shop-drawings submittal log record 1...mar 27, 2018 · project #1295 hawthorne (4976 cambie) #1295...
TRANSCRIPT
Project #1295 Hawthorne (4976 Cambie) #1295Date Tuesday, March 27th, 2018
Address 4976 Cambie Street
Created By Paul WarwickCreated Tuesday, March 27th, 2018
Shop-drawings Submittal Log
Record 1
Record Name: shop drawings submittal-008
Code: 15-400Drawing Description: Pumps GC-P-1/2, CH-P-1/2, B-P-1/2, DW-RP-1, DW-P-1/2, HW-P-1/2, HW-P-3/4, HW-P-5/6, DWBP-1/2
Vendor (Trade): PML- 011 Required by: 2018-04-11
Submissions
# Received From Trade Sent To ConsultantReceived From Consultant
Review Status
1 2018-03-23 2018-03-27 2018-03-27
C09092 - 011
Response Requested By:
Subject: Shop DrawingsSent Via: EmailStatus: For Review
SUBMITTALS
ITEM DESCRIPTION
COMMENTS
To: Performance Construction Ltd.
2572 Davies AvenuePort Coquitlam, BC V3C 2J9
Phone: 604-468-9999Fax: 604-468-9925
Submittal
Submittal ID:Date Sent: 23-Mar-18
11-Apr-18
Project Name: Hawthorne
Paul Warwick1150 - 21331 Gordon WayRichmond, BC V6W [email protected]
From: Dal Seymour
SUPPLIER SPECIFICATION SECTIONPumps GC-P-1/2, CH-P-1/2, B-P-1/2, EmcoDW-RP-1, DW-P-1/2, HW-P-1/2, HW-P-3/4, HW-P-5/6, DWBP-1/2
PROJECT:
CONTRACTOR: Professional Mechanical Ltd.
SUBMITTED BY: EMCO CorporationQUOTE #: EM17-7508
PREPARED BY: Ryan Hall/ewong
DATE: 2-Feb-18
BRITISH COLUMBIA ALBERTA SASKATCHEWAN MANITOBA ONTARIO
ABBOTSFORD LANGLEY CALGARY PRINCE ALBERT WINNIPEG DRYDEN
CAMPBELL RIVER PORT COQUITLAM CAMROSE REGINA THUNDER BAY
CHILLIWACK PRINCE GEORGE EDMONTON SASKATOON
COQUITLAM RICHMOND FORT MCMURRAY
COURTENAY SALMON ARM GRAND PRAIRIE
CRANBROOK SURREY HIGH LEVEL
DAWSON CREEK TERRACE LETHBRIDGE
FORT ST. JOHN VANCOUVER RED DEER
KAMLOOPS VERNON
KELOWNA VICTORIA
"The Ensuite" DESIGNER SHOWROOMSBURNABY EDMONTON CALGARY WINNIPEG VICTORIA
EMCO DESIGN SERVICES - B.C. DISTRICT3139 Sumner Avenue Burnaby, B.C. V5G 3E3
Tel. No. 604-412-2830 Fax. 604-412-3932 www.emcobc.ca
Hawthorne - 4988 Cambie Street - Pennyfarthing QE Park Properties 44 units
SKU DESCRIPTION
tag GC-P-1/2
armstrong 4380DE, 2.5x2.5x5, 190 Usgpm, 35ft, 3hp, 208/3/60nd FTV-4FA, 4" triple duty valvend SG-425, 4x2.5" suction guidetag CH-P-1/2
nd 4380DE, 2x2x5, 185 Usgpm, 52ft, 5hp, 208/3/60nd FTV-4FA, 4" triple duty valvend SG-42, 4x2" suction guidetag B-P-1/2
nd 4380DE, 1.5x1.5x6, 72 Usgpm, 42ft, 1.5hp, 208/3/60nd FTV-2.5FA, 2.5" triple duty valvend SG-2515 2.5x1.5" suction guidetag DW-RP-1
nd Astro 250SS-TA, 13 Usgpm, 5.5ft, 115/1/60w/ timer, aquastat, 6' line cordtag DW-P-1/2
nd E15.2B, 34 Usgpm, 14ft, .04hp, 115/1/60tag HW-P-1/2
nd E15.2, 34 Usgpm, 14ft, 115/1/60tag HW-P-3/4
nd Astro 280CI, 9 Usgpm, 21ft, 115/1/60tag HW-P-5/6
nd 4380DE, 1.5x1.5x6, 36 Usgpm, 47ft, 1.5hp, 1800, 208/3/60nd FTV-2GS, 2" triple duty valvend SG-215TF 2x1.5" suction guidetag DWBP-1/2
nd N260322-20 hp Duplex variable speed boosternd Construction: Standardnd Operation: Lead/1-Lagnd Meets ASHRAE 90.1: Yesnd Total flow: 370.0 Usgpmnd Booster pressure: 88.0 psi
NOTES
DESIGN SERVICES3139 Sumner Avenue Burnaby, B.C. V5G 3E3
Tel. No. 604-412-2830 Fax. 604-412-3932
----- EQUIPMENT SCHEDULE -----
Hawthorne - 4988 Cambie Street - Pennyfarthing QE Park Properties 44 units
Page 1 of 2
SKU DESCRIPTION NOTES
nd Piping material: Stainless Steel 304nd Suction header size: 6 innd Discharge header size: 6innd Suction header connection rating: ANSI-150nd Discharge header connection rating: ANSI-150nd Valve type: Check valve onlynd IVS model 20 hp/20 hpnd Enclosure: NEMA 12 Painted steel enclosurend Tank mounting: Remote Mountednd Tank size/rating: 132 US Gallon Non-ASMEnd Other options: BMS Port (serial communication port for connection to nd BMS - BacNet (MS/TP)ndndtag
HMI: Touch Screen 4" Standard Start-up included
Page 2 of 2
TAG:-
Submittal Ref. #: 630442.2 rev1
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 2505-003.0
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: GC-P-1/2 Pipe orientation: ParallelSuction pressure: 0 ftService: CHW - Chiller & B.T.
