notice.

position wheel along shaft to position marked duringdisassembly.

NOTE: If previous shaft was not marked or if replacingprevious motor, set blower wheel position by sliding blowerwheel along motor shaft to 1−1/8−in. above rubber grommets.(See Figure 17.)

4. Hold blower wheel in place and carefully tightensetscrew.

5. Position motor and blower wheel assembly to blowerhousing as originally oriented.

6. Secure motor mount to blower housing using boltspreviously removed.

7. Attach green wire to blower housing with screw.8. Connect electrical and capacitor leads to original

terminals.9. Replace blower access door and tighten all four

screws.10. Reinsert disconnect pullout only after blower access

door is secured. Test blower for proper operation.

Figure 17 − Motor, Inlet Ring, and Blower Wheel Assembly

GROMMET

BLOWERWHEEL

INLETRING

MOTOR

11⁄8≤

A86006

REFRIGERANT FLOW−CONTROLDEVICESThermostatic Expansion Valves (TXV)The FSA4X, FEA4X, FEM4X, FXM4X, FCM4X, FVM4,WAHM, WAHT, WAHL, WAXM, WAXT, WAXL, and REM4XFan Coils are factory equipped with a hard shutoff (HSO)TXV. The hard shutoff TXV has no bleed port and allows nobleed−through after system is shutdown.The TXV is a bi−flow metering device that is used incondensing and heat pump systems to adjust to changingload conditions by maintaining a preset superheattemperature at outlet of evaporator coil. The volume ofrefrigerant metered through valve seat is dependent upon thefollowing:

1. Superheat temperature sensed by sensing bulb onsuction tube at outlet of evaporator coil. As long as thisbulb contains some liquid refrigerant, this temperatureis converted into pressure pushing downward on thediaphragm, which opens the valve via push rods.

2. The suction pressure at outlet of evaporator coil istransferred via the external equalizer tube to undersideof diaphragm.

The bi−flow TXV is used on split system heat pumps. Incooling mode, TXV operates the same as a standard TXVpreviously explained. However, when system is switched toheating mode of operation, refrigerant flow is reversed.The bi−flow TXV has an additional internal check valve andtubing. These additions allow refrigerant to bypass TXV whenrefrigerant flow is reversed with only a 1−psig to 2−psigpressure drop through device.

When heat pump switches to defrost mode, refrigerant flowsthrough a completely open (not throttled) TXV. The bulbsenses the residual heat of outlet tube of coil that had beenoperating in heating mode (about 85�F and 155 psig). Thistemporary, not−throttled valve decreases indoor pressuredrop, which in turn increases refrigerant flow rate, decreasesoverall defrost time, and enhances defrost efficiency.PROBLEMS AFFECTING TXVA. Low Suction Pressure

1. Restriction in TXV2. Low refrigerant charge3. Low indoor load4. Low evaporator airflow

B. High Suction Pressure1. Overcharging2. Sensing bulb not secure to vapor tube3. High indoor load4. Large evaporator face area

NOTE: When installing or removing TXV, wrap TXV with awet cloth. When reattaching TXV, make sure sensing bulb isin good thermal contact with suction tube.

5. The needle valve on pin carrier is spring−loaded, whichalso exerts pressure on underside of diaphragm viapush rods, which closes valve. Therefore, bulbpressure equals evaporator pressure at outlet of coilplus spring pressure. If load increases, temperatureincreases at bulb, which increases pressure on topsideof diaphragm, which pushes pin carrier away from seal,opening valve and increasing flow of refrigerant. Theincreased refrigerant flow causes increased leaving

Page 25: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 25Specifications subject to change without notice.

evaporator pressure which is transferred via theequalizer tube to underside of diaphragm, with whichthe pin carrier spring pressure closes valve. Therefrigerant flow is effectively stabilized to load demandwith negligible change in superheat.

Figure 18 − Refrigerant Flow−Control DeviceFEM4P, WAPM, WAPT, WAPL, REM4P

PISTON

PISTONRETAINER

BRASSHEX NUT

BRASSHEX BODY

TEFLON SEAL

A93530

Piston Body Cleaning and Replacement

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmentaldamage.

Do not vent refrigerant to atmosphere. Recover duringsystem repair or final unit disposal.

CAUTION!

UNIT DAMAGE HAZARD

Failure to follow this caution could result in equipmentdamage.

Damage may occur to the scroll compressor if operatedat a negative suction pressure during a systempumpdown.

CAUTION!

1. Pump down outdoor unit. Close service valves atoutdoor unit.

2. Recover remaining refrigerant from tubing and coilthrough gage port on vapor−tube service valve.Disconnect refrigerant (liquid) tube from piston body.(See Figure 18.)

