single-duct table of contents · 2006-05-22 · single-duct vav-prc008-en sd 1 table of contents...

30
Single-Duct SD 1 VAV-PRC008-EN Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General Data – Valve/Controller Airflow Guidelines SD 6 Performance Data – Air Pressure Requirements SD 7 – 9 Performance Data – Hot Water Coil SD 10 – 15 Performance Data – Electric Data SD 16 – 17 Performance Data – Acoustics SD 18 – 21 Dimensional Data SD 22 – 27 Mechanical Specifications SD 28 – 30

Upload: others

Post on 18-Jan-2020

1 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 1VAV-PRC008-EN

Table ofContents

Service Model Number Description SD 2 – 3

Selection Procedure SD 4 – 5

General Data – Valve/Controller Airflow Guidelines SD 6

Performance Data – Air Pressure Requirements SD 7 – 9

Performance Data – Hot Water Coil SD 10 – 15

Performance Data – Electric Data SD 16 – 17

Performance Data – Acoustics SD 18 – 21

Dimensional Data SD 22 – 27

Mechanical Specifications SD 28 – 30

Page 2: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 2

ServiceModel NumberDescription

Single-Duct VAVTerminal UnitsThe features of the single-duct VAVterminal units are described by theproduct categories shown in bold.Within each category the availableoptions are listed.

Digit 1, 2—Unit TypeVC VariTrane single-duct

Digit 3—ReheatC Cooling OnlyE Electric HeatW Hot Water Heat

Digit 4—Development SequenceF Sixth

Digit 5, 6—Primary Air Valve04 4" inlet (225 cfm)05 5" inlet (350 cfm)06 6" inlet (500 cfm)08 8" inlet (900 cfm)10 10" inlet (1400 cfm)12 12" inlet (2000 cfm)14 14" inlet (3000 cfm)16 16" inlet (4000 cfm)24 24" x 16" inlet (8000 cfm)

Digit 7, 8—Not Used00 N/A

Digit 9—Not Used0 N/A

Digit 10, 11—Design SequenceC0 Third (factory assigned)

Digit 12, 13, 14, 15—ControlsENON No controls, field-installed DDC/

electricPNON No controls, field-installed

pneumaticDD00 Trane elec actuator onlyDD01 DDC – Cooling onlyDD02 DDC – N.C. on/off water valve

controlDD03 DDC – Prop hot water valve

controlDD04 DDC – On/off electric heatDD05 DDC – Pulse-width modulation

electric heatDD07 DDC – N.O. on/off water valve

controlDD11 LonTalk DDC Controller—

Cooling onlyDD12 LonTalk DDC Controller w/ N.C.

on/off hot water controlDD13 LonTalk DDC Controller w/

proportional hot water controlDD14 LonTalk DDC Controller–on/off

electric heat control

DD15 LonTalk DDC Controller w/pulse-width modulation electricheat control

DD17 LonTalk DDC Controller w/ N.O.on/off hot water control

AT08 FM Automated Logic ZN341v+AT10 FM Automated Logic ZN141v+FM00 FM – Customer-supplied

actuator & controllerFM01 FM – Trane actuator w/

customer-supplied controlHNY2 FM Honeywell W7751HINV3 FM Invensys MNL-V2RPWR1 FM Siemens 540-100 w/

GDE131.1 actuatorPWR2 FM Siemens 540-103 w/

GDE131.1 actuatorPW12 FM Siemens 550-065PW13 FM Siemens 550-067VMA2 FM Johnson VMA-1420EI05 Analog – With optional on/off

reheatEI28 Analog – With optional on/off

reheat with dual-minimum cfmEI29 Analog – With optional on/off

reheat with constant-volume cfmPC00 PN – N.C. Trane pneumatic

actuatorPC04 PN – N.C. with optional on/off HW,

DA StatPC05 PN – N.C. with optional on/off

electric, RA StatPN00 PN – N.O. Trane pneumatic

actuator, RA StatPN04 PN – N.O. PVR, DA StatPN05 PN – N.O. PVR, RA StatPN11 PN – N.O. dual-minimum cfm,

DA StatPN32 PN – Water Valve, N.O. constant

volume, DA StatPN34 PN – Electric heat, N.O. constant

volume, DA Stat

Notes:N.C. = Normally-closedN.O. = Normally-openedDA Stat = Direct-acting pneumatic t-stat (by

others)RA Stat = Reverse-acting pneumatic

t-stat (by others)PN = PneumaticFM = Factory installation of customer-

supplied controllerPVR = Pneumatic Volume Regulator

VCCF

VCWF

VCEF

Page 3: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 3VAV-PRC008-EN

Digit 27, 28, 29—Electric Heat kW000 None050 0.5 kW010 1.0 kW015 1.5 kW

460 46.0 kW

Notes:0.5 to 8.0 kW – ½ kW increments8.0 to 18.0 kW – 1 kW increments18.0 to 46.0 kW – 2 kW increments

Digit 30—Electric Heat Stages0 None1 1 Stage2 2 Stages Equal3 3 Stages Equal

Digit 31—Contactors0 None1 24-volt magnetic2 24-volt mercury3 PE with magnetic4 PE with mercury

Digit 32—Not Used0 N/A

Digit 33—Not Used0 N/A

Digit 34—Actuator0 StandardA Spring Return (Normally Open)B Spring Return (Normally

Closed)

Digit 35—Sensor Options0 Standard (Wired)1 Factory Mounted Wireless

Receiver (Sensor Accessory)

ServiceModel NumberDescription

Digit 16—InsulationA 1/2" Matte-facedB 1" Matte-facedC 1/2" Foil-facedD 1" Foil-facedF 1" Double-wallG 3/8" Closed-cell

Digit 17—Not Used0 N/A

Digit 18—Not Used0 N/A

Digit 19—Outlet Plenum (Connectionis Slip & Drive)0 NoneA 1 Outlet RHB 1 Outlet ENDC 1 Outlet LHD 2 Outlets, 1 RH, 1 ENDE 2 Outlets, 1 LH, 1 ENDF 2 Outlets, 1 RH, 1 LHH 3 Outlets, 1 LH, 1 RH, 1 ENDJ 4 Outlets, 1 LH, 1 RH, 2 END

Note: See unit drawings for outlet sizes/damper information.

Digit 20—Not Used0 N/A

Digit 21—Water Coil0 None1 1-Row2 2-Row

Digit 22—Electrical Connections (VCCF,VCWF can be flipped in the field toachieve opposite-hand connection)L Left (Airflow hitting you in the

face)R Right (Airflow hitting you in the

face)0 Opposite side connection – coil

and control

Digit 23—Transformer0 None1 120/24 volt (50 VA)2 208/24 volt (50 VA)3 240/24 volt (50 VA)4 277/24 volt (50 VA)5 480/24 volt (50 VA)6 347/24 Volt (50 VA)7 575/24 Volt (50 VA)8 380/24 Volt (50 VA)

Note: For VCEF units with transformersthe VA depends on the staging, control,and contactor type (ranges are 40 VAto 75 VA)

Digit 24—Disconnect Switch0 NoneW With

Note: VCCF, VCWF – Toggle DisconnectVCEF – Door Interlocking PowerDisconnect

Digit 25—Power Fuse0 NoneW With

Digit 26—Electric Heat Voltage0 NoneA 208/60/1B 208/60/3C 240/60/1D 277/60/1E 480/60/1F 480/60/3G 347/60/1H 575/60/3J 380/50/3K 120/60/1

Page 4: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 4

SelectionProcedure

This section describes the catalogselection of single-duct VAV terminalunits with specific examples. Acomputer selection program is alsoavailable to aid in selection of VAVterminal units.

Selection of single-duct VAV terminalunits can involve three elements:

• Air valve selection• Heating coil selection (if required)• Acoustics

Air Valve Selection

The wide-open static pressure andairflows are found in the performancedata section of the catalog. To select anair valve, locate the required designcooling airflow for your terminal unittype and find the smallest air valve sizethat has a pressure drop equal to orlower than the maximum wide-openstatic pressure requirement.

Selection Example—Cooling Only VCCF Terminal Unit

Design cooling airflow: 1700 cfmMaximum wide openAir pressure drop: 0.25 in. wgMinimum cooling airflow: 850 cfm

From the performance data charts,select a valve size 12, which has a wide-open static pressure drop of 0.01 in. wg

Check the minimum and maximum cfmdesired with the minimum andmaximum cfm allowed in the table inthe general data section. The maximumsetting of 1700 cfm is within theacceptable range. The desired minimumsetting of 850 cfm is acceptable for thecooling only box desired. Note that if anelectric reheat box was selected, theminimum cfm would be dependentupon the kW of the electric heater. (SeeElectric Heat Unit Selection.)

Heating Coil Selection (Ifrequired)First, determine the amount of heatrequired to meet space anddownstream duct heat losses from aload calculation.

Hot Water HeatSelect a hot water coil sufficient to meetthe design heat loss.

Example:VCWF, Hot Water Unit Heat, Size 12(See air Valve Selection)Heating airflow: 850 cfmHot water flow: 1.0 gpmDesign Heat Loss: Q =25 MBh

Select hot water coil from the coilperformance table in the PerformanceData section of the catalog.

Selection:A one-row coil is sufficient to meetdesign conditions. From the Hot WaterCoil Capacity Data of the PerformanceData Section, a one-row coil for a size12 air valve will operate at the aboveconditions as follows:

Coil Capacity: 25.17 MBhWater pressure drop: 0.72 ft WPD

Air pressure drop (APD) of the hotwater coil is included in the chartpreceding the hot water coilperformance data section.

APD = 0.35 in. wg

Electric HeatDetermine the kW required to meetzone design heat loss.

kW = MBh / 3.414

MBh = Design Heat Loss

Select the nearest available kW withvoltage and steps desired from theelectric heater kW guideline table in thePerformance Data section of thecatalog.

Example:VCEF, Electric Unit Heat, Size 12(See Air Valve Selection)Heating airflow: 850 cfmVoltage: 277/60/1 VACDesign Heat Loss: Q = 25 MBh

kW = Q/3.414

kW = 25/3.414

kW = 7.3

Selection:Select 7.5 kW from the electric heattable in the voltage and stagesrequired. The table shows theminimum cfm allowable for the kWselected. The static pressurerequirement is shown as 0.06 in. wgfor this example with a design coolingflow of 1700 cfm.

Check Leaving Air Temperature:

T is the primary entering airtemperature 55°F for this example.

Decide if leaving air temperature of82.8°F is satisfactory for yourapplication.

AcousticsThe acoustical data found in the"Performance Data" section of the VAVcatalog is used to make adetermination of the amount of noisethe terminal unit will generate. Locatethe table for the VAV terminal unit ofinterest. Sound power data and anequivalent NC level for an ARI 885-98transfer function is listed.

Example:VCCF, Cooling-Only Terminal Unit, Size10 (See air Valve Selection)Cooling Airflow: 1100 cfm

Maximum inlet staticpressure: 1.5 in. wg

Interpolation gives sound powerdata of:

LAT = 3414 x 7.51.085 x 850

+ 55 = 82.8

LAT = Q1.085 x CFM

+ T

The maximum NC level is NC-37. If themaximum NC level was exceeded, itwould have been necessary to reselectthe next larger unit size.

Computer SelectionThe advent of personal computers hasserved to automate many processesthat were previously repetitive andtime-consuming. One of those tasks isthe proper scheduling, sizing, andselection of VAV terminal units. Tranehas developed a computer program toperform these tasks. The software iscalled the Trane Official ProductSelection System (TOPSS).

The TOPSS program will take the inputspecifications and output the properlysized VariTrane VAV terminal unit alongwith the specific performance for thatsize unit.

The program has several requiredfields, denoted by red shading in theTOPSS screen, and many otheroptional fields to meet the criteria youhave. Required values includemaximum and minimum airflows,control type, and model. If selectingmodels with reheat, you will berequired to enter information to make

The NC level above is determined byusing either the catalog’s ARI 885-98(mineral fiber for radiated sound)transfer function for the conditionsshown in the acoustics table. Adifferent transfer function could beapplied as conditions dictate.

Octave 2 3 4 5 6 7 NCBandDisch. 68 68 65 65 60 57 28SoundPowerRad. 63 58 54 47 39 32 29

SoundPower

Page 5: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 5VAV-PRC008-EN

SelectionProcedure

Rearrange what fields you seeand in what order with a fewclicks of a button.

Required entry fields (in Redon TOPSS screen).

that selection also. The user is giventhe option to look at all the informationfor one selection on one screen or as aschedule with the other VAV units onthe job.

The user can select single-duct, dual-duct, and fan-powered VAV boxes withthe program, as well as most otherTrane products, allowing you to selectall your Trane equipment with onesoftware program.

The program will also calculate soundpower data for the selected terminalunit. The user can enter a maximumindividual sound level for each octaveband or a maximum NC value. Theprogram will calculate acoustical datasubject to default or user suppliedsound attenuation data.

Schedule ViewThe program has many time-saving features such as:

• Copy/Paste from spreadsheets like Microsoft® Excel• Easily arranged fields to match your schedule• Time-saving templates to store default settings

The user can also export the Schedule View to Excel to modify and put into a CADdrawing as a schedule.

Specific details regarding the program, its operation, and how to obtain a copy of itare available from your local Trane sales office.

Page 6: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 6

General Data—Valve/ControllerAirflow Guidelines

Note: Maximum airflow must be greater than or equal to minimum airflow.

