Page 1: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

Carolinas HealthCare System

Shaft Walls

Submittal Package

STI Contacts:

Eric LacroixT: 704-236-7047

E: [email protected]

Jay GuidottiT: 704-787-0422

E: [email protected]

Specified Technologies Inc. | 210 Evans Way | Somerville, NJ 08876 USA | T: 800.992.1180 | www.stifirestop.com

Page 2: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

Assembly Ratings - 1 and 2 Hr (See Items 2 and 3B)Joint Width- 1 in. Max

L Rating At Ambient - Less Than 1 CFM/Lin Ft (See Item 3B)L Rating At 400°F - Less Than 1 CFM/Lin Ft (See Item 3B)

Class II Movement Capabilities-25 Percent Compression or Extension

1. Floor Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3 )structural concrete.

2. Shaft Wall Assembly - With the exception of the ceiling runner, the 1 or 2 hr fire rated shaft wall assembly shall be constructedof the materials and in the manner described in the individual U400 or V400-Series Wall and Partition Design in the UL FireResistance Directory. The wall shall include the following construction features:

A. Floor and Wall Runners - (Not Shown) - "J"-shaped runner, min 2-1/2 in. (64 mm) wide with unequal legs of 1 in. (25 mm)and 2 in. (51 mm), fabricated from min 24 MSG galv steel. Runners positioned with short leg toward finished side of wall.Runners attached to walls and floor with steel fasteners spaced max 24 in. (610 mm) OC. As an alternate to the "J"-shapedrunner, a min 2-1/2 in. (64 mm) wide by 1 or 1-1/4 in. (25 or 32 mm) deep channel formed from min 24 MSG galv steel maybe used for the floor runner.

B. Light Gauge Framing* - Slotted Ceiling Track - Slotted ceiling track shall consist of galv steel channels with slottedflanges. Slotted ceiling track sized to accommodate steel "C-H" studs (Items 2C). Attached to concrete at ceiling with steelfasteners spaced max 12 in. OC (305 mm).

BRADY CONSTRUCTION INNOVATIONS INC,

DBA SLIPTRACK SYSTEMS - SLP-TRK

CALIFORNIA EXPANDED METAL PRODUCTS CO - CST

CLARKWESTERN BUILDING SYSTEMS INC - Type SLT, SLT-H

MARINO/WARE, DIV OF WARE INDUSTRIES

INC - Type SLT

SCAFCO STEEL STUD MANUFACTURING CO

STEELER INC - Steeler Slotted Ceiling Runner

TELLING INDUSTRIES L L C - True-Action Deflection Track

THE STEEL NETWORK INC - VertiTrack VT, series,250VT, 362VT, 400VT, 600VT and 800VT

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

June 24, 2011

1 2

Ì76HWDÇ!~ÈANÇ&8+xÎ

HW-D-0194

2B

2C

3B3A

2C

2B

2D

3B2B

2C

2D

3B

2C2B

2E

2D2E

2E

1

1

Page 3: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

C. Steel Studs - "C-H"-shaped steel studs to be min 2-1/2 in. (64 mm) wide and formed of min 24 MSG galv steel. Studs cut1/2 to 3/4 in. (13 to 19 mm) less in length than assembly height with bottom nesting in and resting on floor runner and withtop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gypsum board liner panels (Item2D), studs secured to flange of floor runner on finished side of wall only with No. 6 by 1/2 in. (13 mm) long self-drilling,self-tapping steel screws. Studs secured to flange of slotted ceiling track on finished side of wall only with No. 8 by 1/2 in.(13 mm) long self-drilling, self-tapping wafer head steel screws at slot midheight.

D. Gypsum Board* - 1 in. (25 mm) thick by 24 in. (610 mm) wide gypsum board liner panels as specified in the individualU400 or V400-Series Wall and Partition Design. Panels cut 1 in. (25 mm) less in length than floor to ceiling height. Verticaledges inserted in "H"-shaped section of "C-H" studs. Free edge of end panels attached to long leg of "J" runner (Item 2A)with 1-5/8 in. (41 mm) long Type S steel screws spaced max 12 in. (305 mm) OC.

E. Gypsum Board* - Gypsum board sheets, 1/2 or 5/8 in. (13 or 16 mm) thick, applied vertically or horizontally in one or twolayers on finished side of wall as specified in the individual U400 or V400-Series Wall and Partition Design. A max 1 in. (25mm) gap shall be maintained between the top of the gypsum board and the bottom surface of the concrete floor. Thescrews attaching the gypsum board layers to the C-H studs shall be located 1 in. (25 mm) below the bottom of the slottedceiling track (Item 2C). No gypsum board attachment screws are to penetrate the slotted ceiling track.

The hourly fire rating of the joint system is equal to the hourly fire rating of the wall.

3. Joint System - Max separation between bottom of floor and top of liner panel (Item 2D) and between bottom of floor and top ofgypsum board sheets (Item 2E) at time of installation of joint system is 1 in. (25 mm). The joint system is designed toaccommodate a maximum 25 percent compression or extension from its installed width. The joint system consists of bondbreaker tape and sealant, as follows:

A. Bond Breaker Tape - Polyethylene tape supplied in rolls. Tape applied to flanges of slotted ceiling track (Item 2D) toprevent bonding of the sealant at points other than the top and bottom of the linear gap. Bond breaker tape is optional whenmovement capability of the joint is limited to compression only.

B. Fill, Void or Cavity Material* - Sealant - Min 1 in. (25 mm) depth of sealant to be installed to fill linear gap between top ofgypsum board liner panel (Item 2D) and top inside surface of slotted ceiling track (Item 2B) prior to installation of gypsumboard sheets on finished side of wall. For 1 hr fire rated walls, min 5/8 in. (16 mm) depth of sealant to be installed to filllinear gap between top of gypsum board sheet (Item 2E) and bottom of concrete floor. For 2 hr walls, min 1 in. (25 mm)depth of sealant to be installed to fill linear gap between top of gypsum board sheets (Item 2E) and bottom of concrete floor.

SPECIFIED TECHNOLOGIES INC - SpecSeal ES Elastomeric Sealant or SpecSeal LCI Sealant. L Ratings apply whenSpecSeal ES Elastomeric Sealant is used. When SpecSeal LCI Sealant is used, the movement capability of the jointis limited to 25 percent in compression only.

*Bearing the UL Classification Mark

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

June 24, 2011

2 2HW-D-0194

Page 4: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1. Floor Assembly - The fire-rated fluted steel deck/concrete floor assembly shall be constructed of the materials and in themanner described in the individual D900 Series Floor-Ceiling Design in the UL Fire Resistance Directory. The hourly firerating of the floor assembly shall be equal to or greater than the hourly fire rating of the wall assembly. The floor assemblyshall include the following construction features:A. Steel Floor and Form Units* - Max 3 in. (76 mm) deep galv steel fluted floor units.B. Concrete - Min 2-1/2 in. (64 mm) thick reinforced concrete, as measured from the top plane of the floor units.

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

1 5

Ì73HWDÇ%PÈAOÇ!+-SÎ

HW-D-0548

System No. HW-D-0548

ANSI/UL2079

Assembly Ratings - 1 and 2 Hr (See Item 2)

Maximum Joint Width - 3/4, 1 or 1-1/2 In. (See Item 3)

Class II Movement Capabilities - 50 or 100 %Compression orExtension (See Item 3)

L Rating At Ambient - Less Than 1 CFM/sq ft

L Rating At 400 F - Less Than 1 CFM/sq ft

CAN/ULC S115

F Ratings - 1 and 2 Hr (See Item 2)

FT Ratings - 1 and 2 Hr (See Item 2)

FH Ratings - 1 and 2 Hr (See Item 2)

FTH Ratings - 1 and 2 Hr (See Item 2)

Maximum Joint Width - 19, 25 or 38 mm (See Item 3)

Class II Movement Capabilities - 50 or 100 % Compression orExtension (See Item 3)

L Rating At Ambient - Less Than 1 CFM/sq ft

L Rating At 400 F - Less Than 1 CFM/sq ft

Page 5: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1A. Roof Assembly - (Not Shown) - As an alternate to the floor assembly (Item 1), a fire rated fluted steel deck roof assemblymay be used. The roof assembly shall be constructed of the materials and in the manner described in the individual P900Series Roof-Ceiling Design in the UL Fire Resistance Directory. The hourly fire rating of the roof assembly shall be equal toor greater than the hourly fire rating of the wall assembly. The roof assembly shall include the following constructionfeatures:A. Steel Roof Deck - Max 3 in. (76 mm) deep galv steel fluted roof deck.B. Roof Insulation - Min 2-1/4 in. (57 mm) thick poured insulating concrete, as measured from the top plane of the steel

roof deck.1B. Floor Assembly - As an alternate to the floor assembly (Item 1), min 4-1/2 in. (114 mm) thick reinforced lightweight or

normal weight (100-150 pcf or 1600-2400 kg/m3) structural concrete. Floor may also be constructed of any UL Classifiedhollow-core Precast Concrete Units*.

See Precast Concrete Units (CFTV) in Fire Resistance Directory for names of manufacturers.

2. Shaft Wall Assembly - The 1 or 2 hr fire rated shaft wall assembly shall be constructed of the materials and in the mannerdescribed in the individual U400, V400 or W400 Series Wall and Partition Design in the UL Fire Resistance Directory andshall include the following construction features:

A. Floor and Ceiling Runners - "J"-shaped runner, min 2-1/2 in. (64 mm) wide with unequal legs of min 1-1/2 in. (38mm) and min 2 in. (51 mm), fabricated from min 24 MSG galv steel. Runners positioned with short leg toward finishedside of wall. Flange height of ceiling runner shall be min 1/4 in. (6 mm) greater than max extended joint width.Runners attached to walls and floor with steel fasteners spaced max 24 in. (610 mm) OC. As an alternate to the"J"-shaped runner, a min 2-1/2 in. (64 mm) wide by 1 in. or 1 1/4 in. (25 or 32 mm) deep channel formed from min 24MSG galv steel may be used for the floor runner. Ceiling runner installed parallel with or perpendicular to direction offluted steel deck and secured to steel deck valley withy steel fasteners or welds spaced max 24 in. (610 mm) OC.

A1. Floor And Ceiling Runners - As an alternate to Item 2A, floor and ceiling runners of wall assembly shall consist ofgalv steel channels sized to accommodate steel "C-H" studs. Flange height of ceiling runner shall be min 1/2 in. (13mm) greater than nom joint width. Ceiling runner installed parallel with or perpendicular to direction of fluted steel deckand secured with steel masonry anchors or welds spaced max 24 in. (610 mm) OC.

A2. Light Gauge Framing* - Slotted Ceiling Track - (for use in Configuration A Only) As an alternate to Item 2A,slotted ceiling track shall consist of galv steel channels with slotted flanges. Slotted ceiling track sized toaccommodate steel "C-H" studs (Item 2C). Attached to concrete at ceiling with steel fasteners spaced max 12 in. OC(305 mm).

BRADY CONSTRUCTION INNOVATIONS INC, DBA SLIPTRACK SYSTEMS - SLP-TRK, SLPTRK325

CALIFORNIA EXPANDED METAL PRODUCTS CO - CST

CLARKDIETRICH BUILDING SYSTEMS - Type SLT, SLT-H

MARINO/WARE, DIV OF WARE INDUSTRIES INC - Type SLT

SCAFCO STEEL STUD MANUFACTURING CO

TELLING INDUSTRIES L L C - True-Action Deflection Track

THE STEEL NETWORK INC - VertiTrack VT, series,250VT, 362VT, 400VT, 600VT and 800VT

A3. Light Gauge Framing* - Slotted Ceiling Runner - As an alternate to the ceiling runner in Items 2A through 2A3,slotted ceiling runner to consist of galv steel channel with 3-1/4 in. (83 mm) high slotted flanges sized to accommodatesteel studs (Item 2B). Ceiling runner installed parallel or perpendicular with direction of fluted steel deck and securedto steel deck valley with steel fasteners or welds spaced max 24 in. (610 mm) OC.

BRADY CONSTRUCTION INNOVATIONS INC, DBA SLIPTRACK SYSTEMS - SLPTRK325

B. Steel Studs - "C-H"-shaped steel studs to be min 2-1/2 in. (64 mm) wide and formed of min 24 MSG galv steel. Forconfiguration A studs cut 1/2 to 1-1/4 in. (13 to 32 mm) less in length than assembly height or for configuration B studscut 1 to 1-1/2 in. (25 to 38 mm) less in length than assembly height with bottom nesting in and resting on floor runnerand with top nesting in ceiling runner or slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation ofgypsum board liner panels (Item 2D), studs secured to flange of floor runner on finished side of wall with No. 6 by 1/2in. (13 mm) long self-drilling, self-tapping steel screws. Studs secured to flange of slotted ceiling track on finished sideof wall only with No. 8 by 1/2 in. (13 mm) long self-drilling, self-tapping wafer head steel screws at slot midheight.

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

2 5HW-D-0548

Page 6: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

C. Gypsum Board* - 1 in. (25 mm) thick by 24 in. (610 mm) wide gypsum board liner panels. Panels cut 1 in. (25 mm)less in length than floor to ceiling height. Vertical edges inserted in "H"-shaped section of "C-H" studs. Free edge ofend panels attached to long leg of "J" runner (Item 2A) with 1-5/8 in. (41 mm) long Type S steel screws spaced max12 in. (305 mm) OC.