3. Avoid damaging seal ring or machined surfaces onpiston, bore, and retainer.

4. Using small wire with a hook on end of it, removepiston from body.

UNIT DAMAGE HAZARD

Failure to follow this caution could result in equipmentdamage.

When cleaning the piston orifice, be careful not toscratch or enlarge the opening, as this will affectoperation.

CAUTION!

5. Install new or cleaned piston into body.6. Replace seal ring on retainer.7. Reconnect refrigerant tube to piston body.8. Pressurize tubing and coil, then leak check.9. Evacuate tubing and coil as necessary.

UNIT DAMAGE HAZARD

Failure to follow this caution could result in equipmentdamage.

Use a backup wrench and do not over tighten, asdeformation of the piston body will occur, causing thepiston to lodge in a partially open or closed position.

CAUTION!

LIQUID TUBE STRAINERIn R−22 units, the TXV and refrigerant flow−control device isprotected on the indoor coil by a wire mesh strainer. It islocated inside the 3/8−in. liquid tube at field braze joint justoutside unit casing. Access to strainer is through field brazejoint.

COIL & CONDENSATE PAN REMOVALAND REPLACEMENT

Figure 19 − A−Coil Component Location

COIL TOP SEAL

EXPANSION DEVICE(TXV SHOWN)

HORIZONTALCONDENSATE

PAN

HORIZONTALPAN CLIP

DELTA PLATE

VERTICALCONDENSATEPANCOIL BRACKET

(4 PER UNIT) SCREWS–DELTA PLATE TOPAN (4 PER UNIT)

A90268

A−Coil UnitsIf it is determined that system does not have leaks andrefrigerant is not contaminated, proceed as follows:

1. Recover system refrigerant.a. Attach manifold/gage set to service valves.b. Front seat (close) liquid tube service valve.c. Start unit in cooling mode.d. Run unit until low pressure switch opens (350kPa)

or vapor pressure reaches 5 psig (35kPa). Do notallow compressor to pump into a vacuum.

e. Turn off electrical supply to outdoor unit.f. Front seat (close) vapor service valve.

g. Recover any remaining refrigerant.NOTE: All outdoor unit coils will hold only factory−suppliedamount of refrigerant. Excess refrigerant, such as in long−lineapplications, may cause compressor internal pressure reliefvalve to open (indicated by sudden rise in vapor pressure)before vapor pressure reaches 5 psig (35kPa). If this occurs,turn off electrical supply to outdoor unit immediately, front seatvapor service valve, and recover any remaining refrigerant.

2. Turn off electrical supply to indoor unit.3. Disconnect condensate drain tube.

Page 26: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

26 496 08 8001 00Specifications subject to change without notice.

4. Disconnect liquid and vapor tubes from indoor coil. Usea tubing cutter to cut tubes.

NOTE: If a torch is used to unbraze tube set, protect fittingpanel with a wet cloth or braze shield, as necessary.

5. Remove coil access panel.6. Remove clip securing fitting panel to condensate drain

pan. Remove fitting panel.7. Remove any shipping clips, including horizontal pan

clip, and slide coil/condensate pan assembly out ofunit.

8. Upflow or Horizontal Applications Only—Removehorizontal condensate drain pan from coil/condensatepan assembly. (See Figure 19.)

9. Remove the four coil brackets. (See Figure 19.)10. Remove screws at delta plates and remove coil from

vertical condensate drain pan. (See Figure 19.)11. Horizontal Applications Only—Remove coil top seal

(attached with four screws) and J−shaped tube fromoriginal coil and install it in same position on new coil.(See Figure 19.)

12. Place coil assembly in plastic condensate pan andsecure using four screws through delta plate. (SeeFigure 19.)

13. Horizontal and Upflow Applications Only—Attachthe four coil brackets to coil/pan assembly. (SeeFigure 19.)

14. Horizontal Applications only—Place horizontalcondensate pan into position on coil/pan assembly.

NOTE: Installation of horizontal condensate pan is notnecessary for upflow or downflow applications.

15. Slide complete assembly into unit.16. Reinstall fitting panel and reconnect clip securing fitting

panel to condensate drain pan.17. Horizontal Applications Only—Reinstall horizontal

pan clip. Secure with one screw. (See Figure 19.)Reinstall coil access panel.

18. Reconnect liquid and vapor refrigerant tubes, andcondensate drain tube. Install new R−410A liquid linefilter−drier.

19. Evacuate tube set and indoor coil to 500 microns, backseat (open) liquid and vapor service valves.

20. Turn on electrical supplies to indoor and outdoor units.21. Check system refrigerant charge and operation. See

”Application Guideline and Service Manual for R−410A”for further information.