Location: Mech Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUPump/motor run qty: 2
Duty flow per pump: 190 USgpm Specific gravity: 1.0000
Duty head: 35 ft Safety factor % head: 0 %
Environment: Indoors Total dissolved solids: 0 ppm
Materials of construction
Construction: LPDESF Impeller: Stainless Steel 316, A743 CF8MRating: ANSI-125 Pump Shaft: SS ASTM A276 Type 416Connections: Inlet: 2.5 in, Outlet: 2.5 in Casing o-ring: EPDM
Casing (volute): Ductile Iron A536 GR 65-45-12, e-coated Flush line: Braided Stainless Steel
Stub Shaft: SS ASTM A276 Type 416
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon CarbideSprings: Stainless Steel Secondary seal: EPDMRotating hardware: Stainless Steel
iECM Data
ArmstrongSupplier: Insulation class: Class F InsulationSize: 3 hp Inverter motor type: Not applicableFrame number: IEC90 Efficiency: IE5Enclosure: TEFC Operating speed @ 100% flow: 2785 rpmMotor Electrics: 208/3/60 Operating speed @ 50% flow: 1902 rpm
Sensorless control: Yes-Quadratic press control Communication port: RS 485BMS protocol: BACnet MS/TP(card) Analog inputs: 2 (current or voltage)Enclosure: UL Type 12
Digital inputs:Analog outputs: 1 (current or voltage)
Fused disconnect switch: No 2 (programmable)
Control orientation: L5 Digital outputs: 2 (programmable)Expansion card: Not Applicable Cooling: Not ApplicableBHP at 50% load/flow and 55% of design head: 0.54 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)
Meets ASHRAE 90.1: Yes EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: 14 ft
*If minimum maintained system pressure is not known, default is 40% of design head.**If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 1 of 40
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: GC-P-1/2 Service: CHW - Chiller & B.T. Location: Mech Room
--- Motor Data --- Motor Size: 3 hp
--- Design Duty Point --- Flow: 190 usgpm Head: 35 ft Impeller: 4.41 in
--- Performance Data --- • NPSHR: 7.1201 ft • Eff. @ Design: 77.34 % • BHP @ Design: 2.17 hp • Mtr Capability @ Rated Spd: 2.5 hp • %Mtr Safety: 15.23% • BEP @ Design Imp.: 77.72 % @ 180.2 usgpm • %max imp. range: 62.90 % • Outlet Velocity: 12.73 ft/s • VFD Op.Speed: 2785 rpm • VFD Setting: 46.4 Hz
Series 4380Design Envelope: 2505-003.0 @ 46.4 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 80 160 240 320 4000
10
20
30
40
50
60
70
80
Flow (usgpm)
Head
(ft)
4.94 in
3.49 in
System
4.41 in
1.5 hp
2 hp
3 hp
79
79
77
77
72
72
65
65
55
55%
42
Water, spgr= 1.0000
PT673-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1
80
--- Admin Data --- Tag Num: GC-P-1/2 Service: CHW - Chiller & B.T. Location: Mech Room
--- Motor Data --- Motor Size: 3 hp
--- Design Duty Point --- Flow: 190 usgpm Head: 35 ft Impeller: 4.41 in
--- Control Data --- 1. Hmax @ 46.4 Hz: • 190 @ 35, 2.17 hp 2. Control (QPC) @ 43.2 Hz: • 171.1 @ 31, 1.73 hp 3. Control (QPC) @ 39.8 Hz: • 150.9 @ 27.3, 1.34 hp 4. Control (QPC) @ 36.5 Hz: • 129.6 @ 23.8, 1.01 hp 5. Control (QPC) @ 33.3 Hz: • 107.5 @ 20.7, 0.74 hp 6. Control (QPC) @ 30.0 Hz: • 80.9 @ 17.8, 0.51 hp 7. Hmin: 14 ft • Setting= 40.00% Hmax
Series 4380Design Envelope: 2505-003.0
Integrated Intelligent Variable Speed with Sensorless Control
0 80 160 240 320 4000
10
20
30
40
50
60
70
80
Flow (usgpm)
Head
(ft)
3300 rpm
1800 rpm
System
Avg.Load (QPC)
2785 rpm
3 hp
78
77
77
74
74
70
70
62
62
52
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT673-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1
1
23
45
6
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 2 of 40
--- Admin Data --- Tag Num: GC-P-1/2 Service: CHW - Chiller & B.T. Location: Mech Room
--- Motor Data --- Motor Size: 3 hp
--- System Design Data --- Piping: Parallel, Run Qty = 2 Fluid: Water Sp.Gr.= 1.0000, vis= 31 ssu, 60 F Suction: 0 ft System: Closed, M.Head: 0 ft Total Design Flow = 380 usgpm Total Design Head = 35 ft
--- Pump Data @ Curve# 2 --- NPSHR: 7.1313 ft Flow: 380 usgpm Head: 35 ft Eff: 77.3%, BEP: 77.7% %BEP (Flow): 105% BHP = 4.34 hp BHP/Pump= 2.17 hp
Parallel Pump CurveDesign Envelope: 2505-003.0
Integrated Intelligent Variable Speed with Sensorless Control
0 100 200 300 400 500 6000
10
20
30
40
50
Flow (usgpm)
Head
(ft)
System
1
1
2
2
11
11
22
22
Water, spgr= 1.0000
PT673-2-0 (3.30.1.5)
Options
Sensorless Bundle: Yes Parallel Sensorless: NoEnergy Performance Bundle: No Protection Bundle: No
Dual Season Setup: No Zone Optimization Bundle: No
Cooling Heating
Q1: N/A Q2: N/AH1: N/A H2: N/A
H1min: N/A H2min: N/A
Maximum Flow: N/A Minimum Flow: N/A
Optional Services
On-Site Pump Commissioning: Cost Not Included Extended Warranty: NoPump Manager: No Include Spare Parts Qty: 0
Design envelope pumping unit capability
Operating point Flow Head Efficiency
Full capability at 100% design flow 44.3 ft190 USgpm 77.65 %Design point 190 USgpm 35 ft 77.34 %
50% average flow (with default load profile) 95 usgpm 19.3 ft 74.64 %
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 3 of 40
Dimensional data (not for construction)
Top viewSide view
Weight: 80.5 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 2.5 7ANSI-125 4 0.6255.5
Outlet 2.5 7ANSI-125 4 0.6255.5
*Equally spaced straddling centreline
Special instructions
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
Pump Manager and Extended Warranty Note:
Keep your system running as intended with Pump Manager, or combined with anExtended Warranty to provide price certainty in your maintenance and repairbudget. Both are available directly to the owner/end user of the pump. PumpManager proactively tracks performance and provides early diagnostic warnings,web accessible trends and analysis along with automated reports. Contact yourArmstrong contacts to take advantage of an Extended Warranty or Pump Manager.Additional equipment Flotrex: FTV-4FA (570200-478) Suction Guide: SG-425 (516860-036)
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 4 of 40
Submittal Ref. #: 630442.2 rev1
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 0205-005.0
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: CH-P-1/2 Pipe orientation: SingleSuction pressure: 0 ftService: CHW - Load & B.T.