D. Gypsum Board* - Gypsum board sheets, 1/2 or 5/8 in. (13 or 16 mm) thick, applied vertically or horizontally in one ortwo layers on finished side of wall as specified in the individual U400 or V400-Series Wall and Partition Design. A max1 in. (25 mm) gap shall be maintained between the top of the gypsum board and the bottom surface of the concretefloor. The screws attaching the gypsum board layers to the C-H studs shall be located 1 in. (25 mm) below the bottomof the slotted ceiling track (Item 2C). No gypsum board attachment screws are to penetrate the slotted ceiling track.

The hourly fire rating of the joint system is equal to the hourly fire rating of the wall.

Configuration A

3. Joint System - Max separation between bottom of floor and top of liner panel (Item 2C) and between bottom offloor and top of gypsum board sheets (Item 2D) at time of installation of joint system 1-1/2 in. (38 mm). The jointsystem is designed to accommodate a maximum 50 percent compression or extension from its installed width.The joint system consists of forming material and sealant, as follows:

A. Forming Material* - In floor or roof assembly constructed with steel fluted floor units, compression-fit a minimum 1 in.(25 mm) depth of nom 4 pcf (64 kg/m3) mineral wool batt insulation into far recess of flute valley as a permanent form.Strips of mineral wool batt insulation cut to width of gypsum liner panel (Item 2C) and compressed 50 percent inthickness. Strip installed between top of gypsum liner panel and bottom of steel ceiling runner.

IIG MINWOOL L L C - MinWool 1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - SAFE

ROXUL INC - SAFE

THERMAFIBER INC - SAF

B. Fill, Void or Cavity Material*- Sealant - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or 1.5 mm dry thickness) ofspray applied to cover mineral wool batt insulation within joint cavity (when present; Item 3A) and mineral wool battinstalled above gypsum liner panel (Item 2C). Maintain min 1/2 in. (13 mm) overlaps onto surrounding substrates.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

C. Forming Material* - Sections of min 4 pcf (64kg/m3) density mineral wool batt insulation cut to fill flute area (whenpresent) flush with interior surface of wall after installation of spray (Item 3B). Strips of mineral wool batt insulation cutto width of gypsum board layers (Item 2D) and compressed 50 percent in thickness. Strips installed above gypsumboard layers on finished side of wall assembly flush with the wall surface.

IIG MINWOOL L L C - MinWool 1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - SAFE

ROXUL INC - SAFE

THERMAFIBER INC - SAF

D. Fill, Void or Cavity Material*- Sealant - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or 1.5 mm dry thickness) ofspray applied to cover mineral wool batt insulation on finished side of wall. Maintain min 1/2 in. (13 mm) overlaps ontosurrounding substrates.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

Configuration B

3. Joint System - Max separation between bottom of floor and top of liner panel (Item 2C) and between bottom offloor and top of gypsum board sheets (Item 2D) at time of installation of joint system is 1-1/2 in. (38 mm). The jointsystem is designed to accommodate a maximum 50 percent compression or extension from its installed width.The joint system consists of forming material and sealant, as follows:

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

3 5HW-D-0548

Page 7: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

A. Forming Material* - Strips of min 4 pcf (64kg/m3) density mineral wool batt insulation cut to width of gypsum linerpanel (Item 2C) and compressed 50 percent in thickness. Strip installed between top of gypsum liner panel andbottom of steel ceiling runner.

IIG MINWOOL L L C - MinWool 1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - SAFE

ROXUL INC - SAFE

THERMAFIBER INC - SAF

B. Fill, Void or Cavity Material*- Sealant - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or1.5 mm dry thickness) ofspray applied to cover mineral wool batt insulation within joint cavity. Maintain min 1/2 in. (13 mm) overlaps ontosurrounding substrates.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

C. Forming Material* - Strips of min 4 pcf (64kg/m3) density mineral wool batt insulation cut to width of gypsum boardlayers (Item 2D) and compressed 50 percent in thickness. Strips installed above gypsum board layers on finished sideof wall assembly flush with the wall surface.

IIG MINWOOL L L C - MinWool 1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - SAFE

ROXUL INC - SAFE

THERMAFIBER INC - SAF

D. Fill, Void or Cavity Material*- Sealant - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or 1.5 mm dry thickness) ofspray applied to cover mineral wool batt insulation on finished side of wall. Maintain min 1/2 in. (13 mm) overlaps ontosurrounding substrates.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

Configuration C

3. Joint System - Max separation between bottom of floor and top of liner panel (Item 2C) and between bottom offloor and top of gypsum board sheets (Item 2D) at time of installation of joint system is 3/4 or 1 in. (19 or 25 mm).The joint system is designed to accommodate a maximum 100 percent compression or extension for 3/4 in. (19mm) wide joints and a maximum 100 percent compression only for 1 in. (25 mm) wide joints, from its installedwidth. The joint system consists of the following:

A. Forming Material* - Nom 3/16 in. (4.8 mm) thick by 4 in. (102 mm) high joint forming material profile installed on bothsides of the wall assembly. Profile installed on the shaft side of the wall by first marking a line across the top of thewall 3 in. (76 mm) below the bottom plane of the bottom of the "J" or ceiling runner on the interior surface of thegypsum liner. Joint profile material on shaft side positioned with its top edge against both the underside of the ceilingrunner with its bottom edge on the line scribed on the shaft liner. Profile installed on the finished side of the wall byfirst marking a line across the top of the wall 3 in. (76 mm) below the bottom plane of the steel floor or roof deckvalleys. Joint profile material on finished side positioned with its top edge against both the underside of the floor orsteel deck with its bottom edge on the line scribed on the finished side of the wall assembly. Bottom of the joint profileattached to gypsum board with nom 1/2 in. (13 mm) long steel staples spaced not greater than 8 in. (203 mm) OC.Adjoining lengths of profile to overlap approx 3/4 in. (19 mm) at shiplapped ends.

SPECIFIED TECHNOLOGIES INC - SpecSeal Speed Flex Joint Profile

B. Fill, Void or Cavity Material*- Sealant - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or1.5 mm dry thickness) ofspray applied to cover forming material within joint cavity (Item 3A) and forming material installed above gypsum linerpanel (Item 2D). Maintain min 1/2 in. (13 mm) overlaps onto surrounding substrates.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

4 5HW-D-0548

Page 8: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

C. Forming Material* - Sections of min 4 pcf (64kg/m3) density mineral wool batt insulation cut to fill flute area (whenpresent) flush with interior surface of wall after installation of spray (Item 3B). Strips of mineral wool batt insulation cutto width of gypsum board layers (Item 2E) and compressed 50 percent in thickness. Strips installed above gypsumboard layers on finished side of wall assembly flush with the wall surface.

IIG MINWOOL L L C - MinWool 1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - SAFE

ROXUL INC - SAFE

THERMAFIBER INC - SAF

D. Fill, Void or Cavity Material*- Sealant - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or 1.5 mm dry thickness) ofspray applied to cover forming material (Item 3C) on finished side of wall. Maintain min 1/2 in. (13 mm) overlaps ontosurrounding substrates.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

*Bearing the UL Classification Mark

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

5 5HW-D-0548

Page 9: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

1 4

Ì78HWDÇ&JÈAOÇ!+-4Î

HW-D-0642

System No. HW-D-0642

ANSI/UL2079

Assembly Ratings - 1 and 2 Hr (See Item 1)

Nominal Joint Width - 3/4 or 1-1/2 In. (See Item 3)

Class II Movement Capabilities - 50% or 100% Compression orExtension (See Item 3)

L Rating At Ambient - Less Than 1 CFM/sq ft

L Rating At 400 F - Less Than 1 CFM/sq ft

CAN/ULC S115

F Ratings - 1 and 2 Hr (See Item 1)

FT Ratings - 1 and 2 Hr (See Item 1)

FH Ratings - 1 and 2 Hr (See Item 1)

FTH Ratings - 1 and 2 Hr (See Item 1)

Nominal Joint Width - 3/4 or 1-1/2 In. (See Item 3)

Class II Movement Capabilities - 50% or 100% Compression orExtension (See Item 3)

L Rating At Ambient - Less Than 1 CFM/sq ft

L Rating At 400 F - Less Than 1 CFM/sq ft

A

Section A-A2E

3B 3A

3A

3B

2C

2B

1D

1B

1A

1C1C

2A

2B

2B

2E

1D

A

2D

2A

CONFIGURATION A

3A

Page 10: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1. Floor Assembly - The fire-rated fluted steel deck/concrete floor assembly shall be constructed of the materials and in themanner described in the individual D700, D800, or D900 Series Floor-Ceiling Design in the UL Fire Resistance Directory andshall include the following construction features:A. Steel Floor And Floor Units* - Max 3 in. (76 mm) deep galv steel fluted floor units.B. Concrete - Min 2-1/2 in. (64 mm) thick reinforced concrete, as measured from the top plane of the floor units.C. Structural Steel Support - Steel beam, as specified in the individual D700, D800, or D900 Series Floor-Ceiling Design,

used to support steel floor units. Steel beam centered over and parallel with wall assembly.D. Spray-Applied Fire Resistive Material* - After installation of the steel attachment clips (Item 2B), steel floor units and

structural steel support to be sprayed with the min thickness of material specified in the individual D700, D800, or D900Series Design. The flutes of the steel floor units are to be filled with material across the entire top flange of the steel beam.Additional material shall be applied to the web of the steel beam on each side of the wall. For a 1 hr AssemblyRating, the thickness of material applied to each side of the steel beam web shall be 13/16 in. (21 mm). For a 2 hrAssembly Rating, the thickness of material applied to each side of the steel beam web shall be 1-3/8 in. (35 mm).

SOUTHWEST FIREPROOFING PRODUCTS CO - Type 5, Type 5GP

W R GRACE & CO - CONN - Type MK-6/HY

D1. Spray-Applied Fire Resistive Material* - After installation of the steel attachment clips (Item 2B), steel floor units andstructural steel support to be sprayed with the min thickness of material specified in the individual D700, D800, or D900Series Design. The flutes of the steel floor units are to be filled with material across the entire top flange of the steel beam.Additional material shall be applied to the web of the steel beam on each side of the wall. For a 1 hr AssemblyRating, the thickness of material applied to each side of the steel beam web shall be 11/16 in. (18 mm). For a 2 hrAssembly Rating, the thickness of material applied to each side of the steel beam web shall be 1-1/2 in. (38 mm).

ISOLATEK INTERNATIONAL - Type 300 or Type II

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

2 4HW-D-0642

B

Section A-A2E

3B 3A

3A

3B

2C

1D

1B

1A

1C1C

2A2B

2B

2E

1D

B

CONFIGURATION B

2D

3B3A

Page 11: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

2. Shaft Wall Assembly - The 1 hr or 2 hr fire rated shaft wall assembly shall be constructed of the materials and in the mannerdescribed in the individual U400, V400 or W400 Series Wall and Partition Design in the UL Fire Resistance Directory and shallinclude the following construction features:

A. Floor, Wall and Ceiling Runners - "J"-shaped runner, min 2-1/2 in. (64 mm) wide with unequal legs of min 1-1/2 in. (38mm) and min 2 in. (51 mm), fabricated from min 24 MSG galv steel. Runners positioned with short leg toward finished sideof wall. Flange height of ceiling runner shall be min 1/4 in. (6 mm) greater than max extended joint width. Runnersattached to steel attachment clips (Item 2B) with welds or steel fasteners spaced max 24 in. (610 mm) OC. As an alternateto the "J"-shaped runner, a min 2-1/2 in. (64 mm) wide by 1 in. or 1 1/4 in. (25 or 32 mm) deep channel formed from min24 MSG galv steel may be used for the floor runner.

A1. Light Gauge Framing* - Slotted Ceiling Track - (Not Shown) - As an alternate to ceiling runner in Item 2A, slotted ceilingtrack shall consist of galv steel channels with slotted flanges. Slotted ceiling track sized to accommodate steel "C-H" studs(Item 2C) and attached to steel attachment clips (Item 2B) with welds or steel fasteners spaced max 24 in. (610 mm) OC.

BRADY CONSTRUCTION INNOVATIONS INC, DBA SLIPTRACK SYSTEMS - SLP-TRK

CALIFORNIA EXPANDED METAL PRODUCTS CO - CST

CLARKDIETRICH BUILDING SYSTEMS - Type SLT, SLT-H

SCAFCO STEEL STUD MANUFACTURING CO

STEELER INC - Steeler Slotted Ceiling Runner

TELLING INDUSTRIES L L C - True-Action Deflection Track

THE STEEL NETWORK INC - VertiTrack VT, series,250VT, 362VT, 400VT, 600VT and 800VT

B. Steel Attachment Clips - Z-shaped clips formed from 1 in. (25 mm) wide strips of min 20 ga galv steel. Clips to be sizedto extend through the thickness of the spray-applied fire-resistive material on the bottom flange of the steel beam with 2 in.(51 mm) long upper and lower legs. Legs of clips fastened to bottom of beam (prior to application of spray-appliedfire-resistive materials) and top of ceiling runner with steel fasteners or welds. Clips spaced max 24 in. (610 mm) OC.

C. Steel Studs - "C-H"-shaped steel studs to be min 2-1/2 in. (64 mm) wide and formed of min 24 MSG galv steel. Studs cut1/2 to 1-1/4 in. (13 to 32 mm) less in length than assembly height beneath protected beam with bottom nesting in andresting on floor runner and with top nesting in ceiling runner or slotted ceiling track. Studs spaced 24 in. (610 mm) OC.After installation of gypsum board liner panels (Item 2D), studs secured to flange of floor runner on finished side of wallwith No. 6 by 1/2 in. (13 mm) long self-drilling, self-tapping steel screws. Studs secured to flange of slotted ceiling track onfinished side of wall only with No. 8 by 1/2 in. (13 mm) long self-drilling, self-tapping wafer head steel screws at slotmidheight.

