Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick Created Tuesday, March 27th, 2018 Shop-drawings Submittal Log Record 1 Record Name: shop drawings submittal-008 Code: 15-400 Drawing Description: Pumps GC-P-1/2, CH-P- 1/2, B-P-1/2, DW-RP-1, DW-P-1/2, HW-P-1/2, HW- P-3/4, HW-P-5/6, DWBP-1/2 Vendor (Trade): PML- 011 Required by: 2018-04-11 Submissions # Received From Trade Sent To Consultant Received From Consultant Review Status 1 2018-03-23 2018-03-27 2018-03-27

Upload: others

Post on 30-Nov-2020

3 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Project #1295 Hawthorne (4976 Cambie) #1295Date Tuesday, March 27th, 2018

Address 4976 Cambie Street

Created By Paul WarwickCreated Tuesday, March 27th, 2018

Shop-drawings Submittal Log

Record 1

Record Name: shop drawings submittal-008

Code: 15-400Drawing Description: Pumps GC-P-1/2, CH-P-1/2, B-P-1/2, DW-RP-1, DW-P-1/2, HW-P-1/2, HW-P-3/4, HW-P-5/6, DWBP-1/2

Vendor (Trade): PML- 011 Required by: 2018-04-11

Submissions

# Received From Trade Sent To ConsultantReceived From Consultant

Review Status

1 2018-03-23 2018-03-27 2018-03-27

 

Page 2: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

C09092 - 011

Response Requested By:

Subject: Shop DrawingsSent Via: EmailStatus: For Review

SUBMITTALS

ITEM DESCRIPTION

COMMENTS

To: Performance Construction Ltd.

2572 Davies AvenuePort Coquitlam, BC V3C 2J9

Phone: 604-468-9999Fax: 604-468-9925

Submittal

Submittal ID:Date Sent: 23-Mar-18

11-Apr-18

Project Name: Hawthorne

[email protected]

Paul Warwick1150 - 21331 Gordon WayRichmond, BC V6W [email protected]

From: Dal Seymour

SUPPLIER SPECIFICATION SECTIONPumps GC-P-1/2, CH-P-1/2, B-P-1/2, EmcoDW-RP-1, DW-P-1/2, HW-P-1/2, HW-P-3/4, HW-P-5/6, DWBP-1/2

Page 3: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

PROJECT:

CONTRACTOR: Professional Mechanical Ltd.

SUBMITTED BY: EMCO CorporationQUOTE #: EM17-7508

PREPARED BY: Ryan Hall/ewong

DATE: 2-Feb-18

BRITISH COLUMBIA ALBERTA SASKATCHEWAN MANITOBA ONTARIO

ABBOTSFORD LANGLEY CALGARY PRINCE ALBERT WINNIPEG DRYDEN

CAMPBELL RIVER PORT COQUITLAM CAMROSE REGINA THUNDER BAY

CHILLIWACK PRINCE GEORGE EDMONTON SASKATOON

COQUITLAM RICHMOND FORT MCMURRAY

COURTENAY SALMON ARM GRAND PRAIRIE

CRANBROOK SURREY HIGH LEVEL

DAWSON CREEK TERRACE LETHBRIDGE

FORT ST. JOHN VANCOUVER RED DEER

KAMLOOPS VERNON

KELOWNA VICTORIA

"The Ensuite" DESIGNER SHOWROOMSBURNABY EDMONTON CALGARY WINNIPEG VICTORIA

EMCO DESIGN SERVICES - B.C. DISTRICT3139 Sumner Avenue Burnaby, B.C. V5G 3E3

Tel. No. 604-412-2830 Fax. 604-412-3932 www.emcobc.ca

Hawthorne - 4988 Cambie Street - Pennyfarthing QE Park Properties 44 units

Page 4: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

SKU DESCRIPTION

tag GC-P-1/2

armstrong 4380DE, 2.5x2.5x5, 190 Usgpm, 35ft, 3hp, 208/3/60nd FTV-4FA, 4" triple duty valvend SG-425, 4x2.5" suction guidetag CH-P-1/2

nd 4380DE, 2x2x5, 185 Usgpm, 52ft, 5hp, 208/3/60nd FTV-4FA, 4" triple duty valvend SG-42, 4x2" suction guidetag B-P-1/2

nd 4380DE, 1.5x1.5x6, 72 Usgpm, 42ft, 1.5hp, 208/3/60nd FTV-2.5FA, 2.5" triple duty valvend SG-2515 2.5x1.5" suction guidetag DW-RP-1

nd Astro 250SS-TA, 13 Usgpm, 5.5ft, 115/1/60w/ timer, aquastat, 6' line cordtag DW-P-1/2

nd E15.2B, 34 Usgpm, 14ft, .04hp, 115/1/60tag HW-P-1/2

nd E15.2, 34 Usgpm, 14ft, 115/1/60tag HW-P-3/4

nd Astro 280CI, 9 Usgpm, 21ft, 115/1/60tag HW-P-5/6

nd 4380DE, 1.5x1.5x6, 36 Usgpm, 47ft, 1.5hp, 1800, 208/3/60nd FTV-2GS, 2" triple duty valvend SG-215TF 2x1.5" suction guidetag DWBP-1/2

nd N260322-20 hp Duplex variable speed boosternd Construction: Standardnd Operation: Lead/1-Lagnd Meets ASHRAE 90.1: Yesnd Total flow: 370.0 Usgpmnd Booster pressure: 88.0 psi

NOTES

DESIGN SERVICES3139 Sumner Avenue Burnaby, B.C. V5G 3E3

Tel. No. 604-412-2830 Fax. 604-412-3932

----- EQUIPMENT SCHEDULE -----

Hawthorne - 4988 Cambie Street - Pennyfarthing QE Park Properties 44 units

Page 1 of 2

Page 5: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

SKU DESCRIPTION NOTES

nd Piping material: Stainless Steel 304nd Suction header size: 6 innd Discharge header size: 6innd Suction header connection rating: ANSI-150nd Discharge header connection rating: ANSI-150nd Valve type: Check valve onlynd IVS model 20 hp/20 hpnd Enclosure: NEMA 12 Painted steel enclosurend Tank mounting: Remote Mountednd Tank size/rating: 132 US Gallon Non-ASMEnd Other options: BMS Port (serial communication port for connection to nd BMS - BacNet (MS/TP)ndndtag

HMI: Touch Screen 4" Standard Start-up included

Page 2 of 2

Page 6: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

TAG:-

EWong
Text Box
EWong
Typewritten Text
ARMSTRONG PUMPS
Page 7: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 2505-003.0

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: GC-P-1/2 Pipe orientation: ParallelSuction pressure: 0 ftService: CHW - Chiller & B.T.