Location: Mech Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUDuty flow per pump: 185 USgpm
Specific gravity: 1.0000Duty head: 52 ft
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: LPDESF Impeller: Stainless Steel 316, A743 CF8MRating: ANSI-125 Pump Shaft: SS ASTM A276 Type 416Connections: Inlet: 2 in, Outlet: 2 in Casing o-ring: EPDM
Casing (volute): Ductile Iron A536 GR 65-45-12, e-coated Flush line: Braided Stainless Steel
Stub Shaft: SS ASTM A276 Type 416
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon CarbideSprings: Stainless Steel Secondary seal: EPDMRotating hardware: Stainless Steel
iECM Data
ArmstrongSupplier: Insulation class: Class F InsulationSize: 5 hp Inverter motor type: Not applicableFrame number: IEC112 Efficiency: IE5Enclosure: TEFC Operating speed @ 100% flow: 3089 rpmMotor Electrics: 208/3/60 Operating speed @ 50% flow: 2080 rpm
Sensorless control: Yes-Quadratic press control Communication port: RS 485BMS protocol: BACnet MS/TP(card) Analog inputs: 2 (current or voltage)Enclosure: UL Type 12
Digital inputs:Analog outputs: 1 (current or voltage)
Fused disconnect switch: No 2 (programmable)
Control orientation: L5 Digital outputs: 2 (programmable)Expansion card: Not Applicable Cooling: Not ApplicableBHP at 50% load/flow and 55% of design head: 0.79 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)
Meets ASHRAE 90.1: Yes EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: 20.8 ft
*If minimum maintained system pressure is not known, default is 40% of design head.**If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 5 of 40
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: CH-P-1/2 Service: CHW - Load & B.T. Location: Mech Room
--- Motor Data --- Motor Size: 5 hp
--- Design Duty Point --- Flow: 185 usgpm Head: 52 ft Impeller: 4.97 in
--- Performance Data --- • NPSHR: 12.9 ft • Eff. @ Design: 76.64 % • BHP @ Design: 3.17 hp • Mtr Capability @ Rated Spd: 4.04 hp • %Mtr Safety: 27.57% • BEP @ Design Imp.: 78.78 % @ 161.0 usgpm • %max imp. range: 100.00 % • Outlet Velocity: 17.69 ft/s • VFD Op.Speed: 3089 rpm • VFD Setting: 51.5 Hz
Series 4380Design Envelope: 0205-005.0 @ 51.5 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 50 100 150 200 250 3000
10
20
30
40
50
60
70
80
Flow (usgpm)
Head
(ft)
4.97 in
3.50 in
System
4.97 in
5
7.5 hp
8080
77
77
74
74
69
69
62
62
53
53%
Water, spgr= 1.0000
PT674-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1
79
--- Admin Data --- Tag Num: CH-P-1/2 Service: CHW - Load & B.T. Location: Mech Room
--- Motor Data --- Motor Size: 5 hp
--- Design Duty Point --- Flow: 185 usgpm Head: 52 ft Impeller: 4.97 in
--- Control Data --- 1. Hmax @ 51.5 Hz: • 185 @ 52, 3.17 hp 2. Control (QPC) @ 47.2 Hz: • 163.4 @ 45.2, 2.4 hp 3. Control (QPC) @ 42.8 Hz: • 140.8 @ 38.9, 1.76 hp 4. Control (QPC) @ 38.7 Hz: • 117.4 @ 33.4, 1.26 hp 5. Control (QPC) @ 34.3 Hz: • 90.3 @ 28.2, 0.83 hp 6. Control (QPC) @ 30.0 Hz: • 55.9 @ 23.6, 0.48 hp 7. Hmin: 20.8 ft • Setting= 40.00% Hmax
Series 4380Design Envelope: 0205-005.0
Integrated Intelligent Variable Speed with Sensorless Control
0 80 160 240 320 4000
20
40
60
80
100
120
140
160
Flow (usgpm)
Head
(ft)
3960 rpm
1800 rpm
System
Avg.Load (QPC)
3089 rpm
5 hp
7978
78
76
76
71
71
65
65
56
56
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT674-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1
12
34
56
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 6 of 40
Options
Sensorless Bundle: Yes Parallel Sensorless: NoEnergy Performance Bundle: No Protection Bundle: No
Dual Season Setup: No Zone Optimization Bundle: No
Cooling Heating
Q1: N/A Q2: N/AH1: N/A H2: N/A
H1min: N/A H2min: N/A
Maximum Flow: N/A Minimum Flow: N/A
Optional Services
On-Site Pump Commissioning: Cost Not Included Extended Warranty: NoPump Manager: No Include Spare Parts Qty: 0
Design envelope pumping unit capability
Operating point Flow Head Efficiency
Full capability at 100% design flow 70.7 ft185 USgpm 78.61 %Design point 185 USgpm 52 ft 76.64 %
50% average flow (with default load profile) 92.5 usgpm 28.6 ft 77.60 %
Dimensional data (not for construction)
Top viewSide view
Weight: 85 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 2 6ANSI-125 4 0.6254.75
Outlet 2 6ANSI-125 4 0.6254.75
*Equally spaced straddling centreline
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 7 of 40
Special instructions
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
Pump Manager and Extended Warranty Note:
Keep your system running as intended with Pump Manager, or combined with anExtended Warranty to provide price certainty in your maintenance and repairbudget. Both are available directly to the owner/end user of the pump. PumpManager proactively tracks performance and provides early diagnostic warnings,web accessible trends and analysis along with automated reports. Contact yourArmstrong contacts to take advantage of an Extended Warranty or Pump Manager.Additional equipment Flotrex: FTV-4FA (570200-478) Suction Guide: SG-42 (516860-035)
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 8 of 40
Submittal Ref. #: 630442.2 rev1
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 1503-001.5
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: B-P-1&2 Pipe orientation: SingleSuction pressure: 0 ftService: Boiler Loop
Location: Mech Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUDuty flow per pump: 72 USgpm
Specific gravity: 1.0000Duty head: 42 ft