Primary Airflow Control Factory Settings – I-PControl Air Valve Maximum Valve Maximum Controller Minimum Controller Constant Volume

Type Size (in.) Cfm Cfm Cfm Cfm

4 225 25–225 0,25–225 25–2255 350 40–350 0,40–350 40–3506 500 60–500 0,60–500 60–500

Direct Digital Control/ 8 900 105–900 0,105–900 105–900UCM 10 1400 165–1400 0,165–1400 165–1400

12 2000 240–2000 0,240–2000 240–200014 3000 320–3000 0,320–3000 320–300016 4000 420–4000 0,420–4000 420–4000

24 x 16 8000 800–8000 0,800–8000 800–80004 225 38–225 0,38–225 38–2255 350 63–350 0,63–350 63–3506 500 73–500 0,73–500 73–500

Pneumatic with 8 900 134–900 0,134–900 134–900Volume Regulator 10 1400 215–1400 0,215–1400 215–1400

12 2000 300–2000 0,300–2000 300–200014 2887 408–2887 0,408–2887 408–288716 3789 536–3789 0,536–3789 536–3789

24 x 16 7745 1096–7745 0,1096–7745 1096–77454 225 52–225 0,52–225 52–2255 350 82–350 0,82–350 82–3506 500 120–500 0,120–500 120–500

Analog Electronic 8 900 210–900 0,210–900 210–90010 1400 328–1400 0,328–1400 328–140012 2000 470–2000 0,470–2000 470–200014 3000 640–3000 0,640–3000 640–300016 4000 840-4000 0,840–4000 840–4000

24 x 16 8000 1600-8000 0,1600–8000 1600–8000

Primary Airflow Control Factory Settings – SIControl Air Valve Maximum Valve Maximum Controller Minimum Controller Constant Volume

Type Size (in.) L/s L/s L/s L/s

4 106 12–106 0,12–106 12–1065 165 19–165 0,19–165 19–1656 236 28–236 0,28–236 28–236

Direct Digital Control/ 8 425 50–425 0,50–425 50–425UCM 10 661 77–661 0,77–661 77–661

12 944 111–944 0,111–944 111–94414 1416 151–1416 0,151–1416 151–141616 1888 198–1888 0,198–1888 198–1888

24 x 16 3776 378–3776 0,378–3776 378–37764 106 18–106 0,18–106 18–1065 165 30–165 0,30–165 30–1656 236 35–236 0,35–236 35–236

Pneumatic with 8 425 63–425 0,63–425 63–425Volume Regulator 10 661 102–661 0,102–661 102–661

12 944 141–944 0,141–944 141–94414 1363 193–1363 0,193–1363 193–136316 1788 253–1788 0,253–1788 253–1788

24 x 16 3656 517–3656 0,517–3656 517–36564 106 25–106 0,25–106 25–1065 165 39–165 0,39–165 39–1656 236 57–236 0,57–236 57–236

Analog Electronic 8 425 100–425 0,100–425 100–42510 661 155–661 0,155–661 155–66112 944 222–944 0,222–944 222–94414 1416 303–1416 0,303–1416 303–141616 1888 397–1888 0,397–1888 397–1888

24 x 16 3776 756–3776 0,756–3776 756–3776

Page 7: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 7VAV-PRC008-EN

PerformanceData—Air PressureRequirements

Note: Hot water pressure drops are for the entire unit, not just the coil. To calculate the hot water coil only pressure drop, subtract the cooling only pressure drop from theother pressure drop.

Air Pressure Drop – in. wg (I-P)Inlet Airflow Cooling Hot Water ElectricSize Cfm Only 1-row coil 2-row coil Heat

04 50 0.01 0.01 0.01 0.01100 0.01 0.02 0.02 0.01150 0.01 0.03 0.03 0.01225 0.01 0.06 0.06 0.02

05 100 0.01 0.01 0.03 0.01200 0.01 0.05 0.08 0.01300 0.01 0.09 0.17 0.02350 0.02 0.12 0.22 0.02

06 100 0.01 0.02 0.03 0.01250 0.05 0.11 0.17 0.05350 0.10 0.22 0.32 0.11500 0.22 0.45 0.63 0.23

08 200 0.01 0.03 0.05 0.01400 0.02 0.10 0.17 0.02600 0.04 0.20 0.34 0.05900 0.08 0.40 0.69 0.11

10 500 0.01 0.07 0.12 0.01800 0.01 0.15 0.26 0.021100 0.01 0.27 0.44 0.031400 0.01 0.42 0.66 0.05

12 800 0.01 0.10 0.19 0.011200 0.01 0.19 0.35 0.031600 0.01 0.31 0.55 0.052000 0.01 0.45 0.79 0.08

14 1500 0.01 0.10 0.23 0.012000 0.01 0.16 0.36 0.012500 0.01 0.22 0.51 0.013000 0.01 0.30 0.69 0.01

16 2000 0.01 0.11 0.30 0.012500 0.01 0.16 0.46 0.023000 0.01 0.22 0.65 0.024000 0.01 0.35 1.14 0.03

24 x 16 4000 0.01 0.40 0.66 0.155500 0.01 0.70 1.12 0.306500 0.01 0.95 1.47 0.448000 0.01 1.37 2.06 0.69

Air Pressure Drop – Pa (SI)Inlet Airflow Cooling Hot Water ElectricSize L/s Only 1-row coil 2-row coil Heat

04 25 3 3 3 350 3 4 4 370 3 7 7 3105 3 15 15 3

05 45 3 3 6 395 3 12 21 3140 3 22 41 5165 4 29 54 6

06 45 3 4 7 3120 13 29 43 14165 26 55 79 27235 55 112 155 57

08 95 3 8 13 3190 4 25 43 6280 9 49 83 12420 21 99 169 28

10 235 3 16 29 3375 3 37 63 5520 3 67 110 9660 3 104 165 13

12 375 3 24 47 3565 3 47 88 7755 3 76 138 13940 3 111 195 19

14 700 3 26 55 3945 3 40 89 31180 3 56 127 31415 3 74 171 3

16 940 3 28 73 31180 3 40 114 41415 3 54 162 51885 3 87 284 8

24 x 16 1885 3 100 165 382600 3 176 279 763070 3 236 366 1103775 3 341 513 172

Page 8: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 8

PerformanceData—Air PressureRequirements (I-P)

(TOP VIEW)ARRANGEMENTS A B C D

OUTLET PLENUMHFE J

A,B,C IIII, II III, IV IVI, II I, II

OUTLHJ

D,E,F

N/A

I, II

I, II

N/A

I, II

I, II

N/A

I, II

I, II

I, II, III

N/AI, II, III

II, III, IV

I

II, III, IVIII, IV

I, II

III, IV

OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINALØ

VALV 4

OUTL CONVERSION CHART

NOMINALØ

5" (127 mm)6" (152 mm)

8" (203 mm)10" (254 mm)IV

5 6SYMBOL

II

III

I8 10 12

Integral Outlet Plenum Air Pressure Drop – in. wg (I-P)

OutletInlet Outlet Diameter Airflow (Cfm)Size Configuration (in.) 50 100 150 200 250 350 400 500 600 800 900 1100 1200 1400 1600 2000

4,5,6 A,C 5 0.02 0.07 0.15 0.26 0.41 0.80 1.04 1.634,5,6 6 0.01 0.03 0.07 0.13 0.20 0.37 0.48 0.748,10 AC 8 0.04 0.06 0.11 0.14 0.23 0.33 0.58 0.74 1.11 1.33 1.8110 10 0.01 0.02 0.04 0.05 0.08 0.12 0.21 0.27 0.41 0.48 0.6612 10 0.03 0.06 0.08 0.12 0.17 0.29 0.37 0.54 0.64 0.86 1.11 1.71

4,5,6 B 5 0.01 0.03 0.08 0.15 0.23 0.48 0.64 1.024,5,6 6 0.01 0.01 0.01 0.03 0.04 0.07 0.10 0.15

8 8 0.01 0.01 0.02 0.02 0.03 0.05 0.07 0.0910 B 8 0.02 0.04 0.07 0.09 0.14 0.20 0.35 0.44 0.65 0.76 1.0310 10 0.01 0.01 0.01 0.01 0.02 0.02 0.04 0.06 0.08 0.10 0.1312 10 0.02 0.04 0.05 0.08 0.11 0.19 0.24 0.36 0.43 0.58 0.76 1.17

4,5,6 D,E 5 0.01 0.01 0.02 0.04 0.05 0.09 0.12 0.174,5,6 6 0.01 0.01 0.01 0.01 0.01 0.01 0.02 0.03

8 D, E 5 0.06 0.09 0.18 0.23 0.35 0.49 0.85 1.068 6 0.02 0.03 0.05 0.07 0.11 0.15 0.26 0.328 8 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.0110 D, E 6 0.02 0.04 0.07 0.10 0.15 0.22 0.38 0.48 0.72 0.85 1.1610 8 0.01 0.01 0.01 0.02 0.02 0.04 0.06 0.08 0.12 0.14 0.1910 10 0.01 0.01 0.01 0.01 0.01 0.01 0.02 0.02 0.03 0.04 0.0512 D, E 8 0.01 0.02 0.03 0.05 0.07 0.12 0.15 0.23 0.28 0.38 0.49 0.7712 10 0.01 0.01 0.02 0.02 0.04 0.05 0.07 0.08 0.11 0.14 0.21

4,5,6 F 6 0.01 0.01 0.03 0.05 0.08 0.16 0.21 0.324,5,6,8 5 0.01 0.03 0.06 0.10 0.16 0.30 0.38 0.58 0.83 1.43 1.788,10 F 6 0.05 0.08 0.14 0.18 0.27 0.37 0.61 0.76 1.08 1.26 1.668,10 8 0.01 0.02 0.04 0.06 0.09 0.13 0.23 0.29 0.43 0.52 0.7110 F 10 0.01 0.01 0.02 0.02 0.03 0.04 0.07 0.08 0.12 0.14 0.1812 8 0.02 0.04 0.05 0.07 0.10 0.17 0.21 0.31 0.37 0.50 0.64 0.9812 10 0.01 0.02 0.02 0.03 0.04 0.06 0.08 0.11 0.13 0.16 0.21 0.30

4,5,6 H 5 0.01 0.01 0.01 0.01 0.01 0.03 0.04 0.064 6 0.01 0.01 0.01 0.015 6 0.01 0.01 0.01 0.01 0.01 0.016 6 0.01 0.01 0.01 0.01 0.01 0.01 0.018 H 5 0.03 0.05 0.09 0.11 0.18 0.25 0.43 0.548 6 0.01 0.01 0.02 0.03 0.04 0.06 0.10 0.138 8 0.01 0.01 0.01 0.01 0.01 0.01 0.02 0.0310 H 6 0.01 0.02 0.04 0.05 0.08 0.11 0.18 0.22 0.32 0.38 0.5010 8 0.01 0.01 0.01 0.01 0.01 0.02 0.03 0.03 0.05 0.05 0.0710 10 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.01 0.0112 H 8 0.01 0.01 0.02 0.03 0.04 0.06 0.08 0.11 0.13 0.17 0.21 0.3212 10 0.01 0.01 0.01 0.01 0.01 0.02 0.02 0.03 0.03 0.05 0.06 0.0910 J 5 0.02 0.02 0.05 0.06 0.09 0.13 0.23 0.29 0.43 0.51 0.7012 5 0.03 0.06 0.08 0.12 0.17 0.30 0.38 0.57 0.68 0.92 1.20 1.8712 6 0.01 0.02 0.03 0.04 0.06 0.11 0.14 0.21 0.25 0.35 0.45 0.71

Page 9: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 9VAV-PRC008-EN

PerformanceData—Air PressureRequirements (SI)

(TOP VIEW)ARRANGEMENTS A B C D

OUTLET PLENUMHFE J

A,B,C IIII, II III, IV IVI, II I, II

OUTLHJ

D,E,F

N/A

I, II

I, II

N/A

I, II

I, II

N/A

I, II

I, II

I, II, III

N/AI, II, III

II, III, IV

I

II, III, IVIII, IV

I, II

III, IV

OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINALØ

VALV 4

OUTL CONVERSION CHART

NOMINALØ

5" (127 mm)6" (152 mm)

8" (203 mm)10" (254 mm)IV

5 6SYMBOL

II

III

I8 10 12

Integral Outlet Plenum Air Pressure Drop – Pa (SI)

OutletInlet Outlet Diameter Airflow (L/s)Size Configuration (mm) 25 50 70 95 120 165 190 235 280 375 420 520 565 660 755 940

4,5,6 A,C 127 4 17 37 66 102 199 260 4054,5,6 152 3 8 18 32 49 93 120 1858,10 AC 203 9 14 27 36 56 81 145 185 277 330 45110 254 3 5 10 13 21 30 53 67 101 120 16412 254 8 15 19 29 42 73 91 134 159 214 277 427

4,5,6 B 127 3 8 20 36 58 119 158 2544,5,6 152 3 3 4 6 10 19 24 37

8 203 3 3 5 6 8 11 19 2310 B 203 6 9 17 22 35 49 86 109 161 190 25710 254 3 3 3 3 4 6 11 14 20 24 3312 254 5 10 12 19 28 48 61 90 107 145 188 292

4,5,6 D,E 127 3 3 6 9 13 23 29 424,5,6 152 3 3 3 3 3 3 4 6

8 D, E 127 15 23 44 57 87 123 211 2648 152 5 7 13 17 26 37 64 818 203 3 3 3 3 3 3 3 310 D, E 152 6 9 18 24 37 54 95 120 179 213 28910 203 3 3 3 4 6 9 16 20 30 35 4810 254 3 3 3 3 3 3 4 5 8 9 1212 D, E 203 3 6 7 12 17 30 38 57 69 94 123 19312 254 3 3 3 4 6 10 12 17 20 27 34 52

4,5,6 F 152 3 4 8 14 21 40 52 814,5,6,8 127 3 7 15 25 39 74 95 145 206 355 4448,10 F 152 13 19 35 45 66 92 153 189 269 315 4148,10 203 3 5 10 14 22 31 56 72 108 129 17710 F 254 3 3 4 5 7 10 17 21 29 34 4512 203 5 9 11 18 25 43 53 78 92 124 159 24412 254 3 4 5 7 9 16 19 27 31 41 51 75

4,5,6 H 127 3 3 3 3 3 7 9 154 152 3 3 3 35 152 3 3 3 3 3 36 152 3 3 3 3 3 3 38 H 127 8 12 22 29 44 62 108 1368 152 3 3 6 7 11 15 26 338 203 3 3 3 3 3 3 5 610 H 152 4 5 10 13 19 27 45 56 81 95 12610 203 3 3 3 3 3 4 6 8 12 14 1810 254 3 3 3 3 3 3 3 3 3 3 312 H 203 3 3 4 6 9 15 19 27 32 42 53 8012 254 3 3 3 3 3 4 5 7 9 11 15 2210 J 127 4 6 11 15 23 33 58 73 108 128 17312 127 7 14 19 29 42 75 95 142 168 229 299 46712 152 3 5 7 11 15 28 35 53 63 86 113 178

Page 10: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 10

PerformanceData—Hot WaterCoil (I-P)

LAT = EAT + MBH x 921.7 Cfm( ) WTD = EWT - LWT = 2 x MBH

Gpm( )

Notes:1. Fouling Factor = 0.000252. Capacity based on 55°F entering air temperature and 180°F entering water temperature. Refer to correction factors for different

entering conditions on page 42.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).