Location: Mech Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUPump/motor run qty: 2

Duty flow per pump: 190 USgpm Specific gravity: 1.0000

Duty head: 35 ft Safety factor % head: 0 %

Environment: Indoors Total dissolved solids: 0 ppm

Materials of construction

Construction: LPDESF Impeller: Stainless Steel 316, A743 CF8MRating: ANSI-125 Pump Shaft: SS ASTM A276 Type 416Connections: Inlet: 2.5 in, Outlet: 2.5 in Casing o-ring: EPDM

Casing (volute): Ductile Iron A536 GR 65-45-12, e-coated Flush line: Braided Stainless Steel

Stub Shaft: SS ASTM A276 Type 416

Mechanical seal data

Seal type: Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon CarbideSprings: Stainless Steel Secondary seal: EPDMRotating hardware: Stainless Steel

iECM Data

ArmstrongSupplier: Insulation class: Class F InsulationSize: 3 hp Inverter motor type: Not applicableFrame number: IEC90 Efficiency: IE5Enclosure: TEFC Operating speed @ 100% flow: 2785 rpmMotor Electrics: 208/3/60 Operating speed @ 50% flow: 1902 rpm

Sensorless control: Yes-Quadratic press control Communication port: RS 485BMS protocol: BACnet MS/TP(card) Analog inputs: 2 (current or voltage)Enclosure: UL Type 12

Digital inputs:Analog outputs: 1 (current or voltage)

Fused disconnect switch: No 2 (programmable)

Control orientation: L5 Digital outputs: 2 (programmable)Expansion card: Not Applicable Cooling: Not ApplicableBHP at 50% load/flow and 55% of design head: 0.54 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)

Meets ASHRAE 90.1: Yes EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: 14 ft

*If minimum maintained system pressure is not known, default is 40% of design head.**If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 1 of 40

EWong
Highlight
Page 8: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: GC-P-1/2 Service: CHW - Chiller & B.T. Location: Mech Room

--- Motor Data --- Motor Size: 3 hp

--- Design Duty Point --- Flow: 190 usgpm Head: 35 ft Impeller: 4.41 in

--- Performance Data --- • NPSHR: 7.1201 ft • Eff. @ Design: 77.34 % • BHP @ Design: 2.17 hp • Mtr Capability @ Rated Spd: 2.5 hp • %Mtr Safety: 15.23% • BEP @ Design Imp.: 77.72 % @ 180.2 usgpm • %max imp. range: 62.90 % • Outlet Velocity: 12.73 ft/s • VFD Op.Speed: 2785 rpm • VFD Setting: 46.4 Hz

Series 4380Design Envelope: 2505-003.0 @ 46.4 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 80 160 240 320 4000

10

20

30

40

50

60

70

80

Flow (usgpm)

Head

(ft)

4.94 in

3.49 in

System

4.41 in

1.5 hp

2 hp

3 hp

79

79

77

77

72

72

65

65

55

55%

42

Water, spgr= 1.0000

PT673-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1

80

--- Admin Data --- Tag Num: GC-P-1/2 Service: CHW - Chiller & B.T. Location: Mech Room

--- Motor Data --- Motor Size: 3 hp

--- Design Duty Point --- Flow: 190 usgpm Head: 35 ft Impeller: 4.41 in

--- Control Data --- 1. Hmax @ 46.4 Hz: • 190 @ 35, 2.17 hp 2. Control (QPC) @ 43.2 Hz: • 171.1 @ 31, 1.73 hp 3. Control (QPC) @ 39.8 Hz: • 150.9 @ 27.3, 1.34 hp 4. Control (QPC) @ 36.5 Hz: • 129.6 @ 23.8, 1.01 hp 5. Control (QPC) @ 33.3 Hz: • 107.5 @ 20.7, 0.74 hp 6. Control (QPC) @ 30.0 Hz: • 80.9 @ 17.8, 0.51 hp 7. Hmin: 14 ft • Setting= 40.00% Hmax

Series 4380Design Envelope: 2505-003.0

Integrated Intelligent Variable Speed with Sensorless Control

0 80 160 240 320 4000

10

20

30

40

50

60

70

80

Flow (usgpm)

Head

(ft)

3300 rpm

1800 rpm

System

Avg.Load (QPC)

2785 rpm

3 hp

78

77

77

74

74

70

70

62

62

52

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT673-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1

1

23

45

6

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 2 of 40

Page 9: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

--- Admin Data --- Tag Num: GC-P-1/2 Service: CHW - Chiller & B.T. Location: Mech Room

--- Motor Data --- Motor Size: 3 hp

--- System Design Data --- Piping: Parallel, Run Qty = 2 Fluid: Water Sp.Gr.= 1.0000, vis= 31 ssu, 60 F Suction: 0 ft System: Closed, M.Head: 0 ft Total Design Flow = 380 usgpm Total Design Head = 35 ft

--- Pump Data @ Curve# 2 --- NPSHR: 7.1313 ft Flow: 380 usgpm Head: 35 ft Eff: 77.3%, BEP: 77.7% %BEP (Flow): 105% BHP = 4.34 hp BHP/Pump= 2.17 hp

Parallel Pump CurveDesign Envelope: 2505-003.0

Integrated Intelligent Variable Speed with Sensorless Control

0 100 200 300 400 500 6000

10

20

30

40

50

Flow (usgpm)

Head

(ft)

System

1

1

2

2

11

11

22

22

Water, spgr= 1.0000

PT673-2-0 (3.30.1.5)

Options

Sensorless Bundle: Yes Parallel Sensorless: NoEnergy Performance Bundle: No Protection Bundle: No