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: LPDESF Impeller: Stainless Steel 316, A743 CF8MRating: ANSI-125 Pump Shaft: SS ASTM A276 Type 416Connections: Inlet: 1.5 in, Outlet: 1.5 in Casing o-ring: EPDM
Casing (volute): Ductile Iron A536 GR 65-45-12, e-coated Flush line: Braided Stainless Steel
Stub Shaft: SS ASTM A276 Type 416
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon CarbideSprings: Stainless Steel Secondary seal: EPDMRotating hardware: Stainless Steel
iECM Data
ArmstrongSupplier: Insulation class: Class F InsulationSize: 1.5 hp Inverter motor type: Not applicableFrame number: IEC90S Efficiency: IE5Enclosure: TEFC Operating speed @ 100% flow: 4161 rpmMotor Electrics: 208/3/60 Operating speed @ 50% flow: 2886 rpm
Sensorless control: Yes-Quadratic press control Communication port: RS 485BMS protocol: BACnet MS/TP(card) Analog inputs: 2 (current or voltage)Enclosure: UL Type 12
Digital inputs:Analog outputs: 1 (current or voltage)
Fused disconnect switch: No 2 (programmable)
Control orientation: L5 Digital outputs: 2 (programmable)Expansion card: Not Applicable Cooling: Not ApplicableBHP at 50% load/flow and 55% of design head: 0.26 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)
Meets ASHRAE 90.1: No EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: 16.8 ft
*If minimum maintained system pressure is not known, default is 40% of design head.**If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 9 of 40
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: B-P-1&2 Service: Boiler Loop Location: Mech Room
--- Motor Data --- Motor Size: 1.5 hp
--- Design Duty Point --- Flow: 72 usgpm Head: 42 ft Impeller: 3.05 in
--- Performance Data --- • NPSHR: 10.5 ft • Eff. @ Design: 72.40 % • BHP @ Design: 1.05 hp • Mtr Capability @ Rated Spd: 1.26 hp • %Mtr Safety: 19.13% • BEP @ Design Imp.: 72.58 % @ 75.8 usgpm • %max imp. range: 100.00 % • Outlet Velocity: 11.35 ft/s • VFD Op.Speed: 4161 rpm • VFD Setting: 55.5 Hz
Series 4380Design Envelope: 1503-001.5 @ 55.5 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 20 40 60 80 100 1200
10
20
30
40
50
60
Flow (usgpm)
Head
(ft)
3.05 in
2.38 in
System
3.05 in1.5 hp
74747575
70
70
66
66
61
61
5344
Water, spgr= 1.0000
PT679-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1
73
--- Admin Data --- Tag Num: B-P-1&2 Service: Boiler Loop Location: Mech Room
--- Motor Data --- Motor Size: 1.5 hp
--- Design Duty Point --- Flow: 72 usgpm Head: 42 ft Impeller: 3.05 in
--- Control Data --- 1. Hmax @ 55.5 Hz: • 72 @ 42, 1.05 hp 2. Control (QPC) @ 50.9 Hz: • 63.3 @ 36.3, 0.81 hp 3. Control (QPC) @ 46.5 Hz: • 54.5 @ 31.2, 0.6 hp 4. Control (QPC) @ 42.0 Hz: • 44.6 @ 26.5, 0.43 hp 5. Control (QPC) @ 37.5 Hz: • 33.3 @ 22.2, 0.29 hp 6. Index @ 33.0 Hz: • 18 @ 18.4, 0.17 hp 7. Hmin: 16.8 ft 30.9 Hz: • Setting= 40.00% Hmax
Series 4380Design Envelope: 1503-001.5
Integrated Intelligent Variable Speed with Sensorless Control
0 20 40 60 80 100 120 140 1600
20
40
60
80
100
Flow (usgpm)
Head
(ft)
4950 rpm
2473 rpm
2315 rpm
1800 rpm System
Avg.Load (QPC)
4161 rpm
1.5 hp
73
72
72
69
69
64
64
57
57
47
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT679-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1
1
2
34
56
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 10 of 40
Options
Sensorless Bundle: Yes Parallel Sensorless: NoEnergy Performance Bundle: No Protection Bundle: No
Dual Season Setup: No Zone Optimization Bundle: No
Cooling Heating
Q1: N/A Q2: N/AH1: N/A H2: N/A
H1min: N/A H2min: N/A
Maximum Flow: N/A Minimum Flow: N/A
Optional Services
On-Site Pump Commissioning: Cost Not Included Extended Warranty: NoPump Manager: No Include Spare Parts Qty: 0
Design envelope pumping unit capability
Operating point Flow Head Efficiency
Full capability at 100% design flow 54.1 ft72 USgpm 71.23 %Design point 72 USgpm 42 ft 72.40 %
50% average flow (with default load profile) 36 usgpm 23.1 ft 66.01 %
Dimensional data (not for construction)
Top viewSide view
Weight: 53 lb• Not to scale • R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 1.5 5ANSI-125 4 0.53.88
Outlet 1.5 5ANSI-125 4 0.53.88
*Equally spaced straddling centreline
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 11 of 40
Special instructions
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
Pump Manager and Extended Warranty Note:
Keep your system running as intended with Pump Manager, or combined with anExtended Warranty to provide price certainty in your maintenance and repairbudget. Both are available directly to the owner/end user of the pump. PumpManager proactively tracks performance and provides early diagnostic warnings,web accessible trends and analysis along with automated reports. Contact yourArmstrong contacts to take advantage of an Extended Warranty or Pump Manager.Additional equipment Flotrex: FTV-2.5FA (570200-476) Suction Guide: SG-2515 (516860-034)
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 12 of 40
Submittal Ref. #: 630442.2 rev1
Wet rotor circulator
Model: Part number: 110223b-149Series ASTRO 250SS-TA
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: DW-RP-1 Pipe orientation: SingleSuction pressure: 0 ftService: DHW
Location: Mech Room Fluid: Water:
Quantity: 1 Operating temperature: 60 F*Viscosity: 31 SSUDuty flow per pump: 13 USgpm
Specific gravity: 1.0000Duty head: 5.5 ft
Total dissolved solids: 0 ppm
* for open systems, it is recommended that the fluid temperature be less than 150F (66C) to avoid precipitation of calcium.