Inlet Size 04, 05, 06 (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 45 60 90 100 150 200 250 300 400 500

1-Row 0.5 0.55 4.16 4.82 5.83 6.10 7.26 8.17 8.94 9.62 10.73 11.60Capacity 1.0 1.84 4.42 5.20 6.41 6.75 8.22 9.42 10.47 11.40 13.00 14.36

MBH 1.5 3.74 4.52 5.34 6.63 7.00 8.60 9.93 11.11 12.17 14.02 15.622.0 6.22 4.57 5.41 6.75 7.13 8.80 10.21 11.46 12.59 14.60 16.342.5 9.24 4.61 5.46 6.82 7.22 8.93 10.39 11.68 12.86 14.97 16.81

2-Row 0.5 1.14 5.07 6.36 8.47 9.06 11.41 13.07 14.30 — — —Capacity 1.0 3.84 5.25 6.68 9.16 9.89 12.97 15.34 17.23 18.77 21.15 22.90

MBH 1.5 7.80 5.31 6.79 9.40 10.18 13.53 16.20 18.39 20.21 23.10 25.302.0 12.95 5.34 6.84 9.52 10.32 13.83 16.66 19.01 20.99 24.18 26.652.5 19.16 5.36 6.88 9.59 10.41 14.01 16.94 19.39 21.48 24.87 27.51

Applicable Range Size 04Size 05Size 06

Inlet Size 08 (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 165 200 300 400 500 600 700 800 900

1-Row 0.5 0.86 8.81 9.51 11.15 12.41 13.41 14.24 14.95 — —Capacity 1.0 2.90 10.04 10.97 13.19 14.99 16.54 17.92 19.13 20.21 21.18

MBH 1.5 5.96 10.52 11.56 14.06 16.14 17.95 19.56 21.01 22.35 23.582.0 9.97 10.78 11.88 14.54 16.79 18.76 20.53 22.14 23.61 24.972.5 14.89 10.95 12.08 14.85 17.20 19.29 21.17 22.88 24.46 25.93

2-Row 2.0 0.35 15.01 16.97 21.32 24.48 26.88 28.78 30.32 31.61 32.70Capacity 4.0 1.22 16.00 18.30 23.68 27.79 31.06 33.75 36.00 37.92 39.58

MBH 6.0 2.57 16.36 18.79 24.57 29.09 32.75 35.79 38.37 40.60 42.558.0 4.38 16.55 19.05 25.05 29.79 33.67 36.92 39.69 42.10 44.2110.0 6.63 16.66 19.21 25.35 30.23 34.25 37.63 40.54 43.06 45.2912.5 10.05 16.76 19.34 25.59 30.60 34.74 38.24 41.25 43.87 46.20

Inlet Size 10 (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 350 450 550 650 750 850 1000 1100 1300 1400

1-Row 0.7 2.07 15.52 17.18 18.54 19.71 20.72 — — — — —Capacity 1.0 3.87 16.89 18.79 20.51 22.01 23.34 24.54 26.12 27.07 28.74 29.48

MBH 1.5 7.93 18.16 20.40 22.37 24.13 25.76 27.28 29.33 30.58 32.81 33.832.0 13.20 18.87 21.30 23.47 25.42 27.22 28.87 31.18 32.62 35.23 36.422.5 19.67 19.31 21.88 24.18 26.26 28.19 29.98 32.45 33.97 36.82 38.14

2-Row 2.0 0.72 27.75 31.74 34.93 37.54 39.72 41.58 43.91 45.22 47.42 48.35Capacity 4.0 2.62 30.43 35.52 39.76 43.37 46.48 49.21 52.71 54.74 58.23 59.74

MBH 6.0 5.61 31.41 36.93 41.62 45.66 49.19 52.30 56.36 58.73 62.86 64.678.0 9.65 31.92 37.68 42.61 46.89 50.65 53.99 58.37 60.94 65.44 67.4310.0 14.71 32.24 38.15 43.23 47.66 51.57 55.05 59.64 62.35 67.10 69.20

Page 11: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 11VAV-PRC008-EN

Notes:1. Fouling Factor = 0.0005 °F ft² h/Btu.2. Capacity based on 55°F entering air temperature and 180°F entering water temperature. Refer to correction factors found on page 42

for different entering conditions.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).

PerformanceData—Hot WaterCoil (I-P)

LAT = EAT + MBH x 921.7 Cfm( ) WTD = EWT - LWT = 2 x MBH

Gpm( )

Inlet Size 12 (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 400 600 800 1000 1200 1400 1600 1800 2000

1-Row 1.0 0.68 18.07 21.12 23.48 25.37 26.96 28.30 29.47 30.49 31.39Capacity 2.0 2.37 20.76 24.83 28.16 31.04 33.61 35.88 37.91 39.74 41.41

MBH 3.0 4.95 21.84 26.41 30.24 33.58 36.55 39.24 41.74 44.03 46.134.0 8.38 22.42 27.28 31.40 35.02 38.28 41.26 43.99 46.51 48.885.0 12.62 22.78 27.83 32.14 35.95 39.41 42.57 45.49 48.21 50.74

2-Row 2.0 0.25 — — — — — — — — —Capacity 5.0 1.38 35.55 45.61 53.18 59.13 63.96 67.96 71.36 74.28 76.82

MBH 8.0 3.35 36.91 47.07 56.74 63.72 69.50 74.37 78.57 82.22 85.4411.0 6.14 37.56 49.28 58.51 66.04 72.33 77.69 82.33 86.40 90.0114.0 9.72 37.95 50.00 59.58 67.45 74.06 79.73 84.66 88.99 92.8517.5 14.90 38.24 50.54 60.39 68.53 75.39 81.30 86.46 91.01 95.06

Notes:1. Fouling Factor = 0.0005 °F ft² h/Btu.2. Capacity based on 55°F entering air temperature and 180°F entering water temperature.

Inlet Size 14 (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 700 900 1100 1300 1500 1700 2000 2300 2600 3000

1-Row 2.0 1.23 31.76 35.18 38.24 40.91 43.27 45.38 48.18 50.62 52.77 55.28Capacity 3.0 2.56 34.35 38.43 42.00 45.19 48.14 50.86 54.53 57.80 60.73 64.21

MBH 4.0 4.32 35.80 40.28 44.24 47.82 51.09 54.10 58.28 62.10 65.56 69.725.0 6.50 36.73 41.47 45.70 49.54 53.07 56.34 60.85 64.96 68.79 73.446.0 9.08 37.38 42.31 46.73 50.76 54.48 57.94 62.74 67.12 71.15 76.137.0 12.05 37.86 42.93 47.49 51.67 55.53 59.14 64.15 68.75 73.01 78.21

2-Row 5.0 1.09 55.66 63.95 70.65 76.21 80.91 84.94 90.02 94.23 97.79 101.78Capacity 9.0 3.32 59.72 69.65 77.96 85.04 91.16 96.51 103.42 109.29 114.33 120.09

MBH 13.0 6.71 61.41 72.08 91.13 88.93 95.74 101.76 109.59 116.30 122.14 128.8617.0 11.24 62.34 73.44 82.92 91.13 98.35 104.76 113.16 120.39 126.71 134.0321.0 16.89 62.94 74.31 84.06 92.56 100.05 106.72 115.49 123.08 129.73 137.4522.5 19.29 63.11 74.56 84.40 92.98 100.54 107.29 116.17 123.87 130.62 138.46

Notes:1. Fouling Factor = 0.0005 °F ft² h/Btu.2. Capacity based on 55°F entering air temperature and 180°F entering water temperature.

Inlet Size 16 (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 900 1200 1500 1800 2000 2400 2800 3200 3600 4000

1-Row 2.0 1.37 38.24 43.01 46.92 50.22 52.17 55.58 58.48 60.99 63.19 65.12Capacity 3.0 2.84 41.85 47.41 52.24 56.54 59.12 63.73 67.76 71.32 74.49 77.34

MBH 4.0 4.77 43.89 50.10 55.46 60.22 63.20 68.61 73.40 77.69 81.56 85.075.0 7.16 45.21 51.85 57.64 62.82 66.00 71.85 77.19 82.01 86.39 90.406.0 9.98 46.14 53.08 59.19 64.67 68.06 74.28 79.91 85.13 89.90 94.297.5 15.02 47.10 54.38 60.81 66.64 70.24 76.91 82.97 88.52 93.67 98.49

2-Row 5.0 1.15 68.70 79.75 88.29 95.11 98.96 105.40 110.59 114.89 118.51 121.61Capacity 9.0 3.50 74.51 88.21 99.24 108.35 113.62 122.64 130.12 136.45 141.90 146.64

MBH 13.0 7.05 76.95 91.85 104.07 114.31 120.28 130.63 139.34 146.78 153.23 158.9017.0 11.78 78.30 93.89 106.80 117.70 124.11 135.27 144.71 152.85 159.94 166.2021.0 17.67 79.16 95.20 108.56 119.91 126.60 138.31 148.26 156.86 164.39 171.0622.5 20.18 79.40 95.58 109.07 120.55 127.32 139.19 149.30 158.04 165.70 172.49

Page 12: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 12

LAT = EAT + MBH x 921.7 Cfm( ) WTD = EWT - LWT = 2 x MBH

Gpm(

PerformanceData—Hot WaterCoil (I-P)

)Temperature Correction Factors for Water Pressure Drop (ft)

Average Water Temperature 200 190 180 170 160 150 140 130 120 110Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150

Temperature Correction Factors for Coil Capacity (MBH)

Entering Water Minus Entering Air 40 50 60 70 80 100 125 140 150 160 180 200Correction Factor 0.32 0.40 0.48 0.56 0.64 0.80 1.00 1.12 1.20 1.28 1.44 1.60

Coil Only–Water Weights

Internal Internal OperatingInlet Coil Volume Volume WeightSize Type (in.3) (Gal.) (lbs)04 1-Row 9.37 0.041 5.305 1-Row 9.37 0.041 5.306 1-Row 9.37 0.041 5.308 1-Row 12.78 0.055 5.510 1-Row 19.06 0.083 7.712 1-Row 30.05 0.130 10.714 1-Row 51.21 0.222 13.916 1-Row 58.62 0.254 16.2

24 x 16 1-Row 66.03 0.286 20.404 2-Row 23.68 0.102 6.905 2-Row 23.68 0.102 6.906 2-Row 23.68 0.102 6.908 2-Row 35.47 0.154 9.010 2-Row 48.83 0.211 11.712 2-Row 67.34 0.292 15.514 2-Row 94.27 0.408 19.816 2-Row 109.09 0.472 23.3

24 x 16 2-Row 123.91 0.536 29.8

Notes:1. Fouling Factor = 0.0005 °F ft² h/Btu.2. Capacity based on 55°F entering air temperature and 180°F entering water temperature. Refer to correction factors found on page 42

for different entering conditions.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).

Inlet Size 16 x 24 (I-P)Water

Pressure Airflow (Cfm)Rows Gpm Drop (ft) 1000 1700 2400 3100 3800 4500 5200 5900 6600 7300 8000

1-Row 2.0 1.51 42.77 52.52 59.23 64.28 68.27 71.50 74.18 76.44 78.38 80.05Capacity 3.0 3.11 47.00 58.99 68.05 75.19 81.02 85.90 90.04 93.62 96.75 99.50

MBH 4.0 5.21 49.47 62.79 73.31 81.88 89.04 95.14 100.43 105.05 109.14 112.795.0 7.81 51.07 65.46 76.79 86.39 94.52 101.55 107.71 113.15 118.01 122.376.0 10.88 52.20 67.37 79.41 89.63 98.51 106.25 113.09 119.18 124.65 129.607.5 16.35 53.37 69.38 82.26 93.19 102.80 111.34 118.95 125.79 131.98 137.62

2-Row 5.0 1.26 77.04 99.78 113.85 123.52 130.63 136.11 140.49 144.09 147.10 149.66Capacity 9.0 3.71 83.86 113.03 132.54 146.70 157.53 166.15 173.21 179.13 184.17 188.53

MBH 13.0 7.34 86.70 118.88 141.13 157.68 170.59 181.01 189.66 196.97 203.26 208.7417.0 12.13 88.27 122.18 146.09 164.10 178.31 189.88 199.55 207.78 214.89 221.1321.0 18.02 89.27 124.32 149.31 168.32 183.42 195.79 206.17 215.05 222.75 229.5122.5 20.52 59.56 124.93 150.25 169.56 184.92 197.53 208.13 217.20 225.07 232.00

Page 13: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 13VAV-PRC008-EN

PerformanceData—Hot WaterCoil (SI)

Notes:1. Fouling Factor = 0.0005.2. Capacity based on 12°C entering air temperature and 82°C entering water temperature. Refer to correction factors for different

entering conditions on page 45.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).