D. Gypsum Board* - 1 in. (25 mm) thick by 24 in. (610 mm) wide gypsum board liner panels. Liner panels cut 1 in. (25 mm)less in length than assembly height beneath protected beam. Vertical edges inserted in "H"-shaped section of "C-H" studs.Free edge of end panels attached to long leg of "J" runner (Item 2A) with 1-5/8 in. (41 mm) long Type S steel screwsspaced max 12 in. (305 mm) OC.

E. Gypsum Board* - Gypsum board sheets, 1/2 or 5/8 in. (13 or 16 mm) thick, applied vertically or horizontally in one or twolayers on finished side of wall as specified in the individual U400 or V400-Series Wall and Partition Design. A max 3/4 in.(19 mm) gap shall be maintained between the top of the gypsum board and the bottom surface of the protected steelbeam. The screws attaching the gypsum board layers to the C-H studs shall be located 1 in. (25 mm) below the bottom ofthe ceiling runner (Item 2A or 2A1). No gypsum board attachment screws are to penetrate the ceiling runner.

CONFIGURATION A

3. Joint System - Max separation between spray applied fire resistive material on bottom of structural support memberand top of gypsum board (Item 2E) at time of installation of joint system is 1-1/2 in. (38 mm). The joint system isdesigned to accommodate a max 50 percent compression or extension from its installed width as measured betweenbottom plane of the protective material on the steel beam and the top of the gypsum board. The joint system shallconsist of forming and fill materials, as follows:

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

3 4HW-D-0642

Page 12: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

A. Forming Material* - Sections of nom 4 pcf (64 kg/m3) mineral wool batt insulation to be compressed 50 percent inthickness and installed cut edge first to completely fill the gap above the top of the liner panels (Item 2D) and the gapabove the top of the gypsum board (Item 2E).

IIG MINWOOL L L C - MinWool-1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - SAFE

ROXUL INC - SAFE

THERMAFIBER INC - Type SAF

B. Fill, Void or Cavity Material* - Sealant - Min 1/8 in. (3.2 mm) wet thickness or 1/16 in. (1.6 mm) dry thickness of fillmaterial spray applied over the forming material within the stud cavity prior to installing the finished surface gypsum boardand on the finished side of the wall. Fill material to overlap min 1/2 in. (13 mm) onto gypsum board liner panel and ceilingrunner within wall cavity, min 1/2 in. (13 mm) onto the finished surface gypsum board and min 2 in. (51 mm) onto the sprayapplied material (Item 1D) on the steel beam.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

CONFIGURATION B

3. Joint System - Max separation between bottom plane of spray-applied fire resistive material on the steel attachmentclip (Item 1D) and the top of the gypsum board is 3/4 in. (19 mm) or 1 in. (25 mm). The joint system is designed toaccommodate a max 100 percent compression or extension from its installed width as measured between bottomplane of the protective material on the steel beam and the top of the gypsum board or max 100 percent compression(only) from its installed width when the joint width is greater than 3/4 in. The joint system consists of the following:

A. Forming Material* - Nom 3/16 in. (4.8 mm) thick by 4 in. (102 mm) high joint forming material profile installed within andon the finished side of the wall assembly. Profile installed on the shaft side of the wall by first marking a line across the topof the wall 3 in. (76 mm) below the web of the "J" runner or ceiling runner channel on the interior surface of the gypsumliner. Joint profile material on shaft side positioned with its top edge against the web of the ceiling runner with its bottomedge on the line scribed on the shaft liner. Profile installed on the finished side of the wall by first marking a line across thetop of the wall 3 in. (76 mm) below the bottom plane of the spray-applied fire resistive material. Joint profile material onfinished side positioned with its top edge against the underside of the spray-applied fire resistive material with its bottomedge on the line scribed on the finished side of the wall assembly. Bottom of the joint profile attached to gypsum linerpanel and gypsum board with nom 1/2 in. (13 mm) long steel staples spaced not greater than 8 in. (203 mm) OC.Adjoining lengths of profile to overlap approx 3/4 in. (19 mm) at shiplapped ends.

SPECIFIED TECHNOLOGIES INC - SpecSeal Speed Flex Joint Profile

B. Fill, Void or Cavity Material*- Sealant - Min 1/8 in. (3.2 mm) wet thickness (min 1/16 in. or 1.5 mm dry thickness) ofelastomeric spray applied to cover forming material (Item 3A) within wall cavity and on finished side of wall. Maintain min1/2 in. (13 mm) overlap onto surrounding substrates with min 2 in. (51 mm) overlap onto spray applied fire resistivematerial on finished side of wall.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

*Bearing the UL Classification Mark

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RJanuary 11, 2011

4 4HW-D-0642

Page 13: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

Assembly Ratings - 1 and 2 Hr (See Item 2)Nominal Joint Width - 1 In.

L Rating At Ambient - Less Than 1 CFM/Lin FtL Rating At 400°F - Less Than 1 CFM/Lin Ft

Class II Movement Capabilities - 12.5% Compression or Extension

1. Floor Assembly - The fire-rated fluted steel deck/concrete floor assembly shall be constructed of the materials and in themanner described in the individual D700 or D800 Series Floor-Ceiling Design in the UL Fire Resistance Directory. The hourlyfire rating of the floor assembly shall be equal to or greater than the hourly fire rating of the wall assembly. The floor assemblyshall include the following construction features:

A. Steel Floor And Floor Units* - Max 3 in. (76 mm) deep galv steel fluted floor units.

B. Concrete - Min 2-1/2 in. (64 mm) thick reinforced concrete, as measured from the top plane of the floor units.

C. Structural Steel Support - Steel beam or open-web steel joist, as specified in the individual D700 or D800 SeriesFloor-Ceiling Design, used to support steel floor units. Structural steel support oriented parallel to and 1 to 6 in. (25 to 152mm) from wall assembly.

D. Steel Lath - When structural steel support (Item 1C) consists of open-web steel joists, 3/8 in. (10 mm) diamond meshexpanded steel lath having a nom weight of 1.7 to 3.4 lb per sq yd (0.9 to 1.8 kg/m2) shall be installed to completely coverone side of each joist which is located within 6 in. (152 mm) of wall assembly. The lath shall be secured with steel tie wireand shall be fully covered with spray applied fire resistive material.

E. Spray-Applied Fire Resistive Material* - After installation of the ceiling runner (Item 2A or 2A1), steel floor units andstructural steel supports to be sprayed with the thickness of material specified in the individual D700 or D800 SeriesDesign. The flutes of the steel floor units above the structural steel supports and above the ceiling runner (Item 2A or 2A1)shall be filled with spray-applied fire resistive material. As an alternate, the spray-applied fire resistive material in the flutesabove the ceiling runner may be applied to follow the contour of the steel floor units.

ISOLATEK INTERNATIONAL - Type 300 or Type II

W R GRACE & CO - CONN - Type MK-6/HY, MK-6/HYES, MK-65 and RG.

1A. Roof Assembly - (Not Shown) - As an alternate to the floor assembly (Item 1), a fire rated fluted steel deck roof assemblymay be used. The roof assembly shall be constructed of the materials and in the manner described in the individual P700 orP800 Series Roof-Ceiling Design in the UL Fire Resistance Directory. The hourly fire rating of the roof assembly shall beequal to or greater than the hourly fire rating of the wall assembly. The roof assembly shall include the following constructionfeatures:

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

January 11, 2011

1 3

Ì77HWDÇ&KÈAOÇ!+-:Î

HW-D-0643

3B

A

3A

1C

2B

2C

1B1A A

Section A-A

1D

1E

3B

3B

3A

3C

1B1A

2A

2D

Page 14: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

A. Steel Roof Deck - Max 3 in. (76 mm) deep galv steel fluted roof deck.

B. Roof Insulation - Mineral and Fiber Board* - Min 3/4 in. (19 mm) thick boards applied in one or more layers directly oversteel roof deck or over gypsum board sheathing laid atop steel roof deck.

C. Roof Covering* - Hot-mopped or cold-application materials compatible with mineral and fiber board insulation.

D. Structural Steel Support - Steel beam or open-web steel joist, as specified in the individual P700 or P800 SeriesRoof-Ceiling Design, used to support steel floor units. Structural steel support oriented parallel to and 1 in. to 6 in. (25 to152 mm) from wall assembly.

E. Steel Lath - When structural steel support (Item 1D) consists of open-web steel joists, 3/8 in. (10 mm) diamond meshexpanded steel lath having a nom weight of 1.7 to 3.4 lb per sq yd (0.9 to 1.8 kg/m2) shall be installed to completely coverone side of each joist which is located within 6 in. (152 mm) of wall assembly. The lath shall be secured with steel tie wireand shall be fully covered with spray applied fire resistive material.

F. Spray-Applied Fire Resistive Material* - After installation of the ceiling runner (Item 2A or 2A1), steel roof deck andstructural steel supports to be sprayed with a thickness of spray applied fire resistive material as specified in the individualP700 or P800 Series Roof-Ceiling design. The flutes of the steel deck above the structural steel supports and above theceiling runner (Item 2A or 2A1) shall be filled with spray-applied fire resistive material. As an alternate, the spray-appliedfire resistive material in the flutes above the ceiling runner may be applied to follow the contour of the steel roof deck.Excess material shall be removed from the flanges of the ceiling runner or deflection track beyond the required thicknessof spray-applied fire resistive material on the steel roof deck.

ISOLATEK INTERNATIONAL - Type 300 or Type II

W R GRACE & CO - CONN - Type MK-6/HY, MK-6/HYES, MK-65 and RG.

2. Shaft Wall Assembly - The 1 or 2 hr fire rated shaft wall assembly shall be constructed of the materials and in the mannerdescribed in the individual U400 or V400 Series Wall and Partition Design in the UL Fire Resistance Directory. The wall shallinclude the following construction features:

A. Floor, Wall and Ceiling Runners - "J"-shaped runner, min 2-1/2 in. (64 mm) wide with unequal legs of 1 in. (25 mm) and2 in. (51 mm), fabricated from min 24 MSG galv steel. Runners positioned with short leg toward finished side of wall.Runners attached to ceiling, walls and floor with steel fasteners spaced max 24 in. (610 mm) OC. As an alternate to the"J"-shaped runner, a min 2-1/2 in. (64 mm) wide by 1 or 1-1/4 in. (25 or 32 mm) deep channel formed from min 24 MSGgalv steel may be used for the floor runner.

B. Steel Studs - "C-H"-shaped steel studs to be min 2-1/2 in. (64 mm) wide and formed of min 24 MSG galv steel. Studs cut1/2 to 3/4 in. (13 to 19 mm) less in length than assembly height with bottom nesting in and resting on floor runner and withtop nesting in ceiling runner. Studs spaced 24 in. (610 mm) OC. After installation of gypsum board liner panels (Item 2D),studs secured to flange of floor runner on finished side of wall only with No. 6 by 1/2 in. (13 mm) long self-drilling,self-tapping steel screws.

C. Gypsum Board* - 1 in. (25 mm) thick by 24 in. (610 mm) wide gypsum board liner panels as specified in the individualU400 or V400 Series Wall and Partition Design. Panels cut 1 in. (25 mm) less in length than floor to ceiling height. Verticaledges inserted in "H"-shaped section of "C-H" studs. Free edge of end panels attached to long leg of "J" wall runner (Item2A) with 1-5/8 in. (41 mm) long Type S steel screws spaced max 12 in. (305 mm) OC.

D. Gypsum Board* - Gypsum board sheets, 1/2 or 5/8 in. (13 or 16 mm) thick, applied vertically or horizontally in one or twolayers on finished side of wall as specified in the individual U400 or V400-Series Wall and Partition Design. A max 1/2 in.(13 mm) gap shall be maintained between the top of the gypsum board and the spray-applied fire resistive material on theunderside of the steel deck.

3. Joint System - Max separation between bottom plane of steel floor unit and top of gypsum board liner panel (Item2D) at time of installation of joint system is 1 in. (25 mm). Max separation between spray applied fire resistivematerial on structural support member and surface of wall is 4 in. (102 mm). The joint system is designed toaccommodate a max 12.5 percent compression or extension from its installed width as measured between thebottom plane of the steel floor unit and the top of the gypsum board liner panel. The joint system shall consist offorming and fill materials, as follows:

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

January 11, 2011

2 3HW-D-0643

Page 15: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

A. Forming Material* - Nom 4 pcf (64 kg/m3) density mineral wool batt insulation. Nom 1 in. (25 mm) wide strips of mineralwool batt insulation compressed min 50 percent in thickness and inserted cut-edge first into gap above top of gypsum linerpanels prior to installation of gypsum board on finished side of wall. Sections of mineral wool batt cut to a width of 4 in.(102 mm) and stacked to attain a thickness which is 50 percent greater than the width of the linear gap between the sprayapplied fire resistive material on the structural steel member and the finished side of the shaft wall assembly. Stackedsections of mineral wool compressed minimum 33 percent in thickness and installed cut edge first into linear gap until thebottom edge is flush with the bottom surface of the spray applied fire resistive material on the structural steel member.When the spray-applied fire resistive material in the flutes above the wall follows the contour of the steel deck, sections ofmineral wool batt cut to the shape of the fluted deck and stacked to a min 6 in. (152 mm) thickness shall be installed in theflutes of the steel floor or roof deck between the top of the ceiling runner and the spray-applied fire resistive material. Themineral wool batt insulation is to be installed flush with the gypsum board surface on the side of the wall opposite thestructural steel support.