Dual Season Setup: No Zone Optimization Bundle: No

Cooling Heating

Q1: N/A Q2: N/AH1: N/A H2: N/A

H1min: N/A H2min: N/A

Maximum Flow: N/A Minimum Flow: N/A

Optional Services

On-Site Pump Commissioning: Cost Not Included Extended Warranty: NoPump Manager: No Include Spare Parts Qty: 0

Design envelope pumping unit capability

Operating point Flow Head Efficiency

Full capability at 100% design flow 44.3 ft190 USgpm 77.65 %Design point 190 USgpm 35 ft 77.34 %

50% average flow (with default load profile) 95 usgpm 19.3 ft 74.64 %

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 3 of 40

Page 10: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Dimensional data (not for construction)

Top viewSide view

Weight: 80.5 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 2.5 7ANSI-125 4 0.6255.5

Outlet 2.5 7ANSI-125 4 0.6255.5

*Equally spaced straddling centreline

Special instructions

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

Pump Manager and Extended Warranty Note:

Keep your system running as intended with Pump Manager, or combined with anExtended Warranty to provide price certainty in your maintenance and repairbudget. Both are available directly to the owner/end user of the pump. PumpManager proactively tracks performance and provides early diagnostic warnings,web accessible trends and analysis along with automated reports. Contact yourArmstrong contacts to take advantage of an Extended Warranty or Pump Manager.Additional equipment Flotrex: FTV-4FA (570200-478) Suction Guide: SG-425 (516860-036)

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 4 of 40

Page 11: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 0205-005.0

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: CH-P-1/2 Pipe orientation: SingleSuction pressure: 0 ftService: CHW - Load & B.T.

Location: Mech Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUDuty flow per pump: 185 USgpm

Specific gravity: 1.0000Duty head: 52 ft

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: LPDESF Impeller: Stainless Steel 316, A743 CF8MRating: ANSI-125 Pump Shaft: SS ASTM A276 Type 416Connections: Inlet: 2 in, Outlet: 2 in Casing o-ring: EPDM

Casing (volute): Ductile Iron A536 GR 65-45-12, e-coated Flush line: Braided Stainless Steel

Stub Shaft: SS ASTM A276 Type 416

Mechanical seal data

Seal type: Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon CarbideSprings: Stainless Steel Secondary seal: EPDMRotating hardware: Stainless Steel

iECM Data

ArmstrongSupplier: Insulation class: Class F InsulationSize: 5 hp Inverter motor type: Not applicableFrame number: IEC112 Efficiency: IE5Enclosure: TEFC Operating speed @ 100% flow: 3089 rpmMotor Electrics: 208/3/60 Operating speed @ 50% flow: 2080 rpm

Sensorless control: Yes-Quadratic press control Communication port: RS 485BMS protocol: BACnet MS/TP(card) Analog inputs: 2 (current or voltage)Enclosure: UL Type 12

Digital inputs:Analog outputs: 1 (current or voltage)

Fused disconnect switch: No 2 (programmable)

Control orientation: L5 Digital outputs: 2 (programmable)Expansion card: Not Applicable Cooling: Not ApplicableBHP at 50% load/flow and 55% of design head: 0.79 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)

Meets ASHRAE 90.1: Yes EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: 20.8 ft

*If minimum maintained system pressure is not known, default is 40% of design head.**If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 5 of 40

EWong
Highlight
Page 12: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: CH-P-1/2 Service: CHW - Load & B.T. Location: Mech Room

--- Motor Data --- Motor Size: 5 hp

--- Design Duty Point --- Flow: 185 usgpm Head: 52 ft Impeller: 4.97 in

--- Performance Data --- • NPSHR: 12.9 ft • Eff. @ Design: 76.64 % • BHP @ Design: 3.17 hp • Mtr Capability @ Rated Spd: 4.04 hp • %Mtr Safety: 27.57% • BEP @ Design Imp.: 78.78 % @ 161.0 usgpm • %max imp. range: 100.00 % • Outlet Velocity: 17.69 ft/s • VFD Op.Speed: 3089 rpm • VFD Setting: 51.5 Hz

Series 4380Design Envelope: 0205-005.0 @ 51.5 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 50 100 150 200 250 3000

10

20

30

40

50

60

70

80

Flow (usgpm)

Head

(ft)

4.97 in

3.50 in

System

4.97 in

5

7.5 hp

8080

77

77

74

74

69

69

62

62

53

53%

Water, spgr= 1.0000

PT674-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1

79

--- Admin Data --- Tag Num: CH-P-1/2 Service: CHW - Load & B.T. Location: Mech Room

--- Motor Data --- Motor Size: 5 hp

--- Design Duty Point --- Flow: 185 usgpm Head: 52 ft Impeller: 4.97 in

--- Control Data --- 1. Hmax @ 51.5 Hz: • 185 @ 52, 3.17 hp 2. Control (QPC) @ 47.2 Hz: • 163.4 @ 45.2, 2.4 hp 3. Control (QPC) @ 42.8 Hz: • 140.8 @ 38.9, 1.76 hp 4. Control (QPC) @ 38.7 Hz: • 117.4 @ 33.4, 1.26 hp 5. Control (QPC) @ 34.3 Hz: • 90.3 @ 28.2, 0.83 hp 6. Control (QPC) @ 30.0 Hz: • 55.9 @ 23.6, 0.48 hp 7. Hmin: 20.8 ft • Setting= 40.00% Hmax

Series 4380Design Envelope: 0205-005.0

Integrated Intelligent Variable Speed with Sensorless Control

0 80 160 240 320 4000

20

40

60

80

100

120

140

160

Flow (usgpm)

Head

(ft)

3960 rpm

1800 rpm

System

Avg.Load (QPC)

3089 rpm

5 hp

7978

78

76

76

71

71

65

65

56

56

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT674-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1

12

34

56

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 6 of 40

Page 13: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Options

Sensorless Bundle: Yes Parallel Sensorless: NoEnergy Performance Bundle: No Protection Bundle: No

Dual Season Setup: No Zone Optimization Bundle: No

Cooling Heating

Q1: N/A Q2: N/AH1: N/A H2: N/A

H1min: N/A H2min: N/A

Maximum Flow: N/A Minimum Flow: N/A

Optional Services

On-Site Pump Commissioning: Cost Not Included Extended Warranty: NoPump Manager: No Include Spare Parts Qty: 0