LAT = EAT + kW x 0.83 L/s ) WTD = EWT - LWT = kW

(4.19) L/s)((

Inlet Size 08 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 78 94 142 189 236 283 330 378 425

1-Row 0.03 2.12 2.47 2.66 3.12 3.47 3.75 3.99 4.18 4.35 4.50Capacity 0.06 7.05 2.81 3.06 3.68 4.18 4.61 4.99 5.33 5.63 5.90

kW 0.09 14.35 2.94 3.22 3.92 4.49 4.99 5.44 5.84 6.22 6.560.13 23.82 3.01 3.31 4.05 4.67 5.22 5.71 6.15 6.56 6.930.16 35.35 3.06 3.37 4.13 4.78 5.36 5.88 6.35 6.79 7.20

2-Row 0.13 0.98 — — — — — — — — —Capacity 0.25 3.48 4.54 5.18 6.67 7.79 8.69 9.42 10.03 10.55 11.01

kW 0.38 7.37 4.65 5.33 6.92 8.16 9.16 9.99 10.70 11.30 11.830.50 12.56 4.70 5.40 7.06 8.36 9.42 10.31 11.07 11.72 12.290.63 19.04 4.74 5.45 7.15 8.49 9.59 10.51 11.30 11.99 12.590.79 28.90 4.77 5.49 7.22 8.60 9.73 10.68 11.50 12.22 12.84

Inlet Size 10 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 165 212 260 307 354 401 472 519 613 661

1-Row 0.04 5.29 4.36 4.83 5.21 5.54 5.83 6.08 6.41 6.61 6.94 7.09Capacity 0.06 9.81 4.74 5.27 5.75 6.17 6.54 6.88 7.33 7.60 8.07 8.28

kW 0.09 19.90 5.09 5.71 6.26 6.75 7.21 7.63 8.21 8.55 9.18 9.470.13 33.00 5.28 5.96 6.56 7.10 7.60 8.07 8.71 9.11 9.84 10.170.16 48.93 5.40 6.11 6.75 7.33 7.87 8.37 9.06 9.48 10.28 10.64

2-Row 0.13 2.07 7.87 8.98 9.87 10.59 11.20 11.72 12.36 12.73 13.34 13.60Capacity 0.25 7.53 8.64 10.06 11.23 12.23 13.10 13.85 14.81 15.37 16.34 16.75

kW 0.38 16.15 8.93 10.46 11.76 12.88 13.86 14.72 15.83 16.49 17.62 18.120.50 27.83 9.07 10.68 12.05 13.23 14.27 15.19 16.40 17.10 18.34 18.880.63 42.50 9.17 10.81 12.22 13.45 14.53 15.49 16.75 17.50 18.80 19.38

Notes:1. Fouling Factor = 0.0005.2. Capacity based on 12°C entering air temperature and 82°C entering water temperature.

Inlet Size 04, 05, 06 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 21 28 42 47 71 94 118 142 189 236

1-Row 0.03 1.57 1.20 1.38 1.66 1.73 2.05 2.30 2.52 2.70 3.01 3.26Capacity 0.06 5.26 1.27 1.49 1.82 1.91 2.31 2.64 2.93 3.19 3.63 4.01

kW 0.010 10.72 1.30 1.53 1.88 1.98 2.42 2.78 3.10 3.39 3.91 4.350.13 17.82 1.32 1.55 1.91 2.02 2.47 2.86 3.20 3.51 4.06 4.540.16 26.47 1.32 1.56 1.93 2.04 2.51 2.91 3.26 3.58 4.16 4.67

2-Row 0.06 1.85 1.48 1.88 2.54 2.73 3.53 4.14 4.61 4.99 5.58 6.00Capacity 0.13 6.39 1.52 1.94 2.68 2.90 3.84 4.60 5.22 5.73 6.56 7.19

kW 0.19 13.28 1.53 1.96 2.72 2.95 3.96 4.77 5.45 6.02 6.96 7.690.25 22.39 1.54 1.97 2.75 2.98 4.01 4.86 5.57 6.18 7.18 7.960.32 33.61 1.54 1.98 2.76 3.00 4.05 4.92 5.65 6.28 7.32 8.14

Notes:1. Fouling Factor = 0.0005.2. Capacity based on 12°C entering air temperature and 82°C entering water temperature.

Page 14: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 14

PerformanceData—Hot WaterCoil (SI)

Notes:1. Fouling Factor = 0.0005.2. Capacity based on 12°C entering air temperature and 82°C entering water temperature. Refer to correction factors for different

entering conditions on page 45.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).

LAT = EAT + kW x 0.83 L/s( ) WTD = EWT - LWT = kW

(4.19) L/s)(

Inlet Size 12 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 189 283 378 472 566 661 755 849 944

1-Row 0.06 2.04 5.30 6.19 6.88 7.44 7.90 8.29 8.64 8.93 9.20Capacity 0.13 7.08 6.08 7.28 8.25 9.10 9.85 10.51 11.11 11.65 12.14

kW 0.19 14.79 6.40 7.74 8.86 9.84 10.71 11.50 12.23 12.90 13.520.25 25.04 6.57 8.00 9.20 10.26 11.22 12.09 12.89 13.63 14.330.32 37.73 6.68 8.16 9.42 10.54 11.55 12.48 13.33 14.13 14.87

2-Row 0.13 0.74 — — — — — — — — —Capacity 0.32 4.12 10.42 13.37 15.59 17.33 18.74 19.92 20.91 21.77 22.51

kW 0.50 10.01 10.82 14.09 16.63 18.68 20.37 21.80 23.03 24.10 25.040.69 18.35 11.01 14.44 17.15 19.35 21.20 22.77 24.13 25.32 26.380.88 29.06 11.12 14.65 17.46 19.77 21.71 23.37 24.81 26.08 27.211.10 44.53 11.21 14.81 17.70 20.08 22.10 23.83 25.34 26.67 27.86

Inlet Size 14 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 330 425 519 613 708 802 944 1085 1227 1416

1-Row 0.13 3.69 9.31 10.31 11.21 11.99 12.68 13.30 14.12 14.84 15.47 16.20Capacity 0.19 7.67 10.07 11.26 12.31 13.24 14.11 14.91 15.98 16.94 17.80 18.82

kW 0.25 12.93 10.49 11.80 12.97 14.01 14.97 15.86 17.08 18.20 19.21 20.430.32 19.43 10.76 12.15 13.39 14.52 15.55 16.51 17.83 19.04 20.16 21.520.38 27.13 10.95 12.40 13.69 14.88 15.97 16.98 18.39 19.67 20.85 22.310.44 36.01 11.09 12.58 13.92 15.14 16.28 17.33 18.80 20.15 21.40 22.92

2-Row 0.32 3.24 16.31 18.74 20.71 22.34 23.71 24.89 26.38 27.62 28.66 29.83Capacity 0.57 9.93 17.50 20.41 22.85 24.92 26.72 28.28 30.31 32.03 33.51 35.20

kW 0.82 20.07 18.00 21.13 23.78 26.06 28.06 29.82 32.12 34.08 35.80 37.761.07 33.61 18.27 21.52 24.30 26.71 28.82 30.70 33.16 35.28 37.14 39.281.32 50.49 18.45 21.78 24.64 27.13 29.32 31.28 33.85 36.07 38.02 40.281.42 57.67 18.50 21.85 24.73 27.25 29.47 31.44 34.05 36.30 38.28 40.58

Inlet Size 16 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 425 566 708 849 944 1133 1321 1510 1699 1888

1-Row 0.13 4.10 11.21 12.61 13.75 14.72 15.29 16.29 17.14 17.87 18.52 19.09Capacity 0.19 8.48 12.26 13.90 15.31 16.57 17.33 18.68 19.86 20.90 21.83 22.67

kW 0.25 14.26 12.86 14.68 16.25 17.65 18.52 20.11 21.51 22.77 23.90 24.930.32 21.39 13.25 15.20 16.89 18.41 19.34 21.06 22.62 24.03 25.32 26.490.38 29.83 13.52 15.56 17.35 18.95 19.95 21.77 23.42 24.95 26.35 27.630.47 44.89 13.80 15.94 17.82 19.53 20.59 22.54 24.32 25.94 27.45 28.87

2-Row 0.32 3.44 20.13 23.37 25.88 27.88 29.00 30.89 32.41 33.67 34.73 35.64Capacity 0.57 10.45 21.84 25.85 29.08 31.76 33.30 35.94 38.14 39.99 41.59 42.98

kW 0.82 21.07 22.55 26.92 30.50 33.50 35.25 38.28 40.84 43.02 44.91 46.571.07 35.21 22.95 27.52 31.30 34.50 36.37 39.64 42.41 44.79 46.87 48.711.32 52.82 23.20 27.90 31.82 35.14 37.10 40.53 43.45 45.97 48.18 50.131.42 60.31 23.27 28.01 31.97 35.33 37.31 40.79 43.75 46.32 48.56 50.55

Notes:1. Fouling Factor = 0.0005.2. Capacity based on 12°C entering air temperature and 82°C entering water temperature.

Notes:1. Fouling Factor = 0.0005.2. Capacity based on 12°C entering air temperature and 82°C entering water temperature.

Page 15: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 15VAV-PRC008-EN

PerformanceData—Hot WaterCoil (SI)

Temperature Correction Factors for Water Pressure Drop (kPa)

Average Water Temperature 93 88 82 77 71 66 60 54 49 43Correction Factor 0.970 0.985 1.000 1.020 1.030 1.050 1.080 1.100 1.130 1.150

Temperature Correction Factors for Coil Capacity (kW)

Entering Water Minus Entering Air 22 28 33 39 44 56 69 78 83 89 100 111Correction Factor 0.32 0.40 0.48 0.56 0.64 0.80 1.00 1.12 1.20 1.29 1.45 1.61

LAT = EAT + kW x 0.83 L/s( ) WTD = EWT - LWT = kW

(4.19) L/s)(

Notes:1. Fouling Factor = 0.0005.2. Capacity based on 12°C entering air temperature and 82°C entering water temperature. Refer to correction factors for different

entering conditions on page 45.3. The following equations may be used in calculating Leaving Air Temperature (LAT) and Water Temperature Difference (WTD).

Inlet Size 16x24 (SI)Water

Pressure Airflow (L/s)Rows L/s Drop (kPa) 472 802 1133 1463 1793 2124 2454 2784 3115 34451-Row 0.13 4.50 12.54 15.39 17.36 18.84 20.01 20.95 21.74 22.40 22.97 23.46

Capacity 0.19 9.28 13.77 17.29 19.94 22.04 23.74 25.17 26.39 27.44 28.35 29.16kW 0.25 15.59 14.50 18.40 21.48 24.00 26.09 27.88 29.43 30.79 31.99 33.05

0.32 23.35 14.97 19.19 22.50 25.32 27.70 29.76 31.57 33.16 34.58 35.860.38 32.53 15.30 19.74 23.27 26.27 28.87 31.14 33.14 34.93 36.53 37.980.47 48.88 15.64 20.33 24.11 27.31 30.13 32.63 34.86 36.87 38.68 40.33

2-Row 0.32 3.75 22.58 29.24 33.37 36.20 38.28 39.89 41.17 42.23 43.11 43.86Capacity 0.57 11.08 24.58 33.13 38.84 42.99 46.17 48.70 50.76 52.50 53.97 55.25

kW 0.82 21.95 25.41 34.84 41.36 46.21 49.99 53.05 55.58 57.73 59.57 61.181.07 36.25 25.87 35.81 42.81 48.09 52.26 55.65 58.48 60.89 62.98 64.811.32 53.88 26.16 36.43 43.76 49.33 53.76 57.38 60.42 63.02 65.28 67.261.42 61.34 26.25 36.61 44.03 49.69 54.20 57.89 61.00 63.65 65.96 67.99

Coil Only –Water Weights

Internal Internal OperatingInlet Coil Volume Volume WeightSize Type (cm3) (liters) (kg)04 1-Row 153.6 0.154 2.42105 1-Row 153.6 0.154 2.42106 1-Row 153.6 0.154 2.42108 1-Row 209.4 0.209 2.47710 1-Row 312.4 0.312 3.48712 1-Row 492.5 0.493 4.85314 1-Row 839.1 0.839 6.30916 1-Row 960.6 0.961 7.337

24x16 1-Row 1082.0 1.082 9.27304 2-Row 388.0 0.388 3.1205 2-Row 388.0 0.388 3.1206 2-Row 388.0 0.388 3.1208 2-Row 581.3 0.580 4.09910 2-Row 800.1 0.799 5.29412 2-Row 1103.0 1.101 7.02614 2-Row 1545.0 1.542 8.96516 2-Row 1788.0 1.784 10.57

24x16 2-Row 2030.0 2.027 13.53

Page 16: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 16

PerformanceData—Electric Data

Minimum Circuit Ampacity (MCA) Equation— MCA = heater amps x 1.25

Maximum Overcurrent Protection (MOP) Equation— MOP = heater amps— However since MOP ≤ MCA, then choose next fuse greater than MCA.— Units without electric reheat would use smallest fuse sizing.— Standard Fuse Sizes: 15, 20, 25, 30, 35, 40, 45, 50, and 60.