IIG MINWOOL L L C - MinWool-1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - SAFE

ROXUL INC - SAFE

THERMAFIBER INC - Type SAF

B. Fill, Void or Cavity Material* - Sealant - Min 1/8 in. (3.2 mm) wet thickness or 1/16 in. (1.6 mm) dry thickness of fillmaterial spray applied over the forming material in the linear gap above the gypsum liner panels and on the on theunderside of the forming material between the structural steel support member on the finished side of the wall. Fill materialto overlap a min of 1/2 in. (13 mm) onto the gypsum board and inside of the ceiling runner and a min of 2 in. (51 mm) ontothe spray applied material on the structural steel support member.

SPECIFIED TECHNOLOGIES INC - SpecSeal AS200 Elastomeric Spray

*Bearing the UL Classification Mark

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

January 11, 2011

3 3HW-D-0643

Page 16: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1. Floor Assembly - Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3)structural concrete. Floor may also be constructed of any min 6 in. thick (152 mm) UL Classified hollow-core Precast ConcreteUnits*.

See Precast Concrete Units (CFTV) category in Fire Resistance Directory for names of manufacturers.

2. Wall Assembly - The 1 or 2 hr fire rated gypsum board/steel stud shaft wall assembly shall be constructed of the materials andin the manner specified in the individual U400, V400 or W400 Series Wall and Partition Design in the UL Fire ResistanceDirectory. The wall shall include the following construction features:

A. Steel Floor Runner - "J"-shaped runners, min 4 in. (102 mm) deep, with unequal legs of 1 in. (25 mm) and 2 in. (51 mm),fabricated from min 24 MSG galv steel. Runners positioned with short leg toward finished side of wall. Runners attached tostructural supports with steel fasteners located not greater than 2 in. (51 mm) from ends and not greater than 24 in. (610mm) OC.

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RMarch 20, 2013

1 2

Ì68hwdÇ&Å#4-oÎ

HW-D-0697

System No. HW-D-0697

ANSI/UL2079

Assembly Ratings - 1 and 2 Hr (See Item 2)

Nominal Joint Width - 3/4 in.

Class II or III Movement Capabilities - 100% Compression (SeeItem 3)

L Rating at Ambient - Less Than 1 CFM/Lin Ft

L Rating at 400°F - Less Than 1 CFM/Lin Ft

CAN/ULC S115

F Ratings - 1 and 2 Hr (See Item 2)

FT Ratings - 1 and 2 Hr (See Item 2)

FH Ratings - 1 and 2 Hr (See Item 2)

FTH Ratings - 1 and 2 Hr (See Item 2)

Nominal Joint Width - 19 mm

Class II or III Movement Capabilities - 100% Compression (SeeItem 3)

L Rating at Ambient - Less Than 1 CFM/Lin Ft

L Rating at 400°F - Less Than 1 CFM/Lin Ft

SECTION A-A

3A2A

2C

1

1

3A

2C3B

2A

3A

1

3A

2C3A 3B 3B

2B

A

A

Page 17: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

B. Studs - "C-H", "E" (back-to-back), “I” or "C-T"-shaped studs, min 2-1/2 in. (64 mm) deep, fabricated from min 25 MSG galvsteel. Cut to lengths 3/8 to 1/2 in. (10 to 13 mm) less than floor-to-ceiling height and spaced 24 in. (610 mm) OC.

C. Gypsum Board* - 1 in. (25 mm) thick gypsum liner panels and 1/2 in., 5/8 in. or 3/4 in. (13, 16 or 19 mm) thick gypsumpanels installed as specified in the individual wall designs in the UL Fire Resistance Directory.

The hourly ratings of the joint system are equal to the hourly rating of the wall.

3. Joint System - Max separation between bottom of floor and top of wall is 3/4 in. (19 mm). The joint system consists of thefollowing:

A. Fill, Void or Cavity Material* - Factory-supplied intumescent gasket installed over the steel “J” shaped ceiling runner (Item2A) prior to attachment to bottom of concrete floor. Gypsum liner panel to be installed maintaining a maximum 3/4 in. (19mm) gap between the top of the liner panel and the bottom surface of the ceiling runner. Gypsum wallboard layer(s) to beinstalled on finished side of the wall maintaining a minimum 1/8 in. (3 mm) overlap over the intumescent paper profile attime of installation.

SPECIFIED TECHNOLOGIES INC - Speed Flex Track Top Gasket

B. Forming Material* - Nom 4 in. (102 mm) thick by 6 in. (152 mm) wide sections of 4 pcf (64 kg/m3) mineral wool battinsulation installed between studs (Item 2 B) flush with the bottom surface of the steel “J” shaped floor runner.

IIG MINWOOL L L C - MinWool-1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - Safe

ROXUL INC - Safe

THERMAFIBER INC - SAF

*Bearing the UL Classification Mark

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RMarch 20, 2013

2 2HW-D-0697

Page 18: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1. Floor Assembly - Min 4-1/2 in. (114 mm) thick steel-reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3)structural concrete. Floor may also be constructed of any min 6 in. thick (152 mm) UL Classified hollow-core Precast ConcreteUnits*.

See Precast Concrete Units (CFTV) category in Fire Resistance Directory for names of manufacturers.

2. Wall Assembly - The 1 or 2 hr fire rated gypsum board/steel stud shaft wall assembly shall be constructed of the materials andin the manner specified in the individual U400, V400 orW400 Series Wall and Partition Design in the UL Fire ResistanceDirectory. The wall shall include the following construction features:

A. Steel Floor Runner - "J"-shaped runners, min 4 in. (102 mm) deep, with unequal legs of 1 in. (25 mm) and 2 in. (51 mm),fabricated from min 24 MSG galv steel. Runners positioned with short leg toward finished side of wall. Runners attached tostructural supports with steel fasteners located not greater than 2 in. (51 mm) from ends and not greater than 24 in. (610mm) OC.

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RMarch 20, 2013

1 2

Ì67hwdÇ&Æ#4-uÎ

HW-D-0698

System No. HW-D-0698

ANSI/UL2079

Assembly Ratings - 1 and 2 Hr (See Item 2)

Nominal Joint Width - 1/2 in.

Class II or III Movement Capabilities - 100% Compression or 50% Extension (See Item 3)

L Rating at Ambient - Less Than 1 CFM/Lin Ft

L Rating at 400°F - Less Than 1 CFM/Lin Ft

CAN/ULC S115

F Ratings - 1 and 2 Hr (See Item 2)

FT Ratings - 1 and 2 Hr (See Item 2)

FH Ratings - 1 and 2 Hr (See Item 2)

FTH Ratings - 1 and 2 Hr (See Item 2)

Nominal Joint Width - 13 mm

Class II or III Movement Capabilities - 100% Compression or 50% Extension (See Item 3)

L Rating at Ambient - Less Than 1 CFM/Lin Ft

L Rating at 400°F - Less Than 1 CFM/Lin Ft

SECTION A-A

3A2A

2C

1

1

3A

2C3B

2A

3A

1

3A

2C3A 3B 3B

2B

A

A

Page 19: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

B. Studs - "C-H", "E" (back-to-back), “I” or "C-T"-shaped studs, min 2-1/2 in. (64 mm) deep, fabricated from min 25 MSG galvsteel. Cut to lengths 3/8 to 1/2 in. (10 to 13 mm) less than floor-to-ceiling height and spaced 24 in. (610 mm) OC.

C. Gypsum Board* - 1 in. (25 mm) thick gypsum liner panels and 1/2 in., 5/8 in. or 3/4 in. (13, 16 or 19 mm) thick gypsumpanels installed as specified in the individual designs in the UL Fire Resistance Directory.

The hourly ratings of the joint system are equal to the hourly rating of the wall.

3. Joint System - Max separation between bottom of floor and top of wall is 1/2 in. (13 mm). The joint system consists of thefollowing:

A. Fill, Void or Cavity Material* - Factory-supplied intumescent gasket installed over the steel “J” shaped ceiling runner (Item2A) prior to attachment to bottom of concrete floor. Gypsum liner panel to be installed maintaining a maximum 1/2 in. (13mm) gap between the top of the liner panel and the bottom surface of the ceiling runner. Gypsum wallboard layer(s) to beinstalled on finished side of the wall maintaining a minimum 1/8 in. (3 mm) overlap over the intumescent paper profile attime of installation.

SPECIFIED TECHNOLOGIES INC - Speed Flex Track Top Gasket

B. Forming Material* - Nom 4 in. (102 mm) thick by 6 in. (152 mm) wide sections of 4 pcf (64 kg/m3) mineral wool battinsulation installed between studs (Item 2 B) flush with the bottom surface of the steel “J” shaped floor runner.

IIG MINWOOL L L C - MinWool-1200 Safing

ROCK WOOL MANUFACTURING CO - Delta Board

ROCKWOOL MALAYSIA SDN BHD - Safe

ROXUL INC - Safe

THERMAFIBER INC - SAF

*Bearing the UL Classification Mark

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RMarch 20, 2013

2 2HW-D-0698

Page 20: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud shaft wall assembly shall be constructed of the materials and inthe manner specified in the individual U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shallincorporate the following construction features:A. Steel Studs - "C-H" or "C-T" shaped studs, min 2-1/2 in. (64 mm) wide by 1-1/2 in. (38 mm) deep, fabricated from min No.

25 gauge (0.6 mm thick) galv steel, spaced max 24 in. (610 mm) OC.B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max diam of circular

cutout in gypsum liner panel is 10 in. (254 mm).C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type,

thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and PartitionDesign. Max diam of circular cutout in gypsum board is 10 in. (254 mm).

The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it isinstalled.

2. Metallic Sleeve - Cylindrical sleeve fabricated from min No. 30 gauge (0.3 mm thick) galv sheet steel and having a min 2 in.(51 mm) lap along the longitudinal seam. Length of the sleeve to be equal to the thickness of the wall. Sleeve installed bycoiling the sheet steel to a diam smaller than the through opening, inserting the coil through the opening and releasing the coilto let it uncoil against the circular cutouts in the gypsum board layers. The ends of the steel sleeve shall be flush with eachsurface of the wall.

3. Through Penetrant - - One metallic pipe, tube or conduit installed concentrically or eccentrically within the firestop system.The annular space between the pipe, tube or conduit and the periphery of the sleeved opening to be min 0 in. (0 mm, pointcontact) to max 2 in. (51 mm). Pipe, tube or conduit to be rigidly supported on both sides of wall assembly. One of the followingtypes and sizes of pipe, tube or conduit may be used:A. Steel Pipe - Nom 8 in. (203 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.B. Iron Pipe - Nom 8 in. (203 mm) diam (or smaller) cast or ductile iron pipe.C. Conduit - Nom 4 in. (102 mm) diam (or smaller) rigid steel conduit, steel electrical metallic tubing (EMT) or flexible steel

conduit.D. Copper Pipe or Tube - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe or Type L (or heavier)

copper tube.

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RAugust 24, 2011

1 2

Ì86WL0Ç,SÈAAÇ(8+2Î

W-L-1251

A2

1C

4B4A

1A

4A

4B

2

3

34B

1B

A

System No. W-L-1251

ANSI/UL1479 (ASTM E814)

F Ratings - 1 and 2 Hr (See Item 1)

T Rating - 0 Hr

CAN/ULC S115

F Ratings - 1 and 2 Hr (See Item 1)

FT Rating - 0 Hr

FH Ratings - 1 and 2 Hr (See Item 1)

FTH Rating - 0 Hr

Page 21: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

4. Firestop System - The firestop system consist of the following items:A. Packing Material - Min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into sleeved opening as a permanent

form. Packing material to extend throughout thickness of wall except for a 1 in. (25 mm) deep recess on the finished side ofwall to accommodate the fill material.

B. Fill Void or Cavity Materials* - Sealant or Putty - Min 1 in. (25 mm) thickness of fill material applied within sleeve, flushwith finished surface of wall. At the point contact location, a min 3/8 in. (10 mm) diam bead of fill material shall be applied atthe penetrant/sleeve interface.

SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, or SpecSeal Putty

*Bearing the UL Classification Mark

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RAugust 24, 2011

2 2W-L-1251

Page 22: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

F Rating - 2 HrT Rating - 2 Hr

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud shaft wall assembly shall be constructed of the materials and inthe manner specified in the individual U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shallincorporate the following construction features:

A. Steel Studs - "C-H" or "C-T" shaped studs, min 2-1/2 in. (64 mm) wide by 1-1/2 in. (38 mm) deep, fabricated from min No.25 gauge (0.6 mm thick) galv steel, spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Diam of circular cutoutin gypsum liner panel to be equal to outside diam of firestop device (Item 3B).

C. Gypsum Board* - 1/2 in. or 5/8 in. (13 to 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type,thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and PartitionDesign. Diam of circular cutout in gypsum board to be max 1/2 in. (13 mm) larger than diam of through penetrant (Item 2).

The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it isinstalled.

2. Through Penetrant - One nonmetallic pipe or conduit installed centered within the firestop system. Pipe or conduit to be rigidlysupported on both sides of wall assembly. One of the following types and sizes of nonmetallic pipe or conduit may be used:

A. Polyvinyl Chloride (PVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC solid or cellular core PVC pipefor use in vented (drain, waste or vent) or closed (process or supply) piping systems.

B. Acrylonitrile Butadiene Styrene (ABS) Pipe - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 ABS solid or cellularcore PVC pipe for use in vented (drain, waste or vent) or closed (process or supply) piping systems.