Design envelope pumping unit capability

Operating point Flow Head Efficiency

Full capability at 100% design flow 70.7 ft185 USgpm 78.61 %Design point 185 USgpm 52 ft 76.64 %

50% average flow (with default load profile) 92.5 usgpm 28.6 ft 77.60 %

Dimensional data (not for construction)

Top viewSide view

Weight: 85 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 2 6ANSI-125 4 0.6254.75

Outlet 2 6ANSI-125 4 0.6254.75

*Equally spaced straddling centreline

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 7 of 40

Page 14: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Special instructions

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

Pump Manager and Extended Warranty Note:

Keep your system running as intended with Pump Manager, or combined with anExtended Warranty to provide price certainty in your maintenance and repairbudget. Both are available directly to the owner/end user of the pump. PumpManager proactively tracks performance and provides early diagnostic warnings,web accessible trends and analysis along with automated reports. Contact yourArmstrong contacts to take advantage of an Extended Warranty or Pump Manager.Additional equipment Flotrex: FTV-4FA (570200-478) Suction Guide: SG-42 (516860-035)

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 8 of 40

Page 15: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 1503-001.5

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: B-P-1&2 Pipe orientation: SingleSuction pressure: 0 ftService: Boiler Loop

Location: Mech Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUDuty flow per pump: 72 USgpm

Specific gravity: 1.0000Duty head: 42 ft

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: LPDESF Impeller: Stainless Steel 316, A743 CF8MRating: ANSI-125 Pump Shaft: SS ASTM A276 Type 416Connections: Inlet: 1.5 in, Outlet: 1.5 in Casing o-ring: EPDM

Casing (volute): Ductile Iron A536 GR 65-45-12, e-coated Flush line: Braided Stainless Steel

Stub Shaft: SS ASTM A276 Type 416

Mechanical seal data

Seal type: Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon CarbideSprings: Stainless Steel Secondary seal: EPDMRotating hardware: Stainless Steel

iECM Data

ArmstrongSupplier: Insulation class: Class F InsulationSize: 1.5 hp Inverter motor type: Not applicableFrame number: IEC90S Efficiency: IE5Enclosure: TEFC Operating speed @ 100% flow: 4161 rpmMotor Electrics: 208/3/60 Operating speed @ 50% flow: 2886 rpm

Sensorless control: Yes-Quadratic press control Communication port: RS 485BMS protocol: BACnet MS/TP(card) Analog inputs: 2 (current or voltage)Enclosure: UL Type 12

Digital inputs:Analog outputs: 1 (current or voltage)

Fused disconnect switch: No 2 (programmable)

Control orientation: L5 Digital outputs: 2 (programmable)Expansion card: Not Applicable Cooling: Not ApplicableBHP at 50% load/flow and 55% of design head: 0.26 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)

Meets ASHRAE 90.1: No EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: 16.8 ft

*If minimum maintained system pressure is not known, default is 40% of design head.**If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 9 of 40

EWong
Highlight
Page 16: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: B-P-1&2 Service: Boiler Loop Location: Mech Room

--- Motor Data --- Motor Size: 1.5 hp

--- Design Duty Point --- Flow: 72 usgpm Head: 42 ft Impeller: 3.05 in

--- Performance Data --- • NPSHR: 10.5 ft • Eff. @ Design: 72.40 % • BHP @ Design: 1.05 hp • Mtr Capability @ Rated Spd: 1.26 hp • %Mtr Safety: 19.13% • BEP @ Design Imp.: 72.58 % @ 75.8 usgpm • %max imp. range: 100.00 % • Outlet Velocity: 11.35 ft/s • VFD Op.Speed: 4161 rpm • VFD Setting: 55.5 Hz

Series 4380Design Envelope: 1503-001.5 @ 55.5 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 20 40 60 80 100 1200

10

20

30

40

50

60

Flow (usgpm)

Head

(ft)

3.05 in

2.38 in

System

3.05 in1.5 hp

74747575

70

70

66

66

61

61

5344

Water, spgr= 1.0000

PT679-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1

73

--- Admin Data --- Tag Num: B-P-1&2 Service: Boiler Loop Location: Mech Room

--- Motor Data --- Motor Size: 1.5 hp

--- Design Duty Point --- Flow: 72 usgpm Head: 42 ft Impeller: 3.05 in

--- Control Data --- 1. Hmax @ 55.5 Hz: • 72 @ 42, 1.05 hp 2. Control (QPC) @ 50.9 Hz: • 63.3 @ 36.3, 0.81 hp 3. Control (QPC) @ 46.5 Hz: • 54.5 @ 31.2, 0.6 hp 4. Control (QPC) @ 42.0 Hz: • 44.6 @ 26.5, 0.43 hp 5. Control (QPC) @ 37.5 Hz: • 33.3 @ 22.2, 0.29 hp 6. Index @ 33.0 Hz: • 18 @ 18.4, 0.17 hp 7. Hmin: 16.8 ft 30.9 Hz: • Setting= 40.00% Hmax

Series 4380Design Envelope: 1503-001.5

Integrated Intelligent Variable Speed with Sensorless Control

0 20 40 60 80 100 120 140 1600

20

40

60

80

100

Flow (usgpm)

Head

(ft)

4950 rpm

2473 rpm

2315 rpm

1800 rpm System

Avg.Load (QPC)

4161 rpm

1.5 hp

73

72

72

69

69

64

64

57

57

47

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT679-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1

1

2

34

56

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 10 of 40

Page 17: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Options

Sensorless Bundle: Yes Parallel Sensorless: NoEnergy Performance Bundle: No Protection Bundle: No

Dual Season Setup: No Zone Optimization Bundle: No

Cooling Heating

Q1: N/A Q2: N/AH1: N/A H2: N/A

H1min: N/A H2min: N/A

Maximum Flow: N/A Minimum Flow: N/A

Optional Services

On-Site Pump Commissioning: Cost Not Included Extended Warranty: NoPump Manager: No Include Spare Parts Qty: 0

Design envelope pumping unit capability

Operating point Flow Head Efficiency

Full capability at 100% design flow 54.1 ft72 USgpm 71.23 %Design point 72 USgpm 42 ft 72.40 %

50% average flow (with default load profile) 36 usgpm 23.1 ft 66.01 %

Dimensional data (not for construction)