Example–For MOP of Single-Duct UnitA model VCEF, electric reheat unit size 14 has 480/3 phase 15 kW electric reheat with 2 stages.15 kW – 480/3 heater 15 x 1000 = 18.06

480 x 1.73MCA = 18.06 x 1.25 = 22.58 amps. Since MOP ≤ MCA, then MOP = 25.

kW = 1214 x L/s x ATD

1φamps = kW x 1000Primary Voltage

ATD = kW x 3145Cfm

3145Cfm x ATDkW =

3φamps =kW x 1000

Primary Voltage x √ 3

1214 x L/sATD = kW

Useful formulas:

VCEF Electric Coil kW Guidelines – Minimum to MaximumInlet Single-Phase Voltage Three-Phase VoltageSize Stages 120V 208V/240V 277V 347V 480V 208V 480V 575V 380V/50 Hz

04 1 1.0 1.0 1.0 1.0 1.0 1.0 1.0 — 1.02 1.0 1.0 1.0 1.0 — — — — —3 1.0 1.0 1.0 1.0 — — — — —

05 1 1.0–2.5 1.0–2.5 1.0–2.5 1.0–2.5 1.0–2.5 1.0–2.5 1.0–2.5 1.5–2.5 1.0–2.52 1.0–2.5 1.0–2.5 1.0–2.5 1.0–2.5 1.5–2.5 1.0–2.5 — — —3 1.0–2.5 1.0–2.5 1.0–2.5 1.5–2.5 — — — — —

06 1 1.0–4.0 1.0–4.0 1.0–4.0 1.0–4.0 1.0–4.0 1.0–4.0 1.0–4.0 1.5–4.0 1.0–4.02 1.0–4.0 1.0–4.0 1.0–4.0 1.0–4.0 1.5–4.0 1.0–4.0 — — —3 1.0–4.0 1.0–4.0 1.0–4.0 1.5–4.0 — — — — —

08 1 1.0–5.0 1.0–7.0 1.0–7.0 1.0–7.0 1.0–7.0 1.0–7.0 1.0–7.0 1.5–7.0 1.0–7.02 1.0–5.0 1.0–7.0 1.0–7.0 1.0–7.0 1.5–7.0 2.0–7.0 4.0 — 3.0–7.03 1.0–5.0 1.0–7.0 1.0–7.0 1.5–7.0 2.0–7.0 — 6.0 — 4.0–7.0

10 1 1.0–5.0 1.0–9.0 1.0–11.0 1.0–11.0 1.0–11.0 1.0–11.0 1.0–11.0 1.5–11.0 1.0–11.02 1.0–5.0 1.0–9.0 1.0–11.0 1.0–11.0 1.0–11.0 1.0–11.0 3.0–11.0 9.0–10.0 2.0–11.03 1.0–5.0 1.0–9.0 1.0–11.0 1.5–11.0 1.5–11.0 2.0–11.0 5.0–11.0 — 3.0–11.0

12 1 1.0–5.0 1.0–9.0 1.0–13.0 1.0–16.0 1.0–16.0 1.0–16.0 1.0–16.0 1.5–16.0 1.0–16.02 1.0–5.0 1.0–9.0 1.0–13.0 1.0–16.0 1.0–16.0 1.0–16.0 3.0–16.0 3.5–16.0 1.5–16.03 1.0–5.0 1.0–9.0 1.0–13.0 1.5–16.0 1.5–16.0 2.0–16.0 4.0–15.0 5.5–16.0 2.5–16.0

14 1 1.0–5.0 1.0–9.0 1.0–13.0 1.0–16.0 1.0–22.0 1.0–16.0 1.0–22.0 1.5–22.0 1.0–22.02 1.0–5.0 1.0–9.0 1.0–13.0 1.0–16.0 1.0–22.0 1.0–16.0 2.0–22.0 3.0–22.0 1.5–22.03 1.0–5.0 1.0–9.0 1.0–13.0 1.5–16.0 1.5–22.0 2.0–16.0 3.0–20.0 4.5–18.0 2.5–22.0

16 1 1.0–5.0 1.0–9.0 1.0–13.0 1.0–16.0 1.0–22.0 1.0–16.0 1.0–30.0 1.5–30.0 1.0–30.02 1.0–5.0 1.0–9.0 1.0–13.0 1.0–16.0 1.0–22.0 1.0–16.0 2.0–30.0 2.5–30.0 1.5–30.03 1.0–5.0 1.0–9.0 1.0–13.0 1.5–16.0 1.5–22.0 2.0–16.0 3.0–30.0 4.0–26.0 2.5–30.0

24 x 16 1 1.0–5.0 1.0–9.0 1.0–13.0 1.0–16.0 1.0–22.0 1.0–16.0 1.0–38.0 1.5–46.0 1.0–30.02 1.0–5.0 1.0–9.0 1.0–13.0 1.0–16.0 1.0–22.0 1.0–16.0 2.0–38.0 2.5–46.0 1.5–30.03 1.0–5.0 1.0–9.0 1.0–13.0 1.5–16.0 1.5–22.0 1.5–16.0 3.0–38.0 3.5–40.0* 2.5–30.0

* 36.0 not availableNotes:1. Coils available with 24-volt magnetic or mercury contactors, load carrying P.E switches, and P.E. switch with magnetic or mercury contactors.2. Available kW increments are by 0.5 kW from 1.0 to 8.0 kW, by 1.0 kW from 9.0 to 18.0 kW, and by 2.0 kW from 18.0 to 46.0 kW.3. Each stage will be equal in kW output.4. All heaters contain an auto-thermal cutout and a manual-reset cutout.5. The current amp draw for the heater elements is calculated by the formula below.6. The maximum allowable kW is based on the largest kW possible per a voltage and the minimum airflow per an inlet size and kW.

Page 17: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 17VAV-PRC008-EN

PerformanceData—Electric Data

Minimum and Maximum Airflow per Inlet Size and kW

14 1.0–9.0 640 3000 302 141510.0 720 3000 340 141511.0 800 3000 378 141512.0 880 3000 415 141513.0 960 3000 453 141514.0 1040 3000 491 141515.0 1120 3000 529 141516.0 1200 3000 566 141517.0 1280 3000 604 141518.0 1345 3000 635 141520.0 1475 3000 696 141522.0 1600 3000 755 1415

16 1.0–12.0 840 4000 396 188613.0 910 4000 430 188614.0 980 4000 463 188615.0 1050 4000 496 188616.0 1120 4000 529 188617.0 1190 4000 562 188618.0 1260 4000 595 188620.0 1400 4000 661 188622.0 1540 4000 727 188624.0 1680 4000 793 188626.0 1820 4000 859 188628.0 1960 4000 925 188630.0 2100 4000 991 1886

24 x 16 1.0–22.0 1600 8000 755 377224.0 1800 8000 850 377226.0 2000 8000 944 377228.0 2200 8000 1038 377230.0 2400 8000 1133 377232.0 2600 8000 1227 377234.0 2800 8000 1322 377236.0 3000 8000 1416 377238.0 3200 8000 1510 377240.0 3400 8000 1605 377242.0 3600 8000 1699 377244.0 3800 8000 1794 377246.0 4000 8000 1888 3772

I-P SIInlet Min Max Min MaxSize kW Cfm Cfm L/s L/s

I-P SIInlet Min Max Min MaxSize kW Cfm Cfm L/s L/s

4 1.0 130 225 61 1065 1.0 125 350 59 165

1.5 165 350 78 1652.0 185 350 87 1652.5 205 350 97 165

6 1.0 120 500 57 2361.5 150 500 71 2362.0 180 500 85 2362.5 210 500 99 2363.0 240 500 113 2363.5 270 500 127 2364.0 300 500 142 236

8 1.0–3.0 210 900 99 4253.5 265 900 125 4254.0 315 900 149 4254.5 345 900 163 4255.0 380 900 179 4255.5 420 900 198 4256.0 450 900 212 4256.5 490 900 231 4257.0 525 900 248 425

10 1.0–4.5 330 1400 156 6605.0 370 1400 175 6605.5 410 1400 194 6606.0 450 1400 212 6606.5 495 1400 234 6607.0 550 1400 260 6607.5 605 1400 286 6608.0 660 1400 312 6609.0 710 1400 335 66010.0 765 1400 361 66011.0 820 1400 387 660

12 1.0–6.5 470 2000 222 9437.0 520 2000 245 9437.5 565 2000 267 9438.0 615 2000 290 9439.0 705 2000 333 94310.0 785 2000 371 94311.0 860 2000 406 94312.0 940 2000 444 94313.0 1000 2000 472 94314.0 1055 2000 498 94315.0 1115 2000 526 94316.0 1175 2000 555 943

Note: Minimum and maximum airflow is based on UL listing and certification.

Page 18: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 18

PerformanceData—Acoustics

Discharge Sound Power (dB)Discharge Sound Power (dB)

Inlet Fan 0.5" ∆∆∆∆∆Ps 1.0" ∆∆∆∆∆Ps 2.0" ∆∆∆∆∆Ps 3.0"∆∆∆∆∆PsSize Cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

4 80 38 57 57 45 44 40 37 58 61 52 51 47 46 60 66 60 60 60 56 61 69 66 66 64 61120 57 60 60 48 48 43 41 64 65 54 53 49 47 64 69 63 60 57 55 65 72 70 68 63 60150 71 60 60 48 49 45 42 65 66 55 54 51 49 67 72 64 61 58 56 68 72 71 68 64 61225 106 65 64 53 54 50 49 70 71 60 59 55 54 73 77 67 64 61 59 72 78 72 69 65 63

5 130 61 52 52 44 43 41 38 55 58 51 50 48 47 57 64 60 59 58 55 59 68 68 66 63 60200 94 55 55 47 47 43 40 59 61 55 53 50 49 62 67 63 61 58 56 61 69 69 67 63 61250 118 57 57 48 49 44 42 62 63 56 55 52 50 65 69 63 60 58 57 65 71 71 69 63 61350 165 59 59 53 53 48 47 66 65 58 57 53 53 70 72 66 62 59 58 70 74 72 69 64 63

6 200 94 52 53 45 44 41 38 56 59 54 52 49 47 58 66 63 60 58 55 60 70 71 67 63 60300 142 56 56 47 48 44 41 59 61 55 53 50 48 63 67 64 61 58 56 64 71 71 69 64 62400 189 57 56 50 49 44 42 63 63 57 55 51 50 66 69 65 61 58 57 68 72 72 68 63 62500 236 61 60 54 53 49 47 65 65 60 58 53 53 69 71 68 63 60 59 71 74 72 69 64 63

8 350 165 54 54 47 45 44 40 57 61 53 51 50 53 61 68 61 58 58 60 64 73 70 66 63 61520 245 56 56 50 48 45 42 59 63 56 53 52 56 64 71 64 61 60 66 66 73 71 66 65 66700 330 58 57 53 51 48 44 62 64 59 56 53 57 66 71 66 62 61 64 68 74 73 68 66 69900 425 61 60 56 56 52 49 65 65 61 59 56 57 70 72 68 64 62 65 72 75 73 68 67 68

10 550 260 53 52 52 51 45 40 58 60 57 57 53 48 64 66 64 66 62 58 66 69 69 71 66 62820 387 56 55 54 51 46 42 61 62 60 60 55 52 66 68 65 66 62 60 69 72 69 70 66 631100 519 60 58 57 54 49 46 65 65 63 61 56 53 70 70 67 68 63 60 72 73 72 71 67 641400 661 64 61 61 58 53 51 69 66 64 62 57 54 73 72 69 66 63 60 74 75 72 70 67 64

12 800 378 54 52 52 49 47 41 59 59 57 55 55 52 66 67 65 63 63 61 67 69 68 67 67 641200 566 56 54 54 50 49 43 62 62 60 57 57 55 68 69 67 63 64 62 72 73 71 68 68 661600 755 59 57 58 53 52 46 64 64 62 58 57 56 70 71 69 64 65 63 73 75 73 69 69 662000 944 63 60 61 56 56 51 68 67 65 61 60 59 73 73 70 65 65 64 76 75 74 69 69 67

14 1100 519 54 52 51 46 44 39 60 60 57 54 53 51 65 71 66 62 61 59 68 72 71 67 66 631600 755 57 55 55 49 46 41 63 61 60 56 54 51 67 70 67 63 62 61 70 75 72 67 67 642100 991 60 59 59 52 49 44 65 65 63 57 54 52 69 71 69 64 62 61 72 73 73 68 67 643000 1416 66 65 67 57 55 52 71 70 68 61 58 58 76 76 72 66 64 61 77 77 75 70 69 66

16 1400 661 54 52 51 47 46 40 60 60 58 55 55 51 66 71 67 63 63 62 69 75 73 69 67 662100 991 57 55 55 51 49 43 63 62 60 57 55 52 68 70 68 64 64 61 70 75 73 70 68 662800 1321 61 60 61 54 51 48 66 65 64 58 57 54 69 71 70 65 64 63 72 73 73 70 69 654000 1888 68 67 68 63 57 54 71 70 70 63 61 59 75 75 73 68 65 64 77 76 76 72 70 67

24 2700 1274 68 67 61 58 54 50 72 71 67 65 62 58 74 75 73 71 68 65 75 77 76 75 72 69x 4000 1888 70 70 65 62 58 54 74 75 71 68 65 61 78 79 77 75 72 68 79 81 80 78 76 7216 5300 2501 69 70 67 64 61 58 75 76 75 71 67 63 78 82 81 78 74 70 81 84 84 81 78 74

6000 2832 68 70 68 65 62 60 75 76 76 72 68 65 79 82 83 79 75 71 81 85 86 82 79 757500 3540 67 70 70 67 63 63 76 76 77 73 70 68 80 83 88 81 76 73 82 86 90 84 80 768000 3776 67 70 71 68 64 64 76 76 78 74 71 69 80 83 89 82 77 74 82 86 91 85 81 77

Notes:1. All data are measured in accordance with current Industry Standard ARI 880, version 1998.2. All sound power levels, dB re: 10-12 watts.3. Where ∆Ps is inlet static pressure minus discharge static pressure.