SLOPE COIL UNITSIf it is determined that system does not have leaks andrefrigerant is not contaminated, proceed as follows:

1. Recover system refrigerant.a. Attach manifold/gage set to service valves.b. Front seat (close) liquid tube service valve.c. Start unit in cooling mode.d. Run unit until low pressure switch opens at 50 psig

(350kPa) or vapor pressure reaches 5 psig(35kPa). Do not allow compressor to pump into avacuum.

e. Turn off electrical supply to outdoor unit.f. Front seat vapor service valve.

g. Recover any remaining refrigerant.NOTE: All outdoor unit coils will hold only factory−suppliedamount of refrigerant. Excess refrigerant, such as in long−lineapplications, may cause compressor internal pressure reliefvalve to open (indicated by sudden rise in vapor pressure)

before vapor pressure reaches 5 psig (35kPa). If this occurs,turn off electrical supply to outdoor unit immediately, front seatvapor service valve, and recover any remaining refrigerant.

Figure 20 − Slope Coil Component Location

COIL MOUNTINGSCREW

COILSUPPORTRAIL

SLOPE COIL

SKI

REFRIGERANTCONNECTIONS

COIL TO PAN SCREW

(BOTH SIDES)

DRAINPAN

A98113

2. Turn off electrical supply to indoor unit.3. Disconnect condensate drain tube.4. Disconnect liquid and vapor tubes from indoor coil. Use

either a tubing cutter to cut tubes or a torch to unbrazetubes as required.

NOTE: If a torch is used to unbraze line set, protect fittingpanel with a wet cloth or braze shield, as necessary. Systemcontains oil vapors which may ignite when exposed to aflame.

5. Remove coil access and fitting panels.6. Remove 1 screw securing coil to unit casing.7. Remove coil/pan assembly from unit.8. Place assembly on a flat surface. Remove the two

screws securing coil support columns to pan. (SeeFigure 20.)

9. Rotate columns 90�, pull away from coil, and removecolumns from assembly.

10. Remove the remaining two screws securing coil tocondensate pan.

11. Remove coil from condensate pan.12. Remove coil top seal. (See Figure 20.)13. Install new coil into condensate pan using the two

original screws and two support columns.NOTE: Correct coil position in condensate pan is essential toreliable operation.

14. Install new coil/pan assembly into unit. Secure with thetwo screws previously removed from unit casing.

15. Reinstall coil access and fitting panels.16. Reconnect liquid and vapor refrigerant tubes, and

condensate drain tube. Install new R−410A liquid linefilter−drier.

17. Evacuate tube set and indoor coil to 500 microns, backseat (open) liquid and vapor service valves.

18. Turn on electrical supplies to indoor and outdoor units.19. Check system refrigerant charge and operation. See

”Application Guideline and Service Manual for R−410A”for further information.

Page 27: SERVICE AND MAINTENANCE INSTRUCTIONSicpindexing.toddsit.com/documents/003350/49608800100.pdfSERVICE AND MAINTENANCE FAN COILS 496 08 8001 00 Specifications subject to change without

SERVICE AND MAINTENANCE FAN COILS

496 08 8001 00 27Specifications subject to change without notice.

R−410A QUICK REFERENCE GUIDE

R−410A refrigerant operates at 50% − 70% higher pressures than R−22. Be sure that servicing equipment andreplacement components are designed to operate with R−410A.

R−410A refrigerant cylinders are rose colored.

Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400 or DOT BW400.

R−410A systems should be charged with liquid refrigerant. Use a commercial type metering device in themanifold hose.

Manifold sets should be 750 psig high−side and 200 psig low−side with 520 psig low−side retard.

Use hoses with 750 psig service pressure rating.

Leak detectors should be designed to detect HFC refrigerant.

R−410A, as with other HFC refrigerants, is only compatible with POE oils.

POE oils absorb moisture rapidly. Do not expose oil to atmosphere.

POE oils may cause damage to certain plastics and roofing materials.

Vacuum pumps will not remove moisture from oil.

A liquid line filter−drier is required on every unit.

Do not use liquid line filter−driers with rated working pressures less than 600 psig.

Do not install a suction line filter−drier in liquid line.

Wrap all filter−driers and service valves with wet cloth when brazing.

Do not use capillary tube indoor coils.

Never open system to atmosphere while it is under a vacuum.

When system must be opened for service, break vacuum with dry nitrogen and replace all filter−driers.

Do not vent R−410A into the atmosphere.

Observe all warnings, cautions, notes and bold text.

Do not use R−22 TXV

Copyright 2014 International Comfort ProductsLewisburg, TN 37091 USA