Top viewSide view

Weight: 53 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 1.5 5ANSI-125 4 0.53.88

Outlet 1.5 5ANSI-125 4 0.53.88

*Equally spaced straddling centreline

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 11 of 40

Page 18: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Special instructions

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

Pump Manager and Extended Warranty Note:

Keep your system running as intended with Pump Manager, or combined with anExtended Warranty to provide price certainty in your maintenance and repairbudget. Both are available directly to the owner/end user of the pump. PumpManager proactively tracks performance and provides early diagnostic warnings,web accessible trends and analysis along with automated reports. Contact yourArmstrong contacts to take advantage of an Extended Warranty or Pump Manager.Additional equipment Flotrex: FTV-2.5FA (570200-476) Suction Guide: SG-2515 (516860-034)

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 12 of 40

Page 19: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Wet rotor circulator

Model: Part number: 110223b-149Series ASTRO 250SS-TA

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: DW-RP-1 Pipe orientation: SingleSuction pressure: 0 ftService: DHW

Location: Mech Room Fluid: Water:

Quantity: 1 Operating temperature: 60 F*Viscosity: 31 SSUDuty flow per pump: 13 USgpm

Specific gravity: 1.0000Duty head: 5.5 ft

Total dissolved solids: 0 ppm

* for open systems, it is recommended that the fluid temperature be less than 150F (66C) to avoid precipitation of calcium.

Materials of construction

Construction: SS150 Impeller: Polyether Imide (PEI)

Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic

Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01

Companion flange: Bronze 1 1/2" Listing: ETL listed for US and Canada

**certified <0.25 weighted average percent lead and complies with Californai Health and Safety Code section 114875 (commonly known as AB1953)

Motor electrical data

Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.157 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 3600 rpmMotor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 13 of 40

EWong
Highlight
Page 20: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Performance curve

--- Admin Data --- Tag Num: DW-RP-1 Service: DHW Location: Mech Room

--- Motor Data --- Motor Size: 0.157 hp Motor Speed: [3] 3600 rpm

--- Design Duty Point --- Flow: 13 usgpm Head: 5.5 ft

--- Pump Data --- Pump Size: Astro 250SS Impeller: 2.68 in Suction Head Req: 0 ft Projected Flow: 14.1 usgpm Projected Head: 6.4309 ft

Series Astro MultiSpeedAstro 250SS @ Discrete Speeds

0 4 8 12 16 200

5

10

15

20

25

30

Flow (usgpm)

Head

(ft)

System

Projected

[1] 2300

[2] 2900

[3] 3600

Water:, spgr= 1.0000

PT620-0-228 (3.30.1.5)

Dimensional data (not for construction)

Top viewSide view

Weight: 9 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 14 of 40

Page 21: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Special instructions

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 15 of 40

Page 22: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

E.2 series dry motor circulator

Model: Part number: 182212-662Series E15.2B brz 120V

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: DW-P-1/2 Pipe orientation: SingleSuction pressure: 0 ftService: DHW Production

Location: Mech Room Fluid: Water:

Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUDuty flow per pump: 34 USgpm

Specific gravity: 1.0000Duty head: 14 ft

Total dissolved solids: 0 ppm

Materials of construction

Construction: AB (All Bronze) Impeller: 30% Glass-filled NorylRating: Not applicable Bearings: Permanently lubricated SS

Connections: 1.25 in. Dia. 2-Bolt flanges

Mechanical seal data

Manufacturer: Armstrong Seal: Silicon CarbideSeal type: Bellows-style Silicon Carbide

Motor electrical data

Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.4 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 3400 rpmMotor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 16 of 40

EWong
Highlight
Page 23: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Performance curve

--- Admin Data --- Tag Num: DW-P-1/2 Service: DHW Production Location: Mech Room

--- Motor Data --- Motor Size: 0.4 hp Motor Speed: 3600 rpm

--- Design Duty Point --- Flow: 34 usgpm Head: 14 ft

--- Pump Data --- Pump Size: E15.2B Impeller: 2.4 in Projected Flow: 36.6 usgpm Projected Head: 16.3 ft

Series E.2Selected Size: E15.2B @ 3400 rpm

0 20 40 60 80 100 120 140 1600

10

20

30

40

50

60

70

80

Flow (usgpm)

Head

(ft)

System

Projected

E15.2B

Water:, spgr= 1.0000

PT518-0-168 (3.30.1.5)

Dimensional data (not for construction)

Top viewSide view

Weight: 23 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 17 of 40

Page 24: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 1.25 7.5N/A 4 0.6256

Outlet 1.25 7.5N/A 4 0.6256

*Equally spaced straddling centreline

Special instructions

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 18 of 40

Page 25: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

E.2 series dry motor circulator

Model: Part number: 182212-661Series E15.2 ci 120V

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: HW-P-1/2 Pipe orientation: ParallelSuction pressure: 0 ftService: DHW Source Pump

Location: Mech Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUPump/motor run qty: 2

Duty flow per pump: 34 USgpm Specific gravity: 1.0000

Duty head: 14 ft Total dissolved solids: 0 ppm

Materials of construction

Construction: STD125 Impeller: 30% Glass-filled NorylRating: Not applicable Bearings: Permanently lubricated SS

Connections: 1.25 in. Dia. 2-Bolt flanges

Mechanical seal data

Manufacturer: Armstrong Seal: Silicon CarbideSeal type: Bellows-style Silicon Carbide

Motor electrical data

Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.4 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 3400 rpmMotor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 19 of 40

EWong
Highlight
Page 26: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Performance curve

--- Admin Data --- Tag Num: HW-P-1/2 Service: DHW Source Pump Location: Mech Room

--- Motor Data --- Motor Size: 0.4 hp Motor Speed: 3600 rpm

--- Design Duty Point --- Flow: 34 usgpm Head: 14 ft

--- Pump Data --- Pump Size: E15.2 Impeller: 2.4 in Projected Flow: 36.6 usgpm Projected Head: 16.3 ft

Series E.2Selected Size: E15.2 @ 3400 rpm

0 20 40 60 80 100 120 140 1600

10

20

30

40

50

60

70

80

Flow (usgpm)

Head

(ft)