Page 19: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 19VAV-PRC008-EN

PerformanceData—Acoustics

Radiated Sound Power (dB)Radiated Sound Power (dB)

Inlet 0.5" ∆∆∆∆∆Ps 1.0" ∆∆∆∆∆Ps 2.0"∆∆∆∆∆Ps 3.0" ∆∆∆∆∆PsSize Cfm L/s 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7 2 3 4 5 6 7

4 80 38 48 45 40 33 31 23 48 47 43 37 34 25 48 51 53 47 43 35 46 52 60 54 48 42120 57 47 45 40 33 30 23 49 48 45 38 34 27 50 51 54 46 42 36 51 54 60 52 47 42150 71 47 45 41 35 30 24 51 49 46 39 35 28 52 53 55 47 43 37 51 56 61 53 48 42225 106 52 49 44 40 35 30 57 54 49 43 39 33 60 59 57 48 45 39 59 61 63 54 49 44

5 130 61 47 44 35 29 24 21 48 45 41 35 30 25 48 48 50 45 39 33 48 51 58 51 45 40200 94 48 45 38 32 25 22 49 47 43 37 32 26 50 52 52 45 39 35 50 55 58 51 45 40250 118 48 44 40 34 27 23 50 48 45 38 33 27 52 53 53 44 40 35 53 56 60 52 44 40350 165 51 47 44 38 31 26 55 51 47 41 35 31 59 56 55 47 41 37 56 58 60 51 44 40

6 200 94 52 46 38 31 25 22 50 47 43 36 31 26 52 51 52 43 38 33 51 55 59 50 44 40300 142 52 48 41 33 25 22 55 50 46 38 32 27 56 53 53 44 38 35 57 57 60 50 44 39400 189 55 49 44 36 28 24 56 53 48 40 33 28 59 56 55 46 40 35 59 58 60 50 43 40500 236 55 49 47 40 32 27 59 54 51 43 36 31 62 59 57 47 41 36 63 60 61 52 44 40

8 350 165 46 42 38 31 27 22 48 45 43 36 35 27 54 52 53 42 41 36 56 58 64 52 46 42520 245 49 43 41 35 31 24 51 48 47 39 37 29 55 54 54 45 43 38 56 57 63 51 47 44700 330 50 46 44 38 34 26 54 51 50 42 38 34 58 57 57 48 45 39 60 59 62 52 48 44900 425 56 49 50 44 37 29 59 53 53 46 41 35 62 59 57 49 46 39 63 61 62 53 49 44

10 550 260 48 44 42 32 25 24 52 49 48 40 31 26 55 55 53 47 39 32 58 58 59 50 44 38820 387 53 47 43 36 28 25 57 52 49 41 33 27 60 58 55 48 40 33 62 61 60 52 44 381100 519 58 50 46 39 30 27 61 55 51 43 35 29 64 61 57 50 42 35 67 63 61 53 45 391400 661 62 53 49 42 34 30 66 58 54 46 38 33 69 63 58 51 43 37 71 65 63 55 46 41

12 800 378 49 46 40 33 27 27 54 51 46 39 34 29 58 58 53 46 42 35 59 62 59 51 47 401200 566 54 48 43 35 29 27 59 54 48 41 35 30 64 61 55 48 43 37 66 64 60 52 47 421600 755 60 53 47 38 32 30 63 58 50 42 37 32 68 64 57 49 43 39 71 66 61 53 48 432000 944 63 58 52 42 37 34 67 62 54 45 40 38 72 68 58 50 45 42 75 68 61 54 50 45

14 1100 519 47 46 36 30 24 23 53 53 42 36 32 27 57 61 52 43 40 35 60 64 60 48 43 381600 755 52 49 39 32 24 23 56 54 45 38 32 26 60 63 52 44 39 35 63 67 60 49 43 402100 991 55 52 43 35 27 25 59 57 48 40 33 28 63 64 55 46 40 36 65 67 61 50 44 403000 1416 63 59 51 42 34 31 65 64 54 44 36 34 68 68 57 48 41 37 69 69 60 52 45 41

16 1400 661 50 47 38 32 26 23 54 54 45 40 35 29 60 62 53 47 43 38 63 66 61 52 47 432100 991 51 49 41 35 28 24 56 54 47 41 36 30 61 61 55 49 44 39 64 66 60 53 48 432800 1321 56 54 45 38 31 27 59 56 49 43 37 32 62 62 56 49 44 39 65 65 61 54 49 444000 1888 61 60 55 45 38 32 63 63 56 47 41 36 67 66 59 51 46 41 69 66 62 55 50 45

24 2700 1274 65 63 53 45 38 30 70 65 60 52 45 37 71 69 66 59 51 45 72 71 69 62 54 50x 4000 1888 67 67 57 48 40 32 71 71 64 55 48 41 74 75 69 61 54 48 76 77 72 65 58 52

16 5300 2501 67 66 58 49 42 35 74 75 69 57 49 42 76 77 74 64 56 50 78 79 76 67 60 536000 2832 68 66 59 51 44 37 74 75 69 58 50 43 77 78 75 65 57 51 79 80 77 68 61 547500 3540 69 67 61 54 48 42 75 74 70 59 51 45 78 80 78 66 58 52 80 81 79 69 62 558000 3776 69 67 62 55 49 44 75 74 70 59 52 46 79 81 79 67 59 52 80 82 80 70 63 56

Notes:1. All data are measured in accordance with current Industry Standard ARI 880, version 1998.2. All sound power levels, dB re: 10-12 watts.3. Where ∆Ps is inlet static pressure minus discharge static pressure.

Page 20: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 20

PerformanceData—Acoustics

Discharge RadiatedInlet Pressure (∆∆∆∆∆Ps) Inlet Pressure (∆∆∆∆∆Ps)

Inlet 0.5" 1.0" 2.0" 3.0" 0.5" 1.0" 2.0" 3.0"Size Cfm L/s (127 Pa) (254 Pa) (508 Pa) (762 Pa) (127 Pa) (254 Pa) (508 Pa) (762 Pa)

4 80 38 15 20 26 30 — 16 27 35120 57 19 25 30 34 — 19 29 35150 71 19 26 34 34 — 20 30 36225 106 24 32 39 40 17 23 32 38

5 130 61 — 16 24 29 — 15 24 33200 94 — 20 27 30 — 16 26 33250 118 15 22 30 32 — 19 27 35350 165 17 25 34 36 17 21 30 35

6 200 94 — 17 26 31 — 16 26 34300 142 — 20 27 32 15 20 27 35400 189 — 22 30 34 17 22 30 35500 236 19 25 32 36 21 25 32 36

8 350 165 — 17 27 34 — 16 27 39520 245 — 21 31 34 — 21 29 38700 330 — 22 31 35 17 24 32 37900 425 17 24 32 36 24 27 32 37

10 550 260 — 16 24 27 15 22 27 34820 387 — 19 26 31 16 23 30 351100 519 — 22 29 32 20 25 32 361400 661 17 24 31 35 25 30 34 38

12 800 378 — 16 25 27 — 20 27 341200 566 — 19 27 32 16 22 31 351600 755 — 21 30 35 22 27 35 372000 944 16 25 32 35 27 32 39 41

14 1100 519 — 16 30 31 — 21 31 351600 755 — 17 29 35 16 22 34 382100 991 15 22 30 32 20 26 35 383000 1416 22 29 36 37 29 35 39 40

16 1400 661 — 16 30 35 — 22 32 372100 991 — 19 29 35 16 22 31 372800 1321 16 22 30 32 22 25 32 364000 1888 25 29 35 36 30 34 37 37

24 2700 1274 25 30 35 37 34 36 41 45x 4000 1888 29 35 39 41 38 42 47 50

16 5500 2501 29 36 42 45 37 47 50 526000 2832 29 36 42 46 37 47 51 547500 3540 29 36 44 47 38 46 55 568000 3776 29 36 44 47 38 46 56 57

Notes:1. “—” represents NC levels below NC 15.2. NC Values are calculated using current Industry Standard ARI 885, 2002 addendum to revision 1998. Radiated Transfer Function

obtained from Appendix E, Type 2 Mineral Fiber Insulation.3. Where ∆Ps is inlet static pressure minus discharge static pressure.

Sound Noise Criteria (NC)

ARI 885-98 DISCHARGE TRANSFER FUNCTION ASSUMPTIONS:Octave Band

2 3 4 5 6 7

Small Box (< 300 cfm) -24 -28 -39 -53 -59 -40Medium Box (300-700 cfm) -27 -29 -40 -51 -53 -39Large Box (> 700 cfm) -29 -30 -41 -51 -52 -39Note: Add to terminal unit sound power to determine discharge soundpressure in the space.

ARI 885-98 RADIATED TRANSFER FUNCTION ASSUMPTIONS:Octave Band

2 3 4 5 6 7

Type 1 – Glass Fiber -19 -19 -21 -25 -29 -35Type 2 – Mineral Fiber Insulation -18 -19 -20 -26 -31 -36Type 3 – Solid Gypsum Board -23 -26 -25 -27 -27 -28Note: Select the ceiling type which most closely represents theapplication. Next, add to terminal unit sound power to determine radiatedsound pressure in the space.

Page 21: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 21VAV-PRC008-EN

PerformanceData—Acoustics

Inlet 1.5" Inlet Pressure (381 Pa)Size Cfm L/s 2 3 4 5 6 7

4 150 71 67 70 60 58 55 535 250 118 63 66 60 57 55 546 400 189 65 67 62 59 56 558 700 330 64 68 62 59 58 6010 1100 519 69 68 66 66 61 5712 1600 755 68 69 66 61 62 6014 2100 991 68 68 66 61 59 5816 2800 1321 69 68 67 62 61 60

24x16 5300 2501 77 79 78 75 71 68

Discharge Sound Power (dB)ARI Conditions

Inlet 1.5" Inlet Pressure (381 Pa)Size Cfm L/s 2 3 4 5 6 7

4 150 71 52 52 50 43 39 335 250 118 52 50 49 42 37 316 400 189 58 54 51 43 37 328 700 330 57 54 53 45 42 3610 1100 519 63 59 54 47 39 3212 1600 755 66 62 54 46 40 3614 2100 991 61 61 51 43 37 3216 2800 1321 60 60 53 46 41 36

24x16 5300 2501 75 76 72 61 53 46

Radiated Sound Power (dB)ARI Conditions

Notes:1. All sound data rated in accordance with current Industry Standard

ARI 880, version 1998.2. All sound power levels, dB re: 10-12 watts.

Page 22: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 22

DimensionalData

NOTES:

1. Air inlet centered in unit front panel.

2. Outlet combinations to remote diffusers have optional integral balancing dampers. (See specification sheet.)

3. Outlet connections are centered in plenum panel.

4. Plenum not available with size 14 & 16 units.

5. Minimum of 1.5 duct diamenters of straight duct required at inlet for proper flow reading.

6. Allow 12" (305 mm) on control side for servicing.

7. Weights are an estimation and will vary based on selected options, insulation type, etc.

8. Unit is field convertible from a left-hand connection (shown) to right-hand by rotating unit.

AIRFLOW

VALVE

AIRFLOW

C

L

D

W

H

BACK VIEW

TOP VIEW

A B C D FE H J

NOMINALØ

5" (127 mm)6" (152 mm)

8" (203 mm)

10" (254 mm)

OUTL CONVERSION CHART

SYMBOL

II

IIIIV

I

OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINALØ

A,B,C

HOUTL

J

VALV

D,E,F

N/A N/A N/A

IIII, II

4 5

III, IV

6

IV

8 10 12

I, II I, II

I, II I, II I, II I, II, III II, III, IV III, IV

I, II I, II I, IIIN/A I, II

I, II, III II, III, IV III, IV

OUTLET PLENUMARRANGEMENTS

(TOP VIEW)

E

AIR

VALV

04

05

06

08

10

12

14

16

24RT 8000

4000

3000

2000

1400

900

500

350

225

CFM

1416

1888

3776

994

661

425

236

165

106

L/s

14" (356 mm)

16" (406 mm)

24" x 16"

12" (305 mm)

10" (254 mm)

8" (203 mm)

6" (152 mm)

5" (127 mm)

4" (104 mm)

INLET SIZE(NOMINAL Ø)

(610 mm x 406 mm)

5.00" (127 mm)

4.50" (114 mm)

3.50" (89 mm)

5.00" (127 mm)

5.55" (141 mm)

D

9.50" [241 mm]

15.50" [394 mm]

13.50" [343 mm]

H

11.50" [292 mm]

19.50" [495 mm]

11.50" (292 mm)

20.50" (521 mm)

18.50" (470 mm)

12.50" (318 mm)

W

15.50" (394 mm)

24.50" (622 mm)

28.50" (724 mm)

L

18.00" (457 mm)

15.00" (381 mm)

11.50" (292 mm)

11.00" (279 mm)

12.00" (305 mm)

13.00" (330 mm)

14.00" (356 mm)

DISCHARGE DIM W/O OUTLET PLENUM

A (h) B (w)

18.00" (457 mm)

23.00" (584 mm)

27.00" (686 mm)

8.00" (203 mm)

10.00" (254 mm)

12.00" (305 mm)

14.00" (356 mm)

19.00" (483 mm)

17.00" (432 mm)

14.00" (356 mm)

11.00" (279 mm)

9.85" (250 mm)C

SINGLE-DUCT COOLING ONLY WITH OPTIONAL OUTLET PLENUM (VCCF)

21 (9.5)

22 (10)

30 (14)

38 (17)

46 (21)

51 (23)

70 (32)

E

11.50" (292 mm)

14.00" (356 mm)

14.00" (356 mm)

SIZE 04 & 055.75" (146 mm)

4.00"[102mm]

FLOW RINGTUBING

CONTROL BOXANALOG OR DDC/UCM(PNEU. CONTROLS AREA)

6.50"(165 mm)

ACTUATOR

SLIP & DRIVECONNECTION

8.25"(210 mm)

5.50"(140 mm)

NA

NA

NA

DIMENSIONS (BxA)DISCHARGE

(25.4 mm)1.00"

Z

2.25" (57 mm)

2.75" (70 mm)

4.25" (108 mm)

3.25" (83 mm)

2.75" (70 mm)

Z

2.25" (57 mm)5.50" (140 mm)

ARRANGEMENT "H"1.50" (38 mm) FLANGE

WTLBS

(KGS)

Page 23: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 23VAV-PRC008-EN

DimensionalData

WATERCOIL

VALVE

AIRFLOW

C

D

L

H

W

BACK VIEW

TOP VIEW

E

NOMINALØ

5" (127 mm)6" (152 mm)

8" (203 mm)10" (254 mm)

OUTL CONVERSION CHART

SYMBOL

II

IIIIV

I

OUTLET AVAILABILITY CHART - SEE OUTL CONVERSION FOR NOMINALØ

A,B,C

HOUTL

J

VALV

D,E,F

N/A N/A N/A

IIII, II

4 5

III, IV

6

IV

8 10 12

I, II I, II

I, II I, II I, II I, II, III II, III, IV III, IV

I, II I, II I, IIIN/A I, II

I, II, III II, III, IV III, IV

NOTES:

1. Air inlet is centered in unit front panel. 2. Outlet combinations to remote diffusers have optional integral balancing dampers (See specification sheet.)

3. Outlet connections are centerd in plenum panel.

4. Plenum not available with sizes 14 & 16 units.

5. Minimum of 1.5 duct diameters of straight duct required for proper flow reading.

6. Allow 12" (305 mm) on control side for servicing.

7. Weights are an estimation and will vary based on selected options, insulation type, etc.

8. Coil furnished with stub sweat connections. Handedness of coil connections is determined by facing air stream.

9. Coils are provided without internal insulation. If the unit is to be installed in a location with high humidity, external insulation around the heating coil should be installed as required.