C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 4 in. (102 mm) diam (or smaller) SDR17 CPVC pipe for use in vented(drain, waste or vent) or closed (process or supply) piping systems.

D. Rigid Nonmetallic Conduit+ - Nom 4 in. (102 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance withArticle 347 of the National Electrical Code (NFPA 70).

3. Firestop System - The firestop system consist of the following items:

A. Fill Void or Cavity Materials* - Sealant or Putty - (Optional) - Min 1/4 in. (6 mm) thickness of fill material applied withinannulus of gypsum board on finished side of wall.

SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant or SpecSeal Putty

B. Firestop Device* - Firestop device sized to the specific diam of the through penetrant to be friction fit into circular cutout ingypsum liner panel from the interior of the wall. Diam of circular cutout in gypsum liner panel to be equal to outside diam offirestop device. Device shall be secured to the gypsum liner panel with min 3/16 in. (5 mm) diam steel toggle bolts or mollybolts in conjunction with 1-1/4 in. (32 mm) diam steel fender washers in accordance with the accompanying installationinstructions. Second firestop device sized to the specific diam of the through penetrant installed around the throughpenetrant on the finished side of the wall and secured to the gypsum board with min 3/16 in. (5 mm) diam steel toggle boltsor molly bolts in conjunction with 1-1/4 in. (32 mm) diam steel fender washers in accordance with the accompanyinginstallation instructions.

SPECIFIED TECHNOLOGIES INC - SpecSeal Firestop Collar, SpecSeal LCC Collar or SpecSeal SSC Collar

*Bearing the UL Classification Mark

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

November 27, 2012

1 1

Ì79WL0Ç6YÈALÇ+;,QÎ

W-L-2257

21A

3A

3B

1C

2

3B3B

1B

A

A

Page 23: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud shaft wall assembly shall be constructed of the materials and inthe manner specified in the individual U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shallincorporate the following construction features:A. Steel Studs - "C-H" or "C-T" shaped studs, min 2-1/2 in. (64 mm) wide by 1-1/2 in. (38 mm) deep, fabricated from min No.

25 gauge (0.6 mm thick) galv steel, spaced max 24 in. (610 mm) OC.B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max diam of circular

cutout in gypsum liner panel is 4 in. (102 mm).C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type,

thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and PartitionDesign. Max diam of circular cutout in gypsum board is 4 in. (102 mm).

The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it isinstalled.

2. Metallic Sleeve - Cylindrical sleeve fabricated from min No. 30 gauge (0.3 mm thick) galv sheet steel and having a min 2 in.(51 mm) lap along the longitudinal seam. Length of the sleeve to be equal to the thickness of the wall. Sleeve installed bycoiling the sheet steel to a diam smaller than the through opening, inserting the coil through the opening and releasing the coilto let it uncoil against the circular cutouts in the gypsum board layers. The ends of the steel sleeve shall be flush with eachsurface of the wall.

3. Cables - Aggregate cross-sectional area of cables to be max 51 percent of the cross-sectional area of the opening. Cables tobe tightly bundled. The annular space within the firestop system shall be min 0 in. (point contact) to max 1 in. (0 to 25 mm).Cables to be rigidly supported on both sides of wall assembly. Any combination of the following types and sizes of cables maybe used:A. Max 400 pair No. 24 AWG telephone cable with PVC insulation and jacket.

B. Max 1/C - 750 kcmil copper conductor cable with XLPE or PVC insulation and jacket.C. Max 7/C No. 12 AWG with PVC insulation and jacket.D. Max 4 pair No. 24 AWG data cable with PVC insulation and jacket.E. Max RG/U coaxial cable with fluorinate ethylene jacket and insulation.

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RAugust 24, 2011

1 2

Ì76WL0Ç?nÈAAÇ(8+YÎ

W-L-3178

A

Section A-A

2 1C

4B4A1A

4B

2

3

3

1BA

System No. W-L-3178

ANSI/UL1479 (ASTM E814)

F Ratings - 1 and 2 Hr (See Item 1)

T Rating - 1/4 Hr

CAN/ULC S115

F Ratings - 1 and 2 Hr (See Item 1)

FT Rating - 1/4 Hr

FH Ratings - 1 and 2 Hr (See Item 1)

FTH Rating - 1/4 Hr

Page 24: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

F. Multiple fiber optic cables jacketed with PVC and having a max OD of 5/8 in.G. Max 3/C No. 3/0 aluminum or copper conductor SER cable with PVC insulation and jacket.H. Max 4/C No. 2/0 AWG copper or aluminum conductor steel or aluminum jacketed Metal-Clad# or Armored-Clad# cable.

AFC CABLE SYSTEMS INC4. Firestop System - The firestop system consist of the following items:

A. Packing Material - Min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into sleeved opening as a permanentform. Packing material to extend throughout thickness of wall except for a 1 in. (25 mm) deep recess on the finished side ofwall to accommodate the fill material.

B. Fill Void or Cavity Materials* - Sealant or Putty - Min 1 in. (25 mm) thickness of fill material applied within sleeve, flushwith finished surface of wall. Fill material forced into grouped cable interstices to max extent possible. At the point contactlocation, a min 1/4 in. (6 mm) diam bead of fill material shall be applied at the cable bundle/sleeve interface.

SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant or SpecSeal Putty

*Bearing the UL Classification Mark

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RAugust 24, 2011

2 2W-L-3178

Page 25: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud shaft wall assembly shall be constructed of the materials and inthe manner specified in the individual U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shallincorporate the following construction features:A. Steel Studs - "C-H" or "C-T" shaped studs, min 2-1/2 in. (64 mm) wide by 1-1/2 in. (38 mm) deep, fabricated from min No.

25 gauge (0.6 mm thick) galv steel, spaced max 24 in. (610 mm) OC.B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max diam of circular

cutout in gypsum liner panel is 8 in. (204 mm).C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type,

thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and PartitionDesign. Max diam of circular cutout in gypsum board is 8 in. (203 mm).

The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it isinstalled.

2. Metallic Sleeve - Cylindrical sleeve fabricated from min No. 30 gauge (0.6 mm thick) galv sheet steel and having a min 2 in.(51 mm) lap along the longitudinal seam. Length of the sleeve to be equal to the thickness of the wall. Sleeve installed bycoiling the sheet steel to a diam smaller than the through opening, inserting the coil through the opening and releasing the coilto let it uncoil against the circular cutouts in the gypsum board layers. The ends of the steel sleeve shall be flush with eachsurface of the wall.

3. Steel Duct - One nom 6 in. (152 mm) diam (or smaller) min No. 30 gauge (0.3 mm thick) galv steel vent duct to be installedeither concentrically or eccentrically within the firestop system. The annular space between the vent duct and the periphery ofthe opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Steel vent duct to be rigidly supported on both sidesof the wall assembly.

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RAugust 24, 2011

1 2

Ì76WL0ÇfbÈAAÇ(8+<Î

W-L-7066

A

2

1C

4B4A

1A

4A4B

2

3

3

1B4B

A

System No. W-L-7066

ANSI/UL1479 (ASTM E814)

F Ratings - 1 and 2 Hr (See Item 1)

T Rating - 0 Hr

CAN/ULC S115

F Ratings - 1 and 2 Hr (See Item 1)

FT Rating - 0 Hr

FH Ratings - 1 and 2 Hr (See Item 1)

FTH Rating - 0 Hr

Page 26: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

4. Firestop System - The firestop system consist of the following items:

A. Packing Material - Min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into sleeved opening as a permanentform. Packing material to extend throughout thickness of wall except for a 1 in. (25 mm) deep recess on the finished side ofwall to accommodate the fill material.

B. Fill Void or Cavity Materials* - Sealant or Putty - Min 1 in. (25 mm) thickness of fill material applied within sleeve, flushwith finished surface of wall. At the point contact location, a min 3/8 in. (10 mm) diam bead of fill material shall be applied atthe penetrant/sleeve interface.

SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, or SpecSeal Putty

*Bearing the UL Classification Mark

Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

RAugust 24, 2011

2 2W-L-7066

Page 27: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

F Ratings - 1 and 2 Hr (See Item 1)T Rating - 0 Hr

L Rating At Ambient - Less Than 1 CFM/sq ftL Rating At 400 F - Less Than 1 CFM/sq ft

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum board/stud shaft wall assembly shall be constructed of the materials and inthe manner specified in the individual U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shallincorporate the following construction features:

A. Steel Studs - "C-H" or "C-T" shaped studs, min 2-1/2 in. (64 mm) wide by 1-1/2 in. (38 mm) deep, fabricated from min No.25 gauge (0.6 mm thick) galv steel, spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - 1 in. (25 mm) thick, 24 in. (610 mm) wide gypsum liner panels installed vertically. Max area of opening is90 sq in. (581 cm2) with max dimension of 9-1/2 in. (241 mm).

C. Gypsum Board* - 1/2 in. or 5/8 in. (13 or 16 mm) thick, 48 in. (1.2 m) wide gypsum boards. The gypsum board type,thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall and PartitionDesign. Max area of opening is 90 sq in. (581 cm2) with max dimension of 9-1/2 in. (241 mm).

The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it isinstalled.

2. Steel Duct - One nom 8 by 8 in. (203 by 203 mm) (or smaller) min No. 30 gauge (0.3 mm thick) galv steel vent duct to beinstalled either concentrically or eccentrically within the firestop system. The annular space between the vent duct and theperiphery of the opening shall be min 1/2 in. to max 1 in. (13 to 25 mm). Steel vent duct to be rigidly supported on both sides ofthe wall assembly.

3. Firestop System - The firestop system consists of the following items:

A. Forming Material - Min 4 pcf (64 kg/m3) mineral wool batt insulation compression fit between the gypsum liner panel andthe gypsum board as a permanent form within the stud cavity. Height and width of mineral wool batt forming material to benom 12 by 12 in. (305 by 305 mm) and centered around steel duct. Thickness of batt to be min 10 percent greater than thedepth of the stud cavity to maintain compression between gypsum liner panel and gypsum board.

B. Fill, Void or Cavity Material* - Sealant - Fill material thickness installed to full depth of gypsum board layers on each sideof wall assembly.

SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal LC150 Sealant orSpecSeal LE600 Sealant.

*Bearing the UL Classification Mark

R Created or Revised:Reproduced courtesy of Underwriters Laboratories, Inc.

PAGE OF(800)992-1180 (908)526-8000 FAX (908)231-8415 E-Mail:[email protected] Website:www.stifirestop.com

April 24, 2009

1 1

Ì79WL0ÇfzÈAAÇ$8)IÎ

W-L-7090

3A3B

2

A

3A

1B 1C

1A

3B3B

A

Page 28: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

Certificate of Conformance • Technical Service 1-800-992-1180 • www.stifirestop.com

SpecSeal® Series SSS Intumescent Sealant SpecSeal® Series LCI Intumescent Sealant SpecSeal® Series LC Firestop Sealant

SpecSeal® Series ES Elastomeric Sealant SpecSeal® Series SIL300 Silicone Sealant SpecSeal® Series SIL300SL Silicone Sealant

Pensil® PEN300 Silicone Sealant Pensil® PEN300SL Silicone Sealant Pensil® PEN200 Silicone Foam

Type WF300 Firestop Caulk SpecSeal® Series AS200 Elastomeric Spray SpecSeal® Series FT Fast Tack™ Firestop Spray

SpecSeal® Series SSP Putty & Putty Pads SpecSeal® Series EP PowerShield™ Box Insert SpecSeal® Series SSM Firestop Mortar

SpecSeal® Series SSB Firestop Pillows SpecSeal® Series CS Composite Sheet SpecSeal® Series SSW Wrap Strips

SpecSeal® Series LCC Firestop Collars SpecSeal® Series SSC Firestop Collars SpecSeal® Series RTC Firestop Collars

SpecSeal® Series FP Firestop Plugs SpecSeal® Series CD Cast-In Firestop Devices FyreFlange™Firestop Angle

EZ-Path® Series 22 EZ-Path® Series 33 EZ-Path® Series 44 or 44+

Ready™ Sleeve Ready™ Sleeve Split Ready™ Firestop Grommet

SpecSeal® Series SSAMW Mineral Wool SpecSeal® SpeedFlex™ Fire Rated Joint Profile

Description:

SpecSeal® Firestop Products; Pensil® Silicone Sealants; EZ-Path® Fire Rated Pathways; Ready® Sleeve Firestop Sleeves; STI Firestop Products

Included Products:

These products are tested to one or more of the following standards:

• ASTM E814 (ANSI/UL1479) Standard Test Method for Fire Tests of Penetration Firestop Systems

• ASTM E1966 (ANSI/UL2079) Standard Test Method for Fire-Resistive Joint Systems

• ASTM E119 (ANSI/UL263) Standard Test Methods for Fire Tests of Building Construction and Materials

• ASTM E2307 Standard Test Method for Determining Fire Resistance of Perimeter Fire Barrier Systems Using Intermediate Scale, Multi-Story Test Apparatus

• ASTM E1399 Standard Test Method for Cyclic Movement and Measuring the Minimum and Maximum Joint Widths of Architectural Joint Systems

• ASTM E84 (ANSI/UL723) Standard Test Method for Surface Burning Characteristics of Building Materials

• CAN/ULC S115 Standard Method of Fire Tests of Firestop Systems

• CAN/ULC S101 Standard Methods of Fire Endurance Tests of Building Construction and Materials

• IMO Resolution A.754(18)

Chemical Content Statement:

No asbestos, PCB’s, lead, or water-soluble intumescent ingredients are used or contained in these products.