System

Projected

E15.2/E15.2B

Water, spgr= 1.0000

PT518-0-168 (3.30.1.5)

--- Admin Data --- Tag Num: HW-P-1/2 Service: DHW Source Pump Location: Mech Room

--- Motor Data --- Motor Size: 0.4 hp Motor Speed: 3600 rpm

--- System Design Data --- Piping: Parallel, Run Qty = 2 Fluid: Water Sp.Gr.= 1.0000, vis= 31 ssu, 60 F Suction: 0 ft System: Closed, M.Head: 0 ft Total Design Flow = 68 usgpm Total Design Head = 14 ft

--- Pump Data @ Curve# 2 --- NPSHR: 1 ft Projected Flow: 73.3 usgpm Projected Head: 16.3 ft Eff: 100.0%, BEP: 100.0% %BEP (Flow): 66% BHP = 0.3 hp BHP/Pump= 0.15 hp

Parallel Pump CurveSeries E.2

E15.2 @ 3400 rpm

0 80 160 240 3200

10

20

30

40

50

60

70

Flow (usgpm)

Head

(ft)

System

Projected

1 2

Water, spgr= 1.0000

PT518-0-168 (3.30.1.5)

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 20 of 40

Page 27: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Dimensional data (not for construction)

Top viewSide view

Weight: 23 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 1.25 7.5N/A 4 0.6256

Outlet 1.25 7.5N/A 4 0.6256

*Equally spaced straddling centreline

Special instructions

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 21 of 40

Page 28: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Wet rotor circulator

Model: Part number: 110223-320Series ASTRO 280CI FLG

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: HW-P-3/4 Pipe orientation: ParallelSuction pressure: 0 ftService: MAU Heating

Location: Mech Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUPump/motor run qty: 2

Duty flow per pump: 9 USgpm Specific gravity: 1.0000

Duty head: 21 ft Total dissolved solids: 0 ppm

Materials of construction

Construction: STD125 Impeller: Polyether Imide (PEI)Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic

Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01

Companion flange: Cast Iron 1 1/2" Listing: ETL listed for US and Canada

Motor electrical data

Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.333 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 3600 rpmMotor Electrics: 115/1/60

Operating limits (temperature - pressure)

Maximum pressure: 150 psi

Maximum temperature: 230 F

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 22 of 40

EWong
Highlight
Page 29: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Performance curve

--- Admin Data --- Tag Num: HW-P-3/4 Service: MAU Heating Location: Mech Room

--- Motor Data --- Motor Size: 0.333 hp Motor Speed: [3] 3600 rpm

--- Design Duty Point --- Flow: 9 usgpm Head: 21 ft

--- Pump Data --- Pump Size: Astro 280CI Impeller: 2.95 in Suction Head Req: 0 ft Projected Flow: 9.5656 usgpm Projected Head: 23.7 ft

Series Astro MultiSpeedAstro 280CI @ Discrete Speeds

0 5 10 15 20 25 300

4

8

12

16

20

24

28

32

Flow (usgpm)

Head

(ft)

System

Projected

[1] 2300

[2] 2900 [3] 3600

Water, spgr= 1.0000

PT626-0-232 (3.30.1.5)

--- Admin Data --- Tag Num: HW-P-3/4 Service: MAU Heating Location: Mech Room

--- Motor Data --- Motor Size: 0.333 hp Motor Speed: [3] 3600 rpm

--- System Design Data --- Piping: Parallel, Run Qty = 2 Fluid: Water Sp.Gr.= 1.0000, vis= 31 ssu, 60 F Suction: 0 ft System: Closed, M.Head: 0 ft Total Design Flow = 18 usgpm Total Design Head = 21 ft

--- Pump Data @ Curve# 2 --- NPSHR: 1 ft Projected Flow: 19.1 usgpm Projected Head: 23.7 ft Eff: 100.0%, BEP: 100.0% %BEP (Flow): 49% BHP = 0.115 hp BHP/Pump= 0.057 hp

Parallel Pump CurveSeries Astro MultiSpeedAstro 280CI @ 3600 rpm

0 10 20 30 40 50 60 700

8

16

24

32

Flow (usgpm)

Head

(ft)

System

Projected

1 2

Water, spgr= 1.0000

PT626-0-232 (3.30.1.5)

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 23 of 40

Page 30: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Dimensional data (not for construction)

Top viewSide view

Weight: 11 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative

Special instructions

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 24 of 40

Page 31: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Design envelope close coupled vertical in-line pump

Model: Series Design Envelope Sensorless 4380 1503-001.5

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: HW-P5/6 Pipe orientation: SingleSuction pressure: 0 ftService: Fan Coil Heating Pump

Location: Mech Room Fluid: Non-Potable Fluid - Water

Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUDuty flow per pump: 36 USgpm

Specific gravity: 1.0000Duty head: 47 ft

Safety factor % head: 0 %Environment: Indoors

Total dissolved solids: 0 ppm

Materials of construction

Construction: LPDESF Impeller: Stainless Steel 316, A743 CF8MRating: ANSI-125 Pump Shaft: SS ASTM A276 Type 416Connections: Inlet: 1.5 in, Outlet: 1.5 in Casing o-ring: EPDM

Casing (volute): Ductile Iron A536 GR 65-45-12, e-coated Flush line: Braided Stainless Steel

Stub Shaft: SS ASTM A276 Type 416

Mechanical seal data

Seal type: Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon CarbideSprings: Stainless Steel Secondary seal: EPDMRotating hardware: Stainless Steel

iECM Data

ArmstrongSupplier: Insulation class: Class F InsulationSize: 1.5 hp Inverter motor type: Not applicableFrame number: IEC90S Efficiency: IE5Enclosure: TEFC Operating speed @ 100% flow: 3997 rpmMotor Electrics: 208/3/60 Operating speed @ 50% flow: 2918 rpm

Sensorless control: Yes-Quadratic press control Communication port: RS 485BMS protocol: BACnet MS/TP(card) Analog inputs: 2 (current or voltage)Enclosure: UL Type 12

Digital inputs:Analog outputs: 1 (current or voltage)

Fused disconnect switch: No 2 (programmable)

Control orientation: L5 Digital outputs: 2 (programmable)Expansion card: Not Applicable Cooling: Not ApplicableBHP at 50% load/flow and 55% of design head: 0.19 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)

Meets ASHRAE 90.1: No EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: 18.8 ft

*If minimum maintained system pressure is not known, default is 40% of design head.**If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 25 of 40

EWong
Highlight
Page 32: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Operating limits (temperature - pressure)

Maximum pressure: 175 psi

Maximum temperature: 250 F

Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.