10. Unit is field convertible from a left-hand connection (shown) to right-hand by rotating unit.

(TOP VIEW)ARRANGEMENTS

A B C D

OUTLET PLENUM

HFE J

AIR

VALV

04

05

06

08

10

12

14

16

24RT 8000

4000

3000

2000

1400

900

500

350

225

CFM

1416

1888

3776

994

661

425

236

165

106

14" (356 mm)

16" (406 mm)

24" x 16"

12" (305 mm)

10" (254mm)

8" (203 mm)

6" (152 mm)

5" (127 mm)

4" (104 mm)

INLET SIZE(NOMINAL Ø)

(610 mm x 406 mm)

5.00" (127 mm)

4.50" (114 mm)

3.50" (89 mm)

5.55" (141 mm)

D

9.50" (241 mm)

15.50" (394 mm)

13.50" (343 mm)

H

11.50" (292 mm)

19.50" (495 mm)

11.50" (292 mm)

20.50" (521 mm)

18.50" (470 mm)

12.50" (318 mm)

W

15.50" (394 mm)

24.50" (622 mm)

28.50" (724 mm)

L

18.00" (457 mm)

15.00" (381 mm)

11.50" (292 mm)

11.00" (279 mm)

12.00" (305 mm)

13.00" (330 mm)

14.00" (356 mm)

DISCHARGE DIM W/O OUTLET PLENUM

A (h) B (w)

18.00" (457 mm)

23.00" (584 mm)

27.00" (686 mm)

8.00" (203 mm)

10.00" (254 mm)

12.00" (305 mm)

14.00" (356 mm)

19.00" (483 mm)

17.00" (432 mm)

14.00" (356 mm)

11.00" (279 mm)

10.00" (254 mm)

C

SINGLE-DUCT HOT WATER WITH OPTIONAL OUTLET PLENUM (VCWF)WT

27 (12)

LBS

30 (14)

40 (18)

51 (23)

62 (28)

71 (32)

95 (43)

(KGS)

(140 mm)

AIR FLOW

COIL ACCESS76 mm x 178 mm(3.00" x 7.00")

CONTROL BOXANALOG OR DDC/UCM(PNEU. CONTROLS AREA)

FLOW RINGTUBING

ACTUATOR

SLIP & DRIVECONNECTION

4.00"(102 mm)

SIZE 04 & 055.75" (146 mm)

L/s E

14.00" (356 mm)

14.00" (356 mm)

11.50" (292 mm)

DIMENSIONS (BxA)DISCHARGE

NA

NA

NA2.25" (57 mm)

2.75" (70 mm)

4.25" (108 mm)

3.25" (83 mm)

2.75" (70 mm)

Z

2.25" (57 mm)5.50" (140 mm)

5.00" (127 mm)

Z

6.50"(165 mm)

ARRANGEMENT "H"1.50" (38 mm) FLANGE

5.50"

8.25(210 mm)

04, 05, 06 – 7.70" (196 mm)all others – 7.40" (188 mm)

Page 24: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 24

DimensionalData

L.H. and R.H. coil connections are available (L.H. shown).Location of coil connections is determined by facing air stream.1.

CUSTOMER NOTES:

2. Coil furnished with stub sweat connections.

08

10

12

14

VALV

04

05

06

COIL INFORMATION FOR 1-ROW COIL

CONNECTION

7" (178 mm)3 / 8 " (10 mm) O.D.

8/ " (10 mm) O.D.

8 " (22 mm) O.D.

7 / 8 " (22 mm) O.D.

B DCA

1400 661

3000

2000 994

1416

SECOND

LITERS

900

350

500

225

per

165

425

236

CFM

106 (203 mm)8"

3. Use port at bottom for inlet and port at top for outlet.

Coil height and width is dependent upon unit height4.and width.

Access Panel is standard and found on connection side.5.

16

24 x 16

4000

8000

1888

3776

(10 mm) O.D.8 "

(10 mm) O.D./38 "

(10 mm) O.D./38 "

(22 mm) O.D.

(22 mm) O.D.7 / 8

/7

"

"

COIL

7" (178 mm)

7" (178 mm)

9" (229 mm)

11" (279 mm)

9 (248 mm)

(400 mm)

(400 mm)15

(17 mm)32/21 "SEE

SEE

32/ (17 mm)"

(17 mm)"

(22 mm)7 / 8 (22 mm)

"

(64 mm)"

(38 mm)"

2

7 /

1 /

(53 mm)

"

"

"

(13 mm)"

(13 mm)

7 (11 mm)/ "

(27 mm)"

(203 mm)8"

"

10"

(305 mm)12 "

(356 mm)14"

"

18 "

(457 mm)18 "/ (27 mm)1 1 "(400 mm)4/15 " (38 mm)/1 1 "

(FIG 1)(FIG 2)

(FIG 1)

(FIG 2)

(210 mm)

(FIG 2)

OUTLET

C

(FIG 1)

133 "/32

A

"4/1

(44 mm)

B

3

(210 mm)

8 41/ "

1

(29 mm)

C

649/ "

"/ 167

(198 mm)

13

AIR FLOW

A

B

2

(57 mm)"4/1

"

(86 mm)

3 /3213

AIR FLOW7

(198 mm)16/

13 "

D

INLET

1/8 "

Water coil discharge dimensions located on VCWF6.dimension page.

27" (686 mm)

(584 mm)

(482 mm)

(432 mm)

(356 mm)

(279 mm)

(254 mm)

(254 mm)

(254 mm)

11"

23"

19"

17"

14"

10"

10"

10"

E

E

E

INLET

OUTLET

AIR FLOWAIR FLOW

Coils can be field rotated 180˚ for opposite connections.

D

Page 25: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 25VAV-PRC008-EN

DimensionalData

(FIG 1)(FIG 2)

(FIG 1) (FIG 2)

(FIG 1)

(FIG 2)

L.H. and R.H. coil connections are available (L.H. shown).Location of coil connections is determined by facing air stream.1.

CUSTOMER NOTES:

2. Coil furnished with stub sweat connections.

08

10

12

14

VALV

04

05

06

COIL INFORMATION FOR 2-ROW COIL

(10 mm) O.D.

(10 mm) O.D.

(22 mm) O.D.

(22 mm) O.D.

BA

1400 661

3000

2000 994

1416

SECOND

LITERS

900

350

500

225

per

165

425

236

CFM

106

3. Use port at bottom for inlet and port at top for outlet.

Coil height and width is dependent upon unit height4.and width.

Access Panel is standard and found on connection side.5.

16

24 x 16

4000

8000

1888

3776

(10 mm) O.D.

(22 mm) O.D.

(22 mm) O.D.

/ 8

/7/ 8

"

"

AIR FLOW

(22 mm) O.D.

(22 mm) O.D.

AIR FLOW

" (191 mm)

"

" (210 mm)

(260 mm)"(311 mm)"

"(413 mm)"1

4/(413 mm)16 "4/

4/8 1// "(210 mm)

23 "/64(9 mm)

AB

(9 mm)

2364/ "

(86 mm)3 13

32/ "

(11 mm)

7/ "16

(198 mm)7 13

32/ "

32313/3 "

BA

(198 mm)7 32

13/3 "

(210 mm)81

4/1 "

212/ "

64/691 "

(27 mm)16

11 / "

(25 mm)

1"

(79 mm)/37//64// "

OUTLET

(460 mm)

(460 mm)

(460 mm)

(359 mm)

(308 mm)

(257 mm)

(206 mm)

18 8/

Water coil discharge dimensions located on VCWF6.dimension page.

27" (686 mm)

(254 mm)

(254 mm)

(254 mm)

(279 mm)

(356 mm)

(432 mm)

(482 mm)

(584 mm)

10"

17"

19"

23"

11"

14"

10"

10"

C

Coils can be field rotated 180˚ for opposite connections.

C

C

INLET

OUTLET

AIR FLOW

AIR FLOW

CONNECTIONCOIL

SEE

SEE

Page 26: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 26

DimensionalData

AIRFLOW

AIRFLOW

AIR

VALV

04

05

06

08

10

12

14

16

24RT 8000

4000

3000

2000

1400

900

500

350

225

CFM

1416

1888

3776

994

661

425

236

165

106

perLITERS

SECOND

14" (356 mm)

16" (406 mm)

24" x 16"

12" (305 mm)

10" (254 mm)

8" (203 mm)

6" (152 mm)

5" (127 mm)

4" (104 mm)

INLET SIZE(NOMINAL Ø)

(610 mm x 406 mm)

5.00" (127 mm)

4.50" (114 mm)

3.50" (89 mm)

5.50" (140 mm)

5.55" (141 mm)

D

9.50" (241 mm)

15.50" (394 mm)

13.50" (343 mm)

H

11.50" (292 mm)

19.50" (495 mm)

16.00" (406 mm)

25.00" (635 mm)

23.00" (584 mm)

17.00" (432 mm)

W

20.00" (508 mm)

29.00" (737 mm)

33.00" (838 mm)

L

45.50" (1156 mm)

DISCHARGE DIMENSIONS

A

B

18.00" (457 mm)

23.00" (584 mm)

8.00" (203 mm)

10.00" (254 mm)

12.00" (305 mm)

14.00" (356 mm)

19.00" (483 mm)

17.00" (432 mm)

14.00" (356 mm)

11.00" (279 mm)

10.00" (254 mm)

C

BACK VIEW

TOP VIEW

CUSTOMER NOTES:

1. Air inlet is centered in unit front panel.

2. Slip and Drive discharge outlet standard.

3. 1.5 times duct diameter of straight duct at inlet for proper flow reading.

4. For electric heater access, side hinged door must have minimum distance per NEC or local code.

5. Allow 48" (1219 mm) of straight duct downstream of unit before first runout & inside of the duct should be equal discharge size (A & B).

6. Left-hand unit shown. Opposite hand available. (Moves all components to the other side of the unit.)

L

C

W

H

B

27.00" (686 mm)

A

SINGLE-DUCT ELECTRIC HEAT (VCEF)

D

43.50" (1105 mm)

WTLBS/KGS

63 (29)

67 (30)

81 (37)

93 (42)

108 (49)

121 (55)

135 (61)

VALVE

8.25"(210 mm)

SLIP & DRIVECONNECTION

5.50"(140 mm)

FLOW RINGTUBING

CONTROL BOXELECTRIC OR DDC/UCM

(PNEU. CONTROLS AREA)

6.50"(165 mm")

ACTUATOR

4.00"(102 mm)

ELECTRIC HEATERCONTROL AREA

SIZE 04 & 055.75" (146 mm)

Page 27: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 27VAV-PRC008-EN

DimensionalData

AIRFLOWDISCHARGE OUTLET

AIRFLOW

AIR

VALV

04

05

06

08

10

12

14

16

24RT 8000

4000

3000

2000

1400

900

500

350

225

CFM

1416

1888

3776

994

661

425

236

165

106

perLITERS

SECOND

14" (356 mm)

16" (406 mm)

24" x 16"

12" (305 mm)

10" (254 mm)

8" (203 mm)

6" (152 mm)

5" (127 mm)

4" (104 mm)

INLET SIZE(NOMINAL Ø)

(610 mm x 406 mm)

5.00" (127 mm)

4.50" (114 mm)

3.50" (89 mm)

5.50" (140 mm)

5.55" (141 mm)

D

9.50" (241 mm)

15.50" (394 mm)

13.50" (343 mm)

H

11.50" (292 mm)

19.50" (495 mm)

16.00" (406 mm)

25.00" (635 mm)

23.00" (584 mm)

17.00" (432 mm)

W

20.00" (508 mm)

29.00" (737 mm)

33.00" (838 mm)

L

45.50" (1156 mm)

DISCHARGE DIMENSIONS

A

B

18.00" (457 mm)

23.00" (584 mm)

8.00" (203 mm)

10.00" (254 mm)

12.00" (305 mm)

14.00" (356 mm)

19.00" (483 mm)

17.00" (432 mm)

14.00" (356 mm)

11.00" (279 mm)

10.00" (254 mm)

C

BACK VIEW

TOP VIEW

CUSTOMER NOTES:

1. Air inlet is centered in unit front panel.

2. Slip & Drive discharge outlet standard.

3. 1.5 times duct diameter of straight duct at inlet.

4. For electric heater access, side hinged door must have minimum distance per NEC or local code for proper flow reading.

5. Allow 48" (1219 mm) of straight duct downstream of unit before first runout & inside of the duct should be equal discharge size (A & B)

L

C

W

H

B

27.00" (686 mm)

A

SINGLE-DUCT ELECTRIC HEAT (VCEF) RIGHT-HAND

D

43.50" (1105 mm)

WTLBS/KGS

63 (29)

67 (30)

81 (37)

93 (42)

108 (49)

121 (55)

135 (61)

VALVE

SLIP & DRIVECONNECTION

ACTUATOR

8.25"(210 mm)

6.50"(165 mm")

5.50"(140 mm)

4.00"(102 mm)

SIZE 04 & 055.75" (146 mm)

CONTROL BOXELECTRIC OR DDC/UCM

(PNEU. CONTROLS AREA)

FLOW RINGTUBING

ELECTRIC HEATERCONTROL AREA

Page 28: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 28

to prevent over-stroking. At 3.0 in. wgair valve leakage does not exceed6% of maximum airflow.

Air Valve Combinations Available:Air Valve Size Maximum Cataloged Airflow

in. (mm) cfm (L/s)

04 (102) 225 (106)05 (127) 350 (165)06 (152) 500 (236)08 (203) 900 (425)10 (254) 1400 (660)12 (305) 2000 (943)14 (356) 3000 (1415)16 (406) 4000 (1886)

24 RT–24x16 (610x406) 8000 (3773)

OUTLET CONNECTION

Slip & Drive Connection—Terminalunits come standard with slip & driveconnection.

Outlet Plenum—A sheet metal,insulated box with circular opening(s)is attached to the discharge of themain unit at the factory. The circularopening(s) are centered on the unitplenum to accept round ductworkconnections.

Outlet Plenum with BalancingDampers—A sheet metal, insulatedbox with circular opening(s) is factory-connected to the main unit. Thecircular opening(s) with balancingdamper(s) are centered on the unitplenum to accept round ductworkconnections.

HOT WATER COILS

1-Row Hot Water Coils—The 1-rowhot water reheat coil is factory-installedon the discharge outlet. The coil has144 aluminum-plated fins per foot. Fullfin collars provided for accurate finspacing and maximum fin-tubecontact. The 3/8" (9.5 mm) ODseamless copper tubes aremechanically expanded into the fincollars. Coils are proof tested at450 psig (3102 kPa) and leak tested at300 psig (2068 kPa) air pressure underwater. Coil connections are left-hand.Right-hand connections are optional.