Paul M. JankowskiQuality Control Manager

James P. Stahl Jr., CFPSVice President of Engineering

GENERAL CERTIFICATE OF CONFORMANCEJanuary 25, 2011

Page 29: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1Technical Service 1-800-992-1180www.stifirestop.com

SERIES AS200 ELASTOMERIC SPRAY

PRODUCT DATA SHEET

APPLICATIONSSpecSeal® Elastomeric Spray is designed primarily for

the protection of construction joints, curtain wall safing

gaps, and certain through-penetrations.

PRODUCT DESCRIPTIONSpecSeal® Series AS200 Elastomeric Spray is a non-halogenated latex-based, highly elastomeric coating designed to provide passive smoke and fire protection in construction joints.

SpecSeal® Series AS200 Elastomeric Spray is engineered to adhere to virtually all construction surfaces and may be applied using airless spray equipment or with a brush (ideally for, but not limited to, small applications or touch ups).

SpecSeal® Series AS200 Elastomeric Spray dries to form a flexible shield against the propagation of fire. Its premium latex binder system is totally resistant to water and will not re-emulsify after drying. SpecSeal® Series AS200 Elastomeric Spray contains no inorganic fibers, asbestos, solvents.

• Water-Based for easy installation and cleanup

• Non-halogenated.

• Thixotropic for high-build application.

• Auto Bonding. • Safe... no solvents! No asbestos!

• Flexible! • Water Resistant!• Low Abrasion for longer pump life and less maintenance.

• UL Classified.

• Tested with spray applied fire resistive materials (SFRM).

• Paintable

FEATURES

When applied to a wet film thickness of 1/8" (3.2 mm) over appropriate backing materials, SpecSeal® Series AS200 Elastomeric Spray has been successfully tested in one, two, three and four hour joints tested in accordance with ASTM E1966 (ANSI/UL2079) and CAN/ULCS115. This product has also been tested for use in Perimeter Fire Barrier Systems in accordance with ASTM E2307. Consult factory for individual system designs and application requirements.

LIMITATIONS: Use product as per manufacturer’s instructions. Use only in applications per the manufacturer’s tested and published designs or specific recommendations. End user must ultimately determine the suitability of the product and designs to his specific requirement and assumes responsibility for its use. PRODUCT CONTAINS WATER AND IS CONDUCTIVE UNTIL DRY. DO NOT APPLY IN THE PRESENCE OF EXPOSED OR ENERGIZED ELECTRICAL CONDUCTORS.

PERFORMANCE

PHYSICAL PROPERTIES

STI Product Data Sheet • Series AS200 Elastomeric Spray • FOD-5042-1292

PROPERTIES: SERIES AS SPRAYColor Pale Blue and Red

Odor Mild Latex

Specific Gravity 1.3

Solids Content by Weight

Solids Content by Volume

74%

66.4%

Flame Spread 0*

Smoke Developed 25*

Movement ±50%**

Coverage 12.8 sq ft/gal @ 1/8˝ (0.31 sq m/L @ 3.2 mm)

Viscosity 110,000 cps

pH 7.5

PROPERTIES: SERIES AS SPRAYSolvent Content None

Plasticizer None

In-Service Temp. ≤185° F (85° C)

Storage Temp. 40°F (4°C) - 95°F (35°C)

Drying Time Tack Free 2 Hours

Dry Through 24-48 HoursA

STC Rating 61

VOC ContentB 10 g/L

Shelf Life 18 Months

* Tested to ASTM E84 (UL723) @ 14% coverage.**500 Cycles per UL2079, AC30 (ICBO) and ASTM E1399A Dependent on temperature and humidity.BPer ASTM D3960 EPA Fed. Reference Method 24

FILL, VOID OR CAVITY MATERIALS FOR USE IN JOINT SYSTEMS & THROUGHPENETRATION FIRESTOP

SYSTEMS. SEE UL FIRE RESISTANCE DIRECTORY.

3L73

FBC™ System Compatible indicates that this product has been tested, and is monitored on an ongoing basis, to assure its chemical compatibility with FlowGuard Gold®, BlazeMaster® and Corzan® pipe and fittings. FBC, FlowGuard Gold, BlazeMaster and Corzan are licensed trademarks of The Lubrizol Corporation.

Page 30: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

2 Technical Service 1-800-992-1180www.stifirestop.com

STI Product Data Sheet • Series AS200 Elastomeric Spray • FOD-5042-1292

FIG. 2: SLAB-EDGE SAFING GAP APPLICATIONS

UL System No. CW-S-2061F Rating – 2 Hr • T Rating – 1/4 HrLinear Opening Width - 8 In Max

L Rating At Ambient - Less than 1 CFM/Lin FtL Rating At 400o F - Less Than 1 CFM/Lin Ft

FIG. 1: METALLIC PIPE PENETRATIONS - CONCRETE/MASONRY FLOORS & WALLS

UL System No. C-AJ-1318F Rating – 2 Hr • T Rating – 0 Hr

Steel or Iron Pipe: <12", Copper Pipe: <6"Annulus: Point Contact to 2"

Forming Material: Nom 4 pcf mineral wool to 4" depthSpray Depth: 1/8" wet depth (+1/2" overlap)

UL System No. HW-D-0043Assembly Ratings - 1,2,3 and 4 Hr.Nominal Joint Widths - 1 and 2 In.

L Rating At Ambient - Less than 1 CFM/Lin Ft.L Rating At 400o F - Less Than 1 CFM/Lin Ft.Class II Movement Capabilities - 40 or 50%

Compression and extension.

FIG. 3: HEAD-OF-WALL APPLICATIONS

Page 31: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

3Technical Service 1-800-992-1180www.stifirestop.com

STI Product Data Sheet • Series AS200 Elastomeric Spray • FOD-5042-1292

AVAILABILITY

MAINTENANCEInspection: Installations should be inspected periodically for subsequent damage. Following safety precautions listed below (See Precautionary Information) and pertinent installation guidelines, remove coating in damaged areas down to undamaged material. Reapply fresh coating material to original coating thickness.

TECHNICAL SERVICE

Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL Systems, Material Safety Data Sheets and other technical information is available at the Technical Library at www.stifirestop.com.

PRECAUTIONARY INFORMATION

Consult Material Safety Data Sheet for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. The use of an OSHA or NIOSH approved mask for dust and mist environment is recommended. Apply in areas with adequate ventilation.

SpecSeal® Series AS200 Elastomeric Spray is available worldwide from authorized distributors. Consult factory for the names and locations of the nearest sales representatives or distributors..

GENERAL: Areas to be protected must be clean and free of oil, loose dirt, rust or scale. Recommended storage temperatures range between40°F (4°C) and 95°F (35°C). Installation temperature shall be between 40˚F (4˚C) and 95˚F (35˚C). Although not a requirement, the optimal application temperature range is 60°F (16°C) to 90°F (32°C). When applying product at the lower end of the temperature range, warming the material to 70°F (21°C) will enhance drying characteristics. Drying time will vary according to prevailing temperature and humidity. Allow to thoroughly dry before exposure to moisture.

Consult appropriate manufacturer’s drawing for system design requirements. Forming or packing materials are required as an integral part of various system designs.

Coating may be applied by airless spray in a single pass up to 3/16" (4.8mm) wet coating depth. If applying by brush or spraying on vertical surfaces where coating appears to be prone to slumping, multiple coats or the application of a thin tack coat may be required. DO NOT ATTEMPT TO THIN PRODUCT BY ADDING WATER. When dry, may be painted using most non-solvent based paints.

INSTALLATION INSTRUCTIONS

SPECIFICATIONS

The fire protective joint coating shall be a water-based, non-halogenated elastomeric coating and shall contain no solvents, inorganic fibers, nor asbestos. The coating shall dry to form a flexible, moisture resistant film and shall adhere to all common construction surfaces. The coating shall provide up to 50 percent movement. The coating shall be thixotropic and shall be capable of being applied by brush or by airless spray. The approved coating shall be SpecSeal® Series AS200 Elastomeric Spray.

SPECIFIED DIVISIONS

DIV. 7 07 84 00 Through-Penetration Firestopping

DIV. 4 04 22 00 Concrete Unit Masonry

DIV. 7 07 21 00 Thermal Insulation

DIV. 8 08 44 00 Curtain Wall and Glazed Assemblies

Page 32: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

4 Technical Service 1-800-992-1180www.stifirestop.com

STI Product Data Sheet • Series AS200 Elast Spray • FOD-5042 01/2012

Important Notice: All statements, technical information, and recommendations contained herein are based upon testing believed to be reliable, but the accuracy and completeness thereof is not guaranteed.

WARRANTY: Specified Technologies Inc. manufactures its goods in a manner to be free of defects. Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt notification, will at its option, exchange or repair the goods or refund the purchase price.

Limitations and Exclusions: THIS WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.No statement or recommendation not contained herein shall have any force or effect unless in an agreement signed by officers of seller and manufacturer.

MADE IN THE USA – COPYRIGHT © 2012 SPECIFIED TECHNOLOGIES INC.

ORDERING INFORMATION

SpecSeal® Elastomeric Spray is available in 5 gal. pails, 55 gal. drums are available on a special order basis.

AS205 Pale Blue Color 5 gal. Pail 1,155 cu. in. (19 liters)AS205R Red Color 5 gal. Pail 1,155 cu. in. (19 liters)

CITY OF NEW YORK MEA 310-99-M

210 Evans Way, Somerville NJ 08876 USA • Phone: 800.992.1180 • Fax: 908.526.9623

TABLE A: APPLICATION EQUIPMENT

NOTICE: Spray application of SpecSeal Elastomeric Spray requires airless spray equipment meeting the following specifications:

Working Pressure: Min. 2500 PSI (172 Bar)

Delivery: Min. .72 U.S. gpm (2.7 l/min.) recommended

Spray Tip Orifice: 0.023˝ to 0.026˝ (0.58 to 0.66 mm) recommended

Wetted Parts All seals and contact surfaces suitable for contact with latex emulsions.

A minimum 3/8˝ (9.5 mm) fluid line is required, a 1/2˝ (13 mm) line is preferred. Consult pump manufacturer for long hose runs or lifts to higher elevations. A reversible spray tip is recommended. A 6˝ (152 mm) fan pattern is suggested to minimize overspray.

The following airless spray equipment has demonstrated suitability for application of this product. STI makes no warranties concerning the suitability or use of this equipment and has no affiliation of any kind with its manufacturer.

Manufacturer Model Number & Description

Titan Tool Inc. 740ix Electric Airless Sprayer

Graco Inc. Ultra Max II 695 Electric Airless Sprayer

Page 33: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

SERIES ES ELASTOMERIC SEALANT

1Technical Service 1-800-992-1180www.stifirestop.com

PRODUCT DESCRIPTIONAPPLICATIONS

PERFORMANCE

• Water-Based for easy installation and cleanup.

• Non-halogenated.

• Thixotropic for high-build application.

• Auto bonding.

• Safe... No solvents! No asbestos!

• Elastomeric!

• Water-Resistant!

• UL Classified.

• Acoustical sealant

• Paintable

FEATURES

PRODUCT DATA SHEET

FILL, VOID OR CAVITY MATERIALS CLASSIFIED BY UNDERWRITERS LABORATORIES INC. ® FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS.

SEE UL FIRE RESISTANCE DIRECTORY

UNDERWRITERS LABORATORIES INC.® CLASSIFIED WALL PROTECTION MATERIAL. SEE PRODUCT CATEGORY IN UL FIRE RESISTANCE DIRECTORY

CLASSIFIED FILL, VOID, OR CAVITY MATERIALS FOR USE IN THROUGH-PENETRATION FIRESTOP SYSTEMS. SEE UL DIRECTORY OF PRODUCTS CERTIFIED FOR CANADA AND UL FIRE RESISTANCE DIRECTORY

PHYSICAL PROPERTIES

SpecSeal® Elastomeric Sealant is designed primarily for the protection of construction joints.

SpecSeal® Elastomeric Sealant is a non-halogenated latex-based, highly elastomeric caulk designed to provide passive smoke and fire protection in construction joints. This material is also designed to restore sound attenuation properties to sound-rated ceilings and partitions.

SpecSeal® Elastomeric Sealant is engineered to adhere to virtually all construction surfaces and may be applied using standard caulking equipment or by troweling. SpecSeal® Elastomeric Sealant dries to form a flexible shield against the propagation of fire. Its premium latex binder system is totally resistant to water and will not re-emulsify after drying. SpecSeal® Elastomeric Sealant contains no inorganic fibers, asbestos, or solvents.

When applied to a wet film thickness of 1/4" (6.3 mm) to 1/2" (12.5 mm) over appropriate backing materials, SpecSeal® Elastomeric Sealant has been successfully tested in one, two, three and four hour joints when tested in accordance with UL2079 (ASTM E1966). All tested systems have been cycled 500 times at total movement up to + 25%. Consult factory for individual system designs and application requirements. LIMITATIONS: Use product as per manufacturer’s instructions. Use only in applications per the manufacturer’s tested and published designs or per specific recommendations. End user must ultimately determine the suitability of the product and designs to his specific requirement and assumes responsibility for its use.