Performance curve

--- Admin Data --- Tag Num: HW-P5/6 Service: Fan Coil Heating Pump Location: Mech Room

--- Motor Data --- Motor Size: 1.5 hp

--- Design Duty Point --- Flow: 36 usgpm Head: 47 ft Impeller: 3.05 in

--- Performance Data --- • NPSHR: 4.7322 ft • Eff. @ Design: 55.81 % • BHP @ Design: 0.77 hp • Mtr Capability @ Rated Spd: 1.21 hp • %Mtr Safety: 57.66% • BEP @ Design Imp.: 72.58 % @ 72.8 usgpm • %max imp. range: 100.00 % • Outlet Velocity: 5.67 ft/s • VFD Op.Speed: 3997 rpm • VFD Setting: 53.3 Hz

Series 4380Design Envelope: 1503-001.5 @ 53.3 Hz

Integrated Intelligent Variable Speed with Sensorless Control

0 20 40 60 80 100 1200

10

20

30

40

50

60

Flow (usgpm)

Head

(ft)

3.05 in

2.38 in

System

3.05 in1.5 hp

74747575

70

70

66

66

61

61

5344

Water, spgr= 1.0000

PT679-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1

73

--- Admin Data --- Tag Num: HW-P5/6 Service: Fan Coil Heating Pump Location: Mech Room

--- Motor Data --- Motor Size: 1.5 hp

--- Design Duty Point --- Flow: 36 usgpm Head: 47 ft Impeller: 3.05 in

--- Control Data --- 1. Hmax @ 53.3 Hz: • 36 @ 47, 0.77 hp 2. Control (QPC) @ 49.5 Hz: • 31.8 @ 40.7, 0.6 hp 3. Control (QPC) @ 45.7 Hz: • 27.3 @ 35.1, 0.47 hp 4. Control (QPC) @ 42.0 Hz: • 22.5 @ 29.8, 0.35 hp 5. Control (QPC) @ 38.1 Hz: • 16.8 @ 24.9, 0.25 hp 6. Index @ 34.4 Hz: • 9 @ 20.6, 0.17 hp 7. Hmin: 18.8 ft 32.7 Hz: • Setting= 40.00% Hmax

Series 4380Design Envelope: 1503-001.5

Integrated Intelligent Variable Speed with Sensorless Control

0 20 40 60 80 100 120 140 1600

20

40

60

80

100

Flow (usgpm)

Head

(ft)

4950 rpm

2578 rpm

2449 rpm

1800 rpm System

Avg.Load (QPC)

3997 rpm

1.5 hp

73

72

72

69

69

64

64

57

57

47

Index Flow (25.0% Duty Flow)

Water, spgr= 1.0000

PT679-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1

1

2

3

4

56

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 26 of 40

Page 33: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Options

Sensorless Bundle: Yes Parallel Sensorless: NoEnergy Performance Bundle: No Protection Bundle: No

Dual Season Setup: No Zone Optimization Bundle: No

Cooling Heating

Q1: N/A Q2: N/AH1: N/A H2: N/A

H1min: N/A H2min: N/A

Maximum Flow: N/A Minimum Flow: N/A

Optional Services

On-Site Pump Commissioning: Cost Not Included Extended Warranty: NoPump Manager: No Include Spare Parts Qty: 0

Design envelope pumping unit capability

Operating point Flow Head Efficiency

Full capability at 100% design flow 73.6 ft36 USgpm 48.75 %Design point 36 USgpm 47 ft 55.81 %

50% average flow (with default load profile) 18 usgpm 25.9 ft 43.47 %

Dimensional data (not for construction)

Top viewSide view

Weight: 53 lb• Not to scale• R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports

Connection details

Connection Size Rating OD Bolt quantity* BCD Bolt size

Inlet 1.5 5ANSI-125 4 0.53.88

Outlet 1.5 5ANSI-125 4 0.53.88

*Equally spaced straddling centreline

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 27 of 40

Page 34: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Special instructions

The operating point %BEP results in reduced Sensorless control accuracy.

OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified

Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout

Pump Manager and Extended Warranty Note:

Keep your system running as intended with Pump Manager, or combined with anExtended Warranty to provide price certainty in your maintenance and repairbudget. Both are available directly to the owner/end user of the pump. PumpManager proactively tracks performance and provides early diagnostic warnings,web accessible trends and analysis along with automated reports. Contact yourArmstrong contacts to take advantage of an Extended Warranty or Pump Manager.Additional equipment Flotrex: FTV-2GS (570200-208) Suction Guide: SG-215TF (516860-062)

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 28 of 40

Page 35: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Design Envelope Booster System

Series : 6800 G/E Design Envelope Model: N260322-20 hp

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Tag number: DWBP-1/2 Water Supply: City Mains or Tank

Suction (supply) pressure: 40.0 psiService: DW Booster

Location: Mech Room Total flow capacity: 370.0 USgpm

Quantity: 1 System boost pressure rating: 88.0 psiPower Supply: Discharge pressure: 295.7 ft208/3/60

System construction data

System description: Duplex Piping material: Stainless Steel 304Header size: 6 in Valve type Check valve only

Header connections: Grooved Maximum working pressure: 536.0 ft

Suction orientation: Right* Discharge orientation: Right*

*when facing booster controller Low lead certification: NSF 372

Pump data

Number of pumps: 2 Duty flow per pump: 185 USgpmOperation: 2 Duty Duty head: 88 psig

Series: 4700 Motor size: 20 hp

Size: VMS-45:03-2 Motor speed: 3600 rpmMotor efficiency: NEMA Premium (12.12)Construction: Stainless Steel 304

Standby Pump No Motor enclosure: ODP

Booster control panel data

Enclosure: NEMA 12 Painted steel Human Machine Interface: Touch Screen 4” StandardSelected features: BMS Port (serial communication port for connection to BMS - BacNet (MS/TP))