Materials of construction
Construction: SS150 Impeller: Polyether Imide (PEI)
Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic
Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01
Companion flange: Bronze 1 1/2" Listing: ETL listed for US and Canada
**certified <0.25 weighted average percent lead and complies with Californai Health and Safety Code section 114875 (commonly known as AB1953)
Motor electrical data
Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.157 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 3600 rpmMotor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 13 of 40
Performance curve
--- Admin Data --- Tag Num: DW-RP-1 Service: DHW Location: Mech Room
--- Motor Data --- Motor Size: 0.157 hp Motor Speed: [3] 3600 rpm
--- Design Duty Point --- Flow: 13 usgpm Head: 5.5 ft
--- Pump Data --- Pump Size: Astro 250SS Impeller: 2.68 in Suction Head Req: 0 ft Projected Flow: 14.1 usgpm Projected Head: 6.4309 ft
Series Astro MultiSpeedAstro 250SS @ Discrete Speeds
0 4 8 12 16 200
5
10
15
20
25
30
Flow (usgpm)
Head
(ft)
System
Projected
[1] 2300
[2] 2900
[3] 3600
Water:, spgr= 1.0000
PT620-0-228 (3.30.1.5)
Dimensional data (not for construction)
Top viewSide view
Weight: 9 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 14 of 40
Special instructions
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 15 of 40
Submittal Ref. #: 630442.2 rev1
E.2 series dry motor circulator
Model: Part number: 182212-662Series E15.2B brz 120V
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: DW-P-1/2 Pipe orientation: SingleSuction pressure: 0 ftService: DHW Production
Location: Mech Room Fluid: Water:
Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUDuty flow per pump: 34 USgpm
Specific gravity: 1.0000Duty head: 14 ft
Total dissolved solids: 0 ppm
Materials of construction
Construction: AB (All Bronze) Impeller: 30% Glass-filled NorylRating: Not applicable Bearings: Permanently lubricated SS
Connections: 1.25 in. Dia. 2-Bolt flanges
Mechanical seal data
Manufacturer: Armstrong Seal: Silicon CarbideSeal type: Bellows-style Silicon Carbide
Motor electrical data
Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.4 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 3400 rpmMotor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 16 of 40
Performance curve
--- Admin Data --- Tag Num: DW-P-1/2 Service: DHW Production Location: Mech Room
--- Motor Data --- Motor Size: 0.4 hp Motor Speed: 3600 rpm
--- Design Duty Point --- Flow: 34 usgpm Head: 14 ft
--- Pump Data --- Pump Size: E15.2B Impeller: 2.4 in Projected Flow: 36.6 usgpm Projected Head: 16.3 ft
Series E.2Selected Size: E15.2B @ 3400 rpm
0 20 40 60 80 100 120 140 1600
10
20
30
40
50
60
70
80
Flow (usgpm)
Head
(ft)
System
Projected
E15.2B
Water:, spgr= 1.0000
PT518-0-168 (3.30.1.5)
Dimensional data (not for construction)
Top viewSide view
Weight: 23 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 17 of 40
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 1.25 7.5N/A 4 0.6256
Outlet 1.25 7.5N/A 4 0.6256
*Equally spaced straddling centreline
Special instructions
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 18 of 40
Submittal Ref. #: 630442.2 rev1
E.2 series dry motor circulator
Model: Part number: 182212-661Series E15.2 ci 120V
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: HW-P-1/2 Pipe orientation: ParallelSuction pressure: 0 ftService: DHW Source Pump
Location: Mech Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUPump/motor run qty: 2
Duty flow per pump: 34 USgpm Specific gravity: 1.0000
Duty head: 14 ft Total dissolved solids: 0 ppm
Materials of construction
Construction: STD125 Impeller: 30% Glass-filled NorylRating: Not applicable Bearings: Permanently lubricated SS
Connections: 1.25 in. Dia. 2-Bolt flanges
Mechanical seal data
Manufacturer: Armstrong Seal: Silicon CarbideSeal type: Bellows-style Silicon Carbide
Motor electrical data
Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.4 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 3400 rpmMotor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 19 of 40
Performance curve
--- Admin Data --- Tag Num: HW-P-1/2 Service: DHW Source Pump Location: Mech Room
--- Motor Data --- Motor Size: 0.4 hp Motor Speed: 3600 rpm
--- Design Duty Point --- Flow: 34 usgpm Head: 14 ft
--- Pump Data --- Pump Size: E15.2 Impeller: 2.4 in Projected Flow: 36.6 usgpm Projected Head: 16.3 ft
Series E.2Selected Size: E15.2 @ 3400 rpm
0 20 40 60 80 100 120 140 1600
10
20
30
40
50
60
70
80
Flow (usgpm)
Head
(ft)
System
Projected
E15.2/E15.2B
Water, spgr= 1.0000
PT518-0-168 (3.30.1.5)
--- Admin Data --- Tag Num: HW-P-1/2 Service: DHW Source Pump Location: Mech Room
--- Motor Data --- Motor Size: 0.4 hp Motor Speed: 3600 rpm
--- System Design Data --- Piping: Parallel, Run Qty = 2 Fluid: Water Sp.Gr.= 1.0000, vis= 31 ssu, 60 F Suction: 0 ft System: Closed, M.Head: 0 ft Total Design Flow = 68 usgpm Total Design Head = 14 ft
--- Pump Data @ Curve# 2 --- NPSHR: 1 ft Projected Flow: 73.3 usgpm Projected Head: 16.3 ft Eff: 100.0%, BEP: 100.0% %BEP (Flow): 66% BHP = 0.3 hp BHP/Pump= 0.15 hp
Parallel Pump CurveSeries E.2
E15.2 @ 3400 rpm
0 80 160 240 3200
10
20
30
40
50
60
70
Flow (usgpm)
Head
(ft)
System
Projected
1 2
Water, spgr= 1.0000
PT518-0-168 (3.30.1.5)
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 20 of 40
Dimensional data (not for construction)
Top viewSide view