2-Row Hot Water Coils—The 2-rowhot water reheat coil is factory-installedon the discharge outlet. The coil has144 aluminum-plated fins per foot. Fullfin collars provided for accurate finspacing and maximum fin-tubecontact. The 3/8" (9.5 mm) OD seamlesscopper tubes are mechanicallyexpanded into the fin collars. Coils areproof tested at 450 psig (3102 kPa) andleak tested at 300 psig (2068 kPa) airpressure under water. Coils areassembled with headers that provide

MechanicalSpecifications

MODELS VCCF, VCWFand VCEFSingle-duct terminal units.

VCCF – Cooling Only

VCWF – With Hot Water Coil

VCEF – With Electric Coil

CASING22-gage galvanized steel.

AGENCY LISTINGThe unit is UL and Canadian UL Listedas a room air terminal unit. Control #9N65.

ARI 880 Certified.

INSULATION

1/2" (12.7 mm) Matte-facedInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with ½-inch, 1.5 lb/ft3

(12.7 mm, 24.0 kg/m3) compositedensity glass fiber with a high-densityfacing. The insulation R-Value is 1.9. Theinsulation is UL listed and meets NFPA-90A and UL 181 standards. There areno exposed edges of insulation(complete metal encapsulation).

1" (25.4 mm) Matte-facedInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with 1-inch, 1.0 lb/ft3

(25.4 mm, 16.0 kg/m3) compositedensity glass fiber with a high-densityfacing. The insulation R-Value is 3.85.The insulation is UL listed and meetsNFPA-90A and UL 181 standards. Thereare no exposed edges of insulation(complete metal encapsulation).

1/2" (12.7 mm) Foil-facedInsulation—The interior surface ofthe unit casing is acoustically andthermally lined with ½-inch, 1.5 lb/ft3

(12.7 mm, 24.0 kg/m3) density glassfiber with foil facing. The insulationR-Value is 2.1. The insulation is ULlisted and meets NFPA-90A and UL 181standards as well as bacteriologicalstandard ASTM C 665. There are noexposed edges of insulation (completemetal encapsulation).

1" (25.4 mm) Foil-facedInsulation—The interior surface of theunit casing is acoustically andthermally lined with 1-inch, 1.5 lb/ft3

(25.4 mm, 24.0 kg/m3) density glassfiber with foil facing. The insulationR-Value is 4.1. The insulation is ULlisted and meets NFPA-90A and UL 181standards as well as bacteriologicalstandard ASTM C 665. There are no

exposed edges of insulation (completemetal encapsulation).

1" (25.4 mm) Double-wallInsulation—The interior surface of theunit casing is acoustically andthermally lined with a 1-inch, 1.0 lb./ft3

(25.4 mm, 16.0 kg/m3) compositedensity glass fiber with high-densityfacing. The insulation R-value is 3.8. Theinsulation is UL listed and meetsNFPA-90A and UL 181 standards. Theinsulation is covered by an interiorliner made of 26-gage galvanized steel.All wire penetrations are covered bygrommets. There are no exposededges of insulation (complete metalencapsulation).

3/8" (9.5 mm) Closed-cellInsulation—The interior surface of theunit casing is acoustically andthermally lined with 3/8-inch, 4.4 lb/ft3

(9.5 mm, 70.0 kg/m3) closed-cellinsulation. The insulation is UL listedand meets NFPA-90A and UL 181standards. The insulation has anR-Value of 1.4. There are no exposededges of insulation (complete metalencapsulation).

PRIMARY AIR VALVE

Air Valve Round—The primary airinlet connection is an 18-gagegalvanized steel cylinder sized to fitstandard round duct. A multiple-point,averaging flow sensing ring isprovided with balancing taps formeasuring +/-5% of unit catalogedairflow. An airflow-versus-pressuredifferential calibration chart is provided.The damper blade is constructed of aclosed-cell foam seal that ismechanically locked between two22-gage galvanized steel disks. Thedamper blade assembly is connectedto a cast zinc shaft supported by self-lubricating bearings. The shaft is castwith a damper position indicator. Thevalve assembly includes a mechanicalstop to prevent over-stroking. At 4.0 in.wg, air valve leakage does not exceed1% of cataloged airflow.

Air Valve Rectangular—Inlet collar isconstructed of 22-gage galvanized steelsized to fit standard rectangular duct.An integral multiple-point, averagingflow-sensing ring provides primaryairflow measurement within +/-5% ofunit cataloged airflow. Damper is22-gage galvanized steel. The damperblade assembly is connected to a castzinc shaft supported by self-lubricatingbearings. The shaft is cast with adamper position indicator. The valveassembly includes a mechanical stop

Page 29: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

SD 29VAV-PRC008-EN

MechanicalSpecifications

7/8" (22.2 mm) OD braze connections.Right-hand connections are optional.

ELECTRIC HEAT COILThe electric heater is a factory-providedand -installed, UL recognizedresistance open-type heater withairflow switch. It also contains a disc-type automatic pilot duty thermalprimary cutout, and manual reset loadcarrying thermal secondary device.Heater element material is nickel-chromium. The heater terminal box isprovided with 7/8" (22 mm) knockoutsfor customer power supply. Terminalconnections are plated steel withceramic insulators. Heater controlaccess is on the left-hand side.

ELECTRIC HEAT OPTIONS

Electric Heat Transformer—Anoptional transformer is an integralcomponent of the heater control panel(dependent on unit load requirements)to provide 24 VAC for controls. There is19 VA available for controls.

Magnetic Contactor—An optionalelectric heater 24-volt contactor for usewith direct digital control (DDC) oranalog electronic controls.

Mercury Contactor—An optionalelectric heater 24-volt contactor for usewith direct digital control (DDC) oranalog electronic controls.

P.E. Switch with MagneticContactor—This optional switch andmagnetic contactor is for use withpneumatic controls.

P.E. Switch with MercuryContactor—This optional switch andmercury contactor is for use withpneumatic controls.

Airflow Switch— An air pressuredevice designed to disable the heaterwhen the system fan is off. This isstandard on single-duct units.

Line Fuse—An optional safety fuselocated in the line of power of theelectric heater to prevent power surgedamage to the electric heater.

Disconnect Switch—A optionalfactory-provided door interlockingdisconnect switch on the heater controlpanel disengages primary voltage tothe terminal.

UNIT CONTROLS SEQUENCE OFOPERATIONThe unit controller continuouslymonitors the zone temperature againstits setpoint and varies the primaryairflow as required to meet zonesetpoints. Airflow is limited by

minimum and maximum positionsetpoints. Upon a further call for heatafter the air valve is at minimum, anyhot water or electric heat associatedwith the unit is enabled.

DIRECT DIGITAL CONTROLS

DDC Actuator—Trane 3-wire,24-VAC, floating-point control actuatorwith linkage release button. Torque is35 in-lb minimum and is non-springreturn with a 90-second drive time.Travel is terminated by end stops atfully-opened and -closed positions. Anintegral magnetic clutch eliminatesmotor stall.Direct Digital Controller—Themicroprocessor based terminal unitcontroller provides accurate, pressure-independent control through the useof a proportional integral controlalgorithm and direct digital controltechnology. The controller, named theUnit Control Module (UCM), monitorszone temperature setpoints, zonetemperature and its rate of change,and valve airflow using a differentialpressure signal from the pressuretransducer. Additionally, the controllercan monitor either supply duct airtemperature or CO2 concentration viaappropriate sensors. The controller isprovided in an enclosure with 7/8"(22 mm) knockouts for remote controlwiring. A Trane DDC zone sensoris required.DDC Zone Sensor—The UCMcontroller senses zone temperaturethrough a sensing element located inthe zone sensor. In addition to thesensing element, zone sensor optionsmay include an externally-adjustablesetpoint, communications jack for usewith a portable edit device, and anoverride button to change theindividual controller from unoccupiedto occupied mode. The override buttonhas a cancel feature that will return thesystem to unoccupied. Wired zonesensors utilize a thermistor to vary thevoltage output in response to changesin the zone temperature. Wiring to theUCM controller must be 18- to 22-awg.twisted pair wiring. The setpointadjustment range is 50–88ºF (10–31°C).Depending upon the features availablein the model of sensor selected, thezone sensor may require from a 2-wireto a 5-wire connection. Wireless zonesensors report the same zoneinformation as wired zone sensors, butdo so using radio transmittertechnology. Therefore with wireless,

wiring from the zone sensor to the UCMis unnecessary.Digital Display Zone Sensor withLiquid Crystal Display (LCD)—The digital display zone sensor containsa sensing element, which sends a signalto the UCM. A Liquid Crystal Display(LCD) displays setpoint or spacetemperature. Sensor buttons allow theuser to adjust setpoints, and allow spacetemperature readings to be turned on oroff. The digital display zone sensor alsoincludes a communication jack for usewith a portable edit device, and anoverride button to change the UCM fromunoccupied to occupied. The overridebutton has a cancel feature, whichreturns the system to unoccupied mode.System Communications— TheController is designed to send andreceive data from a Tracer Summit™

or other Trane controllers. Current unitstatus conditions and setpoints may bemonitored and/or edited via this datacommunication feature. The networktype is a twisted wire pair shieldedserial communication.

ANALOG ELECTRONIC CONTROLS

Analog Actuator—A Trane 3- wire,24-VAC, floating-point control actuatorwith linkage release button. Torque is35 in-lb minimum and is non-springreturn with a 90-second drive time.Travel is terminated by end stops atfully-opened and -closed positions. Anintegral magnetic clutch eliminatesmotor stall.Analog Electronic Controller—Thecontroller consists of a circuit board thatoffers basic VAV unit operation andadditional override functions andoperates using 24 VAC power. Thecontroller uses a capacitive typepressure transducer to maintainconsistent air delivery regardless ofsystem pressure changes. The enclosurehas 7/8" (22 mm) knockouts for remotecontrol wiring. A Trane electronic zonesensor is required.Analog Electronic Thermostat—Thissingle-temperature, wall-mountedelectronic device utilizes a thermistor tovary the voltage output in response tochanges in the zone temperature.Connections to the VAV unit circuitboard are made using standard three-conductor thermostat wire. The setpointadjustment range is 63–85ºF (17–29°C).The sensor is available in two models.One model has a concealed, internally-adjustable setpoint. The other modelhas an externally-adjustable setpoint.

Page 30: Single-Duct Table of Contents · 2006-05-22 · Single-Duct VAV-PRC008-EN SD 1 Table of Contents Service Model Number Description SD 2 – 3 Selection Procedure SD 4 – 5 General

Single-Duct

VAV-PRC008-ENSD 30

PNEUMATIC CONTROLS

Normally Open Actuator —Pneumatic 3 to 8 psig (20 to 55 kPa)spring-range pneumatic actuator.

Normally-Closed Actuator—Pneumatic 8 to 13 psig (55 to 90 kPa)spring-range pneumatic actuator.

3011 Pneumatic Volume Regulator(PVR)—The regulator is a thermostatreset velocity controller, whichprovides consistent air delivery within5% of cataloged flow down to 18% orless of unit cataloged cfm, independentof changes in system static pressure.Factory-calibrated, field-adjustablesetpoints for minimum and maximumflows. Average total unit bleed rate,excluding thermostat, is 28.8 scim at20 psig (7.87 ml/min at 138 kPa) supply.

CONTROL OPTIONS

Transformer (VCCF, VCWF)—The50-VA transformer is factory-installedin an enclosure with 7/8" (22 mm)knockouts to provide 24 VAC forcontrols.

Disconnect Switch (VCCF, VCWF)—A toggle disconnect disengagesprimary power to the terminal.

Fuse (VCCF, VCWF)—Optional fuse isfactory-installed in the primary voltagehot leg.

HOT WATER VALVES

Two-Position Valve—The valve is afield-adaptable, 2-way or 3-wayconfiguration and ships with a cap tobe field-installed when configured as a2-way valve. All connections areNational Pipe Thread (NPT). The valvebody is forged brass with a stainlesssteel stem and spring. Upon demand,the motor strokes the valve. When theactuator drive stops, a spring returnsthe valve to its fail-safe position.

Flow Capacity – 1.17 CvOverall Diameter – ½" NPTClose-off Pressure – 30 psi (207 kPa)

Flow Capacity – 3.0 CvOverall Diameter – 3/4" NPTClose-off Pressure – 14.5 psi (100 kPa)

Flow Capacity – 6.4 CvOverall Diameter – 1" NPTClose-off Pressure – 9 psi (62 kPa)

Maximum Operating FluidTemperature – 203ºF (95ºC)

Maximum system pressure – 300 psi(2067 kPa)

Maximum static pressure – 300 psi(2067 kPa)

Electrical Rating – 7 VA at 24 VAC,6.5 Watts, 50/60 Hz

8 feet (2.44 m) of plenum rated wirelead is provided with each valve.

MechanicalSpecifications

Proportional Water Valve—Thevalve is a field-adaptable, 2-way or3-way configuration and ships with acap over the bottom port. Thisconfigures the valve for 2-wayoperation. For 3-way operation,remove the cap. The valve is designedwith an equal percentage plug. Theintended fluid is water or water andglycol (50% maximum glycol). Theactuator is a synchronous motor drive.The valve is driven to a predeterminedposition by the UCM controller using aproportional plus integral controlalgorithm. If power is removed, thevalve stays in its last position. Theactuator is rated for plenumapplications under UL 94-5V and UL873 standards.

Pressure and Temperature Ratings –The valve is designed and tested in fullcompliance with ANSI B16.15 Class250 pressure/temperature ratings,ANSI B16.104 Class IV control shutoffleakage, and ISA S75.11 flowcharacteristic standards.

Flow Capacity – 3.80 Cv , 6.60 Cv,0.70 Cv, 2.2 Cv

Overall Diameter – ½" NPT, ¾" NPT(7.30 Cv)

Maximum Allowable Pressure – 300psi (2068 kPa)

Maximum Operating FluidTemperature – 200ºF (93°C)

Maximum Close-off Pressure – 55 psi(379 kPa)

Electrical Rating – 6VA at 24 VAC.

10 feet (3.05 m) of plenum rated22-gage wire for connection.Terminations are #6 stabs.