HMI: Touch Screen 4” Standard

IVS-102 variable frequency control data

Quantity: 2 (integrated with motors) EMI/RFI control: Integrated filter to meet EN61800-3Enclosure: UL Type 12 Cooling: Fan cooled through back channel

Harmonic suppression: Integrated DC link reactor Ambient temperature: -10C to +45C(upto 1000m elevation)

Drawdown tank data

Size and rating: 132 US Gallon Non-ASME Mounting: Remote Mounted

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 29 of 40

EWong
Highlight
Page 36: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Performance curve

Dimensional data (not for construction)

WEIGHTS (lb) NOT for CONSTRUCTION

Weights

1703

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 30 of 40

Page 37: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 31 of 40

rlogozzo
Line
Page 38: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Booster controller wiring diagram

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 32 of 40

Page 39: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 33 of 40

rlogozzo
Rectangle
Page 40: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Flo-trex valveModel: FTV-F (2.5 to 12 inch), FTV-G

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

DesignflowrateTag Qty Model Size Config Flange rating Pressure

Drop* Associated pump

GC-P-1/2 2 FTV-4FA 4 in Angle Flanged

ANSI-125 190.0 USgpm 2.8 ft GC-P-1/2 Design Envelope Sensorless 4380 2505-003.0

CH-P-1/2 2 FTV-4FA 4 in Angle Flanged

ANSI-125 185.0 USgpm 2.8 ft CH-P-1/2 Design Envelope Sensorless 4380 0205-005.0

B-P-1&2 2 FTV-2.5FA 2.5 in Angle Flanged

ANSI-125 72.0 USgpm 3.2 ft B-P-1&2 Design Envelope Sensorless 4380 1503-001.5

HW-P5/6 2 FTV-2GS 2 in Straight None 36.0 USgpm 3.0 ft HW-P5/6 Design Envelope Sensorless 4380 1503-001.5

*at design flow

Materials of construction

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

FTV-2.5FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12

Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302

Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and

Gasketed Cap

Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 34 of 40

Page 41: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

FTV-2GS-Flo-Trex Valve-GRV-Straight FTV1.25-2

Body: SS 304 A351 Spring: SS ASTM A-313 TYPE 302-(18-8)

Disc: Brass C46500 EPDMO rings:2 metering ports: Brass Body with EPDM Check and

Gasketed CapStem: Brass C46500

2 drain tappings: ¼" NPT with SS 304 Plug

Operating limits (temperature - pressure)

FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged

Maximum pressure: 175 psi

Maximum temperature: 230 F

FTV-2GS-Flo-Trex Valve-GRV-Straight

Maximum pressure: 175 psi

Maximum temperature: 230 F

Dimensional data (not for construction)

Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb

Side view Front view

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 35 of 40

Page 42: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Model: FTV-2.5FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 33 lb

Side view Front view

Model: FTV-2GS-Flo-Trex Valve-GRV-Straight Weight: 6 lb

Side view Front view

Not to scale Units of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 36 of 40

Page 43: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Submittal Ref. #: 630442.2 rev1

Suction guideModel: SG (2 to 12 inches), SG-TF

Project name: CC-17860 Hawthorne - 4988 Cambie St

Location: Vancouver Representative: Con-Cur West Marketing Inc.

Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062

Engineer: Rocky Point Engineering e-mail: [email protected]

Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo

Application design data

Design flowrateTag Qty Model System Pump Pressure

Drop* Associated pump

GC-P-1/2 2 SG-425 4 in 2.5 in 190.0 USgpm 1.3 ft GC-P-1/2 Design Envelope Sensorless 4380 2505-003.0

CH-P-1/2 2 SG-42 4 in 2 in 185.0 USgpm 1.3 ft CH-P-1/2 Design Envelope Sensorless 4380 0205-005.0

B-P-1&2 2 SG-2515 2.5 in 1.5 in 72.0 USgpm 1.1 ft B-P-1&2 Design Envelope Sensorless 4380 1503-001.5

HW-P5/6 2 SG-215TF 2 in 1.5 in 36.0 USgpm 0.1 ft HW-P5/6 Design Envelope Sensorless 4380 1503-001.5

*at design flow

Materials of construction

SG-425Body: Ductile Iron Cover gasket: Synthetic fiber

Guide vanes: Ductile Iron Strainer: Stainless steel .188(5mm) perforated

Cover plate: Ductile Iron Start-up strainer*: 10 mesh Galvanized steel

SG-42Body: Ductile Iron Cover gasket: Synthetic fiber

Guide vanes: Ductile Iron Strainer: Stainless steel .188(5mm) perforated

Cover plate: Ductile Iron Start-up strainer*: 10 mesh Galvanized steel

SG-2515Body: Ductile Iron Cover gasket: Synthetic fiber

Guide vanes: Ductile Iron Strainer: Stainless steel .188(5mm) perforated

Cover plate: Ductile Iron Start-up strainer*: 10 mesh Galvanized steel

SG-215TF

Body: Ductile Iron Cover gasket: Synthetic fiber

Guide vanes: Ductile Iron Strainer: Stainless Steel,0.125"(3mm)Perf.

Cover plate: Ductile Iron Start-up strainer*: Fine Mesh Galvanized Steel

*Remove start up strainer after 24 hours

Operating limits (temperature - pressure)

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 37 of 40

Page 44: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

SG-425-Suction Guide-ANSI-125

Maximum pressure: 175 psi

Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure

SG-215TF-Suction Guide-ANSI-125

Maximum pressure: 175 psi

Maximum temperature: 230 F

Units are hydrostatically tested to 150% of maximum working pressure

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 38 of 40

Page 45: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

Dimensional data (not for construction)

SG-425 Weight: 61 lb

Side view Top view

SG-42 Weight: 58 lb

Side view Top view

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 39 of 40

Page 46: Shop-drawings Submittal Log Record 1...Mar 27, 2018  · Project #1295 Hawthorne (4976 Cambie) #1295 Date Tuesday, March 27th, 2018 Address 4976 Cambie Street Created By Paul Warwick

SG-2515 Weight: 33 lb

Side view Top view

SG-215TF Weight: 24 lb

Side view Top view

Not to scaleUnits of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be usedFor certified dimensions, please contact your Armstrong representative

www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 40 of 40