Weight: 23 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 1.25 7.5N/A 4 0.6256
Outlet 1.25 7.5N/A 4 0.6256
*Equally spaced straddling centreline
Special instructions
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 21 of 40
Submittal Ref. #: 630442.2 rev1
Wet rotor circulator
Model: Part number: 110223-320Series ASTRO 280CI FLG
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: HW-P-3/4 Pipe orientation: ParallelSuction pressure: 0 ftService: MAU Heating
Location: Mech Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUPump/motor run qty: 2
Duty flow per pump: 9 USgpm Specific gravity: 1.0000
Duty head: 21 ft Total dissolved solids: 0 ppm
Materials of construction
Construction: STD125 Impeller: Polyether Imide (PEI)Connections: Inlet: 1.25 in, Outlet: 1.25 in Bearings: Ceramic
Connection type: NPSM union Certified standard: UL 778 & CSA C22.2 No. 108-01
Companion flange: Cast Iron 1 1/2" Listing: ETL listed for US and Canada
Motor electrical data
Factory ChoiceSupplier: Insulation class: Not applicableSize: 0.333 hp Inverter motor type: Not applicableFrame number: Not applicable Efficiency: StdEnclosure: ODP Speed: 3600 rpmMotor Electrics: 115/1/60
Operating limits (temperature - pressure)
Maximum pressure: 150 psi
Maximum temperature: 230 F
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 22 of 40
Performance curve
--- Admin Data --- Tag Num: HW-P-3/4 Service: MAU Heating Location: Mech Room
--- Motor Data --- Motor Size: 0.333 hp Motor Speed: [3] 3600 rpm
--- Design Duty Point --- Flow: 9 usgpm Head: 21 ft
--- Pump Data --- Pump Size: Astro 280CI Impeller: 2.95 in Suction Head Req: 0 ft Projected Flow: 9.5656 usgpm Projected Head: 23.7 ft
Series Astro MultiSpeedAstro 280CI @ Discrete Speeds
0 5 10 15 20 25 300
4
8
12
16
20
24
28
32
Flow (usgpm)
Head
(ft)
System
Projected
[1] 2300
[2] 2900 [3] 3600
Water, spgr= 1.0000
PT626-0-232 (3.30.1.5)
--- Admin Data --- Tag Num: HW-P-3/4 Service: MAU Heating Location: Mech Room
--- Motor Data --- Motor Size: 0.333 hp Motor Speed: [3] 3600 rpm
--- System Design Data --- Piping: Parallel, Run Qty = 2 Fluid: Water Sp.Gr.= 1.0000, vis= 31 ssu, 60 F Suction: 0 ft System: Closed, M.Head: 0 ft Total Design Flow = 18 usgpm Total Design Head = 21 ft
--- Pump Data @ Curve# 2 --- NPSHR: 1 ft Projected Flow: 19.1 usgpm Projected Head: 23.7 ft Eff: 100.0%, BEP: 100.0% %BEP (Flow): 49% BHP = 0.115 hp BHP/Pump= 0.057 hp
Parallel Pump CurveSeries Astro MultiSpeedAstro 280CI @ 3600 rpm
0 10 20 30 40 50 60 700
8
16
24
32
Flow (usgpm)
Head
(ft)
System
Projected
1 2
Water, spgr= 1.0000
PT626-0-232 (3.30.1.5)
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 23 of 40
Dimensional data (not for construction)
Top viewSide view
Weight: 11 lb• Not to scale• Units of measure : inches [millimeters]• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative
Special instructions
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 24 of 40
Submittal Ref. #: 630442.2 rev1
Design envelope close coupled vertical in-line pump
Model: Series Design Envelope Sensorless 4380 1503-001.5
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: HW-P5/6 Pipe orientation: SingleSuction pressure: 0 ftService: Fan Coil Heating Pump
Location: Mech Room Fluid: Non-Potable Fluid - Water
Quantity: 2 Operating temperature: 60 FViscosity: 31 SSUDuty flow per pump: 36 USgpm
Specific gravity: 1.0000Duty head: 47 ft
Safety factor % head: 0 %Environment: Indoors
Total dissolved solids: 0 ppm
Materials of construction
Construction: LPDESF Impeller: Stainless Steel 316, A743 CF8MRating: ANSI-125 Pump Shaft: SS ASTM A276 Type 416Connections: Inlet: 1.5 in, Outlet: 1.5 in Casing o-ring: EPDM
Casing (volute): Ductile Iron A536 GR 65-45-12, e-coated Flush line: Braided Stainless Steel
Stub Shaft: SS ASTM A276 Type 416
Mechanical seal data
Seal type: Inside Single Spring Rotating face: Resin Bonded CarbonManufacturer code: C-ssc L EPSS 2A Stationary seat: Sintered Silicon CarbideSprings: Stainless Steel Secondary seal: EPDMRotating hardware: Stainless Steel
iECM Data
ArmstrongSupplier: Insulation class: Class F InsulationSize: 1.5 hp Inverter motor type: Not applicableFrame number: IEC90S Efficiency: IE5Enclosure: TEFC Operating speed @ 100% flow: 3997 rpmMotor Electrics: 208/3/60 Operating speed @ 50% flow: 2918 rpm
Sensorless control: Yes-Quadratic press control Communication port: RS 485BMS protocol: BACnet MS/TP(card) Analog inputs: 2 (current or voltage)Enclosure: UL Type 12
Digital inputs:Analog outputs: 1 (current or voltage)
Fused disconnect switch: No 2 (programmable)
Control orientation: L5 Digital outputs: 2 (programmable)Expansion card: Not Applicable Cooling: Not ApplicableBHP at 50% load/flow and 55% of design head: 0.19 hp Ambient temperature: 14F to 113F (up to 3280ft elevation)
Meets ASHRAE 90.1: No EMI/RFI control: Integrated filter to meet EN61800-3Min. maintained sys. pressure: 18.8 ft
*If minimum maintained system pressure is not known, default is 40% of design head.**If supplied with the system electrical details, Armstrong will run a computer simulation of the system wide harmonics. If system harmonic levels are exceeded, Armstrong can also recommend additional harmonic mitigation and the cost for such mitigation.
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 25 of 40
Operating limits (temperature - pressure)
Maximum pressure: 175 psi
Maximum temperature: 250 F
Pump casings are hydrostatically tested to 150% of maximum pump working pressure rating.