STI Product Data Sheet • ES Elastomeric Sealant • FOD-5032 01/2012

Table A: PRODUCT NAME Series ES

Color Pale Blue or Red

Odor Mild Latex

Density 10 Lb/Gal (1.19 kg/L)

Solids 66%

pH 7.5

Solids Content By Weight 81%

Solids Content By Volume 71.5%

In-Service Temp. <185°F (85°C)

Storage Temp. 40°F (4°C) - 95°F (35°C)

Flame Spread 5*

Smoke Development 5*

Movement ±25%**

Solvent Content None

Drying Time Tack Free 2 HoursA

Dry through 5 to 7 daysA

STC Rating 62

Shelf Life 2 yrs

VOC 43 g/L

* Tested to ASTM E84 (UL723) at 14% surface

**500 Cycles per UL2079, AC30 (ICBO) and ASTM E1399ADependent on temperature and humidity

Page 34: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

2 Technical Service 1-800-992-1180www.stifirestop.com

INSTRUCTIONS

FIG. 3: HEAD-OF-WALL JOINT - GYPSUM WALLBOARD WALL TO CONCRETE FLOOR

FIG. 4: HEAD-OF-WALL JOINT - GYPSUM WALLBOARD WALL CUT TO FIT CONTOURS OF STEEL DECK

FIG. 5: HEAD-OF-WALL JOINT - GYPSUM WALLBOARD WALL TO CONCRETE OVER STEEL DECK

GENERAL: Areas to be protected must be clean and

free of oil, loose dirt, rust or scale. Recommended

storage and application temperatures range between

40°F (4°C) and 95°F (35°C). When applying product

at the lower end of the temperature range, warming

the material to 70°F (21°C) will enhance drying

characteristics. Drying time will vary according

to prevailing temperature and humidity. Allow to

thoroughly dry before exposure to moisture.

Consult appropriate manufacturer’s drawing for

system design requirements. Forming or packing

materials may be required as an integral part of

various system designs. See Table B for estimation

information.

Sealant is auto-bonding and may be applied in stages. DO NOT ATTEMPT TO THIN PRODUCT BY ADDING WATER.

THIS PRODUCT IS DESIGNED FOR PROFESSIONAL INSTALLATION ONLY. This sealant is designed to contract while drying. Proper joint design is critical to sealant performance. Avoid three point adhesion through the use of appropriate backing or bond-breaking materials.

See Figure 2 for recommended joint designs. Consult ASTM C1193 Standard Guide for Use of Joint Sealants for additional guidelines concerning the proper application of sealant materials.

STI Product Data Sheet • ES Elastomeric Sealant • FOD-5032 01/2012

SPECIFICATIONS

The fire protective sealant shall be a water-based, non-halogenated, elastomeric and shall contain no solvents, inorganic fibers, nor asbestos. The sealant shall dry to form a flexible, moisture resistant seal and shall adhere to all common construction surfaces. The sealant shall have demonstrated sound attentuation properties. The approved sealant shall be SpecSeal® Elastomeric Sealant.

SPECIFIED DIVISIONSDIV. 7 — 07 84 00 FirestoppingDIV. 7 — 07 84 43 Fire Resistant Joint Sealants

MAINTENANCE

Inspection: Installations should be inspected

periodically for subsequent damage. Following

safety precautions listed in Precautionary Information

and pertinent installation guidelines, remove coating

in damaged areas down to undamaged material.

Reapply fresh coating material to original coating

thickness.

UL System No. HW-D-0079Assembly Rating – 1 & 2 Hr • Movement Capabilities: 25% Compress.

Nominal Joint Width: 3/4˝ • Forming Material: In 1 hr walls, apply bond breaker tape to ceiling track.Sealant Depth: 5/8˝ depth on both sides.

UL System No. HW-D-0103Assembly Rating – 1 & 2 Hr • Movement Capabilities: 25% Compress.

Nominal Joint Width: 3/4˝ • Forming Material: In 1 hr walls, apply bond breaker tape to ceiling track.Sealant Depth: 1/2˝ depth on both sides.

UL System No. HW-D-0034Assembly Rating – 1 & 2 Hr • Movement Capabilities: ±25% Compress/Extend.

Nominal Joint Width: 1˝ • Forming Material: Nom 4 pcf mineral wool to full depth.Sealant Depth: 1/2˝ depth on both sides.

Page 35: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

3Technical Service 1-800-992-1180www.stifirestop.com

FIG. 6: HEAD-OF-WALL JOINT - MASONRY WALL TO CONCRETE OVER STEEL DECK

UL System No. HW-D-0039Assembly Rating – 2 Hr

Movement Capabilities: ±25% Compress/Extend.Nominal Joint Width: 1˝

Forming Material: Nom 4 pcf mineral wool to full depth.Sealant Depth: 1/4˝ depth on both sides.

FIG. 7: HEAD-OF-WALL JOINT - MASONRY WALL TO CONCRETE FLOOR

UL System No. HW-D-0041Assembly Rating – 3 Hr

Movement Capabilities: ±12.5% Compress/Extend or 25% Compress.Nominal Joint Width: 1˝ or 3/4˝ (See System).Forming Material: Optional foam backer rod.

Sealant Depth: 1˝ or 1/2˝ (See System) on both sides.

FIG. 8: FLOOR-TO-FLOOR JOINT - CONCRETE FLOOR TO CONCRETE FLOOR

UL System No. FF-D-0005Assembly Rating – 3 Hr

Movement Capabilities: ±12.5% Compress/ExtendNominal Joint Width: 1˝

Forming Material: Optional foam backer rod.Sealant Depth: 1/2˝ top and bottom.

FIG. 9: FLOOR-TO-WALL JOINT - CONCRETE FLOOR TO \CONCRETE WALL

UL System No. FW-D-0005Assembly Rating – 3 Hr

Movement Capabilities: ±12.5% Compress/ExtendNominal Joint Width: 1˝

Forming Material: Optional foam backer rod.Sealant Depth: 1/2˝ top and bottom.

FIG. 10: FLOOR-TO-FLOOR JOINT - CONCRETE FLOOR TO CONCRETE FLOOR

UL System No. FF-D-1008Assembly Rating – 3 Hr

Movement Capabilities: ±15% Compress/ExtendNominal Joint Width: 4˝

Forming Material: Nom 4 pcf mineral wool to 4˝ depth.Sealant Depth: 1/2˝ depth of sealant.

FIG. 11: FLOOR-TO-WALL JOINT - CONCRETE FLOOR TO CONCRETE WALL

UL System No. FW-D-1007Assembly Rating – 3 Hr

Movement Capabilities: ±15% Compress/ExtendNominal Joint Width: 4˝

Forming Material: Nom 4 pcf mineral wool to 4˝ depth.Sealant Depth: 1/2˝ depth of sealant.

STI Product Data Sheet • ES Elastomeric Sealant • FOD-5032 01/2012

Page 36: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

4 Technical Service 1-800-992-1180www.stifirestop.com

IMPORTANT NOTICE: All statements, technical information, and recommendations contained herein are based upon testing believed to be reliable, but the accuracy and completeness thereof is not guaranteed.

WARRANTYSpecified Technologies Inc. manufactures its goods in a manner to be free of defects. Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt notification, will at its option, exchange or repair the goods or refund the purchase price.

LIMITATIONS AND EXCLUSIONS: THIS WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.No statement or recommendation not contained herein shall have any force or effect unless in an agreement signed by officers of seller and manufacturer.

MADE IN THE USA – COPYRIGHT © 2012 SPECIFIED TECHNOLOGIES INC.

CITY OF NEW YORK MEA 290-98-M

AVAILABILITY

TECHNICAL SERVICE

PRECAUTIONARY INFORMATION

Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL Systems, Material Safety Data Sheets and other technical information is available at the Technical Library at www.stifirestop.com.

Consult Material Safety Data Sheet for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. Apply in areas with adequate ventilation.

SpecSeal® Elastomeric Sealant is available from authorized distributors nationwide. Consult factory for the names and locations of the nearest sales representatives or distributors.

Table B: PRODUCT ESTIMATION INFORMATION (Construction Joints)JOINT PER 1/4” INSTALLED DEPTH PER 1/2” INSTALLED DEPTH PER 1” INSTALLED DEPTH

WIDTH CU IN/FT FT/GAL GAL/100 FT CU IN/FT FT/GAL GAL/100 FT CU IN/FT FT/GAL GAL/100 FT

0.5 1.5 154 .65 3 77.0 1.3 6 38.5 2.6

0.75 2.3 102 .95 4.5 51.3 1.9 9 25.7 3.9

1.0 3.0 77 1.3 6.0 38.5 2.6 12 19.3 5.2

1.5 4.5 51 2 9.0 25.7 3.9 18 12.8 7.8

2.0 6.0 38 2.6 12 19.3 5.2 24 9.6 10.4

2.5 8.0 31 3.3 15 15.4 6.5 30 7.7 13.0

3.0 9.0 25 3.9 18 12.8 7.8 36 6.4 15.6

3.5 11 22 4.6 21 11.0 9.1 42 5.5 18.2

4.0 12 19 5.2 24 9.6 10.4 48 4.8 20.8

5.0 15 15 6.5 30 7.7 13.0 60 3.9 26.0

6.0 18 12 7.8 36 6.4 15.6 72 3.2 31.2

ORDERING INFORMATIONSpecSeal® Elastomeric Sealant is available in caulk tubes, sausages and pails.

Cat. No. Description

ES100 10.1 oz. Tube (300 ml) 18.2 cu.in.ES129 29.0 oz. Tube (858 ml) 52 cu.in.ES120 20 oz. Sausage (592 ml) 36 cu. in.ES105 5 Gal. Pail (19.0 liters) 1,155 cu.in.

STI Product Data Sheet • ES Elastomeric Sealant • FOD-5032 01/2012

210 Evans Way, Somerville NJ 08876 USA • Phone: 800.992.1180 • Fax: 908.526.9623

Page 37: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

1Technical Service 1-800-992-1180www.stifirestop.com

SpecSeal® Series SSS Sealant is a latex based, high solids firestop compound. This material, when properly installed, will effectively seal penetration openings against the spread of fire, smoke, toxic gasses and water.

SpecSeal® Series SSS Sealant features STI’s patented and proprietary two-stage intumescent technology. When exposed to high temperatures or fire, this material expands aggressively in a highly directionalized fashion to quickly close off voids left by the burning or melting of combustible materials.

SpecSeal® Series SSS Sealant’s unique multi-viscosity formula yields a single grade that has excellent caulking properties as well as high build properties on vertical or overhead surfaces. This single grade may be pumped, caulked (standard cartridge or bulk loaded), knifed or troweled. In addition, SpecSeal Series SSS Sealant does not contain PCB’s or asbestos.

SpecSeal® Series SSS Sealant is storage stable (when stored according to the manufacturer’s recommendations) and will not separate nor shrink when dried. SpecSeal Series SSS Sealant will adhere to all common construction and penetrant materials and contains no solvents that might adversely effect plastic pipes or cable jackets.

3L73

SERIES SSS INTUMESCENT SEALANT

STI Product Data Sheet • Series SSS Intumescent Sealant • FOD-5001 05/2010

PRODUCT DATA SHEET

APPLICATIONS PRODUCT DESCRIPTION

SpecSeal® Series SSS Sealant is used to seal through-penetrations as well as construction gaps and blank openings. SpecSeal Series SSS has been tested for use with metallic penetrants up to 30" (762 mm) trade size. This product is also used with other SpecSeal® Products such as SpecSeal® Firestop Collars and Wrap Strips.

See Table A for a summary application list.

• Water-Based Easy installation, cleanup, and disposal.• Two-Stage Intumescence Extremely fast and directionalized expansion.• Endothermic Fillers Absorb heat & release water.• High Solids Formula No shrinkage!• Sandable & Paintable (when dry)• Water-Resistant Will not re-emulsify when dry!• Safe Safe for contact with plastics. • Red Color Easy identification and inspection.• Multi Viscosity Grade Excellent caulking properties along with high build capabilities. • Excellent Smoke Seal

FEATURE BENEFIT

PERFORMANCESpecSeal® Series SSS Sealant is the basis for systems that meet the exacting criteria of ASTM E814 (UL1479) as well as the time-temperature requirements of ASTM E119 (UL263). Systems have been tested for all common forms of construction and most common penetrants with ratings up to 4 hours. STI firestop systems are designed to maximize the fire resistance of the seal by not only sealing off the spread of fire and hot gasses but also by minimizing the amount of heat conducted through the assembly. Thus all systems have been designed to provide T Ratings capable of matching the rating of the wall or floor assembly (where possible) when tested without penetrants.

FILL, VOID OR CAVITY MATERIALS FOR USE IN JOINT SYSTEMS AND THROUGH-PENETRATION FIRESTOP SYSTEMS. SEE UL

DIRECTORY OF PRODUCTS CERTIFIED FOR CANADA AND UL FIRE RESISTANCE DIRECTORY.

Properties Series SSS

Color Red

Odor Mild Latex

Density 9.4 lb/gal (1.13 kg/L)

Solids Content 80% ± 2%

pH 8.3

In Service Temperature -10°F (-23˚C) - 185°F (85˚C)

Storage Temperature 40°F (4˚C) - 95°F (35˚C)

Flame Spread 0*

Smoke Developed* 10** Tested to ASTM E84 (UL723) at 14% surface coverage (modified test for sealants and caulks)

Properties Series SSS

STC Rating (ASTM E90/ASTM C919) 62

VOC Content (EPA Method 24/ASTM D3960)

0.18 lbs/gal (22.0 g/L)

Shelf Life 2 yrs

Expansion Begins 230°F (110°C) 1st Stage

350°F (177°C) 2nd Stage

Expansion Range 230°F to > 1,000°F

(110°C to > 538°C)

Volume Expansion > 500% Free Expansion

PHYSICAL PROPERTIES

Page 38: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

2 Technical Service 1-800-992-1180www.stifirestop.com

Shown below and on the following page are just a few of the most common applications for SpecSeal Series SSS Sealant. Consult the Technical Library at www.stifirestop.com for over 200 avail-

able designs utilizing this product.