Performance curve
--- Admin Data --- Tag Num: HW-P5/6 Service: Fan Coil Heating Pump Location: Mech Room
--- Motor Data --- Motor Size: 1.5 hp
--- Design Duty Point --- Flow: 36 usgpm Head: 47 ft Impeller: 3.05 in
--- Performance Data --- • NPSHR: 4.7322 ft • Eff. @ Design: 55.81 % • BHP @ Design: 0.77 hp • Mtr Capability @ Rated Spd: 1.21 hp • %Mtr Safety: 57.66% • BEP @ Design Imp.: 72.58 % @ 72.8 usgpm • %max imp. range: 100.00 % • Outlet Velocity: 5.67 ft/s • VFD Op.Speed: 3997 rpm • VFD Setting: 53.3 Hz
Series 4380Design Envelope: 1503-001.5 @ 53.3 Hz
Integrated Intelligent Variable Speed with Sensorless Control
0 20 40 60 80 100 1200
10
20
30
40
50
60
Flow (usgpm)
Head
(ft)
3.05 in
2.38 in
System
3.05 in1.5 hp
74747575
70
70
66
66
61
61
5344
Water, spgr= 1.0000
PT679-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1
73
--- Admin Data --- Tag Num: HW-P5/6 Service: Fan Coil Heating Pump Location: Mech Room
--- Motor Data --- Motor Size: 1.5 hp
--- Design Duty Point --- Flow: 36 usgpm Head: 47 ft Impeller: 3.05 in
--- Control Data --- 1. Hmax @ 53.3 Hz: • 36 @ 47, 0.77 hp 2. Control (QPC) @ 49.5 Hz: • 31.8 @ 40.7, 0.6 hp 3. Control (QPC) @ 45.7 Hz: • 27.3 @ 35.1, 0.47 hp 4. Control (QPC) @ 42.0 Hz: • 22.5 @ 29.8, 0.35 hp 5. Control (QPC) @ 38.1 Hz: • 16.8 @ 24.9, 0.25 hp 6. Index @ 34.4 Hz: • 9 @ 20.6, 0.17 hp 7. Hmin: 18.8 ft 32.7 Hz: • Setting= 40.00% Hmax
Series 4380Design Envelope: 1503-001.5
Integrated Intelligent Variable Speed with Sensorless Control
0 20 40 60 80 100 120 140 1600
20
40
60
80
100
Flow (usgpm)
Head
(ft)
4950 rpm
2578 rpm
2449 rpm
1800 rpm System
Avg.Load (QPC)
3997 rpm
1.5 hp
73
72
72
69
69
64
64
57
57
47
Index Flow (25.0% Duty Flow)
Water, spgr= 1.0000
PT679-2-0 (3.30.1.5)ANSI/HI 14.6.3.4.1
1
2
3
4
56
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 26 of 40
Options
Sensorless Bundle: Yes Parallel Sensorless: NoEnergy Performance Bundle: No Protection Bundle: No
Dual Season Setup: No Zone Optimization Bundle: No
Cooling Heating
Q1: N/A Q2: N/AH1: N/A H2: N/A
H1min: N/A H2min: N/A
Maximum Flow: N/A Minimum Flow: N/A
Optional Services
On-Site Pump Commissioning: Cost Not Included Extended Warranty: NoPump Manager: No Include Spare Parts Qty: 0
Design envelope pumping unit capability
Operating point Flow Head Efficiency
Full capability at 100% design flow 73.6 ft36 USgpm 48.75 %Design point 36 USgpm 47 ft 55.81 %
50% average flow (with default load profile) 18 usgpm 25.9 ft 43.47 %
Dimensional data (not for construction)
Top viewSide view
Weight: 53 lb• Not to scale• R = minimum lifting clearance required above motor• Units of measure : inches [millimeters]• Coupling guard and flush line (not shown) are supplied• Tolerance of ± 0.125 inch (± 3 mm) should be used• For certified dimensions, please contact your Armstrong representative• Pump equipped with casing drain plug and ¼ inch NPT suction and discharge gauge ports
Connection details
Connection Size Rating OD Bolt quantity* BCD Bolt size
Inlet 1.5 5ANSI-125 4 0.53.88
Outlet 1.5 5ANSI-125 4 0.53.88
*Equally spaced straddling centreline
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 27 of 40
Special instructions
The operating point %BEP results in reduced Sensorless control accuracy.
OSHPD Seismic Certification OSP-0422-10UL STD 778 & CSA STD C22.2 no.108 certified
Selected options Environmental Application: Indoors Sensorless Bundle: Sensorless control Constant flow control Constant pressure control Flow readout
Pump Manager and Extended Warranty Note:
Keep your system running as intended with Pump Manager, or combined with anExtended Warranty to provide price certainty in your maintenance and repairbudget. Both are available directly to the owner/end user of the pump. PumpManager proactively tracks performance and provides early diagnostic warnings,web accessible trends and analysis along with automated reports. Contact yourArmstrong contacts to take advantage of an Extended Warranty or Pump Manager.Additional equipment Flotrex: FTV-2GS (570200-208) Suction Guide: SG-215TF (516860-062)
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 28 of 40
Submittal Ref. #: 630442.2 rev1
Design Envelope Booster System
Series : 6800 G/E Design Envelope Model: N260322-20 hp
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Tag number: DWBP-1/2 Water Supply: City Mains or Tank
Suction (supply) pressure: 40.0 psiService: DW Booster
Location: Mech Room Total flow capacity: 370.0 USgpm
Quantity: 1 System boost pressure rating: 88.0 psiPower Supply: Discharge pressure: 295.7 ft208/3/60
System construction data
System description: Duplex Piping material: Stainless Steel 304Header size: 6 in Valve type Check valve only
Header connections: Grooved Maximum working pressure: 536.0 ft
Suction orientation: Right* Discharge orientation: Right*
*when facing booster controller Low lead certification: NSF 372
Pump data
Number of pumps: 2 Duty flow per pump: 185 USgpmOperation: 2 Duty Duty head: 88 psig
Series: 4700 Motor size: 20 hp
Size: VMS-45:03-2 Motor speed: 3600 rpmMotor efficiency: NEMA Premium (12.12)Construction: Stainless Steel 304
Standby Pump No Motor enclosure: ODP
Booster control panel data
Enclosure: NEMA 12 Painted steel Human Machine Interface: Touch Screen 4” StandardSelected features: BMS Port (serial communication port for connection to BMS - BacNet (MS/TP))
HMI: Touch Screen 4” Standard
IVS-102 variable frequency control data
Quantity: 2 (integrated with motors) EMI/RFI control: Integrated filter to meet EN61800-3Enclosure: UL Type 12 Cooling: Fan cooled through back channel
Harmonic suppression: Integrated DC link reactor Ambient temperature: -10C to +45C(upto 1000m elevation)
Drawdown tank data
Size and rating: 132 US Gallon Non-ASME Mounting: Remote Mounted
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 29 of 40
Performance curve
Dimensional data (not for construction)
WEIGHTS (lb) NOT for CONSTRUCTION
Weights
1703
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 30 of 40
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 31 of 40
Booster controller wiring diagram
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 32 of 40
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 33 of 40
Submittal Ref. #: 630442.2 rev1
Flo-trex valveModel: FTV-F (2.5 to 12 inch), FTV-G
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
DesignflowrateTag Qty Model Size Config Flange rating Pressure
Drop* Associated pump
GC-P-1/2 2 FTV-4FA 4 in Angle Flanged
ANSI-125 190.0 USgpm 2.8 ft GC-P-1/2 Design Envelope Sensorless 4380 2505-003.0
CH-P-1/2 2 FTV-4FA 4 in Angle Flanged
ANSI-125 185.0 USgpm 2.8 ft CH-P-1/2 Design Envelope Sensorless 4380 0205-005.0
B-P-1&2 2 FTV-2.5FA 2.5 in Angle Flanged
ANSI-125 72.0 USgpm 3.2 ft B-P-1&2 Design Envelope Sensorless 4380 1503-001.5
HW-P5/6 2 FTV-2GS 2 in Straight None 36.0 USgpm 3.0 ft HW-P5/6 Design Envelope Sensorless 4380 1503-001.5
*at design flow
Materials of construction
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
FTV-2.5FA-Flo-Trex Valve-ANSI-125-Angle Flanged FTV-Flanged-2.5-12
Body: Cast Iron ASTM A48 Class 30 Spring: Stainless Steel ASTM A313 Type 302
Disc: Bronze ASTM B584-C84400 BUNA (STEM) Elastomers & EPDMO rings:Seat: EPDM 2 metering ports: Brass Body with EPDM Check and
Gasketed Cap
Stem: Stainless Steel ASTM A582 Type 416 2 drain tappings: ¼" NPT with Brass Plug
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 34 of 40
FTV-2GS-Flo-Trex Valve-GRV-Straight FTV1.25-2
Body: SS 304 A351 Spring: SS ASTM A-313 TYPE 302-(18-8)
Disc: Brass C46500 EPDMO rings:2 metering ports: Brass Body with EPDM Check and
Gasketed CapStem: Brass C46500
2 drain tappings: ¼" NPT with SS 304 Plug
Operating limits (temperature - pressure)
FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged
Maximum pressure: 175 psi
Maximum temperature: 230 F
FTV-2GS-Flo-Trex Valve-GRV-Straight
Maximum pressure: 175 psi
Maximum temperature: 230 F
Dimensional data (not for construction)
Model: FTV-4FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 59 lb
Side view Front view
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 35 of 40
Model: FTV-2.5FA-Flo-Trex Valve-ANSI-125-Angle Flanged Weight: 33 lb
Side view Front view
Model: FTV-2GS-Flo-Trex Valve-GRV-Straight Weight: 6 lb
Side view Front view
Not to scale Units of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be used For certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 36 of 40
Submittal Ref. #: 630442.2 rev1
Suction guideModel: SG (2 to 12 inches), SG-TF
Project name: CC-17860 Hawthorne - 4988 Cambie St
Location: Vancouver Representative: Con-Cur West Marketing Inc.
Date submitted: 2/1/2018 10:10:37 PM Phone number: 604-312-9062
Engineer: Rocky Point Engineering e-mail: [email protected]
Contractor: PML Professional Mechanical Ltd Submitted by: Rocco Logozzo
Application design data
Design flowrateTag Qty Model System Pump Pressure
Drop* Associated pump
GC-P-1/2 2 SG-425 4 in 2.5 in 190.0 USgpm 1.3 ft GC-P-1/2 Design Envelope Sensorless 4380 2505-003.0
CH-P-1/2 2 SG-42 4 in 2 in 185.0 USgpm 1.3 ft CH-P-1/2 Design Envelope Sensorless 4380 0205-005.0
B-P-1&2 2 SG-2515 2.5 in 1.5 in 72.0 USgpm 1.1 ft B-P-1&2 Design Envelope Sensorless 4380 1503-001.5
HW-P5/6 2 SG-215TF 2 in 1.5 in 36.0 USgpm 0.1 ft HW-P5/6 Design Envelope Sensorless 4380 1503-001.5
*at design flow
Materials of construction
SG-425Body: Ductile Iron Cover gasket: Synthetic fiber
Guide vanes: Ductile Iron Strainer: Stainless steel .188(5mm) perforated
Cover plate: Ductile Iron Start-up strainer*: 10 mesh Galvanized steel
SG-42Body: Ductile Iron Cover gasket: Synthetic fiber
Guide vanes: Ductile Iron Strainer: Stainless steel .188(5mm) perforated
Cover plate: Ductile Iron Start-up strainer*: 10 mesh Galvanized steel
SG-2515Body: Ductile Iron Cover gasket: Synthetic fiber
Guide vanes: Ductile Iron Strainer: Stainless steel .188(5mm) perforated
Cover plate: Ductile Iron Start-up strainer*: 10 mesh Galvanized steel
SG-215TF
Body: Ductile Iron Cover gasket: Synthetic fiber
Guide vanes: Ductile Iron Strainer: Stainless Steel,0.125"(3mm)Perf.
Cover plate: Ductile Iron Start-up strainer*: Fine Mesh Galvanized Steel
*Remove start up strainer after 24 hours
Operating limits (temperature - pressure)
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 37 of 40
SG-425-Suction Guide-ANSI-125
Maximum pressure: 175 psi
Maximum temperature: 230 F
Units are hydrostatically tested to 150% of maximum working pressure
SG-215TF-Suction Guide-ANSI-125
Maximum pressure: 175 psi
Maximum temperature: 230 F
Units are hydrostatically tested to 150% of maximum working pressure
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 38 of 40
Dimensional data (not for construction)
SG-425 Weight: 61 lb
Side view Top view
SG-42 Weight: 58 lb
Side view Top view
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 39 of 40
SG-2515 Weight: 33 lb
Side view Top view
SG-215TF Weight: 24 lb
Side view Top view
Not to scaleUnits of measure: inches [millimeters]Tolerance of +/- 0.125 inch (+/- 3 mm) should be usedFor certified dimensions, please contact your Armstrong representative
www.armstrongfluidtechnology.com 2/1/2018, Ref. # 630442.2 rev1 Page 40 of 40