Table A: APPLICATIONSTESTED AND CLASSIFIED

FOR FIRE RESISTANCE

• Metallic Pipes including steel, iron, or copper pipe and tubing through all common constructions.

• Nonmetallic Pipes, Conduits &Tubing including PVC, CPVC, PVDF, PEX, PEX-

AL-PEX, ABS, PB through all common constructions.

• Cable, Cable Trays & Bus Duct • HVAC Ductwork• Insulated Pipes• Multi-Service Penetrations including AC line sets, electrical, telephone,

or TV service entrance and interior penetrations.

• Complete Wood Floor firestopping package for electrical, plumbing, HVAC, TV and telephone.

Fig. 1: METALLIC PIPE PENETRATIONS - CONCRETE/MASONRY FLOORS & WALLS

UL SYSTEM C-AJ-1079F Rating: 4 Hr • T Rating: 0

Steel or Iron Pipe: 24", Copper Pipe 6"Annulus: Point Contact to 4" • S alant Depth: 1/2" Forming Mate-

rial: Nom 4 pcf Mineral WoolThickness: 1-1/2" for 6" Steel or Iron Pipe3" for 4" Copper or 6" Iron or Steel Pipe

UL SYSTEM C-AJ-1217F Rating: 4 Hr • T Rating: 0

Steel or Iron Pipe: 30", Copper Pipe 6"Annulus: Point Contact to 2" • S alant Depth: 1/2"

Forming Material: Nom 4 pcf Mineral WoolTightly Packed to a 3" Depth.

Fig. 2: INSULATED METALLIC PIPE PENETRATIONS - CONCRETE/MASONRY FLOORS & WALLS

UL SYSTEM C-AJ-5087F Rating: 2 Hr • T Rating: 1

Steel or Iron Pipe: 24"Insulated with 2" Thick Fiber Glass or Mineral Wool Pipe Insulation

Annulus: 1/2" to 1-1/2" • Sealant Depth: 1/2" Forming Material: Nom 4 pcf Mineral Wool Tightly Packed to a 4" Depth.

The firestopping sealant shall be a one-part, two-stage intumescent latex compound. The sealant when exposed to high heat or flame shall be capable of expanding a minimum of 8 times. Range of continuing expansion shall be from 230°F to >1,000°F (110°C to > 538°C). The sealant shall be thixotropic and shall be capable of caulking or troweling onto vertical surfaces or overhead. The sealant shall be UL Classified and/or FM Systems Approved and tested to the requirements of ASTM E814 (UL1479).

SPECIFIED DIVISIONSDIV. 7 07840 Through-Penetration Firestopping

DIV. 13 13900 Special Construction Fire Suppression & Supervisory Systems

DIV. 15 15250 Mechanical Insulation – Fire Protection

DIV. 16 16050 Basic Electrical Materials & Methods

SPECIFICATIONS

STI Product Data Sheet • Series SSS Intumescent Sealant • FOD-5001 05/2010

Pipe Size Diameter of Opening (in.) 1.5 2.0 3.0 4.0 5.0 6.0 7.0 8.0 10 12 14 26Trade Pipe

Size O.D.

0.5" 0.840 0.3 0.6 1.6 3.0 4.8 6.9 9.5 12.4 19.5 28.1 38.3 132.61" 1.315 0.1 0.4 1.4 2.8 4.6 6.7 9.3 12.2 19.3 27.9 38.1 132.41.5" 1.900 1.1 2.4 4.2 6.4 8.9 11.9 18.9 27.6 37.8 132.02" 2.375 0.7 2.0 3.8 6.0 8.5 11.5 18.5 27.2 37.4 131.62.5" 2.875 0.1 1.5 3.3 5.4 8.0 10.9 18.0 26.7 36.9 131.13" 3.500 0.7 2.5 4.7 7.2 10.2 17.2 25.9 36.1 130.33.5" 4.000 1.8 3.9 6.5 9.4 16.5 25.1 35.3 129.64" 4.500 0.8 3.0 5.6 8.5 15.6 24.2 34.4 128.76" 6.625 1.1 4.0 11.1 19.7 29.9 124.28" 8.625 4.9 13.6 23.8 118.010" 10.750 5.6 15.8 110.012" 12.750 6.6 100.824" 24.000 19.6IMPORTANTNOTE:Thistableisforestimationpurposesonly.ConsultULFireResistanceDirectoryorSTIProduct&ApplicationGuideforspecificinstallationrequirementsandlimitationsMetricEstimationTableavailableuponrequest.

SEALANT REQUIREMENTS IN CUBIC INCHES PER 1/4 INCH OF INSTALLED DEPTH*

*Different Sealant Depth?

1/2" Multiply by 2 5/8" Multiply by 2.5 1" Multiply by 4 1-1/4" Multiply by 5

Page 39: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

3Technical Service 1-800-992-1180www.stifirestop.com

Fig. 5: BARE & INSULATED METALLIC PIPE PENETRATIONS - RATED GYPSUM WALLBOARD ASSEMBLIES

UL SYSTEM W-L-1049F Rating: 2 hr • T Rating: 0 hr

Steel or Iron Pipe: 24", Copper Pipe: 6"Annulus: Point Contact to 2"

Sealant Depth: 5/8" with 3/8" Crown

UL SYSTEM W-L-5014 F Rating: 1 & 2 Hr • T Rating: 1 & 2 hr

Steel or Iron Pipe: 12", Copper Pipe: 4"Insulated with 2" Thick Fiber Glass

or Mineral Wool Pipe InsulationAnnulus: 0" to 1-1/4"

Sealant Depth: 5/8" with 3/8" Crown

UL SYSTEM W-L-5051F Rating: 1 & 2 Hr • T Rating: 3/4, 1, 1-1/2 & 2 Hr

Steel or Iron Pipe: 16", Copper Pipe: 6”Foam Glass Pipe Insulation: 1” to 3” Thick

12" Wide 0.010" Thick Metal Jacket Wrapped Around Insulation and Secured with Metal Banding as Shown Annulus: 0” to 1-1/2"

Sealant Depth: 5/8"

INSTALLATION INSTRUCTIONSGeneral: Areas to be protected must be clean and free of oil, loose dirt, rust or scale. Installation temperatures must be between 35°F and 100°F (2˚C and 38˚C). Allow product to dry a minimum of 24 hours before exposure to moisture.

System Selection: Selection of an appropriate firestop system design is critical to the fire protection process. Space limitations preclude highly detailed information pertaining to individual application systems. Please consult the STI Product & Application Guide as well as the UL® Fire Resistance Directory for additional information.

Forming: Some installations may require forming as either an integral part of the system or as an option to facilitate installation. In systems where forming is required, mineral wool batts (min. nom. 4 lb/cu. ft (64 kg/m3) density) are recommended. Some gypsum wallboard systems utilize fiberglass. Cut forming material over-size to allow for tight packing. Position forming material to allow for the proper depth of fill material.

Fill Material: SpecSeal® Series SSS Sealant may be installed by caulking using a standard caulking gun or from bulk containers using a bulk loading caulk gun, or by manually troweling using a mason’s trowel or putty knife. If the sealant tends to pull back from a surface, clean the surface with a damp rag or sponge and reapply. Work sealant into all areas exercising care to eliminate voids or seams. The surface of the sealant can be smoothed using a putty knife dipped in water. Adding water to the sealant itself is not recommended. Sealant (when dry) may be sanded and painted using most non-solvent based paints. In gypsum wallboard penetrations, crown sealant 1/4" (6 mm) from penetrant to wallboard surface at a point approximately 1/2" (13 mm) or more from opening. Sealant (ehen dry) may be painted using most non-solvent based paints,

Smoke Sealing: In some applications including firestop collars, SpecSeal® Series SSS Sealant is recommended as a smoke seal. It is suggested in these application that the sealant be applied to both sides of walls. In floor applications, a sealing bead is suggested top and bottom.

Fig. 3: ELECTRICAL, DATA OR COMMUNICATIONS PENETRATIONS - RATED GYPSUM WALLBOARD ASSEMBLIES

UL SYSTEM W-L-3076F Rating: 1 or 2 Hr • T Rating: 0 hr

Up to 4" Cable BundleCentered in 4 - 1/2" Opening

Sealant Depth: 5/8" with 1/4" Crown

UL SYSTEM W-L-2093F Rating: 1 or 2 Hr • T Rating: 1, 1-1/2 Hr

2" Rigid PVC, ENMT, or Optical Fiber Raceway.

1-1/4" PVDF Optical Fiber Raceway.Sealant Depth: 5/8" with 1/4" Crown

Fig. 4: ELECTRICAL PENETRATIONS - CONCRETE/MASONRY FLOORS & WALLS

UL SYSTEM C-AJ-3154F Rating: 1, 2, 3 & 4 Hr • T Rating: 0, 1/2, & 2 3/4 Hr

Optional Sleeve-PVC or SteelElectrical, Telephone or Data Cables

Annulus: 0" to 2"Sealant Depth: 1/2"

Forming Materials: Nom 4 pcf Mineral Wool Sealant Depth: 1/2” for 1, 2, 3 Hr; 1” for 4 Hr

UL SYSTEM C-AJ-6008F Rating: 3 Hr • T Rating: 0 Hr

Aluminum or Copper Bus Duct 5,000 AmpSteel Cover Plate

Sealant Depth: 1/2"Forming Materials: Nom 4 pcf Mineral Wool

Tightly Packed to a depth of 1-1/2"

STI Product Data Sheet • Series SSS Intumescent Sealant • FOD-5001 05/2010

Page 40: Shaft Walls - Firestop CHStop nesting in slotted ceiling track. Studs spaced 24 in. (610 mm) OC. After installation of gy psum board liner panels (Item 2D), studs secured to flange

4 Technical Service 1-800-992-1180www.stifirestop.com

Inspection: Installations should be inspected periodically for subsequent damage. Any damage should be repaired using SpecSeal® products per the original approved design.

Retrofit: When adding or removing penetrants, care should be taken to minimize damage to the seal. Reseal using SpecSeal® products per the approved design. NOTE: New penetrants of a different nature than the original design may require a totally new firestop design or extensive modifications to the existing design. Reseal all openings as per the requirements of the modified design.

Specified Technologies Inc. provides toll free technical support to assist in product selection and appropriate installation design. UL Systems, Material Safety Data Sheets and other technical information is available through the Technical Library at www.stifirestop.com.

Consult Material Safety Data Sheet for additional information on the safe handling and disposal of this material. Wash areas of skin contact with soap and water. Avoid contact with eyes. SEALANT IS CONDUCTIVE UNTIL DRY.

SpecSeal® Series SSS Sealant is available from authorized STI distributors. Consult factory or website for the names and locations of the nearest sales representatives or distributors.

AVAILABILITY

PRECAUTIONARY INFORMATION

TECHNICAL SERVICE

MAINTENANCE

IMPORTANT NOTICE: All statements, technical information, and recommendations contained herein are based upon testing believed to be reliable, but the accuracy and completeness thereof is not guaranteed.

WARRANTYSpecified Technologies Inc. manufactures its goods in a manner to be free of defects. Should any defect occur in its goods (within one year), Specified Technologies Inc., upon prompt notification, will at its option, exchange or repair the goods or refund the purchase price.

LIMITATIONS AND EXCLUSIONS: THIS WARRANTY IS IN LIEU OF ALL OTHER REPRESENTATIONS EXPRESSED OR IMPLIED (INCLUDING THE IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR USE) AND UNDER NO CIRCUMSTANCES SHALL SPECIFIED TECHNOLOGIES INC. BE RESPONSIBLE FOR ANY INCIDENTAL OR CONSEQUENTIAL PROPERTY DAMAGE OR LOSSES. PRIOR TO USE, THE USER SHALL DETERMINE THE SUITABILITY OF THE PRODUCT FOR ITS INTENDED USE, AND THE USER ASSUMES ALL RISKS AND LIABILITY FOR SUBSEQUENT USE.

No statement or recommendation not contained herein shall have any force or effect unless in an agreement signed by officers of seller and manufacturer.

MADE IN THE USA – COPYRIGHT © 2010 SPECIFIED TECHNOLOGIES INC.

Specified Technologies Inc. • 210 Evans Way, Somerville, NJ 08876 USA • Phone: 800.992.1180 • Fax: 908.526.9623

CATALOG NUMBER DESCRIPTION

SSS100 10.1 oz. Tube (300 ml) 18.2 cu.in.

SSS129 29 oz. Tube (858 ml) 52 cu. in.

SSS120 20 oz. Sausage (592 ml) 36 cu. in.

SSS102 2 Gal. Pail (7.6 liters) 462 cu.in.

SSS105 5 Gal. Pail (19.0 liters) 1,155 cu.in.

STI Product Data Sheet • Series SSS Intumescent Sealant • FOD-5001 05/2010

INSTALLATION INSTRUCTIONS LIMITATIONS: SpecSeal® Series SSS Sealant is water-based and cures through the evaporation of water. Low temperatures as well as high humidity may retard drying. Non-porous or impermeable backing materials, plates, or coatings may retard the drying process. Do not paint or seal in any way that prevents contact with air until sealant has dried through completely. This product has been designed to be safe with plastics and has been used extensively and successfully with a variety of different types of plastic pipes, tubes, and plastic cable insulations. Variations in these materials however, make it impos-sible to guarantee compatibility. STI strongly recommends that the user consult with the manufacturer of the pipe, tubing, or cable in question regarding any known sensitivities or potential restrictions before applying this product.

CITY OF NEW YORK MEA 28-92-M